Installer's Guide Convertible Air Handlers 2-5 Ton TEM6
Transcript of Installer's Guide Convertible Air Handlers 2-5 Ton TEM6
SSAAFFEETTYY WWAARRNNIINNGGOnly qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, andair-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or alteredequipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in theliterature and on the tags, stickers, and labels that are attached to the equipment.
March 2018 1188--GGFF7744DD11--11KK--EENN
Convertible Air Handlers2 — 5 TonTEM6A0B24H21SBTEM6A0B30H21SBTEM6A0C36H31SBTEM6A0C42H41SBTEM6A0C48H41SBTEM6A0D48H41SBTEM6A0C60H51SBTEM6A0D60H51SB
The TEM6 series air handler is designed for installation in a closet,utility room, alcove, basement, crawlspace or attic. These versatileunits are applicable to air conditioning and heat pumpapplications. Several models are available to meet the specificrequirements of the outdoor equipment. Field installed electricresistance heaters are available.
Installer’s Guide
©2018 Ingersoll Rand 18-GF74D1-1K-EN
SAFETY SECTIONAIR HANDLERSIImmppoorrttaanntt:: This document contains a wiring diagram,
a parts list, and service information. This iscustomer property and is to remain withthis unit. Please return to serviceinformation pack upon completion of work.
IImmppoorrttaanntt:: These instructions do not cover allvariations in systems nor provide for everypossible contingency to be met inconnection with the installation. Shouldfurther information be desired or shouldparticular problems arise which are notcovered sufficiently for the purchaser’spurposes, the matter should be referred toyour installing dealer or local distributor.
WWAARRNNIINNGGHHAAZZAARRDDOOUUSS VVOOLLTTAAGGEE!!FFaaiilluurree ttoo ffoollllooww tthhiiss WWaarrnniinngg ccoouulldd rreessuulltt iinnpprrooppeerrttyy ddaammaaggee,, sseevveerree ppeerrssoonnaall iinnjjuurryy,, oorrddeeaatthh..DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmootteeddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerrlloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerrccaannnnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd..
CCAAUUTTIIOONNGGRROOUUNNDDIINNGG RREEQQUUIIRREEDD!!FFaaiilluurree ttoo iinnssppeecctt oorr uussee pprrooppeerr sseerrvviiccee ttoooollss mmaayyrreessuulltt iinn eeqquuiippmmeenntt ddaammaaggee oorr ppeerrssoonnaall iinnjjuurryy..RReeccoonnnneecctt aallll ggrroouunnddiinngg ddeevviicceess.. AAllll ppaarrttss ooff tthhiisspprroodduucctt tthhaatt aarree ccaappaabbllee ooff ccoonndduuccttiinngg eelleeccttrriiccaallccuurrrreenntt aarree ggrroouunnddeedd.. IIff ggrroouunnddiinngg wwiirreess,, ssccrreewwss,,ssttrraappss,, cclliippss,, nnuuttss,, oorr wwaasshheerrss uusseedd ttoo ccoommpplleettee aappaatthh ttoo ggrroouunndd aarree rreemmoovveedd ffoorr sseerrvviiccee,, tthheeyy mmuussttbbee rreettuurrnneedd ttoo tthheeiirr oorriiggiinnaall ppoossiittiioonn aanndd pprrooppeerrllyyffaasstteenneedd..
WWAARRNNIINNGGLLIIVVEE EELLEECCTTRRIICCAALL CCOOMMPPOONNEENNTTSS!!FFaaiilluurree ttoo ffoollllooww tthhiiss WWaarrnniinngg ccoouulldd rreessuulltt iinnpprrooppeerrttyy ddaammaaggee,, sseevveerree ppeerrssoonnaall iinnjjuurryy,, oorrddeeaatthh..FFoollllooww aallll eelleeccttrriiccaall ssaaffeettyy pprreeccaauuttiioonnss wwhheenneexxppoosseedd ttoo lliivvee eelleeccttrriiccaall ccoommppoonneennttss.. IItt mmaayy bbeenneecceessssaarryy ttoo wwoorrkk wwiitthh lliivvee eelleeccttrriiccaall ccoommppoonneennttssdduurriinngg iinnssttaallllaattiioonn,, tteessttiinngg,, sseerrvviicciinngg,, aannddttrroouubblleesshhoooottiinngg ooff tthhiiss pprroodduucctt..
WWAARRNNIINNGGPPRREESSSSUURRIIZZEEDD RREEFFRRIIGGEERRAANNTT!!FFaaiilluurree ttoo ffoollllooww tthhiiss WWaarrnniinngg ccoouulldd rreessuulltt iinnppeerrssoonnaall iinnjjuurryySSyysstteemm ccoonnttaaiinnss ooiill aanndd rreeffrriiggeerraanntt uunnddeerr hhiigghhpprreessssuurree.. RReeccoovveerr rreeffrriiggeerraanntt ttoo rreelliieevvee pprreessssuurreebbeeffoorree ooppeenniinngg tthhee ssyysstteemm.. DDoo nnoo uussee nnoonn--aapppprroovveedd rreeffrriiggeerraannttss oorr rreeffrriiggeerraanntt ssuubbssttiittuutteess oorrrreeffrriiggeerraanntt aaddddiittiivveess..
CCAAUUTTIIOONNSSHHAARRPP EEDDGGEE HHAAZZAARRDD!!FFaaiilluurree ttoo ffoollllooww tthhiiss CCaauuttiioonn ccoouulldd rreessuulltt iinnpprrooppeerrttyy ddaammaaggee oorr ppeerrssoonnaall iinnjjuurryy..BBee ccaarreeffuull ooff sshhaarrpp eeddggeess oonn eeqquuiippmmeenntt oorr aannyyccuuttss mmaaddee oonn sshheeeett mmeettaall wwhhiillee iinnssttaalllliinngg oorrsseerrvviicciinngg..
CCAAUUTTIIOONNHHAAZZAARRDDOOUUSS VVAAPPOORRSS!!FFaaiilluurree ttoo ffoollllooww tthhiiss ccaauuttiioonn ccoouulldd rreessuulltt iinnpprrooppeerrttyy ddaammaaggee oorr ppeerrssoonnaall iinnjjuurryy..EEqquuiippmmeenntt ccoorrrroossiioonn ddaammaaggee.. TToo pprreevveennttsshhoorrtteenniinngg iittss sseerrvviiccee lliiffee,, tthhee aaiirr hhaannddlleerr sshhoouullddnnoott bbee uusseedd dduurriinngg tthhee ffiinniisshhiinngg pphhaasseess ooffccoonnssttrruuccttiioonn oorr rreemmooddeelliinngg.. TThhee llooww rreettuurrnn aaiirrtteemmppeerraattuurreess ccaann lleeaadd ttoo tthhee ffoorrmmaattiioonn ooffccoonnddeennssaattee.. CCoonnddeennssaattee iinn tthhee pprreesseennccee ooffcchhlloorriiddeess aanndd fflluuoorriiddeess ffrroomm ppaaiinntt,, vvaarrnniisshh,, ssttaaiinnss,,aaddhheessiivveess,, cclleeaanniinngg ccoommppoouunnddss,, aanndd cceemmeennttccrreeaatteess aa ccoorrrroossiivvee ccoonnddiittiioonn wwhhiicchh mmaayy ccaauusseerraappiidd ddeetteerriioorraattiioonn ooff tthhee ccaabbiinneett aanndd iinntteerrnnaallccoommppoonneennttss..
CCAAUUTTIIOONNCCOOIILL IISS PPRREESSSSUURRIIZZEEDD!!•• CCooiill iiss pprreessssuurriizzeedd wwiitthh aapppprrooxxiimmaatteellyy 88––1122 ppssiiddrryy aaiirr aanndd ffaaccttoorryy cchheecckkeedd ffoorr lleeaakkss..•• CCaarreeffuullllyy rreelleeaassee tthhee pprreessssuurree bbyy rreemmoovviinngg tthheerruubbbbeerr pplluugg oonn tthhee lliiqquuiidd lliinnee..•• IIff nnoo pprreessssuurree iiss rreelleeaasseedd,, cchheecckk ffoorr lleeaakkss..
