Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055...
Transcript of Instruction manual Harmo PAC ZVWX1017/1022/1032/1041/1055...
0
Imported by: Zwembad BVBA Industrieweg 9 3190 Boortmeerbeek België www.harmopool.eu
Instruction manual – Harmo PAC ZVWX1017/1022/1032/1041/1055/1056/1061
1
Table of content Introduction ................................................................................................................................................... 2
Safety instructions .......................................................................................................................................... 3
Specifications .................................................................................................................................................. 4
Installation ...................................................................................................................................................... 5
Installation items ........................................................................................................................................ 5
Location ...................................................................................................................................................... 5
Installation of the valve .............................................................................................................................. 6
Installation of the pool system ................................................................................................................... 7
Installation of the bypass............................................................................................................................ 7
Electrical wiring .......................................................................................................................................... 8
Start-up procedure ..................................................................................................................................... 8
Condensing ................................................................................................................................................. 8
Guidelines ....................................................................................................................................................... 9
Water chemistry ......................................................................................................................................... 9
Winter-ready .............................................................................................................................................. 9
Spring start-up .......................................................................................................................................... 10
Owner inspection ..................................................................................................................................... 10
Display Controller Operation ........................................................................................................................ 11
The buttons of LED wire controller .......................................................................................................... 11
Activating the heat pump. ...................................................................................................................... 11
Setting the heating/cooling mode ........................................................................................................... 11
Setting the real time ................................................................................................................................. 11
Water temperature setting ..................................................................................................................... 12
Automatic start/stop the heat pump ..................................................................................................... 12
Running data setting ................................................................................................................................. 13
Current status ........................................................................................................................................... 15
Q&A .............................................................................................................................................................. 17
Error code ................................................................................................................................................. 17
Other malfunctions ................................................................................................................................... 18
Maintenance ................................................................................................................................................. 19
2
Introduction
Read the manual carefully before you open or maintain the unit. The manufacturer of this product will not be held responsible for injuries or damage to the unit, as a result of improper installation, debugging or unnecessary maintenance. It is essential that the instructions of this manual are adhered at all times. Qualified personnel must install the unit.
○ A qualified installer, center, personnel or an authorized dealer, can only repair the unit.
○ Maintenance and operation must be carried out according to the recommended time and frequency, as stated in this manual.
○ Use genuine standard spare parts only. Failure to comply with these recommendations will void
warranty.
