7(/ )$; ZZZVHWHFRPFRP IRU GHWDLOHG PDQXDO IVT -1260 / IVT -2460 Generator Auxiliary Excitation Booster (Patent Pending) Converts DC battery power into AC power source for use by the AVR to boost motor starting capacity in shunt generators Features Exceeds normal generator motor starting capabilities Applicable for generator no-load excitation voltage between 20-50 Vdc Provides the load response benefits of a PMG Easy to install and maintenance free Compact size & high efficiency Battery voltage abnormal protection Battery input reverse polarity protection Battery current limit protection Power output self-test Built-in DC bolt-on fuse Very low power consumption in hibernate mode Lower cost than PMG kit Applicable AVR Models KUTAI EA08A, EA448, ADVR-12, ADVR-2200M, ADVR-08 Caterpillar VR6 Basler AVC63-12, AVC125-10 *Suitable for full wave AVR equipped with Auxiliary power input. (More models adding continuously) Specifications Sensing Input Voltage 80-600 Vac single phase Input Current Limited IVT-1260 @ 60A Frequency 50 / 60 Hz IVT-2460 @ 30A Power Input IVT-1260 12 Vdc / 60A Battery Battery Voltage Range IVT-1260 @ 8-14 Vdc IVT-2460 24 Vdc / 30A Battery IVT-2460 @ 16-28 Vdc Output Voltage 180 Vac Static Power Consumption < 1 watt (hibernate < 0.5 watts) Max. output 500 VA Environment Operation Temperature -40 - +70 °C Frequency 400-480 Hz Storage Temperature -40 - +85 °C Response Time 10 ms Relative Humidity Max. 95% Efficiency >90% @ Full load Vibration 3Gs @ 100-2K Hz Mechanical Specifications Adjustment Droop % Level of sensitivity set on the trigger ( 5% to 14% ) Time ON Power output activation time ( 15s to 60s ) LED Indicators Output LED Boost Power ON Ready LED Ready for output Test LED Self-Test in progress Batt-Volt LED Battery Voltage abnormal OVLD LED Overload Physical Specification Dimensions 115.0 (L) x 115.0 (W) x 98.5 (H) mm Weight 2400 g +/- 2%

Transcript of IVT-1260 , IVT-2460 ma e - Setecom...

Page 1: IVT-1260 , IVT-2460 ma e - Setecom S.A.setecom.com/wp-content/uploads/2015/09/ivt1260ivt2460-manual-en.pdf · KUTAI EA08A, EA448, ADVR-12, ADVR-2200M, ADVR-08 Caterpillar VR6 ...

7(/������������������)$;���������������������ZZZ�VHWHFRP�FRP���������IRU�GHWDLOHG�PDQXDO��

IVT-1260 / IVT-2460 Generator Auxiliary Excitation Booster (Patent Pending) Converts DC battery power into AC power source for use by the AVR to boost

motor starting capacity in shunt generators

Features Exceeds normal generator motor starting capabilities

Applicable for generator no-load excitation voltage between 20-50 Vdc

Provides the load response benefits of a PMG

Easy to install and maintenance free

Compact size & high efficiency

Battery voltage abnormal protection

Battery input reverse polarity protection

Battery current limit protection

Power output self-test

Built-in DC bolt-on fuse

Very low power consumption in hibernate mode

Lower cost than PMG kit

Applicable AVR Models KUTAI EA08A, EA448, ADVR-12, ADVR-2200M, ADVR-08 Caterpillar VR6

Basler AVC63-12, AVC125-10

*Suitable for full wave AVR equipped with Auxiliary power input. (More models adding continuously)

SpecificationsSensing Input Voltage 80-600 Vac single phase Input Current Limited IVT-1260 @ 60A

Frequency 50 / 60 Hz IVT-2460 @ 30A

Power Input IVT-1260 12 Vdc / 60A Battery Battery Voltage Range IVT-1260 @ 8-14 Vdc

