Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500...

76
Installer manual APH NIBE™ VVM 500 Indoor module IHB GB 1428-5 031991

Transcript of Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500...

Page 1: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Installer manual

APH

NIBE™ VVM 500Indoor module

IHB GB 1428-5031991

Page 2: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

A detailed explanation of the button functions can be found on page 30.

How to scroll through menus and make different settings is described on page 32.

The mode for setting the indoor temperature is reached, when in the start mode in the main menu, by pressingthe OK button twice. Read more about the settings on page 34.

To temporarily increase the amount of hot water, first turn the control knob to mark menu 2 (water droplet) andthen press the OK button twice. Read more about the settings on page 40.

In event of disturbances in comfortIf a disturbance in comfort of any type occurs there are some measures that can be taken before you need tocontact your installer. See page 58 for instructions.

Page 3: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Table of Contents

21 Important information2Safety information

52 Delivery and handling5Transport

5Assembly

6Supplied components

7Removing the covers

83 Indoor module's design

104 Pipe connections10General pipe connections

11Dimensions and pipe connections

14Installation alternative

185 Electrical connections18General

20Connections

22Settings

23Optional connections

26Connecting accessories

276 Commissioning and adjusting27Preparations

27Filling and venting

28Start-up and inspection

307 Control - Introduction30Display unit

31Menu system

348 Control - Menus34Menu 1 - INDOOR CLIMATE

40Menu 2 - HOT WATER

42Menu 3 - INFO

43Menu 4 - MY SYSTEM

49Menu 5 - SERVICE

559 Service55Service actions

5810 Disturbances in comfort58Info-menu

58Manage alarm

58Troubleshooting

6011 Accessories

6112 Technical data61Dimensions and setting-out coordinates

62Hot water capacity

63Technical specifications

64Electrical circuit diagram, 3 x 400V

69Index

1Table of Contents |NIBE™ VVM 500

Page 4: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Safety informationThis manual describes installation and service proced-ures for implementation by specialists.

This appliance can be used by childrenaged from 8 years and above and per-sons with reduced physical, sensory ormental capabilities or lack of experienceand knowledge if they have been givensupervision or instruction concerninguse of the appliance in a safe way andunderstand the hazards involved. Chil-dren shall not play with the appliance.Cleaning and user maintenance shallnot be made by children without super-vision.

Rights to make any design or technicalmodifications are reserved.

©NIBE 2014.

Symbols

NOTE

This symbol indicates danger to machine orperson.

Caution

This symbol indicates important informationabout what you should observe when main-taining your installation.

TIP

This symbol indicates tips on how to facilitateusing the product.

MarkingVVM 500 is CE marked and fulfils IP21.

The CE marking means that NIBE ensures that theproduct meets all regulations that are placed on itbased on relevant EU directives. The CE mark is obligat-ory for most products sold in the EU, regardless wherethey are made.

IP21 means that the product can be touched by hand,that objects with a diameter larger than or equivalentto 12.5 mm cannot penetrate and cause damage andthat the product is protected against vertically fallingdrops.

Serial numberThe serial number can be found at the bottom right ofthe front cover and in the info menu (menu 3.1).

Caution

Always give the product's serial number (14digits) when reporting a fault.

Country specific information

Installer manual

This installer manual must be left with the customer.

NIBE™ VVM 500Chapter 1 | Important information2

1 Important information

Page 5: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Inspection of the installationCurrent regulations require the heating installation to be inspected before it is commissioned. The inspection mustbe carried out by a suitably qualified person. Fill in the page for information about installation data in the Usermanual.

DateSignatureNotesDescription✔

Heating medium (page 15)

System flushed

System vented

Expansion vessel

Particle filter

Safety valve

Shut off valves

Boiler pressure

Connected according to outline diagram

Hot water (page 15)

Shut off valves

Mixing valve

Safety valve

Electricity (page 18)

Connected communication

Circuit fuses

Fuses, indoor module

Fuses property

Outside sensor

Room sensor

Current sensor

Safety breaker

Earth circuit-breaker

Setting of emergency mode thermostat

Miscellaneous

Docked to

3Chapter 1 | Important informationNIBE™ VVM 500

Page 6: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Contact information

KNV Energietechnik GmbH, Gahberggasse 11, 4861 SchörflingAT

Tel: +43 (0)7662 8963-0 Fax: +43 (0)7662 8963-44 E-mail: [email protected] www.knv.atNIBE Wärmetechnik AG, Winterthurerstrasse 710, CH-8247 FlurlingenCH

