KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20 …epoxy paint to ensure durability. Answer 4: Use...

11
Page 1 of 2 KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20-044-ITT Prince of Wales Public School New Elevator & Renovation ADDENDUM NO. 3 This addendum shall form an integral part of the bid documents for the above noted Tender and shall be read in conjunction therewith. This addendum shall, however, take precedence over all requirements as it pertains to the particular and specific items noted below. Part 1 Answers to Questions Question 1: New Roller shades are noted on the drawings; however, they are not in the specifications. Please confirm if they are required. Answer 1: See specification 12 24 00 “Window Shades” in Addendum No 1, prepared by AECOM Canada Architects Ltd, attached. Question 2: Coat and Hat Racks are in the specifications; however, the drawings show individual hooks. Please confirm which option to use. Answer 2: Use coat hooks as specified. Delete specification section 10 91 13 “Miscellaneous Specialties”. Question 3: Detail 13/A601 shows 3 custom cushions. Can an allowance be added as there are no specifications on the cushions? Answer 3: The Cash Allowance value in the Bidding System has been increased from $3,000.00 to $4,500.00 to allow for the cushions. Question 4: Detail 1/A206 shows a painted detail on the floor. Our paint contractor is suggesting an epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete & Garage, self-priming, 1-part Epoxy, Statin finish, or approved equal. Install as per manufacturers recommendations. Allow for 2 colours. Question 5: For LULA elevator, it appears there is an intermediate stop but I am not sure what you would call the level. The drawings show ground level, first floor, and second floor but there is an intermediate stop between the ground level and the first floor on the opposite side of the cab. Is there a basement level, ground level, 1st and 2nd floor? Could you clarify as the specification just shows the maximum number of stops and it doesn’t tell you the number of stops and the drawings do not identify the intermediate stop. Answer 5: There are 3 stops (floors) at the front door and 1 stop (exterior grade) at the rear door. Total 4 stops. See Elevator Section 1/A205. Question 6: If the tender closing is going to proceed without a site meeting, can you make a cash allowance for refinishing of millwork and hardwood floors? Answer 6: The cash allowance will not be increased to include the work described above. Review Room Finish Schedule and notes #1 thru #9 below the schedule.

Transcript of KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20 …epoxy paint to ensure durability. Answer 4: Use...

Page 1: KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20 …epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete & Garage,

Page 1 of 2

KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD

PUR20-044-ITT

Prince of Wales Public School New Elevator & Renovation

ADDENDUM NO. 3 This addendum shall form an integral part of the bid documents for the above noted Tender and shall be read in conjunction therewith. This addendum shall, however, take precedence over all requirements as it pertains to the particular and specific items noted below.

Part 1 – Answers to Questions Question 1: New Roller shades are noted on the drawings; however, they are not in the

specifications. Please confirm if they are required. Answer 1: See specification 12 24 00 “Window Shades” in Addendum No 1, prepared by AECOM

Canada Architects Ltd, attached. Question 2: Coat and Hat Racks are in the specifications; however, the drawings show individual

hooks. Please confirm which option to use. Answer 2: Use coat hooks as specified. Delete specification section 10 91 13 “Miscellaneous

Specialties”. Question 3: Detail 13/A601 shows 3 custom cushions. Can an allowance be added as there are no

specifications on the cushions? Answer 3: The Cash Allowance value in the Bidding System has been increased from $3,000.00 to

$4,500.00 to allow for the cushions. Question 4: Detail 1/A206 shows a painted detail on the floor. Our paint contractor is suggesting an

epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete &

Garage, self-priming, 1-part Epoxy, Statin finish, or approved equal. Install as per manufacturers recommendations. Allow for 2 colours.

Question 5: For LULA elevator, it appears there is an intermediate stop but I am not sure what you

would call the level. The drawings show ground level, first floor, and second floor but there is an intermediate stop between the ground level and the first floor on the opposite side of the cab. Is there a basement level, ground level, 1st and 2nd floor? Could you clarify as the specification just shows the maximum number of stops and it doesn’t tell you the number of stops and the drawings do not identify the intermediate stop.

Answer 5: There are 3 stops (floors) at the front door and 1 stop (exterior grade) at the rear door.

Total 4 stops. See Elevator Section 1/A205. Question 6: If the tender closing is going to proceed without a site meeting, can you make a cash

allowance for refinishing of millwork and hardwood floors? Answer 6: The cash allowance will not be increased to include the work described above. Review

Room Finish Schedule and notes #1 thru #9 below the schedule.

Page 2: KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20 …epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete & Garage,

Page 2 of 2

Question 7: DWG E301 Detail 1 Luminaire Schedule: Can we please provide equals to manufacturers listed here? As not all the manufacturers are the same.

Answer 7: Equivalent products will be subject to consultant review and approval. Question 8: DWG E204 Detail 3: Please provide manufacturer and part number for exit signs. Answer 8: T&B Emergilite ES series, ES-2-W-U-VR (for double face) or ES-1-W-U-VR (for single

face) or approved equals. Question 9: Detail 1/A202 RCP- In the classrooms can you clarify how the outside of C1 are being

terminated, as they are being dropped below the plaster ceilings. Answer 9: Install extruded aluminum trim around perimeter of suspended ceilings in the four

classrooms. 4” high Compasso Standard, colour ‘white’ by USG-CGC. Question 10: Please provide a floor tile for pricing. Answer 10: Floor tile to be equal to Olympia Spectra series. Allow for two colours. Question 11: The following elevator company is asking to be added to the tender specification:

[email protected] Joe Leone EDM-A B&L Elevator Services Inc. O - 705-325-0330 or 833-325-0330 C - 705-817-7022 www.bl-elevator.ca

Answer 11: See Addendum No 1, prepared by AECOM Canada Architects Ltd, attached. Question 12: Please clarify door and drawer front style and finish. Elevations show shaker style. Spec

2.2.4.8 notes doors to be veneer faced 19mm MDF. Typically, one-piece MDF Shaker doors have a paint finish, but photos of existing cabinets show wood finish with solid wood stile and rails.

Answer 12: Cabinet doors to be MDF, Shaker style, painted. Question 13: Typical elevation notes are to “sand and paint wood base.” Should this be “sand and

lacquer” as per existing? Answer 13: See Room Finish Schedule Notes: Note #4 for Classrooms, Note #7 for Resource Room

#110. See detail 16, 17, 18, 19 & 20/A601 for finishing existing trim in the Classrooms. See detail 21/A610 for new stained baseboard in Resource Room #110.

Part 2 – Additional Information

Add: Addendum No. 1, prepared by AECOM Canada Architects Ltd, (9 pages)

END OF ADDENDUM NO. 3

Page 3: KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20 …epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete & Garage,

AECOM Canada Architects Ltd.

300 Water Street 905 215 1400 tel

Whitby, ON, Canada L1N 9J2 905 668 0221 fax

www.aecom.com

AECOM Addendum No. 1

Project Name: Prince of Wales Public School - New Elevator & Renovation_______________________________________________________

Project No.: KPRDSB Tender No. PUR20-044-ITT (AECOM #60624140)_______________________________________________________

Date: March 24, 2020_______________________________________________________

The following information supplements and/or supersedes the bid documents issued on:

The addendum forms part of the contract documents and is to be read, interpreted and coordinated withall other parts. The cost of all contained herein is to be included in the contract sum. The followingrevisions supersede the information contained in the original drawings and specifications issued for theabove – named project to the extent referenced and shall become part thereof. Acknowledge receipt ofthis addendum by inserting its number and date on the Tender Form. Failure to do so may subject thebidder to disqualification.

General:

1-Operations and Maintenance Manuals: Contractor(s) shall include a dollar value in each progress drawfor manuals and as-built drawings. (General - $3,000) (Mechanical - $2,500) (Electrical - $2,500)

Drawings:

Drawing A201, “DEMOLITION FLOOR PLANS”Demolition note D10, turn salvaged coat hooks over to the school board.

Drawing A203 “NEW LAYOUT FLOOR PLANS”Add construction note #C26. Remove existing tackboard and make good existing plaster wall inHall #15A. Paint existing wall from Resource Room #110 window and over to new opening at Hall#110A (6.5m wide by 4.0m high). Install existing salvaged lockers. See image below.

Page 4: KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20 …epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete & Garage,

AECOM Canada Architects Ltd.

300 Water Street 905 215 1400 tel

Whitby, ON, Canada L1N 9J2 905 668 0221 fax

www.aecom.com

AECOM Addendum No. 1

Drawing A205, “ELEVATOR – PLANS and SECTIONS” 4/A205.Install wall type W5 at infill location next to Classroom No.11. Install baseboard on ClassroomNo11 side of wall similar to detail 21/A601. Paint wall infill in Classroom No.11.

Drawing A604, “ROOM ELEVATIONS” Detail 5/A604. “GUARDRAIL ELEVATION”.Tempered glazing to be 13mm thick. Install stainless steel U-channels to support glazing.

Drawing M-103, “NEW LAYOUT – HVAC”.Provide access doors for control valves of the wall fins installed behind the bookshelves inResource Room #110 (4 required). The access door shall be equivalent to ACUDOR universalFlush model # UF-5000, size 24 X 24. Provide all necessary hardware to install the access doors.Co-ordinate the exact locations of control valves on site.

Drawing S104, “CANOPY PLANS AND DETAILS”New drawing issued.

Drawings E102, E203, & E304.Drawings re-issued.

Specifications:

12 24 00 “Window Shades”.New specification section issued.

14 20 00 “LULA Elevator”, 1.2.1.2, Alternate Manufacturers.Include manufacturer(s) Cambridge Elevating and Niagara Belco.

End of AECOM Addendum No.1

Page 5: KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20 …epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete & Garage,

New Elevator & Renovation at Prince of Wales Public School Section 12 24 00Kawartha Pine Ridge District School Board WINDOW SHADESProject No. 60624140 PAGE 1

AECOM 2020-03-04

General

1.1 RELATED WORK SPECIFIED ELSEWHERE

.1 Steel stud framing.

.2 Acoustic Ceilings

1.2 WORK INCLUDED

.1 Supply and install manually operated roller shades at all windows, except as noted on drawings.Provide all components as needed for a complete and proper installation.

.2 Remove and dispose of all existing window coverings and hardware.

1.3 QUALITY ASSURANCE

.1 Use adequate numbers of skilled workers who are thoroughly trained and experienced in thenecessary crafts and who are completely familiar with the specific requirements and methodsneeded for proper performance of the work in this Section.

1.4 SUBMITTALS

.1 Submit list of proposed materials.

.2 Submit manufacturer=s specifications, product data, and other data needed to prove compliance

with the specified requirements.

.3 Shop drawings shall include sufficient detail to show fabrication, installation, anchorage, electricaland control wiring, and interface of work of this section with the work of adjacent trades. Indicatefield measurements on shop drawings.

