Isolated power systems with WTG

download Isolated power systems with WTG

of 6

Transcript of Isolated power systems with WTG

  • 7/29/2019 Isolated power systems with WTG

    1/6

    599 1

    The control of isolated power systems with

    wind generation

    Cristian Cristea,IEEE Student Member, Joo Peas Lopes,IEEE Senior Member,

    Mircea Eremia,IEEE Senior Member, Lucian Toma,IEEE Student Member

    Abstract The present work investigates the dynamicbehaviour of a mixed system consisting of a wind farm and

    a diesel group supplying a load, under different

    disturbances. In this regard, dynamic models and control

    systems that enable the generation part to support the grid

    are needed. The objective of this work has been also the

    implementation of the diesel group model and its afferent

    control system into Matlab-Simulink and to demonstrate

    their use by evaluating the response in time of the electric

    parameters.

    Index Terms wind generators, diesel engine, systemstability

    I. INTRODUCTION

    ustainable development and environment conservation is

    the reasonability of every human being and therefore

    common actions should be taken to limit the greenhouse

    effect gases exhausted by the fossil fuelled power plants. In

    this support the engineers have to develop technologies to

    exploit, as efficiently as possible, clean energy sources. The

    technology with the greatest impact in this area is the windpower production. However, their operation is a great

    challenge for the responsible operators of the power systems

    since they could introduce several frequency and voltage

    perturbations into the system due to the random variation of

    the wind, which lead to variations of the output power.

    The wind-diesel system is one of the most appropriate

    hybrid systems utilized in weak or isolated power systems. A

    wind-diesel system is very reliable because the diesel group

    acts to correct the power imbalances due to variations in wind

    speed, by always providing appropriate amount of active

    power equal to load power minus the output power of the

    wind farm. The control of the voltage and frequency of a

    weak autonomous wind-diesel system is more challengingthan in large grids [7]. Wind-diesel hybrid systems are

    generally used for remote power supply. These systems are

    often classed as weak grid systems as they have limited

    reactive support. Power fluctuation problems are experienced

    when the wind generator system uses an induction generator

    for energy conversion. This problem could be due also to the

    reactive power drawn by these induction generators from the

    power system, when appropriate reactive sources are not

    incorporated within the wind system. Power quality and

    reliability are also some of the major concerns in a wind-

    diesel hybrid system.

    Cristian Cristea, Mircea Eremia and Lucian Toma are with University

    Politehnica of Bucharest, Power Engineering Faculty, 313 Spl.

    Independenei, 060042 Bucharest, Romania (phone: +40720008956; fax:

    +40214029446; e-mail: [email protected]).

    Joo Peas Lopes is with University of Porto, Department of Electrical

    Engineering, Faculty of Engineering; (e-mail: [email protected]).

    II. MODEL DESCRIPTIONThe dynamic analysis of a wind-diesel hybrid system has

    been performed in this paper to study the effect of some

    disturbances such as random wind variation and network

    disturbances such as short-circuits. Voltage and power

    fluctuations resulting from random wind velocity and short-

    circuits can be a problem for the power system. Remote area

    power supplies are characterized by low inertia, low damping

    and poor reactive power support.

    McGowan [8] developed a dynamic model for a no-storage

    wind-diesel system and validated its components by

    comparing the simulation results with experimental data.

    Uhlen et al. [9, 10] implemented and compared two robust

    controllers of a Norwegian wind-diesel prototype system.

    Papathanassiou and Papadopoulos [11] studied the dynamics

    of a small autonomous wind-diesel system using simplified

    models and classic control theory techniques.

    Diesel Engine

    SynchronousGenerator

    Bus bar20 kV

    WindTurbine

    Load

    SG

    IG

    IG

    IG

    Diesel Group

    Wind Farm

    InductionGenerator

    Transformer

    690V/20kV

    Transformer2.4kV/20kV

    Fig. 1. Wind -diesel power system.

    To simulate an isolated power system we consider a wind

    farm consisting of three wind generators and a diesel group to

    S

  • 7/29/2019 Isolated power systems with WTG

    2/6

    599 2

    maintain the frequency at constant value, which supply a

    consumption area (Fig. 1).

    Normal operation and response to a short-circuit are

    analyzed.

