IPGSM-DP Commercial Fire Communicator - Honeywell Power Products

16
I I P P G G S S M M - - D D P P Commercial Fire Communicator Installation and Setup Guide IPGSM-DP Commercial Fire Communicator RADIO TROUBLE LOW BATT AC ON AC LOSS 800-08074 1/11 Rev. A

Transcript of IPGSM-DP Commercial Fire Communicator - Honeywell Power Products

IIPPGGSSMM--DDPP CCoommmmeerrcciiaall FFiirree CCoommmmuunniiccaattoorr

IInnssttaallllaattiioonn aanndd SSeettuupp GGuuiiddee

IPGSM-DP Commercial Fire Communicator

RADIO TROUBLE

LOW BATT

AC ONAC LOSS

800-08074 1/11 Rev. A

Contents General Information .......................................................................................................................1

Package Contents .......................................................................................................................1 Compatible Fire Panels ..............................................................................................................1

Operation .........................................................................................................................................1 Installation ......................................................................................................................................1

UL Compliance............................................................................................................................1 STEP 1 – Activate the SIM and Setup the Customer Account................................................2 STEP 2 – Register the Communications Module with AlarmNet ...........................................2 STEP 3 – Determine the Signal Strength and Select a Location ............................................3 STEP 4 – Mount and Wire .........................................................................................................3 STEP 5 – Program the Communications Module .....................................................................6 STEP 6 – Configure the Fire Panel ...........................................................................................7 STEP 7 – Test the System..........................................................................................................7

IPGSM-DP Trouble Detection Information...................................................................................8 Dialer Capture Module Information ..............................................................................................8 LED Display Information ...............................................................................................................8 PowerBoost1 Module Information..................................................................................................9 iGSM Communications Module Information ..............................................................................10

RF Specifications ......................................................................................................................11 IPGSM-DP Specifications.............................................................................................................11 Wiring Diagram.............................................................................................. Inside of Back Cover

IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide

– 1 –

General Information The IPGSM-DP Commercial Fire Communicator (henceforth referred to as IPGSM-DP) includes everything you need to upgrade a commercial fire system that previously reported by POTS to a system that uses the Internet as its primary reporting path, and uses a GSM cellular reporting path as a backup. In addition, this communicator utilizes a sophisticated power module (PowerBoost1) that monitors and reports AC power loss, low battery, and missing battery conditions.

Package Contents

Red Fire Cabinet and Back Plate Antenna and Mounting Adapter LED Display board Cam Lock with Key PowerBoost1 Mounting Rails (for above) Dialer Capture Module Battery harness Hardware Bag iGSM Communications Module Wall Outlet Box (P/N K14358) Transformer, 18VAC (N8167) 50 ohm cable assembly Ferrite Filter

Compatible Fire Panels

The IPGSM-DP works with Fire Panels that use the Contact ID communication format as described in the SIA DC-05 Standard. After completing the field installation, verify communications with the central station is successful by sending several events. Also, get confirmation that these events were received.

Note: For a fire panel that has more than 9 active partitions, the first 9 partitions are reported to the central station uniquely. Beyond 9 partitions, only the 2nd digit of the partition is reported along with a leading zero (example partition 14 is reported as 04). The installer must inform the central station of this condition.

Operation The IPGSM-DP replaces the fire panel's POTS communications path. When an event occurs, the fire panel goes off-hook to dial the central station. The IPGSM-DP detects the off-hook condition and provides the fire panel with a dial tone. When the fire panel detects the dial tone, it begins dialing the central station. The IPGSM-DP considers the three second period after dialing as the number dialing has been completed. After the dialing is completed, the Dialer Capture Module returns a handshake to the fire panel.

The fire panel then sends the contact ID reports to the IPGSM-DP, which in turn sends a kiss-off after the report is successfully received from the fire panel. Within the IPGSM-DP, the Dialer Capture Module sends the contact ID reports over the ECP bus to the iGSM Communications Module. When all the reports are sent, the fire panel goes on-hook. The IPGSM-DP then transmits the messages to the central station (either over the internet or the GSM network).