.4 Manufacturer=s recommended installation procedure. Construct one complete light proof window

shade with attachments and accessories for approval by Owner which, when approved by theOwner will become the basis for accepting or rejecting actual installation procedures used on thework.

.5 Fabric to be flame retardant. Provide proof of compliance with CAN/ULC S109, Flame Tests ofFlame-Resistant Fabrics and Films, small scale vertical burn requirements test.

.6 Submit fabric samples for colour selection by the Owner.

.7 Provide printed operation and maintenance instructions to Owner.

1.5 WARRANTY

.1 Provide a warranty for an extended period of three (3) years from date of completion againstmechanical and fabric failure (including fabric fading) under normal conditions.

Products

2.1 WINDOW SHADES

.1 Manual shades shall be roller blind system with smooth operation chain and sprocket roller asmanufactured by Shade-O-Matic Products Ltd., or pre tender approved equivalent.

.2 Provide system with easy lift (chain operated) action with infinite positioning. Left or right handoperation to be determined on site.

.3 Provide fully factory assembled shade unit consisting of two end brackets, shade tube, fascia(where specified), hem bar, drive chain and specified fabric.

.1 Mounting type: Wall mounted above frame opening, or on block opening inside butnever on window frame.

.2 Removal must not require the disassembly of the shade units.

Page 6: KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20 …epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete & Garage,

New Elevator & Renovation at Prince of Wales Public School Section 12 24 00Kawartha Pine Ridge District School Board WINDOW SHADESProject No. 60624140 PAGE 2

AECOM 2020-03-04

.4 End Brackets

.1 70 x 83mm end bracket shall be made of 16 gauge enameled galvanized steel capable ofbeing mounted in any position.

.2 Clutch and bracket shall have multi-channel chain control and guide insert.

.3 The idle-end bracket shall have a means of leveling the shade after installation, the screwshall provide infinite leveling degrees.

.4 Bracket colour shall coordinate with fabric colour.

.5 Shade Tube

.1 38mm extruded anodized aluminum shade tube shall be 1.52mm thick with three internalcontinuous fins 4.82mm high, for strength and drive capabilities when attached to thenylon sprocket.

.2 The fins shall be spaced 120 degrees apart.

.3 The tube shall incorporate an integral channel for affixing the shade band to the tube viaa spine.

.6 Fascia (Optional as noted on Drawings)

.1 Extruded anodized aluminum fascia shall be 1.7mm thick, squared design, to coverunderside of assembly.

.2 Finish shall be anodized aluminum or painted baked enamel.

.7 Drive Assembly

.1 Shall be factory set for size and travel of shades.

.2 Capable of being field adjusted from the exterior of the shade unit without having todisassemble the hardware.

.3 Provide with built-in shock absorber system to prevent chain breakage, under normalusage conditions.

.8 Drive Chain

.1 No. 10 stainless steel bead chain formed in a continuous loop. Chain shall have a 90#test strength.

.9 Exterior Hembar

.1 Extruded aluminum, clear anodized, with plastic end finials. Hembar to be fully enclosedin hem and non removable.

2.2 OPAQUE FABRIC (CLASSROOMS)

.1 Sun block / duplex room darkening 12 oz fibreglass

.2 Seams, if required, shall be equally spaced vertically to form material in equal widths. Location asper drawings.

.3 Fabric shall hang flat, without buckling or distortion. Edge, when trimmed, shall hang straight,without raveling. An unguided shade cloth shall roll true and straight, without shifting sidewaysmore than 3mm in either direction due to warp distortion or weave design.

.4 Fabric shall be woven vinyl coated polyester, dimensionally stable and flame retardant, inaccordance with CAN/ULC S-109 small scale vertical burn test.

.5 Owner to choose colour when shop drawings are submitted. Colours will be selected by theOwner from the manufacturers standard collection. A minimum of 9 colour choices must beoffered.

Page 7: KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20 …epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete & Garage,

New Elevator & Renovation at Prince of Wales Public School Section 12 24 00Kawartha Pine Ridge District School Board WINDOW SHADESProject No. 60624140 PAGE 3

AECOM 2020-03-04

2.3 SUN SHADING FABRIC (OFFICES AND STAFF ROOMS)

.1 5% open weave flame retardant, 25% polyester / 75% vinyl on polyester.

.2 Seams, if required, shall be equally spaced vertically to form material in equal widths. Location asper drawings.

.3 Fabric shall hang flat, without buckling or distortion. Edge, when trimmed, shall hang straight,without raveling. An unguided shade cloth shall roll true and straight, without shifting sidewaysmore than 3mm in either direction due to warp distortion or weave design.

.4 Fabric shall be woven vinyl coated polyester, dimensionally stable and flame retardant, inaccordance with CAN/ULC S-109 small scale vertical burn test.

.5 Owner to choose colour when shop drawings are submitted. Colours will be selected by theOwner from the manufacturers standard collection. A minimum of 9 colour choices must beoffered. (Colour to match Jackson shear weave Pebblestone)

2.4 BLACK OUT SHADES (DRAMA ROOMS AND THEATERS OR AS NOTED)

.1 Light proof shades to be 100% opaque blackout flame retardant.

.2 Seams, if required, shall be equally spaced vertically to form material in equal widths. Location asper drawings.

.3 Fabric shall hang flat, without buckling or distortion. Edge, when trimmed, shall hang straight,without raveling. An unguided shade cloth shall roll true and straight, without shifting sidewaysmore than 3mm in either direction due to warp distortion or weave design.

.4 Fabric shall be woven vinyl coated polyester, dimensionally stable and flame retardant, inaccordance with CAN/ULC S-109 small scale vertical burn test.

.5 Owner to choose colour when shop drawings are submitted. 2 Colours will be selected by theOwner from the manufacturer=s standard collection. A minimum of 9 colour choices must be

offered.

Execution

3.1 EXISTING CONDITIONS

.1 Examine the areas and conditions under which the work of this section will be performed. Correctconditions detrimental to timely and proper completion of the work.

.2 Remove and dispose of all existing window coverings and hardware.

3.2 INSTALLATION

.1 Co-ordinate as required with the Owner as to hours of work.

.2 Install the work of this section in strict accordance with approved Shop Drawings, pertinentrequirements of Government Agencies having jurisdiction, and the manufacturer=s recommended

installation procedures as approved by the Owner, anchoring all components firmly into positionfor long life.

.3 Install the work plumb, level and in proper operating condition.

.4 Upon completion of the installation, put each operating component through at least five completecycles, adjust as required to achieve optimum operation.

.5 Touch up scratches and blemishes to any damaged existing finishes.

END OF SECTION

Page 8: KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20 …epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete & Garage,

HSS102x76x4.8

HSS102x76x4.8

HS

S8

9x8

9x4.8

HS

S8

9x8

9x4.8

HS

S8

9x8

9x4.8

4

S104

2

S104

3

S104

38 DP x 0.91 THK

PREFINISHED ROOFING

950 950 150

19

00

30

51

50

HSS102x102x6.4

HSS102x102x6.4

Mr = 15 kN MIN.

Mr = 15 kN MIN.

HS

S8

9x8

9x4.8

HS

S8

9x8

9x4.8

4

S104

5

S104

Mr = 15 kN MIN.

HSS102x76x4.8

5

S104

20

02

20

01

20

0

MIN

.

90

0

950 150950

38 DP x 0.91 THK

GALVANIZED STEEL DECK

HSS102x76x4.8

HSS89x89x4.8

HSS102x102x6.4

EXIST. MULTI-WYTHE

BRICK WALL

150 GRANULAR 'A'

COMPACTED TO 98%

S.P.M.D.D., OR AS

REQUIRED BY

GEOTECHNICAL ENGINEER

PROVIDE 25 THK GROUT BASE

(TYP.)

300 DIA. 25 MPa CONCRETE

PIER IN SONOTUBE

POUR 300x300 BOX ABOVE

GRADE

6

S104TYP.

20

02

20

09

00

4501900

12

00

MIN

.

EXIST. MULTI-WYTHE

BRICK WALL

38 DP x 0.91 THK

PREFINISHED ROOFING

HSS102x76x4.8

PROVIDE CLOSURE TRIM

AT PERIMETER PER

ARCHITECTURAL

DRAWINGS

HSS102x102x6.4

300 DIA. 25 MPa CONCRETE

PIER IN SONOTUBE

150 GRANULAR 'A'

COMPACTED TO 98%

S.P.M.D.D., OR AS

REQUIRED BY

GEOTECHNICAL ENGINEER

PROVIDE 25 THK GROUT BASE

(TYP.)

POUR 300x300 BOX ABOVE

GRADE

20320335 35

75

75

19Ø THREADED ROD C/W

HILTI HY-70 EPOXY AND

SLEEVE, MIN EMBED = 330

(TYP. FOR 2)

PL12x475X150

HSS102x76x4.8

6

70

70

30

30

70 70 3030

16Ø ANCHOR RODS, MIN.

EMBED = 250

PL9.5x200x200

HSS102x102x6.4

6

14026635 35

65

65

19Ø THREADED ROD C/W

HILTI HY-70 EPOXY AND

SLEEVE, MIN EMBED = 330

(TYP. FOR 2)

PL12x475X150

HSS102x76x4.8

6

Printed on ___% Post-ConsumerRecycled Content Paper

KEY PLAN

REGISTRATION

CLIENT

Kawartha Pine Ridge

District School Board1994 Fisher Drive, Peterborough, Ontario

705.742.9773 tel 705.742.7801 fax

www.kprdsb.ca

PROJECT

New Elevator & Renovation

Prince of Wales

Public School1211 Monaghan Road. S. Peterborough, Ontario

PROJECT NUMBER

60624140

CONSULTANT

AECOM Canada Ltd.

300 Water Street

Whitby, Ontario, Canada L1N 9J2

905.215.1400 tel 905.668.0221 faxwww.aecom.com

NORTH

CO

NS

TRU

CTIO

NN

OR

TH

1

3

0.50

10 2

32

4 5 10'

4m

BARSCALE 1=50

I/R DATE DESCRIPTION

ISSUE/REVISION

1 2020-03-24 AECOM ADDENDUM #1

SHEET TITLE

CANOPY PLANS AND DETAILS

SHEET NUMBER

S10420

20

-03

-24

__

__

__

___

__

___

_W

AL

ES

EL

EV

AT

OR

SH

AF

T\C

AD

\60

624

14

0-S

.DW

G

Scale: 1:20

CANOPY PLAN1S104

Scale: 1:20

CANOPY SECTION2S104 Scale: 1:20

CANOPY ELEVATION3S104

Scale: 1:5

DETAIL4S104

Scale: 1:5

DETAIL6S104

CANOPY DESIGN LOADS

DEAD LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.10 kPa

SNOW LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.59 kPa

WIND UPLIFT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.26 kPa

1. REFER TO DRAWING S101 FOR STRUCTURAL NOTES.

2. VERIFY EXISTING WALL CONSTRUCTION PRIOR TO INSTALLING

ANCHORS. NOTIFY ENGINEER IF ANY DISCREPANCY EXISTS

BETWEEN DRAWINGS AND EXISTING CONSTRUCTION.

