Isolated power systems with WTG
Transcript of Isolated power systems with WTG
-
7/29/2019 Isolated power systems with WTG
1/6
599 1
The control of isolated power systems with
wind generation
Cristian Cristea,IEEE Student Member, Joo Peas Lopes,IEEE Senior Member,
Mircea Eremia,IEEE Senior Member, Lucian Toma,IEEE Student Member
Abstract The present work investigates the dynamicbehaviour of a mixed system consisting of a wind farm and
a diesel group supplying a load, under different
disturbances. In this regard, dynamic models and control
systems that enable the generation part to support the grid
are needed. The objective of this work has been also the
implementation of the diesel group model and its afferent
control system into Matlab-Simulink and to demonstrate
their use by evaluating the response in time of the electric
parameters.
Index Terms wind generators, diesel engine, systemstability
I. INTRODUCTION
ustainable development and environment conservation is
the reasonability of every human being and therefore
common actions should be taken to limit the greenhouse
effect gases exhausted by the fossil fuelled power plants. In
this support the engineers have to develop technologies to
exploit, as efficiently as possible, clean energy sources. The
technology with the greatest impact in this area is the windpower production. However, their operation is a great
challenge for the responsible operators of the power systems
since they could introduce several frequency and voltage
perturbations into the system due to the random variation of
the wind, which lead to variations of the output power.
The wind-diesel system is one of the most appropriate
hybrid systems utilized in weak or isolated power systems. A
wind-diesel system is very reliable because the diesel group
acts to correct the power imbalances due to variations in wind
speed, by always providing appropriate amount of active
power equal to load power minus the output power of the
wind farm. The control of the voltage and frequency of a
weak autonomous wind-diesel system is more challengingthan in large grids [7]. Wind-diesel hybrid systems are
generally used for remote power supply. These systems are
often classed as weak grid systems as they have limited
reactive support. Power fluctuation problems are experienced
when the wind generator system uses an induction generator
for energy conversion. This problem could be due also to the
reactive power drawn by these induction generators from the
power system, when appropriate reactive sources are not
incorporated within the wind system. Power quality and
reliability are also some of the major concerns in a wind-
diesel hybrid system.
Cristian Cristea, Mircea Eremia and Lucian Toma are with University
Politehnica of Bucharest, Power Engineering Faculty, 313 Spl.
Independenei, 060042 Bucharest, Romania (phone: +40720008956; fax:
+40214029446; e-mail: [email protected]).
Joo Peas Lopes is with University of Porto, Department of Electrical
Engineering, Faculty of Engineering; (e-mail: [email protected]).
II. MODEL DESCRIPTIONThe dynamic analysis of a wind-diesel hybrid system has
been performed in this paper to study the effect of some
disturbances such as random wind variation and network
disturbances such as short-circuits. Voltage and power
fluctuations resulting from random wind velocity and short-
circuits can be a problem for the power system. Remote area
power supplies are characterized by low inertia, low damping
and poor reactive power support.
McGowan [8] developed a dynamic model for a no-storage
wind-diesel system and validated its components by
comparing the simulation results with experimental data.
Uhlen et al. [9, 10] implemented and compared two robust
controllers of a Norwegian wind-diesel prototype system.
Papathanassiou and Papadopoulos [11] studied the dynamics
of a small autonomous wind-diesel system using simplified
models and classic control theory techniques.
Diesel Engine
SynchronousGenerator
Bus bar20 kV
WindTurbine
Load
SG
IG
IG
IG
Diesel Group
Wind Farm
InductionGenerator
Transformer
690V/20kV
Transformer2.4kV/20kV
Fig. 1. Wind -diesel power system.
To simulate an isolated power system we consider a wind
farm consisting of three wind generators and a diesel group to
S
-
7/29/2019 Isolated power systems with WTG
2/6
599 2
maintain the frequency at constant value, which supply a
consumption area (Fig. 1).
Normal operation and response to a short-circuit are
analyzed.
