Modcon was founded in 1972 and has an excellent reputation as an innovative supplier of turnkey on-line analysis, process automation and modern control systems for oil refineries, natural gas, chemical and energy industries worldwide.
Modcon Systems is a key player and recognized leader in: Oil refineries on-line analyzers and process optimization Pipeline SCADA, metering stations, qualitative and quantitative control solutions Environmental control of air pollutions, contaminated soil and waste water Process analyzer shelters and complete analytical laboratories Turn-key pipeline, compressor stations and processing plants EPC projects
Main Products and Services: Petroleum on-line analyzers (NMR, NIR, ASTM,
etc.) Analyzer Houses for oil refineries and petrochemical
industry SCADA and MCS solutions for natural gas pipelines Natural gas analyzer systems and metering stations Continuous emissions monitoring systems
SYSTEMS LTD
LEADERS IN PROCESS ANALYSIS AND CONTROL
Intrinsically Safe Gas Detector
Model «FDG3»
Bayblend OR Aluminium Enclosure Availible
Modcon Systems specializes in performing process control automation, instrumentation and analyzer projects with turn-key delivery, support and training, since 1972. Modcon Systems is a key player in: On-line Process Analyzers and Systems Process Control & Automation SCADA and Industrial Network Solutions Environmental Control Gas Detectors and Air Pollution Analyzers
Modcon Systems - Model FGD3 is a Certified Intrinsically Safe Gas Transmitter / Display for use in industrial gas moni-toring applications. It can be configured to detect a variety of flammable and toxic gases as well as CO2 and Oxygen.
An LCD display and pushbutton operation make the Model FGD3 easy to operate and configure. The unit comes ready
for direct integration with plant PLC or DCS. A plug-in sensor design makes maintenance fast and easy. The FGD is
housed in a rugged, waterproof, and dustproof enclosure that features a tamper-proof cover.
Intrinsically Safe Gas Detectors – F o r t h e D e t e c t i o n o f O x y g e n o r T o x i c G a s e s
M O D E L « F G D 3 »
Features: LCD readout 4 to 20 milliamp output Pushbutton calibration Green flashing 'confidence' LED Integral sensor for cost sensitive applications Intrinsically safe Water and dust proof to IP66 RFI protected Marine version available (cast aluminium enclosure to provide higher RFI immunity where high power portable ra-
dios are used in the close confines of a vessel) Plug-in replaceable sensors
Hazardous Area Certificate Number
BAS 01ATEX2300 II 2 G EEx ia IIC T4 (-20⁰C<Ta<+60⁰C)
Zones 1 & 2
ENV
IRON
MEN
TAL A
NA
LYSIS
SECTION - GAS DETECTORS
4 Modcon Systems International [email protected]
www.modcon.ru
W h a t I s A n I n t r i n s i c a l l y S a f e G a s D e t e c t o r ?
An Intrinsically Safe Gas Detector is one which is intended for use in a potentially explosive atmos-phere where, due to the nature of the environment or the industrial process taking place, there is the risk of an in-cendive spark from electrical apparatus causing an explosion.
These gas detectors are designed so that the energy produced in the event of an electrical fault is insufficient to cause an incendive spark.
An Electrical Safety Barrier Device must be used to connect power and signals between the gas detector and the 'Safe Area' (i.e. the area outside the potentially explosive atmosphere where mains powered equipment exists). This is nec-essary in order to preserve the safety integrity of the installation by limiting the power entering the potentially explo-sive atmosphere to a safe level - refer to the Accessories section for details of suitable barriers.
Examples are the water, pharmaceuticals and chemicals industries.
Modcon Systems offer the following ranges of intrinsically safe gas detectors:-
T y p e F G D 3 S e r i e s
The FGD3 series gas detectors are powered from an intrinsically safe dc power supply and provide an industry stand-ard 4 to 20mA output signal.
They are available for detection of the following common gas types - follow the links below for further information:-
ENV
IRO
NM
ENTA
L A
NA
LYSI
S SECTION - GAS DETECTORS
5 Modcon Systems International [email protected]
www.modcon-systems.com
Nitrogen Dioxide Detector
Ammonia Detector
Sulphur Dioxide Detector
Nitric Oxide Detector
Hydrogen Detector
Hydrogen Chloride Detector
Hydrogen Cyanide Detector
Flammable Infrared Gas Detector
Carbon Dioxide Infrared Detector
Flammable Gas Detector (including Hydrogen) using 'Pellistor' sensor technology.
