Installer manual LEK LEK LEK NIBE™ F2040 8, 12, 16 kW Air/water heat pump IHB GB 1540-5 231844

Transcript of Installer manual

Page 1: Installer manual

Installer manualLEK

LEK

LEK

NIBE™ F20408, 12, 16 kW

Air/water heat pump

IHB GB 1540-5 231844

Page 2: Installer manual
Page 3: Installer manual

Table of Contents

21 Important information2Safety information

62 Delivery and handling6Transport and storage

6Assembly

8Supplied components

9Removing the covers

9Removing the front panel

10Removing the side panel

113 The heat pump design11General

16Electrical connection

194 Pipe connections19General

19Pipe coupling heating medium circuit

21Docking alternatives

225 Electrical connections22General

24Connections

306 Commissioning and adjusting30Preparations

30Filling and venting the heating medium sys-tem

30Compressor heater

31Start-up and inspection

32Readjusting, heating medium side

33Adjustment, charge flow

347 Control

358 Disturbances in comfort35Troubleshooting

399 Alarm list

4210 Accessories

4411 Technical data44Dimensions and setting-out coordinates

46Sound pressure levels

47Technical specifications

54Energy labelling

58Electrical circuit diagram

64Index

1Table of Contents |NIBE™ F2040

Page 4: Installer manual

Safety informationThis manual describes installation and service proced-ures for implementation by specialists.

This appliance can be used by childrenaged from 8 years and above and per-sons with reduced physical, sensory ormental capabilities or lackof experienceandknowledge if theyhavebeengivensupervision or instruction concerninguse of the appliance in a safe way andunderstand the hazards involved. Chil-dren shall not play with the appliance.Cleaning and user maintenance shallnot bemadeby childrenwithout super-vision.

Rights to make any design or technicalmodifications are reserved.

©NIBE 2015.

Symbols

NOTE

This symbol indicates danger to machine orperson.

Caution

This symbol indicates important informationabout what you should observe when main-taining your installation.

TIP

This symbol indicates tips on how to facilitateusing the product.

MarkingThe CE marking means that NIBE ensures that theproduct meets all regulations that are placed on itbased on relevant EUdirectives. The CEmark is obligat-ory for most products sold in the EU, regardless wherethey are made.

Serial numberThe serial number for F2040 can be found on the sideof the foot.

F2040-8

LEK

DATA

Serial number

F2040-12

LEK

DATA

Serial number

NIBE™ F2040Chapter 1 | Important information2

1 Important information

Page 5: Installer manual

F2040-16

LEK

DATA

Serial number

Caution

Alwaysgive theproduct's serial numberwhenreporting a fault.

Country specific information

Installer manualThis installer manual must be left with the customer.

3Chapter 1 | Important informationNIBE™ F2040

Page 6: Installer manual

Inspection of the installationCurrent regulations require the heating installation to be inspected before it is commissioned. The inspection mustbe carried out by a suitably qualified person. Fill in the page for information about installation data in the Usermanual.

DateSignatureNotesDescription

System flushed

System vented

Particle filter

Shut-off and drain valve

Charge flow set

Fuses property

Safety breaker

Communication cable connected

F2040 addressed (only when cascadeconnection)

Miscellaneous

NIBE™ F2040Chapter 1 | Important information4

Page 7: Installer manual

Contact information

KNV Energietechnik GmbH, Gahberggasse 11, 4861 SchörflingAT

Tel: +43 (0)7662 8963-0 Fax: +43 (0)7662 8963-44 E-mail: [email protected] www.knv.atNIBE Wärmetechnik c/o ait Schweiz AG, Industriepark, CH-6246 AltishofenCH

Tel: (52) 647 00 30 Fax: (52) 647 00 31 E-mail: [email protected] www.nibe.chDruzstevni zavody Drazice s.r.o, Drazice 69, CZ - 294 71 Benatky nad JizerouCZ

Tel: +420 326 373 801 Fax: +420 326 373 803 E-mail: [email protected] www.nibe.czNIBE Systemtechnik GmbH, Am Reiherpfahl 3, 29223 CelleDE

Tel: 05141/7546-0 Fax: 05141/7546-99 E-mail: [email protected] www.nibe.deVølund Varmeteknik A/S, Member of the Nibe Group, Brogårdsvej 7, 6920 VidebækDK

Tel: 97 17 20 33 Fax: 97 17 29 33 E-mail: [email protected] www.volundvt.dkNIBE Energy Systems OY, Juurakkotie 3, 01510 VantaaFI

Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: [email protected] www.nibe.fiNIBE Energy Systems France Sarl, Zone industrielle RD 28, Rue du Pou du Ciel, 01600 ReyrieuxFR

Tel : 04 74 00 92 92 Fax : 04 74 00 42 00 E-mail: [email protected] www.nibe.frNIBE Energy Systems Ltd, 3C Broom Business Park, Bridge Way, Chesterfield S41 9QGGB

Tel: 0845 095 1200 Fax: 0845 095 1201 E-mail: [email protected] www.nibe.co.ukNIBE Energietechniek B.V., Postbus 634, NL 4900 AP OosterhoutNL

Tel: 0168 477722 Fax: 0168 476998 E-mail: [email protected] www.nibenl.nlABK AS, Brobekkveien 80, 0582 Oslo, Postadresse: Postboks 64 Vollebekk, 0516 OsloNO

Tel. sentralbord: +47 23 17 05 20 E-mail: [email protected] www.nibeenergysystems.noNIBE-BIAWAR Sp. z o. o. Aleja Jana Pawła II 57, 15-703 BIAŁYSTOKPL

Tel: 085 662 84 90 Fax: 085 662 84 14 E-mail: [email protected] www.biawar.com.pl© "EVAN" 17, per. Boynovskiy, Nizhny NovgorodRU

Tel./fax +7 831 419 57 06 E-mail: [email protected] www.nibe-evan.ruNIBE AB Sweden, Box 14, Hannabadsvägen 5, SE-285 21 MarkarydSE

Tel: +46-(0)433-73 000 Fax: +46-(0)433-73 190 E-mail: [email protected] www.nibe.se

For countries not mention in this list, please contact Nibe Sweden or check www.nibe.eu for more information.

5Chapter 1 | Important informationNIBE™ F2040

Page 8: Installer manual

Transport and storageF2040 must be transported and stored vertically.

Assembly Place F2040 outdoors on a solid level base that cantake the weight, preferably a concrete foundation.If concrete slabs are used they must rest on asphaltor shingle.

The concrete foundationor slabsmust bepositionedso that the lower edge of the evaporator is at thelevel of the average local snow depth, although aminimum of 300 mm.

The F2040 should not bepositionednext to sensitivewalls, for example, next to a bedroom.

Also ensure that the placement does not inconveni-ence the neighbours.

F2040must not beplaced so that recirculation of theoutdoor air can occur. This causes lower output andimpaired efficiency.

Theevaporator shouldbe sheltered fromdirectwind,which negatively affects the defrosting function.Place F2040 protected from wind against the evap-orator.

Large amounts of condensationwater aswell asmeltwater from defrosting can be produced. Condensa-tion water must be led off to a drain or similar (seepage 7).

Care must be exercised so that the heat pump is notscratched during installation.

LEKLEK

LEK

Cirka 1 m

LEKLEK

LEK

Cirka 1 m

min 300 mmMin. 300 mm

Do not place F2040 directly on the lawn or other nonsolid surface.

If there is a risk of snow slip from roof, a protective roofor cover must be erected to protect the heat pump,pipes and wiring.

NIBE™ F2040Chapter 2 | Delivery and handling6

2 Delivery and handling

Page 9: Installer manual

Condensation run off

Condensation water trough

The condensation water trough is used to collect andlead away condensation water from the heat pump.

NOTE

It is important to the heat pump function thatcondensation water is led away and that thedrain for the condensationwater run off is notpositioned so that it can cause damage to thehouse.

NOTE

Pipe with heating cable for draining the con-densation water trough are not included.

NOTE

To ensure this function the accessory KVR 10should be used.

NOTE

The electrical installation and wiring must becarriedout under the supervisionof anauthor-ised electrician.

NOTE

Self regulating heating cables must not beconnected.

Caution

If none of the recommended alternatives isused good lead off of condensation watermust be assured.

The condensation water (up to 50 litres/day) collec-ted in the trough should be routed by pipe to anappropriate drain, it is recommended that theshortest outdoor stretch possible is used.

The section of the pipe that can be affected by frostmust be heated by the heating cable to preventfreezing.

Route the pipe downward from F2040. The outlet of the condensation water pipe must beat a depth that is frost free or alternatively indoors(with reservation for local ordinances and regula-tions).

Use awater trap for installationswhere air circulationmay occur in the condensation water pipe.

The insulation must be tight against the bottom ofthe condensation water trough.

Drain pan heater, control

Thedrain panheater is suppliedwith powerwhenoneof the following conditions is met:1. Operatingmode "Heating" or "Hot water" is activ-

ated.

2. The compressor has been in operation for at least30 minutes after last start.

3. The ambient temperature is lower than 1 C.

Recommended alternatives

Stone caisson

LEK

Frostfritt djupFrost proof depth

If the house has a cellar the stone caisson must be po-sitioned so that condensation water does not affectthe house. Otherwise the stone caisson can be posi-tioned directly under the heat pump.