A. Diesel Group
The diesel engine model gives a description of the fuel
consumption rate as a function of speed and mechanical
power at the output of the engine. The diesel engine is usuallymodelled by a simple first order model relating the fuel
consumption (fuel rack position) to the engine mechanical
power. Notice that the transfer function of a reciprocating
engine involves a small but significant time delay associated
with the mean time between firing [5].The efficiency of the combustion is the ratio of the
effective horsepower developed by the engine and available
on its crankshaft to the heat consumed during the same time,
that is [4]:
uB
i
Hm
vzW'
&
= (1)
Incomplete combustion is the main reason for which theindicated efficiency is lower than the ideal efficiency. The
mean effective pressure of the engine is defined as [4]:ip
h
ii
V
Wp = (2)
By solving (1) with respect to and substituting into (2)
we get:
iW
== '1'
BB
h
ui mCm
vzV
Hp && (3)
where Cis the appropriate proportionality constant. Note thatfor normal or stable power system operation is almost
constant and its value is imposed in order to keep the system
frequency constant at 50 Hz.
v
The mean pressure of mechanical losses is taken in a first
approximation proportional to the mean piston speed ,
, where since the piston travels a
distance of twice the stroke per revolution. Thus, can be
generally written as valid for any
engine with appropriate constant C.
dU
df Up md SfU 2=
fp
= 3Cpf )2( mpf=
The real mean effective pressure of the engine must be:kp
(4)fik ppp =
The real mechanical power of the diesel engine is
given by the equation:
DmP
km
HkHkhDm pK
VvpVvpzVP
=== (5)
The mechanical torque of the engine is given by the
following relation, in the p.u.:
kk
b
H
bm
DmDm pCp
KT
V
T
PT 2=
=
= (6)
The combustion efficiency of the engine depends on the
combustion quality as it has been mentioned before. Since
detailed representation of the fuel combustion model is not the
scope of this paper, the combustion efficiency is represented
as a function of the air-fuel ratio
B
L
m
mas follows:
=
B
L
m
mf (7)
Analytic expressions of
B
L
m
mf for a specific engine can
be found in [12]. At normal operation of the engine will beconsidered constant during simulations.
The block diagram of the diesel engine derived using the
above considerations is presented in Figure 2. Typical values
for the parameters of the model can be found in [12].
Figure 2 illustrates the block diagram of the diesel enginetogether with its governor. This model was implemented in
Simulink and was attached to an existing model of a
synchrounous machine (6).
DmT
minDmT
maxDmT
0
0
ref
0
-+
R
1
s
K12
2
1 s
K
+
DsH+2
1
+
- cP
2C
3C
DeT
+
-
Engine
Governor
1se
1
C
Bm&
Fig. 2. Diesel group control system.
B. Wind turbine
The wind turbine model is based on the steady-state power
characteristics of the turbine. The stiffness of the drive train is
infinite and the friction factor and the inertia of the turbine
must be combined with those of the generator coupled to the
turbine. The output power of the turbine is given by the
following equation:
3
2),( windpm v
AcP
= (8)
The mechanical power as a function of generator speed,
for different wind speeds and for blade pitch angle
mP
= 0 , is
illustrated in figure 3. This figure is obtained with the default
parameters (base wind speed = 12 m/s, maximum power at
base wind speed = 0.73 p.u. ( = 0.73) and base rotational
speed = 1.2 p.u.).
pk
-
7/29/2019 Isolated power systems with WTG
3/6
599 3
Fig. 3 Turbine power characteristics.
Figure 4 presents the structure of the wind turbine and the
induction generator. The stator winding of the wind generator
is connected directly to the grid and the rotor is driven by the
wind turbine. The wind energy is converted by the wind
turbine into electrical power with the help of the induction
generator and is transmitted to the grid through the statorwinding. The pitch angle is controlled in order to limit the
generator output power to its nominal value for high wind
speeds. The reactive power absorbed by the induction
generator is provided by the grid or by some devices like
capacitor banks.
Fig. 4. Structure of wind turbine with induction generator.
The electrical part of the machine is represented by a
fourth-order state-space model and the mechanical part by a
second-order system. All electrical variables and parameters
are referred to the stator. All stator and rotor quantities are in
the arbitrary two-axis reference frame (dq frame).