    A. Diesel Group

    The diesel engine model gives a description of the fuel

    consumption rate as a function of speed and mechanical

    power at the output of the engine. The diesel engine is usuallymodelled by a simple first order model relating the fuel

    consumption (fuel rack position) to the engine mechanical

    power. Notice that the transfer function of a reciprocating

    engine involves a small but significant time delay associated

    with the mean time between firing [5].The efficiency of the combustion is the ratio of the

    effective horsepower developed by the engine and available

    on its crankshaft to the heat consumed during the same time,

    that is [4]:

    uB

    i

    Hm

    vzW'

    &

    = (1)

    Incomplete combustion is the main reason for which theindicated efficiency is lower than the ideal efficiency. The

    mean effective pressure of the engine is defined as [4]:ip

    h

    ii

    V

    Wp = (2)

    By solving (1) with respect to and substituting into (2)

    we get:

    iW

    == '1'

    BB

    h

    ui mCm

    vzV

    Hp && (3)

    where Cis the appropriate proportionality constant. Note thatfor normal or stable power system operation is almost

    constant and its value is imposed in order to keep the system

    frequency constant at 50 Hz.

    v

    The mean pressure of mechanical losses is taken in a first

    approximation proportional to the mean piston speed ,

    , where since the piston travels a

    distance of twice the stroke per revolution. Thus, can be

    generally written as valid for any

    engine with appropriate constant C.

    dU

    df Up md SfU 2=

    fp

    = 3Cpf )2( mpf=

    The real mean effective pressure of the engine must be:kp

    (4)fik ppp =

    The real mechanical power of the diesel engine is

    given by the equation:

    DmP

    km

    HkHkhDm pK

    VvpVvpzVP

    === (5)

    The mechanical torque of the engine is given by the

    following relation, in the p.u.:

    kk

    b

    H

    bm

    DmDm pCp

    KT

    V

    T

    PT 2=

    =

    = (6)

    The combustion efficiency of the engine depends on the

    combustion quality as it has been mentioned before. Since

    detailed representation of the fuel combustion model is not the

    scope of this paper, the combustion efficiency is represented

    as a function of the air-fuel ratio

    B

    L

    m

    mas follows:

    =

    B

    L

    m

    mf (7)

    Analytic expressions of

    B

    L

    m

    mf for a specific engine can

    be found in [12]. At normal operation of the engine will beconsidered constant during simulations.

    The block diagram of the diesel engine derived using the

    above considerations is presented in Figure 2. Typical values

    for the parameters of the model can be found in [12].

    Figure 2 illustrates the block diagram of the diesel enginetogether with its governor. This model was implemented in

    Simulink and was attached to an existing model of a

    synchrounous machine (6).

    DmT

    minDmT

    maxDmT

    0

    0

    ref

    0

    -+

    R

    1

    s

    K12

    2

    1 s

    K

    +

    DsH+2

    1

    +

    - cP

    2C

    3C

    DeT

    +

    -

    Engine

    Governor

    1se

    1

    C

    Bm&

    Fig. 2. Diesel group control system.

    B. Wind turbine

    The wind turbine model is based on the steady-state power

    characteristics of the turbine. The stiffness of the drive train is

    infinite and the friction factor and the inertia of the turbine

    must be combined with those of the generator coupled to the

    turbine. The output power of the turbine is given by the

    following equation:

    3

    2),( windpm v

    AcP

    = (8)

    The mechanical power as a function of generator speed,

    for different wind speeds and for blade pitch angle

    mP

    = 0 , is

    illustrated in figure 3. This figure is obtained with the default

    parameters (base wind speed = 12 m/s, maximum power at

    base wind speed = 0.73 p.u. ( = 0.73) and base rotational

    speed = 1.2 p.u.).

    pk

  • 7/29/2019 Isolated power systems with WTG

    3/6

    599 3

    Fig. 3 Turbine power characteristics.

    Figure 4 presents the structure of the wind turbine and the

    induction generator. The stator winding of the wind generator

    is connected directly to the grid and the rotor is driven by the

    wind turbine. The wind energy is converted by the wind

    turbine into electrical power with the help of the induction

    generator and is transmitted to the grid through the statorwinding. The pitch angle is controlled in order to limit the

    generator output power to its nominal value for high wind

    speeds. The reactive power absorbed by the induction

    generator is provided by the grid or by some devices like

    capacitor banks.

    Fig. 4. Structure of wind turbine with induction generator.