Oxygen Deficiency Detector
Hydrogen Sulphide Detector
Carbon Monoxide Detector
Chlorine Detector
Description
The FGD 3 Oxygen or Toxic gas detectors use Pellistor, electrochemical or non-dispersive Infrared (NDIR) sensor technology to detect for gases in the atmosphere in potentially explosive atmospheres in Zones 0, 1 and 2. The detec-tors use the industry standard 4-20mA current loop both to power the detector and to convey the gas levels detected to a control unit. This means that under zero gas conditions 4mA is drawn from the supply, and under full scale gas conditions 20mA is drawn from the supply. The current varies linearly for gas levels between zero and full scale. The detector head uses a two-wire connection.
FGD3 model Bayblend® enclosure is the trade name for product line of amorphous, thermoplastic polymer blends
based on polycarbonate (PC) and acrylonitrile butadiene styrene copolymer (ABS) as well as the rubber-modified
polycarbonate (PC) and styrene-acrylonitrile copolymer (SAN) blends. The blend technology employed supplies
products with an attractive combination of mechanical, thermal and rheological properties. Particular mention
should be made of Bayblend®`s high heat resistance (between that of ABS and PC), its high impact and notched im-
pact strength, and its high stiffness and dimensional stability.
The Bayblend® product range comprises:
- Nonreinforced standard grades (T grades)
- Nonreinforced flame-retardant grades (FR grades)
- Mineral-filled grades
- Glass fiber-reinforced T grades
- Special-purpose grades for specific applications
A marine version of the FGD3 is also available. This version is housed in a cast aluminium enclosure to provide higher RFI immunity where high power portable radios are used in the close confines of a vessel. The enclosure is plated and painted in order to withstand the harsh salt spray environment of the marine industry. The digital display is fitted with a sliding stainless steel front cover which remains over the display window when not being viewed thereby maintaining the RFI shielding properties of the enclosure during normal operation. An optional weather guard is available for installations exposed to the atmosphere or contaminants and is also suitable for use in other areas where hosing down takes place. The weather guard reduces the possibility of water or other contaminants entering into the gas sensor thereby improving the overall reliability of the gas detector in harsh environments. The weather guard is attached with tamperproof screws to ensure that it is not inadvertently removed.
Optional Weatherguard (may not be suitable for use with absorbent gases)
ENV
IRON
MEN
TAL A
NA
LYSIS
SECTION - GAS DETECTORS
6 Modcon Systems International [email protected]
www.modcon.ru
Technical Characteristic
Performance
Measurement range
Dependent upon sensor type
Response time
Sensor response times vary according to the sensor type.
Sensor Type Pellistor, electrochemical, non-dispersive Infrared (NDIR)
Sensor MTBF 5 years for NDIR Infrared, temperature compensated, dual element
Gas Types Oxygen \ Toxic
Electrical Specifications
Supply volt-age
7 to 30 volts dc (for 4 to 20 mA signal)
Output Signal
4-20 мА (2-wire connection, current source ) 0mA - open circuit
2mA - fault
4mA - zero gas
20mA - full scale gas
22mA - over-range
Cable loop resistance
Signal - 480 Ohms at nominal 20v Sensor - 41 Ohms at 8.0V DC
Max. Cable Loop
Resistance
Signal - 560 ohms at 24vdc
ENV
IRO
NM
ENTA
L A
NA
LYSI
S SECTION - GAS DETECTORS
7 Modcon Systems International [email protected]
www.modcon-systems.com
Mechanical Specifications
Enclosure Material Bayblend (ABS and Polycarbonate blending)
Optional marine version : This version is housed in a cast Aluminium enclo-sure .