Installation UL Compliance

To meet UL864/NFPA, ensure the following:

IPGSM-DP must be installed in accordance with NFPA (National Fire Protection Association) standards 70 and 72.

IPGSM-DP must be mounted in the same room and within 20 feet of the fire panel. The wiring must be routed through conduit.

IPGSM-DP, and all equipment used for the IP connection (such as the router, hub, modem, etc.) shall be listed, must be powered from an un-switched branch circuit, and be provided with appropriate standby power.

IPGSM-DP must use a 7AH battery (not supplied) to provide 24-hour backup capability.

IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide

– 2 –

STEP 1 – Activate the SIM and Setup the Customer Account

The communicator requires a subscriber account (customer account) to be setup with AlarmNet Direct. This is accomplished by registering the communicator's iGSM communications module with AlarmNet. Registering, enables the fire panel to send reports.

To setup the customer account you will need to contact the central monitoring station to get account information, and have access to the AlarmNet Direct website. To access the AlarmNet Direct website visit – https://services.alarmnet.com/AlarmNetDirect

If you do not wish to use the AlarmNet Direct website, you may call AlarmNet to setup the account, just phone 800-222-6525, then select option 1. (Monday–Friday 8:00 am to 9:00 pm, Saturday 9:00 am to 5:30 pm EST)

Have the following information ready:

Primary City ID (two digits), obtained from your monitoring station.

Primary Subscriber ID (four digits), obtained from your monitoring station.

Primary Central Station ID (two digits), obtained from your monitoring station.

Communication Module's MAC ID, and MAC CRC number located on outside of box, and inside of the module.

Note: The IPGSM-DP comes with a SIM (Subscriber Identity Module) that needs to be activated.

1. To activate the SIM, log into the AlarmNet Direct website and choose “SIM Activation/Status”, then enter the required information. Click Activate SIM.

2. Setup the customer account by choosing "Program New Device GSM/I", enter the required information. When complete, click DONE.

STEP 2 – Register the Communications Module with AlarmNet

Registering the module activates the account with AlarmNet and enables the fire system's control panel to send reports. There are three methods that can be used to register the communications module.

Register the module by logging into AlarmNet Direct and choosing “Show Programmed Devices GSM/I”. Search for the account using the Account Information or MAC ID. Under the “Actions” column, use the pulldown menu and choose Register. OR

After the IPGSM-DP is installed and programmed, you can register the module by clicking the Tamper Switch 3 times. OR

After the IPGSM-DP is installed and programmed, you can register the module using the 7720P Programming tool. Simply: Press [Shift ] then press []. Please wait for "Registration SUCCESS" message.

IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide

– 3 –

STEP 3 – Determine the Signal Strength and Select a Location

IMPORTANT - Do Not mount this device outdoors.

RF Exposure Warning - The antenna(s) used for this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must not be collocated or operating in con-junction with any other antenna or transmitter.

When choosing a suitable mounting location, understand that signal strength is very important for proper operation. For most installations using the supplied antenna, mounting the unit as high as practical, and avoiding large metal components provides adequate signal strength for proper operation.

You will use the iGSM Communications Module to determine signal strength in order to find a suitable mounting location.

Note: If the SIM is already activated, the RSSI signal strength indicators will indicate signal strength.

If the SIM has not been activated, the firmware in the communications module enables it to communicate with the cellular network towers (without the SIM being activated) so that signal strength measurements can be determined. In this case, you can display the signal strength by simultaneously pressing the MODE and TAMPER switches.

1. For this procedure you will need a fully charged 12V battery.

2. Attach the Antenna (see illustration on page 5).

3. Temporarily wire the battery's negative [–] terminal to TB1–4 on the iGSM communications module, then wire the battery's plus [+] terminal to TB1–2 on the communications module. Wait about one minute for the module to initialize.

