Isolating switching amplifier 2-channel IM1-22EX … · Isolating switching amplifier 2-channel...
Transcript of Isolating switching amplifier 2-channel IM1-22EX … · Isolating switching amplifier 2-channel...
Isolating switching amplifier2-channelIM1-22EX-R/24VDC
The 2-channel isolating switching amplifierIM1-22EX-R/24VDC is equipped with intrinsi-cally safe input circuits.
Sensors according to EN 60947-5-6 (NA-MUR) can be connected to the device or po-tential-free contactors.
The output circuits feature 2 relays, each withone NO contact.
Six front panel switches are available to setthe output mode separately for each channel(NO/NC mode), as well as to enable/disablewire-break (WB) and short-circuit (SC) moni-toring separately.
When using mechanical contacts, wire-breakand short-circuit monitoring must be switchedoff or the contact must be wired with resistors(II) (see circuit diagram).
The Pwr LED lights green to indicate oper-ational readiness. The 2-color LEDs 1 and2 below light yellow to indicate the switch-ing status of the corresponding output. In theevent of an input circuit error, the associated2-color LED turns red, provided the input cir-cuit monitoring function is activated. There-upon the corresponding output relay dropsout.
■ ATEX, FM
■ Installation in zone 2
■ Adjustable output mode (NO/NC)
■ Input circuits monitored for wire-break/short-circuit (ON/OFF switchable)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Isolating switching amplifier2-channelIM1-22EX-R/24VDC
Type code IM1-22EX-R/24VDCIdent no. 7541210
Flammability class acc. to UL 94 V-0
Nominal voltage 24 VDCOperating voltage range 10…30 VDCPower loss, typical ð 0.99 W
NAMUR EN 60947-5-6No-load voltage 8 VDCShort-circuit current 8 mAInput resistance 1 kòCable resistance ð 50 òSwitch-on threshold: 1.55 mASwitch-off threshold: 1.75 mAWire breakage threshold ð 0.1 mAShort-circuit threshold ï 6 mA
Output circuits (digital) 2 x relays (NO)Relay switching voltage ð 250 VAC/120 VDCSwitching current per output ð 2 ASwitching capacity per output ð 500 VA/60 WSwitching frequency ð 10 HzContact quality AgNi, 3µ Au
Ex approval acc. to conformity certificate PTB 00 ATEX 2033Application area II (1) G, II (1) DProtection type [Ex ia Ga] IIC; [Ex ia Da] IIICMax. values: terminal connection 1…6Max.output voltage Uo ð 9.6 VMax. output current Io ð 21.4 mAMax. output power Po ð 26 mWCharacteristic linearInternal inductance/capacitance Li/Ci Ci negligibly small, Li negligibly smallExternal inductance/capacitance Lo/Co Ex ia IIC IIIC
Lo [mH] 1 5 1 5Co [µF](2 Klem-men)
1,1 0,84 6,2 4,4
Co [µF](3 Klem-men odermehr
1,1 0,8 6,2 4,3
MTTF 400 years acc. to SN 29500 (Ed. 99) 40 °C
State/ Fault 2 x yellow / red
Mechanical DataProtection class IP20Storage temperature -40…+80°CRelative humidity ð 95 %Dimensions 104 x 18 x 110 mmWeight 145 gMounting instruction For mounting on DIN rail or mounting panelHousing material polycarbonate/ABSElectrical connection 4 x 3-pole removable terminal blocks, reverse polari-
ty protected, screw connectionTerminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Tightening torque 0.5 Nm
Dimensions
Output relay – Electrical lifetime
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Isolating switching amplifier2-channelIM1-22EX-R/24VDC
Accessories
Type code Ident no. Description Dimension drawing
IM-CC-3X2BU/2BK 6900475 Cage clamp terminals for IM modules ( Ex-devices with 18mm overall width); includes: 2 pcs. 3-pin blue terminals and 2pcs. 3-pin black terminals.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Isolating switching amplifier2-channelIM1-22EX-R/K51
The 2-channel isolating switching amplifierIM1-22EX-R/K51 is equipped with intrinsicallysafe input circuits.
Sensors according to EN 60947-5-6 (NAMUR)or potential-free contact transmitters can beconnected to the device.