The outlet of the condensation water pipe must be atfrost free depth.

Drain indoors

Water seal

The condensation water is lead to an indoor drain(subject to local rules and regulations).

Route the pipe downward from F2040.

7Chapter 2 | Delivery and handlingNIBE™ F2040

Page 10: Installer manual

The condensation water pipe must have a water sealto prevent air circulation in the pipe.

Gutter drainage

Frostfritt

djup

LEK

Frost proof depth

Water seal

The outlet of the condensation water pipe must be atfrost free depth.

Route the pipe downward from F2040.

The condensation water pipe must have a water sealto prevent air circulation in the pipe.

Installation areaThe distance between F2040 and the house wall mustbe at least 150mm. Clearance in front of F2040 shouldbe at least one metre.

50

255

Ställb

ar 4

0-5

0 9

55

243

512

110

395

265

50

452 1075

1145

108

Ø40*

14

85

3000 m

m

400 mm

Minimalt

fritt utrymme

Minimalt

fritt utrymme

Fritt utrymme

framför

150 m

m Fritt

utrymme

bakom

600mm

Minimumfree space

Minimumfree space

Freespacebehind

400 mm 600 mm

150 mm

3000 mm

Free spacein front

Supplied components

LEK

Particle filter R25 (HQ1).2 flexible hoses (R25) with4 seals

NIBE™ F2040Chapter 2 | Delivery and handling8

Page 11: Installer manual

Removing the coversF2040-8

LEK

F2040-12

LEK

F2040-16

LEK

Removing the front panelF2040-8

LEK

9Chapter 2 | Delivery and handlingNIBE™ F2040

Page 12: Installer manual

F2040-12

LEK

F2040-16

LEK

Removing the side panelF2040-12

LEK

F2040-16

LEK

DATA

NIBE™ F2040Chapter 2 | Delivery and handling10

Page 13: Installer manual

GeneralF2040-8

LEK

GQ1

DH

UB3

EP1

EB11

CM

20S

63H1

LPT

SM2

SM1

FM01

PWB2 PWB3 PWB1

BT12

BT15

BP4

QN2

BT3

PF3

HS1

EP2

GQ10 QN1

BP2

QM35

QM36

BP1

QN3

CH

EB10

AA23

X1

F TBBT14 Tho-D

Tho-SBT17

LEK

DATA

XL2

UB1

UB2

W1

XL1

UB3

LEK

DATA

PF1PF3

Tho-ABT28

Tho-R1 Tho-R2BT16

11Chapter 3 | The heat pump designNIBE™ F2040

3 The heat pump design

Page 14: Installer manual

F2040-12

LEK

QN1

GQ1

GQ10 QM35

QN3

QM36

TB

BP1

QN2

PWB1

PWB2

PWB3

DH

UB3

BT3

BP4

PF3

BT15

EP1

EP2HS1BP2

BT12

X1

EB11

CM

20S

63H1

LPT SM2

SM1

FM01

CH

EB10

AA23

Tho-DBT14

BT17 Tho-S

LEK

DATA

XL2

UB1

UB2

W1

XL1

UB3

LEK

DATA

Tho-ABT28

PF1PF3 Tho-R1BT16

Tho-R2

NIBE™ F2040Chapter 3 | The heat pump design12

Page 15: Installer manual

F2040-16

LEK

GQ1

DH

X1

CM

63H1

CH

SM2

SM1

FM01

PWB2 PWB3 PWB1

QN2 20S

BT12

TB

BP1

PF3

QN3

BP4

BT3

BT15

UB3

GQ10 HS1

QN1

EP2

QM36

QM35

EB11

GQ2 FM02

EP1

F

LPT

BP2

AA23

Tho-D

BT14 EB10

Tho-SBT17

13Chapter 3 | The heat pump designNIBE™ F2040

Page 16: Installer manual

LEK

DATA

XL2

UB1

UB2

XL1

UB3

W1

LEK

DATA

PF3 PF1

BT28Tho-A

Tho-R1 Tho-R2BT16

NIBE™ F2040Chapter 3 | The heat pump design14

Page 17: Installer manual

Component list F2040-8 , -12 , -16

Pipe connectionsService valve, liquid sideQM35Service valve, gas sideQM36Connection, heatingmedium out ofF2040,G1" (Ø28 mm)

XL1

Connection, heating medium in to F2040,G1" (Ø28 mm)

XL2

Sensors etc.High pressure pressostatBP1 (63H1)Temperature sensor, heatingmediumreturnline

BT3

Temperature sensor, condenser supply lineBT12Temperature sensor, hot gasBT14 (Tho-

D)Temperature sensor, fluid pipeBT15Temperature sensor 1, evaporatorBT16 (Tho-

R1)Temperature sensor, suction gasBT17 (Tho-

S)Temperature sensor, ambientBT28 (Tho-

A)Low pressure transmitterBP2 (LPT)High pressure sensorBP4Temperature sensor 2, evaporatorTho-R2

Electrical componentsCommunication boardAA23Fuse for external heating cable (250 mA),max 45W.

AA23-F3

DIP switch, addressing of outdoor unitAA23-S3Terminal block, KVRAA23-X1Terminal block, communication from indoormodule

AA23-X4

Communication with TBAA23-X100

Compressor heaterEB10 (CH)Drip tray heaterEB11 (DH)Main fuse compressor unitFFanGQ1

(FM01)FanGQ2

(FM02)Control boardPWB1Inverter boardPWB2Filter boardPWB3Terminal block, incoming supply and com-munication with board AA23

TB

Cooling components4-way valveQN2 (20S)CompressorGQ10 (CM)

Expansion valve, coolingQN3 (SM1)Expansion valve, heatingQN1 (SM2)Evaporator (air coil, copper pipe with alu-minium flange)

EP1

Condenser (ACH30, copper/stainless steel)EP2Drying filterHS1

MiscellaneousType platePF1Serial numberPF3Cable gland, incoming supplyUB1Cable grommet, communicationUB2Cable grommet, heating cable (EB14)UB3Cable, incoming supplyW1

Designations in component locations according tostandard IEC 81346-1 and 81346-2. Designationswithin brackets according to the supplier's standard.

15Chapter 3 | The heat pump designNIBE™ F2040

Page 18: Installer manual

Electrical connectionElectrical components

Communication boardAA23Fuse for external heating cable (250 mA),max 45W.

AA23-F3

DIP switch, addressing of outdoor unitAA23-S3Terminal block, KVRAA23-X1Terminal block, communication from indoormodule

AA23-X4

Communication with TBAA23-X100

Compressor heaterEB10 (CH)Drip tray heaterEB11 (DH)Main fuse compressor unitFFanGQ1

(FM01)FanGQ2

(FM02)Control boardPWB1Inverter boardPWB2Filter boardPWB3Terminal block, incoming supply and com-munication with board AA23

TB

Designations in component locations according tostandard IEC 81346-1 and 81346-2. Designationswithin brackets according to the supplier's standard.

F2040-8

LEK

AA23

AA23-F3

AA23-X4

AA23-X1

AA23-S3

AA23-X100

LEK

PWB2PWB1

PWB3

TB

NIBE™ F2040Chapter 3 | The heat pump design16

Page 19: Installer manual

F2040-12

Främre el

Bakre el

LEK

LEK

EB11

PWB3 PWB1

EB10

AA23

FM01TB

F

AA23-F3

AA23-X4

AA23-X1

DH

CH

GQ1

AA23-S3

AA23-X100

Främre el

Bakre el

LEK

LEK

PWB2

Capacitor

Reactor

AF moduleDiode module

17Chapter 3 | The heat pump designNIBE™ F2040

Page 20: Installer manual

F2040-16

Främre el

Bakre el

LEK

LEK

PWB3 PWB1

EB10

FM01

AA23-X4

DH

CH

GQ1

TB

AA23-X1 AA23-F3

EB11

F

AA23 AA23-S3

FM02GQ2

AA23-X100

Främre el

Bakre elLEK

LEK

PWB2

PWB2

Capacitor

Reactor

AF moduleDiode module

NIBE™ F2040Chapter 3 | The heat pump design18

Page 21: Installer manual

GeneralPipe installationmust be carriedout in accordancewithcurrent norms and directives.

F2040 can only operate up to a return temperature ofabout 55 °C and an outgoing temperature of about58 °C from the heat pump.

F2040 is not equippedwith external shut off valves onthewater side; thesemust be installed to facilitate anyfuture servicing. The return temperature is limited bythe return line sensor.

Water volumesWhen docking with F2040 free flow in the climatesystem is recommended for correct heat transfer. Thiscan be achieved by use of a bypass valve. If free flowcannot be ensured, it is recommended that a buffertank (NIBE UKV) is installed.

Following water volumes are recommended

-16-12-8F2040

150 l80 l50 lMinimum volume, climate sys-tem during heating/cooling

150 l100 l80 lMinimum volume, climate sys-tem during under floor cooling

NOTE

Thepipeworkmust be flushedbefore theheatpump is connected, so that any contaminantsdo not damage the components.