4. Position the assembly near a suitable mounting position and observe the RSSI display.

5. Look for a mounting position that yields at least 3 bars lit solid. Four or five bars are better.

6. Verify the signal strength remains steady for a few minutes, then mark that mounting position. Disconnect the battery.

STEP 4 – Mount and Wire

For UL compliant installations, refer to the topic on UL Compliance in this manual. For Dry/Indoor use only. Unless otherwise specified, use 18AWG. External cabinet wiring may be routed in conduit if desired.

This communicator comes partially assembled with all the components mounted except the Antenna, LED Display board, and PowerBoost1. To protect certain components on the PowerBoost1, it is shipped un-mounted but fully wired.

Note: Refer to the diagram on page 5, and to the Wiring Diagram on the inside of the back cover of this manual for wiring and component identification.

1. Remove knockouts from cabinet to accommodate the power input wires, and wiring to the control panel. Then mount the cabinet securely to the wall using 4 screws or bolts. Use mounting screws or bolts that are suitable for the material being anchored to.

2. Ensure the cabinet door lock is installed.

3 BARS MIN.

GY GGR Y7845i-GSM-025-V0

IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide

– 4 –

3. Install the two plastic mounting rails for the LED Display board. They simply snap into the back plate holes.

4. Connect the LED Display board to its connector, then slide the board into the mounting rails. (Yellow LED and Buzzer are on top.)

5. Carefully remove the packaging material that surrounds the PowerBoost1.

6. Mount the PowerBoost1 on the three unused standoffs. Use the plastic screw (prevents shorting) to secure the upper right corner of the PowerBoost1 and the two metal screws and lock washers to fasten the left side of the circuit board. Ensure the lock washers are located between the circuit board and the head of the two metal screws.

7. Mount the Wall Outlet Box to an un-switched facility power outlet and run a conduit to the cabinet. 8. In this step DO NOT plug the transformer in. Route 16AWG wire from the transformer,

through the conduit. Pass the wires through the Ferrite Filter, then loop the wires back through again making a loop. Connect the wires to the PowerBoost1 AC terminals.

9. Connect and route 16AWG insulated wire from facility power ground (typically a cold water pipe) to the cabinet's ground post. Ensure all ground connections are tight.

10. Connect the Ethernet cable and the Telco 1 and Telco 2 lines. If you choose to use an optional Cabinet Tamper Switch (if the control panel supports it) mount and wire it.

Note: The Ethernet cable, Telco 1, Telco 2 lines, and the optional cabinet Tamper Switch (if used) must be run through conduit.

11. Verify the PowerBoost1 module DIP switches are configured as shown below.

iPG

SM

-CO

M-0

08-V

0

PowerBoost1

1 5

ON

2 3 4

1 5

ON

2 3 4

(Switch handle = white)

12. Ensure the following:

LED Display board is fully seated.

All wiring terminals and connectors are tight.

All wiring has been completed and secured with cable ties.

13. Install the battery (not supplied). Plug the power transformer in, and attach the battery cable.

IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide

– 5 –

IPG

SM

-DP

-001

-V2[

US

Onl

y]TB 1

678

5

1011

9

234

1

FOR EXTERNAL ANTENNA50 OHM MMCX ONLY

PRIMARY POWER: 9 - 16.5 VACCURRENT: 900mA PEAK, 70mA STANDBYBATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP

FCC:XXXXXXXXXX IC: YYYYYYYYYY

RS

SI

M0

M1

GP

RS

IBS

7720P PROGRAMMER PORTNOT FOR TELEPHONE SERVICE USE!