Cable entry 1 x M20 or ½” NPT
Dimensions 122 x 122 x 75 mm
Weights FGD3 (excluding weatherguard) – 660grams
Weatherguard – 225 grams
Hazardous Area Certification
Certificate Number BAS 01ATEX2300, Code II 2G EEx ia IIC
Standards
EN 50014:1997 + Amds 1 & 2
EN 50018:2000
EN 50020:1994
Temperature Code T4 (-20OC<Ta<+60OC)
Zones 1 & 2
Operating Conditions
Operating Temperature - 20 to +40 deg.C
Storage temperature - 20 to +50 ⁰C
Humidity Range Oxygen - 0 to 99% RH non-condensing
Toxic - 15 to 95% RH non-condensing
Operating Pressure Ambient + or - 10%
IP rating Enclosure IP66, Sensor IP65
8 Modcon Systems International [email protected]
www.modcon.ru
ENV
IRON
MEN
TAL A
NA
LYSIS
SECTION - GAS DETECTORS
Gas Formula Stock Number
Maximum Range
Typical Range Setting
Expected Life (in Air)
Resolution Response Time
Oxygen O2 SS401 0 - 25% vol. * 0 - 21% vol. * 2 years 0.05% vol. T95<15 sec
Hydrogen sulfide H2S SS402 0 – 100ppm 0 - 50ppm 2 years 1ppm T90<30 sec
Carbon monoxide CO SS403 0 – 500ppm 0 - 500ppm 2 years 1ppm T90<25 sec
Chlorine CL2 SS404 0 – 50ppm 0 - 20ppm 2 years 0.1ppm T90<30 sec
Nitrogen dioxide NO2 SS405 0 – 20ppm 0 - 20ppm 2 years 0.1ppm T90<25 sec
Ammonia NH3 SS406 0 – 1000ppm 0 - 100ppm 1-2 years 1ppm T90<60 sec
Ozone O3 SS407 0 – 2ppm 0 - 2ppm 2 years 20ppb T90<150 sec
Volatile organic compounds
V.O.C. SS408 0-1000 ppm Detects a range of volatile organic compounds
Sulfur dioxide SO2 SS409 0 – 20ppm 0 - 20ppm 2 years 0.1ppm T90<35 sec
Nitric oxide NO SS410 0 – 250ppm 0 –100ppm 2 years 1ppm T90<20 sec
Hydrogen H2 SS411 0 – 100% LEL
0 – 100% LEL 2 years 1% LEL < 180 sec
Phosphine PH3 0 – 1ppm 0 – 0.5ppm 18 months 1ppb ** T90<30 sec
Hydrogen cyanide HCN 0 – 50ppm 0 – 25ppm 2 years 0.1ppm T90<200 sec
Hydrogen chloride HCL 0 – 50ppm 0 - 20ppm 1 year 0.1ppm T90<120 sec
Typical Sensor Characteris cs
* The oxygen instrument is not designed for hazardous area use in oxygen-enriched atmospheres. Hazardous area applications must be in the range is 0-21%. ** The resolution of the sensor itself is 15ppb.
ENV
IRO
NM
ENTA
L A
NA
LYSI
S SECTION - GAS DETECTORS
9 Modcon Systems International [email protected]
www.modcon-systems.com
Typical MCU Control Unit Oxygen and Toxic Alarm Level Se ngs (Adjustable)
Gas Formula Level 1 Level 2 Level 3 Max. Adjustable FSD
Oxygen O2 19% vol. 23% vol. 25% vol. 25% vol.
Carbon monoxide CO 50ppm 110ppm 200ppm 500ppm
Chlorine CL2 1ppm 1.5ppm 2ppm 20ppm
Nitrogen dioxide NO2 10ppm 15ppm 20ppm 20ppm
Sulfur dioxide SO2 3ppm 5ppm 8ppm 20ppm
Hydrogen chloride HCL 1ppm 1.5ppm 2ppm 20ppm
Ozone O3 1ppm 1.5ppm 2ppm 2ppm
Hydrogen sulfide H2S 10ppm 15ppm 20ppm 50ppm
Ammonia NH3 25ppm 35ppm 50ppm 30ppm
Hydrogen cyanide HCN 5ppm 10ppm 15ppm 25ppm
Hydrogen H2 20% LEL
40% LEL 60% LEL 0-100% LEL
Nitric oxide NO 25ppm 35ppm 50ppm 100ppm
Phosphine PH3 150ppb 200ppb 250ppb 500ppb
I n t r i n s i c a l l y S a f e O u t p u t M o d u l e T y p e « S S 3 5 9 »
* The Intrinsically Safe Output Module shown above provides the necessary interface between a non-intrinsically safe, mains powered system and an FGD3 Infrared Gas Detector. Note that an intrinsically safe earth must be connected to the module to ensure safety.