A Proportional-Integral (PI) controller (Fig. 5) is used to
control the blade pitch angle in order to limit the electric
output power to the nominal mechanical power. The pitch
angle is kept constant at zero degree when the measured
electric output power is under its nominal value. When itincreases above its nominal value the PI controller increases
the pitch angle to bring back the measured power to its
nominal value.
+
-
Pitch angle max.
Pel Pitch angleController (PI)
Pitch angle
0Pmec
Fig. 5 Pitch angle controller
III. MODELING IN SIMULINK
The diesel group has an important role in this work since its
responsibility is to regulate the frequency in the system. The
components of the block diagram of the diesel group
implemented in Simulink are shown in Figure 6. The diesel
group consists of three major components: the synchronous
generator, the diesel engine together with the governor and the
automatic voltage regulator (AVR).
The models of the synchronous machine and the automaticvoltage regulator (exciter) used in this work has been chosen
from the preset models available in SimPowerSystems library.
These models are in accordance with IEEE recommendations.
Fig. 6. The Simulink model of the diesel group.
Asynchronous generators are frequently used to convert the
mechanical force into electrical energy. The implementation in
Simulink/Matlab of the induction generator and wind turbine
with the pitch control can be seen in Figure 7.
Fig. 7. Implementation of the induction generator and wind turbine.
Fig. 8. Representation in Simulink of the power system.
-
7/29/2019 Isolated power systems with WTG
4/6
599 4
The input of the wind turbine and controller block are the
wind speed (m/s) and the speed (p.u.), while the outputs are
the mechanical power (p.u.) and the pitch angle (degrees).
IV. RESULTS
As mentioned before, the isolated system consists of a wind
farm, a diesel generator and a load. The wind farm consists of
three wind generators. They are connected to a common 20
kV busbar via a step-up transformer boosting the voltage from690 V. A diesel generator is connected to same 20 kV busbar,
through a 2.4kV/20kV, to correct the variations in wind power
generation. The diesel generator is provided with speed and
voltage control capabilities. The diesel group has an installed
power of 15 MW, the load is 7 MW and the wind generators
are of 1.5 MW each.
Two disturbances are considered is our first scenario. After
30 seconds from the starting of simulations, the connection of
a new wind turbine is considered, then after another 40
seconds, time in which all parameters stabilizes, a symmetrical
three-phase-to-ground fault occurs at one of the three wind
turbine.
Activepower[p.u.]
0 10 20 30 40 50 60 70 80 90-0.5
-0.25
0
0.25
0.5
0.75
1
1.25
Time (s)
a.
MechanicalPower[p.u.]
0 10 20 30 40 50 60 70 80 900
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Time (s)
b.
Frequency[p.u.]
0 10 20 30 40 50 60 70 80 900.95
0.96
0.97
0.98
0.99
1
1.01
1.02
1.03
1.04
Time (s)
c.
Fig. 9. Frequency related parameters.
Figure 9 shows the active power produced by the wind
farm, the mechanical power of the diesel group and the system
frequency, and Figure 10 presents the bus voltage on the 20
kV busbar, the reactive power drawn by the wind farm and the
field voltage of diesel group, al in the case of the above
mentioned disturbances.
Busvoltage[p.u.]
0 10 20 30 40 50 60 70 80 900
0.2
0.4
0.6
0.8
1
1.2
1.4
Time (s)
a.
Reactivepower[p.u.]
10 20 30 40 50 60 70 80 90
0
0.3
0.6
0.9
1.2
1.5
1.8
2.1
Time (s)
b.
Fieldvoltage
[p.u.]
0 10 20 30 40 50 60 70 80 900
1
2
3
4
5
6
Time (s)
c.
Fig. 10. Voltage related parameters.
As it can be seen, when some disturbances occurs into the
system such as connection of additional wind generator or
occurrence of a short circuit, the wind generator satisfy the
load voltage ride through capability requirements. High
currents are flowing during a voltage drop. Due to the highthermal capacity of the induction machine it can be expected
that these currents will cause no problem. More problematic
might be the high amount of reactive power required by the
turbine during voltage disturbances. When the dip lasts to
long this may lead to voltage collapse for the wind generator
and therefore it will be disconnected from the network.