Characteristics
○ Durable: The heating exchanger is made of PVC & Titanium tube, which can withstand prolonged exposure to swimming pool water.
○ Easy operation: The desired temperature can be easily. Instructions can be found in this manual. ○ Quiet operation: Through the intelligent LCD controller, the desired water temperature can be
set
○ Low cost: The operational cost is very low due to its high performance.
3
Safety instructions ○ Place the heat pump at a safe distance. Never place the pump within a radius of 350cm from the
pool. ○ Your heat pump may be fitted with a RCD safety plug. ○ Put the RDC plug directly and solely into a grounded wall outlet. Never use an extension cord or
similar. ○ Check the voltage on the plug to the power at the socket. Only use a grounded outlet. ○ Always check that the safety plug is working properly to ensure safety. Never remove the safety plug. ○ Place the pump and plug in a dry location. ○ The failure to comply with these instructions could result in serious injuries. Safety test Splash-proof 1. See the wiring diagram in the manual. 2. Plug into the socket. 3. Press the RESET button. The indicator "ON (on)" is highlighted. 4. Press the "TEST" button. The indicator "ON (on) goes out. 5. Press the RESET button for use of the device. Do not use if above test fails
4
Specifications
Product code: ZVWX1017 ZVWX1022 ZVWX1032 ZVWX1041 ZVWX1055 ZVWX1056 ZVWX1061
Product type: MONO MONO MONO Vertical/MONO Vertical/MONO Vertical/TRI Vertical/TRI
COP 27°T air 24°T water 5.5 5.5 5.5 5.5 5.5 5.5 5.5
Minimum outside temperature 5° 5° 5° 5° 5° 5° 5°
Heating Capacity (kW) 27°T air 2 7.0 10.0 13.0 18.0 22.0 22.0 26.0
Nominal power consumption (A) 5,1 7,3 9,5 13,1 16 10,5 12,4
Nominal water flow rate (m³ / h) 3 to 5 5 to 7 6 to 8 8 to 10 10 to 12 10 to 12 11 to 13
Heat exchanger Titanium Titanium Titanium Titanium Titanium Titanium Titanium
Airflow (m³/h) 1800 2100 2300 3200 4500 4500 4500
kW 1.3 1.82 2.36 3.3 4.1 4.1 4.1
Connection (mm) 50 50 50 50 50 50 50
Control panel Digital Digital Digital Digital Digital Digital Digital
Compressor (number) 1 1 1 1 1 1 1
Ventilators 1 1 1 1 1 1 1
dB 54 54 54 55 57 57 57
RPM ventilator 950 950 950 830 830 830 830
Weight 54 63 99 108 111 111 112
Compressor Rotary Rotary Rotary Scroll Scroll Scroll Scroll
Volt 230V 230V 230V 230V 230V 380V 380V
5
Installation
Installation items
The factory only provides the heat pump unit. Other necessary items, according to the illustration are to be provided by the user or installer. Attention! Please follow according to the following steps whilst installing the heat pump: ○ The chemicals have to be added downstream of the heat pump. ○ It is recommended to install a bypass when the flow of the pool pump is more than 20% of the rated
flow of the heat pump. ○ Install the heat pump on a solid foundation and use the damping rubbers to eliminate vibrations and
noise. ○ Keep the unit straight up at all times. When the unit has been tilted, it is required to wait 24 hours
before re-starting the heat pump.
Location
The unit may be installed practically anywhere outdoors.
DO NOT put the unit in an enclosed area with a limited air volume where the unit discharge air will be re-circulated.
DO NOT put the unit next to shrubs. This may block the air inlet. Such locations deny a continuous
source of fresh air, which reduces its efficiency and may prevent adequate heat delivery.
The picture below give the minimum required distances from each side of the heat pump:
6
Distance Install the heat pump as close to the swimming pool as possible to minimize the loss of heat through the piping. Put it on a solid base and place the rubber blocks under the heat pump to eliminate vibrations. Normally, the heat pump is installed within a 7,5 meter radius of the pool. Heat loss is minimal up to distances of 30 meters. The heat loss per 30 meters is estimated at 0.6kw/hour for every 5˚C difference between the pool water and surrounding of the pipe. This increases the operation time around 3-5%.
Installation of the valve
Attention! Placement of the chlorinator, water balance equipment, and the placement of injectors of chemicals, are very important aspects of the installation. All addition of chemicals have to be done downstream from the heat pump. Failure to protect the heat pump unit from chemical damage is not covered under the warranty.
7
Installation of the pool system
Installation of the bypass
With the bypass set correctly, your heat pump will deliver its best performance. The bypass has to be built as show below: Setting the valves of the by-pass:
○ Set all 3 valves entirely open
○ Slightly close valve 1 ○ Close valve 3 about half way to adjust the refrigerant pressure
8
Electrical wiring Attention! Verify the local power supply and the operating voltage of the heat pump. It is recommended to use a separate circuit breaker (slow type – D curve) for the heat pump together with the proper wiring characteristics. The current to the heat pump should only be applied when the filter pump is running. For example, a relay controlled by the filter pump could be used to activate the current to the heat pump. Connect the electrical supply to the junction box inside the unit. All heat pumps require single-phase connection. Grounding the heat pump is required to protect you against electrical shocks caused by an eventual short circuit inside the unit. The heat pump is not equipped with a flow switch or any other kind of water flow detection. Therefore, the heat pump has to be wired electrically together with the filter pump to ensure water flow while the heat pump is running. Please consult the Appendix for more information.