Inputs 14-28vDC 12-24V
Current Loop Sensor Supply
Temperature -20 - +40°C
Humidity range 0-95% RH non-condensing
Operating pres-sure
Ambient + or – 10%
Internal Re-sistance
Current Loop : 270R ±5%
Source Re-sistance
Sensor Supply : 12.0R ±5%
Intrinsically Safe Outputs
Terminals 1 & 2 3 & 4
Uo 28V 7.5V
Certificate No. Baseefa 03ATEX0590X
Code II (1) G [EEx ia] IIC
Io .112A .66A
Po .8W 1.24W
Zones 1 or 2
Accessories
10 Modcon Systems International [email protected]
www.modcon.ru
ENV
IRON
MEN
TAL A
NA
LYSIS
SECTION - GAS DETECTORS
T E C H N I C A L D A T A S H E E T - S O U N D E R A L A R M « S S 3 6 7 »
ENV
IRO
NM
ENTA
L A
NA
LYSI
S SECTION - GAS DETECTORS
Accessories
11 Modcon Systems International [email protected]
www.modcon-systems.com
Features: 9 SELECTABLE TONES HIGH IMPACT ABS CASE WIDE SUPPLY AND OPERATING TEMPERATURE BRIGHT RED FINISH OPTIONAL LOOP IN / LOOP OUT
ELECTRICAL SPECIFICATION
Operating Voltage 12V/24V
Supply Current 8mA
Audibility 105dB at 1m
Distance 108m
Frequency 700/950Hz
Operating Temp. Range -40°C to +55°C
Mechanical Specification
Overall Height 85mm
Overall Diameter 104mm
Fixing Holes 4mm Holes max
Fixing Diameters 50mm or 60mm
Gland Entry 2 x 20mm knockouts
T E C H N I C A L D A T A S H E E T - V I S U A L A L A R M ( C O L O U R R E D , A M B E R o r G R E E N ) « S S 3 6 9 »
Accessories
Features: EYE CATCHING FLASH RATE, 60FPM IMPACT RESISTANT POLYCARBONATE RANGE WIDE SUPPLY AND OPERATING TEMPERATURE THREE COLOURS AVAILABLE
ELECTRICAL SPECIFICATION
Operating Voltage 20-30Vdc Supply Current 90mA average Power Rating 2.1W Flash Energy Rating 1.0J
Operating Temperature Range -20°C to +55°C
Mechanical Specification
Overall Height 100mm Base Height 48mm Overall Diameter 93mm Fixing Holes 5mm Holes max Fixing Diameters 50mm or 60mm Gland Entry 2 x 20mm knockouts
12 Modcon Systems International [email protected]
www.modcon.ru
ENV
IRON
MEN
TAL A
NA
LYSIS
SECTION - GAS DETECTORS
T E C H N I C A L D A T A S H E E T - V I S U A L / A U D I B L E S T A T U S I N D I C A T I O N P A N -E L « S S 3 6 6 »
ENV
IRO
NM
ENTA
L A
NA
LYSI
S SECTION - GAS DETECTORS
Accessories
13 Modcon Systems International [email protected]
www.modcon-systems.com
Electrical Specification
Operating Voltage 24V D.C.
Supply Current: Red / Yellow Xenon’s
105mA MAX.
Green LED Lamp 40mA MAX.
Sounder 25mA MAX.
Sounder Output level @1m 79-107dB(A)
(Depending on tone) ± 3dB.
Mechanical Specification
Overall dimensions: 480mm Long x 102mm Wide x 130mm Deep.
Weight: Approximately 3.5Kg.
Cable entries 2 off M20 Compression glands. Cable size: 8mm Di-ameter maximum.
Configuration Common negative supply, inde-pendent positive supply to each lamp and the sounder.
Mentor SCM ~ S i n g l e c h a n n e l c o n t r o l u n i t
Features include: Alphanumeric display with back light Built in audible visual alarms Micro-controller based Fully configurable Choice of remote and directly mounted gas detector heads One-man calibration for remote mounted gas detector heads Lockable steel enclosure; water and dust proof to IP66 Password protected Battery back-up 3 alarm outputs
The MCU1 is a single channel, wall mounting, monitoring and control unit for use in a safe area where there is no risk of the presence of potentially explosive gases. It can be used in either of the following ways:-
1. Fitted with an integral CO2 (Infrared), oxygen, or toxic sensor for safe area use only.
2. Connected to a remote CO2 (Infrared), oxygen, or a toxic gas detector head for safe area use only.
3. Fitted with an internal (or external) safety barrier and connected to a remote certified intrinsically safe (Ex ia) flammable, oxygen or toxic gas detector head sited in a hazardous area. (The range of heads includes flammable and CO2 (Infrared) types).
