Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part...

28
VD4 Vacuum circuit-breaker on withdrawable part – high duty Contents 1 Summary 5 2 Technical data 6 3 Circuit-breaker on withdrawable part 8 4 Operation of the switchgear 11 5 Maintenance 15 Medium voltage products

Transcript of Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part...

Page 1: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

VD4Vacuum circuit-breaker on withdrawable part – high duty

Instruction manual BA 414/07 E

Contents

1 Summary 5

2 Technical data 6

3 Circuit-breaker on withdrawable part 8

4 Operation of the switchgear 11

5 Maintenance 15

BA 414-07_GB_AMC.indd 1 18.07.12 10:24

Medium voltage products

Page 2: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

BA 414-07_GB_AMC.indd 2 18.07.12 10:24

Page 3: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

Your safety first – always!

That’s why our instruction manual begins with these recommendations:

• Only install switchgear and/or switchboards in enclosed rooms suitable for electrical equipment.

• Ensure that installation, operation and maintenance are carried out by specialist electricians only.

• Comply in full with the legally recognized standards (DIN VDE/IEC), the connection conditions of the local electrical utility and the applicable safety at work regulations.

• Observe the relevant information in the instruction manual for all actions involving switchgear and switchboards.

• Danger!

Pay special attention to the hazard notes in the instruction manual marked with this warning symbol.

• Make sure that under operation condition of the switchgear or switchboard the specified data are not exceeded.

• Keep the instruction manual accessible to all persons concerned with installation, operation and maintenance.

• The user’s personnel are to act responsibly in all matters affecting safety at work and the correct handling of the switchgear.

• Always observe the five safety rules set out in EN 50110 on establishing and securing the off-circuit condition at the place of work for the duration of work on the switchgear.

- Isolate

- Secure to prevent reconnection

- Check the off-circuit condition

- Earth and short-circuit

- Cover the guard off adjacent live parts

If you have any further questions on this instruction manual, the members of our field organization will be pleased to provide the required information.

BA 414-07_GB_AMC.indd 3 18.07.12 10:24

Page 4: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

4 5

Contents Page

1 Summary 5

1.1 General 5

1.2 Standards and specifications 5

1.2.1 Switchgear manufacture 5

1.2.2 Installation and operation 5

1.3 Operating conditions 5

1.3.1 Normal operating conditions 5

1.3.2 Special operating conditions 5

2 Technical data 6

3 Circuit-breaker on withdrawable part 8

3.1 Basic structure 8

3.2 Interlocks / protection against maloperation 8

3.2.1 VD4 circuit-breaker run-on block 8

3.2.2 Basic equipment 9

3.2.3 Mounting of the VD4 on trucks from 9 other manufacturer

4 Operation of the switchgear 11

4.1 Commissioning 11

4.1.1 Preparatory work 11

4.1.2 Start-up 11

4.2 Switching operations 11

4.2.1 Withdrawable circuit-breaker part 11

4.2.2 Circuit-breaker 13

Contents Page

5 Maintenance 15

5.1 General 15

5.2 Inspection and functional testing 15

5.2.1 General 15

5.2.2 Withdrawable assembly 16

5.3 Servicing 16

5.4 Repairs 16

5.4.1 Switchgear in general 16

5.4.2 Replacement of components 17

5.5 Testing withdrawable parts with a VD4 type circuit-breaker 17

5.5.1 Motor-operated withdrawable parts 17

5.5.2 Checking the correctness of dimensional settings 17

5.5.3 Checking auxiliary switch settings on type A withdrawable parts 17

5.5.4 Checking auxiliary switch settings on type B withdrawable parts 18

5.5.5 Checking the direction of rotation of the travel motors on motor-operated withdrawable parts 18

5.5.6 Testing of interlock conditions 18

5.6 Spare parts, auxiliary materials, lubricants 19

5.6.1 Spare parts 19

5.6.2 Auxiliary materials and lubricants 21

5.7 Wiring diagrams 24

We reserve all rights to this publication. Misuse, particularly including duplication and making available of this manual – or extracts – to third parties is prohibited. The information supplied is without liability. Subject to alteration.

© ABB AG, 2012

BA 414-07_GB_AMC.indd 4 18.07.12 10:24

Page 5: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

4 55

1 Summary

1.1 General

The vacuum circuit-breaker of type VD4 on with-drawable part are intended for indoor installation in air-insulated switchgear of withdrawable design. Their switching capacity is sufficient to handle any conditions arising from switching of equipment and systems components under normal operating conditions, particulary short-circuits, within the parameters of their technical data.

Vacuum circuit-breaker have particular advantages for use in networks where there is a high switching frequency in the working current range and/or where a certain number of short-circuit breaking operations are expected. The vacuum circuit-breakers of the type VD4, designed in column form, are suitable for autoreclosing, and have exceptionally high operating reliability and long life.

Together with this instruction manual, it is essential to consult manual BA 359, Vacuum circuit-breaker type VD4, high current.

1.2 Standards and specifications

1.2.1 Switchgear manufacture

The switchgear complies with the following speci-fications in accordance with DIN VDE/the relevant IEC publications:

• VDE0670,part1000/IEC60694.

• DINVDE0670,part104,andIEC62271-100

• DINVDE0847,part4,andIEC61000-4.

1.2.2 Installation and operation

The relevant specifications are to be taken into ac-count during installation and operation, particu larly:

• DIN VDE 0101, Power installations exceedingAC 1 kV

• VDE0105,Operationofelectricalinstallations

• DINVDE0141,Earthingsystemsforspecialpo-wer installations with rated voltages above 1 kV

• Accidentprevention regulations issuedby theappropriate professional bodies or comparable organisations.

In Germany, these comprise the following safety regulations:

– Health and Safety at Work Standards BGV A1 and BGV A2

• Safetyguidelinesforauxiliaryandoperatingma-terials

• Orderrelateddetailsprovidedby ABB Calor Emag.

1.3 Operating conditions

1.3.1 Normal operating conditions

Design to VDE 0670, part 1000, “Common specifi-ca tions for high-voltage switchgear and control-gear standards” and IEC publi cation 60694, with the following limit values:

• Ambienttemperature:

– Maximum +40°C

– Maximum 24 hour average +35°C

– Minimum (according to “minus 5 indoor class”) -5°C

• Humidity:

– the average value of the relative humidity, measured over a period of 24 h, does not exceed 95%

– the average value of the water vapour pressure, over a period of 24 h, does not exceed 2.2 kPa

– the average value of the relative humidity, over a period of one month, does not exceed 90%

– the average value of the water vapour pressure, over a period of one month, does not exceed 1.8 kPa

• Maximumsitealtitude: ≤ 1000 m above sea level.

1.3.2 Special operating conditions

Special operating conditions are to be agreed on by the manufacturer and user. The manufacturer must be consulted in advance about each special operating condition:

• Sitealtitudeover1000m:

– Allow for the reduction in the dielectric strength of the air.

• Increasedambienttemperature:

– Current carrying capacity is reduced.

– Provide additional ventilation for heat dissipa-tion.

• Climate:

– Avoid the risk of corrosion or other damage in areas:

• withhighhumidityand/or

• withmajorrapidtemperaturefluctuations.

– Implement preventive measures (e.g. electric heaters) to preclude condensation phe no mena.

BA 414-07_GB_AMC.indd 5 18.07.12 10:24

Page 6: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

6 7

Rated voltage 17.5 kV

Panel type Breakertype Parameters Pole centres p Weight for Dimension hand-operated drawings: mechanism1)2) Number [mm] [kg] of Figure

UniGear- VD4 1250 A, 40 kA 210 190 2/1 type ZS1 1600 A, 40 kA 210/275 190/195 2/1 2000 A, 40 kA 275 195 2/1 2500 A, 40 kA 275 205 2/1 3150 A, ...40 kA 275 280 2/1 4000 A, 3) ...40 kA 275 280 2/1 1) The weight raises about 5 kg for breakers with motor-operated mechanisms2) The weight raises about 2 kg for motor-driven withdrawable parts3) With fan cooling

Together with this instruction manual, it is essen-tial to consult manual BA 359, Vacuum circuit-breaker type VD4, high current.