Pipe couplingheatingmediumcircuit F2040 can be connected directly to the heating sys-tem see the section "Docking" or according to oneof the systemsolutions that canbedownloaded fromthe website www.nibe.eu.

Theheat pumpmust be ventedby theupper connec-tion (QM20)using the ventingnippleon theenclosedflexible hose.

Install the supplied particle filter (HQ1) before theinlet, i.e. the connection (XL2, HM-in) on F2040.

All outdoor pipes must be thermally insulated withat least 19mm thick pipe insulation.

Install shutoff valves (QM31 and QM32) and drainvalves (QM1) so that F2040 can be emptied in theevent of prolonged power failures. Shutoff - (QM31and QM32) and drain valve (QM31) are not part ofthe delivery

F2040-8/F2040-12

F2040-16

F2040

Tryckfall (kPa)

Flöde l/s

0

5

10

15

20

25

30

0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8

Flow l/s

Pressure drop (kPa) 8 kW, 12 kW

16 kW

-EB101

-FL10

XL1

XL2

-RN10 -QM40

-HQ1 -QM41

-QM1

Heat pumpEB101Safety valveFL10Particle filterHQ1Trim valveRN10Tapping valveQM1Shut-off valveQM40Shut-off valveQM41

19Chapter 4 | Pipe connectionsNIBE™ F2040

4 Pipe connections

Page 22: Installer manual

F2040-8

LEK

Heat insulation

F2040-12

LE

K

DATA

LEK

Heat insulation

F2040-16

LEK

DATA

NIBE™ F2040Chapter 4 | Pipe connections20

Page 23: Installer manual

LEK

Heat insulation

Docking alternativesF2040 can be installed in several different ways. Therequisite safety equipmentmust be installed in accord-ance with current regulations for all docked options.

See www.nibe.eu for more docking options.

Connecting accessoriesInstructions for connectingaccessories are in the install-ation instructions provided for the respective accessory.See page 42 for the list of the accessories that can beused with F2040.

21Chapter 4 | Pipe connectionsNIBE™ F2040

Page 24: Installer manual

General A heat pump must not be connected without thepermission of the electricity supplier and must beconnected under the supervision of a qualified elec-trician.

If a miniature circuit breaker is used this should havemotor characteristic "C" (compressor operation). ForMCB size see "Technical Specifications".

F2040 does not include a circuit breaker on the in-coming power supply. The heat pump’s supply cable(W1) must be connected to a circuit-breaker with atleast a 3 mm breaking gap. When the building isequippedwith an earth-fault breaker the heat pumpshould be equipped with a separate one. Incomingsupply must be 230 V 50Hz via distribution boardswith fuses.

If an insulation test is to be carriedout in thebuilding,disconnect the heat pump.

Communication cable (W2) is inserted from the rearside through UB2.

Connect communication cable (W2) from terminalblock (AA23-X4) to the indoor section.

NOTE

Electrical installation and service must be car-ried out under the supervision of a qualifiedelectrician. Electrical installation and wiringmust be carried out in accordance with thestipulations in force.

NOTE

The external control must be taken into con-sideration when connecting.

NOTE

If the supply cable is damaged, only NIBE, itsservice representative or similar authorisedperson may replace it to prevent any dangerand damage.

F2040-8

LEK

AA23

AA23-F3

AA23-X4

AA23-X1

AA23-S3

AA23-X100

LEK

PWB2PWB1

PWB3

TB

NIBE™ F2040Chapter 5 | Electrical connections22

5 Electrical connections

Page 25: Installer manual

F2040-12

Främre el

Bakre el

LEK

LEK

DH

PWB3

CH

AA23

FM01TBF AA23-F3AA23-X1

PWB1

AA23-X4

AA23-S3

Främre el

Bakre el

LEK

LEK

PWB2

F2040-16Främre el

Bakre el

LEK

LEK

DH

PWB3

CH

AA23

FM01

TBF

AA23-F3AA23-X1

PWB1

AA23-X4

AA23-S3

Främre el

Bakre el

LEK

LEK

PWB2

23Chapter 5 | Electrical connectionsNIBE™ F2040

Page 26: Installer manual

Connections NOTE

To prevent interference, unscreened commu-nicationand/or sensor to external connectionscables must not be laid closer than 20 cm tohigh voltage cables when cable routing.

Power connection

F2040-8

LEK

DATA

LEK

Incoming supply

Power connection

W1

XL2

UB1

UB2

W1

XL1

UB3

NIBE™ F2040Chapter 5 | Electrical connections24

Page 27: Installer manual

F2040-12

LEK

DATA

LEK

Incoming supply

W1

W1

UB2

UB1

XL1

XL2

UB3

Power connection

25Chapter 5 | Electrical connectionsNIBE™ F2040

Page 28: Installer manual

F2040-16

LEK

DATA

LEK

Incoming supply

Power connection

W1

XL2

UB1

UB2

XL1

UB3

W1

Incoming supply cable (W1) is supplied and factoryconnected to terminal block X1. Approx. 1.8 m cableis accessible outside the heat pump.

Connect communication cable (W2) (provided by in-staller) to terminal blockAA23-X4 and securewith twocable ties, see image.

For connection of accessory KVR 10, heating cable(EB14) is connected via cable grommetUB3, see Extern-al heating cable KVR 10 (Accessory) on page 28.

List of componentsCable grommet, cascade connectionUB1Cable grommet, communicationUB2Cable grommet, heating cable (EB14)UB3Cable, incoming supplyW1

NIBE™ F2040Chapter 5 | Electrical connections26

Page 29: Installer manual

F2040-8

LEK

Cables for communication (W2)are routed through ferritebeads/EMI filters.

LEK

F2040-12

LEK

Secure the communicationcable (W2) here using twocable ties.

Främre el

Bakre el

LEK

LEK

F2040-16

LEK

Främre el

Bakre el

LEK

LEK

Secure the communicationcable (W2) here using twocable ties.

27Chapter 5 | Electrical connectionsNIBE™ F2040

Page 30: Installer manual

External heating cable KVR 10 (Accessory)F2040 is equipped with a plinth for external heatingcable EB14 not supplied). The connection is fusedwith250 mA (F3 on the communication board AA23). Ifanother cable is to be used, the fuse must be replacedwith a suitable one (see table).

NOTE

Self regulating heating cables must not beconnected.

NIBE Part no.

Fuse

Fuse (F3)Total

power(W)

Length(m)

718085T100mA/250V151518900*T250mA/250V453718086T500mA/250V906

* Fitted at the factory.

Connect external heating cable (EB14) to terminal blockX1:4–6 according to following image:

56

42

31

External F2040

X1

EB14

External heat cable

AA23

F3

NOTE

The pipe must be able to withstand the heatfrom the heating cable.

To ensure this function the accessory KVR 10should be used.

Cable routing

The following images show recommended cable rout-ing fromthedistributionbox to the condensationwaterpipe. Route the heating cable (EB14) through thegrommet underneath and secure with two cable tiesat the electrical connection. Transfer betweenelectricalcable and heating cable must occur after the lead-into the condensation water pipe.

F2040-8

LEK

Heating cable (EB14)

Secure the heatingcable (EB14) hereusing two cable ties.

NIBE™ F2040Chapter 5 | Electrical connections28

Page 31: Installer manual

F2040-12

LEK

Heating cable (EB14)

Secure the heatingcable (EB14) hereusing two cable ties.

F2040-16

LEK

Heating cable (EB14)

Secure the heating cable(EB14) here using two cableties.

Ambient temperature sensorAn ambient temperature sensor (Tho-A) is located onthe rear of F2040.

CommunicationF2040 can communicate with NIBE indoor modules,by connecting the indoormodule to the terminal blockX4:1–3 according to the following image:

Innemodul

X4

F2040

GNDGND

B-B-

A+15

14

13

A+

GND

B-

A+AA3

1

2

3

4

5

6

ExternalF2040

X4

AA3

For connection of indoormodule, see relevantmanualon www.nibe.eu.

Addressing via cascade connectionThe communication address is selected for F2040 tothe control module on the communication board(AA23-S3). Default has F2040 address 1. In a cascadeconnection all F2040must have a unique address. Theaddress is coded in binary.

S3:3S3:2S3:1Address

OFFOFFOFF1

OFFOFFOn2

OFFOnOFF3

OFFOnOn4

OnOFFOFF5

OnOFFOn6

OnOnOFF7

OnOnOn8

29Chapter 5 | Electrical connectionsNIBE™ F2040

Page 32: Installer manual

Preparations Before commissioning, check that the charge circuitand climate system are filled and well vented.

Check the pipe system for leaks.

Filling andventing theheatingmedium system1. The heatingmedium system is filled with water to

the required pressure.2. Vent the system using the venting nipple (QM20)

on the enclosed flexible hose and possibly the cir-culation pump.

LEK

QM20

Compressor heaterF2040 is equippedwith a compressor heater that heatsthe compressor before start-up and when the com-pressor is cold.