BATTERY

ANTENNAMOUNTINGADAPTER

CONDUIT

WALL OUTLETBOX (K14358)

CABINETDOOR

TO FacilityGround

ANTENNA

NUT,WASHER

TRANSFORMER(N8167)

1 5

ON

2 3 4

FUSE

+

(not supplied)

BATTERY7AH

Dialer Capture Module

Telc

o 1

Telc

o 2

ECP

Tip

2R

ing

2ZN

-EO

LEO

L

ZN+

PWR

GN

DTi

p 1

Rin

g 1

Dat

a O

utD

ata

In12

V In

GN

DD

ata Out

RED

GREEN

iGSM Comm Module

Wiring for Grounds, Power, and RF

IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide

– 6 –

STEP 5 – Program the Communications Module

You must use the 7720P Programming tool to program the IPGSM-DP.

When using the 7720P Programming tool, the values given below are for most installations. Press the [#] key to accept the displayed default value (xxx) or enter the new value and press the [#] key for the next prompt. Use the [Space] key to scroll through a list of options.

1. (no display)

Connect the 7720P.

2. 7720P PROGRAMMER

Press [#].

3. Strt Prog Mode? Y/N

Press [Shift] then [Y], then [#].

4. Program Device? Y/N

Press [Shift] then [Y], then [#].

5. Com Path Choice (IP&GSM)

Press [Space] to scroll choices; IP&GSM, IP, or GSM. At choice, press [#].

6. Primary City ID (??)

Enter number 01-99, then press [#].

7. Primary CS ID (??)

Enter number 01-FE, then press [#].

8. Primary Sub ID (????)

Enter number 0001-9999, then press [#].

Note: If a Com Path Choice of IP&GSM or IP was selected, prompt 9 will appear.

9. Use DHCP? Y/N (Y)

If your router is configured for DHCP, press [Shift] then [Y], then press [#].

Note: If DHCP is not selected (your router is set for a static IP), prompts 10 through 13 will appear.

10. NIC IP Address: 255.255.255.255

Enter choice, then press [#]. Follow the prompts.

11. Subnet Mask: 255.255.255.255

Enter choice, then press [#]. Follow the prompts.

12. Gateway IP Address: 255.255.255.255

Enter choice, then press [#]. Follow the prompts.

13. DNS Serv IP Addr: 255.255.255.255

Enter choice, then press [#]. Follow the prompts.

14. Review? Y/N

Enter choice, then press [#]. Follow the prompts.

15. Create Password? Y/N

Enter choice, then press [#]. Follow the prompts.

16. Exit Prog Mode? Y/N

Press [Shift] then [Y], then press [#].

17. DONE

Note: If an error in programming occurs, set the factory defaults (see next topic) and reprogram the IPGSM-DP.

IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide

– 7 –

To exit the programming mode, press [N] in response to the "Review?" prompt. Then press [Y] to the "Exit Prog Mode?" prompt. Upon exiting, the root file is updated to log the changes made. A message is displayed telling the user that this step is being executed. When complete, the message "DONE" is displayed to indicate the file was successfully uploaded.

Note: If critical configuration changes were made, such as the mode of operation, the communications module will reset to ensure that the programming features are enabled.

If the file is not successfully uploaded, one of the following prompts will be displayed. Follow the steps shown below until the upload is successful.

Display Description What to do

Cannot Upload Try Again? Y/N_

Module is not yet initialized. Wait for RSSI indicator LEDs to be lit. Press [Y].

Failed to Update Root File!

Network problem, or you answered "N" to "Cannot Upload Try Again?" prompt.

Initiate the Force Server Update Command by pressing the [0] key.

Setting Factory Defaults

To reset the programming options to factory-default values, at the "Exit Prog Mode?" prompt press [Shift] plus [ESC]. Note, setting the factory defaults will also erase any password that may have been entered.

Set Default?

Y/N_

Press [Y] to reset factory default values. Press [N] to cancel this function.

Press [Shift] then [Y], then [#]. The Create Password prompt appears, follow the prompts then exit.