    The electrical part of the machine is represented by a

    fourth-order state-space model and the mechanical part by a

    second-order system. All electrical variables and parameters

    are referred to the stator. All stator and rotor quantities are in

    the arbitrary two-axis reference frame (dq frame).

    A Proportional-Integral (PI) controller (Fig. 5) is used to

    control the blade pitch angle in order to limit the electric

    output power to the nominal mechanical power. The pitch

    angle is kept constant at zero degree when the measured

    electric output power is under its nominal value. When itincreases above its nominal value the PI controller increases

    the pitch angle to bring back the measured power to its

    nominal value.

    +

    -

    Pitch angle max.

    Pel Pitch angleController (PI)

    Pitch angle

    0Pmec

    Fig. 5 Pitch angle controller

    III. MODELING IN SIMULINK

    The diesel group has an important role in this work since its

    responsibility is to regulate the frequency in the system. The

    components of the block diagram of the diesel group

    implemented in Simulink are shown in Figure 6. The diesel

    group consists of three major components: the synchronous

    generator, the diesel engine together with the governor and the

    automatic voltage regulator (AVR).

    The models of the synchronous machine and the automaticvoltage regulator (exciter) used in this work has been chosen

    from the preset models available in SimPowerSystems library.

    These models are in accordance with IEEE recommendations.

    Fig. 6. The Simulink model of the diesel group.

    Asynchronous generators are frequently used to convert the

    mechanical force into electrical energy. The implementation in

    Simulink/Matlab of the induction generator and wind turbine

    with the pitch control can be seen in Figure 7.

    Fig. 7. Implementation of the induction generator and wind turbine.

    Fig. 8. Representation in Simulink of the power system.

  • 7/29/2019 Isolated power systems with WTG

    4/6

    599 4

    The input of the wind turbine and controller block are the

    wind speed (m/s) and the speed (p.u.), while the outputs are

    the mechanical power (p.u.) and the pitch angle (degrees).

    IV. RESULTS

    As mentioned before, the isolated system consists of a wind

    farm, a diesel generator and a load. The wind farm consists of

    three wind generators. They are connected to a common 20

    kV busbar via a step-up transformer boosting the voltage from690 V. A diesel generator is connected to same 20 kV busbar,

    through a 2.4kV/20kV, to correct the variations in wind power

    generation. The diesel generator is provided with speed and

    voltage control capabilities. The diesel group has an installed

    power of 15 MW, the load is 7 MW and the wind generators

    are of 1.5 MW each.

    Two disturbances are considered is our first scenario. After

    30 seconds from the starting of simulations, the connection of

    a new wind turbine is considered, then after another 40

    seconds, time in which all parameters stabilizes, a symmetrical

    three-phase-to-ground fault occurs at one of the three wind

    turbine.

    Activepower[p.u.]

    0 10 20 30 40 50 60 70 80 90-0.5

    -0.25

    0

    0.25

    0.5

    0.75

    1

    1.25

    Time (s)

    a.

    MechanicalPower[p.u.]

    0 10 20 30 40 50 60 70 80 900

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    Time (s)

    b.

    Frequency[p.u.]

    0 10 20 30 40 50 60 70 80 900.95

    0.96

    0.97

    0.98

    0.99

    1

    1.01

    1.02

    1.03

    1.04

    Time (s)

    c.

    Fig. 9. Frequency related parameters.

    Figure 9 shows the active power produced by the wind

    farm, the mechanical power of the diesel group and the system

    frequency, and Figure 10 presents the bus voltage on the 20

    kV busbar, the reactive power drawn by the wind farm and the

    field voltage of diesel group, al in the case of the above

    mentioned disturbances.

    Busvoltage[p.u.]

    0 10 20 30 40 50 60 70 80 900

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4

    Time (s)

    a.

    Reactivepower[p.u.]

    10 20 30 40 50 60 70 80 90

    0

    0.3

    0.6

    0.9

    1.2

    1.5

    1.8

    2.1

    Time (s)

    b.

    Fieldvoltage

    [p.u.]

    0 10 20 30 40 50 60 70 80 900

    1

    2

    3

    4

    5

    6

    Time (s)

    c.

    Fig. 10. Voltage related parameters.

    As it can be seen, when some disturbances occurs into the

    system such as connection of additional wind generator or

    occurrence of a short circuit, the wind generator satisfy the

    load voltage ride through capability requirements. High

    currents are flowing during a voltage drop. Due to the highthermal capacity of the induction machine it can be expected

    that these currents will cause no problem. More problematic

    might be the high amount of reactive power required by the

    turbine during voltage disturbances. When the dip lasts to

    long this may lead to voltage collapse for the wind generator

    and therefore it will be disconnected from the network.