In the second scenario a short-circuit on the 20 kV busbar
occurring after 60 seconds from the start of simulation is
considered. The simulation lasts for 120 seconds. The active
and reactive power is considered for entire wind farm.
-
7/29/2019 Isolated power systems with WTG
5/6
599 5
Activepower[p.u.]
20 30 40 50 60 70 80 90 100 110 120
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
Time (s)
a.
Frequency[p.u.]
0 20 40 60 80 100 120
0.94
0.95
0.96
0.97
0.98
0.99
1
1.01
1.02
Time (s)
b.
MechanicalPower[p.u.]
0 20 40 60 80 100 1200.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
Time (s)
c.
Busvoltage[p.u.]
0 20 40 60 80 100 1200.4
0.5
0.6
0.7
0.8
0.9
1
1.1
Time (s)
d.
Reactivepower[p.u.]
20 30 40 50 60 70 80 90 100 110 120
0.5
1
1.5
2
2.5
Time (s)
e.
Fig. 11. Response in the case of the second scenario.
V. CONCLUSIONS
A diesel group dynamic model and a wind farm have been
implemented based on individual mathematical models. The
models used to simulate the wind farm include aerodynamic
aspects and mechanical details of the turbines, the electrical
system of the turbine, the cable connections inside the farm
and the connection to the transformer. These models present a
powerful tool for the investigation of wind farm dynamics and
for the development of wind farm controllers.These models developed in Simulink are flexible since they
can be easily connected one to another forming an equivalent
electrical network including electrical machines and other
components, allowing the steady-state and dynamic analysis
of the power system, which is the purpose of the presented
methodology.
The wind farm models can be used to develop wind farm
control, investigate dynamic interaction within the farm and
between the wind farm and the diesel group as well as to study
the wind farm in response to wind speed increase/decrease
and systems faults.
Dynamic models of wind farms based on individual
turbines are large and complicated. The number of statevariables is high and some of the time constants are small,
leading to a relatively long simulation time. When
incorporating the dynamic models of wind farms in large
electric grids, the complexity of the wind farm models has to
be reduced. Aggregated wind farm models, in which all
turbines are represented by equivalent models, are more
suitable for this purpose. However, aggregated models of the
wind farms based on individual turbines are less accurate and
therefore less applicable.
MATLAB/Simulink appears to be less suitable for very
large models with many (thousand or more) state variables.
Computation of the steady state becomes high time consuming
and the simulation time for normal runs increases more thanproportional.
The malleability of the developed platform was confirmed
though the analysis of sudden loss of power generated by
renewable sources (wind power) as well as in scenarios where
the diesel group is no longer alone in the task of maintaining
the system frequency control.
VI. NOMENCLATURE
- diesel engine efficiency of the combustion;
uH - diesel engine heat value of the fuel (kJ / kg);
z - number of cylinders of the Diesel engine (operatingduring a combustion cycle);
v - diesel engine stroke cycles per second [ ]
where: K=2 for two-stroke engine or K=4 for a four-
stroke engine;
)/( Km =
iW - diesel engine means effective work (developed by
one piston during a combustion cycle) (kWh);
Bm& - diesel engine consumption rate (kg/sec);
hV - diesel engine one stroke volume [ where
D: cylinder diameter, S: stroke] (m
4/2 SD=3);
-
7/29/2019 Isolated power systems with WTG
6/6
599 6
m - diesel engine speed (rad/sec);
HV - diesel engine total stroke volume [ ] (mhzV=3);
bT - base toque for the per-unit transformation;
mP - mechanical output power of the turbine (W);
pc - performance coefficient of the turbine;
- air density (kg/m3);
A - turbine swept area (m2);
windv - wind speed (m/s);
- tip speed ratio of the rotor blade tip speed to wind
speed;
- blade pitch angle (deg);
VII. REFERENCES
[1] J. Peas Lopes, Integration of Dispersed Generation on Distribution
NetworksImpact Studies, Proc. of the IEEE Winter Meeting, N.Y.,
February 2002.