STEP 6 – Configure the Fire Panel

1. Ensure the Telco Fault on the panel is enabled. Then choose a setting that is no higher than 90 seconds (or as close to that) as the panel allows.

2. Ensure no more than 1 pause character (usually a comma) is programmed into the dialing string (usually 2 seconds). Note, this is necessary since the Dialer Capture Module waits only 3 seconds after the phone number is dialed. Having more than 3 seconds of pause time will cause it to think the phone number is complete and cause it to generate the high-low tones at an incorrect moment.

STEP 7 – Test the System

1. Close the Wall Outlet Box, then close and lock the cabinet cover.

2. Refer to the fire panel's installation/operation guide the testing procedure.

3. (Notify the monitoring station that a test will be conducted.) Test the system to ensure it is operating.

IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide

– 8 –

IPGSM-DP Trouble Detection Information Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-DP, and Telco 2 is used by the IPGSM-DP to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to report events if there are no faults in the iGSM Communications module.

Fault Condition Indication to Fire Panel

PowerBoost1 fault Telco 2 is cut. iGSM Communications Module fault

Failure of one of the two communications paths.

Telco 2 is cut.

Failure of both communications paths.

Telco 1 and 2 are cut.

Dialer Capture Module buffer is full. Hang up. (Panel will retry, giving the buffer a chance to empty.)

Dialer Capture Module Information

LED Indicator STATUS

RED – Steady ON Messages exist in buffer.

RED – Flashing No messages to be sent. Waiting for messages.

GREEN – Steady ON Normal Indication.

GREEN – Blinks every 2 sec. PowerBoost1 communication problem.

GREEN – Blinks twice every sec. Communication Module connection is lost.

GREEN – Blinks 10 times every sec. PowerBoost1 and Communications Module connection is lost.

iPG

SM

-CO

M-0

04-V

0

Dialer Capture Module

Telc

o 1

Telc

o 2

ECP

Tip

2R

ing

2ZN

-EO

LEO

L

ZN+

PWR

GN

DTi

p 1

Rin

g 1

Dat

a O

utD

ata

In12

V In

GN

D

RED

GREEN

LED Display Information

Panel Status LED Indicator

RADIO TROUBLE Yellow – ON when radio trouble is present.

Buzzer – Upon loss of AC power, this will beep once every 10 seconds.

LOW BATTERY Yellow – ON when battery is low.

Yellow – (not used)

AC LOSS Yellow – ON when no AC is present.

AC ON Green – ON when AC is present.

Note: Telco ports 1 (primary dialer) and 2 (secondary dialer) may be used instead of the terminal board.

Whichever connection method is used, both Telco paths must be connected to the Fire Panel.

iPG

SM

-CO

M-0

06-V

0

Buz

zer

IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide

– 9 –

Note: If a wire pulled out of the LED Board Connector refer to the diagram on right and reinsert wire, ensuring the connector pin is locked in.

PowerBoost1 Module Information

LED Indicator STATUS

AC (green)

AC power available.

ACTIVE (green)

Cyclical flashing – normal communications. Repetition of 3 flashes – loss of communications.

LOW BATT (yellow) Missing or low battery.

TROUBLE (yellow) One or more trouble conditions exist, such as; overload, output supervision, ground fault, or charger failure.

Notes:

If AC power is lost and the battery voltage falls below 10v, the module's output voltage will be turned off. The output power is turned back on when AC power is restored.