4. Connected to a remote flameproof (Ex d) certified flammable, oxygen or toxic gas detector head sited in a hazardous area.
14 Modcon Systems International [email protected]
www.modcon.ru
ENV
IRON
MEN
TAL A
NA
LYSIS
SECTION - GAS DETECTORS
ENV
IRO
NM
ENTA
L A
NA
LYSI
S SECTION - GAS DETECTORS
15 Modcon Systems International [email protected]
www.modcon-systems.com
Integral S e n s i n g H e a d
Accepts any industrial transducer with voltage output or 4-20mA current output, e.g. gas, pressure, temperature, flow, humidity, fire, smoke.
Inbuilt visual alarms: Green – Healthy Amber – Fault Red – Alarm Inbuilt audible alarm Alphanumeric display Pushbutton facilities for: Dual level alarms Configuration Calibration Menu options Minimum eight hours backup from optional battery. Interface to plant provided by voltage-free DPCO relay contacts for Alarm 1, Alarm 2 and Fault. Two independent switched supplies for external audible and visual alarms. Lockable steel enclosure waterproof and dustproof to IP66. Fitted with pre-prepared gland entries. Water and dust proof to IP66.
Mechanical Specifications
Enclosure Material Bayblend (ABS and Polycarbonate blending)
Optional marine version : This version is housed in a cast Aluminium enclo-sure .
Format
Slim wall mounting cabinet
Dimensions 249mm x 268mm x 200mm
Weights 4 kgs
Operating voltages
110 – 120v AC 50-60Hz
220 – 240v AC 50-60Hz
20 – 28v DC
24 volt common out-puts (open collector)
Output one for external audible alarm (200ma maximum)
Output two for external visual alarm (200ma maximum)
Relays
Relay one operates when Alarm Level 1 is encountered
Relay two operates when Alarm Level 2 is encountered
Relay three operates when a fault condition occurs
LED indicators
Green LED indication of POWER ON
Red LED indication of ALARM CONDITION
Yellow LED indication of FAULT CONDITION
Visual indication unit
Green indication status : healthy
Red indication status : alarm
Yellow indication status : fault / mains fail
The input circuit is designed to accept virtually all sensor configurations available. It can be connected to any sensor with either of the following characteristics:-
Input formats
Current loop 4-20mA, internal or external variable 5-24v (source)
Current loop 4-20mA, internal or external (sink)
3 – wire pellistor
Voltage input
Output formats
4-20mA current source proportional to detected signal
4-20mA current sink proportional to detected signal
0-5v voltage output proportional to detected signal
Universal input/output card with optional isolating barriers
16 Modcon Systems International [email protected]
www.modcon.ru
ENV
IRON
MEN
TAL A
NA
LYSIS
SECTION - GAS DETECTORS
I n t e r n a l S a f e t y B a r r i e r U n i t
ENV
IRO
NM
ENTA
L A
NA
LYSI
S SECTION - GAS DETECTORS
Accessories
17 Modcon Systems International [email protected]
www.modcon-systems.com
For applications where the gas detector head (or other sensor type) is sited in a potentially explosive atmosphere, a safety barrier must be fitted in order to limit the maximum voltage and current under a fault condition (e.g. short cir-cuit) such that an incendive spark cannot be created. Where suitable*, the internal safety barrier shown above may be fitted within the control unit. This can either be fitted at the time of manufacture (where requested) or at a later time if the system is extended by the installation of additional detectors.
* Note that some installations may necessitate the use of external barriers sited at the safe area/hazardous area inter-face - see the accessories page.