NOTE

The compressor heater must have been con-nected for 6 – 8 hours before the first start, seethe section “Start-up and inspection” in theinstaller manual for the indoor section

NIBE™ F2040Chapter 6 | Commissioning and adjusting30

6 Commissioning and adjusting

Page 33: Installer manual

Start-up and inspection1. The compressor heater (CH)must have been oper-

ational for at least 6 - 8 hours before the com-pressor start can be initiated. This is done byswitchingon the control voltageanddisconnectingthe communication cable.

2. F2040 must be addressed if it is to have anotheraddress than1. See chapterAddressing via cascadeconnection, on page 29.

3. The communication cable on the terminal blockAA23-X4 must not be connected.

4. Turn the isolator switch on.5. Ensure that the F2040 is connected to the power

source.6. After 6 – 8 hours the communication cable (W2) is

connected to terminal block AA23-X4.7. Restart the indoormodule. Follow the instructions

for "Start-up and inspection" in the installationmanual for the indoor module.

The heat pump starts 30 minutes after the outdoorunit is powered and the communication cable (W2) isconnected, if necessary.

If scheduledsilent operation is required, it must bescheduled in the inner section or control module.

Caution

Silentmode should only be scheduled period-ically because the maximum output is limitedto approx. the nominal values.

Caution

Do not start any electrical work until at leasttwo minutes after cutting the power.

F2040-8

LEK

AA23

AA23-X4

AA23-S3

31Chapter 6 | Commissioning and adjustingNIBE™ F2040

Page 34: Installer manual

F2040-12

Främre el

Bakre el

LEK

LEK

AA23

AA23-X4

AA23-S3

F2040-16

Främre el

Bakre el

LEK

LEK

AA23

AA23-X4

AA23-S3

Readjusting, heating mediumsideAir is initially released from the hot water and ventingmay be necessary. If bubbling sounds can be heardfrom the heat pump, the circulation pump and radiat-ors the entire systemwill require further venting.Whenthe system is stable (correct pressure and all air elimin-ated) the automatic heating control system can be setas required.

NIBE™ F2040Chapter 6 | Commissioning and adjusting32

Page 35: Installer manual

Adjustment, charge flowInstructions for adjusting hotwater charging are in theinstallation manual for the respective indoor section.See page 42 for the list of the indoor sections and ac-cessories that can be used with F2040.

33Chapter 6 | Commissioning and adjustingNIBE™ F2040

Page 36: Installer manual

Menu 5.11.1.1 – Heat pump EB101These settings are made on the display in the indoormodule.

Cooling permitted

Here you can set whether the cooling function is to beactivated for the heat pump.

Silent mode permitted

Set whether silentmode is to be activated for the heatpump here.

Current limit

Setwhether the current limiting function is to be activ-ated for the heat pump here. During active functionyou can limit the value of the maximum current.

Setting range: 6 – 32 A

Factory setting: 32 A

Stop temperature compressor

Here you can limit the value for set outdoor temperat-ure down to the value the heat pump is to work.

Setting range -20 – -2 °C

Factory setting -20 °C

blockFreq 1

Select a frequency range within which the heat pumpmay work here.

blockFreq 2

Select a frequency range within which the heat pumpmay work here.

NIBE™ F2040Chapter 7 | Control34

7 Control

Page 37: Installer manual

TroubleshootingNOTE

Work behind covers secured by screws mayonly be carriedout by, or under the supervisionof, a qualified installation engineer.

NOTE

As F2040 can be connected to a large numberof external units, these should alsobe checked.

NOTE

In the event of action to rectify malfunctionsthat require work within screwed hatches theincoming electricitymust isolated at the safetyswitch.

NOTE

The alarm is acknowledged on the indoormodule or by the voltage to the heat pumpbeing interrupted and then restarted.

The following tips can be used to rectify comfort dis-ruption:

Basic actionsStart by checking the following possible fault sources: That the heat pump is running or that the supplycable to F2040 is connected.

Group and main fuses of the accommodation. The property's earth circuit breaker. The heat pump's motor circuit breaker (F).

Low hot water temperature or a lack of hotwaterThis part of the fault-tracing chapter only applies if theheat pump is docked to the hot water heater. Large hot water consumption. Wait until the hot water has heated up.

Incorrect settings in the indoor module. See the manual for the indoor module.

Low room temperature Closed thermostats in several rooms. Set the thermostats to max in as many rooms aspossible.

External switch for changing the roomheating activ-ated. Check any external switches.

Incorrect settings in indoor module. See the manual for the indoor module.

High room temperature External switch for changing the roomheating activ-ated. Check any external switches.

Incorrect settings in indoor module. See the manual for the indoor module.

F2040 not in operationF2040 communicates all alarms to the indoormodule. Ensure that the F2040 is connected to the powersource.

Check the indoormodule. See section "Disturbancesin comfort" in the installationmanual for the indoormodule.

F2040 does not communicate Check that the addressing of F2040 is correct. Check that the communication cable has been con-nected.

35Chapter 8 | Disturbances in comfortNIBE™ F2040

8 Disturbances in comfort

Page 38: Installer manual

Sensor placement Connection to card (PWB1)

F2040-8

LEK

EB11EB10 GQ1

PWB1

BP1 QN2 QN3 QN1 BP2SM1 SM2 LPTFM01DH20SCH63H1

F2040-12 /F2040-16

BP1

Tho-R2 BT16 BT14 BT17 BT28

63H1

Tho-R1 Tho-D Tho-S Tho-A LPTBP2

DHEB11

20SQN2

CHEB10

FM01GQ1

CTBE1

SM2QN1

SM1QN3

Sensors etc.Current sensorBE1 (CT)High pressure pressostatBP1 (63H1)Low pressure transmitterBP2 (LPT)Pressure sensor, condenserBP4Temperature sensor, heating mediumreturn line

BT3

Temperature sensor, condenser supplyline

BT12

Temperature sensor, hot gasBT14 (Tho-D)Temperature sensor, fluid pipeBT15Temperature sensor, heat exchanger, 1BT16 (Tho-R1)Temperature sensor, suction gasBT17 (Tho-S)Temperature sensor, ambientBT28 (Tho-A)Compressor heaterEB10 (CH)Drip tray heaterEB11 (DH)CondenserEP2FanGQ1 (FM01)CompressorGQ10 (CM)Drying filterHS1Expansion valve, heatingQN1 (SM2)4-way valveQN2 (20S)Expansion valve, coolingQN3 (SM1)Temperature sensor, heat exchanger, 2Tho-R2

NIBE™ F2040Chapter 8 | Disturbances in comfort36

Page 39: Installer manual

Connection to card (AA23)

BP4 BT15 BT12 BT3

AA23-S3

Sensor placement in F2040

Defrost/Cooling

Defrost/Cooling

kW

kW

kW

Defrost/Cooling

Defrost/Cooling

kW

kW

kW

37Chapter 8 | Disturbances in comfortNIBE™ F2040

Page 40: Installer manual

Data for temperature sensor in F2040

Tho-D

0

20

40

60

80

100

120

140

160

180

200

0 20 40 60 80 100 120 140 160 (ºC)

(kΩ)

Tho-S, Tho-R1, Tho-R2

5

10

15

0 20 40 60 80 100 (ºC)

(kΩ)

Tho-A

0

5

10

15

20

25

30

35

0 10 20 30 40 50 (ºC)

(kΩ)

Data for return line temperature sensor (BT3),condensor supply (BT12) and fluid pipe (BT15)

Voltage (VDC)Resistance(kOhm)

Temperature(°C)

3.256351.0-403.240251.6-353.218182.5-303.189133.8-253.15099.22-203.10574.32-153.04756.20-102.97642.89-52.88933.0202.78925.6152.67320.02102.54115.77152.39912.51202.24510.00252.0838.045301.9166.514351.7525.306401.5874.348451.4263.583501.2782.968551.1362.467601.0072.068650.8911.739700.7851.469750.6911.246800.6071.061850.5330.908900.4690.779950.4140.672100

NIBE™ F2040Chapter 8 | Disturbances in comfort38

Page 41: Installer manual

May be due toDescriptionAlarm text on the dis-play

Alarm

Open circuit or short circuit on sensorinput

Sensor does not work (see section"Disturbances in comfort")

Defective control boardAA23 in F2040

Sensor fault, Sensor incoming water inF2040 (BT3).

Sensor fault BT33

Open circuit or short circuit on sensorinput

Sensor does not work (see section"Disturbances in comfort")

Defective control boardAA23 in F2040

Sensor fault, Sensor outgoing water inF2040 (BT12).

Sensor fault BT1212

Open circuit or short circuit on sensorinput

Sensor does not work (see section"Disturbances in comfort")

Defective control boardAA23 in F2040

Sensor fault, Sensor fluid pipe in F2040(BT15).

Sensor fault BT1515

Low flow during heating operation Too high set temperatures

Too high temperature out from the con-denser. Self-resetting.

High condenser out162

Temperature generated by anotherheat source

Too high temperature into the condens-er. Self-resetting.

High condenser in163

Set when the heat pump runs the de-frosting procedure

Not an alarm, but an operating status.Defrosting in progress183

Insufficient air circulation or blockedheat exchanger

Open circuit or short circuit on inputfor high pressure switch (63H1)

Defective high pressure switch Expansion valve not correctly connec-ted

Service valve closed Defective control board in F2040 Low or no flow during heating opera-tion

Defective circulation pump Defective fuse, F(4A)

The high pressure switch (63H1) de-ployed 5 times within 60 minutes or for60 minutes continuously.