The output circuits feature 2 relays, each withone NO contact.
You can set each channel separately to work/closed current, i.e. NO/NC mode and multiplysignals via 3 switches at the front. The switch-ing state of channel 1 is thereby transmitted tothe outputs 1 and 2. You can also set the out-put mode separately for each channel.
The Pwr LED lights green to indicate oper-ational readiness. The 2-color LEDs 1 and2 below light yellow to indicate the outputswitching status. In the event of an input cir-cuit error, the associated 2-color LED turnsred, provided the input circuit monitoring func-tion is activated. Thereupon the correspon-dent output relay drops out.
■ ATEX, IECEx, CSA, FM, UL, NEPSI,-KOSHA, GOST
■ Installation in zone 2
■ 2 relay outputs (NO)
■ Adjustable current flow (NO/NC)
■ Input circuits monitored for wire-break/short-circuit (ON/OFF switchable)
■ Test voltage 4.0 kV
■ Complete galvanic isolation
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Isolating switching amplifier2-channelIM1-22EX-R/K51
Type code IM1-22EX-R/K51Ident no. 7541238
Flammability class acc. to UL 94 V-0
Nominal voltage Universal voltage supply unitOperating voltage 20…250 VACFrequency 40…70 HzOperating voltage range 20…125 VDCPower consumption ð 3 W
NAMUR EN 60947-5-6No-load voltage 8.2 VDCShort-circuit current 8.2 mAInput resistance 1 kòCable resistance ð 50 òSwitch-on threshold: 1.55 mASwitch-off threshold: 1.75 mAWire breakage threshold ð 0.1 mAShort-circuit threshold ï 6 mA
Output circuits (digital) 2 x relays (NO)Relay switching voltage ð 250 VAC/120 VDCSwitching current per output ð 2 ASwitching capacity per output ð 500 VA/60 WSwitching frequency ð 10 HzContact quality AgNi, 3µ Au
Galvanic isolationTest voltage 4.0 kV
Ex approval acc. to conformity certificate TÜV 04 ATEX 2553Application area II (1) G, II (1) DProtection type [Ex ia Ga] IIC; [Ex ia Da] IIICMax. values: terminal connection: 1+4 / 2+5Max.output voltage Uo ð 9.6 VMax. output current Io ð 11 mAMax. output power Po ð 26 mWCharacteristic linearInternal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly smallExternal inductance/capacitance Lo/Co Ex ia IIC IIB
Lo[mH]
1 5 10 2 10 20
Co[µF]
1,1 0,83 0,74 5,2 3,8 3,4
Ex approval acc. to conformity certificate TÜV 06 ATEX 552968 XApplication area II 3 GProtection type Ex nA nC [ic Gc] IIC/IIB T4 GcMax. values: terminal connection: 1+4 / 2+5Max.output voltage Uo ð 9.6 VMax. output current Io ð 11 mAMax. output power Po ð 26 mWCharacteristic linearInternal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly smallExternal inductance/capacitance Lo/Co Ex ic IIC IIB
Lo[mH]
1 5 10 1 5 10
Co[µF]
1.9 1.4 1.2 11 7.5 6.6
MTTF 400 years acc. to SN 29500 (Ed. 99) 40 °C
IndicationOperational readiness greenSwitching state yellowError indication red
Load curve
Output relay – Electrical lifetime
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Isolating switching amplifier2-channelIM1-22EX-R/K51
Mechanical DataProtection class IP20Ambient temperature -25…+70 °CStorage temperature -40…+80°CRelative humidity ð 95 %Dimensions 104 x 18 x 110 mmWeight 147 gMounting instruction For mounting on DIN rail or mounting panelHousing material polycarbonate/ABSElectrical connection 4 x 3-pole removable terminal blocks, reverse polari-
ty protected, screw connectionTerminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Tightening torque 0.5 Nm
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Isolating switching amplifier2-channelIM1-22EX-R/K51
Accessories
Type code Ident no. Description Dimension drawing
IM-CC-3X2BU/2BK 6900475 Cage clamp terminals for IM modules ( Ex-devices with 18mm overall width); includes: 2 pcs. 3-pin blue terminals and 2pcs. 3-pin black terminals.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Isolating switching amplifier2-channelIM1-22EX-R
The 2-channel isolating switching amplifierIM1-22EX-R is equipped with an intrinsicallysafe input circuit.