Start-up procedure
Start-up Procedure - after the installation is completed, you should follow these steps:
1. Turn on your filter pump. Check for water leaks and verify the flow to and from the pool. 2. Turn on the electrical power supply to the unit and turn the unit ON with the switch. The unit
will start after the time delay period has lapsed. 3. After running a few minutes, check whether the air leaving the side of the unit cooled down. 4. Allow the unit and pool pump to run 24 hours per day until desired pool water temperature
is reached. When the set temperature is reached, the unit just shuts off. The unit will now automatically restart (as long as your pool pump is running) when the pool temperature drops more than 1 degree Celsius below set temperature. Several days are needed to bring the temperature of you swimming pool water to its required value.
Water flow switch- The unit is equipped with a flow switch that switches on when enough water has flowed through the unit and vice versa. Time Delay - the unit is equipped with a 3-minute built-in delay to protect the control circuit components and to eliminate restart cycling and contactor chatter. This time delay will automatically restart the unit approximately 3 minutes after each circuit interruption. Even a brief power interruption will activate this delay and prevent the unit from starting until the 3-minute countdown is completed.
Condensing Since the Heat pump cools down the air about 8 - 12 °C, causing condense on the fins of the evaporator. If the relative humidity is very high, this could be as much as several liters an hour. Sometimes this condensation water is misjudges and considered a leakage.
9
Guidelines
Water chemistry
Special care should be taken to keep the chemical balance of your swimming pool within limits: pH 7,0 – 7,4 Free chlorine 0,5 – 1,2 mg/l TAC 80 – 150 mg/l (10°F – 30°F) Salt max 3 g/l Attention! ○ Failure to keep the swimming pool water between above limits will void the warranty ○ When the concentration of one or more products mentioned above becomes too high, irrevocable
damage to your heat pump may occur. Make sure that you always install water treatment equipment after the heat pump.
○ When an automatic chemical feeder is installed in the plumbing, it must be installed downstream of the heat pump.
○ A check-valve must be installed between the heat pump and the chemical feeder to prevent back-siphoning of chemically saturated water into the heat pump where it will damage the components.
Winter-ready
Attention! Failure to winterize could cause damage to the heat pump and will void warranty In areas where freezing temperatures occur, you should protect your pump, filter and heat pump from the elements. Perform the following steps to completely drain the heat pump: 1. Turn off the electrical power to the heat pump at the main breaker panel. 2. Shut off the water supply to the heat pump: close valves 2 and 3 on the by-pass completely. 3. Disconnect the water inlet and outlet and let the water drain from the heat pump.
10
Spring start-up If your heat pump has been made winter-ready, perform the following steps whilst starting the system in the spring: 1. Inspect the system for any debris or structural problems. 2. Connect the water inlet and outlet unions firmly. 3. Turn on the filter pump to supply water to the heat pump. Adjust the by-pass to allow water flow
through the heat pump. 4. Turn on the electrical power to the heat pump at the main breaker panel.
Owner inspection
The ECO heat pumps are designed and constructed to provide long performance life when installed and operated properly under normal conditions. Periodic inspections are important to keep your heat pump running safely and efficiently through the years. The following basic guidelines are suggested for your inspection:
1. Make sure the front of the unit is accessible for future service. 2. Keep the surrounding areas of the heat pump clear of all debris. 3. Keep all plants and shrubs trimmed and away from the heat pump. 4. Keep lawn sprinkler heads from spraying on the heat pump to prevent corrosion and damage.
Use a deflector if needed. 5. If the unit is installed under a very sharp roof pitch or under a roof without a gutter, a gutter or
diverter should be fitted to prevent excessive water from pouring down onto the unit. 6. Do not use the heat pump if any part has been under water. Immediately call a qualified
professional technician to inspect the heat pump and replace any part of the control system, which has been submerged.
The heat pump will produce condensation (water) while in operation. The heat pump base is designed to allow the condensation to exit through the bottom drain port. The condensation will increase as the outdoor air humidity level increases. Check the following at regular intervals to ensure proper condensate drainage: 1. Visually inspect and clear the bottom drain port of any debris that could clog the port. 2. Keep the air intake area and discharge area clear of debris so the airflow through the heat pump
is not restricted. The cooler discharge air should not accumulate and be drawn into the side air intake coils. During normal operation, the heat pump produces ten to twenty liters of condensate per hour. If condensate drainage is above this range during operation or if water continues to drain from the base when the heat pump is not in operation for more than an hour, a leak in the internal plumbing may have occurred. Call a qualified heat pump technician to investigate the problem.