18-GF74D1-1K-EN 3
WWAARRNNIINNGGSSAAFFEETTYY HHAAZZAARRDD!!FFiibbeerrggllaassss dduusstt aanndd cceerraammiicc ffiibbeerrss aarree bbeelliieevveedd bbyytthhee ssttaattee ooff CCaalliiffoorrnniiaa ttoo ccaauussee ccaanncceerr tthhrroouugghhiinnhhaallaattiioonn.. GGllaasssswwooooll ffiibbeerrss mmaayy aallssoo ccaauusseerreessppiirraattoorryy,, sskkiinn,, oorr eeyyee iirrrriittaattiioonn..PPRREECCAAUUTTIIOONNAARRYY MMEEAASSUURREESS•• AAvvooiidd bbrreeaatthhiinngg ffiibbeerrggllaassss dduusstt•• UUssee aa NNIIOOSSHH aapppprroovveedd dduusstt//mmiisstt rreessppiirraattoorr•• AAvvooiidd ccoonnttaacctt wwiitthh tthhee sskkiinn oorr eeyyeess.. WWeeaarr lloonngg--sslleeeevveedd,, lloooossee ffiittttiinngg ccllootthhiinngg,, gglloovveess,, aanndd eeyyeepprrootteeccttiioonn•• WWaasshh ccllootthheess sseeppaarraatteellyy ffrroomm ootthheerr ccllootthhiinngg,,rriinnssee wwaasshheerr tthhoorroouugghhllyy•• OOppeerraattiioonnss ssuucchh aass ssaawwiinngg,, bblloowwiinngg,, tteeaarr--oouutt,,aanndd sspprraayyiinngg mmaayy ggeenneerraattee ffiibbeerr ccoonncceennttrraattiioonnssrreeqquuiirriinngg aaddddiittiioonnaall rreessppiirraattoorryy pprrootteeccttiioonn.. UUsseetthhee aapppprroopprriiaattee NNIIOOSSHH aapppprroovveedd rreessppiirraattoorr iinntthheessee ssiittuuaattiioonnssFFIIRRSSTT AAIIDD MMEEAASSUURREESS•• EEYYEE CCOONNTTAACCTT:: FFLLUUSSHH EEYYEESS WWIITTHH WWAATTEERR TTOORREEMMOOVVEE DDUUSSTT.. IIFF SSYYMMPPTTOOMMSS PPEERRSSIISSTT,, SSEEEEKKMMEEDDIICCAALL AATTTTEENNTTIIOONN..•• SSKKIINN CCOONNTTAACCTT:: WWAASSHH AAFFFFEECCTTEEDD AARREEAAGGEENNTTLLYY WWIITTHH SSOOAAPP AANNDD WWAARRMM WWAATTEERR AAFFTTEERRHHAANNDDLLIINNGG..TThhiiss wwaarrnniinngg ccoommpplliieess wwiitthh ssttaattee ooff CCaalliiffoorrnniiaa llaaww,,PPrrooppoossiittiioonn 6655..
WWAARRNNIINNGGSSAAFFEETTYY HHAAZZAARRDD!!TThhiiss aapppplliiaannccee iiss nnoott ttoo bbee uusseedd bbyy ppeerrssoonnss((iinncclluuddiinngg cchhiillddrreenn)) wwiitthh rreedduucceedd pphhyyssiiccaall,,sseennssoorryy,, oorr mmeennttaall ccaappaabbiilliittiieess,, oorr llaacckk ooffeexxppeerriieennccee aanndd kknnoowwlleeddggee,, uunnlleessss tthheeyy hhaavvee bbeeeennggiivveenn ssuuppeerrvviissiioonn oorr iinnssttrruuccttiioonn..
WWAARRNNIINNGGSSAAFFEETTYY HHAAZZAARRDD!!CChhiillddrreenn sshhoouulldd bbee ssuuppeerrvviisseedd ttoo eennssuurree tthhaatt tthheeyyddoo nnoott ppllaayy wwiitthh tthhee aapppplliiaannccee..
IImmppoorrttaanntt:: Installation of this unit shall be made inaccordance with the National Electric Code,NFPA No. 90A and 90B, and any other localcodes or utilities requirements.
IImmppoorrttaanntt:: Air handlers do not require repositioning ofthe coil or drain pan for upflow orhorizontal left applications. See thedownflow and horizontal right installationsections for application instructions.
NNoottee:: Air handlers have been evaluated in accordancewith the Code of Federal Regulations, ChapterXX, Part 3280 or the equivalent. “SUITABLE FORMOBILE HOME USE.”
NNoottee:: Condensation may occur on the surface of the airhandler when installed in an unconditionedspace. When units are installed in unconditionedspaces, verify that all electrical and refrigerantline penetrations on the air handler are sealedcompletely.
NNoottee:: The manufacturer recommends installing ONLYA.H.R.I approved, matched indoor and outdoorsystems. Some of the benefits of installingapproved matched indoor and outdoor splitsystems are maximum efficiency, optimumperformance, and the best overall systemreliability.
SSAAFFEETTYY SSEECCTTIIOONN AAIIRR HHAANNDDLLEERRSS
4 18-GF74D1-1K-EN
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Installation Instructions . . . . . . . . . . . . . . . . . . . 5
Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Performance and Electrical Data . . . . . . . . . . . 12
Minimum Airflow CFM . . . . . . . . . . . . . . . . . . . . 21
Outline Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Heater Pressure Drop Table . . . . . . . . . . . . . . . 24Subcooling Adjustment . . . . . . . . . . . . . . . . . . 24
Subcooling Adjustment forTEM6A0C48H41 & TEM6A0C60H51 . . . . . . . 24
Coil Conversion Instructions. . . . . . . . . . . . . . . 25Coil Conversion . . . . . . . . . . . . . . . . . . . . . . . . . 29
Checkout Procedures . . . . . . . . . . . . . . . . . . . . . . 37
Table of Contents
18-GF74D1-1K-EN 5
FeaturesTable 1. Standard Features
• MULTI-POSITION UPFLOW, DOWNFLOW, HORIZONTAL LEFTAND HORIZONTAL RIGHT
• PAINTED FINISH ON GALVANIZED STEEL EXTERIOR WITHFULLY INSULATED CABINET THAT MEETS R4.2 VALUE
• STURDY POLYCARBONATE DRAIN PANS
– These air handlers have factory installed drain pans andare shipped for upflow and horizontal left applications
• 208/230 VAC OPERATION
• VARIABLE-SPEED DIRECT DRIVE BLOWER.
• FACTORY INSTALLED R-410ATHERMAL EXPANSION VALVE
• ALL ALUMINUM COIL
• BOTTOM RETURN
• MEETS THE MINIMUM LEAKAGE REQUIREMENTS FOR THEFLORIDA AND CALIFORNIA BUILDING CODES
Table 2. Optional Accessories
• 4,5,8,10,15,20, and 25 KW SINGLE PHASE ELECTRICHEATERS
– Circuit breakers available on single phase 4, 5, 8, 10,15, 20, and 25 KW heaters
– Lugs available on single phase 4, 5, 8, and 10 KWheaters
– Lugs available on three phase 10 and 15 KW heaters
• SINGLE POINT POWER ENTRY KIT (for 15 and 20 KWheaters)
• SUPPLY DUCT FLANGE KIT
• DOWNFLOW SUB-BASE KITS -TAYBASE185, TAYBASE235,TAYBASE260
• SLIM FIT FILTER BOX KIT— BAYSF1185AAA,BAYSF1235AAA, BAYSF1265AAA
Installation Instructions1. UUnnppaacckkiinngg
Carefully unpack the unit and inspect the contentsfor damage. If any damage is found at the time ofdelivery, proper notification and claims should bemade with the carrier.
Check the rating plate to assure model number andvoltage, plus any kits match with what you ordered.The manufacturer should be notified within 5 daysof any discrepancy or parts shortage.
2. LLooccaattiioonn
The air handler should be centrally located and maybe installed in a closet, alcove, utility room,basement, crawl space or attic. Minimumclearances must be met.
IImmppoorrttaanntt:: The downflow sub-base may berequired with electric heat applications.See minimum clearance table.
The unit should be installed in a level position toensure proper condensation drainage. Up to an
additional 1/4” rise over the width or depth of theunit is allowed to create additional sloping towardsthe drain. Unit must be positioned between leveland ¼” rise, sloping toward the drain connections.
When the unit is installed in a closet or utility room,the room should be large enough, and have anopening to allow replacement of the unit. Allservicing is done from the front and a clearance of21" is needed for service unless the closet dooraligns with the front of the air handler.
If you are installing the unit in an unconditionedspace such as an attic or crawl space, you mustensure that the area provides sufficient aircirculation to prevent moisture collection on thecabinet during high dew point conditions. A drainpan must be installed under the entire unit when itis installed in or above a finished ceiling or in anunconditioned space.
3. DDuucctt WWoorrkk
The duct work should be installed in accordancewith the NFPA No. 90A "Installation of AirConditioning and Ventilating systems" and No. 90B"Residential Type Warm Air Heating and AirConditioning Installation."
The duct work should be insulated in accordancewith the applicable requirements for the particularinstallation as required by HUD, FHA, VA theapplicable building code, local utility or othergoverning body.
4. CCoonnddeennssaattee DDrraaiinn
The unit is supplied with primary and auxiliarycondensate drains that have 3/4" NPT connections.The primary drain must be trapped outside the unitand piped in accordance with applicable buildingcodes.
The figure shows the operation of a properlydesigned trap under normal operating conditionswhen the blower is running and the condensate isdraining. Note the difference in height of the watercolumn must at least equal the normal negativestatic pressure existing during operation betweenthe cooling coil and blower. It is advisable to havethe difference in water column height somewhatgreater than the normal maximum operating staticto allow for greater static caused by dirty filters orfor the bounce of the water column on start up.
6 18-GF74D1-1K-EN
NegativePressure
BlowerRunning
Drain Pan
“C”“A”
To Drain
Proper operation of condensate trap undernormal operating conditions.
“A” height of water column equalsnegative static pressure existing in system.
“C” dimension should at least equal twotimes the maximum negative static pressurethat can occur in system.
Do not reduce the drain line size less than theconnection size on the drain pan. Condensateshould be piped to an open drain or to the outside.All drains must pitch downward away from the unita minimum of 1/4" per foot of line to ensure properdrainage.
IImmppoorrttaanntt:: If cleanout Tee is used, stand pipe mustbe sealed/capped.
IImmppoorrttaanntt:: If a vent Tee is used, it must bedownstream from the trap.
To Drain
Vent-This vent pipe MUST terminate above the dotted line Cleanout
(with Cap)
Cleanout(Plug)
Insulate the primary drain line to prevent sweatingwhere dew point temperatures may be met.(Insulation is optional depending on climate andapplication needs.)
5. RReeffrriiggeerraanntt PPiippiinngg
Refrigerant piping external to the unit shall be sizedin accordance with the instructions of themanufacturer of the outdoor equipment.