IVT-2460 24 Vdc / 30A Battery IVT-2460 @ 16-28 Vdc

Output Voltage 180 Vac Static Power Consumption < 1 watt (hibernate < 0.5 watts)

Max. output 500 VA Environment Operation Temperature -40 - +70 °C

Frequency 400-480 Hz Storage Temperature -40 - +85 °C

Response Time 10 ms Relative Humidity Max. 95%

Efficiency >90% @ Full load Vibration 3Gs @ 100-2K Hz

Mechanical Specifications Adjustment Droop % Level of sensitivity set on the trigger ( 5% to 14% )

Time ON Power output activation time ( 15s to 60s )

LED Indicators Output LED Boost Power ON

Ready LED Ready for output

Test LED Self-Test in progress

Batt-Volt LED Battery Voltage abnormal

OVLD LED Overload

Physical Specification Dimensions 115.0 (L) x 115.0 (W) x 98.5 (H) mm

Weight 2400 g +/- 2%

Page 2: IVT-1260 , IVT-2460 ma e - Setecom S.A.setecom.com/wp-content/uploads/2015/09/ivt1260ivt2460-manual-en.pdf · KUTAI EA08A, EA448, ADVR-12, ADVR-2200M, ADVR-08 Caterpillar VR6 ...

7(/������������������)$;���������������������ZZZ�VHWHFRP�FRP���������IRU�GHWDLOHG�PDQXDO��

IVT-1260 & IVT-2460 Generator Auxiliary Excitation Booster

Operation Manual (Patent Pending)

The IVT-1260 / IVT-2460 is used to boost motor starting capacity in shunt generators. It achieves boosting power by converting DC battery power to an AC source for use by the AVR. This independent power behaves in the same way as a PMG, augmenting the generator’s ability to handle a larger motor starting current, thereby exceeding its normal motor starting capabilities. It is easy to install, allowing the unit to be integrated to the generator excitation systems quickly. Applicable for generator no-load excitation voltage between 20 − 50 Vdc.

Suitable for full wave AVR equipped with Auxiliary power input. Applicable AVR Models (More models adding continuously)烉 KUTAI EA08A, EA448, ADVR-12, ADVR-2200M Basler AVC63-12, AVC125-10, CATERPILLAR VR6

Page 3: IVT-1260 , IVT-2460 ma e - Setecom S.A.setecom.com/wp-content/uploads/2015/09/ivt1260ivt2460-manual-en.pdf · KUTAI EA08A, EA448, ADVR-12, ADVR-2200M, ADVR-08 Caterpillar VR6 ...

___________________________________________________________________________________________ 2 IVT-1260 & IVT-2460

SECTION 1 : SPECIFICATION Sensing Input S1, S2 Static Power Consumption

Voltage 80 − 600 Vac, 1 phase < 1 watt (hibernate < 0.5 watts) Frequency 50/60 Hz

Efficiency Power Output OUT1, OUT2 > 90% @ Full load

Voltage 180 Vac, 1 phase Max. Output 500VA Environment Frequency 400/480 Hz Operation Temperature -40 − +70 ˚C

Storage Temperature -40 − +85 ˚CBattery Power Input B+, B- Relative Humidity Max. 95%

IVT-1260 Volts 12 Vdc (8 − 14 Vdc) / 60A Vibration 3 Gs @ 100 − 2K Hz IVT-2460 Volts 24 Vdc (16 − 28 Vdc) / 30A Battery Voltage Reverse Polarity Protection Dimensions Battery Current Limit 115.0 (L) x 115.0 (W) x 98.5 (H) mm Fuse Spec. IVT-1260 (60A) / IVT-2460 (30A)

Weight Response Time 2400 g +/- 2%

10 ms

SECTION 2 : OUTLINE / SIZE

Accessories : 1. Connection wires ( White*2, Brown*2 )2. Screw bolt M6L20*4

Page 4: IVT-1260 , IVT-2460 ma e - Setecom S.A.setecom.com/wp-content/uploads/2015/09/ivt1260ivt2460-manual-en.pdf · KUTAI EA08A, EA448, ADVR-12, ADVR-2200M, ADVR-08 Caterpillar VR6 ...