HP alarm220

Open circuit or short circuit on inputfor low pressure sensor

Defective low pressure sensor Defective control board in AMS 10 Open circuit or short circuit on inputfor suction gas sensor (Tho-S)

Defective suction gas sensor (Tho-S)

Too lowvalue on the lowpressure sensor3 times within 60 minutes.

LP alarm221

Any circuit breakers for AMS 10 off Incorrect cable routing

Communication between the controlboard and the communication board isinterrupted. Theremust be 22 volt directcurrent (DC) at the switch CNW2 on thecontrol board (PWB1).

OU Com. error223

39Chapter 9 | Alarm listNIBE™ F2040

9 Alarm list

Page 42: Installer manual

May be due toDescriptionAlarm text on the dis-play

Alarm

The fan cannot rotate freely Defective control board in F2040 Defective fan motor Control board in F2040 dirty Fuse (F2) blown

Deviations in the fan speed in F2040.Fan alarm224

Sensor does not work (see section"Ambient temperature sensor")

Insufficient air circulation or heat ex-changer

Blocked If the fault persists during cooling,there may be an insufficient amountof refrigerant.

Defective control board in F2040

Temperature deviation on the hot gassensor (Tho-D) twice within 60 minutesor for 60 minutes continuously.

Continuously high hotgas

230

F2040 not powered Fault in the communication cable.

Communication fault with accessoryboard

Communication error254

Sensor does not work (see section"Disturbances in comfort")

Insufficient air circulation or blockedheat exchanger

Defective control board in F2040 Too much refrigerant

Temperature deviation on the heat ex-changer sensor (Tho-R1/R2) five timeswithin 60 minutes or for 60 minutescontinuously.

High temperature inheatexchanger

261

Can occur when 15V power supply tothe inverter PCB is unstable.

When IPM (Intelligent power module)displays FO-signal (Fault Output) fivetimes during a 60-minute period.

Power transistor too hot262

Incoming power supply interference Service valve closed Insufficient amount of refrigerant Compressor fault Defective circuit board for inverter inF2040

Voltage from the inverter outside theparameters four timeswithin 30minutes.

Inverter error263

Open circuit in connection betweenboards

Defective circuit board for inverter inF2040

Defective control board in F2040

Communication between circuit boardfor inverter and control board broken.

Inverter error264

Defective fan motor Defective circuit board for inverter inAMS 10

Continuousdeviationonpower transistorfor 15 minutes.

Inverter error265

Service valve closed Loose connection sensor (BT15, BT3) Defective sensor (BT15, BT3) Too little refrigerant

Insufficient refrigerant is detected uponstart-up in cooling mode.

Insufficient refrigerant266

Defective circuit board for inverter inF2040

Defective control board in F2040 Compressor fault

Failed start for compressorInverter error267

NIBE™ F2040Chapter 9 | Alarm list40

Page 43: Installer manual

May be due toDescriptionAlarm text on the dis-play

Alarm

Sudden power failureOvercurrent, Inverter A/F moduleInverter error268

Cold weather conditions Sensor fault

Temperature of BT28 below the valuethat permits operation

Cold outdoor air271

Warm weather conditions Sensor fault

Temperature of BT28 above the valuethat permits operation

Hot outdoor air272

Open circuit or short circuit on sensorinput

Sensor does not work (see section"Disturbances in comfort")

Defective control board in F2040

Sensor fault, heat exchanger inF2040(Tho-R).

Sensor fault Tho-R277

Open circuit or short circuit on sensorinput

Sensor does not work (see section"Disturbances in comfort")

Defective control board in F2040

Sensor fault, outdoor temperature sensorin F2040 (Tho-A).

Sensor fault Tho-A278

Open circuit or short circuit on sensorinput

Sensor does not work (see section"Disturbances in comfort")

Defective control board in F2040

Sensor fault, hot gas in F2040 (Tho-D).Sensor fault Tho-D279

Open circuit or short circuit on sensorinput

Sensor does not work (see section"Disturbances in comfort")

Defective control board in F2040

Sensor fault, suction gas in F2040 (Tho-S).

Sensor fault Tho-S280

Open circuit or short circuit on sensorinput

Sensor does not work (see section"Disturbances in comfort")

Defective control board in F2040 Fault in the refrigerant circuit

Sensor fault, low pressure transmitter inF2040.

Sensor fault LPT281

Outdoor module and indoor moduleare not compatible.

Heat pump and indoor module do notwork properly together due to technicalparameters.

Non-compatibleoutdoorair heat pump

294

Open circuit or short circuit on sensor in-put

Sensor fault, Sensor high pressure heat-ing/low pressure cooling in F2040 (BP4).

Sensor fault BP4404

Sensor does not work (see section "Dis-turbances in comfort")

Defective control board AA23 in F2040

41Chapter 9 | Alarm listNIBE™ F2040

Page 44: Installer manual

Condensation water pipeCondensation water pipe, different lengths.

Earth circuit breaker 1-phase.

KVR 10-10 F2040

1 metres

Part no. 067 233

KVR 10-30 F2040

2.5 metres

Part no. 067 235

KVR 10-60 F2040

5 metres

Part no. 067 237

Ground stand

Ground stand F2040-8

Part no. 015 295

Ground stand F2040-12 /-16

Part no. 015 268

Indoor module

VVM 310

Part no. 069 430VVM 310

With integrated EMK 310

Part no. 069 084

VVM320

Copper, 3 x 400 V

Part no. 069 108Stainless Steel, 3 x 400 V

Part no. 069 109Enamel, 3 x 400 V

With integrated EMK 300

Part no. 069 110Stainless Steel, 3 x 230 V

Part no. 069 113Stainless Steel, 1 x 230 V

Part no. 069 111Stainless Steel, 1 x 230 V

With T&P valve

Part no. 069 112

VVM 500

Part no. 069 400

SMO 20

Control module

Part no. 067 224

SMO 40

Control module

Part no. 067 225

Wall mounting

Wall mounting F2040-8

Part no. 067 210

Wall mounting F2040-12

Part no. 067 210

Water heater/Accumulator tank

VPA 300/200

Water heater with double-jacketed vessel.Part no. 088 710CopperPart no. 088 700Enamel

VPA 450/300

Water heater with double-jacketed vessel.Part no. 088 660CopperPart no. 088 670Enamel

VPB 200

Water heater with charge coil.Part no. 088 515CopperPart no. 088 517EnamelPart no. 088 518Stainless

steel

VPB 300

Hot water heater with charge coilPart no. 083 009CopperPart no. 083 011EnamelPart no. 083 010Stainless

steel

VPB 500

Copper lined water heater with charge coil

Part no. 083 220

VPB 750-2

Copper lined water heater with charge coil

Part no. 083 231

VPB 1000

Copper lined water heater with charge coil

Part no. 083 240

NIBE™ F2040Chapter 10 | Accessories42

10 Accessories

Page 45: Installer manual

VPAS 300/450

Water heater with double-jacketed vessel and solarcoil.

Part no. 087 720CopperPart no. 087 710Enamel

43Chapter 10 | AccessoriesNIBE™ F2040

Page 46: Installer manual

Dimensions and setting-out coordinatesF2040-8

50

Ställb

ar 4

0-5

0 8

55

400

670

100

365

225

422 965

1035

95

15

90

Ø40*

F2040

Adjustable 40-50

* Accessory KVR 10 is required.

F2040-12

50

255

Ställb

ar 4

0-5

0 9

55

243

512

110

395

265

50

452 1075

1145

108

Ø40*

14

85

150 m

m

Fritt utrymme bakom

Min. avstånd

vid användning

av flera F2040

600 mm

3000 m

m

400 mm 600mm

Minimalt

fritt utrymme

Minimalt

fritt utrymme

Fritt utrymme

framför

Adjustable 40-50

* Accessory KVR 10 is required.

NIBE™ F2040Chapter 11 | Technical data44

11 Technical data

Page 47: Installer manual

F2040-16

50

180

Ställb

ar 4

0-5

0 1

410

243

512

110

395

265

80

452 1075

1145

108

Ø40*

14

85

Adjustable 40-50

* Accessory KVR 10 is required.

50

255

Ställb

ar 4

0-5

0 9

55

243

512

110

395

265

50

452 1075

1145

108

Ø40*

14

85

150 m

m

Fritt utrymme bakom

Min. avstånd

vid användning

av flera F2040

600 mm

3000 m

m

400 mm 600mm

Minimalt

fritt utrymme

Minimalt

fritt utrymme

Fritt utrymme

framför

Free space behind

Free space infront

Minimum freespace

Minimum freespace

Min. distance when usingseveral F2040

45Chapter 11 | Technical dataNIBE™ F2040

Page 48: Installer manual

Sound pressure levelsF2040 is usually placed next to a house wall, whichgives a directed sound distribution that should beconsidered. Accordingly, you should always attemptwhenpositioning to choose the side that faces the leastsound sensitive neighbouring area.