    In the second scenario a short-circuit on the 20 kV busbar

    occurring after 60 seconds from the start of simulation is

    considered. The simulation lasts for 120 seconds. The active

    and reactive power is considered for entire wind farm.

  • 7/29/2019 Isolated power systems with WTG

    5/6

    599 5

    Activepower[p.u.]

    20 30 40 50 60 70 80 90 100 110 120

    0

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4

    1.6

    Time (s)

    a.

    Frequency[p.u.]

    0 20 40 60 80 100 120

    0.94

    0.95

    0.96

    0.97

    0.98

    0.99

    1

    1.01

    1.02

    Time (s)

    b.

    MechanicalPower[p.u.]

    0 20 40 60 80 100 1200.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    0.9

    Time (s)

    c.

    Busvoltage[p.u.]

    0 20 40 60 80 100 1200.4

    0.5

    0.6

    0.7

    0.8

    0.9

    1

    1.1

    Time (s)

    d.

    Reactivepower[p.u.]

    20 30 40 50 60 70 80 90 100 110 120

    0.5

    1

    1.5

    2

    2.5

    Time (s)

    e.

    Fig. 11. Response in the case of the second scenario.

    V. CONCLUSIONS

    A diesel group dynamic model and a wind farm have been

    implemented based on individual mathematical models. The

    models used to simulate the wind farm include aerodynamic

    aspects and mechanical details of the turbines, the electrical

    system of the turbine, the cable connections inside the farm

    and the connection to the transformer. These models present a

    powerful tool for the investigation of wind farm dynamics and

    for the development of wind farm controllers.These models developed in Simulink are flexible since they

    can be easily connected one to another forming an equivalent

    electrical network including electrical machines and other

    components, allowing the steady-state and dynamic analysis

    of the power system, which is the purpose of the presented

    methodology.

    The wind farm models can be used to develop wind farm

    control, investigate dynamic interaction within the farm and

    between the wind farm and the diesel group as well as to study

    the wind farm in response to wind speed increase/decrease

    and systems faults.

    Dynamic models of wind farms based on individual

    turbines are large and complicated. The number of statevariables is high and some of the time constants are small,

    leading to a relatively long simulation time. When

    incorporating the dynamic models of wind farms in large

    electric grids, the complexity of the wind farm models has to

    be reduced. Aggregated wind farm models, in which all

    turbines are represented by equivalent models, are more

    suitable for this purpose. However, aggregated models of the

    wind farms based on individual turbines are less accurate and

    therefore less applicable.

    MATLAB/Simulink appears to be less suitable for very

    large models with many (thousand or more) state variables.

    Computation of the steady state becomes high time consuming

    and the simulation time for normal runs increases more thanproportional.

    The malleability of the developed platform was confirmed

    though the analysis of sudden loss of power generated by

    renewable sources (wind power) as well as in scenarios where

    the diesel group is no longer alone in the task of maintaining

    the system frequency control.

    VI. NOMENCLATURE

    - diesel engine efficiency of the combustion;

    uH - diesel engine heat value of the fuel (kJ / kg);

    z - number of cylinders of the Diesel engine (operatingduring a combustion cycle);

    v - diesel engine stroke cycles per second [ ]

    where: K=2 for two-stroke engine or K=4 for a four-

    stroke engine;

    )/( Km =

    iW - diesel engine means effective work (developed by

    one piston during a combustion cycle) (kWh);

    Bm& - diesel engine consumption rate (kg/sec);

    hV - diesel engine one stroke volume [ where

    D: cylinder diameter, S: stroke] (m

    4/2 SD=3);

  • 7/29/2019 Isolated power systems with WTG

    6/6

    599 6

    m - diesel engine speed (rad/sec);

    HV - diesel engine total stroke volume [ ] (mhzV=3);

    bT - base toque for the per-unit transformation;

    mP - mechanical output power of the turbine (W);

    pc - performance coefficient of the turbine;

    - air density (kg/m3);

    A - turbine swept area (m2);

    windv - wind speed (m/s);

    - tip speed ratio of the rotor blade tip speed to wind

    speed;

    - blade pitch angle (deg);

    VII. REFERENCES

    [1] J. Peas Lopes, Integration of Dispersed Generation on Distribution

    NetworksImpact Studies, Proc. of the IEEE Winter Meeting, N.Y.,

    February 2002.