[2] P. Ledesma, Dynamic Analysis of Power Systems with Wind
Generation, Ph.D. dissertation, Univ. Carlos III de Madrid, Madrid,
Spain, 2001.[3] J. G. Slootweg, S. W. H. de Haan, H. Polinder and W. L. Kling,
Modelling Wind Turbine in Power System Dynamics Simulations,
2001 IEEE Power Engineering Society Summer Meeting, Vancouver,
Canada, July 15-19, 2001.
[4] G.S. Stavrakakis and G.N. Kariniotakis, A General Simulation
Algorithm for the Accurate Assessment of Isolated Diesel Wind
Turbine Systems Interaction. Part I: A General Multimachine Power
System Model, IEEE Transaction on Energy Conversion, vol. 10, pp.
577-583, 1995
[5] S. Roy, O.P. Malik. G.S. Hope. "An adaptive control scheme for speed
control of Diesel driven power plants". IEEE Trans. on Energy
Conversion, vol. 6. no. 4. December 1991.
[6] V. Akhmatov, Analysis of Dynamic Behavior of Electric Power System
with Large Amount of Wind Power, PhD Thesis, April 2003.
[7] F. Jurado, J. Saez, Neuro-fuzzy control in biomass-based wind-diesel
power system, 14thPSCC Sevilla, 24 28 June 2002.
[8] J. G. McGowan, W.Q. Jeffries and J. F. Manwell, Development of
Dynamic Models for no Storage Wind-Diesel Systems, Proceedings of
the 17th British Wind Energy Association Conference, UK, pp 111-116,
July 1995
[9] K. Uhlen, B. A. Foss and O. B. Gjosaerter, Robust Control and
Analysis of a Wind-Diesel Hybrid Power Plant, IEEE Trans. Energy
Conversion, Vol. 9, No. 4, 1994, pp 701-708
[10] K. Uhlen, Modeling and robust control of autonomous hybrid power
systems, Ph.D. thesis, The University of Trondheim, 1994.
[11] S. A. Papathanassiou and M.P. Papadopoulos, dynamic characteristicsof autonomous wind diesel systems, Renewable Energy, vol. 23, no. 2,
2001, pp 293-311.[12] V. L Maleev, Internal Combustion Engines, McGraw Hill (19th
edition), 1985.
Cristian Cristea (MS06) was born in Videle, Romania, in 1982. He received
the B.Sc (Hons.) degree in electrical engineering from the UniversityPolitehnicaof Bucharest in 2006. He is currently pursuing his Ph.D. degree
in power systems. His research interests include renewable energy, with
particular focus on wind energy, and application of FACTS devices in power
systems.
J. A. Peas Lopes (M80SM94) received the Electrical Engineering degree
(five-year course), the Ph.D. degree in electrical engineering, and the
Aggregation degree from the University of Porto, Porto, Portugal, in 1981,
1988, and 1996, respectively. He is an Associate Professor of aggregation
with the Department of Electrical Engineering, Faculty of Engineering,
University of Porto. In 1989, he joined the staff of Instituto de Engenharia de
Sistemas e Computadores do Porto (INESC) as a Senior Researcher, and he is
presently Co-coordinator of the Power Systems Unit of INESC.
Mircea Eremia (M98, SM02) received the B.S. and Ph.D. degree in
electrical engineering from the Polytechnic Institute of Bucharest in 1968 and
1977 respectively. He is currently Professor at the Electric Power Engineering
Department from University Politehnica of Bucharest. His area of research
includes transmission and distribution of electrical energy, power system
stability and FACTS applications in power systems.
Lucian Toma (MS04) was born in Romania in 1977. He received the
engineer degree and M.S. in power systems from University Politehnica of
Bucharest in 2002 and 2003, respectively. He is currently pursuing his Ph.D.degree in power systems. Mr. Toma is employed as assistant professor Electric
Power Engineering Department from University Politehnica of Bucharest.
Since 2002 he has been with the where he is now. His main fields of interests
are electricity markets, transmission and distribution of electrical energy and
FACTS applications in power systems.