3. ALL EXTERIOR STEEL TO BE HOT DIP GALVANIZED TO CSA G164.

4. FIX DECK TO HSS MEMBERS WITH PUDDLE WELDS AT 300 O/C.

5. PROVIDE MOMENT CONNECTIONS WHERE INDICATED.

6. PROVIDE SHOP DRAWINGS FOR CONSULTANT REVIEW PRIOR TO

FABRICATION. SHOP DRAWINGS TO BE STAMPED BY ENGINEER

CERTIFIED IN THE PROVINCE OF ONTARIO.

7. DRAWING TO BE READ IN CONJUNCTION WITH ARCHITECTURAL

DRAWINGS. NOTIFY CONSULTANT IF ANY DISCREPANCY EXISTS.

NOTES:

Scale: 1:5

DETAIL5S104

Page 9: KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20 …epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete & Garage,

B06H

HALL

B12

ELECT.

PANEL 'DP1'

'PANEL #13'

FIRE CONTROL

PANEL (EXISTING

PANEL TO BE

REMOVED)

Printed on ___% Post-Consumer

Recycled Content Paper

This draw

ing has been prepared for the use of A

EC

OM

's client and m

ay not be used, reproduced or relied upon by third parties, except as agreed by A

EC

OM

and its client, as required by law

or for use by governm

ental review

ing agencies. A

EC

OM

accepts no responsibility, and denies any liability w

hatsoever, to any party that m

odifies this draw

ing w

ithout A

EC

OM

's express w

ritten consent. D

o not scale this docum

ent. A

ll m

easurem

ents m

ust be obtained from

stated dim

ensions.

KEY PLAN

REGISTRATION

CLIENT

Kawartha Pine Ridge

District School Board

1994 Fisher Drive, Peterborough, Ontario

705.742.9773 tel 705.742.7801 fax

www.kprdsb.ca

PROJECT

New Elevator & Renovation

Prince of Wales

Public School

1211 Monaghan Road. S. Peterborough, Ontario

PROJECT NUMBER

60624140

AR

CH

D

2

4" x 3

6"

CONSULTANT

AECOM Canada Ltd.

300 Water Street

Whitby, Ontario, Canada L1N 9J2

905.215.1400 tel 905.668.0221 fax

www.aecom.com

N

O

R

T

H

C

O

N

S

T

R

U

C

T

I

O

N

N

O

R

T

H

1

3

0.50

10 2

32

4 5 10

54

15

6 7 8m

20 25'

BARSCALE 1=100

I/R DATE DESCRIPTION

ISSUE/REVISION

1 MAR/04/2020 TENDER AND PERMIT

2 MAR/23/2020 AECOM ADDENDUM NO1

SHEET TITLE

ELECTRICAL

SINGLE LINE DIAGRAM

AND NEW PANEL DETAILS

SHEET NUMBER

E102

La

st sa

ve

d b

y: S

HA

RO

N.L

IN

(2

02

0-0

3-2

4) L

ast P

lo

tte

d: 2

02

0-0

3-2

4P

ro

je

ct M

an

ag

em

en

t In

itia

ls:

De

sig

ne

r:

Ch

ecke

d:

Ap

pro

ve

d:

__

__

__

__

__

__

__

_

File

na

me

: \\C

AW

BY

1F

P0

01

\D

AT

A\P

RO

JE

CT

S\6

06

24

14

0\9

00

-C

AD

_G

IS

\9

10

-C

AD

\2

0-S

HE

ET

S\E

\6

06

24

14

0-S

HT

-E

10

1-E

10

3.D

WG

1200A-3P FRAME C/W

1200A TRIP UNIT

SUPPLY AUTHORITY

METERING CABINET

800A-3P

800A TRIP

RM. B07B

208V, 3PH, 4W, 1200A, EX. SWITCHBOARD 'AA'

................

N.T.S

EX. SINGLE LINE DIAGRAM1

E102

RM. B12

208V, 3PH, 4W, 800A, EX. DISTRIBUTION PANEL 'DP-1'

NEW

PANEL

'13A'

100A-3P

RM. B12

Scale: 1:50

ELECT. RM. B12 LAYOUT2

E102

EX. LOAD

EX.

BREAKERS

N.T.S

NEW PANEL SCHEDULE - '13A'3

E102

PANEL

'13A'

ACCESS CONTROL PANEL

4#3 AWG + GND IN 41 mmC

1. PROVIDE 53mm CONDUIT STUBBED AND CAPPED IN CEILING SPACE FOR FUTURE LOAD.

CONFIRM AND COORDINATE FINAL LOCATION ON SITE WITH TRENT AND CLIENT.

NOTES:

EX

FROM UTILITY

EX

EX

NOT ALL BREAKERS ARE SHOWN.

NEW CIRCUIT BREAKER TYPE AND KAIC RATING TO MATCH EXISTING CIRCUIT BREAKER.

NOTES:

2

2

1.

MASTER CONTROL PANEL

FOR VIDEO INTERCOM

SYSTEM

2

2

2

2

2

AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
FACP
AutoCAD SHX Text
M
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C
Page 10: KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20 …epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete & Garage,

T

110

RESOURCE

ROOM

110B

W.R.

110A

HALL

110C

EXISTING

SHAFT

AC-1

ERV-1

AC-5

CCT: 13A-13/15

CCT: 13A-1/3/5

CCT: 13A-13/15

AC-4

CCT: 13A-13/15

AC-3

CCT: 13A-13/15

AC-2

CCT: 13A-13/15

EDH-1

CCT: 13A-7/9/11

EX

EX

RL

RL

EX. 'PANEL

#2 - 38'

EX. 'PANEL

#2 - 38'

EX. 'PANEL

#2 - 38'

EX. 'PANEL

#2 - 36'

EX. 'PANEL

#2 - 36'

EX. 'PANEL

#2 - 39'

EX. 'PANEL

#2 - 42'

EX. 'PANEL

#2 - 40'

EX. 'PANEL

#2 - 41'

EX. 'PANEL

#2 - 37'

EX. 'PANEL

#2 - 37'

EX. 'PANEL

#2 - 37'

EX. 'PANEL

#2 - 39'

IWB

RL

EX. 'PANEL

#2 - 37'

T T T T T

RL RL RL RL

IWB

RL

26

CLASSROOM

25

CLASSROOM

23

STAFF

ROOM

21

CLASSROOM

22

CLASSROOM

30H CORRIDOR

23A

HALL

IWB IWB IWB

RL RL

RL

RL

RL

RL

TR TR

EX. 'PANEL

#1 - 22'

EX. 'PANEL

#1 - 22'

EX. 'PANEL

#1 - 22'

EX. 'PANEL

#1 - 22'

EX. 'PANEL

#1 - 22'

EX. 'PANEL

#1 - 22'

EX. 'PANEL

#1 - 20'

EX. 'PANEL

#1 - 20'

EX. 'PANEL

#1 - 20'

EX. 'PANEL

#1 - 20'

EX. 'PANEL

#1 - 20'

EX. 'PANEL

#1 - 20'

EX. 'PANEL

#1 - 22'

EX. 'PANEL

#1 - 11'

EX. 'PANEL

#1 - 11'

EX. 'PANEL

#1 - 22'

EX. 'PANEL

#1 - 22'

TR TR

EX. 'PANEL

#1 - 12'

EX. 'PANEL

#1 - 12'

TR TR

EX. 'PANEL

#1 - 18'

EX. 'PANEL

#1 - 18'

TR TR

EX. 'PANEL

#1 - 17'

EX. 'PANEL

#1 - 17'

EX. 'PANEL

#1 - 20'

EX. 'PANEL

#1 - 20'

EX. 'PANEL

#1 - 20'

T

TGFI

5-20R

CCT: 13A-8

GFI

5-20R

CCT: 13A-10

WP,GFI

5-15R

CCT: 13A-20

B05

CUST.

B06

HALL

B07

BOILER ROOM

B07B

ELECT. RM.

B07A

B01H CORRIDOR

B06H HALL

B12

ELECT.

STORAGE

B06C

HALL

B06D

STORAGE

B06B

MACHINE

ROOM

B06A

ELEV.

EF-1

CCT: 13A-12

FFH-1

CCT: 13A-14

CCT: 13A-16

FOR

SECURITY

CCT: 13A-18

CCT: 13A-18CCT:

13A-18

F

F

ACCU-1ACCU-1

CCT: 13A-2/4

WP,GFI

5-20R

CCT: 13A-6

Printed on ___% Post-Consumer

Recycled Content Paper

This draw

ing has been prepared for the use of A

EC

OM

's client and m

ay not be used, reproduced or relied upon by third parties, except as agreed by A

EC

OM

and its client, as required by law

or for use by governm

ental review

ing agencies. A

EC

OM

accepts no responsibility, and denies any liability w

hatsoever, to any party that m

odifies this draw

ing w

ithout A

EC

OM

's express w

ritten consent. D

o not scale this docum

ent. A

ll m

easurem

ents m

ust be obtained from

stated dim

ensions.

KEY PLAN

REGISTRATION

CLIENT

Kawartha Pine Ridge

District School Board

1994 Fisher Drive, Peterborough, Ontario

705.742.9773 tel 705.742.7801 fax

www.kprdsb.ca

PROJECT

New Elevator & Renovation

Prince of Wales

Public School

1211 Monaghan Road. S. Peterborough, Ontario

PROJECT NUMBER

60624140

AR

CH

D

2

4" x 3

6"

CONSULTANT

AECOM Canada Ltd.