6. MMeetteerriinngg DDeevviiccee
All units are shipped and installed with aninternally-checked, non-bleed TXV designed for airconditioning or heat pump operation. Someoutdoor models may require a start assist kit. Seeoutdoor unit for more information.
7. BBlloowweerr
This unit is supplied with a variable speed motorwith a direct drive blower wheel which can obtainvarious air flows. The unit is shipped with factoryset cooling and heating air flows. Performancetables are available for additional airflow settings.Disconnect all power to the unit before making anyadjustments to the airflow settings. Be sure tocheck the air flow and the temperature drop acrossthe evaporator coil to ensure sufficient air flow.
8. AAiirrffllooww AAddjjuussttmmeenntt
CCAAUUTTIIOONNEEQQUUIIPPMMEENNTT DDAAMMAAGGEE!!FFaaiilluurree ttoo ffoollllooww tthhiiss pprroocceedduurree mmaayy rreessuulltt iinneeqquuiippmmeenntt ddaammaaggee..DDiissccoonnnneecctt ppoowweerr ttoo tthhee aaiirr hhaannddlleerr bbeeffoorreecchhaannggiinngg ddiipp sswwiittcchh ppoossiittiioonnss..
Blower speed changes are made on the ECM FanControl. The ECM Fan Control controls the variablespeed motor.
There is a bank of 8 dip switches. The dip switcheswork in pairs to match the airflow for the outdoorunit size (tons). cooling airflow adjustment, Fan off-delay options, and heating airflow adjustment. Theswitches appear as shown in Figure 2, p. 7
Figure 1. ECM Fan Control
CFM SELECTIONLIGHT
DIP SWITCHES
FFeeaattuurreess
18-GF74D1-1K-EN 7
Figure 2. Dip Switches
DIP SWITCHES (TYPICAL SETTINGS)
COOLING HEATING
AIRFLOW
FAN OFFDELAY
AUXILARYHEAT SPEEDS
If the airflow needs to be increased or decreased,see the Airflow Label on the air handler or BlowerPerformance Table.
Be sure to set the correct airflow for cooling andheating.
Switches 1–4 Cooling Airflow
Switches 5–6 Fan Off Delay Options
Switches 7–8 Auxiliary Heat
IInnddoooorr BBlloowweerr TTiimmiinngg
IImmppoorrttaanntt:: Leave dip switches 5 and 6 in the “as-shipped” positions during system start-up and check out. Afterwards, adjust asdesired.
Table 3. Cooling Off — Delay Options
SWITCH SETTINGS SELECTION NOMINALAIRFLOW
5— OFF 6 — OFF NONE SAME
5 — ON 6— OFF 1.5 MINUTES 100% (a)
5 — OFF 6— ON 3 MINUTES 50%
5—ON 6— ON ENHANCED(b)
50–100%
(a) Default setting(b) This ENHANCED MODE selection provides a ramping up and ramping
down of the blower speed to provide improved comfort, quietness,and potential energy savings. The graph shows the ramping process.
Figure 3. Enhanced Mode
OFF OFF
50%
80%
100% if necessary
50%
DehumidifyWarm Air Heating
Fast Coil CoolingFast Coil Heating Efficiency
7.5minutes
3minutes
1minute
FA
N O
PE
RA
TIO
N (
CF
M)
as required
COMPRESSOR OPERATION ON OFF
9. WWiirriinngg
Consult all schematic and pictorial wiring diagramsof this unit and the outdoor equipment todetermine compatibility of wiring connections andto determine specific requirements.
All field wiring to the air handler should be installedin accordance with the latest edition of the NationalElectric Code NFPA No. 70 and any local codes.Check rating plates on unit for rated volts,minimum circuit ampacity and maximum overcurrent protection. Supply circuit power wiringmust be 75 degree C (167 degree F) minimumcopper conductors only. Copper supply wires shallbe sized to the National Electric Code or local coderequirements, whichever is more stringent.
The unit is shipped wired for 230/240 Volt AC 60 HZ1 Phase Operation. If the unit is to be operated at208 VAC 60HZ, follow the instructions on the indoorunit wiring diagram to change the low voltagetransformer to 208 VAC operation (Ensure unit isproperly grounded).
Class 2 low voltage control wiring should not be runin conduit with power wiring and must beseparated from power wiring unless class 1 wirewith proper voltage rating is used.
Low voltage control wiring should be 18 Awg, colorcoded (105 degree C minimum). For lengths longerthan 100ft., 16 Awg wire should be used. Makecertain that separation of control wiring and powerwiring has been maintained.
10. AAiirr FFiilltteerr
To protect the coil, blower and other internal partsfrom excessive dirt and dust an air filter must beinstalled before air enters the evaporator coil. Aremote filter must be installed. Consult the filtermanufacturer for proper sizing and maximumvelocity requirements.
IImmppoorrttaanntt:: Air filters shall meet the test requirementsin UL 900.
11. TThheerrmmoossttaatt
Select a thermostat that is commonly used with HPor AC single stage heating/cooling with electricheat. The thermostat will energize the fan on ademand for heat or cool.
Install the thermostat on an inside wall, away fromdrafts, lights or other heat sources in a location thathas sufficient air circulation from other rooms beingcontrolled by the thermostat.
12. SSeeqquueennccee ooff OOppeerraattiioonnCCoooolliinngg ((CCoooolliinngg oonnllyy))
When the thermostat calls for cooling, the circuitfrom R to G is completed. The blower motor isenergized directly by the ECM fan control, whichreceives the 24VAC signal from the thermostat.
The circuit from R to Y is also complete energizingthe compressor contactor of the outdoor unit. The
FFeeaattuurreess
8 18-GF74D1-1K-EN
contactor will close and start the compressor andcondenser fan motor.
CCoooolliinngg ((hheeaatt ppuummpp))
When the thermostat calls for cooling, the circuitfrom R to G is completed. The blower motor isenergized directly by the ECM fan control, whichreceives the 24VAC signal from the thermostat.
The circuit from R to Y is also complete energizingthe compressor contactor of the outdoor unit. Thecontactor will close and start the compressor andcondenser fan motor.
Circuit R to O energizes the reversing valve to thecooling position.
HHeeaattiinngg ((hheeaatt ppuummpp))
When the thermostat calls for heating, the circuitfrom R to G is completed and the blower motor isenergized directly by the ECM fan control, whichreceives the 24VAC signal from the thermostat.
The circuit from R to Y is also complete energizingthe compressor contactor of the outdoor unit. Thecontactor will close and start the compressor andcondenser fan motor.
In the heating mode, the reversing valve of theoutdoor unit is not energized.
If the indoor temperature continues to fall, the R toW circuit is completed energizing the electric heatcontactor(s).
HHeeaattiinngg ((eelleeccttrriicc hheeaatt oonnllyy))
NNoottee:: The thermostat must be setup to bring theblower on when the electric heat is energized.
When the thermostat calls for heating, the circuitfrom R to G is completed and the blower motor isenergized directly by the ECM fan control, whichreceives the 24VAC signal from the thermostat. Thecircuit from R to W is completed energizing theheating contactor(s).
DDeeffrroosstt
Supplemental heat during defrost can be providedby connecting the X2 (black) wire from the outdoorunit to W1 or W2 at the indoor unit. This willprevent cold air from being discharged from theindoor unit during defrost.
13. OOppeerraattiioonnaall aanndd CChheecckkoouutt PPrroocceedduurreess
To obtain proper performance, all units must beoperated and charge adjustments made inaccordance with procedures found in the ServiceFacts document of the outdoor unit. Afterinstallation has been completed, it is recommendedthat the entire system be checked against thecheckout list located at the back of this document.See “Checkout Procedures,” p. 37
14. MMaaiinntteennaannccee
The system air filter(s) should be inspected, cleanedor replaced at least monthly. Make certain that theaccess panels are replaced and secured properlybefore placing the unit back in operation. Thisproduct is designed for dependable service;however, periodic maintenance should bescheduled and conducted by trained professionalservice personnel. This service should beconducted at least annually, and should includetesting and inspection of electrical and refrigerantcomponents. The heat transfer surface should becleaned. The blower motor is permanentlylubricated for normal operating conditions.
FFeeaattuurreess
18-GF74D1-1K-EN 9
Field Wiring
Single Stage, Cooling Only
Thermostat Air Handler OutdoorUnit
R
G
B
W1
W2
B
Y
R
G
B
Y
W1
Blue
24 VAC HOT
FAN
24 VAC Common
SOV
COOL/HEAT1st STAGE
HEATING2nd STAGE
EMERGENCYHEAT
White
White
W2
O
Y1
1. * Units with pigtails require wirenuts for connections.2. Cap all unused wires.3. For BK enabled comfort control, do not connect Y1 or Y2 at the air handler
Y2
BKWH/BLK
4. For BK enabled comfort control, cut the jumper wire between R and BK on the control board. See wiring schematic for details.5. In AC systems for multiple stages of electric heat, jumper W1 and W2 together if comfort control has only one stage of heat.
Single Stage, HP
Thermostat Air Handler OutdoorUnit
R
G
B
W1
W2
R
B
O
Y
X2
R
G
B
O
Y
W1
Blue
24 VAC HOT
FAN
24 VAC Common
SOV
COOL/HEAT1st STAGE
HEATING2nd STAGE
EMERGENCYHEAT
White
BlackWhite
W2
O
Y1
Y2
BK
Optional
WH/BLK
1. * Units with pigtails require wirenuts for connections.2. Cap all unused wires.3. For BK enabled comfort control, do not connect Y1 or Y2 at the air handler4. For BK enabled comfort control, cut the jumper wire between R and BK on the control board. See wiring schematic for details.5. In systems for multiple stages of electric heat, jumper W1 and W2 together if comfort control has only one stage of heat.