You must use the DIP switch settings shown below.

iPGSM-COM-003-V0

TROUBLE LEDINDICATOR

PowerBoost1

1 5

ON

2 3 4

Confiure DIP switchas shown:

AC LEDINDICATOR

ACTIVE LEDINDICATOR

LOW BATT LEDINDICATOR

1 5

ON

2 3 4

(Switch handle = white)

NC

NC

LED Board ConnectorWires

VioletBlackWhiteRed

BrownYellowGray

IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide

– 10 –

iGSM Communications Module Information

TB 1

678

5

1011

9

234

1

PRIMARY POWER: 9 - 16.5 VACCURRENT: 900mA PEAK, 70mA STANDBYBATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP

FCC:XXXXXXXXXX IC: YYYYYYYYYY

RS

SI

M0

M1

GP

RS

IBS

iPG

SM

-CO

M-0

02-V

1

RSSI / Modeandstatus LEDs

ON – Message transmission pending.QUICK PERIODIC BLINK – Normal.FAST BLINK – Message waiting for network ACK.SLOW BLINK – Idle power abnormal.SLOW BLINK – In unison with green LED, registratration in progress.

Ethernet Link/ActivityGREEN

ON – Ethernet Link detected.OFF – No link detected.FAST BLINK – Transmitting/Receiving Data.

Link SpeedGREEN

Network CollisionYELLOW

Note: If all LEDs FAST BLINK in unison with the RSSI LEDs this indicates a Hardware Error.

ON – No contact with network.OFF – Normal.SLOW BLINK – Loss of communication with the Dialer Capture Module (ECP fault).

ON – NOT registered with AlarmNet.OFF – Registered with AlarmNet.FAST BLINK – Download session with Compass in progress.SLOW BLINK – In unison with yellow LED, registration in progress.

ModeSwitch

TamperSwitch

GRN

YEL

RED

ECP

Zone (NOT USED)

4204 (NOT USED)

2 - 4204 (NOT USED)

MODULE'S RECEIVED SIGNAL STRENGTH (RSSI)

When the Mode Switch is NOT depressed, LED 1 will illuminate red.The remaining LEDs indicate RSSI (Received Signal Strength).

MODULE'S OPERATION MODE

When the Mode Switch IS depressed, LED 1 will be OFF. LEDs 2 and 3 indicate the module's communication mode with the Dialer Capture Module.

Mode LED 2 (yellow) LED 3 (yellow)

MODULE'S STATUS

When the Mode Switch IS depressed, LED 1 will be OFF.

LEDs 4, 5, and 6 indicate the module's Status.

FAST BLINK - Module registered, secondsite available, excellent signal strength.

LED 4 (green) LED 5 (green) LED 6 (green)

ON - Connected toInternet.

ON - Module registered, no secondsite available.

ON - GPRS serviceavailable.

OFF - No GPRS serviceavailable

OFF - Module not registered withnetwork carrier.

FAST BLINK - GPRS inuse.

SLOW BLINK - Module registered, secondsite available, and low signal strength.

NORMAL BLINK - Module registered, secondsite available, acceptable signal strength.

OFF - Not connectedto Internet.

7720PProgrammerPort

BLINKING – Network collision detected.OFF – Normal.

ON – 100 MB/S link to Internet.OFF – 10 MB/S link to Internet.

FAST BLINK – No network contact AND loss of communi- cation with the Dialer Capture Module.

OFF

ON

OFF

ON

OFF

OFF

ON

ON

IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide

– 11 –

RF Specifications

Band

Transmission Frequency

(MHz)

Transmit Power (dBm)

Receive Frequency

(MHz)

Receive Sensitivity

(dBm)

Number of

Channels

Channel Spacing

(MHz)

Duplex Separation

(kHz)

GSM 850 824-849 33 869-894 -107 124 200 45

GSM 900 890-915 33 935-960 -107 124 200 45

GSM 1800 1710-1785 30 1805-1880 -106 374 200 95

GSM 1900 1850-1910 30 1930-1990 -105.5 299 200 80

IPGSM-DP Specifications

ITEM SPECIFICATION

Cabinet Dimensions: Width = 12 3/4 inches

Height = 14 7/8 inches

Depth = 3 inches

Transformer: N8167

Primary – 120VAC, 60Hz

Secondary – 18VAC, 50VA

Battery: 12V, 7Ah sealed lead acid type (not supplied)

Use a Honeywell 712BNP, Yuasa NP7-12 or equivalent.