The soundpressure levels are further affectedbywalls,bricks, differences in ground level, etc and shouldtherefore only be seen as guide values.

F2040adjusts the fan speeddependingon theambienttemperature and evaporation temperature.

2 m

6 m

10 m

2 m

LEK

F2040-16F2040-12F2040-8Air-water heat pump

615754LW(A)Sound power level* According to EN12102 at 7/45 (nominal)

474340dB(A)Sound pressure level at 2 m free standing.*

37.533.530.5dB(A)Sound pressure level at 6 m free standing.*

332926dB(A)Sound pressure level at 10 m free standing.*

* Free space.

NIBE™ F2040Chapter 11 | Technical data46

Page 49: Installer manual

Technical specificationsF2040-16F2040-12F2040-8Air-water heat pump

NominalNominalNominalOutd. temp: /Supply temp.

Heating

7.03/1.45/4.855.21/1.09/4.783.86/0.83/4.657/35 °C (floor)Output data according to EN14511 ΔT5K9.33/2.38/3.926.91/1.79/3.865.11/1.36/3.762/35 °C (floor)

Specified/supplied power/COP (kW/kW/-)12.12/4.33/2.808.98/3.26/2.756.64/2.48/2.68-7/35 °C (floor)8.67/3.62/2.406.42/2.72/2.364.75/2.07/2.292/55 °C6.75/1.74/3.885.00/1.31/3.823.70/1.00/3.707/45 °C9.18/2.98/3.086.80/2.24/3.045.03/1.70/2.962/45 °C12.01/5.36/2.248.90/4.03/2.216.58/3.06/2.15-7/45 °C9.36/5.31/1.766.94/3.99/1.745.13/3.03/1.69-15/45 °C6.38/2.04/3.134.73/1.54/3.073.50/1.17/2.997/55 °C9.66/4.69/2.067.15/3.53/2.035.29/2.68/1.97-7/55 °C

MaxMaxMaxOutd. temp: /Supply temp.

Cooling

13.30/3.99/3.339.87/3.16/3.137.52/2.37/3.1727/7 °COutput data according to EN14511 ΔT5K17.70/4.52/3.9111.70/3.32/3.5211.20/3.20/3.5027/18 °C

Specified/supplied power/EER13.04/4.53/2.889.45/3.41/2.777.10/2.65/2.6835/7 °C15.70/5.04/3.1211.20/3.58/3.129.19/2.98/3.0835/18 °C

Electrical data230V 50 Hz, 230V 2AC 50HzRated voltage

252316ArmsMax operating current, heat pump

242215ArmsMax operating current, compressor

555ArmsStarting current

2 x 868686WNominal output, fan252516ArmsFuse1)

Refrigerant circuitR410AType of refrigerant

Twin RotaryType of compressorM-MA68Compressor oil

4.02.92.55kgVolume4.15 (41.5 bar)MPaCut-out value pressostat HP0.079 (0.79 bar)MPaCut-out value pressostat LP

Brine600043803000m3/hAirflow

-20/43°CMax/Min air tempreverse cycleDefrosting system

Heating medium0.05/0.25 (0.5/2.5bar)MPaMin/Max system pressure heating medium

1508050lMin volume, climate system, heating/cooling15010080lMin volume, climate system, under floor cooling0.790.570.38l/sMax flow, climate system0.390.290.19l/sMin flow, climate system, at 100% circulation

pump speed (defrosting flow)0.250.150.12l/sMin flow, heating

47Chapter 11 | Technical dataNIBE™ F2040

Page 50: Installer manual

F2040-16F2040-12F2040-8Air-water heat pump

0.320.200.15l/sMin flow, cooling58/25°CMax/Min heating medium temp continuous

operationG1"Connection heating medium ext thread

Dimensions and weight114511451035mmWidth452452422mmDepth

1450 (+50/-0)995 (+50/-0)895 (+50/-0)mmHeight with stand13510590kgWeight (excl. packaging)

MiscellaneousIP 24Enclosure class

dark greyColour064 108064 092064 109Part No.

1)Specified output is limited with lower fusing.

NIBE™ F2040Chapter 11 | Technical data48

Page 51: Installer manual

Working range, compressor operation - heating

F2040-8 , -12 , -16

65

58

55

40

60

50

45

35

25

30

20

154340302520100-10-20-30 50

Utomhustemperatur (°C)

35

30

15

25

20

12

7

10

5

04540 43353025201510 50

Vattentemperatur

(°C)

Vattentemperatur

(°C)

Utomhustemperatur (°C)

Water temperature

°C

°C

Outdoor air temperature

Framledning

Returledning

Framledning

Returledning

Supply temperatureReturn temp

During shorter time it is allowed to have lower working temperatures on the water side, e.g. during start up.

Working range, compressor operation - cooling

F2040-8 , -12 , -16

65

58

55

40

60

50

45

35

25

30

20

154340302520100-10-20-30 50

Utomhustemperatur (°C)

35

30

15

25

20

12

7

10

5

04540 43353025201510 50

Vattentemperatur

(°C)

Vattentemperatur

(°C)

Utomhustemperatur (°C)

Water temperature

°C

°C

Outdoor air temperature

Framledning

Returledning

Framledning

Returledning

Supply temperatureReturn temp

49Chapter 11 | Technical dataNIBE™ F2040

Page 52: Installer manual

Output and COP at different supply temperatures

F2040-8

0,00

2,00

4,00

6,00

8,00

10,00

12,00

(kW

)

T out

Max avgiven e!ekt F2040-8

35

45

55

0,00

1,00

2,00

3,00

4,00

5,00

CO

P

COP F2040-8

35

45

55

15105-5-10-15-20-25 0

T out

15105-5-10-15-20-25 0

COP F2040-8

Max specified output F2040-8

Outdoor temperature

Outdoor temperature

kW

COP

NIBE™ F2040Chapter 11 | Technical data50

Page 53: Installer manual

F2040-12

0,00

2,00

4,00

6,00

8,00

10,00

12,00

14,00

16,00

(kW

)

Max avgiven eekt F2040-12

35

45

55

0,00

1,00

2,00

3,00

4,00

5,00

6,00

CO

P

COP F2040-12

35

45

55

T out

15105-5-10-15-20-25 0

T out

15105-5-10-15-20-25 0

Outdoor temperature

Outdoor temperature

Max specified output F2040-12

COP F2040-12

kW

COP

51Chapter 11 | Technical dataNIBE™ F2040

Page 54: Installer manual

F2040-16

0,00

5,00

10,00

15,00

20,00

25,00

(kW

)

Max avgiven e!ekt F2040-16

35

45

55

0,00

1,00

2,00

3,00

4,00

5,00

6,00

CO

P

COP F2040-16

35

45

55

T out

15105-5-10-15-20-25 0

T out

15105-5-10-15-20-25 0

Outdoor temperature

Outdoor temperature

Max specified output F2040-16

COP F2040-16

kW

COP

NIBE™ F2040Chapter 11 | Technical data52

Page 55: Installer manual

Output with lower fuse rating than recommended

F2040-12 /16

Avgiven eekt F2040-12 vid avsäkring 16A

Avgiven eekt F2040-12 vid avsäkring 20A

Avgiven eekt F2040-16 vid avsäkring 20A

0,00

8,00

6,00

4,00

2,00

10,00

12,00

14,00

16,00

(kW

)

35

45

55

35

45

55

35

45

55

T ute

15105-5-10-15-20-25 0

T ute

15105-5-10-15-20-25 0

T ute

15105-5-10-15-20-25 0

(kW

)

0,00

8,00

6,00

4,00

2,00

10,00

12,00

14,00

16,00

0,00

5,00

10,00

15,00

20,00

25,00

(kW

)

fusing 16A

fusing 20A

fusing 20A

Specified output F2040-12

Specified output F2040-12

Specified output F2040-16

Outdoor temperature

kW

Outdoor temperature

kW

Outdoor temperature

kW

53Chapter 11 | Technical dataNIBE™ F2040

Page 56: Installer manual

Energy labelling

Information sheet

NIBESupplier

F2040-16F2040-12F2040-8Model

VVM 310VVM 320VVM 320Model hot water heater

35 / 5535 / 5535 / 55°CTemperature application

XLXLXLDeclared load profile for water heating

A++ / A++A++ / A++A++ / A++Seasonal spaceheatingenergyefficiency class, averageclimate

AAAWater heating energy efficiency class, average climate

14.5 / 14.011.5 / 10.08.2 / 7.0kWRated heat output (Pdesignh), average climate6,702 / 8,4315,382 / 6,1363,882 / 4,447kWhAnnual energy consumption space heating, average

climate1,7021,7021,689kWhAnnual energy consumption water heating, average

climate176 / 134174 / 132172 / 127%Seasonal space heating energy efficiency, average cli-

mate989899%Water heating energy efficiency, average climate353535dBSound power level LWA indoors

15.0 / 16.011.5 / 13.09.0 / 10.0kWRated heat output (Pdesignh), cold climate15.0 / 15.012.0 / 12.08.0 / 8.0kWRated heat output (Pdesignh), warm climate

10,040 / 13,6297,798 / 11,1976,264 / 8,844kWhAnnual energy consumption space heating, cold cli-mate