Sensors according to EN 60947-5-6 (NA-MUR) can be connected to the device or po-tential-free contactors.
The output circuits feature 2 relays, each withone NO contact.
Six front panel switches are available to setthe output mode separately for each channel(NO/NC mode), as well as to enable/disablewire-break (WB) and short-circuit (SC) moni-toring separately.
When using mechanical contacts, wire-breakand short-circuit monitoring must be switchedoff or the contact must be wired with resistors(II) (see circuit diagram).
The Pwr LED lights green to indicate oper-ational readiness. The 2-color LEDs 1 and2 below light yellow to indicate the outputswitching status. In the event of an input cir-cuit error, the associated 2-color LED turnsred, provided the input circuit monitoring func-tion is activated. Thereupon the correspon-dent output relay drops out.
■ ATEX, IECEx, CSA, FM, UL, NEPSI,-KOSHA, GOST
■ Installation in zone 2
■ 2 relay outputs (NO)
■ Adjustable current flow (NO/NC)
■ Input circuits monitored for wire-break/short-circuit (ON/OFF switchable)
■ Complete galvanic isolation
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Isolating switching amplifier2-channelIM1-22EX-R
Type code IM1-22EX-RIdent no. 7541231
Flammability class acc. to UL 94 V-0
Nominal voltage Universal voltage supply unitOperating voltage 20…250 VACFrequency 40…70 HzOperating voltage range 20…125 VDCPower consumption ð 3 WPower loss, typical ð 0.98 W
NAMUR EN 60947-5-6No-load voltage 8.2 VDCShort-circuit current 8.2 mAInput resistance 1 kòCable resistance ð 50 òSwitch-on threshold: 1.55 mASwitch-off threshold: 1.75 mAWire breakage threshold ð 0.1 mAShort-circuit threshold ï 6 mA
Output circuits (digital) 2 x relays (NO)Relay switching voltage ð 250 VAC/120 VDCSwitching current per output ð 2 ASwitching capacity per output ð 500 VA/60 WSwitching frequency ð 10 HzContact quality AgNi, 3µ Au
Galvanic isolationTest voltage 2.5 kV
Ex approval acc. to conformity certificate TÜV 04 ATEX 2553Application area II (1) G, II (1) DProtection type [Ex ia Ga] IIC; [Ex ia Da] IIICMax. values: terminal connection: 1+4 / 2+5Max.output voltage Uo ð 9.6 VMax. output current Io ð 11 mAMax. output power Po ð 26 mWCharacteristic linearRated voltage 250 VInternal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly smallExternal inductance/capacitance Lo/Co Ex ia IIC IIB
Lo[mH]
1 5 10 2 10 20
Co[µF]
1,1 0,83 0,74 5,2 3,8 3,4
Ex approval acc. to conformity certificate TÜV 06 ATEX 552968 XApplication area II 3 GProtection type Ex nA nC [ic Gc] IIC/IIB T4 GcMax. values: terminal connection: 1+4 / 2+5Max.output voltage Uo ð 9.6 VMax. output current Io ð 11 mAMax. output power Po ð 26 mWCharacteristic linearInternal inductance/capacitance Li/Ci Li = 65 µH, Ci negligibly smallExternal inductance/capacitance Lo/Co Ex ic IIC IIB
Lo[mH]
1 5 10 1 5 10
Co[µF]
1.9 1.4 1.2 11 7.5 6.6
Approval SIL 2 acc. to EXIDA FMEDAMTTF 400 years acc. to SN 29500 (Ed. 99) 40 °C
Dimensions
Load curve
Output relay – Electrical lifetime
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Isolating switching amplifier2-channelIM1-22EX-R
IndicationOperational readiness greenSwitching state yellowError indication red
Mechanical DataProtection class IP20Ambient temperature -25…+70 °CStorage temperature -40…+80°CRelative humidity ð 95 %Dimensions 104 x 18 x 110 mmWeight 154 gMounting instruction For mounting on DIN rail or mounting panelHousing material polycarbonate/ABSElectrical connection 4 x 3-pole removable terminal blocks, reverse polari-
ty protected, screw connectionTerminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Tightening torque 0.5 Nm
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Isolating switching amplifier2-channelIM1-22EX-R
Accessories
Type code Ident no. Description Dimension drawing
IM-CC-3X2BU/2BK 6900475 Cage clamp terminals for IM modules ( Ex-devices with 18mm overall width); includes: 2 pcs. 3-pin blue terminals and 2pcs. 3-pin black terminals.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Isolating switching amplifier2-channelIM1-22EX-R/230VAC
The 2-channel isolating switching amplifierIM1-22EX-R/230VAC is equipped with intrinsi-cally safe input circuits.