300 Water Street

Whitby, Ontario, Canada L1N 9J2

905.215.1400 tel 905.668.0221 fax

www.aecom.com

I/R DATE DESCRIPTION

ISSUE/REVISION

1 MAR/04/2020 TENDER AND PERMIT

2 MAR/23/2020 AECOM ADDENDUM NO1

SHEET TITLE

ELECTRICAL

POWER AND SYSTEMS

NEW PLAN

SHEET NUMBER

E203

La

st sa

ve

d b

y: S

HA

RO

N.L

IN

(2

02

0-0

3-2

3) L

ast P

lo

tte

d: 2

02

0-0

3-2

4P

ro

je

ct M

an

ag

em

en

t In

itia

ls:

De

sig

ne

r:

Ch

ecke

d:

Ap

pro

ve

d:

__

__

__

__

__

__

__

_

File

na

me

: \\C

AW

BY

1F

P0

01

\D

AT

A\P

RO

JE

CT

S\6

06

24

14

0\9

00

-C

AD

_G

IS

\9

10

-C

AD

\2

0-S

HE

ET

S\E

\6

06

24

14

0-S

HT

-E

20

3-P

OW

ER

&

S

YS

TE

MS

- N

EW

.D

WG

N

O

R

T

H

C

O

N

S

T

R

U

C

T

I

O

N

N

O

R

T

H

Scale: 1:100

FIRST FLOOR PLAN - POWER & SYSTEMS NEW LAYOUT2

E203

1

3

0.50

10 2

32

4 5 10

54

15

6 7 8m

20 25'

BARSCALE 1=100

Scale: 1:100

SECOND FLOOR PLAN - POWER & SYSTEMS NEW LAYOUT1

E203

Scale: 1:100

GROUND FLOOR PLAN - POWER & SYSTEMS NEW LAYOUT3

E203

3

4

5

5

3

10

8

7

9

6

5

17

1 2

18

1 2

1 2 1 2

5

5

5

19

19 19

Scale: 1:200

ROOF PLAN - POWER & SYSTEMS NEW LAYOUT4

E203

MODULAR SURFACE MOUNTED CONTROL PANEL TO BE INTERSPEC SYSTEMS AND CLASSMATE

CLASSROOM CONTROL PANEL TYPE. REFER TO 1/E302 FOR FURTHER INFORMATION ON INSTALLATION

LAYOUT.

MODULAR CONTROL PANEL RECEPTACLE TO BE CIRCUITED WITH THE CONVENIENCE RECEPTACLES

(NON-IWB CIRCUIT).

SUPPLY AND INSTALL HEAT DETECTOR AND 5-20R GFI RECEPTACLE IN PIT OF ELEVATOR. GFI

RECEPTACLE SHALL BE MOUNTED 100mm (4") BELOW ELEVATOR GROUND FLOOR LANDING OR AS

OTHERWISE DIRECTED BY ELEVATOR INSTALLER. TIE HEAT DETECTOR AND SMOKE DETECTOR AT THE

TOP OF SHAFT INTO NEW FIRE ALARM PANEL.

SMOKE DETECTOR MOUNTED AT THE TOP OF THE ELEVATOR SHAFT. TIE INTO ELEVATOR RECALL AS

PER CSA B44.

FOR ELEVATOR RECALL AS PER CSA B44.

SUPPLY AND INSTALL SUITABLE (3) SLEEVES POSITIONED AS PER ELEVATOR MANUFACTURER

REQUIREMENTS. SLEEVES SHALL BE AT LEAST MIN. 5". THEY SHALL BE PROVIDED BELOW THE

MACHINE ROOM FLOOR FOR ELECTRICAL WIRING. COORDINATE WITH ELEVATOR MANUFACTURER FOR

FINAL SLEEVE SIZING.

SUPPLY AND INSTALL A 1P-30A SN 125V EEMAC 1 LOCKABLE SAFETY DISCONNECT SWITCH WITH ONE

(1) 15A PLUG FUSE. TIE INTO NEW CIRCUIT NOTED. FINAL LOCATION TO BE COORDINATED ON SITE.

SUPPLY AND INSTALL LOCKABLE 208V/30A FUSED DISCONNECT SWITCH FED FROM PANEL 13A-19/21/23

WITH AUXILIARY CONTACT TO ELEVATOR CONTROL PANEL. COORDINATE WITH SUPPLIER FOR TYPE OF

FUSE. POSITION DISCONNECT AS PER ELEVATOR. MANUFACTURER RECOMMENDATIONS. FINAL

LOCATION TO BE COORDINATED ON SITE.

PROVIDE NEW 20A GFI RECEPTACLE IN ELEVATOR MACHINE ROOM COMPLETE WITH NEW DEDICATED

FEED FROM CIRCUIT NOTED.

PROVIDE NEW CAT 6 PHONE LINE FROM ELEVATOR TO MACHINE ROOM, AND ELEVATOR CONTROL

PANEL , MACHINE ROOM TO MAIN PHONE PANEL IN ELECTRICAL ROOM. COORDINATE WITH ELEVATOR

MANUFACTURER AND OWNER'S APPROVED SECURITY MONITORING COMPANY. PROVIDE 21mm

CONDUIT FROM ELECTRICAL ROOM TO MACHINE ROOM WITH PULL STRING.

PROVIDE SMOKE DETECTORS IN EACH ELEVATOR LOBBY/LANDING OUTSIDE ELEVATOR PER ULC 524,

OBC AND CSA B44.

PROVIDE NORMALLY CLOSED CONTACTS REPRESENTING SMOKE DETECTORS FOR PIT, LANDINGS,

MACHINE ROOM, AND WIRE IT AS REQUIRED AS PER CSA B44 AND ULC 524.

THE SMOKE DETECTOR LOCATED IN THE ELEVATOR MACHINE ROOM SHALL BE WIRED TO ACTIVATE

SAME NORMALLY CLOSED CONTACT AS THE SMOKE DETECTOR AT THE DESIGNATED LANDINGS.

COORDINATE ALL REQUIREMENTS WITH ELEVATOR CONTRACTOR.

CONTRACTOR IS RESPONSIBLE FOR CONFIRMING ALL ELEVATOR POWER AND FIRE ALARM

REQUIREMENTS WITH ELEVATOR SHOP DRAWINGS AND ELEVATOR MANUFACTURER.

REFER TO FIRE ALARM SCOPE OF WORK FOR ADDITIONAL REQUIREMENTS.

PROVIDE POWER AND DATA OUTLETS AT HIGH LEVEL FOR INTERACTIVE WHITEBOARD. COORDINATE

WITH ARCHITECTURAL ELEVATIONS AND GENERAL CONTRACTOR TO SUIT LOCATION OF INTERACTIVE

WHITEBOARD. REFER TO 2/E302 FOR DETAIL.

CONTRACTOR TO TIE IN CAMERA CALL-IN BUTTON AND ELECTRIC STRIKE TO EXISTING ACCESS

CONTROL PANEL. PROVIDE ROUGH-INS AND CONDUIT FROM SECURITY PANEL TO DOOR FOR

SECURITY CONTROL.

DEDICATED 20A CIRCUIT FOR PHOTOCOPIER AND LAPTOP CHARGING STATIONS. RECEPTACLE SHALL

BE CSA 5-20R TYPE.

ALL DEVICES ARE NEW EXCEPT WHERE NOTED.

CONTRACTOR TO AVOID ANY SURFACE MOUNT ON TO EXTERIOR WALL OF THE BUILDING.

INSTALL RECEPTACLES IN CLASSROOMS ON THE CHAIR RAIL RUNNING ABOVE THE WALL FINS.

TIE IN THE RECEPTACLE TO THE NEAREST EXISTING RECEPTACLE CIRCUIT IN THE SAME ROOM.

REFER TO ELECTRICAL GENERAL NOTE 12 ON DRAWING E100 FOR WIRING RUNS.

EXISTING DEVICE RELOCATED TO NEW LOCATION. EXTEND/CUT BACK WIRING AS REQUIRED.

REFER TO DRAWING 2/E301 FOR DISCONNECT SWITCH REQUIREMENT.

ALL THE RECEPTACLE AND DATA OUTLET TO BE FED FROM CEILING SPACE FOR FIRST FLOOR AND

GROUND FLOOR, AND ATTIC SPACE FOR THIRD FLOOR.

EXISTING 1-DOOR VIDEO INTERCOM SYSTEM TO BE REPLACED. CONTRACTOR SHALL COORDINATE

REMOVALS WITH TRENT SECURITY INCLUDING BUT NOT LIMITED TO WIRING, ACCESSORIES, ETC.

CONDUIT MAY BE REUSED IF IN GOOD CONDITION. PROVIDE AND INSTALL NEW 2-DOOR VIDEO

INTERCOM SYSTEM TO MATCH AIPHONE JO SERIES COMPLETE WITH DOOR ADAPTER, ELECTRIC

STRIKE (BY OTHERS), MASTER STATION, POWER SUPPLIES AND TWO DESKTOP

MONITOR/WORKSTATIONS. WORK TO BE DONE BY TRENT SECURITY (705.748.2001) UNDER DIV. 26.

CONFIRM DOOR LOCATIONS WITH ARCHITECTURAL DRAWINGS. PROPOSED LOCATIONS AT MAIN

ENTRANCE LOBBY AND HALL B06C. GENERAL CONTRACTOR TO CARRY SERVICES OF TRENT SECURITY

AND ALL ASSOCIATED COSTS TO PROVIDE THESE SERVICES INCLUDING BUT NOT LIMITED TO WIRING,

CONDUIT, ACCESSORIES TO FACILITATE A COMPLETE VIDEO INTERCOM SYSTEM INSTALLATION.

CONFIRM FINAL LOCATION OF EQUIPMENT ON SITE WITH OWNER AND TRENT.

NOTES:

1

2

3

4

5

6

7

8

9

10

11.

12.

13.

14.

15.

16.

17

18

17 17 17

20.

21

21

22

23

22(TYP.)

23

19

24.

17

25

25(TYP.)

25(TYP.)

26.

27.

25

25(TYP.)

22

2

2

2

2

22

22

2

2

28.

2

2

AutoCAD SHX Text
CP
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
U
AutoCAD SHX Text
U
AutoCAD SHX Text
U
AutoCAD SHX Text
U
AutoCAD SHX Text
U
AutoCAD SHX Text
WAP
AutoCAD SHX Text
WAP
AutoCAD SHX Text
U
AutoCAD SHX Text
CP
AutoCAD SHX Text
CP
AutoCAD SHX Text
CP
AutoCAD SHX Text
CP
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
WAP
AutoCAD SHX Text
WAP
AutoCAD SHX Text
WAP
AutoCAD SHX Text
WAP
AutoCAD SHX Text
WAP
AutoCAD SHX Text
WAP
AutoCAD SHX Text
F
AutoCAD SHX Text
CB
AutoCAD SHX Text
PB
AutoCAD SHX Text
PB
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
B
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
F
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C
Page 11: KAWARTHA PINE RIDGE DISTRICT SCHOOL BOARD PUR20 …epoxy paint to ensure durability. Answer 4: Use epoxy paint for field and border colour. Product BEHR Premium, Concrete & Garage,

I/R DATE DESCRIPTION

ISSUE/REVISION

1 MAR/04/2020 TENDER AND PERMIT

2 MAR/23/2020 AECOM ADDENDUM NO1

SHEET TITLE

ELECTRICAL

SPECIFICATIONS

1 OF 2

SHEET NUMBER

E304

La

st sa

ve

d b

y: S

HA

RO

N.L

IN

(2

02

0-0

3-2

4) L

ast P

lo

tte

d: 2

02

0-0

3-2

4

Pro

je

ct M

an

ag

em

en

t In

itia

ls:

De

sig

ne

r:

Ch

ecke

d:

Ap

pro

ve

d:

__

__

__

__

__

__

__

_

File

na

me

: \\C

AW

BY

1F

P0

01

\D

AT

A\P

RO

JE

CT

S\6

06

24

14

0\9

00

-C

AD

_G

IS

\9

10

-C

AD

\2

0-S

HE

ET

S\E

\6

06

24

14

0-S

HT

-E

30

4-E

30

5.D

WG

ELECTRICAL SPECIFICATIONS

1. PART A - GENERAL

1.1. CODES AND STANDARDS

1.1.1. COMPLETE THE INSTALLATION OF THE WORK IN ACCORDANCE WITH

THE LATEST EDITIONS OF THE ONTARIO BUILDING CODE, ONTARIO ELECTRICAL

SAFETY CODE (O.E.S.C.), U.L.C., C.S.A., I.E.E.E., N.E.M.A., N.F.P.A., O.H.S.A. AND

OTHER CODES AS REQUIRED. COMPLY WITH ELECTRICAL AND BUILDING CODE

BULLETINS IN FORCE AT TIME OF BID SUBMISSION. WHILE NOT IDENTIFIED AND

SPECIFIED BY NUMBER IN THIS DIVISION, THEY ARE TO BE CONSIDERED AS

FORMING PART OF RELATED STANDARDS. ALL ELECTRICAL WORK SHALL

COMPLY WITH OWNER'S REQUIREMENTS AND BASE BUILDING STANDARDS.