10 18-GF74D1-1K-EN
2 Stage, 2 Step, Cooling Only
Thermostat Air Handler OutdoorUnit
R
G
B
W1
W2
B
Y1
R
G
B
Y1
W1
Blue
24 VAC HOT
FAN
24 VAC Common
COOL/HEAT1st STAGE
HEATING2nd STAGE
EMERGENCYHEAT
White
White
W2
O
Y1
Y2
BK
Y2 Y2
WH/BLK
1. * Units with pigtails require wirenuts for connections.2. Cap all unused wires.3. For BK enabled comfort control, do not connect Y1 or Y2 at the air handler4. For BK enabled comfort control, cut the jumper wire between R and BK on the control board. See wiring schematic for details.5. In AC systems for multiple stages of electric heat, jumper W1 and W2 together if comfort control has only one stage of heat.
2 Stage, 2 Step, HP
Thermostat Air Handler OutdoorUnit
R
G
B
W1
W2
R
B
O
Y1
X2
R
G
B
O
Y1
W1
Blue
24 VAC HOT
FAN
24 VAC Common
SOV
COOL/HEAT1st STAGE
HEATING2nd STAGE
EMERGENCYHEAT
White
BlackWhite
W2
O
Y1
Y2
BKOptional
Y2Y2
WH/BLK
1. * Units with pigtails require wirenuts for connections.2. Cap all unused wires.3. For BK enabled comfort control, do not connect Y1 or Y2 at the air handler4. For BK enabled comfort control, cut the jumper wire between R and BK on the control board. See wiring schematic for details.5. In systems for multiple stages of electric heat, jumper W1 and W2 together if comfort control has only one stage of heat.
FFiieelldd WWiirriinngg
18-GF74D1-1K-EN 11
Electrical Data
12 18-GF74D1-1K-EN
Performance and Electrical Data
Table 4. Air Flow Performance
TEM6A0B24H21SB COOLING AIRFLOWPERFORMANCE, WET COIL, NO FILTER, NO HEATEROUTDOORUNIT SIZE(TONS)
SPEEDSETTING
AIRFLOWSETTING
DIP SWITCH SETTING AIRFLOWPOWER
EXTERNAL STATIC PRESSURE
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
1.5
LOW 353 CFM/ton ON ON OFF ON CFM
Watts53352
49778
461104
425130
390157
NORMAL 401 CFM/ton ON ON OFF OFF CFM
Watts61165
58095
548125
517155
486185
HIGH 451 CFM/ton ON ON ON OFF CFM
Watts68481
668115
644148
611182
570215
2
LOW 343 CFM/ton OFF ON OFF ON CFM
Watts68782
672115
648149
614182
571215
NORMAL 390 CFM/ton OFF ON OFF OFF CFM
Watts789104
798145
780183
735216
663246
HIGH 439 CFM/ton OFF ON ON OFF CFM
Watts884135
887177
882230
845274
751290
2.5
LOW 300 CFM/ton ON OFF OFF ON CFM
Watts75292
749123
729167
691211
636241
NORMAL(a)
340 CFM/ton OFF OFF OFF OFF CFM
Watts859128
861172
863211
830242
727268
HIGH 383 CFM/ton ON OFF ON OFF CFM
Watts963172
973223
995263
967291
844308
(a) Factory Default Setting
Table 5. Air Flow Performance
TEM6A0B24H21SB HEATING AIRFLOW PERFORMANCE, NO FILTER, NO HEATEROUTDOORUNIT SIZE(TONS)
SPEEDSETTING
AIRFLOWSETTING
DIP SWITCH SETTING AIRFLOWPOWER
EXTERNAL STATIC PRESSURE
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
1.5
LOW 394 CFM/ton ON ON OFF ON CFM
Watts59958
57188
539117
502146
462175
NORMAL 448 CFM/ton ON ON OFF OFF CFM
Watts68072
665109
641145
610178
572209
HIGH 493 CFM/ton ON ON ON OFF CFM
Watts74889
746118
682163
545208
326240
2
LOW 393 CFM/ton OFF ON OFF ON CFM
Watts78597
790128
773175
735223
674253
NORMAL 446 CFM/ton OFF ON OFF OFF CFM
Watts904131
902179
912219
894253
809281
HIGH 491 CFM/ton OFF ON ON OFF CFM
Watts980167
972216
990268
974308
863324
2.5
LOW 350 CFM/ton ON OFF OFF ON CFM
Watts866125
870162
866215
833263
750286
NORMAL(a)
398 CFM/ton ON OFF OFF OFF CFM
Watts995171
988222
1005271
986309
872325
HIGH 437 CFM/ton ON OFF ON OFF CFM
Watts1099220
1086274
1098328
1065362
918353
(a) Factory Default Setting
18-GF74D1-1K-EN 13
Table 6. Air Flow Performance
TEM6A0B30H21SB COOLING AIRFLOWPERFORMANCE, WET COIL, NO FILTER, NO HEATEROUTDOORUNIT SIZE(TONS)
SPEEDSETTING
AIRFLOWSETTING
DIP SWITCH SETTING AIRFLOWPOWER
EXTERNAL STATIC PRESSURE
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
1.5
LOW 353 CFM/ton ON ON OFF ON CFM
Watts53352
49778
461104
425130
390157
NORMAL 401 CFM/ton ON ON OFF OFF CFM
Watts61165
58095
548125
517155
486185
HIGH 451 CFM/ton ON ON ON OFF CFM
Watts68481
668115
644148
611182
570215
2
LOW 343 CFM/ton OFF ON OFF ON CFM
Watts68782
672115
648149
614182
571215
NORMAL 390 CFM/ton OFF ON OFF OFF CFM
Watts789104
798145
780183
735216
663246
HIGH 439 CFM/ton OFF ON ON OFF CFM
Watts884135
887177
882230
845274
751290
2.5
LOW 300 CFM/ton ON OFF OFF ON CFM
Watts75292
749123
729167
691211
636241
NORMAL 340 CFM/ton ON OFF OFF OFF CFM
Watts859128
861172
863211
830242
727268
HIGH 383 CFM/ton ON OFF ON OFF CFM
Watts963172
973223
995263
967291
844308
3LOW 310 CFM/
ton OFF OFF OFF ON CFMWatts
913119
947172
962233
938297
883364
NORMAL(a)
330 CFM/ton OFF OFF OFF OFF CFM
Watts967138
1004194
1022258
1000326
947397
(a) Factory Default Setting
Table 7. Air Flow Performance
TEM6A0B30H21SB HEATING AIRFLOW PERFORMANCE, NO FILTER, NO HEATEROUTDOORUNIT SIZE(TONS)
SPEEDSETTING
AIRFLOWSETTING
DIP SWITCH SETTING AIRFLOWPOWER
EXTERNAL STATIC PRESSURE
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
1.5
LOW 394 CFM/ton ON ON OFF ON CFM
Watts59958
57188
539117
502146
462175
NORMAL 448 CFM/ton ON ON OFF OFF CFM
Watts68072
665109
641145
610178
572209
HIGH 493 CFM/ton ON ON ON OFF CFM
Watts74889
746118
682163
545208
326240
2
LOW 393 CFM/ton OFF ON OFF ON CFM
Watts78597
790128
773175
735223
674253
NORMAL 446 CFM/ton OFF ON OFF OFF CFM
Watts904131
902179
912219
894253
809281
HIGH 491 CFM/ton OFF ON ON OFF CFM
Watts980167
972216
990268
974308
863324
2.5
LOW 350 CFM/ton ON OFF OFF ON CFM
Watts866125
870162
866215
833263
750286
NORMAL 398 CFM/ton ON OFF OFF OFF CFM
Watts995171
988222
1005271
986309
872325
HIGH 437 CFM/ton ON OFF ON OFF CFM
Watts1099220
1086274
1098328
1065362
918353
3LOW 325 CFM/
ton OFF OFF OFF ON CFMWatts
953133
990188
1007251
985318
931389
NORMAL(a)
346 CFM/ton OFF OFF OFF OFF CFM
Watts1010154
1049212
1066279
1047350
1000426
(a) Factory Default Setting
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
14 18-GF74D1-1K-EN
Table 8. Air Flow Performance
TEM6A0C36H31SB, TEM6A0C42H41SB COOLING AIRFLOW PERFORMANCE,WET COIL, NO FILTER, NO HEATEROUTDOORUNIT SIZE(TONS)
SPEEDSETTING
AIRFLOWSETTING
DIP SWITCH SETTING AIRFLOWPOWER
EXTERNAL STATIC PRESSURE
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
2.5
LOW 300 CFM/ton ON ON OFF ON CFM
Watts76163
75598
719131
654163
560193
NORMAL 341 CFM/ton ON ON OFF OFF CFM
Watts86282
861120
834158
781196
700235
HIGH 384 CFM/ton ON ON ON OFF CFM
Watts962106
963147
948190
915234
863279
3
LOW 319 CFM/ton OFF ON OFF ON CFM
Watts961106
962147
947189
914233
862279
NORMAL 363 CFM/ton OFF ON OFF OFF CFM
Watts1092146
1093192
1082240
1060288
1026337
HIGH 408 CFM/ton OFF ON ON OFF CFM
Watts1231196