___________________________________________________________________________________________ IVT-1260 & IVT-2460 3

SECTION 3 : DESCRIPTION

Item / Settings 0 1 2 3 4 5 6 7 8 9 Droop % 10 % 11 % 12 % 13 % 14 % 15 % 16 % 17 % 18 % 19 % Time-ON 15 Sec 20 Sec 25 Sec 30 Sec 35 Sec 40 Sec 45 Sec 50 Sec 55 Sec 60 Sec

Table 1

Droop % Is the level of sensitivity set on the trigger that turns the IVT “ON” when it senses a drop in voltage on terminals S1, S2. This droop can be adjusted 10 to 19 percent of the preset working voltage.

Time-ON Is the time in seconds that the IVT is activated every time it senses a drop in voltage. This timer can be set from 15 to 60 seconds.

To Test the IVT by Moving DIP-SW1 to “ON” 1. Remove any wires from the Power Output Terminals

OUT1 & 2 before starting.2. Move DIP-SW1 to ON to start the test, terminals OUT1 &

2 will now energize for 5 Seconds.3. The TEST LED should show a steady glow Indicating a

good test or a flashing LED if the IVT is damaged.4. Move the DIP-SW1 back to OFF and put back the wires

OUT1 & 2.

WARNING : When doing the Power Output Test DO NOT touch terminals (OUT1 & 2). These emit a dangerous 180 Vac / 400 Hz during the test. Also be careful not to short these terminals, as you can damage the IVT.

Output LED (Green) Boost Power ON LED indicator

Ready LED (Green) Flashing : Waiting Steady Light : Sensing voltage is stable and boosting power is on standby ready for activation.�

Test LED (Green) When flashing : Power Output Test failed. If LED is steady the test was successful.�

Batt-Volt LED (Red) Battery-voltage abnormal indicator Rated Voltage Range IVT-1260 : 8 − 14 Vdc / IVT-2460 : 16 − 28 Vdc

When Battery Voltage Abnormal : IVT has no output, indicator illuminates and prevents output. IVT has output, indicator illuminates and locks off power output, resets after the generator is shutdown.

OVLD LED (Red) Power Output Overload Light When Boost Power is ON and the current from the battery exceeds 60A at 12V or 30A at 24V, the IVT starts a current limiting function and the OVLD LED will turn on.

Connection Wire Sizes IVT-1260 ʁ AWG 8 (8.3mm2) IVT-2460 ʁ AWG10 (5.3mm2)

B+ & B- Battery Power Input

S2 S1 OU

T2

OU

T1

B +B

Time

Test

Output

Ready

Test

Batt-Volt

OVLD

ON

Droop%

S1 & S2 Are the voltage sensing input terminals.

OUT1 & OUT2 Are the power output terminals going to the AVR.

Page 5: IVT-1260 , IVT-2460 ma e - Setecom S.A.setecom.com/wp-content/uploads/2015/09/ivt1260ivt2460-manual-en.pdf · KUTAI EA08A, EA448, ADVR-12, ADVR-2200M, ADVR-08 Caterpillar VR6 ...

___________________________________________________________________________________________ 4 IVT-1260 & IVT-2460

SECTION 4 : AUXILIARY BOOST POWER STARTING PROCEDURE Without the IVT, when a heavy load is placed on a generator, its output voltage drops, as it tries to start large pumps or motors, etc.) The load will, momentarily, appear to have a short circuit to the generator, zapping the power to the AVR and excitation circuits, and the motors fail to start. With the IVT, however, as soon as the voltage drops between 10% and 19%, the ITV takes over, using the battery to immediately power the voltage regulator and the exciting system. Finally, when the IVT output times out (Time-ON setting), the auxiliary boost stops; the regulator returns to normal shunt operation; and, battery power is no longer needed. See the Auxiliary Power start process in Diagram 2 :

When the generator’s load is within 100% of its rated power, its output voltage should be within 10%. However, to avoid the IVT starting frequently and consuming battery power, the Droop setting trigger voltage should be set higher than 10%. At higher than 10% Droop, when the load exceeds (overload) the rated power of the generator (for example, when starting a motor), the sensing voltage drops instantaneously to the Droop setting (10% to 19 %) and the ITV starts within 10ms, instantly delivering power to the AVR and excitation system. When the ITV times out when reaching the Time-ON setting of 15 to 60 seconds, the power from the ITV slowly turns off to avoid unstable voltage output from the generator.