1.2. EXISTING CONDITIONS

1.2.1. VISIT THE SITE AND EXAMINE THE EXISTING CONDITIONS AFFECTING

THE WORK OF THIS DIVISION. NO CLAIM FOR EXTRA PAYMENT SHALL BE MADE

FOR EXTRA WORK MADE NECESSARY BY CIRCUMSTANCES ENCOUNTERED DUE

TO CONDITIONS WHICH WERE VISIBLE UPON, OR REASONABLY INFERABLE

FROM AN EXAMINATION OF THE SITE PRIOR TO SUBMISSION OF THE CONTRACT

PRICE.

1.3. DEFINITIONS

1.3.1. WHEREVER THE WORDS "PROVIDE" OR "SUPPLY AND INSTALL" ARE

USED, IT SHALL BE UNDERSTOOD TO MEAN "SUPPLY AND INSTALL, INCLUSIVE

OF ALL LABOUR, MATERIALS, INSTALLATION, TESTING, AND CONNECTIONS"

FOR THE ITEM(S) TO WHICH IT REFERENCES.

1.3.2. WHEREVER THE WORDS "EQUAL", "APPROVED", OR "APPROVED

EQUAL" ARE USED, IT SHALL BE UNDERSTOOD TO MEAN "EQUAL", "APPROVED",

OR "APPROVED EQUAL" IN THE OPINION OF THE CONSULTANT ONLY.

1.4. SCOPE OF WORK

1.4.1. REFER TO SECTION 01 11 00 - SUMMARY OF WORK FOR OVERALL

PROJECT REQUIREMENTS.

1.4.2. PROVIDE ALL MATERIALS, EQUIPMENT AND LABOUR FOR A

COMPLETE OPERATIONAL INSTALLATION AS DESIGNATED IN THIS

SPECIFICATION AND AS INDICATED ON THE DRAWINGS EXCEPT WHERE

OTHERWISE NOTED.

1.4.3. THE SCOPE OF WORK FOR THIS DIVISION INCLUDES, BUT IS NOT

LIMITED TO, SUPPLY AND INSTALLATION OF THE FOLLOWING ITEMS:

1.4.3.1. POWER DISTRIBUTION

1.4.3.2. LIGHTING

1.4.3.3. EMERGENCY LIGHTING AND EXIT SIGNAGE

1.4.3.4. FEEDERS AND OVERCURRENT PROTECTION FOR MECHANICAL

EQUIPMENT

1.4.3.5. MOTOR STARTERS FOR MECHANICAL EQUIPMENT

1.4.3.6. FIRE ALARM SYSTEM

1.4.3.7. CABLING PATHWAYS FOR TELECOMMUNICATIONS (VOICE/DATA,

WIRELESS, PA, INTERCOM)

1.5. MATERIALS AND EQUIPMENT

1.5.1. ALL MATERIALS AND EQUIPMENT SHALL BE NEW, C.S.A. CERTIFIED

AND MANUFACTURED TO THE STANDARDS SPECIFIED.

1.5.2. WHERE THERE IS NO ALTERNATIVE TO SUPPLYING EQUIPMENT

WHICH IS NOT C.S.A. CERTIFIED, OBTAIN SPECIAL APPROVAL FROM THE

ELECTRICAL SAFETY AUTHORITY AND CONSULTANT.

1.6. DEMOLITION

1.6.1. REFER TO SECTION 02 41 19 - SELECTIVE DEMOLITION FOR OVERALL

SCOPE RELATED TO THIS ITEM.

1.7. PERMITS AND FEES

1.7.1. THE ELECTRICAL CONTRACTOR SHALL ACT AS THE OWNER'S AGENT

IN ACCORDANCE WITH SECTION 2 OF THE O.E.S.C. AND SHALL IMMEDIATELY

UPON AWARD OF CONTRACT, SUBMIT TO THE LOCAL ELECTRICAL INSPECTION

DEPARTMENT, THE NECESSARY NUMBER OF DOCUMENTS FOR EXAMINATION,

SPECIAL INSPECTION AND APPROVAL, PRIOR TO THE COMMENCEMENT OF THE

WORK, AND PAY ALL COSTS AND ASSOCIATED FEES. IF REQUIRED, PREPARE

ANY ADDITIONAL DRAWINGS/DOCUMENTS REQUIRED BY THE AUTHORITY.

1.7.2. THE CONSULTANT WILL PROVIDE UPON REQUEST, AT THE

CONTRACTOR'S COST, THE REQUIRED QUANTITY OF DRAWINGS.

1.7.3. PROVIDE CERTIFICATES(S) OF ACCEPTANCE FROM THE

AUTHORITIES INSPECTION DEPARTMENT, UPON COMPLETION OF WORK.

1.8. INSURANCE

1.8.1. PROVIDE AND MAINTAIN INSURANCE TO PROTECT THE OWNER AND

TRADES FROM ALL POSSIBLE CLAIMS. SUBMIT WITH BID FOR AN AMOUNT

ACCEPTABLE TO OWNER. ALSO ALL INSURANCE AS NOTED WITHIN

ARCHITECTURAL REQUIREMENTS.

1.9. CONTRACT DOCUMENTS

1.9.1. THE DRAWINGS FOR THE ELECTRICAL WORK ARE DIAGRAMMATIC

ONLY, INTENDED TO CONVEY THE SCOPE OF WORK AND INDICATE THE

GENERAL ARRANGEMENT AND APPROXIMATE SIZE AND LOCATION OF

ELECTRICAL EQUIPMENT. THE DRAWINGS DO NOT INTEND TO SHOW

ARCHITECTURAL, INTERIOR DESIGN, MECHANICAL, STRUCTURAL OR BASE

BUILDING DETAILS. BE RESPONSIBLE FOR A THOROUGH KNOWLEDGE OF SAME

BEFORE PROCEEDING WITH THE WORK.

1.9.2. DO NOT SCALE OR MEASURE ELECTRICAL DRAWINGS, BUT OBTAIN

INFORMATION REGARDING ACCURATE DIMENSIONS FROM THE DIMENSIONS

SHOWN ON THE DRAWINGS, OR BY SITE REQUIREMENTS/CONDITIONS.

1.9.3. ANY DISCREPANCIES BETWEEN DRAWINGS AND/OR SPECIFICATIONS

AND EXISTING CONDITIONS, MUST BE REFERRED TO THE CONSULTANT BEFORE

ANY WORK AFFECTED IS BEGUN.

1.9.4. MAKE, AT NO ADDITIONAL COST, ANY CHANGES OR ADDITIONS TO

MATERIALS AND EQUIPMENT NECESSARY TO ACCOMMODATE STRUCTURAL

CONDITIONS (OFFSETS AROUND BEAMS, COLUMN, ETC.)

1.10. INTENT

IT IS THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS THAT THE

CONTRACTOR PROVIDES COMPLETE AND OPERATIONAL SYSTEMS AS

REQUIRED, WHERE DIFFERENCES OCCUR, CONTRACTOR SHALL CONTACT

ENGINEER OF RECORD FOR FURTHER CLARIFICATION.

1.10.1. ANY MISCELLANEOUS ITEMS, HARDWARE, DEVICES, WIRING, ETC.,

NOT SPECIFICALLY DESCRIBED, BUT REQUIRED FOR THE OPERATION OF THE

SYSTEM, MUST BE PROVIDED AND INCLUDED AS PART OF THE CONTRACT

PRICE.

1.11. SHOP DRAWINGS

1.11.1. "SHOP DRAWINGS" SHALL INCLUDE DRAWINGS, DIAGRAMS,

ILLUSTRATIONS, SCHEDULES, PERFORMANCE, CHARTS, BROCHURES, AND

OTHER DATA WHICH ARE TO BE PROVIDED BY CONTRACTOR TO ILLUSTRATE

DETAILS OF WORK UNDER CONTRACT. INDICATE ALL REQUIRED ACCESSORIES

AND ANCHORAGES FOR COMPLETION OF WORK.

1.11.2. SUBMIT SHOP DRAWINGS IN ELECTRONIC FORMAT TO CONSULTANT

FOR REVIEW WITHIN TWO (2) WEEKS OF PROJECT AWARD. CLEARLY IDENTIFY

ANY LONG LEAD ITEMS OR CRITICAL PATH ITEMS. SHOP DRAWINGS SHALL BE

REVIEWED, STAMPED, AND SIGNED BY THE ELECTRICAL CONTRACTOR PRIOR

TO SUBMISSION TO THE CONSULTANT. SHOP DRAWINGS NOT REVIEWED SHALL

BE REJECTED. REVIEW SHALL INCLUDE AT MINIMUM EQUIPMENT

PERFORMANCE, DIMENSIONS, CLEARANCES, COLOURS/FINISHES, ELECTRICAL

REQUIREMENTS INCLUDING VOLTAGES AND RATINGS, AND COORDINATION WITH

EXISTING SITE CONDITIONS.

1.11.3. SUBMIT FOUR (4) COPIES OF SHOP DRAWINGS OF ALL SPECIFIED

EQUIPMENT FOR REVIEW AND RECORDS BEFORE COMMENCEMENT OF WORK.

1.11.4. MAKE CHANGES IN SHOP DRAWINGS AS OWNER OR CONSULTANT

MAY REQUIRE. CHANGES MADE TO THE SHOP DRAWINGS BY THE CONSULTANT

SHALL NOT AFFECT THE CONTRACT PRICE.