1231249
1221301
1203353
1175404
3.5
LOW 315 CFM/ton ON OFF OFF ON CFM
Watts1104150
1105197
1094245
1072293
1039343
NORMAL 357 CFM/ton ON OFF OFF OFF CFM
Watts1258209
1258263
1248317
1229369
1201421
HIGH 402 CFM/ton ON OFF ON OFF CFM
Watts1418286
1415347
1401406
1379462
1348516
4
LOW 308 CFM/ton OFF OFF OFF ON CFM
Watts1238199
1238253
1229306
1210357
1182408
NORMAL(a)
350 CFM/ton OFF OFF OFF OFF CFM
Watts1412282
1410344
1398404
1378462
1349517
HIGH 394 CFM/ton OFF OFF ON OFF CFM
Watts1570393
1528436
1473466
1406483
1326488
(a) Factory Default Setting
Table 9. Air Flow Performance
TEM6A0C36H31SB, TEM6A0C42H41SB HEATING AIRFLOW PERFORMANCE, NO FILTER, NO HEATEROUTDOORUNIT SIZE(TONS)
SPEEDSETTING
AIRFLOWSETTING
DIP SWITCH SETTING AIRFLOWPOWER
EXTERNAL STATIC PRESSURE
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
2.5
LOW 341 CFM/ton ON ON OFF ON CFM
Watts86077
863115
838154
788193
707232
NORMAL 379 CFM/ton ON ON OFF OFF CFM
Watts94998
953138
937180
906224
852269
HIGH 417 CFM/ton ON ON ON OFF CFM
Watts1042122
1046166
1036212
1015259
980308
3
LOW 381 CFM/ton OFF ON OFF ON CFM
Watts1147154
1149203
1141253
1123303
1094353
NORMAL 424 CFM/ton OFF ON OFF OFF CFM
Watts1277204
1279259
1272314
1255368
1228421
HIGH 466 CFM/ton OFF ON ON OFF CFM
Watts1409260
1409323
1401383
1384442
1357500
3.5
LOW 348 CFM/ton ON OFF OFF ON CFM
Watts1222180
1224232
1216285
1200336
1174388
NORMAL 386 CFM/ton ON OFF OFF OFF CFM
Watts1361240
1362300
1354358
1337415
1310471
HIGH 425 CFM/ton ON OFF ON OFF CFM
Watts1497316
1478372
1449420
1408461
1356494
4
LOW 338 CFM/ton OFF OFF OFF ON CFM
Watts1360239
1361299
1353358
1336415
1309470
NORMAL(a)
375 CFM/ton OFF OFF OFF OFF CFM
Watts1511325
1489380
1456426
1412464
1355493
HIGH 413 CFM/ton OFF OFF ON OFF CFM
Watts1659420
1605463
1535488
1450494
1349483
(a) Factory Default Setting
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
18-GF74D1-1K-EN 15
Table 10. Air Flow Performance
TEM6A0C48H41SB, TEM6A0C60H51SB COOLING AIRFLOW PERFORMANCE,WET COIL, NO FILTER, NO HEATEROUTDOORUNIT SIZE(TONS)
SPEEDSETTING
AIRFLOWSETTING
DIP SWITCH SETTING AIRFLOWPOWER
EXTERNAL STATIC PRESSURE
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
3
LOW 324 CFM/ton ON ON OFF ON CFM
Watts99189
985133
974186
984237
994303
NORMAL 368 CFM/ton ON ON OFF OFF CFM
Watts1120118
1119167
1110224
1116279
1122333
HIGH 423 CFM/ton ON ON ON OFF CFM
Watts1282162
1286219
1281280
1280343
1282402
3.5
LOW 314 CFM/ton OFF ON OFF ON CFM
Watts1116117
1114165
1105222
1111277
1117331
NORMAL 357 CFM/ton OFF ON OFF OFF CFM
Watts1263156
1266212
1261273
1261334
1263392
HIGH 411 CFM/ton OFF ON ON OFF CFM
Watts1449218
1458287
1456352
1449421
1447496
4
LOW 298 CFM/ton ON OFF OFF ON CFM
Watts1207140
1208193
1201252
1203311
1207366
NORMAL 339 CFM/ton ON OFF OFF OFF CFM
Watts1368190
1374252
1370315
1367381
1367448
HIGH 389 CFM/ton ON OFF ON OFF CFM
Watts1564264
1577343
1577411
1567484
1561570
5
LOW 305 CFM/ton OFF OFF OFF ON CFM
Watts1534251
1545328
1545394
1536467
1531550
NORMAL(a)
347 CFM/ton OFF OFF OFF OFF CFM
Watts1740344
1758444
1762518
1745594
1734684
HIGH (b) 399 CFM/ton OFF OFF ON OFF CFM
Watts1995484
2022629
2030717
2005783
1987828
(a) Factory Default Setting(b) Airflow must not exceed 1800 cfm in horizontal right, horizontal left, and downflow applications due to condensate blowoff. The 5 ton high tap shall not be
used in these applications.
Table 11. Air Flow Performance
TEM6A0C48H41SB, TEM6A0C60H51SB HEATING AIRFLOW PERFORMANCE, NO FILTER, NO HEATEROUTDOORUNIT SIZE(TONS)
SPEEDSETTING
AIRFLOWSETTING
DIP SWITCH SETTING AIRFLOWPOWER
EXTERNAL STATIC PRESSURE
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
3
LOW 360 CFM/ton ON ON OFF ON CFM
Watts1097112
1094160
1086216
1092271
1099326
NORMAL 400 CFM/ton ON ON OFF OFF CFM
Watts1215142
1216196
1210255
1211314
1215369
HIGH 440 CFM/ton ON ON ON OFF CFM
Watts1333178
1338238
1333300
1331365
1332428
3.5
LOW 348 CFM/ton OFF ON OFF ON CFM
Watts1232147
1234202
1228261
1229322
1233377
NORMAL 387 CFM/ton OFF ON OFF OFF CFM
Watts1366189
1373252
1369314
1366381
1365447
HIGH 426 CFM/ton OFF ON ON OFF CFM
Watts1500238
1511311
1510377
1502449
1498529
4
LOW 338 CFM/ton ON OFF OFF ON CFM
Watts1364188
1370251
1366313
1363379
1363446
NORMAL 375 CFM/ton ON OFF OFF OFF CFM
Watts1509241
1520315
1519382
1511453
1506535
HIGH 413 CFM/ton ON OFF ON OFF CFM
Watts1659305
1674395
1676466
1662541
1654632
5
LOW 326 CFM/ton OFF OFF OFF ON CFM
Watts1637295
1652383
1653453
1641528
1632618
NORMAL(a)
362 CFM/ton OFF OFF OFF OFF CFM
Watts1814381
1834493
1839570
1820645
1807730
HIGH 398 CFM/ton OFF OFF ON OFF CFM
Watts1990481
2017625
2025713
2000779
1982826
(a) Factory Default Setting
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
16 18-GF74D1-1K-EN
Table 12. Air Flow Performance
TEM6A0D48H41SB, TEM6A0D60H51SB COOLING AIRFLOW PERFORMANCE,WET COIL, NO FILTER, NO HEATEROUTDOORUNIT SIZE(TONS)
SPEEDSETTING
AIRFLOWSETTING
DIP SWITCH SETTING AIRFLOWPOWER
EXTERNAL STATIC PRESSURE
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
3
LOW 323 CFM/ton ON ON OFF ON CFM
Watts97987
978126
959170
922217
867269
NORMAL 367 CFM/ton ON ON OFF OFF CFM
Watts1111124
1113168
1101215
1075265
1036317
HIGH 415 CFM/ton ON ON ON OFF CFM
Watts1252165
1259214
1254264
1239314
1212364
3.5
LOW 315 CFM/ton OFF ON OFF ON CFM
Watts1111124
1113168
1101215
1075265
1036317
NORMAL 358 CFM/ton OFF ON OFF OFF CFM
Watts1259167
1266217
1261267
1246317
1220368
HIGH 404 CFM/ton OFF ON ON OFF CFM
Watts1419223
1428279
1425334
1411389
1386444
4
LOW 309 CFM/ton ON OFF OFF ON CFM
Watts1241161
1248210
1243259
1227309
1201359
NORMAL 351 CFM/ton ON OFF OFF OFF CFM
Watts1407218
1416273
1413328
1399383
1373437
HIGH 396 CFM/ton ON OFF ON OFF CFM
Watts1583296
1593359
1594422
1586485
1570547
5
LOW 295 CFM/ton OFF OFF OFF ON CFM
Watts1478249
1487307
1486365
1474423
1452481
NORMAL(a)
335 CFM/ton OFF OFF OFF OFF CFM
Watts1671344
1681412
1684479
1678545
1635565
HIGH 379 CFM/ton OFF OFF ON OFF CFM
Watts1880476
1892556
1900635
1902714
1760650
(a) Factory Default Setting
Table 13. Air Flow Performance
TEM6A0D48H41SB, TEM6A0D60H51SB HEATING AIRFLOW PERFORMANCE, NO FILTER, NO HEATEROUTDOORUNIT SIZE(TONS)
SPEEDSETTING
AIRFLOWSETTING
DIP SWITCH SETTING AIRFLOWPOWER
EXTERNAL STATIC PRESSURE
SW1 SW2 SW3 SW4 0.1 0.3 0.5 0.7 0.9
3
LOW 360 CFM/ton ON ON OFF ON CFM
Watts1087111
1091153
1081199
1055249
1015301
NORMAL 400 CFM/ton ON ON OFF OFF CFM
Watts1205139
1213186
1211234
1198283