2 Technical dataDimensions and weights

Rated voltage 12 kV

Panel type Breakertype Parameters Pole centres p Weight for Dimension hand-operated drawings: mechanism 1) 2) Number [mm] [kg] of Figure

UniGear- VD4 1250 A, 50 kA 210 190 2/1 type ZS1 1600 A, 50 kA 210/275 190/195 2/1 2000 A, 50 kA 275 195 2/1 2500 A, 50 kA 275 205 2/1 3150 A, ...50 kA 275 280 2/1 4000 A, 3) ...50 kA 275 280 2/1

BA 414-07_GB_AMC.indd 6 18.07.12 10:24

Page 7: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

6 77

Stroke 8 -11

19D

E

C

13,513,5

F 230

G

16 p pA 8

16

37025

165

6248

62

70,5

21,5

286 ±2383

303

359,5

øM

U

4

50200 0-3

320

1876

280

310

658

ø190

øW

125

55

!

VD4ABB

1)

2)

1)

Figure 2/1: Vacuum circuit-breaker on withdrawable part, type VD4

• Use in UniGear type ZS1• 12 kV, ...2500 A, 50 kA, 12 kV, 3150/4000 A, ...50 kA• 17.5 kV, ...2500 A, 40 kA, 17.5 kV, 3150/4000 A, ...40 kA

Dimensions in mm

1) Exists only for withdrawable parts of type A (see section 5.5)2) Exists only for rated currents above 2500 A3) with fan cooling

Panel type Parameter p A C D E F G M W U

12 kV 17.5 kV

UniGear-

type ZS1

1250 A, 50 kA

1600 A, 50 kA

2000 A, 50 kA

2500 A, 50 kA

3150 A, …50 kA

4000 A 3), …50 kA

1250 A, 40 kA

1600A, 40 kA

2000 A, 40 kA

2500 A, 40 kA

3150 A, …40 kA

4000 A 3), …40 kA

210

210

275

275

275

275

275

650

650

850

850

850

850

850

618

618

812

812

812

812

812

640

640

836

836

836

836

836

653

653

853

853

853

853

853

44

44

144

144

144

144

144

636

636

844

844

844

844

844

115

115

115

115

149

158

158

79

79

79

79

109

109

109

694

694

694

694

694

735

735

BA 414-07_GB_AMC.indd 7 18.07.12 10:24

Page 8: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

8 9

3 Circuit-breaker on withdrawable part

3.1 Basic structure(Figures 3/1 to 3/3 and 4/1 to 4/4)

The withdrawable part, which can be moved manually or by a motor if fitted, consists of a steel sheet structure on which the circuit-breaker with its ancillary components is mounted.

Insulated contact arms (4.2) with the spring-loaded contact systems (4.3) are fitted to the circuit- breaker poles. These create the electrical connec-tion to the panel when the withdrawable part is inserted into the service position.

A multi-pole control wiring plug connector (10) connects the signalling, protection and control wiring between the panel and the withdrawable part.

The withdrawable assembly and the circuit-breaker are connected via a multi-pole control wiring plug connector (10.3).

As soon as the withdrawable part (13) has been slid into the panel and its base frame has engaged in the test/disconnected position, it is positively connected to the panel. At the same time, it is earthed by its travel rollers in their rails. The stored-energy spring mechanism of the circuit-breaker, including its controls and indicators, is accessible at the front of the withdrawable part.

Withdrawable parts of the same version are inter-changable. With the same dimensions but different circuit-breaker equipment, coding of the control wiring plug prevents impermissible combinations of withdrawable parts and panels.

Besides the design with mounted circuit-breaker, withdrawable parts can also be supplied with other fittings, e.g. for measurement purposes.

3.2 Interlocks/protection against maloperation

A series of interlocks are provided to prevent dan-gerous situations and any maloperation. The inter-locks of the panel system ZS and/or the mounting frame, which are normally effective, are as follows (concerning the circuit-breaker):

• Thewithdrawablepartcanonlybemovedfromthe test/disconnected position into the service position (and back) with the circuit-breaker open and the earthing switch open (that means that the breaker must opened before)

• Thecircuit-breakercanonlybeclosedwhenthewithdrawable part is precisely in the defined test position or service position (mechanical inter lock, with additional electrical interlock for circuit-breakers with electrical releases).

• Thecircuit-breakercanonlybeopenedmanu- ally in the service or test position when no control voltage is applied, and cannot be closed (electromechanical interlock).

• Connection and disconnection of the controlwiring plug connector (10.2) is only in the test/disconnected position possible.

• The earthing switch canonly be closedwhenthe withdrawable part is in the test/disconnected position or the removed position (mechanical interlock).

• Thewithdrawablepart cannotbemoved fromthe test/disconnected position into the service position when the earthing switch is closed (me-chanical interlock).

• Detailsofanyadditionalinterlocks,e.g.inconnec-tion with a blocking magnet on the withdrawable part and/or earthing switch operating mecha-nism, can be found in the order documents for each individual case (see also section 5.5.6).

• Detailsoftypicalinterlocksforthepanelscanbefound in the panel documentation.

3.2.1 VD4 circuit-breaker run-on block

In case of any irregularity in the area of the inner control mechanism and of the charging function of the stored-energy spring mechanism, the run-on block disables the immediately subsequent swit-ching operation.

This is a protective measure to prevent damage to the circuit-breaker

Release of run-on block may only be performed by servicing personnel from ABB or adequately trained specialist stuff.

BA 414-07_GB_AMC.indd 8 18.07.12 10:24

Page 9: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

8 99

3.2.2 Basic equipment

3.2.3 Mounting of the VD4 on trucks from othermanufacturers

VD4 circuit-breakers which are not installed on ABB Calor Emag withdrawable parts must be fitted with one or two additional auxiliary switches which are dependent on the mechanical lock and release device. These must interrupt the circuit of shunt release ON -Y3.

Similarly to auxiliary switches -S8 and -S9 in ABB Calor Emag withdrawable parts, no electrical pulse may arrive during and before mechanical blocking of the spindle mechanism, and may only be applied again after the end of mechanical blocking.

This ensures that the shunt release ON cannot be loaded with an electrical ON pulse when the with-drawable part is in an intermediate position, which could burn out the coil.

Hand-operated breaker

Motor-operated breaker

1st shunt release OFF -Y2

5 pole auxiliary switches -S3, -S4

Auxiliary switch for fault annunciation -S7

Blocking magnet -Y1

Auxiliary switches -S2, -S6

Shunt releases ON, OFF -Y3, -Y2

5 pole auxiliary switches -S1, -S3, -S4

Charging motor -M0

Anti-pump relais -K0

Auxiliary switch for fault annunciation -S7

Blocking magnet -Y1

Auxiliary switches -S2, -S6

BA 414-07_GB_AMC.indd 9 18.07.12 10:24

Page 10: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

10 11

13.13

13.9

10.2

13.6

4.3

4.2

Figure 3/1: Pole side of a withdrawable part with high-voltage circuit-breaker, type VD4

13.9 Protective transport cover (remove before commissioning)13.13 Lifting lug (remove before commissioning4.2 Contact arm 4.3 Contact system

Figure 3/3: Withdrawable assembly with built-in auxiliary switch (type B, see section 5.5)

-S8 Test position indicator -S9 Service position indicator18 Spindle18.2 Scene head on spindle10.3 Control wiring connector plug for withdrawable assembly

Figure 3/2: Withdrawable part with circuit-breaker, type VD4, mechanism side

10.2 Control wiring plug13.6 Socket for charging lever (9)

-S8-S9 10.31818.2

BA 414-07_GB_AMC.indd 10 18.07.12 10:24

Page 11: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

10 1111

4 Operation of the switchgearNote on safety at work

• Theswitchgearmayonlybeoperatedbyspe-cially trained personnel who are familiar with the characteristics of the particular device.

• Observetherelevantinstructionsinsection1.2.

• Due to safety reasons, the circuit-breaker hasto be treated as “switched on” if the switching position can not be clearly determinated.

In this case all high voltage connections to the breaker have to be de-energized and zero potential on the primary side of the breaker has to be confirmed prior to commissioning, opera-tion, maintenance or repair work.