    [2] P. Ledesma, Dynamic Analysis of Power Systems with Wind

    Generation, Ph.D. dissertation, Univ. Carlos III de Madrid, Madrid,

    Spain, 2001.[3] J. G. Slootweg, S. W. H. de Haan, H. Polinder and W. L. Kling,

    Modelling Wind Turbine in Power System Dynamics Simulations,

    2001 IEEE Power Engineering Society Summer Meeting, Vancouver,

    Canada, July 15-19, 2001.

    [4] G.S. Stavrakakis and G.N. Kariniotakis, A General Simulation

    Algorithm for the Accurate Assessment of Isolated Diesel Wind

    Turbine Systems Interaction. Part I: A General Multimachine Power

    System Model, IEEE Transaction on Energy Conversion, vol. 10, pp.

    577-583, 1995

    [5] S. Roy, O.P. Malik. G.S. Hope. "An adaptive control scheme for speed

    control of Diesel driven power plants". IEEE Trans. on Energy

    Conversion, vol. 6. no. 4. December 1991.

    [6] V. Akhmatov, Analysis of Dynamic Behavior of Electric Power System

    with Large Amount of Wind Power, PhD Thesis, April 2003.

    [7] F. Jurado, J. Saez, Neuro-fuzzy control in biomass-based wind-diesel

    power system, 14thPSCC Sevilla, 24 28 June 2002.

    [8] J. G. McGowan, W.Q. Jeffries and J. F. Manwell, Development of

    Dynamic Models for no Storage Wind-Diesel Systems, Proceedings of

    the 17th British Wind Energy Association Conference, UK, pp 111-116,

    July 1995

    [9] K. Uhlen, B. A. Foss and O. B. Gjosaerter, Robust Control and

    Analysis of a Wind-Diesel Hybrid Power Plant, IEEE Trans. Energy

    Conversion, Vol. 9, No. 4, 1994, pp 701-708

    [10] K. Uhlen, Modeling and robust control of autonomous hybrid power

    systems, Ph.D. thesis, The University of Trondheim, 1994.

    [11] S. A. Papathanassiou and M.P. Papadopoulos, dynamic characteristicsof autonomous wind diesel systems, Renewable Energy, vol. 23, no. 2,

    2001, pp 293-311.[12] V. L Maleev, Internal Combustion Engines, McGraw Hill (19th

    edition), 1985.

    Cristian Cristea (MS06) was born in Videle, Romania, in 1982. He received

    the B.Sc (Hons.) degree in electrical engineering from the UniversityPolitehnicaof Bucharest in 2006. He is currently pursuing his Ph.D. degree

    in power systems. His research interests include renewable energy, with

    particular focus on wind energy, and application of FACTS devices in power

    systems.

    J. A. Peas Lopes (M80SM94) received the Electrical Engineering degree

    (five-year course), the Ph.D. degree in electrical engineering, and the

    Aggregation degree from the University of Porto, Porto, Portugal, in 1981,

    1988, and 1996, respectively. He is an Associate Professor of aggregation

    with the Department of Electrical Engineering, Faculty of Engineering,

    University of Porto. In 1989, he joined the staff of Instituto de Engenharia de

    Sistemas e Computadores do Porto (INESC) as a Senior Researcher, and he is

    presently Co-coordinator of the Power Systems Unit of INESC.

    Mircea Eremia (M98, SM02) received the B.S. and Ph.D. degree in

    electrical engineering from the Polytechnic Institute of Bucharest in 1968 and

    1977 respectively. He is currently Professor at the Electric Power Engineering

    Department from University Politehnica of Bucharest. His area of research

    includes transmission and distribution of electrical energy, power system

    stability and FACTS applications in power systems.

    Lucian Toma (MS04) was born in Romania in 1977. He received the

    engineer degree and M.S. in power systems from University Politehnica of

    Bucharest in 2002 and 2003, respectively. He is currently pursuing his Ph.D.degree in power systems. Mr. Toma is employed as assistant professor Electric

    Power Engineering Department from University Politehnica of Bucharest.

    Since 2002 he has been with the where he is now. His main fields of interests

    are electricity markets, transmission and distribution of electrical energy and

    FACTS applications in power systems.