1173333
HIGH 440 CFM/ton ON ON ON OFF CFM
Watts1322175
1333227
1332279
1321332
1297384
3.5
LOW 347 CFM/ton OFF ON OFF ON CFM
Watts1219143
1228191
1226240
1213289
1189339
NORMAL 386 CFM/ton OFF ON OFF OFF CFM
Watts1351184
1363237
1363290
1351344
1328397
HIGH 424 CFM/ton OFF ON ON OFF CFM
Watts1482232
1495291
1497349
1489408
1471466
4
LOW 351 CFM/ton ON OFF OFF ON CFM
Watts1405201
1417256
1418311
1408367
1385422
NORMAL 390 CFM/ton ON OFF OFF OFF CFM
Watts1555262
1568323
1572385
1567447
1553509
HIGH 429 CFM/ton ON OFF ON OFF CFM
Watts1703334
1717403
1723472
1722540
1665560
5
LOW 327 CFM/ton OFF OFF OFF ON CFM
Watts1625294
1639359
1644424
1641489
1630554
NORMAL(a)
363 CFM/ton OFF OFF OFF OFF CFM
Watts1797384
1812459
1820533
1822606
1750615
HIGH 400 CFM/ton OFF OFF ON OFF CFM
Watts1970495
1986581
1999667
2010740
1910680
(a) Factory Default Setting
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
18-GF74D1-1K-EN 17
Table 14. Electrical Data
TEM6A0B24H21SB HEATER DATA
Heater Model No.No. ofCircuits/Phases
240 Volt 208 VoltCapacity Heater
Amps perCircuit
MinimumCircuitAmpacity
MaximumOverloadProtection
Capacity HeaterAmps perCircuit
MinimumCircuitAmpacity
MaximumOverloadProtectionkW BTUH kW BTUH
No Heater 2.5 * 3 15 2.5 * 3 15BAYHTR1504BRKBAYHTR1504LUG 1/1 3.84 13100 16.0 23 25 2.88 9800 13.8 20 20
BAYHTR1505BRKBAYHTR1505LUG 1/1 4.80 16400 20.0 28 30 3.60 12300 17.3 25 25
BAYHTR1508BRKBAYHTR1508LUG 1/1 7.68 26200 32.0 43 45 5.76 19700 27.7 38 40
BAYHTR1510BRKBAYHTR1510LUG 1/1 9.60 32800 40.0 53 60 7.20 24600 34.6 46 50
BAYHTR1517BRKCircuit 1 (a)
2/19.60 32800 40.0 53 60 7.20 24600 34.6 46 50
BAYHTR1517BRKCircuit 2 4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
BAYHTR3510LUG 1/3 9.60 32800 23.1 32 35 7.20 24600 20.0 28 30
BAYHTR3517LUG 1/3 14.40 49100 34.6 46 50 10.80 36900 30.0 40 45
* = Motor Amps(a) MCA and MOP for circuit 1 contains the motor amps
Table 15. Electrical Data
TEM6A0B30H21SB HEATER DATA
Heater Model No.No. ofCircuits/Phases
240 Volt 208 VoltCapacity Heater
Amps perCircuit
MinimumCircuitAmpacity
MaximumOverloadProtection
Capacity HeaterAmps perCircuit
MinimumCircuitAmpacity
MaximumOverloadProtectionkW BTUH kW BTUH
No Heater 4.3 * 5 15 4.3 * 5 15BAYHTR1504BRKBAYHTR1504LUG 1/1 3.84 13100 16.0 25 25 2.88 9800 13.8 23 25
BAYHTR1505BRKBAYHTR1505LUG 1/1 4.80 16400 20.0 30 30 3.60 12300 17.3 27 30
BAYHTR1508BRKBAYHTR1508LUG 1/1 7.68 26200 32.0 45 45 5.76 19700 27.7 40 40
BAYHTR1510BRKBAYHTR1510LUG 1/1 9.60 32800 40.0 55 60 7.20 24600 34.6 49 50
BAYHTR1517BRKCircuit 1 (a)
2/19.60 32800 40.0 55 60 7.20 24600 34.6 49 50
BAYHTR1517BRKCircuit 2 4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
BAYHTR3510LUG 1/3 9.60 32800 23.1 34 35 7.20 24600 20.0 30 30
BAYHTR3517LUG 1/3 14.40 49100 34.6 48 50 10.80 36900 30.0 42 45
* = Motor Amps(a) MCA and MOP for circuit 1 contains the motor amps
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
18 18-GF74D1-1K-EN
Table 16. Electrical Data
TEM6A0C36H31SB, TEM6A0C42H41SB HEATER DATA
Heater Model No.No. ofCircuits/Phases
240 Volt 208 VoltCapacity Heater
Amps perCircuit
MinimumCircuitAmpacity
MaximumOverloadProtection
Capacity HeaterAmps perCircuit
MinimumCircuitAmpacity
MaximumOverloadProtectionkW BTUH kW BTUH
No Heater 4.3 * 5 15 4.3 * 5 15BAYHTR1504BRKBAYHTR1504LUG 1/1 3.84 13100 16.0 25 25 2.88 9800 13.8 23 25
BAYHTR1505BRKBAYHTR1505LUG 1/1 4.80 16400 20.0 30 30 3.60 12300 17.3 27 30
BAYHTR1508BRKBAYHTR1508LUG 1/1 7.68 26200 32.0 45 45 5.76 19700 27.7 40 40
BAYHTR1510BRKBAYHTR1510LUG 1/1 9.60 32800 40.0 55 60 7.20 24600 34.6 49 50
BAYHTR1517BRKCircuit 1 (a)
2/19.60 32800 40.0 55 60 7.20 24600 34.6 49 50
BAYHTR1517BRKCircuit 2 4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
BAYHTR1523BRKCircuit 1 (a)
2/19.60 32800 40.0 55 60 7.20 24600 34.6 49 50
BAYHTR1523BRKCircuit 2 9.60 32800 40.0 50 50 7.20 24600 34.6 43 45
BAYHTR3510LUG 1/3 9.60 32800 23.1 34 35 7.20 24600 20.0 30 30
BAYHTR3517LUG 1/3 14.40 49100 34.6 48 50 10.80 36900 30.0 42 45
* = Motor Amps(a) MCA and MOP for circuit 1 contains the motor amps
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
18-GF74D1-1K-EN 19
Table 17. Electrical Data
TEM6A0C48H41SB, TEM6A0C60H51SB HEATER DATA
Heater Model No.No. ofCircuits/Phases
240 Volt 208 VoltCapacity Heater
Amps perCircuit
MinimumCircuitAmpacity
MaximumOverloadProtection
Capacity HeaterAmps perCircuit
MinimumCircuitAmpacity
MaximumOverloadProtectionkW BTUH kW BTUH
No Heater 6.8 * 9 15 6.8 * 9 15BAYHTR1504BRKBAYHTR1504LUG 1/1 3.84 13100 16.0 29 30 2.88 9800 13.8 26 30
BAYHTR1505BRKBAYHTR1505LUG 1/1 4.80 16400 20.0 34 35 3.60 12300 17.3 30 30
BAYHTR1508BRKBAYHTR1508LUG 1/1 7.68 26200 32.0 49 50 5.76 19700 27.7 43 45
BAYHTR1510BRKBAYHTR1510LUG 1/1 9.60 32800 40.0 59 60 7.20 24600 34.6 52 60
BAYHTR1517BRKCircuit 1 (a)
2/19.60 32800 40.0 59 60 7.20 24600 34.6 52 60
BAYHTR1517BRKCircuit 2 4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
BAYHTR1523BRKCircuit 1 (a)
2/19.60 32800 40.0 59 60 7.20 24600 34.6 52 60
BAYHTR1523BRKCircuit 2 9.60 32800 40.0 50 50 7.20 24600 34.6 43 45
BAYHTR1525BRKCircuit 1 (a)
4/1
6.00 20500 25.0 40 40 4.50 15400 21.6 36 40
BAYHTR1525BRKCircuit 2 6.00 20500 25.0 31 35 4.50 15400 21.6 27 30
BAYHTR1525BRKCircuit 3 6.00 20500 25.0 31 35 4.50 15400 21.6 27 30
BAYHTR1525BRKCircuit 4 6.00 20500 25.0 31 35 4.50 15400 21.6 27 30
BAYHTR3510LUG 1/3 9.60 32800 23.1 36 40 7.20 24600 20.0 33 35
BAYHTR3517LUG 1/3 14.40 49100 34.6 51 60 10.80 36900 30.0 45 45
* = Motor Amps(a) MCA and MOP for circuit 1 contains the motor amps
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
20 18-GF74D1-1K-EN
Table 18. Electrical Data
TEM6A0D48H41SB, TEM6A0D60H51SB HEATER DATA
Heater Model No.No. ofCircuits/Phases
240 Volt 208 VoltCapacity Heater
Amps perCircuit
MinimumCircuitAmpacity
MaximumOverloadProtection
Capacity HeaterAmps perCircuit
MinimumCircuitAmpacity
MaximumOverloadProtectionkW BTUH kW BTUH
No Heater 6.8 * 9 15 6.8 * 9 15BAYHTR1504BRKBAYHTR1504LUG 1/1 3.84 13100 16.0 29 30 2.88 9800 13.8 26 30
BAYHTR1505BRKBAYHTR1505LUG 1/1 4.80 16400 20.0 34 35 3.60 12300 17.3 30 30
BAYHTR1508BRKBAYHTR1508LUG 1/1 7.68 26200 32.0 49 50 5.76 19700 27.7 43 45
BAYHTR1510BRKBAYHTR1510LUG 1/1 9.60 32800 40.0 59 60 7.20 24600 34.6 52 60
BAYHTR1517BRKCircuit 1 (a)
2/19.60 32800 40.0 59 60 7.20 24600 34.6 52 60
BAYHTR1517BRKCircuit 2 4.80 16400 20.0 25 25 3.60 12300 17.3 22 25
BAYHTR1523BRKCircuit 1 (a)
2/19.60 32800 40.0 59 60 7.20 24600 34.6 52 60