4.1 Commissioning

4.1.1 Preparatory work

(Figures 3/1 and 3/3)

In preparation for commissioning, the following work should be carried out prior to connection with the high-voltage power supply:

• Check thegeneralconditionof theswitchgearfor detrimental circumstances of all kinds.

• Performa visual examination of the switchingdevices, withdrawable parts, isolating contacts, insulating parts, etc.

• Checktheconnectionofthemainearthingbarwith the station earthing conductor (DIN VDE 0141).

• Checkthepaintworkfordamageandtouchupas described in section 5.4 where necessary.

• Removeallmaterialresidues,foreignbodiesandtools from the switchgear.

• Clean the switchgear, rubbingdown insulatingparts with a clean, soft, non-fraying and dry cloth. Remove greasy or adhesive dirt as described in section 5.3.

• Properly refit all covers, etc., removed duringassembly and testing processes.

• Transport caps (13.9)on thepolesof vacuumcircuit-breakers, where fitted, must be removed.

• Liftinglugs(13.13)forhighcurrentcircuit-break-ers, if still fitted, must be removed.

• PerformACvoltagetestingonthemaincircuitsto VDE 0670, Part 6 (IEC 60298) as far as neces-sary. Pay special attention during this pro cedure to voltage transformers and cables etc.

• Turntheauxiliaryandcontrolvoltageon.

• Carryout test operationsof switchingdevicesmanually or by electrical control, and simul-taneously observe the relevant position indica-tors.

• Checkmechanical and electrical interlocks foreffectiveness, without using force.

• Set the protective devices in the panel to therequired values, and check their functioning with test equipment.

• Onmotor-drivenwithdrawableparts,checkthedirection of rotation of the travel motors as de-scribed in section 5.5.5.

• Foranyfurtherquestionsonthefunctionsofthewithdrawable circuit-breaker part and its testing, see section 5.5.

• Instruct the localoperators in the fundamentaldetails of regular handling of the switchgear.

• Checkontheoperationalreadinessandswitchingstatus of upstream and downstream electrical installations.

From areas bordering on the switchgear, in accor-dance with responsibilities, check on the following where applicable:

• Powercables

• Auxiliarycables

• Supplyvoltagesource

• Remotecontrol

• Entire earthing installation, according to DIN VDE 0141

• Switchroomequipment

• Switchroomcondition

4.1.2 Start-up

• Complywithallrelevantsafetyregulations.

• Ensure that the circuit-breakers and switchdisconnectors in the switchgear are in the OFF position.

• Removeanyexistingearthingandshort-circuitingconnections in the critical switching area.

• Energizethefeedcables.

• Connecttheswitchgear,step-by-step,observingthe signals and indicators.

• Checkthattherelevantconductorsareinphase,as far as necessary when several incoming feeder cables and switchgear sections are concerned.

• Carryoutallmeasurementsandcheckallfunc-tions dependent on the high voltage power supply being connected.

• Watchoutforirregularitiesofanykind.

4.2 Switching operations

Perform switching operations with the front doors shut.

4.2.1 Withdrawable circuit-breaker part

(Figures 3/1, 3/4, 4/1 to 4/4)

Manual insertion from the test/disconnected posi-tion to the service position:

• Connectcontrolwiringplug(10.2).

• Closethefrontdoor.

• Ensure that the circuit-breaker is in theOFF position.

• Fit the crank (121) on square spigot (18.1) of the spindle mechanism (18).

BA 414-07_GB_AMC.indd 11 18.07.12 10:24

Page 12: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

12 13

Note:

In order to avoid damage to the operating mecha-nism, use the original hand crank only.

• Standardversionwithoutslipclutch

• Optionalversionwithslipclutch

• Movethewithdrawablebreakerpart(13)intotheservice position with 20 clockwise turns of the crank (for Unigear type ZS1 panels).

Note:

Do not force to move the withdrawable breaker part (max. torque 25 Nm)!

Comply with the conditions for movement of the withdrawable part as set out in section 5.5.6!

• Observethepositionindicator.

• Removehandcrank(121)bypressingfirstagainstthe hand crank and then remove.

When removing the crank, it is essential to ensure that the spring-loaded scene head 18.2 slides into the untensioned front position. Spindle 18 is thus locked in place, preventing inadvertent tur-ning of the spindle. Turning of the spindle opens auxiliary switches -S8/-S9 and thus prevents the circuit-breaker from being operated.

Note:

The withdrawable part must not be stopped at any position in the travel range between the service position and test/disconnected position!

Manual withdrawal from the service position into the test/disconnected position:

• Ensurethatthecircuit-breakerisintheOFFpo-sition.

• Reversetheproceduredescribedaboveforin-sertion into the service position.

Note:

Withdrawable parts with blocking magnet -Y0 may not be forcibly moved during power failures. In such a case they are blocked in the service and test po-sitions. For deblocking, see section 5.5.5.

Motor-driven movement of the withdrawable part:

• Brieflyoperatetheelectricalcontrolforinsertionor withdrawal (the withdrawable part then auto-matically moves into the opposite position).

• Observethepositionindicator.

Note:

When the motor fails, the withdrawable part can be moved in emergency manual operation. If the drive motor fails during movement of the withdrawable part, the withdrawable part must be moved into a limit position in emergency manual operation.

Emergency manual operation is carried out with the hand crank (121) on the spindle mechanism (18), in a similar manner to operation of a withdrawable breaker part with manual systems:

• Turn off the supply voltage (m.c.b.), since themotor would otherwise be braked electrically.

• Turnhandcrank(121)intherequireddirection.

When the withdrawable part moves, the motor turns. The motor functions in such a case like a generator, i.e. it can lead to reverse voltages in the terminals.

The motor protection device must not be changed from the specified type and rated value, or the be-haviour of the permanent magnet motor could be irreversibly impaired

Caution:

On emergency manual operation of a motor-ope-rated withdrawable breaker part:

• Whenamotor-operatedearthingswitchisfitted,the mechanical interlock with the earthing switch may not be available unless specially ordered.

• When amanual earthing switch is fitted, themechanical interlock is always effective.

Withdrawal from the test/disconnected position onto the service truck:

• Open thedoorof thecircuit-breakercompart-ment.

• Releasecontrolwiringplug(10.2)andengageitin the storage position on the withdrawable part.

• Positionservicetruck(124)withtheguidepins(124.2) of the adjustable bench top at the correct height facing the panel front, and allow catch (124.3) to engage.

• Move sliding handles (13.11) inwards againstthe springs to release withdrawable part (13), withdraw onto the service truck and secure it in the catches on the truck.

• Pressthereleaselever(atthefrontunderneaththe bench top) and release the service truck from the panel.

Insertion from the service truck into the test/dis-connected position:

• Carryouttheprocedureasdescribedaboveforwithdrawal, changing the order accordingly.

BA 414-07_GB_AMC.indd 12 18.07.12 10:24

Page 13: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

12 1313

4.2.2 Circuit-breaker

(Figures 3/2 and 4/1)

Charging the stored-energy spring system

• Onbreakerswithchargingmotors,charging iscarried out automatically. If the charging motor should fail, the charging procedure can be carried out or completed by hand.

• Onbreakerswithmanualchargingsystems,dooropened and withdrawable part in disconnected position, insert the charging lever (128) into the socket (13.6) and pump for approx. 25 strokes until the charged condition is indicated. When the charging condition is reached, the charging mechanism is auto matically disengaged, and any further strokes of the lever have no effect.

Meaning of the charging condition symbols:

Discharged Charged

Opening and closing the circuit-breaker:

• Withthewithdrawablepartintheserviceposition,on and off switching operations should only be carried out with the doors closed.

• Operatethelocalorremoteelectricalcontrol.

• Observetheswitchpositionindicator.Theswit-ching operation counter (13.5) for the circuit-breaker is automatically incremented by one unit with each operating cycle.