Battery Charging Current: maximum 1A

Supervision: The AC power, backup battery, IP communications, and GSM communications are monitored.

IPGSM-DP Commercial Fire Communicator – Installation and Setup Guide

– 12 –

NOTES

Wiring Diagram The wiring diagram below is depicted for point-to-point electrical connection checks used for troubleshooting or component replacement. It is not intended to show the physical routing of wires. When replacing a wire or component, ensure the wire is routed in the same manner as the original factory wire.

IPG

SM

-DP

-007

-V2

[US

Onl

y]

TB 1

678

5

1011

9

234

1

FOR EXTERNAL ANTENNA50 OHM MMCX ONLY

PRIMARY POWER: 9 - 16.5 VACCURRENT: 900mA PEAK, 70mA STANDBYBATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP

FCC:XXXXXXXXXX IC: YYYYYYYYYY

RS

SI

M0

M1

GP

RS

IBS

7720P PROGRAMMER PORTNOT FOR TELEPHONE SERVICE USE!

RADIOTROUBLE

LOW BATT

AC ON

LED Display

+12V In

FLT Out

ECP OutECP InGND

TAMPERSWITCH

RSSI/MODEINDICATORS

MODE & STATUSSWITCH

INTERNETCONNECTIVITYINDICATORS

iGSM CommModule

AC

ERTH GND

LOWBATT

TROUBLE

ACTI

VEAC

PowerBoost1

DC+

DC-

OUT-DC+

OUT+N/U

DC-OUT-

OUT+RXTX

GND

RED

WHT (LO BATT)

VIO

OU

TP

UT

1O

UT

PU

T 2

N/U

(RADIO TROUBLE)

1 5

ON

2 3 4

Buzzer

(Buzzer)

AC LOSS

(not used)

ANTENNA

GRNYEL

STATUSMESSAGE

FAULT

7720PPROGRAMMERPORT

RED

BLK

YE

L

GR

N

BLK

RE

D

CABINETDOOR

FUSE

GRA

OPTIONAL CABINETTAMPER SWITCH

BLK

+ BATTERY

BATTERY

7AH

CONDUIT

GRA

(AC ON)

To

Fac

ility

Gro

und

(not supplied)

Use a Honeywell 712BNP,Yuasa NP7-12, or equivalent.

To RouterTo Fire PanelTo Fire Panel

YEL

Dialer Capture Module

Telc

o1

ECP

Tip

2R

ing

2ZN

-EO

LEO

L

ZN+

PWR

GN

DTi

p 1

Rin

g 1

YEL

GR

NR

ED BLK

Dat

a O

ut

RED

GREEN

To

Fire

Pan

el M

ain

Dia

ler

To

Fire

Pan

el B

acku

p D

iale

r

Dat

a in

GN

D12

V In

Telc

o2

REDBRN

WHT

VIOBLK

WALL OUTLETBOX (K14358)

TRANSFORMER(N8167)

NOTES All circuits are power limited except the backup battery which is non-power limited. Non-power limited wiring must be separated from the power limited wiring by at least 1/4 inch. If desired, use a Honeywell 955WH Tamper Switch with the 28-2 bracket.

FCC STATEMENT Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

FCC / IC STATEMENT This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference (2) This device must accept any interference received, including interference that may cause undesired operation.

The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment.

DOCUMENTATION AND ONLINE SUPPORT For the latest documentation and online support information, please go to:

http://www.security.honeywell.com/hsc/resources/MyWebTech/

WARRANTY For the latest warranty information, please go to:

http://www.security.honeywell.com/hsc/resources/wa/

Ê800-08074AŠ 800-08074 1/11 Rev. A

2 Corporate Center Drive, Suite 100, P.O. Box 9040, Melville, NY 11747

Copyright 2011 Honeywell International Inc.

www.honeywell.com/security