Attention! A quick way to verify that the water running through the drain is condensation water is to shut off the unit and keep the pool pump running. If the water stops running out of the base pan, it is condensation water.
11
Display Controller Operation
The buttons of LED wire controller
When the heat pump is running, the LED display shows the inlet water temperature. When the heat pump is standby, the LED display shows the real time.
Activating the heat pump.
Press ON to start the heat pump unit, the LED display shows the desired water temperature for 5 seconds, then shows the inlet water temperature. Press OFF to stop the heat pump unit.
Setting the heating/cooling mode
Press
Setting the real time
On standby or running mode, press for 10 seconds, then press or
to adjust hour/minute.
Then press the again to store the new data. Whilst setting the time, and cannot work.
12
Water temperature setting
On standby or running mode, press temperature.
and to adjust the desired water
Note : the heat pump can running only if the water circle/filtration system is running.
Automatic start/stop the heat pump
To set the time to start the unit
Press to set the time to start the unit,then press the time (set the time for start 5 minutes
after the pump).
Press again to store the new data. To set the time to stop the unit Press to set the time to stop running, then press or to adjust the time (set the time for stop 5 minutes before the water pump). Press again to store the new data. Concell the automatic start/stop To concell the automatic starter
Press , then press , light off and the automatic start is off. To concell the automatic starter
Press , then press , light off and the automatic stop is off.
Note : If the water filtration system is stop before the heat pump, the unit will shut down
(security condition) and the code EE3 or ON advertise on the controller.
It is important to program the heat pump link the time program of the water filtration system.
For restart the heat pump, turn off and turn on the electrical power supply to restart the
unit.
13
Running data setting Check the parameters On standby or running mode, press for 10 seconds. Afterwards press or to check the parameters (from 0 to H, see operation parameter table). How to adjust the parameters The parameters can only be adjusted in stand-by 1. Long press for 10 seconds, press again to select the data (from 0 to 10#,
see operation parameter table) you want to adjust. 2. Press or to adjust the parameter. Press again to store the new data. 3. Press or to select other data that needs to be adjusted and repeat the steps above.
14
Press MODE to change mode( Mode only be changed for or parameter 6)
○ Mode can be changed while running
○ Auxiliary electrical heating is not applicable to these modes.
15
Current status
16
Parameter Meaning Range Default Remarks
0
To set the entering water
temp. under cooling mode
15-35℃
27 ℃
Adjustable
1
To set the entering water
temp. under heating mode 15-40℃ 27 ℃
Adjustable
2
Entry into defrosting time period
30-90
Minutes
40
Minutes
Adjustable
3 Terms of Entry defrosting function
-30℃ to
0℃ -7℃ Adjustable
4 Terms of Exit defrosting 2 to 30℃ 15 ℃ Adjustable
5 Time of Exit defrosting 1 to 12
minutes
12
minutes Adjustable
6
Mode: 0 Cool 1 Heat and Cool 2 Heat and cool+ auxiliary elec. Heating 3 Heat
0-3
1
Adjustable
7
Mode selection of Electronic expansion valve 0-1 1(auto)
Adjustable
8 Superheat for heating target
-15℃-15℃ 4℃ Adjustable
9 Superheat for cooling
target -15℃-15℃ -2℃ Adjustable
A
Manual adjustment steps of electronic expansion valve
18-94
70
Adjustable
B Inlet water temperature -9-99 ℃ Exact testing by
value
C outlet gas temperature -9-99℃ Exact testing by
value
D Condenser temperature under
heating mode -9-99℃
Exact testing by
value
E Gas return temperature -9-99 ℃ Exact testing by
value
F Ambient temperature -9-99 ℃ Exact testing by
value
G Condenser temperature under
Cooling mode -9-99 ℃
Exact testing by
value
H Actual steps of electronic
expansion valve N*5 Exact testing by
value
17
Q&A
Error code Malfunction Error
code Reason Solution
Inlet water temperature sensor failure
PP1 The sensor in open or short circuit
Check sensor
or change the
Exhaust temperature sensor failure
PP2 The sensor in open or short circuit
Check sensor
or change the
Heating condenser sensor failure
PP3 The sensor in open or short circuit
Check sensor
or change the