10

128

13.8

(18)/18.1

13.2

13.3

13.413.5

13.11

Figure 4/1: Manual operation and mechanical indicators of a withdrawable breaker part, withdrawable circuit-breaker part in test/disconnected position

10 Control wiring plug connection13.2 Mechanical ON push-button13.3 Mechanical OFF push-button13.4 Mechanical switch position indicator13.5 Mechanical operating cycle counter13.8 Charging condition indicator13.11 Sliding handle, connected to the catch in the withdrawable part base frame(18) Spindle mechanism121 Square spigot128 Charging lever

BA 414-07_GB_AMC.indd 13 18.07.12 10:24

Page 14: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

14 15

18 13 121

124 13 13.11

124.2

124.3

124.1

Figure 4/2: Movement of the withdrawable breaker part between the test/disconnected position and the service position, clockwise up to the stop for the service position and anti-clockwise for the test/disconnected position

13 Withdrawable circuit-breaker part18 Spindle mechanism121 Hand crank

Figure 4/4: Service truck engaged with the panel. Withdrawable circuit-breaker part released for removal by moving the sliding handles inwards

13 Withdrawable circuit-breaker part13.11 Sliding handle124 Service truck (not included in supply)

Figure 4/3: Approaching the panel and positioning the service truck with the guide pins of the adjustable height bench top at the correct height for the catch to engage

124.1 Height adjuster124.2 Guide pin124.3 Catch

BA 414-07_GB_AMC.indd 14 18.07.12 10:25

Page 15: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

14 1515

5 Maintenance

5.1 General

Maintenance serves to preserve trouble-free operation and achieve the longest possible wor-king life of the switchgear. In accordance with DIN 31051 and/or IEC 61208, it comprises the following closely related activities:

Inspection: Determination of the actual condition.

Servicing: Measures to preserve the specified condition.

Repairs: Measures to restore the specified condition.

Vacuum circuit-breakers are characterized by their simple and robust construction. They have a long life expectancy. Their operating mechanisms have a low maintenance requirement, and the interrupters are maintenance-free during their working life. There is no adverse effect on the vacuum, even from frequent switching of operating and short-circuit currents.

The servicing intervals and scope are determined byenvironmentalinfluences,theswitchingsequen-ces and number of short-circuit breaking operati-ons.

Note:

The following must be observed for all maintenance work:

• Therelevantspecificationsinsection1.2.2

• Notesonsafetyatworkinsection4.1

• Standardsandspecifications in thecountryofinstallation.

Maintenance work may only be performed by fully trained personnel, observing all the relevant safety regulations. It is recommended that ABB after-sales service personnel should be called in, at least du-ring the performance of servicing and repair work.

While the work is in progress, all supply voltage sources must also be disconnected and secured to prevent reconnection.

Note:

In order to prevent accidents (particularly injury to hands!) extreme care should be taken during all repair work on the operating mechanism, especially with front plate removed.

The spiral spring in the spring energy storage me-chanism, for instance, retains a basic tension which is independent of the charging and discharging processes during switching, so as to ensure correct function. This spring energy can be inadvertently released if work is performed incorrectly on the spring mechanism!

Together with this instruction manual, it is essential to consult manual BA 359, Vacuum circuit-breaker type VD4, high current.

The service life data fundamentally apply to all componentswhicharenotdirectly influencedbythe operator.

Components operated manually (movement of the withdrawable part, etc.) may deviate, depending on how they are handled.

If necessary, further details can be taken from the technical documentation for the switchgear (inclu-ding, for example, any agreed special operating conditions).

5.2 Inspection and functional testing

5.2.1 General

• Theproperconditionoftheswitchingdeviceisto be verified by regular inspection.

• Thechecksaretobeperformedinaccordancewith BGV A2 standards.

• Inspection at fixed intervalsmay bewaived ifthe switchgear is permanently monitored by a qualified personnel.

• Thechecksfirstand foremostcomprisevisualexamination for contamination, corrosion, moi-sture and discharge phenomena.

• Inunusualoperatingconditions(includingadverseclimatic conditions) and/or special environmental pollutions (e.g. heavy contamination and ag-gressive atmosphere), inspection may also be necessary at shorter intervals.

• Visualcheckingoftheisolatingcontactsystem.We recommend to turn alternately the contact system in order to clean the inner contact points of the contact system.

The contact points should be cleaned if signs of unperminable overheating (discoloured surface) are visible (see section Repairs)

• If irregularconditionsaredetected,thencorre-sponding repair measures should be initiated.

For details of inspection and functional testing, see the relevant sections of manual BA 359.

BA 414-07_GB_AMC.indd 15 18.07.12 10:25

Page 16: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

16 17

5.2.2 Withdrawable assembly

• The inspection should always include a visualexamination of the withdrawable part assembly. Special attention is to be paid to those parts which may possibly be damaged by improper handling. (See section “Inspection/Circuit-breaker in general“.)

• Visualcheckingoftheisolatingcontactsystem.We recommend turning the contact system alter-nately in order to clean the inner contact points.

The contact points should be cleaned if signs of impermissible overheating (discoloured surface) are visible (see section “Repairs“).

• Theinterlockconditionsandtheeaseofmove-ment of the lock and release device are to be checked as described under “Repairs“.

When checking the interlock conditions, it is essential to ensure that no force is used.

Maximum torque 25 Nm!

5.3 Servicing

Cleaning surfaces:

If, on the occasion of an inspection in accordance with (5.2), the necessity of cleaning measures has been established, proceed as follows:

• Before cleaning,where required, theworkingarea must be switched off and secured against reconnection in accordance with the „Safety Regulations“ specified by DIN VDE/IEC.

• Cleaningthesurfacesingeneral:

– Poorly adhering dry dust residues with a soft dry cloth.

– More strongly adhering grime with mildly al-kaline household cleaner or with Rivolta BWR 210.

• Cleaning insulating surfaces and conductivecomponents:

– Minor grime with Rivolta BWR 210.

– Strongly adhering grime with cold cleanser 716.

• Observe themanufacturers’ directions and inparticular ABB operating instructions BA 1002/E and BA 1006/E on safety at work.

• After cleaning, rinsewith cleanwater anddrycarefully.

• Shouldexternaldischargesoccurasaresultofcondensation, application of a thin silicone film on the surface concerned is often effective as a tem-porary remedy. It is advisable to request advice from the ABB after-sales service department on permanent solutions to such unusual problems.

For details of servicing, see also the relevant sec-tions of manual BA 359.

5.4 Repairs

5.4.1 Switchgear in general

Repair of surface damage:

• Sheetsteelparts,painted:

– Remove rust, e.g. with a wire brush.

– Grind off paint coat and degrease.

– Apply anti-rust primer and top coat.

– Use top coat paint in the standard colour RAL7035.

• Sheetsteelparts,withzincsurfaceandpassiva-ted functional parts:

– Remove white rust with a wire brush or cleaning pad (e.g. Scotch-Brite white).

– Remove loosely adhering particles with a dry cloth.

– Apply zinc spray or zinc dust primer.

• Functionalparts,phosphated:

– Remove rust with a wire brush or cleaning pad (e.g. Scotch-Brite white).

– Clean with a dry cloth.

– GreasewithIsoflexTopasNB52.

Switchgear in general:

• Observethemaintenanceinstructionsinthema-nuals for the individual equipment components.

• Checkthattheboltconnectionsatthecontactpoints in the busbar system and the earth con-nections are tight, and that the isolating contact system functions correctly.

• Regrease the contact points andmechanismof the withdrawable part insertion system as necessary, or, when lubrication is inadequate or missing, thoroughly clean the areas concerned andregreasewithIsoflexTopasNB52lubricant.

• Where required, regrease or thoroughly cleanslide plates and bearings in the panel and regrea-sethemwithIsoflexNB52lubricant.

Remove the contact system for thoroughly cleaning as described below (Figure 5/1):

– Slide the two inner annular tension springs (4.4) facing the breaker pole to a position beside the other two outer annual tension springs, thus releasing contact system (4.3), and remove the contact system from contact arm.

– Fit a new contact system back to front on the thin end of arbor (127), and slide it forwards onto the thicker part of the shank.

– Fit arbor (127) onto the relevant contact arm, slide the contact system (4.3) over onto the contact arm, and withdraw the arbor.

– Check all contact fingers and annular tension springs for perfect fit.

Note:

The set installation position of contact arms must not be changed by the improper use of force.