1.10 RECORD DRAWINGS

1.11.1. KEEP A RECORD SET OF DRAWINGS ON THE SITE ON WHICH SHALL

BE CLEARLY INDICATED THE EXACT LOCATION OF PANELS, CONDUITS,

JUNCTION BOXES, ETC.. INFORMATION ON THESE DRAWINGS SHALL BE

INCORPORATED IN THE AS-BUILT DRAWINGS UPON COMPLETION OF THE

CONTRACT AND BEFORE APPLYING FOR FINAL PAYMENT.

1.11 INTERRUPTION OF SERVICES

1.11.1. INTERRUPTION OF ELECTRICAL SERVICE TO ANY PART OF THE

BUILDING SHALL OCCUR ONLY BY PER-ARRANGEMENT WITH AND AT TIMES

SUITABLE TO THE OWNER.

1.12 IDENTIFICATION

1.12.1. PROVIDE LAMACOID NAMEPLATES ON ALL EQUIPMENT TO MATCH

EXISTING NAMEPLATES. NAMEPLATES SHALL BE MECHANICALLY ATTACHED

TO EQUIPMENT BY MEANS OF RIVETS OR SELF TAPPING SCREWS.

1.12.2. CLEARLY MARK ALL EXPOSED CONDUIT, PULLBOXES, JUNCTION

BOXES, ETC., TO INDICATE THE NATURE OF THE SERVICE TO MATCH EXISTING

BUILDING STANDARDS.

1.13 ENGINEERS INSPECTIONS

1.13.1. CONTRACTOR SHALL ARRANGE FOR INSPECTIONS BY THE

CONSULTANT PRIOR TO CEILINGS AND/OR WALLS BEING CLOSED IN. PROVIDE

MINIMUM THREE (3) BUSINESS DAYS' NOTICE. WHERE PROPER NOTICE OR

ARRANGEMENTS HAVE NOT BEEN MADE, CONTRACTOR SHALL OPEN UP ANY

WALLS, CHASES, OR CEILINGS AS REQUIRED FOR FULL AND ADEQUATE

INSPECTION BY THE CONSULTANT.

1.13.2. FINAL INSPECTION IS IMPERATIVE. CONTRACTOR SHALL CONTACT

CONSULTANT AND THE OWNER'S EXISTING REPRESENTATIVE TO PERFORM A

FINAL INSPECTION. ENSURE THAT ALL NEW INSTALLATION PERFORMED IS NOT

OBSTRUCTED FOR INSPECTION. AND ALL NOTED DEFICIENCIES ARE

CORRECTED TO OWNERS/CONSULTANT SATISFACTION.

1.14 PROGRESS PAYMENTS

1.14.1 PROVIDE DETAILED PROGRESS DRAW BREAKDOWN INCLUDING

MATERIALS AND LABOURS FOR ALL DIVISIONS AND SUB-TRADES. SUBMIT

DRAFT TO CONSULTANT FOR REVIEW PRIOR TO FIRST INVOICE. INCLUDE

MINIMUM $2,000.00 FOR CLOSEOUTS INCLUDING O&M MANUALS AND AS-BUILT

DRAWINGS. CLOSEOUTS LINE ITEM SHALL REMAIN UNBILLED UNTIL O&M

MANUALS AND AS-BUILT DRAWINGS HAVE BEEN SUBMITTED AND APPROVED BY

THE CONSULTANT.

1.15 OPERATION AND MAINTENANCE DOCUMENTATION

1.15.1. PROVIDE ELECTRONIC COPY OF O&M MANUAL ON USB DRIVE. O&M

MANUAL SHALL INCLUDE, BUT NOT BE LIMITED TO, TABLE OF CONTENTS,

CONTRACTOR AND SUB-TRADE LIST AND CONTACT INFORMATION, WARRANTY

LETTER, SHOP DRAWINGS INCLUDING CONSULTANT'S REVIEW STAMP, STARTUP

AND TEST REPORTS, ESA CERTIFICATE, FIRE ALARM VERIFICATION REPORT,

EMERGENCY LIGHTING TEST REPORT, O&M MANUALS FOR ALL EQUIPMENT, AND

AS-BUILT DRAWINGS. AS-BUILT DRAWINGS SHALL BE SUBMITTED IN

HARD-COPY AND STAMPED BY THE ELECTRICAL CONTRACTOR. AS-BUILT

DRAWINGS SHALL INCLUDE THE ENTIRE ELECTRICAL DRAWING SET WITH ALL

CHANGES OR EXISTING CONDITIONS MARKED NEATLY IN RED INK. AS-BUILT

DRAWINGS WILL BE REJECTED IF AN INCOMPLETE SET OR MARKUPS ARE

SUBMITTED.

2. PART B - PRODUCTS

2.1. GENERAL

2.1.1. ALL ELECTRICAL EQUIPMENT SHALL BE C.S.A. APPROVED AND BEAR

THE C.S.A. STAMP. ALL EQUIPMENT SHALL BE NEW UNLESS OTHERWISE NOTED.

2.1.2. COMPLETE THE INSTALLATION IN ACCORDANCE WITH CSA C22.1

EXCEPT WHERE SPECIFIED OTHERWISE.

2.2. BUILDING WIRES

2.2.1. CONDUCTORS: COPPER, STRANDED FOR 10 AWG AND LARGER.

MINIMUM SIZE: 12 AWG OR AS INDICATED, WITH 1000 V INSULATION OF

CHEMICALLY CROSS-LINKED THERMOSETTING POLYETHYLENE MATERIAL

RATED RW90.

2.2.2. CONNECTORS: PRESSURE TYPE, FIXTURE TYPE, ETC. TO CSA C22.2

NO. 65 WITH CURRENT CARRYING PARTS OF COPPER SIZED TO FIT COPPER

CONDUCTORS AS REQUIRED. BUSHING STUD TYPE TO EEMAC 1Y-2.

2.3. CONDUIT

2.3.1. LIQUID TIGHT FLEXIBLE METAL CONDUIT TO CSA C22.2 NO. 56 FOR

FINAL CONNECTIONS TO MOTORS/ROOFTOP UNITS IN DAMP OR WET LOCATIONS

AND FLEXIBLE METAL CONDUIT FOR CONNECTION TO SURFACE/RECESSED

LUMINAIRES AND MOTORS IN DRY AREAS. MAXIMUM 1M (3') LENGTH.

2.3.2. ELECTRICAL METALLIC TUBING (BUILDING INTERIOR, WHERE NOT

SUBJECT TO PHYSICAL DAMAGE) TO CSA C22.2 NO. 83 WITH COUPLINGS OR

RIGID METAL CONDUIT - HOT DIPPED GALVANIZED STEEL THREADED (BUILDING

INTERIOR WHERE SUBJECT TO PHYSICAL DAMAGE, ALL BUILDING EXTERIOR

AND EPOXY COATED EXCEPT 2.3.1 ABOVE) TO CSA C22.2 NO. 45 C/W LIQUID

TIGHT COMPRESSION FITTINGS.

2.3.3. CONDUIT TO BE 21MM (3/4") MINIMUM TRADE SIZE.

2.3.4. FOLLOW MANUFACTURER'S RECOMMENDATIONS AND C22.1 FOR

EXPANSION FITTINGS (RMC), FASTENINGS, FITTINGS, ACCESSORIES TO PROVIDE

A COMPLETE INSTALLATION. U SHAPED CHANNELS, HANGARS, CLAMPS SHALL

BE GALVANIZED STEEL TYPE, WITH FREE RUNNING THREADS WHERE FIT.

2.4. OUTLET BOXES, CONDUIT BOXES:

2.4.1. SIZED TO CSA C22.1.

2.4.2. 102MM SQUARE OR LARGER BOXES AS REQUIRED. GANG BOXES

WHERE WIRING DEVICES ARE GROUPED. BLANK COVER PLATES FOR BOXES

WITHOUT WIRING DEVICES. COMBINATION BOXES WITH BARRIERS FOR

DIFFERENT SYSTEMS WHERE GROUPED.

2.4.3. CONDUIT OUTLET BODIES FOR CONDUIT UP TO 35MM AND PULL

BOXES FOR CONDUITS LARGER THAN 35MM. CAST ALUMINUM BOXES WITH

FACTORY THREADED HUBS AND MOUNTING FEET FOR SURFACE WIRING OF

DEVICES.

2.4.4. KNOCKOUT FILLERS TO PREVENT ENTRY OF DEBRIS.

2.5. SERVICE EQUIPMENT

2.5.1. ALL NEW DISCONNECT SWITCHES, ETC. TO BE OF THE SAME

MANUFACTURER. PROVIDE LOCKABLE NEMA 4X DISCONNECTS FOR OUTDOOR

MOUNTING AND NEMA 2 FOR INDOOR.

2.5.2. ENCLOSURE: BOXES SHALL BE GALVANIZED STEEL CONSTRUCTED,

FRONT SHALL HAVE ANSI 49 GRAY ENAMEL ELECTRODE DEPOSITED OVER

CLEANED PHOSPHATIZED STEEL.

2.5.3. MANUFACTURER: - EATON, SIEMENS, SCHNEIDER ELECTRIC

2.6. FUSES

2.6.1. FUSES SHALL BE BUSSMAN 'FUSETRON' DUAL ELEMENT SLOW

BLOW TYPE, SIZED AS NOTED.

2.7. CIRCUIT BREAKERS

2.7.1. BREAKERS TYPE AND KAIC RATING TO MATCH EXISTING BREAKERS.

MOULDED CASE CIRCUIT BREAKERS TO CSA C22.2 NO. 5.

2.7.2. BOLT ON, QUICK MAKE, QUICK BREAK TYPE FOR MANUAL AND

AUTOMATIC OPERATION.

2.7.3. COMMON-TRIP BREAKERS: WITH SINGLE HANDLE FOR MULTI-POLE

APPLICATIONS.

2.7.4. MAGNETIC INSTANTANEOUS TRIP ELEMENTS IN CIRCUIT BREAKERS

TO OPERATE ONLY WHEN VALUE OF CURRENT REACHES SETTING. TRIP

SETTINGS ON BREAKERS WITH ADJUSTABLE TRIPS TO RANGE FROM 3-8 TIMES

CURRENT RATING.

2.7.5. MOULDED CASE CIRCUIT BREAKER TO OPERATE AUTOMATICALLY

BY MEANS OF THERMAL AND MAGNETIC TRIPPING DEVICES TO PROVIDE

INVERSE TIME CURRENT TRIPPING AND INSTANTANEOUS TRIPPING FOR SHORT

CIRCUIT PROTECTION.