Gas return sensor failure PP4 The sensor in open or short circuit
Check sensor
or change the
Ambient temperature sensor failure
PP5 The sensor in open or short circuit
Check or change the sensor
Temperature difference between water inlet and outlet is too much
PP6 Water flow volume not enough ,water pressure difference is too low
Check the water flow volume or water jammed or not
Cooling outlet water temperature is too low
PP7 Water flow volume is not enough
Check the water flow or water system is jammed or not
First grade antifreeze protection in Winter
PP7 Ambient temperature or water inlet temperature is too low
Water pump will run automatically for first grade antifreeze
Second grade antifreeze protection in Winter
PP7 Ambient temperature or water inlet temperature is too low
Heat pump will start heating for second grade antifreeze
Cooling condenser sensor failure
PP8 The sensor in open or short circuit
Check or change the sensor
High pressure protection EE1 Refrigerant is too much Air flow is not enough
Discharge redundant refrigerant from HP gas system Clean the air exchanger
Low pressure protection EE2 Refrigerant is not enough Water flow is not enough Filter jammed or capillary jammed
Check if there is any gas leakage ,re-fill the refrigerant Clean the air exchanger 3.Replace the filter or capillary
Flow switch closed EE3 or «ON«
Low water flow, wrong flow direction, or flow switch failure
Check if the water flow is enough and flow in right direction, or else the flow switch could be failing.
18
Power supply connections wrong
EE4 Lack of connection
Check the connection of the power cable.
Inlet and outlet water temperature difference malfunctions
EE5 Not enough water
Check the water flow rate and whether the water system is jammed.
Communication failure
EE8 Good Check the wire connection
Other malfunctions Malfunctions Observing Reasons Solution
Heat pump not running LED wire controller no display
No power supply Check cable and circuit breaker
“” LED wire controller displays actual time.
Heat pump on stand-by Activate heat pump
“” LED wire controller displays the actual water temperature
1. Water temperature is reaching to the set value, HP under constant 2. Heat pump has just been activated 3. Under defrosting
1. Verify water temperature setting 2. Start-up heat pump after a few minutes 3. LED wire controller should display “defrosting”
Water temperature is cooling when HP runs under heating mode
LED wire controller displays actual water temperature and no error in code displays
1. The wrong mode has been chosen 2. Figure shows defects 3. Controller defect
1. Adjust the mode 2. Replace the defect LED wire controller, and check the status after changing the mode.
Short running LED displays actual water temperature/no error in code displays
1. Fan is off 2. Air ventilation is not enough 3. Refrigerant is not enough
1. Check the cables between the motor and fan. Replace if necessary. 2. Check the location of the heat pump unit, and eliminate obstacles that could cause obstruction. 3. Replace or repair heat pump unit
Water stains Water stains on heat pump unit
1. Concreting 2. Water leakage
1. No action 2. Check whether the heat exchanger has any defects
Too much ice on evaporator Too much ice on evaporator 1. Eliminate all obstacles that could cause obstruction 2. Replace or repair the heat pump unit.
19
Maintenance o Check the water supply to the unit often. Low water flow and air entering into the system should be
avoided, as this will diminish the units’ performance and reliability. You should clean the pool/spa filter regularly to avoid damage to the unit as a result of the dirty or clogged filter.
o The area around the unit should be dry, clean and well ventilated. Clean the side heating exchanger regularly to maintain good heat exchange and to save energy.
o Only a certified technician should service the operation pressure of the refrigerant system. o Check the power supply and cable connection often. Should the unit begin to operate abnormally,
switch it off and contact a qualified technician.
o In winter, please discharge all water from the water pump and other systems to prevent damage from freezing.
o Discharge the water at the bottom of the heat pump if the unit will not work for an extended period
of time. You should check the unit thoroughly and fill the system with water fully before using it for the first time after a prolonged period of no usage.
20
Wiring diagram