1,9041,9041,886kWhAnnual energy consumption water heating, cold cli-mate

3,370 / 4,1832,759 / 3,4191,879 / 2,333kWhAnnual energy consumption space heating, warm cli-mate

1,5511,5511,540kWhAnnual energy consumption water heating, warmclimate

144 / 113142 / 111139 / 108%Seasonal space heating energy efficiency, cold climate888889%Water heating energy efficiency, cold climate

235 / 189229 / 185225 / 180%Seasonal space heating energy efficiency, warm cli-mate

108108109%Water heating energy efficiency, warm climate615754dBSound power level LWA outdoors

Data for energy efficiency of the package

F2040-16F2040-12F2040-8Model

VVM 310VVM 320VVM 320Model hot water heater

35 / 5535 / 5535 / 55°CTemperature application

VIController, class4.0%Controller, contribution to efficiency

180 / 138178 / 136176 / 131%Seasonal space heating energy efficiency of the pack-age, average climate

A+++ / A++A+++ / A++A+++ / A++Seasonal space heating energy efficiency class of thepackage, average climate

148 / 117146 / 115143 / 112%Seasonal space heating energy efficiency of the pack-age, cold climate

239 / 193233 / 189229 / 184%Seasonal space heating energy efficiency of the pack-age, warm climate

The reported efficiency of the package also takes the controller into account. If an external supplementary boiler or solar heating is addedto the package, the overall efficiency of the package should be recalculated.

NIBE™ F2040Chapter 11 | Technical data54

Page 57: Installer manual

Technical documentation

F2040-8Model

VVM 320Model hot water heater

Air-water

Exhaust-water

Brine-water

Water-water

Type of heat pump

Yes NoLow-temperature heat pump

Yes NoIntegrated immersion heater for additional heat

Yes NoHeat pump combination heater

Average Cold WarmClimate

Average (55 °C) Low (35 °C)Temperature application

EN14825 / EN16147Applied standards%127ƞsSeasonal space heating energy efficiencykW7.0PratedRated heat output

Declared coefficient of performance for space heating at part load and atoutdoor temperature Tj

Declared capacity for space heating at part load and at outdoor temperatureTj

kW1.94COPdTj = -7 °CkW6.3PdhTj = -7 °CkW3.11COPdTj = +2 °CkW3.9PdhTj = +2 °CkW4.42COPdTj = +7 °CkW2.6PdhTj = +7 °CkW5.93COPdTj = +12 °CkW3.7PdhTj = +12 °CkW1.83COPdTj = bivkW6.6PdhTj = bivkW1.86COPdTj = TOLkW5.9PdhTj = TOLkWCOPdTj = -15 °C (if TOL < -20 °C)kWPdhTj = -15 °C (if TOL < -20 °C)

°C-10TOLMin. outdoor air temperature°C-8.6TbivBivalent temperature

-COPcycCycling interval efficiencykWPcychCycling interval capacity°C58.0WTOLMax supply temperature-0.97CdhDegradation coefficient

Additional heatPower consumption in modes other than active mode

kW1.1PsupRated heat outputkW0.002POFFOff mode

kW0.010PTOThermostat-off mode

ElectricType of energy inputkW0.015PSBStandby mode

kW0.030PCKCrankcase heater mode

Other items

m3/h3,000Rated airflow (air-water)VariableCapacity control

m3/h0.60Nominal heating medium flowdB35 / 54LWASound power level, indoors/outdoors

m3/hBrine flow brine-water or water-water heatpumps

kWh4,447QHEAnnual energy consumption

For heat pump combination heater

%99ƞwhWater heating energy efficiencyXLDeclared load profile for water heating

kWhQfuelDaily fuel consumptionkWh7.69QelecDaily energy consumption

GJAFCAnnual fuel consumptionkWh1,689AECAnnual energy consumption

55Chapter 11 | Technical dataNIBE™ F2040

Page 58: Installer manual

F2040-12Model

VVM 320Model hot water heater

Air-water

Exhaust-water

Brine-water

Water-water

Type of heat pump

Yes NoLow-temperature heat pump

Yes NoIntegrated immersion heater for additional heat

Yes NoHeat pump combination heater

Average Cold WarmClimate

Average (55 °C) Low (35 °C)Temperature application

EN14825 / EN16147Applied standards%132ƞsSeasonal space heating energy efficiencykW10.0PratedRated heat output

Declared coefficient of performance for space heating at part load and atoutdoor temperature Tj

Declared capacity for space heating at part load and at outdoor temperatureTj

kW1.99COPdTj = -7 °CkW8.9PdhTj = -7 °CkW3.22COPdTj = +2 °CkW5.5PdhTj = +2 °CkW4.61COPdTj = +7 °CkW3.5PdhTj = +7 °CkW6.25COPdTj = +12 °CkW5.0PdhTj = +12 °CkW1.90COPdTj = bivkW9.2PdhTj = bivkW1.92COPdTj = TOLkW8.1PdhTj = TOLkWCOPdTj = -15 °C (if TOL < -20 °C)kWPdhTj = -15 °C (if TOL < -20 °C)

°C-10TOLMin. outdoor air temperature°C-7.9TbivBivalent temperature

-COPcycCycling interval efficiencykWPcychCycling interval capacity°C58.0WTOLMax supply temperature-0.98CdhDegradation coefficient

Additional heatPower consumption in modes other than active mode

kW1.9PsupRated heat outputkW0.002POFFOff mode

kW0.014PTOThermostat-off mode

ElectricType of energy inputkW0.015PSBStandby mode

kW0.035PCKCrankcase heater mode

Other items

m3/h4,380Rated airflow (air-water)VariableCapacity control

m3/h0.86Nominal heating medium flowdB35 / 57LWASound power level, indoors/outdoors

m3/hBrine flow brine-water or water-water heatpumps

kWh6,136QHEAnnual energy consumption

For heat pump combination heater

%98ƞwhWater heating energy efficiencyXLDeclared load profile for water heating

kWhQfuelDaily fuel consumptionkWh7.75QelecDaily energy consumption

GJAFCAnnual fuel consumptionkWh1,702AECAnnual energy consumption

NIBE™ F2040Chapter 11 | Technical data56

Page 59: Installer manual

F2040-16Model

VVM 310Model hot water heater

Air-water

Exhaust-water

Brine-water

Water-water

Type of heat pump

Yes NoLow-temperature heat pump

Yes NoIntegrated immersion heater for additional heat

Yes NoHeat pump combination heater

Average Cold WarmClimate

Average (55 °C) Low (35 °C)Temperature application

EN14825 / EN16147Applied standards%134ƞsSeasonal space heating energy efficiencykW14.0PratedRated heat output

Declared coefficient of performance for space heating at part load and atoutdoor temperature Tj

Declared capacity for space heating at part load and at outdoor temperatureTj

kW2.01COPdTj = -7 °CkW12.5PdhTj = -7 °CkW3.29COPdTj = +2 °CkW7.6PdhTj = +2 °CkW4.68COPdTj = +7 °CkW4.9PdhTj = +7 °CkW6.51COPdTj = +12 °CkW6.8PdhTj = +12 °CkW1.95COPdTj = bivkW12.7PdhTj = bivkW1.95COPdTj = TOLkW11.0PdhTj = TOLkWCOPdTj = -15 °C (if TOL < -20 °C)kWPdhTj = -15 °C (if TOL < -20 °C)

°C-10TOLMin. outdoor air temperature°C-7.6TbivBivalent temperature

-COPcycCycling interval efficiencykWPcychCycling interval capacity°C58.0WTOLMax supply temperature-0.98CdhDegradation coefficient

Additional heatPower consumption in modes other than active mode

kW3.0PsupRated heat outputkW0.002POFFOff mode

kW0.016PTOThermostat-off mode

ElectricType of energy inputkW0.015PSBStandby mode

kW0.035PCKCrankcase heater mode

Other items

m3/h6,000Rated airflow (air-water)VariableCapacity control

m3/h1.21Nominal heating medium flowdB35 / 61LWASound power level, indoors/outdoors

m3/hBrine flow brine-water or water-water heatpumps

kWh8,431QHEAnnual energy consumption

For heat pump combination heater

%98ƞwhWater heating energy efficiencyXLDeclared load profile for water heating

kWhQfuelDaily fuel consumptionkWh7.75QelecDaily energy consumption

GJAFCAnnual fuel consumptionkWh1,702AECAnnual energy consumption

57Chapter 11 | Technical dataNIBE™ F2040

Page 60: Installer manual

Electrical circuit diagramF2040-8

NIBE™ F2040Chapter 11 | Technical data58

Page 61: Installer manual

INV

PW

B2

OR

GR

1

F

P

BK

BK

(4A

)2 3

Th

o­P

BP1

63

H1

BT1

4

Th

o­D

BT1

6

Th

o­R

1

BT1

7

Th

o­S

BT2

8

Th

o­A

BP2

LPT

20

S

QN

2EB

10

CH

EB

11

DH

2 11 2 3 4 5 6

AA

23

- X

1

AA

23

- X

10

0

Ma

tnin

g 2

30

V 5

0 H

z

59Chapter 11 | Technical dataNIBE™ F2040

Page 62: Installer manual

F2040-12

NIBE™ F2040Chapter 11 | Technical data60

Page 63: Installer manual

L1R

DF

(30

A)