LC COMMERCIAL SERIES ~ 1 t o 4 c h a n n e l c o n t r o l u n i t s
FEATURES INCLUDE: LC1 provides 1 monitoring channel LC2 provides 2 monitoring channels LC4 provides 4 monitoring channels Lockable, wall mounting steel enclosure powder coated to RAL7035 IP65 Graphic display simultaneously showing reading for each channel and sensor type Visual indicators for alarm, fault and power Full calibration menu via push buttons on front panel Each channel can accept:
o 2-wire current source 4-20mA o 3-wire power plus current source 4-20mA o 3-wire pellistor systems
and output: o 4-20mA current source proportional to the detected signal o 4-20mA current sink proportional to the detected signal o 0-5V voltage output proportional to the detected signal
2 Alarm relays per channel 1 Common fault relay
24 Modcon Systems International [email protected]
www.modcon.ru
ENV
IRON
MEN
TAL A
NA
LYSIS
SECTION - GAS DETECTORS
ENV
IRO
NM
ENTA
L A
NA
LYSI
S SECTION - GAS DETECTORS
25 Modcon Systems International [email protected]
www.modcon-systems.com
Technical Characteristic
Input Modules
Number of channels 4 max
Signal Inputs 8 Max
4-20mA Current Loop from 24V source.
4-20mA Current Loop sink to 0V.
3-Wire Pellistor Systems.
Analogue Output 8 Max
4-20mA Current source proportional to detected signal.
4-20mA Current sink proportional to detected signal.
1-5V Voltage output proportional to detected signal.
Relays – 18 Max
Contacts
Rating
1 relay assigned to alarm level 1 - channels 1 to 8.
1 relay assigned to alarm level 2 - channels 1 to 8.
1 relay assigned to common alarm level 3.
1 relay assigned to fault condition.
Single Pole Changeover Contacts (voltage free).
5A 240V AC.
Technical Characteristic
Mechanical Specifications
Size 188 x 160 x 106 (LC1), 280 x 219 x 156 (LC2), 390 x 316 x 167(LC4)
Weight 1Kg(LC1),1.9Kg(LC2), 3.8Kg(LC4)
Operating Conditions
Operating Temp -10ºC to +50ºC
Storage Temp -20ºC to +50ºC
Humidity Range 0 to 95% R.H. Non-condensing
Input Voltage 18-28V DC, or 100-240V AC 50/60
Environmental Rating IP65
26 Modcon Systems International [email protected]
www.modcon.ru
ENV
IRON
MEN
TAL A
NA
LYSIS
SECTION - GAS DETECTORS
ENV
IRO
NM
ENTA
L A
NA
LYSI
S SECTION - GAS DETECTORS
27 Modcon Systems International [email protected]
www.modcon-systems.com
LC COMMERCIAL SERIES ~ 8 c h a n n e l c o n t r o l u n i t
FEATURES INCLUDE: Lockable, wall mounting steel enclosure powder coated to RAL7035 IP65 Graphic display simultaneously showing reading for each channel and sensor type Visual indicators for alarm, fault and power Full calibration menu via push buttons on front panel Each channel can accept:
o 2-wire current source 4-20mA o 3-wire power plus current source 4-20mA o 3-wire pellistor systems
and output: o 4-20mA current source proportional to the detected signal o 4-20mA current sink proportional to the detected signal o 0-5V voltage output proportional to the detected signal
2 Alarm relays per channel 1 Common fault relay
Technical Characteristic
User Interface
Display
Keyboard 4 button multifunction keypad
LED Indications Option 1
Red : Indicates alarm condition.
Yellow : Indicates fault condition.
Green : Indicates power ON.
LED Indications Option 2
Green : Indicates power ON
Red : Indicates alarm level 3 condition.
Red : Indicates alarm level 2 condition.
Red : Indicates alarm level 1 condition.
Yellow : Indicates fault condition.
Electrical Specifications
Fuse 1 (AC Input) T1.0A
Fuse 2 (24VDC input) T500mA
Input Modules
Number of channels 8 max
Signal Inputs 8 Max
4-20mA Current Loop from 24V source.
4-20mA Current Loop sink to 0V.
3-Wire Pellistor Systems.
Analogue Output 8 Max
4-20mA Current source proportional to detected signal.
4-20mA Current sink proportional to detected signal.
1-5V Voltage output proportional to detected signal.
Relays – 18 Max
Contacts
Rating
1 relay assigned to alarm level 1 - channels 1 to 8.
1 relay assigned to alarm level 2 - channels 1 to 8.
1 relay assigned to common alarm level 3.
1 relay assigned to fault condition.
Single Pole Changeover Contacts (voltage free).
5A 240V AC.