BAYHTR1523BRKCircuit 2 9.60 32800 40.0 50 50 7.20 24600 34.6 43 45
BAYHTR1525BRKCircuit 1 (a)
4/1
6.00 20500 25.0 40 40 4.50 15400 21.6 36 40
BAYHTR1525BRKCircuit 2 6.00 20500 25.0 31 35 4.50 15400 21.6 27 30
BAYHTR1525BRKCircuit 3 6.00 20500 25.0 31 35 4.50 15400 21.6 27 30
BAYHTR1525BRKCircuit 4 6.00 20500 25.0 31 35 4.50 15400 21.6 27 30
BAYHTR3510LUG 1/3 9.60 32800 23.1 36 40 7.20 24600 20.0 33 35
BAYHTR3517LUG 1/3 14.40 49100 34.6 51 60 10.80 36900 30.0 45 45
* = Motor Amps(a) MCA and MOP for circuit 1 contains the motor amps
PPeerrffoorrmmaannccee aanndd EElleeccttrriiccaall DDaattaa
18-GF74D1-1K-EN 21
Minimum Airflow CFMTEM6A0B24H21SB, TEM6A0B30H21SB
Heater MinimumHeater Airflow CFMWith Heat Pump Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUGBAYHTR1505BRK, BAYHTR1505LUG 660 600
BAYHTR1508BRK, BAYHTR1508LUG 780 600
BAYHTR1510BRK, BAYHTR1510LUG 780 600
BAYHTR1517BRK 1050 850BAYHTR3510LUG 780 600BAYHTR3517LUG 900 850
TEM6A0C36H31SB, TEM6A0C42H41SB
Heater MinimumHeater Airflow CFMWith Heat Pump Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUGBAYHTR1505BRK, BAYHTR1505LUG 875 675
BAYHTR1508BRK, BAYHTR1508LUG 950 820
BAYHTR1510BRK, BAYHTR1510LUG 1000 820
BAYHTR1517BRK 1000 820BAYHTR3510LUG 875 820BAYHTR3517LUG 1000 950BAYHTR1523BRK 1300 1140
TEM6A0C48H41SB, TEM6A0C60H51SB
Heater MinimumHeater Airflow CFMWith Heat Pump Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUGBAYHTR1505BRK, BAYHTR1505LUG 1200 975
BAYHTR1508BRK, BAYHTR1508LUG 1350 975
BAYHTR1510BRK, BAYHTR1510LUG 1350 975
BAYHTR1517BRK 1365 975BAYHTR3510LUG 1300 975BAYHTR3517LUG 1365 1120BAYHTR1523BRK 1365 1300BAYHTR1525BRK 1810 1505
TEM6A0D48H41SB, TEM6A0D60H51SB
Heater MinimumHeater Airflow CFMWith Heat Pump Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUGBAYHTR1505BRK, BAYHTR1505LUG 1150 975
BAYHTR1508BRK, BAYHTR1508LUG 1150 975
BAYHTR1510BRK, BAYHTR1510LUG 1150 975
BAYHTR1517BRK 1300 1125BAYHTR3510LUG 1150 975BAYHTR3517LUG 1300 1125BAYHTR1523BRK 1380 1125BAYHTR1525BRK 1550 1345
22 18-GF74D1-1K-EN
TEM6A0B24H21SB, TEM6A0B30H21SB Airflow Performancewith Auxiliary Heat
Airflow SettingsDip Switch Settings
Nominal AirflowSee following tables forheater application:- Pressure Drop forElectrical Heaters- Minimum HeatingAirflow Matrix (on unit
nameplates)
Switch 7 Switch 8
Low ON ON 601
Med-Lo OFF ON 661
Med-Hi ON OFF 781
High OFF OFF 973
TEM6A0C36H31SB, TEM6A0C42H41SB Airflow Performancewith Auxiliary Heat
Airflow SettingsDip Switch Settings
Nominal AirflowSee following tables forheater application:- Pressure Drop forElectrical Heaters- Minimum HeatingAirflow Matrix (on unit
nameplates)
Switch 7 Switch 8
Low ON ON 696
Med-Lo OFF ON 825
Med-Hi ON OFF 1150
High OFF OFF 1298
TEM6A0C48H41SB, TEM6A0C60H51SB Airflow Performancewith Auxiliary Heat
Airflow SettingsDip Switch Settings
Nominal AirflowSee following tables forheater application:- Pressure Drop forElectrical Heaters- Minimum HeatingAirflow Matrix (on unit
nameplates)
Switch 7 Switch 8
Low ON ON 1000
Med-Lo OFF ON 1130
Med-Hi ON OFF 1354
High OFF OFF 1596
TEM6A0D48H41SB, TEM6A0D60H51SB Airflow Performancewith Auxiliary Heat
Airflow SettingsDip Switch Settings
Nominal AirflowSee following tables forheater application:- Pressure Drop forElectrical Heaters- Minimum HeatingAirflow Matrix (on unit
nameplates)
Switch 7 Switch 8
Low ON ON 997
Med-Lo OFF ON 1129
Med-Hi ON OFF 1350
High OFF OFF 1597
MMiinniimmuumm AAiirrffllooww CCFFMM
18-GF74D1-1K-EN 23
Outline Drawing
NOTE: THIS UNIT IS APPROVED FOR INSTALLATION CLEARANCES TO COMBUSTIBLE MATERIAL AS STATED ON THE UNIT RATING NAMEPLATE
PRODUCT DIMENSIONS
Air Handler Model A B C D E F H FlowControl
Gas LineBraze
TEM6A0B24, 30 46.77 18.50 16.50 16.75 4.68 7.33 20.09 TXV 3/4
TEM6A0C36, 42 51.27 23.50 21.50 21.75 7.01 9.66 24.59 TXV 7/8
TEM6A0C48, 60 55.87 23.50 21.50 21.75 4.68 9.66 27.19 TXV 7/8
TEM6A0D48, 60 53.87 26.50 24.50 24.75 7.01 9.66 27.19 TXV 7/8
All dimensions are in inches
24 18-GF74D1-1K-EN
Heater Pressure Drop Table
AirflowCFM
Number of Racks Heater Racks
1 2 3 4 Heater Model No. of Racks
Air Pressure Drop — Inches W.G. BAYHTR1504 1
1800 0.02 0.04 0.06 0.14 BAYHTR1505 1
1700 0.02 0.04 0.06 0.14 BAYHTR1508 2
1600 0.02 0.04 0.06 0.13 BAYHTR1510 2
1500 0.02 0.04 0.06 0.12 BAYHTR1516 3
1400 0.02 0.04 0.06 0.12 BAYHTR1517 3
1300 0.02 0.04 0.05 0.11 BAYHTR3510 3
1200 0.01 0.04 0.05 0.10 BAYHTR3517 3
1100 0.01 0.03 0.05 0.09 BAYHTR3515 3
1000 0.01 0.03 0.04 0.09 BAYHTR1522 4
900 0.01 0.03 0.04 0.08 BAYHTR1523 4
800 0.01 0.03 BAYHTR1525 4
700 0.01 0.02
600 0.01 0.02
Subcooling AdjustmentSystemMatched with: Indoor Unit Model No. Outdoor Model No. Subcooling
16 SEER HP — 2 ton TEM6A0C36H31 4TWR6024H1000A4TWX6024H1000A4A6H6024H1000A
13 Degrees
15 SEER HP — 2 ton TEM6A0B24H21TEM6A0B30H21
4TWR5024G1000A4A6H5024G1000A
14 Degrees
15 SEER HP — 3 ton TEM6A0B30H21TEM6A0C36H31TEM6A0C42H41
4TWR5036G1000A4A6H5036G1000A
14 Degrees
All other matches must be charged per the nameplate charging instructions
Subcooling Adjustment for TEM6A0C48H41 & TEM6A0C60H51Sub-Cooling Charge Specification For AHRI Rated Performance
OD Equipment Up Flow / Horizontal Down Flow
AC UNIT OD Name Plate OD Name Plate
HP UNIT ≤ 3.5 Tons OD Name Plate OD Name Plate+ 4 Degrees
HP UNIT = 4 and 5 Tons OD Name Plate OD Name Plate
18-GF74D1-1K-EN 25
Coil Conversion InstructionsTable 19. Downflow
Follow the conversion steps when installing the air handler indownflow configuration.
1. Remove the front panels from the air handler. The coil and line setpanel do not need to be separated.
2. Remove the fasteners on both sides of the coil.
Note: The TEM6A0C48 and TEM6A0C60 will have a coil retainingbracket and a shipping bracket. All other coils will havetwo coil retaining brackets.
3. Remove the two screws holding the center horizontal bracket androtate out of place. Retain parts.
Figure 4. TEM8A0C48 and TEM8A0C60 Only
Figure 5. All other models
4. For the TEM6A0C48 and TEM6A0C60, remove the drain pansupport bracket at the top of the drain pan and discard.
Note: The drain pan support bracket should be removed to avoidtearing the cabinet insulation.
26 18-GF74D1-1K-EN
Table 19. Downflow (continued)
5. Slide the coil assembly out. Remove and discard the horizontaldrain pan.
Figure 6. TEM8A0C48 and TEM8A0C60 Only
Figure 7. All other models
6. On both sides of the cabinet, remove the two screws that hold thecoil support brackets and retain for later use. Seal the holes toprevent air leakage.