Sensors according to EN 60947-5-6 (NAMUR)or potential-free contact makers can be con-nected to the device.
The output circuits feature 2 relays, each withone NO contact.
Six front panel switches are available to setthe output mode separately for each channel(NO/NC mode), as well as to enable/disablewire-break (WB) and short-circuit (SC) moni-toring separately.
When using mechanical contacts, wire-breakand short-circuit monitoring must be switchedoff or the contacts must be wired to resistors(II) (see circuit diagram).
The Pwr LED lights green to indicate opera-tional readiness. The 2-color LEDs 1 and 2below light yellow to indicate the switchingstatus of the corresponding output. The sameLEDs turn red in the event of an input circuiterror, provided the input circuit monitoringfunction is switched on. Thereupon the asso-ciated output relay drops out.
■ ATEX
■ Installation in zone 2
■ Adjustable output mode (NO/NC)
■ Input circuits monitored for wire-break/short-circuit (ON/OFF switchable)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Isolating switching amplifier2-channelIM1-22EX-R/230VAC
Type code IM1-22EX-R/230VACIdent no. 7541211
Flammability class acc. to UL 94 V-0
Nominal voltage 230 VACOperating voltage 196…253 VACFrequency 48…62 HzPower consumption ð 2 VA
NAMUR EN 60947-5-6No-load voltage 8 VDCShort-circuit current 8 mAInput resistance 1 kòCable resistance ð 50 òSwitch-on threshold: 1.55 mASwitch-off threshold: 1.75 mAWire breakage threshold ð 0.1 mAShort-circuit threshold ï 6 mA
Output circuits (digital) 2 x relays (NO)Relay switching voltage ð 250 VAC/120 VDCSwitching current per output ð 2 ASwitching capacity per output ð 500 VA/60 WSwitching frequency ð 10 HzContact quality AgNi, 3µ Au
Ex approval acc. to conformity certificate PTB 00 ATEX 2033Application area II (1) G, II (1) DProtection type [Ex ia Ga] IIC; [Ex ia Da] IIICMax. values: terminal connection 1…6Max.output voltage Uo ð 9.6 VMax. output current Io ð 21.4 mAMax. output power Po ð 26 mWCharacteristic linearInternal inductance/capacitance Li/Ci Ci negligibly small, Li negligibly smallExternal inductance/capacitance Lo/Co Ex ia IIC IIIC
Lo [mH] 1 5 1 5Co [µF](2 Klem-men)
1,1 0,84 6,2 4,4
Co [µF](3 Klem-men odermehr
1,1 0,8 6,2 4,3
MTTF 400 years acc. to SN 29500 (Ed. 99) 40 °C
State/ Fault 2 x yellow / red
Mechanical DataProtection class IP20Ambient temperature -25…+70 °CStorage temperature -40…+80°CRelative humidity ð 95 %Dimensions 104 x 18 x 110 mmWeight 148 gMounting instruction For mounting on DIN rail or mounting panelHousing material polycarbonate/ABSElectrical connection 4 x 3-pole removable terminal blocks, reverse polari-
ty protected, screw connectionTerminal cross-section 1 x 2.5 mm2 / 2 x 1.5 mm2
Tightening torque 0.5 Nm
Output relay – Electrical lifetime
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Isolating switching amplifier2-channelIM1-22EX-R/230VAC
Accessories
Type code Ident no. Description Dimension drawing
IM-CC-3X2BU/2BK 6900475 Cage clamp terminals for IM modules ( Ex-devices with 18mm overall width); includes: 2 pcs. 3-pin blue terminals and 2pcs. 3-pin black terminals.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]