BA 414-07_GB_AMC.indd 16 18.07.12 10:25

Page 17: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

16 1717

5.4.2 Replacement of components

1. Withdrawable assembly:

(Figures 5/2 to 5/6)

• Disconnect plug connector (10.3) (only forwithdrawable assembly of type B)

• Removeinterlockrod(13.91)withpin(13.27)from the withdrawable assembly

• Formotorizedwithdrawableassemblies, re-move the two socket head bolts which are accessible from below the assembly

• Unbolt the circuit-breaker from thewithdra-wable assembly (4 x M12 bolts)

• Mount the circuit-breaker on a newwith-drawable assembly in the reverse order, using new circlip and special pliers for pin (13.27)

• Checkthesettingofinterlockingrod(13.91):

– Turn spindlel (18) anti-clockwise to the stop for the disconnected position:

The distance between lever (13.26) and cam (13.25) must be 2+1 mm.

The distance between roller (13.24) and blok-king bracket (13.92) must be 0.2-0.5 mm.

– Turn spindle (18) clockwise to the stop for the service position:

The distance between lever (13.26) and cam (13.25) must be 2+1 mm.

The distance between roller (13.24) and blocking bracket (13.92) must be 0.2-0.5 mm.

– Loosenbolts(13.91.2or13.92.1) foranynecessary adjustment.

For further details on repairs, see also the relevant sections of manual BA 359.

5.5 Testing withdrawable parts with a VD4 type circuit-breaker

When functional tests are carried out on withdra-wable parts, compliance with the con ditions listed below should also be checked. In this context, a distinction should be made between two types of the devices for the VD4 withdrawable part:

• TypeA:Withdrawable assemblywithout inte-grated auxiliary switches (manual operation only).

• TypeB:Withdrawableassemblywith integrated auxiliary switches (manual or motorized operation).

5.5.1 Motor-driven withdrawable parts

(non-standard)

Carry out testing of motor-driven withdrawable parts in the same way as for manually operated withdrawable part:

• Turn off the supply voltage (m.c.b.), since themotor could otherwise be braked electrically.

• Turnhandcrank(121)intherequireddirection.

Note:

When the withdrawable part moves, the motor turns. The motor functions in such a case like a generator, i.e. it can lead to reverse voltages in the terminals.

5.5.2 Checking the correctness of dimensional settings

(Figures 5/2 to 5/6)

1. The distance between lever (13.26) operated by link rod (13.91) and plastic cam (13.25) should be 2+1 mm. If adjustment is required, release the two bolts (13.91.1) and (13.91.2). Deviations from the specified value can have the following effects:

• Dimensionstoolarge,blockingsystemforthedrive spindle deactivated.

• Dimensions too small, proper action of theelectrical interlock no longer guaranteed.

2. The distance between roller (13.24) and angle lever (13.92) should be 0.2-0.5 mm when the circuit-breaker is closed.

If adjustment is required, release the two bolts (13.91.2) and (13.92.1)

5.5.3 Checking auxiliary switch settings on type A with-drawable parts

(Figure 5/2)

Compliance with the interlock conditions in the areas of the test/disconnected position and the service position is ensured by auxiliary switch -S6, located in the breaker housing and factory-set.

In test operations, the withdrawable part must be moved by hand with the crank fitted.

1. Settings in the area of the test/disconnected position

• Movethewithdrawablepartoutof the test/disconnected position towards the service position with a few turns of the crank.

• Slowlymove thewithdrawablepartback tothe stop.

Auxiliary switch -S6 must then operate when the hand crank has a remaining angle of ≥ 60o of turn to reach the stop.

• Slowlyinsertthewithdrawablepartfromthetest/disconnected position towards the service position until auxiliary switch -S6 just operates.

In this position, it must still just be possible to move closing push rod (13.2.1). For this test, the function of the blocking magnet -Y0 must be deactivated manually.

This condition ensures that the electrical interlock takes effect before the mechanical interlock in the motion sequence involved.

BA 414-07_GB_AMC.indd 17 18.07.12 10:25

Page 18: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

18 19

2. Settings in the area of the service position

• Movethewithdrawablepartoutofthelimitpo-sition towards the test/disconnected position with a few turns of the crank.

• Slowlymovethewithdrawablepartforwardsagain to the stop:

Auxiliary switch -S6 must then operate when the hand crank has a remaining angle of ≥ 60o of turn to reach the stop.

5.5.4 Checking auxiliary switch settings on type B with-drawable parts

(Figures 3/3 and 5/2)

Compliance with the interlock conditions in the test/disconnected and service position areas is ensured by position signalling switches -S8 and -S9 located in the withdrawable assembly and factory-set.

In test operations, the withdrawable part must be moved by hand with the crank fitted with the motor power switched off.

1. Settings in the area of the test/disconnected position

• Movethewithdrawablepartoutof the test/disconnected position towards the service position with a few turns of the crank.

• Slowlymove thewithdrawablepartback tothe stop.

Auxiliary switch -S8 must then switch over just before the stop is reached.

• Slowly insert thewithdrawablepart from thetest/disconnected position towards the service position until auxiliary switch -S8 just operates.

In this position, it must still just be possible to move closing push rod (13.2.1). For this test, the function of the blocking magnet -Y0 must be deactivated manually.

This condition ensures that the electrical interlock takes effect before the mechanical interlock in the motion sequence involved.

2. Settings in the area of the service position

• Movethewithdrawablepartoutofthelimitpo-sition towards the test/disconnected position with a few turns of the crank.

• Slowlymovethewithdrawablepartforwardsagain to the stop:

Auxiliary switch -S9 must then switch over just before the stop is reached.

5.5.5 Checking the direction of rotation of the travel motors on motor-driven withdrawable parts

• Movethewithdrawablepartbyhandintoacentralposition between the test/disconnected position and the service position.

• Removethehandcrank.

• Switchthesupplyvoltageforthetravelmotoron.

• Usethelocalelectricalcontrolstocheckthatthewithdrawable part moves in the correct direction.

Caution:

Do not allow the withdrawable part to run up against a block when the travel direction is incorrect! Switch the motor power off immediately (the travel process functions electrically by a seal-in system with limit position switch-off).

There may be a danger of injury when the door is open!

5.5.6 Testing of interlock conditions

(Figures 4/1 and 4/2)

The testing procedures for type A and type B with-drawable parts are identical.

1. The withdrawable part must only be movable from the test/disconnected position into the service position when the circuit-breaker is open and the earthing switch is open.

Check the following conditions individually:

• Withthecircuit-breakerclosed,insertionofthewithdrawable part towards the service position must be blocked after only half a turn of the crank in the clockwise direction, and the travel motor on motor-operated withdrawable parts must not be capable of being switched on.

• Withtheearthingswitchclosed, insertionofthe withdrawable part towards the service position must be blocked after only two clo-ckwise turns of the crank, and the travel motor on motor-operated parts must not be capable of being switched on.

Do not use force (max. torque 25 Nm)!

2. The withdrawable part must only be movable from the service position into the test/discon-nected position with the circuit-breaker open.

Check this condition as follows:

• With the circuit-breaker closed,withdrawalmovement of the withdrawable part must be blocked after only half a turn of the crank in the anti-clockwise direction, and the travel motor on motor-operated withdrawable parts must not be capable of being switched on.

3. Closing of the circuit-breaker must only be pos-sible when the withdrawable part is in the defined test/disconnected position or service position.

The control wiring plug (10.2) must previously have been inserted.

Check this condition as follows:

• Itmustnotbepossible toclose thecircuit-breaker with the withdrawable part in any po-sition between the test/disconnected position and the service position.

BA 414-07_GB_AMC.indd 18 18.07.12 10:25

Page 19: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

18 1919

• Enablingofswitchingwhenthewithdrawablepart moves into the service position is effected electrically by operation of auxiliary switch -S6 in the breaker housing (for type A), or of auxi-liary switch -S9 in the withdrawable assembly (for type B), and mechanically slightly earlier; the latter corresponds to a position approxi-mately half a turn of the crank before stop.

• Formotion into the test/disconnected po-sition, the same enabling conditions apply analogously, in this case by means of auxiliary switch -S6 in the breaker housing(for type A) or the auxiliary switch -S8 in the withdrawable assembly (for type B).