28 Modcon Systems International [email protected]
www.modcon.ru
ENV
IRON
MEN
TAL A
NA
LYSIS
SECTION - GAS DETECTORS
ENV
IRO
NM
ENTA
L A
NA
LYSI
S SECTION - GAS DETECTORS
29 Modcon Systems International [email protected]
www.modcon-systems.com
Technical Characteristic
Mechanical Specifications
Size 500mm Wide x 300mm High x 80mm Deep
Weight 7.65 kg
Operating Conditions
Operating Temp -10ºC to +50ºC
Storage Temp -20ºC to +50ºC
Humidity Range 0 to 95% R.H. Non-condensing
Input Voltage 18-28V DC, or 100-240V AC 50/60
Environmental Rating IP65
Mentor MCU4 ~ 1 t o 1 6 c h a n n e l c o n t r o l u n i t
Features Large LED backlit full-graphics display of all sixteen channels Data logging and event data logging as standard 4 master alarm relays, 3 channel relays Fully configurable relays Dedicated 24 v DC drivers for audible and visual alarms Full calibration menu via external push buttons 1 – 16 input modules available with optional built in safety barriers Lockable steel enclosure, water and dust proof to IP66 Interchangeable gland plates fitted on upper and lower face Available with optional terminal chamber Built in battery back up
30 Modcon Systems International [email protected]
www.modcon.ru
ENV
IRON
MEN
TAL A
NA
LYSIS
SECTION - GAS DETECTORS
ENV
IRO
NM
ENTA
L A
NA
LYSI
S SECTION - GAS DETECTORS
31 Modcon Systems International [email protected]
www.modcon-systems.com
Technical Characteristic
User Interface
Display
Keyboard 4 button multifunction keypad
LED Indications Option 1
Red : Indicates alarm condition.
Yellow : Indicates fault condition.
Green : Indicates power ON.
LED Indications Option 2
Green : Indicates power ON
Red : Indicates alarm level 3 condition.
Red : Indicates alarm level 2 condition.
Red : Indicates alarm level 1 condition.
Yellow : Indicates fault condition.
Electrical Specifications
Fuse 1 (AC Input) T1.0A
Fuse 2 (24VDC input) T500mA
Input Modules
Number of channels 8 max
Signal Inputs 8 Max
4-20mA Current Loop from 24V source.
4-20mA Current Loop sink to 0V.
3-Wire Pellistor Systems.
Analogue Output 8 Max
4-20mA Current source proportional to detected signal.
4-20mA Current sink proportional to detected signal.
1-5V Voltage output proportional to detected signal.
Relays – 18 Max
Contacts
Rating
1 relay assigned to alarm level 1 - channels 1 to 8.
1 relay assigned to alarm level 2 - channels 1 to 8.
1 relay assigned to common alarm level 3.
1 relay assigned to fault condition.
Single Pole Changeover Contacts (voltage free).
5A 240V AC.
Technical Characteristic
Mechanical Specifications
Size 500mm Wide x 300mm High x 80mm Deep
Weight 7.65 kg
Operating Conditions
Operating Temp -10ºC to +50ºC
Storage Temp -20ºC to +50ºC
Humidity Range 0 to 95% R.H. Non-condensing
Input Voltage 18-28V DC, or 100-240V AC 50/60
Environmental Rating IP65
32 Modcon Systems International [email protected]
www.modcon.ru
ENV
IRON
MEN
TAL A
NA
LYSIS
SECTION - GAS DETECTORS
[email protected] www.modcon.ru
Azerbaijan Heydar Aliyev avenue 74/17 Baku AZ 1033 tel: 99412-4929859 fax: 994-12-4929859
Israel Bornshtein St. South Akko Ind. Park, Acre 24222 tel: 972-4-9553955 fax: 972-4-9553956
Romania Aleea Emil Botta, Nr. 4, BL. M104 Sc. 2, Et. 4, Ap. 56 Sector 3 Bucharest RO-031074 tel: 40-21-3260533 fax: 40-21-3260552
Russia Перовская улица 61/2, стр. 1 Москва 111394 tel: +7 (495) 9891840 fax: +7 (495) 9891840 (9)
USA Broadway Street, Suite #1203, San Francisco, CA 94115 2000
tel: 1-917-5916880 fax: 1-360-2375906
UK St John Street London EC1V 4PY 145-157 tel: 44-207-5043626 fax: 44-207-5043626
Kazahstan 140000 г. Павлодар Ул. Кленовая 2 tel / fax: +7 (7182) 644437
Ukraine г .Харьков tel. +38057 763-14-60 fax +38057 763-00-98