2.8. RECEPTACLES

2.8.1. CSA TYPE 5-15R OR 5-20 R (T-SLOT), 125 V, 15A OR 20 A, U GROUND,

TO: CSA C22.2 No.42 WITH FOLLOWING FEATURES: (1) WHITE UREA MOULDED

HOUSING (2) SUITABLE FOR NO. 10 AWG FOR BACK AND SIDE WIRING (3) BREAK

OFF LINKS FOR USE AS SPLIT RECEPTACLES (4) EIGHT BACK WIRED

ENTRANCES , FOUR SIDE WIRING SCREWS (5) TRIPLE WIRE CONTACTS AND

RIVETTED GROUNDING CONTACTS (6) WEATHERPROOF, GFCI CLASS A RATED

FOR OUTDOOR INSTALLATION.

2.8.2. USB: HUBBELL USB ISX2 WHITE

2.8.3. DO NOT INSTALL OUTLETS BACK TO BACK.

2.8.4. RECEPTACLES WITHIN 1500MM (5FT) OF A WET OR DAMP LOCATIONS

SHALL BE GROUND FAULT CIRCUIT INTERRUPTER TYPE. RECEPTACLE COVER

PLATES SHALL BE STAINLESS STEEL UNLESS OTHERWISE NOTED.

2.9. SWITCHES

2.9.1. 15A/20A, 120V, SINGLE POLE SWITCHES, IVORY TOGGLE AND

MATCHING COVER PLATES. USE CAST BOX IF SURFACE MOUNTED.

2.10. GROUNDING

2.10.1. ALL GROUNDING SHALL CONFORM TO THE ONTARIO ELECTRICAL

SAFETY CODE AND LOCAL AUTHORITY REQUIREMENTS.

2.10.2. PROVIDE SEPARATE GREEN INSULATED GROUND CONDUCTOR IN

EVERY POWER CONDUIT TO ALL DEVICES, EQUIPMENT, AND WITH ALL FEEDERS.

2.11. OCCUPANCY SENSORS

2.11.1. ALL SENSORS SHALL BE 24V. PROVIDE POWER PACKS FOR ALL

SENSORS. SENSOR SHALL BE DUAL TECHNOLOGY USING BOTH PASSIVE

INFRARED AND ULTRASOUND.

2.11.2. SENSORS SHALL HAVE A RE-TRIGGER FUNCTION TO CALL ON THE

LIGHTING SYSTEM WITHIN 5 SECONDS OF TURNING OFF, AND HIGH IMMUNITY TO

FALSE TRIGGERING FROM RFI, EMI. SENSORS THAT INTERFERE WITH

OCCUPANTS USING COCHLEAR IMPLANTS OR HEARING AIDS WILL NOT BE

ACCEPTABLE AND SHALL BE REPLACED WITH A SUITABLE PRODUCT DURING

THIS PROJECT.

2.11.3. PIR SHALL HAVE MULTIPLE SEGMENTED FRESNEL LENS, IN A

MULTIPLE TIER CONFIGURATION, WITH GROOVES-IN TO ELIMINATE DUST AND

RESIDUE BUILD UP. ULTRASONIC SENSORS SHALL UTILIZE ADVANCED SIGNAL

PROCESSING TO ADJUST THE DETECTION THRESHOLD DYNAMICALLY TO

COMPENSATE FOR CONSTANTLY CHANGING LEVELS OF ACTIVITY AND AIR

FLOW THROUGHOUT CONTROLLED SPACE. ULTRASONIC OPERATING

FREQUENCY SHALL BE CRYSTAL CONTROLLED AT NOMINALLY 32 KHZ WITHIN ±

0.002% TOLERANCE TO ASSURE RELIABLE PERFORMANCE AND ELIMINATE

SENSOR CROSS-TALK. SENSORS USING MULTIPLE FREQUENCIES ARE NOT

ACCEPTABLE.

2.11.4. ALL SENSORS SHALL BE CAPABLE OF OPERATING WITH

ELECTRONIC BALLASTS AND MOTOR LOADS. SENSORS SHALL UTILIZE

TECHNOLOGY FOR AUTOMATICALLY ADJUSTABLE TIME DELAY AND SENSITIVITY

SETTINGS.. ALL SENSORS SHALL HAVE UL RATED, 94V-0 PLASTIC ENCLOSURES,

WHITE FINISH. LL SENSORS SHALL PROVIDE AN LED AS A VISUAL MEANS OF

INDICATION AT ALL TIMES TO VERIFY THAT MOTION IS BEING DETECTED DURING

BOTH TESTING AND NORMAL OPERATION. INE VOLTAGE SWITCH WITH BUILT IN

PHOTOCELL, CAPABLE OF BEING MOUNTED IN A 1 GANG SWITCH BOX AND

MADE OF HIGH IMPACT INJECTION MOULDED PLASTIC.

2.11.5. WALL SENSOR SHALL BE HUBBELL INC. LIGHTHAWK2 SERIES,

SIGNIFY PHILIPS OCCUSWITCH SERIES OR APPROVED EQUAL WITH AUTO-ON

AND MANUAL-ON OPERATING MODES. CEILING SENSOR SHALL BE HUBBELL INC.

OMNI SERIES, SIGNIFY PHILIPS OCCUSWITCH LLA SERIES OR APPROVED EQUAL.

2.11.6. HUBBELL UNIVERSAL VOLTAGE POWER PACKS TYPE UVPPM,

SIGNIFY PHILIPS OCCUSWITCH SERIES OR APPROVED EQUAL FOR USE WITH

BOTH MANUAL AND AUTOMATIC ON/OFF CONTROL TO BE INSTALLED AT

LOCATIONS WITH UP TO 4 SENSORS, MOUNTED IN A JUNCTION BOX. OPERATING

VOLTAGE 120V, 60 HZ WITH ELECTRICAL LOAD SWITCHING CAPABILITY OF 20A.

REGULATED 24VDC CURRENT; 150MA OUTPUT. AUTOMATIC VOLTAGE

DETECTION. ZERO ARC POINT SWITCHING TO MINIMIZE RELAY-CONTACT WEAR

FROM HIGH INRUSH LOADS.

2.11.7. ALTERNATES SHALL BE LEVITON, LUTRON, PASS & SEYMOUR.

ENSURE COMPATIBILITY WITH SELECTED LUMINAIRE PRIOR TO INSTALLATION.

2.12. LIGHTING

2.12.1. ALL NEW LIGHTING SHALL BE LED. REFER TO LUMINAIRE SCHEDULE

FOR DETAILS OF FIXTURES. LED'S AND DRIVERS ARE TO BE 100% COMPATIBLE

WITH EACH OTHER. NEMA 410 COMPLIANT DRIVERS. LUMINAIRE WITH LED AND

DRIVER TO BE CSA APPROVED OR ULC LISTED, AND CERTIFIED AND TESTED AS

A COMPLETE ASSEMBLY.

2.12.2. SPECIFICATION STANDARDS TO MEET REQUIREMENTS OF IES LM 79

AND WHERE CONNECTED TO DIMMERS, BE 100% COMPATIBLE WITH CONNECTED

DIMMER CONTROLS TO PROVIDE DIMMING DOWN TO 1%. COORDINATE WITH

DIMMING CONTROLS VENDORS TO ENSURE THAT TECHNICAL OPERATIONS OF

DIMMERS (I.E. FORWARD PHASE, REVERSE PHASE, ETC.) MATCH LED/ DRIVER

TECHNOLOGY. CLEARLY IDENTIFY THIS INFORMATION IN SHOP DRAWING

SUBMISSIONS.

2.12.3. LEDS TO BE SELECTED FROM SAME COLOUR BIN SIZE FOR

CONSISTENCY IN CHROMATICITY AND MEET ANSI C78 377A AS A MINIMUM;

GENERALLY, COLOUR TEMPERATURE RANGE TO BE FROM 2700 K TO 6500 K;

SPECIFIC TEMPERATURE REQUIREMENTS TO BE IDENTIFIED ON SCHEDULE OF

LUMINAIRES AND REVIEWED WITH CONSULTANT PRIOR TO ORDERING; MINIMUM

CRI OF 85. MINIMUM RATED LIFE (BASED ON LM-80 AND TM-21) FROM 50,000 TO

70,000 HOURS.

2.12.4. DRIVERS SHALL OPERATE FROM 60 HZ INPUT SOURCE OF 120

VAC/347VAC (AS APPLICABLE) WITH SUSTAINED VARIATIONS OF ± 10%

(VOLTAGE AND FREQUENCY) WITH NO DAMAGE TO DRIVER; OUTPUT

REGULATED TO ±5% ACROSS LOAD RANGE; POWER FACTOR GREATER THAN

0.90; TOTAL HARMONIC DISTORTION LESS THAN 20%; CLASS A SOUND RATING;

COMPLY WITH ANSI C62.41 CATEGORY A FOR TRANSIENT PROTECTION.

2.12.5. EMERGENCY LIGHTING: REMOTE HEADS TO MATCH EXISTING.

CONNECT NEW HEADS TO EXISTING BATTERY UNITS AND AIM HEADS TO SUIT

SITE CONDITIONS. TEST OPERATION OF HEADS AND CONFIRM.

2.12.6. FOLLOW MANUFACTURER RECOMMENDATIONS FOR MOUNTING IN

SUSPENDED OR T-BAR CEILING. USE AIRCRAFT CABLE FOR MOUNTING

REQUIREMENTS.

2.13. SYSTEMS

2.13.1. GENERAL

2.13.1.1. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING

SERVICES OF QUALIFIED SYSTEMS SUB-CONTRACTORS FOR THE SYSTEMS

NOTED BELOW, AND CARRY OUT ALL THE WORK INCLUDING, BUT NOT LIMITED

TO, CONDUIT, WIRING, DEVICES, EQUIPMENT, TESTING AND VERIFICATION.

2.13.1.2. CONFIRM ROOM NUMBERING WITH ARCHITECT AND OWNER PRIOR

TO PROGRAMMING THE SYSTEMS.

2.13.2. FIRE ALARM

2.13.2.1. NEW FIRE ALARM PANEL TO BE SIMPLEX 4100 ES.

2.13.2.2. PROVIDE ALL MATERIAL AND LABOUR REQUIRED FOR A COMPLETE

AND ADEQUATE INSTALLATION OF THE FIRE ALARM SYSTEM AS SHOWN ON THE

DRAWINGS. PANEL TO BE SINGLE STAGE NON-CODED ADDRESSABLE/HYBRID.

WIRE EXISTING CIRCUITS TO NEW PANEL ZONES.

2.13.2.3. ALL NEW DEVICES TO MATCH NEW PANEL.

2.13.2.4. ALL NEW CONDUIT AND WIRING TO EXISTING DETECTION DEVICES

AND CONTROL EQUIPMENT, WHERE REQUIRED DUE TO ARCHITECTURAL AND

MECHANICAL UPGRADES, SHALL MEET LOCAL AND NATIONAL BUILDING, FIRE

AND ELECTRICAL CODES AND STANDARDS, AND MANUFACTURER

REQUIREMENTS.