Tel: (52) 647 00 30 Fax: (52) 647 00 31 E-mail: [email protected] www.nibe.chDruzstevni zavody Drazice s.r.o, Drazice 69, CZ - 294 71 Benatky nad JizerouCZ

Tel: +420 326 373 801 Fax: +420 326 373 803 E-mail: [email protected] www.nibe.czNIBE Systemtechnik GmbH, Am Reiherpfahl 3, 29223 CelleDE

Tel: 05141/7546-0 Fax: 05141/7546-99 E-mail: [email protected] www.nibe.deVølund Varmeteknik A/S, Member of the Nibe Group, Brogårdsvej 7, 6920 VidebækDK

Tel: 97 17 20 33 Fax: 97 17 29 33 E-mail: [email protected] www.volundvt.dkNIBE Energy Systems OY, Juurakkotie 3, 01510 VantaaFI

Puh: 09-274 697 0 Fax: 09-274 697 40 E-mail: [email protected] www.nibe.fiNIBE Energy Systems France Sarl, Zone industrielle RD 28, 01600 ReyrieuxFR

Tel : 03 88 06 24 10 Fax : 03 88 06 24 11 E-mail: [email protected] www.nibe.frNIBE Energy Systems Ltd, 3C Broom Business Park, Bridge Way, Chesterfield S41 9QGGB

Tel: 0845 095 1200 Fax: 0845 095 1201 E-mail: [email protected] www.nibe.co.ukNIBE Energietechniek B.V., Postbus 634, NL 4900 AP OosterhoutNL

Tel: 0168 477722 Fax: 0168 476998 E-mail: [email protected] www.nibenl.nlABK AS, Brobekkveien 80, 0582 Oslo, Postadresse: Postboks 64 Vollebekk, 0516 OsloNO

Tel. sentralbord: +47 23 17 05 20 E-mail: [email protected] www.nibeenergysystems.noNIBE-BIAWAR Sp. z o. o. Aleja Jana Pawła II 57, 15-703 BIAŁYSTOKPL

Tel: 085 662 84 90 Fax: 085 662 84 14 E-mail: [email protected] www.biawar.com.pl© "EVAN" 17, per. Boynovskiy, Nizhny NovgorodRU

Tel./fax +7 831 419 57 06 E-mail: [email protected] www.nibe-evan.ruNIBE AB Sweden, Box 14, Hannabadsvägen 5, SE-285 21 MarkarydSE

Tel: +46-(0)433-73 000 Fax: +46-(0)433-73 190 E-mail: [email protected] www.nibe.se

For countries not mention in this list, please contact Nibe Sweden or check www.nibe.eu for more information.

NIBE™ VVM 500Chapter 1 | Important information4

Page 7: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

TransportVVM 500 should be transported and stored verticallyin a dry place. The VVM 500 may, however, be carefullylaid on its back when being moved into a building.

R

0

R0

AssemblyPosition VVM 500 on a firm base that can take theweight, preferably on a concrete floor or foundation.Use the product's adjustable feet to obtain a horizont-al and stable set-up.

30 - 50 mm

The area where VVM 500 is located must beequipped with floor drainage.

Installation areaLeave a space of 500 mm in front of the product. Allservice on VVM 500 can be carried out from the front.

500

NOTE

Leave 10-25 mm free space between the in-door module and the wall behind for routingof cables and pipes.

5Chapter 2 | Delivery and handlingNIBE™ VVM 500

2 Delivery and handling

Page 8: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Supplied components

Room sensorOutside sensor

LEK

LEK

LEK

O-ringsCurrent sensor

LEK

APH

Cable*Flow meter*

Union nut*Copper pipe with pumpflange*

*Only applies to Norway.

LocationThe kit of supplied items is placed on top of theproduct.

NIBE™ VVM 500Chapter 2 | Delivery and handling6

Page 9: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Removing the coversFront cover

1

2L

EK

LE

K

1. Remove the screws from the lower edge of thefront cover.

2. Lift the cover out at the bottom edge and up.

Side covers

LE

K

LE

K

LE

K

The side covers can be removed to facilitate the install-ation.1. Remove the screws from the upper and lower

edges.2. Twist the cover slightly outward.3. Move the hatch backwards and slightly to the side.4. Pull the cover to one side.5. Pull the hatch forwards.