7. Rotate and lift the two coil support brackets to remove from frontslots in cabinet.
Figure 8. All models
8. Bend the two tabs on each of the coil support brackets. Tabsshould be bent inward so they are parallel to the bottom flange.
Figure 9. All models
Left
Right
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
18-GF74D1-1K-EN 27
Table 19. Downflow (continued)
9. Rotate the unit into the downflow orientation.
10. Pre-drill four clearance holes in the cabinet at dimples locatedbelow the location the screws were removed for the coil supportbrackets. There are two holes per side. See location of holes
11. Replace the center horizontal bracket removed in Step 3. Use thescrews retained from Step 3 to attach.
12. Place coil support brackets into the lower set of slots and rotateinto place. Push downward to lock into place.
13. Secure each bracket with 2 screws that were previously removed.
Figure 10. All models
14. For the TEM6A0C48 and TEM6A0C60models, remove the twoshipping brackets from the coil and discard.
Figure 11. TEM8A0C48 and TEM8A0C60 Only
Shipping Brackets
Rear Viewof Coil
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
28 18-GF74D1-1K-EN
Table 19. Downflow (continued)
Note: It is recommended to remove the shipping brackets from theTEM6A0C48 and TEM6A0C60.
15. Slide the coil assembly back into the air handler cabinet as shown.
16. Remove the appropriate knock out for the condensate piping.
Figure 12. TEM8A0C48 and TEM8A0C60 Only Figure 13. All other models
17. Replace all panels
Figure 14. TEM8A0C48 and TEM8A0C60 Only
Figure 15. All other models
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
18-GF74D1-1K-EN 29
Coil ConversionTable 20. Horizontal Right
Follow the conversion steps when installing the air handler inhorizontal right configuration.
1. Remove the front panels from the air handler. The coil and line setpanel do not need to be separated.
2. Remove the fasteners on both sides of the coil. Retain the coilretaining brackets and screws.
Note: The TEM6A0C48 and TEM6A0C60 will have a coil retainingbracket and a shipping bracket. All other coils will havetwo coil retaining brackets.
3. Remove the two screws holding the center horizontal bracket androtate out of place. Retain parts.
Figure 16. TEM8A0C48 and TEM8A0C60 Only Figure 17. All other models
4. Make note of the horizontal drain pan orientation (up/down).
5. For the TEM6A0C48 and TEMA0C60, remove the drain pansupport bracket at the top of the drain pan and retain for lateruse.
Note: The drain pan support bracket should be removed to avoidtearing the cabinet insulation.Figure 18. TEM6A0C48 and TEM6A0C60 Only
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
30 18-GF74D1-1K-EN
Table 20. Horizontal Right (continued)
6. Slide the coil assembly out.
7. Change location of the front and rear water diverter brackets byremoving the screws on the water diverter brackets that arelocated on the left side of the coil. Attach the water diverters tothe right hand side of the coil using the same screws.
Important: The coil slabs are different and the mount hole locationswill vary. See the illustrations on the following pages thatcorrespond to the unit tonnage to see the correctmounting position of the water diverter bracket.
Important: The water diverter brackets are not symmetrical and willvary by tonnage.
Important: There is no change required for the TEM6A0C48 andTEM6A0C60 water diverters.
Figure 19. TEM8A0C48 and TEM8A0C60 Only
Figure 20. All other models
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
18-GF74D1-1K-EN 31
Table 20. Horizontal Right (continued)
Figure 21.
Remove 2 screwsand water diverterbracket
TEM6A0B24 and TEM6A0B30 - Front view
Figure 22.
Screw is located insecond hole ontube sheet
TEM6A0B24 and TEM6A0B30 - Front view
Replace 2 screwsand water diverterbracket
Figure 23.
TEM6A0B24 and TEM6A0B30 - Rear view
Remove 2 screwsand water diverterbracket
Figure 24.
Screw is located insecond hole ontube sheet
Replace waterdiverter bracket
TEM6A0B24 and TEM6A0B30 - Rear view
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
32 18-GF74D1-1K-EN
Table 20. Horizontal Right (continued)
Figure 25.
Remove 3 screwsand water diverterbracket
TEM6A0C36 and TEM6A0C42 models -Front view
Figure 26.
Screw is located insecond hole ontube sheet
Replace 3 screwsand water diverterbracket
TEM6A0C36 and TEM6A0C42 models-Front view
Figure 27.
Remove 3 screwsand water diverterbracket
TEM6A0C36 and TEM6A0C42 models -Rear view
Figure 28.
Screw is located inuppermost hole ontube sheet
Replace 3 screwsand water diverterbracket
TEM6A0C36 and TEM6A0C42 models -Rear view
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
18-GF74D1-1K-EN 33
Table 20. Horizontal Right (continued)
Figure 29.
TEM6A0D48 and TEM6A0D60 models- Front view
Remove 3 screwsand water diverterbracket
Figure 30.
Screw is located insecond hole ontube sheet
TEM6A0D48 and TEM6A0D60 models - Front view
Replace 3 screwsand water diverterbracket
Figure 31.
TEM6A0D48 and TEM6A0D60 models - Rear view
Remove 3 screwsand water diverterbracket
Figure 32.
TEM6A0D48 and TEM6A0D60 models- Rear view
Replace 3 screwsand water diverterbracket
Screw is located insecond hole ontube sheet
Important: There is no change required for the TEM6A0C48 andTEM6A0C60 water diverters.
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
34 18-GF74D1-1K-EN
Table 20. Horizontal Right (continued)
8. For the TEM6A0C48 and TEM6A0C60models, remove the twoshipping brackets from the coil and discard.
Figure 33. TEM8A0C48 and TEM8A0C60 Only
Shipping Brackets
Rear Viewof Coil
9. Relocate the horizontal drain pan from the left side of the coil tothe right side.
10. Remove the two drain plugs and the drain pan support bracketfrom the front of the drain pan and insert them in the drains at therear of the drain pan.
Note: For the TEM6A0C48 and TEM6A0C60, the drain pansupport bracket should have been removed earlier.
Figure 34. TEM6A0C48 and TEM6A0C60 Only
Important:When reinstalling coil in Step 12, it is important that thecoil corner locks in place under the tab in the side bracketto support the coil weight horizontally.
Figure 35. All other models
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
18-GF74D1-1K-EN 35
Table 20. Horizontal Right (continued)
11. Reinstall the drain pan support bracket. The bracket should belocated between the two drain plugs as shown.
Note: For the TEM6A0C48 and TEM6A0C60 models only, to avoidtearing the interior insulation, the drain pan support bracketshould be installed after the coil has been put into the unit inStep 12.
Figure 36. All other models
12. Slide the coil assembly back into the air handler cabinet.
Important:Make sure that the coil corner locks in place underthe tab in the side left bracket to support the coilweight in the horizontal right position.
13. For the TEM6A0C48 and TEMA0C60 only, install the drain pansupport bracket on the top of the drain pan opposite the drainports and as close to the end as possible
Figure 37. TEM6A0C48 and TEM6A0C60 Only
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
36 18-GF74D1-1K-EN
Table 20. Horizontal Right (continued)
14. Replace the center horizontal bracket using screws removedearlier in Step 3.
15. Replace the two coil retaining brackets removed in a previousstep.
Note: The TEM6A0C48 and TEM6A0C60 will have only one coilretaining bracket.
16. Replace all panels.
Figure 38. TEM6A0C48 and TEM6A0C60 Only
Figure 39. All other models
CCooiill CCoonnvveerrssiioonn IInnssttrruuccttiioonnss
18-GF74D1-1K-EN 37
Checkout Procedures
The final phase of the installation is the system Checkout Procedures. The following list represents the most common items covered in aCheckout Procedure. Confirm all requirements in this document have been met.
All wiring connections are tight and properly secured.
Voltage and running current are within limits.
All refrigerant lines (internal and external to equipment) areisolated, secure, and not in direct contact with each other orstructure.
All braze connections have been checked for leaks. A vacuum of350 microns provides confirmation that the refrigeration systemis leak free and dry.
Final unit inspection to confirm factory tubing has not shiftedduring shipment. Adjust tubing if necessary so tubes do not rubagainst each other or any component when unit runs.
Ductwork is sealed and insulated.
All drain lines are clear with joints properly sealed. Pour waterinto drain pan to confirm proper drainage. Provide enough waterto ensure drain trap is primed.
Supply registers and return grilles are open, unobstructed, andair filter is installed.
Indoor blower and outdoor fan are operating smoothly andwithout obstruction.
Indoor blower motor set on correct speed setting to deliverrequired CFM. “Blower and fan set screws are tight.”
Cover panels are in place and properly tightened.
For gas heating systems, manifold pressure has been checkedand all gas line connections are tight and leak free.
For gas heating systems, flue gas is properly vented.
System functions safely and properly in all modes.
Owner has been instructed on use of system and given manual.
38 18-GF74D1-1K-EN
NNootteess
18-GF74D1-1K-EN 39
NNootteess
Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficientenvironments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® andTrane® —work together to enhance the quality and comfort of air in homes and buildings; transport and protectfood and perishables; and increase industrial productivity and efficiency. We are a global business committed to aworld of sustainable progress and enduring results.
ingersollrand.com
Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specificationswithout notice.We are committed to using environmentally conscious print practices.
18-GF74D1-1K-EN 08 Mar 2018
Supersedes 18-GF74D1-1J-EN (January 2018) ©2018 Ingersoll Rand