F (8

A)

WH R

D WH

21

RD

WH

RD

BL

RD

WH

BL

RD

WH

L1o

No

TB

TB N

P1

N1

RD

RD

WH

BL

BL

BK

RD

BL

P2

N2

UV

W

UV

W

PN

2

DM

NOISE

FILT

ER P

WB3

PW

B2

IN

VER

TER

12

34

SW

3LE

D1

SW

1LE

D2

BL

CT

CN

W(B

K)

CN

W2

(OR

)C

NEEV

1(W

H)

6

CN

I2(W

H)

CN

I4(W

H)

CN

I1(W

H)

CN

I3(W

H)

CN

A2

(WH

)

CN

AC

T1

(WH

)

IPM

CN

A1

(WH

)

BL

RD BL

RD BL

PW

B1

BL

4

OR

3

Y

2

WH

1

RD

CN

EEV

2(R

D)

CN

PS

(RD

)C

NB

(RD

)

6

BL

4

OR

3

Y

2

WH

1

WHRD

BK

CN

IP(Y

)

Th

o­PBK

BK

OR CN

FAN

1(W

H)BL

7

BR

6

WH

54

RD 1

CN

H(B

R)

BP1

63

H1

Tw

o f

an

un

it o

nly

Tw

o f

an

un

it o

nly

BK

BK

CN

S(R

D)

CN

R(W

H)

CN

F(B

K)

BL

BL

EB

10

CH

BR

BR

BT1

4Th

o­DBK

BK

BT1

6Th

o­R

1BK

BK

CN

TH

(WH

) BT1

7Th

o­SRD

RD

BT2

8Th

o­AY

Y

52X

152X

3

EB

11

DH

BK

BK

++

+−

A/F

MO

DU

LEP N2

L1

L

L2

1 2 3

SM

1SM

2

MS

3~

MM

CM

FM0

1

20

SQ

N2

CN

N1

(Y)

BL

BL

SV

1B

P2

LPT

°t

°t°t

°t°t

°t

Th

o­R

2

BK

BK

OR CN

FAN

2(W

H)BL

7

BR

6

WH

54

RD 1

M

FM0

2

M

GN

E

GN

E

52X

252X

4

F (4

A)

Tw

o f

an

mo

tor

un

it o

nly

GN

Y/G

N

2 11 2 3 4 5 6

Matn

ing

230V

50 H

z

AA

23

- X

1

AA

23

- X

10

0

61Chapter 11 | Technical dataNIBE™ F2040

Page 64: Installer manual

F2040-16

NIBE™ F2040Chapter 11 | Technical data62

Page 65: Installer manual

L1R

DF

(30

A)

F (8

A)

WH R

D WH

21

RD

WH

RD

BL

RD

WH

BL

RD

WH

L1o

No

TB

TB N

P1

N1

RD

RD

WH

BL

BL

BK

RD

BL

P2

N2

UV

W

UV

W

PN

2

DM

NOISE

FILT

ER P

WB3

PW

B2 IN

VERTER

12

34

SW

3LE

D1

SW

1LE

D2

BL

CT

CN

W(B

K)

CN

W2

(OR

)C

NEEV

1(W

H)

6

CN

I2(W

H)

CN

I4(W

H)

CN

I1(W

H)

CN

I3(W

H)

CN

A2

(WH

)

CN

AC

T1

(WH

)

IPM

CN

A1

(WH

)

BL

RD BL

RD BL

PW

B1

BL

4

OR

3

Y

2

WH

1

RD

CN

EEV

2(R

D)

CN

PS

(RD

)C

NB

(RD

)

6

BL

4

OR

3

Y

2

WH

1

WHRD

BK

CN

IP(Y

)

Th

o­PBK

BK

OR CN

FAN

1(W

H)BL

7

BR

6

WH

54

RD 1

CN

H(B

R)

BP1

63H

1

Tw

o f

an

unit o

nly

BK

BK

CN

S(R

D)

CN

R(W

H)

CN

F(B

K)

BL

BL

EB

10

CH

BR

BR

BT14

Th

o­DBK

BK

BT16

Th

o­R

1BK

BK

CN

TH

(WH

) BT17

Th

o­SRD

RD

BT28

Th

o­AY

Y

52X

52X

3

EB

11

DH

BK

BK

++

+−

A/F

MO

DU

LEP N2

L1

L

L2

1 2 3

SM

1SM

2

MS

3~

MM

CM

FM01

20

SQ

N2

CN

N1

(Y)

BL

BL

SV

1BP2 L

PT

°t

°t°t

°t°t

°t

Th

o­R

2

BK

BK

OR CN

FAN

2(W

H)BL

7

BR

6

WH

54

RD 1

M

FM02

M

GN

E

GN

E

52X

252X

4

F (4

A)

GN

Y/G

N

Matn

ing

23

0V

50 H

z

2 11 2 3 4 5 6

AA

23 -

X1

AA

23 -

X100

63Chapter 11 | Technical dataNIBE™ F2040

Page 66: Installer manual

Item register

AAccessories, 42Addressing via multi-heat pump operation, 29Adjustment, charge flow, 33Alarm list, 39Ambient temperature sensor, 29Assembly, 6

CCommissioning and adjusting, 30

Adjustment, charge flow, 33Compressor heater, 30Filling and venting the heating medium system, 30Preparations, 30Readjusting, heating medium side, 32Start-up and inspection, 31

Communication, 29Compressor heater, 30Connecting accessories, 21Connections, 24Contact information, 5

DDelivery and handling, 6

Assembly, 6Installation area, 8Removing the covers, 9Removing the front panel, 9Removing the side panel, 10Supplied components, 8Transport and storage, 6

Dimensions and setting-out coordinates, 44Disturbances in comfort, 35

Troubleshooting, 35Docking alternatives, 21

EElectrical circuit diagram, 58Electrical connection, 16Electrical connections, 22

Addressing via multi-heat pump operation, 29Ambient temperature sensor, 29Communication, 29Connecting accessories, 21Connections, 24External heating cable (KVR 10), 28General, 22Power connection to rear side (standard) or underneath (al-ternative), 24

Energy labelling, 54Data for energy efficiency of the package, 54Information sheet, 54Technical documentation, 55

External heating cable (KVR 10), 28

FFilling and venting the heating medium system, 30

IImportant information, 2

Safety information, 2Inspection of the installation, 4Installation area, 8

MMarking, 2

PPipe connections, 19

Docking alternatives, 21

General, 19Pipe coupling heating medium circuit, 19Water volumes, 19

Pipe coupling heating medium circuit, 19Power connection to rear side (standard) or underneath (altern-ative), 24Preparations, 30

RReadjusting, heating medium side, 32Removing the covers, 9Removing the front panel, 9Removing the side panel, 10

SSafety information, 2

Contact information, 5Inspection of the installation, 4Marking, 2Serial number, 2Symbols, 2

Sensor placement, 36Serial number, 2Sound pressure levels, 46Start-up and inspection, 31Supplied components, 8Symbols, 2

TTechnical data, 44

Dimensions and setting-out coordinates, 44Electrical circuit diagram, 58Sound pressure levels, 46Technical Data, 47

Technical Data, 47The heat pump design, 11

Component locations, 11Electrical components, 16Electrical connection, 16List of components, 11

Transport and storage, 6Troubleshooting, 35

Sensor placement, 36

NIBE™ F2040Chapter 12 | Item register64

12 Item register

Page 67: Installer manual

SE

ÅtervinningLämna avfallshanteringen av emballaget till den installatör som installerade produkten eller till särskildaavfallsstationer.

När produkten är uttjänt får den inte slängas bland vanligt hushållsavfall. Den ska lämnas in till särskildaavfallsstationer eller till återförsäljare som tillhandahåller denna typ av service.

Felaktig avfallshantering av produkten från användarens sida gör att administrativa påföljder tillämpasi enlighet med gällande lagstiftning.

GB

RecoveryLeave the disposal of the packaging to the installerwho installed the product or to specialwaste stations.

Do not dispose of used products with normal householdwaste. It must be disposed of at a special wastestation or dealer who provides this type of service.

Improper disposal of theproduct by theuser results in administrative penalties in accordancewith currentlegislation.

DE

RecyclingÜbergeben Sie den Verpackungsabfall dem Installateur, der das Produkt installiert hat, oder bringen Sieihn zu den entsprechenden Abfallstationen.

Wenn das Produkt das Ende seiner Lebensdauer erreicht hat, darf es nicht über den normalen Hausmüllentsorgtwerden. Stattdessenmussesbei speziellenEntsorgungseinrichtungenoderHändlernabgegebenwerden, die diese Dienstleistung anbieten.

Eine unsachgemäße Entsorgung des Produkts durch den Benutzer zieht Verwaltungsstrafen gemäßgeltendem Recht nach sich.

Page 68: Installer manual

WS name: -GemensamtWS version: a74 (working edition)Publish date: 2015-08-31 09:21

NIBE AB Sweden

Hannabadsvägen 5Box 14 SE-285 21 [email protected]

231844