7Chapter 2 | Delivery and handlingNIBE™ VVM 500

Page 10: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

VVM 500

APH

VVM 500

NIBE™ VVM 500Chapter 3 | Indoor module's design8

3 Indoor module's design

Page 11: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Pipe connectionsConnection, heating medium supply line G25int.

XL1

Connection, heating medium return line G25int.

XL2

Connection, cold water G25 int.XL3Connection, hot water G25 int.XL4Connection, docking in heating medium G25int.

XL8

Connection, docking out heating medium G25int.

XL9

Connection, solar system supply line Ø22 mmXL13Connection, solar system return line Ø22 mmXL14Connection, docking in high temp G25 int.XL18Connection, docking out high temp G25 int.XL19Connection, docking pool Ø28 mmXL39

HVAC componentsExpansion tank (connection) G20 int.CM1Circulation pumpGP1Charge pumpGP12Drain valve, climate systemQM1Venting, climate systemQM20Shuttle valve, climate system/water heater, flowline

QN10

Shunt valveQN11

Sensors etc.Temperature sensors, heating medium flowBT2Temperature sensor, heating medium return*BT3Temperature sensor, hot water, control*BT6Temperature sensor, hot water, display*BT7Temperature sensor, solar coil*BT54Temperature sensor, heating medium supplyafter immersion heater

BT63

Electrical componentsImmersion heater cardAA 1Base cardAA 2Input circuit boardAA 3Display unitAA 4

AA4-XJ3 USB socket

AA4-XJ4 Service socketExtra relay circuit boardAA 7Immersion heaterEB 1Miniature circuit-breakerFA 1Temperature limiterFD 1SwitchSF 1Network cable for NIBE UplinkTMW130

MiscellaneousRating platePF 1

Serial number platePF 3Cable glandUB1Cable glandUB2

* Not visible in the image

Designations in component locations according tostandard IEC 81346-1 and 81346-2.

9Chapter 3 | Indoor module's designNIBE™ VVM 500

Page 12: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

General pipe connectionsPipe installation must be carried out in accordance withcurrent norms and directives.

The system requires a low-temperature design of theradiator circuit. At lowest dimensioned outdoor tem-perature the highest recommended temperatures are55 °C on the flow line and 45 °C on the return line, butVVM 500 can handle up to 65 °C.

NOTE

Equip the product with a safety valve on boththe boiler side and domestic coil.

Overflow water from the safety valve goes via overflowcups to a drain so that hot water splashes cannot causeinjury. The entire length of the overflow water pipemust be inclined to prevent water pockets and mustalso be frost proof.

NIBE recommends installing VVM 500 as close to theheat pump as possible for optimum comfort. For furtherinformation about the location of different compon-ents, see section "Installation alternatives" in thismanual.

NOTE

Any high points in the climate system, mustbe equipped with air vents.

NOTE

The pipe systems need to be flushed out be-fore the indoor module is connected so thatany debris cannot damage component parts.

NOTE

Switch (SF1) must not be moved to "" or " "until VVM 500 has been filled with water.Otherwise the temperature limiter, thermostatand the immersion heater etc can be dam-aged.

Maximum boiler and radiator volumes

H

Internal volume in VVM 500for calculating expansionvessel is 500 l. The expansionvessel's volume must be atleast 5 % of the system's totalvolume.

Example table

Volume (l)expansionvessel

Totalvolume (l)(indoormodule andclimate sys-tem)

25500

35700

Volume (l) expansionvessel

Total volume (l) (indoormodule and climate sys-tem)

501000

NOTE

Expansion vessel not supplied with theproduct. Equip the product with an expansionvessel.

The initial pressure of the pressure expansion vesselmust be dimensioned according to the maximumheight (H) between the vessel and the highest posi-tioned radiator, see figure. An initial pressure of 0.5bar (5 mvp) means a maximum permitted height differ-ence of 5 m.

If the standard initial pressure in the pressure vessel isnot high enough it can be increased by filling via thevalve in the expansion vessel. The expansion vessel'sstandard initial pressure must be entered in the checklist on page 3.

Any change in the initial pressure affects the ability ofthe expansion vessel to handle the expansion of thewater.

System diagramVVM 500 consists of a hot water coil, immersion heater,circulation pumps, buffer vessel, control system and isprepared for use with solar panels. VVM 500 connectsto the climate system.

