POTENTIAL TRANSFORMERS POTENTIAL TRANSFORMERS PHONE (614) 889-6152 TECH. ASSISTANCE (614) 876-8308 FAX # (614) 876-8538 6625 McVey Blvd. Columbus, Ohio 43235 Div. Morlan & Associates, Inc. 47 WWW.FLEX-CORE.COM [email protected] HIGH VOLTAGE POTENTIAL TRANSFORMER • Frequency ........................................................ 60Hz. Standard Secondary Voltage ....................... 120VAC Insulation Class ........... 15.5kV, BIL 110KV Full Wave UL Recognized FOR INDOOR USE ONLY Accuracy Class 0.3 WXMYZ, 1.2ZZ at 100% rated voltage with 120V based ANSI burden. 0.3 WXMY, 1.2Z at 58% rated voltage with 69.3 V based ANSI burden. Frequency ....................................................................... 60Hz Insulation Class ...................... 15.5 kV, BIL 110kV Full Wave Thermal Rating ................................... 1500 VA at 30 O C Amb. ............................................................ 1000 VA at 55 O C Amb. Weight ................................................... Approximately 88 lbs. Primary terminals that are fused are 1/4 - 20 brass screws with one flatwasher, lockwasher and two nuts. Secondary terminals are NO. 10-32 brass screws with one flatwasher and lockwasher. The transformers are tested for partial discharge to Canadian Standards CAN 3-C13-M83. This test can also be carried out to IEC requirements if requested. The core and coil assembly is encased in a plastic enclosure and vacuum encapsulated in polyurethane resin. Thermal burden rating is for 120 volt secondaries. Plated steel mounting base. Fuses have 1.63" Dia. Caps and 11.50" clip centers. A test card is provided with each unit. (a*) Voltage transformers connected line-to-ground cannot be considered to be grounding transformers and must not be operated with the secondaries in closed delta because excessive currents may flow in the delta. (b*) Two fuse transformers should not be used for Y connections. It is preferred practice to connect one lead from each voltage transformer directly to the neutral terminal, using a fuse in the line side of the primary only. By this connection a transformer can never be "alive" from the line side by reason of a blown fuse in the neutral side. For continuous operation, the transformer primary voltage should not exceed 110% of rated value. Use one fuse, one bushing models for Y applications. Use two fuse, two bushing models for delta applications. MODEL PTG5 SPECIFICATIONS ® E145172 ® LR89403 Note: It is recommended that the system line-to-line voltage not exceed the transformer insulation level. 7200 60:1 120 PTG5-1-110-722F 8400 70:1 120 PTG5-1-110-842F 12000 100:1 120 PTG5-1-110-123F 14400 120:1 120 ............PTG5-1-110-1442F TWO BUSHING (b*) PRIMARY SECONDARY CATALOG VOLTAGE RATIO VOLTAGE NUMBER 7200 60:1 120 ....PTG5-2-110-722FF 8400 70:1 120 .PTG5-2-110-842FF 12000 100:1 120 ........PTG5-2-110-123FF 14400 120:1 120 ........PTG5-2-110-1442FF SINGLE BUSHING (a*) Two Bushing X2 X1 H2 H1 One Bushing X1 X2 H1 H2 FEATURES 15KV CLASS

description

karakter trafo

Transcript of karakteristik trafo

  • POTENTIAL TRANSFORMERSP

    OTE

    NTIA

    L TRA

    NS

    FOR

    ME

    RS

    PHONE (614) 889-6152TECH. ASSISTANCE (614) 876-8308

    FAX # (614) 876-85386625 McVey Blvd. Columbus, Ohio 43235Div. Morlan & Associates, Inc.

    47

    [email protected]

    HIGH VOLTAGE POTENTIAL TRANSFORMER

    Frequency ........................................................ 60Hz.

    Standard Secondary Voltage ....................... 120VAC

    Insulation Class ........... 15.5kV, BIL 110KV Full Wave

    UL Recognized

    FOR INDOOR USE ONLY

    Accuracy Class0.3 WXMYZ, 1.2ZZ at 100% rated voltage with 120V basedANSI burden. 0.3 WXMY, 1.2Z at 58% rated voltage with 69.3 Vbased ANSI burden.Frequency ....................................................................... 60HzInsulation Class ...................... 15.5 kV, BIL 110kV Full WaveThermal Rating ................................... 1500 VA at 30OC Amb............................................................. 1000 VA at 55OC Amb.

    Weight ...................................................Approximately 88 lbs.

    Primary terminals that are fused are 1/4 - 20 brass screws with one flatwasher, lockwasher and two nuts. Secondary terminals are NO. 10-32 brass screws with one flatwasher and lockwasher. The transformers are tested for partial discharge to Canadian Standards CAN 3-C13-M83. This test can also be

    carried out to IEC requirements if requested. The core and coil assembly is encased in a plastic enclosure and vacuum encapsulated in polyurethane resin. Thermal burden rating is for 120 volt secondaries. Plated steel mounting base. Fuses have 1.63" Dia. Caps and 11.50" clip centers. A test card is provided with each unit.