4. It must only be possible to open the circuit-breaker (manually) when the withdrawable part is in the service position or test/disconnected position and the control voltage has failed.

Check this condition.

5. Withdrawable parts with order-related blocking magnet -Y0 may not be moved in case of control power failure, or when there is no control power. Do not forcibly move blocked withdrawable parts! The blocking magnet -Y0 is only present on manually operated withdrawable parts.

Releasing the blocking magnet -Y0.

• Removefrontplate(1.1),

• Disengageblockingmagnet-Y0bypullingthemagnet armature,

• Whiledoingso,turncrank(121)aboutonehalfturn (either direction of rotation is permissible).

The blocking magnet is only active in the test position and service position. In intermediate positions it has no effect.

6. Disconnection of the control wiring plug (10.2) as well as later insertion must be blocked in the withdrawable part’s service position.

Check this condition.

5.6 Spare parts, auxiliary materials, lubricants

5.6.1 Spare parts

When parts are required, the serial number of the relevant withdrawable breaker part or circuit-breaker should always be quoted. Setting instructions are to be requested separately.

Circuit-breaker VD4

• Shuntrelease,auxiliaryswitch: For notes on settings see drawing GCE 717 96 11

• Chargingmotorwithgearbox: No special notes required (table 1)

Withdrawable assembly of VD4

• Manuallymoveablewithdrawableassembly:

– type A: For notes on settings see drawing GCE 7003570, sheet 1 and 2

– type B: For notes on settings see drawing GCE 7003570, sheet 1 and 2.

• Motor-drivenwithdrawableparts: For notes on settings see drawing GCE 7003571

• Blockingmagnet-Y0: For notes on settings see drawing GCE 7003820, sheet 1. (table 2)

BA 414-07_GB_AMC.indd 19 18.07.12 10:25

Page 20: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

20 21

Table 1: VD4 circuit-breaker

Designation Item Rated supply Part-no. no. voltage (order code)

• Auxiliaryswitches -S1 GCE7002397R0122(with clamp type terminals) -S3 GCE7002397R0121 -S4 GCE7002397R0122 -S5 GCE7002397R01..1)

• Auxiliaryswitchonblockingmagnet -S2 GCE7003022P0101• Auxiliaryswitchforfaultannunciation -S7 GCE0905121P0100• 1stschuntreleaseOFF -Y2 GCE7004590P01..2)

• 2ndshuntreleaseOFF -Y9 GCE7004590R01..2)

• ShuntreleaseON -Y3 GCE7004590P01..2)

• Blockingmagnet -Y1 GCE9478103P01..2)

• Undervoltagerelease -Y4 GCE9371466R01..2)

with spring mechanism• Delayedundervoltagerelease -Y4 GCE9371466R01..2)

with spring mechanism• Indirectovercurrentreleasewithintermediate -Y7 GCE9371466R0112 current transformer and spring mechanism• Intermediatecurrenttransformer GCE9476148R0100 for indirect overcurrent release• Magnetholder,complete(with GCE7000880R0111 integrated rectifiers -V1, -V2, -V3, -V9)• Seriesrectifier -V4/-V7 GCE7004046R0101 Charging motor -M0 DC 24 V GCE0940084P0101 (with gearbox) DC 48 V GCE0940084P0103 DC 60 V GCE0940084P0104 DC/AC 110 V GCE0940084P0105 DC 125 V GCE0940084P0105 DC/AC 220 and GCE0940084P0106 240 V• Push-onsleeve4.8-2.5 DIN46247Page2 for push-on blade 0.8 thick (for additional connections)

1) Quote contact arrangement2) State the type of release and voltage

BA 414-07_GB_AMC.indd 20 18.07.12 10:25

Page 21: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

20 2121

Table 2: VD4 withdrawable assembly

Designation Item Rated supply Part-no. no. voltage (order code)

Auxiliary switch for manually operated mechanism (type A) -S6 GCE7004023R0101

Auxiliary switch for manually operated mechanism (type B) -S8/-S9 •contactssilverplated GCE7004024R0101•contactsgoldplated GCE7004024R0103

Auxiliary switches for motor-operated driving mechanism -S8/-S9•contactssilverplated GCE7004024R0102•contactsgoldplated GCE7004024R0104

Blocking magnet -Y0 24 V GCE7003820R0101 30 V R0102 48 V R0103 60 V R0104 110 V R0105 125 V R0107 220 V R0106

Motor with gearbox -M1 24 V GCE0940150 P0111 30 V P0112 48 V P0113 60 V P0114 110 V P0115 220 V P0116

5.6.2 Auxiliary materials and lubricants

Part-no. (order ref.)

Lubricant:

• IsoflexTopasNB52 GCE0007249P0100

Halogen-free cleansers:

• RivoltaBWR210 GCE0007707P0100

(for general cleaning)

Corresponding ABB operating instructions BA 1002 E GCEA901002P0101

• Coldcleanser716 GCE0007706P0100

(for use with con- ductive components, components of insulating materials and in case of serious grime!)

Corresponding ABB operating instructions BA 1006 E GCEA901006P0101

Touch-up paint:

STandardcolourRAL7035 • 1kg-box GCE9014060R0103 • Spraytin GCE0007895P0100

BA 414-07_GB_AMC.indd 21 18.07.12 10:25

Page 22: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

22 23

13.2.1

13.25

13.26

-Y1

-Y0

Figure 5/4: Manually moveable withdrawable part, front plate removed

-Y0 Blocking magnet for withdrawable part

Figure 5/3: Detailed view of the opening and closing mechanism

13.2.1 ON push rod13.25 Plastic cam13.26 Lever-Y1 Blocking magnet

127.1 127 4.3

13.26

13.2.1

13.24

13.92

10.3

(-S6)

121

Figure 5/1: Fit the contact system back-to-front on the thin end of the arbor and slide it onto the thicker shank area

4.3 Contact system127 Arbor127.1 Journal

Figure 5/2: Motor-driven withdrawable part in an intermediate position close to the test/disconnected position, with fitted crank for manual operation and breaker front plate removed

10.3 Control wiring plug connector for withdrawable assembly13.2.1 ON push rod13.24 Roller13.26 Lever13.92 Angle lever(-S6) Auxiliary switch (only with type A withdrawable part)121 Hand crank

BA 414-07_GB_AMC.indd 22 18.07.12 10:25

Page 23: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

22 2323

13.25

13.26

13.24

13.92

13.91

13.91.2

13.27

2+1

13.91.1

13.92.1

0.2-

0.5

13.25

13.26

13.24

13.92

13.91

13.91.2

13.27

13.90

13.91.1

2+1

0.2-

0.5

13.92.1

Figure 5/6: Mechanical interlock, withdrawable assembly/circuit-breaker with manually operated withdrawable parts

13.24 Roller13.25 Cam 13.26 Lever13.27 Pin13.91 Link rod13.91.1 Bolt13.91.2 Bolt13.92 Angle lever13.92.1 Bolt

Figure 5/5: Detail in the area of a withdrawable part with travel motor, viewed from the left-hand side

13.24 Roller13.25 Cam 13.26 Lever13.27 Pin13.90 Travel motor13.91 Link rod13.91.1 Bolt13.91.2 Bolt13.92 Angle lever13.92.1 Bolt

BA 414-07_GB_AMC.indd 23 18.07.12 10:25

Page 24: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

24 25

Figu

re 5

/7:

Wiri

ng d

iagr

am fo

r V

D4

vacu

um c

ircui

t-b

reak

er o

n m

anua

lly m

ovea

ble

with

dra

wab

le a

ssem

bly

.

• Ty

pe A

of w

ithdr

awab

le p

art

• M

axim

um o

f equ

ipm

ent

• C

ontr

ol w

iring

plu

g 58

-pol

e•

Use

in p

anel

sys

tem

Uni

Gea

r-Ty

p ZS

1•

Dra

win

g no

. GC

E203

2404

5.7 Wiring diagrams for C.B. on withdrawable part

Note:The wiring diagrams comprise the basic com-ponents and all further equipment options for the various VD4 types. The scope of equipment pos-

sible within an individual type series is listed in the relevant switchgear list, and the euquipment fitted in each individual case can be found in the order documentation.