2.13.2.5. PAINT ALL FIRE ALARM JUNCTION BOXES RED. PROVIDE LABELING

FOR INDICATING IDC OR NAC FUNCTION.

2.13.2.6. PROVIDE VERIFICATION REPORT ON COMPLETION OF WORK TO

CAN/ULC S537-M "STANDARD FOR THE VERIFICATION OF FIRE ALARM SYSTEMS".

2.13.2.7. PERFORM AUDIBILITY TESTS AS PER ONTARIO BUILDING CODE (MIN.

65dBA, MAX. 100dBA THROUGHOUT) AND PROVIDE REPORT TO CONSULTANT.

ALL SPACES WITHIN PROJECT AREA SHALL BE TESTED. DOORS SHALL BE

CLOSED DURING TESTING.

2.13.2.8. GRAPHIC PANEL TO BE FRAMED UNDER 3.15MM CLEAR PLASTIC

COVER. CLEARLY OUTLINE DETECTION ZONE BOUNDARIES WITH BLACK INK ON

VINYL, NAMES AND NUMBERS WITH RED INK (MIN. HEIGHT 3MM) AND MARK WITH

HIGH VISIBILITY RED LETTERS WITH ARROW SHOWING "YOU ARE HERE".

GRAPHIC PANEL (508MMX508MM) TO BE FIXED PERMANENTLY TO THE WALL.

SHOW LOCATIONS OF ANNUNCIATOR PANEL AND CONTROL PANEL. ORIENT

BUILDING FLOOR PLAN ON GRAPHIC TO LOCATION OF PERSON VIEWING

GRAPHIC I.E. DIRECTION VIEWER IS FACING IS TOWARD TOP OF GRAPHIC

DISPLAY. PROVIDE NORTH ARROW. LOCATIONS - IN VESTIBULE AT THE

LOCATION OF ANNUNCIATOR PANEL, AND ELECTRICAL ROOM B12.

2.13.2.9. NEW FIRE ALARM ZONING SHALL FOLLOW EXISTING (11 ZONES) AND

ADDITIONALLY INCLUDE 1 NEW ZONE FOR ELEVATOR AND 50% SPARE ZONES

FOR FUTURE. ZONING SHALL FOLLOW THE LATEST OBC REQUIREMENTS

2.13.3. PUBLIC ADDRESS, COMMUNICATIONS & SECURITY:

2.13.3.1. INSTALL P.A. DEVICES, COMMUNICATION SYSTEM AND SECURITY

SYSTEM AS PER EACH MANUFACTURERS REQUIREMENTS.ALL NEW DEVICES TO

MATCH EXISTING.

2.13.3.2. PROVIDE INFRASTRUCTURE AS REQUIRED INCLUDING BUT NOT

LIMITED TO BACK BOXES, CONDUIT COMPLETE WITH POLYPROPYLENE PULL

STRING, INSULATING BUSHINGS, STUBS, JUNCTION BOXES, ETC. TO CONSTITUTE

A COMPLETE PATHWAY IN ORDER TO FACILITATE SYSTEM CABLING/WIRING

INSTALLATION.

2.13.3.3. P.A. SYSTEM: EXISTING BY DUKANE

2.13.3.4. P.A. SPEAKERS: EXISTING BY TORTECH/MCBRIDE WHITE SQUARE

GRILL WITH 25V TRANSFORMERS. SPEAKERS TO BE TAPPED 2-4W FOR GYM AND

BOILER ROOMS, 0.25W FOR OFFICES AND 1W FOR ALL OTHER APPLICATIONS.

2.13.3.5. P.A. WIRING: PROVIDE HOME RUNS FROM P.A. DEVICES TO MAIN P.A.

RACK. CABLING SHALL BE CAT6 FT6 WHITE RATED WHEN IN CONDUIT OR FT6

WHERE CONDUIT INSTALLATION IS NOT POSSIBLE. USE EXISTING

COMMUNICATIONS CONDUIT WHERE POSSIBLE OR USE J-HOOKS FOR RUNNING

NEW WIRING WHEN NOT IN CONDUIT. USE PROPER TOOLS FOR PUNCH DOWN ON

EXISTING BIX PANEL FOR ALL WIRING.

2.13.3.6. P.A., TESTING: PERFORM TESTING AND COMMISSIONING,

ADJUSTMENTS TO EXISTING PROGRAMMING AS REQUIRED, VERIFICATION AND

CERTIFICATION OF THE SYSTEM. MAKE ANY CORRECTIONS AT NO COST TO THE

OWNER. PROVIDE FINAL REPORT TO CONSULTANT FOR REVIEW. REPORT TO

INCLUDE TEST DETAILS FOR ALL LINES INDICATING CONTINUITY, SHORTS AND

GROUND. INCLUDE RESULTS OF IMPEDANCE TESTING AT EACH SPEAKER.

2.13.3.7. SECURITY WIRING: USE EXISTING COMMUNICATIONS CONDUIT

WHERE POSSIBLE OR USE J-HOOKS FOR RUNNING NEW WIRING WHEN NOT IN

CONDUIT. PROVIDE HOME RUNS FROM DEVICES TO MAIN SECURITY CONTROL

PANEL. INSTALL DEVICES AND WIRING AS PER MANUFACTURER REQUIREMENT.

2.13.3.8. SECURITY TESTING: PERFORM TESTING AND COMMISSIONING,

ADJUSTMENTS AS REQUIRED, VERIFICATION AND CERTIFICATION OF THE

SYSTEM. MAKE ANY CORRECTIONS AT NO COST TO THE OWNER. PROVIDE FINAL

REPORT TO CONSULTANT FOR REVIEW.

2.13.3.9. COMMUNICATIONS CABLING PER TIA 568.0-D, 568.01-D, 568.02-D.

2.13.3.10. COMMUNICATIONS PATHWAYS PER TIA 569-E.

2.13.3.11. COMMUNICATIONS GROUNDING AND BONDING PER TIA 607-D.

2.13.3.12. COMMUNICATIONS CABLING: ALL COMMUNICATIONS CABLING

SHALL BE RUN WITHIN EXISTING COMMUNICATIONS CONDUIT/RACEWAYS

WHERE POSSIBLE. ALL CABLING SHALL BE RUN IN CONDUIT FROM

COMMUNICATION OUTLETS TO CORRIDOR CABLE MANAGEMENT SYSTEM.

EXISTING SYSTEM SHALL BE BASED ON PANDUIT STRUCTURED CABLING.

MAXIMUM HORIZONTAL RUN SHALL NOT EXCEED 100m FROM HORIZONTAL

CROSS CONNECT. ALL CABLING MUST BE 24AWG CAT6 100-OHM BALANCED

UNSHIELDED TWISTED PAIR, FT6 RATED, BLUE OUTER SHEATH FOR BOTH VOICE

AND DATA. FACEPLATES TO MOUNT UP TO SIX (6) JACKS IN A SINGLE GANG AND

UP TO NINE (9) JACKS IN A DOUBLE GANG. JACKS SHALL BE 8-POSITIONED

UNKEYED WITH 94 V0 RATING. ALL DROPS SHALL BE CLEARLY LABELED ON THE

PATCH PANEL AND CABLE BOX. PROVIDE YELLOW FOR VOICE AND GREEN FOR

DATA. PROVIDE HOME RUN CABLING TO MAIN SWITCH FROM EACH WIRELESS

ACCESS POINT. ALLOW ENOUGH LENGTH OF CABLE AT EACH END (PATCH

PANEL AND OUTLET) TO ALLOW RELOCATING CABLING IN THE FUTURE.

PROVIDE 4' AND 6' PATCH CABLES AT WORK WORK STATION END AS REQUIRED

TO SUIT THE INSTALLATION. COORDINATE WITH OWNER. FOR EACH ACCESS

POINT, CONTRACTOR TO ALLOW FOR NEW HOMERUN CABLE BACK TO THE MAIN

CONTROL PANEL FOR POSSIBLE RELOCATION.

2.13.3.13. COMMUNICATIONS TESTING: TEST ALL DROPS FOR DATA

TRANSMISSION REQUIREMENTS PER APPLICABLE STANDARDS AND PROVIDE

REPORT TO CONSULTANT.

2.13.3.14. COORDINATE WITH OWNER AND MANUFACTURER FOR ALL

REQUIRED DOCUMENTS, STANDARDS AND RECOMMENDATIONS PRIOR TO

COMMENCING WORK ON P.A., COMMUNICATIONS AND SECURITY.

2.13.3.15. CONTRACTOR SHALL RE-PROGRAM ON EACH SYSTEM (P.A.,

COMMUNICATIONS, SECURITY) AFTER COMPLETION OF INSTALLATION AND

PERFORM TESTING FOR OPERATIONAL READINESS. PROVIDE TEST REPORTS TO

CONSULTANT FOR REVIEW. COORDINATE SCOPE EXTENT OF PROGRAMMING

WITH THE OWNER

2.13.4. LIST OF APPROVED SUB-CONTRACTORS:

2.13.4.1. ACCESS CONTROL SYSTEMS & SECURITY SYSTEMS:

TRENT SECURITY, 705.748.2001

2.13.4.2. P.A., COMMUNICATION SYSTEMS:

ELECTRICAL CONTRACTOR TO BE RESPONSIBLE FOR OBTAINING

THE SERVICES OF A QUALIFIED PUBLIC ADDRESS SYSTEM CONTRACTOR.

2.13.4.3. FIRE ALARM

FIRE ALARM INSTALLER: CFAA CERTIFIED.

Printed on ___% Post-Consumer

Recycled Content Paper

This draw

ing has been prepared for the use of A

EC

OM

's client and m

ay not be used, reproduced or relied upon by third parties, except as agreed by A

EC

OM

and its client, as required by law

or for use by governm

ental review

ing agencies. A

EC

OM

accepts no responsibility, and denies any liability w

hatsoever, to any party that m

odifies this draw

ing w

ithout A

EC

OM

's express w

ritten consent. D

o not scale this docum

ent. A

ll m

easurem

ents m

ust be obtained from

stated dim

ensions.

KEY PLAN

REGISTRATION

CLIENT

Kawartha Pine Ridge

District School Board

1994 Fisher Drive, Peterborough, Ontario

705.742.9773 tel 705.742.7801 fax

www.kprdsb.ca

PROJECT

New Elevator & Renovation

Prince of Wales

Public School

1211 Monaghan Road. S. Peterborough, Ontario

PROJECT NUMBER

60624140

AR

CH

D

2

4" x 3

6"

CONSULTANT

AECOM Canada Ltd.

300 Water Street

Whitby, Ontario, Canada L1N 9J2

905.215.1400 tel 905.668.0221 fax

www.aecom.com

2

2

2

AutoCAD SHX Text
C
AutoCAD SHX Text
C
AutoCAD SHX Text
C