Time

TimeHibernate Standby Power Output Standby

SensingVoltage

Consumption

Sensing Voltage

Droop % (10-19%) levelRated Sensinfg Voltage Droop%

Power Output

Time-ON Setting (15-60 Seconds)

Time

< 1.0W< 0.5W

Shut-Down Generator Running Shut-Down

Hibernate

OutputVoltage

Figure 2! Power Initiation Process

Page 6: IVT-1260 , IVT-2460 ma e - Setecom S.A.setecom.com/wp-content/uploads/2015/09/ivt1260ivt2460-manual-en.pdf · KUTAI EA08A, EA448, ADVR-12, ADVR-2200M, ADVR-08 Caterpillar VR6 ...

___________________________________________________________________________________________ IVT-1260 & IVT-2460 5

SECTION 5 : WIRING CONNECTIONS

G

+

S2 S1 OU

T2

OU

T1

B +B

Fuse

A2

A1

S1

VR

VR

S2

S3

UF UFRO DIPSTAB DROOP TRIM

Z2 F-F+X1 X2Z1E2

E1

VOLT

EA08A

Time

Test

Output

Ready

Test

Batt-Volt

OVLD

ON

Droop%

IVT

Figure 3! IVT-1260 / IVT-2460 & EA08A Wiring Connection

+

S2 S1 OU

T2

OU

T1

B +B

Fuse

G

F+ 30 28F-

ADVR-12

222426 20

9 7 6a8 55a6 4 G3 2

Time

Test

Output

Ready

Test

Batt-Volt

OVLD

ON

Droop%

IVT

Figure 4! IVT-1260 / IVT-2460 & ADVR-12 Wiring Connection

Page 7: IVT-1260 , IVT-2460 ma e - Setecom S.A.setecom.com/wp-content/uploads/2015/09/ivt1260ivt2460-manual-en.pdf · KUTAI EA08A, EA448, ADVR-12, ADVR-2200M, ADVR-08 Caterpillar VR6 ...

___________________________________________________________________________________________ 6 IVT-1260 & IVT-2460

G

+

S2 S1 OUT2

OUT1

B +B

Fuse

EA448

Z2 E-E+X1 X2Z1 0V

60Hz

50Hz

S2

S1

VR

VR

3ph in

Time

Test

Output

Ready

Test

Batt-Volt

OVLD

ON

Droop%

IVT

Figure 5! IVT-1260 / IVT-2460 & EA448 Wiring Connection

+

OU

T1

OU

T2

+

B B

IVT

S2 S1

E2

SR

N

TCT.

Fuse

E1

Exciter

Stator Wires

Generator

P1E3 P2 F+ F-

A2

A1

VR2

VR1

Set the DIP SW Correctly

P4

P3

C2

C1

Shunt with IVT wiring diagram

Time

Test

Output

Ready

Test

Batt-Volt

OVLD

ON

Droop%

ADVR-2200M

ON ON

Figure 6! IVT-1260 / IVT-2460 & ADVR-2200M Wiring Connection

ATTENTION 1. All Sensing AC Voltages should be read as average voltage. 2. IVT-1260 / IVT-2460 highest auxiliary output power is 500 VA. 3. IVT-1260 / IVT-2460 can combine with an auxiliary power AVR.

Ɉ Use only the original protection fuse for replacement. Ɉ Appearance and specifications of products are subject to change for improvement without prior notice.