-X0

2624

2510

35

427

4332

3111

823

67

928

2940

1

2253 54

21

-S1

3132

- M0 M

OFF

- S6

3 42

1

4

13 14

–K0

53 543231

S32221

13 1443 44

-S7

21

13 14

-Y7

-S4

1353

4131 32

4254

2221-S

514

44435453

32312221

4241

-Y1

ON

0-R

02

-S2 -Y

3-K

0A

4121

2218

3316

1719

3839

-Y4

-Y2

-Y2

-Y4

-Y9

1513

3744

4230

2

-V3

-Y9

B

14-X

0

-V0

-Y0

-V1

3646

4535

3420

E

A

- Q0

-X0

P

-Y0

Bloc

k M

agne

t on

truc

k w

ith re

ctifi

er -V

0-Y

1 C

losin

g bl

ock

mag

net w

ith re

ctifie

r -V1

-Y2

1. S

hunt

rele

ase

OFF

with

rect

ifier -

V2-Y

3C

losin

g re

leas

e wi

th re

ctifie

r -V3

-Y4

Und

ervo

ltage

rele

ase

U<

with

rect

ifier -

V4-Y

7In

dire

ct o

verc

urre

nt re

leas

e-Y

92.

Shu

nt re

leas

e O

FF w

ith re

ctifie

r -V9

-M0

Cha

rgin

g m

otor

-K0

Antip

umpi

ng re

lay

Mod

e of

pre

sent

atio

n:

•A

ux. s

witc

h -S

1 sh

own

for c

.b.-m

echa

nism

dis

char

ged

•C

.b.-u

nit i

n se

rvic

e po

sitio

n•

Con

trol w

iring

plu

g 58

-pol

e•

Ear

thin

g sw

itch

mec

hani

cal i

nter

lock

with

c.b

.-uni

t:a)

C.b

.-uni

t in

test

pos

ition

:E

arth

. sw

itch

can

be o

pera

ted

b)E

arth

. sw

itch

open

pos

ition

: C

.b.-u

nit c

an b

e m

oved

in th

e se

rvic

e po

sitio

n

-S1

Auxil

iary

swi

tch

on m

echa

nism

-S2

Auxil

iary

swi

tch

on b

lock

mag

net -

Y1-S

3 Au

xilia

ry s

witc

h on

sw

itch

shaf

t-S

4 Au

xilia

ry s

witc

h on

sw

itch

shaf

t-S

5 Au

xilia

ry s

witc

h on

sw

itch

shaf

t-S

6Au

xilia

ry s

witc

h at

c.b

.-uni

t-S

7 Fl

eetin

g co

ntac

t 35

ms

for c

.b. t

rippe

d in

dica

tion

BA 414-07_GB_AMC.indd 24 18.07.12 10:25

Page 25: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

24 2525

Figu

re 5

/8:

Wiri

ng d

iagr

am fo

r V

D4

vacu

um c

ircui

t-b

reak

er o

n m

anua

lly m

ovea

ble

with

dra

wab

le a

ssem

bly

.

• Ty

pe B

of w

ithdr

awab

le p

art

• M

axim

um o

f equ

ipm

ent

• A

uxilia

ry s

witc

h -S

5 w

ired

• C

ontr

ol w

iring

plu

g 58

-pol

e•

Use

in p

anel

sys

tem

Uni

Gea

r-Ty

p ZS

1•

Dra

win

g no

. GC

E213

2701

P01

01

26-X

0

45

-S3

21 22 20

-S2

0 231 3213 14

-K0

42

1

-Y3

53 54

-K0

A B

-R0

4 14

13 14

43 44 -Y9

2

-Y4

44

-Y2

30

-Y7

-S4

13 14

-S1

22 21

1341

4221

2218

53 54

41 42

31 32

21 22238

1131

3243

53 54

32 31 -M0

M

24

41 42

36-X

034

35155

3

33

27 371 2

-S7

25

-Y1

-Y0 46

13 14

-S5

43 44

53 54

31 32

21 2229 39

289

76

1719

38

1115 54

1658

565557

1049

52

18-X

14

5153

50

16

7-X

94

21

8-X

35

6

1312

17-X

-S8

53 54

43 44

33 34

23 24

13 14

-S9

53 54

43 44

33 34

140

13 14

23 24

OFF ON

AE

-V1

-V0

-V3

-V9

-V4

-V2

P

+ -

~~

~~+

-

+-

~~~ ~

+-

--

++

~~

~~

-Y0

Bloc

k M

agne

t on

truc

k wi

th re

ctifie

r -V0

-Y1

Clos

ing

bloc

k m

agne

t with

rect

ifier -

V1-Y

2 1.

Shu

nt re

leas

e O

FF w

ith re

ctifie

r -V2

-Y3

Clos

ing

rele

ase

with

rect

ifier -

V3-Y

4 Un

derv

olta

ge re

leas

e U<

with

rect

ifier -

V4-Y

7 In

dire

ct o

verc

urre

nt re

leas

e-Y

9 2.

Shu

nt re

leas

e O

FF w

ith re

ctifie

r -V9

-M0

Char

ging

mot

or-K

0 An

tipum

ping

rela

y

SERV

ICE-

POSI

TIO

N

TEST

-PO

SITI

ON

Mod

e of

pre

sent

atio

n:

•Au

x. s

witc

h -S

1 sh

own

for c

.b.-m

echa

nism

disc

harg

ed•

C.b.

-uni

t in

serv

ice p

ositio

n•

Cont

rol w

iring

plu

g 58

-pol

e•

Earth

ing

switc

h m

echa

nica

l inte

rlock

with

c.b

.-uni

t:a)

C.b.

-uni

t in

test

pos

ition:

Earth

. swi

tch

can

be o

pera

ted

b)Ea

rth. s

witc

h op

en p

ositio

n:

C.b.

-uni

t can

be

mov

ed in

the

serv

ice p

ositio

n

-S1

Auxil

iary

swi

tch

on m

echa

nism

-S2

Auxil

iary

swi

tch

on b

lock

mag

net -

Y1-S

3 Au

xilia

ry s

witc

h on

swi

tch

shaf

t-S

4 Au

xilia

ry s

witc

h on

swi

tch

shaf

t-S

5 Au

xilia

ry s

witc

h on

swi

tch

shaf

t-S

7 Fl

eetin

g co

ntac

t 35

ms f

or c.

b. tr

ipped

indic

ation

-S8

Lim

it sw

itch

test

pos

ition

-S9

Lim

it sw

itch

serv

ice p

ositio

n

BA 414-07_GB_AMC.indd 25 18.07.12 10:25

Page 26: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

26 27

Figu

re 5

/9:

Wiri

ng d

iagr

am fo

r V

D4

vacu

um c

ircui

t-b

reak

er o

n m

otor

driv

en w

ithd

raw

able

ass

emb

ly.

• Ty

pe B

of w

ithdr

awab

le p

art

• M

axim

um o

f equ

ipm

ent

• A

uxilia

ry s

witc

h -S

5 fre

e us

ed•

Con

trol

wiri

ng p

lug

58-p

ole

• U

se in

pan

el s

yste

m U

niG

ear-

Typ

ZS1

• D

raw

ing

no. G

CE2

1327

02P

0101

-S3

21 22 20

-S2

0 231 3213 14

-K0

42

1

-Y3

53 54

-K0

A B

-R0

4 14

13 14

43 44 -Y9

2

-Y4

44

-Y2

30

-Y7

-S4

13 14

1341

4221

2218

53 54

41 42

31 32

21 22238

1131

3243

1553

33

27 371 2

-S7

-Y1

13 14

-S5

43 44

53 54

31 32

21 2229 39

289

76

1719

38

1114 48

5458

565557

1049

44

18-X

15

5145

50

16

7-X

92

41

8-X

53

6

1217

-X

-S8

53 54

43 44

33 34

13 14

-S9

53 54

43 44

33 34

140

13 14

26-X

0

-S1

22 21

53 54

32 31 -M0

M

24

41 42

36-X

034

352532 12M

-M1

5-X

1

7-X

1

16

52 53

1347

21 22

21 22

GN WH

-V1

-V3

-V9

-V4

-V2

~~+

-

+-