    (a*) Voltage transformers connected line-to-ground cannot beconsidered to be grounding transformers and must not beoperated with the secondaries in closed delta because excessivecurrents may flow in the delta.

    (b*) Two fuse transformers should not be used for Y connections.It is preferred practice to connect one lead from each voltagetransformer directly to the neutral terminal, using a fuse in theline side of the primary only. By this connection a transformercan never be "alive" from the line side by reason of a blown fusein the neutral side. For continuous operation, the transformerprimary voltage should not exceed 110% of rated value. Useone fuse, one bushing models for Y applications. Use two fuse,two bushing models for delta applications.

    MODEL PTG5

    SPECIFICATIONS

    E145172

    LR89403

    Note: It is recommended that the system line-to-line voltage not exceed the transformer insulation level.

    7200 60:1 120 PTG5-1-110-722F

    8400 70:1 120 PTG5-1-110-842F

    12000 100:1 120 PTG5-1-110-123F

    14400 120:1 120 ............PTG5-1-110-1442F

    TWO BUSHING (b*)PRIMARY SECONDARY CATALOG

    VOLTAGE RATIO VOLTAGE NUMBER

    7200 60:1 120 ....PTG5-2-110-722FF

    8400 70:1 120 .PTG5-2-110-842FF

    12000 100:1 120 ........PTG5-2-110-123FF

    14400 120:1 120 ........PTG5-2-110-1442FF

    SINGLE BUSHING (a*)

    TwoBushing

    X2X1

    H2H1

    OneBushing

    X1 X2

    H1 H2

    FEATURES

    15KV CLASS

  • POTENTIAL TRANSFORMERSP

    OTE

    NTI

    AL

    TR

    AN

    SFO

    RM

    ER

    S

    PHONE (614) 889-6152TECH. ASSISTANCE (614) 876-8308

    FAX # (614) 876-85386625 McVey Blvd. Columbus, Ohio 43235Div. Morlan & Associates, Inc.

    48

    [email protected]

    MODEL PTG5DIMENSIONS, ETC.

    Recommended spacings are for guidance only. User needs to set appropriate values to assure performance for:high potential test; impulse test; high humidity; partial discharge; high altitude; and other considerations like configuration.

    The circle diagram can be used topredict the performance of a transformerfor various loads and power factors. Aconvenient scale of volt-amperes isshown on the unity power factor line(u.p.f.) and commences at the zero orno-load locus. To use the diagram,measure the known V.A. and scribe anarc about the "zero" locus of a lengththat contains the angle of the burdenpower factor. The point at which thearc terminates is the error locus in phaseangle minutes and ratio correctionfactor.

    B = HV To Ground In Air = 6.5" Min.A = Unit To Unit Or To Ground = 1.25" Min.

    B A A BAB

    1" x 2"Notch

    InterruptingAmperes(SYM)

    80,00080,00080,00080,000

    Fuse For ModelPTG5 Transformer

    7200:120V8400:120V

    12000:120V14400:120V

    RatingVolts

    15.5kV15.5kV15.5kV15.5kV

    Clip CenterInches11.5011.5011.5011.50

    LengthInches

    13131313

    Cap Dia.Inches1.631.631.631.63

    ContinuousAmperes

    1.0E1.0E0.5E0.5E

    Y

    ZZ

    Z

    0100

    200300

    400

    500600

    700VA

    0.1 p.f.

    0.2 p.f.0.7 p.f.0.85 p.f.

    u.p.f.

    0.3 ACCURACY CLASS0.6 ACCURACY CLASS1.2 ACCURACY CLASS

    Phase Angle, Minutes+60+50+40+30+20+100-10-20-30-40-50-60

    0.996

    0.998

    1.000

    1.002

    1.004

    1.006

    1.008

    1.010

    1.012

    Rat

    io C

    orre

    ctio

    n Fa

    ctor

    Circle Diagram

    X1X2

    TWO FUSE11.31

    9.00

    8.94

    11.50

    9.19

    10.63

    13.69

    0.56H

    1

    (H2 Ht.)

    10.75

    X1X2

    0.56

    10.9413.06

    ONE FUSE

    4.06

    0.62

    11.50

    13.1311.250.44

    H2: 1/4-20 StudWith Lockwasher,Flatwasher AndTwo Nuts

    2.00

    H1

    PTG5-1-110 DIMENSIONS PTG5-2-110 DIMENSIONS

    RECOMMENDED SPACINGS

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputCondition () /PDFXRegistryName (http://www.color.org) /PDFXTrapped /Unknown