~~~ ~

+-

--

++

~~

~~

SER

VIC

E-PO

SITI

ON

TEST

-PO

SITI

ON

Mod

e of

pre

sent

atio

n:

•Au

x. s

witc

h -S

1 sh

own

for c

.b.-m

echa

nism

dis

char

ged

•C

.b.-u

nit i

n se

rvic

e po

sitio

n•

Con

trol w

iring

plu

g 58

-pol

e•

Earth

ing

switc

h m

echa

nica

l int

erlo

ck w

ith c

.b.-u

nit:

a)C

.b.-u

nit i

n te

st p

ositi

on:

Earth

. sw

itch

can

be o

pera

ted

b)Ea

rth. s

witc

h op

en p

ositi

on:

C.b

.-uni

t can

be

mov

ed in

the

serv

ice

posi

tion

*)C

onn

ectio

n p

oin

ts w

hen

und

ervo

ltag

e re

leas

e -Y

4o

r in

dire

ct o

verc

urre

nt r

elea

se -

Y7

are

fitte

t:-Y

4: 4

2-43

-Y7:

42-

43

AE

OFF

ON

P

-Y1

Clo

sing

blo

ck m

agne

t with

rect

ifier

-V1

-Y2

1. S

hunt

rele

ase

OFF

with

rect

ifier

-V2

-Y3

Clo

sing

rele

ase

with

rect

ifier

-V3

-Y4

Und

ervo

ltage

rele

ase

U<

with

rect

ifier

-V4

-Y7

Indi

rect

ove

rcur

rent

rele

ase

-Y9

2. S

hunt

rele

ase

OFF

with

rect

ifier

-V9

-M0

Cha

rgin

g m

otor

-K0

Antip

umpi

ng re

lay

*)*)

*)*)

-S1

Auxi

liary

sw

itch

on m

echa

nism

-S2

Auxi

liary

sw

itch

on b

lock

mag

net -

Y1-S

3 Au

xilia

ry s

witc

h on

sw

itch

shaf

t-S

4 Au

xilia

ry s

witc

h on

sw

itch

shaf

t-S

5 Au

xilia

ry s

witc

h on

sw

itch

shaf

t-S

7 Fl

eetin

g co

ntac

t 35

ms

for c

.b. t

rippe

d in

dica

tion

-S8

Lim

it sw

itch

test

pos

ition

-S9

Lim

it sw

itch

serv

ice

posi

tion

-M1

Mot

or d

rive

for d

raw

out

BA 414-07_GB_AMC.indd 26 18.07.12 10:25

Page 27: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

26 2727

Figu

re 5

/10:

Wiri

ng d

iagr

am fo

r V

D4

vacu

um c

ircui

t-b

reak

er o

n m

anua

lly m

ovea

ble

with

dra

wab

le a

ssem

bly

.

• Ty

pe B

of w

ithdr

aw p

art o

r/an

d w

ith a

uxilia

ry s

witc

h -S

6 at

with

draw

able

par

t•

Max

imum

of e

quip

men

t•

Con

trol

wiri

ng p

lug

64-p

ole

• U

se in

pan

el s

yste

mZS

, Uni

Gea

r-Ty

p ZS

1•

Dra

win

g no

. GC

E200

9153

SER

VIC

E-PO

SITI

ON

TEST

-PO

SITI

ON

-X0

A7A1

6A1

S122

5332

2154

-M0

31

-S6

OFF

C9

-S3

22

-K0

213 4

141324

1

C15

A5B1

5A1

0

-S7

1

C3

2

1343

1444

C5

B4B5

A12

B13

B2B7

B9B1

1A1

5

-X7

C14

D11

D7

D5

C7

D9

D15

92

D2

5343

-S8

3354

4423

34

4 24 58

3

131 14 6-X

-X

D10

-S9

53

-X12

1713 D12

D16

23 2434

13 14

D4

43

54

33

14

44

D3

1516

D8

D6

D1

C16

1811

1422

4454

4232

-S5

4132

5321

5321

1331

4354

2231

B8B1

A3B1

0B3

B6B1

4A1

4A1

3B1

2C

4A4

-V2

A11

C6

C1

-V4

-Y4

-Y2

A6

-V9

-V3

C2

C8

-K0

-Y9

-Y3

-R0

-S2

2

BA

0

B16

13

-Y7

14-S

4

ON

32315453

-Y1

-Y0

-V1

-V0

41

A2

42

D13

D14

EA

A8A9

-X0

PM

A1

A11

A2A3A4A5A6A7A8A9A10

A12A13A14A15A16

B1

B11

B2B3B4B5B6B7B8B9B10

B12B13B14B15B16

C1

C11

C2C3C4C5C6C7C8C9C10

C12C13C14C15C16

D1

D11

D2D3D4D5D6D7D8D9D10

D12D13D14D15D16

-Q0

-Y0

Bloc

k M

agne

t on

truc

k w

ith re

ctifi

er -V

0-Y

1 C

losi

ng b

lock

mag

net w

ith re

ctifi

er -V

1-Y

2 1.

Shu

nt re

leas

e O

FF w

ith re

ctifi

er -V

2-Y

3 C

losi

ng re

leas

e w

ith re

ctifi

er -V

3-Y

4 U

nder

volta

ge re

leas

e U

< w

ith re

ctifi

er -V

4-Y

7 In

dire

ct o

verc

urre

nt re

leas

e-Y

9 2.

Shu

nt re

leas

e O

FF w

ith re

ctifi

er -V

9-M

0 C

harg

ing

mot

or-K

0 An

tipum

ping

rela

y

-S1

Auxi

liary

sw

itch

on m

echa

nism

-S2

Auxi

liary

sw

itch

on b

lock

mag

net -

Y1-S

3 Au

xilia

ry s

witc

h on

sw

itch

shaf

t-S

4 Au

xilia

ry s

witc

h on

sw

itch

shaf

t-S

5 Au

xilia

ry s

witc

h on

sw

itch

shaf

t-S

6Au

xilia

ry s

witc

h at

c.b

.-uni

t-S

7 Fl

eetin

g co

ntac

t 35

ms

for c

.b. t

rippe

d in

dica

tion

-S8

Lim

it sw

itch

test

pos

ition

-S9

Lim

it sw

itch

serv

ice

posi

tion

Mod

e of

pre

sent

atio

n:•

Aux.

sw

itch

-S1

show

n fo

r c.b

.-mec

hani

sm d

isch

arge

d•C

.b.-u

nit i

n se

rvic

e po

sitio

n•C

ontro

l wiri

ng p

lug

64-p

ole

•Ea

rthin

g sw

itch

mec

hani

cal i

nter

lock

with

c.b

.-uni

t:a)

C.b

.-uni

t in

test

pos

ition

:Ea

rth. s

witc

h ca

n be

ope

rate

db)

Earth

. sw

itch

open

pos

ition

: C

.b.-u

nit c

an b

e m

oved

in th

e se

rvic

e po

sitio

n

BA 414-07_GB_AMC.indd 27 18.07.12 10:25

Page 28: Instruction manual BA 414/07 E VD4 Vacuum circuit … Vacuum circuit-breaker on withdrawable part – high duty Instruction manual BA 414/07 E Contents 1 Summary 5 2 Technical data

MA

_VD

4-W

HD

(EN

)-_1

VC

D60

1411

- 16

01 (G

S)ABB S.p.A.

Electrification Products Division Medium Voltage Products Via Friuli, 4 I-24044 Dalmine Tel.: +39 035 6952 111 Fax: +39 035 6952 874 E-mail: [email protected]

ABB AGCalor Emag Medium Voltage ProductsOberhausener Strasse 33 Petzower Strasse 840472 Ratingen 14542 Werder (Havel) OT GlindowGERMANY GERMANYTel.: 02102 12-0Fax: 02102 12-17 77E-Mail: [email protected]

www.abb.com/mediumvoltage

The data and illustrations are not binding. We reserve the right to modify the contents of this document without prior notice following technical and product developments.

© Copyright 2016 ABB. All rights reserved.