VVM 500 is designed for connection and communica-tion with F2025/F2026/F2030/F2040/F2300, whichtogether make up a complete heating installation.

VVM 500 covers most of the heating and hot waterrequirement down to the heat pump stop temperature.

When it is cold outdoorsF2025/F2026/F2030/F2040/F2300 works with VVM500 and if the outdoor air temperature falls below theheat pump stop temperature, all heating is carried outby VVM 500.

NOTE

Applies to NIBE F2025 and later models orprogram version 55 and later versions.

-FL2-CM1

-EB15

-RN10-EB101

XL2

XL1-HQ1

-QM1

-QM41

-FL10

-QM40

-EB101

-FL1

-QM40-RM1

NIBE™ VVM 500Chapter 4 | Pipe connections10

4 Pipe connections

Page 13: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Symbol key

MeaningSymbol

Shut-off valve

Tapping valve

Non-return valve

Shunt / shuttle valve

Safety valve

ThermometerT

Trim valve

Temperature sensor

Expansion vessel

Pressure gaugeP

Circulation pump

Particle filter

Heat exchanger

Dimensions and pipe connec-tions

28

43

1788

64825-50

691

725

791

900

734

756

66

85

382

763

296

154

73

6157

660 381 290

Pipe connections

G 25 intXL1 Connection, heating medium supply lineG 25 intXL2 Connection, heating medium return lineG 25 intXL3 Connection, cold waterG 25 extXL4 Connection, hot waterG 25 intXL8 Connection, docking in heating mediumG 25 intXL9 Connection, docking out heating medium

11Chapter 4 | Pipe connectionsNIBE™ VVM 500

Page 14: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

ExplanationPool kitCL11Unit boxAA25Temperature sensor, poolBT51Exchanger, poolEP5Pool, pumpGP9Particle filterHQ4Three way valve, poolQN19

VVM 500EB15Connection, heating medium, flow 1XL1Connection, heating medium, return 1XL2Connection, cold waterXL3Connection, hot waterXL4Connection, docking, in heating mediumXL8Connection, docking, out heating mediumXL9Connection, solar system, flowXL13Connection, solar system, returnXL14Connection, accessory, outXL39

Heat pumpEB101Safety valveFL10Particle filterHQ1Trim valveRN10Tapping valveQM1Shut-off valveQM40Shut-off valveQM41

External heat source (Oil, gas, pellets or woodfired boiler with shunt valve)

EM1

Unit boxAA25Temperature sensor, boilerBT52Charge pump, external heat sourceGP15

Climate system 2EP21Unit boxAA25Temperature sensor, heating medium, flowBT2Temperature sensor, heating medium, returnBT3Circulation pump, heating medium, lower shuntGP20Mixing valve, additionQN11

Solar kitEP30Unit boxAA25Temperature sensor, solar panelBT53Expansion vesselCM5Solar panelEP8Pump station SPS 10, SPS20GP30

Active cooling module ACS 310EQ1Unit boxAA25Temperature sensor, cooling, supply lineBT64Single jacket accumulator tank, coolingCP10Charge pumpGP12

Circulation pump, coolingGP13Three way valve cooling/heatingQN12

Pump station SPS 10, SPS 20GP30Safety valve, solarFL4Pump, solarGP4Shut-off valveQM43Shut-off valveQM44Shut-off valveQM45Non-return valveRM3Non-return valveRM4

Miscel-laneous

Expansion vessel closed, heating mediumCM1Safety valve, heating mediumFL2

NIBE™ VVM 500Chapter 4 | Pipe connections12

Page 15: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Outline diagram

-FL2

-CM1

-EB15

-EP30

-EP30-BT53

-EP8

-AA25-CM5

-GP4

-QM45

-RM3

-QM43

-QM44

T P

-FL4

-RM4 T

-GP30

-FL1

-QM40-RM1

-GP20

-BT3

-BT2

-QN25

-EP21-AA25

-GP9

-BT52-EM1-AA25

-EM1

-GP15

-EB101

-GP9 -BT51 -HQ4

-EP5

-AA25

-CL11

-CL11-QN19

13Chapter 4 | Pipe connectionsNIBE™ VVM 500

Page 16: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Installation alternativeCompatible NIBE air/water heat pumpsCompatible NIBE air/water heat pumps must beequipped with a control card with display that has thesoftware version given in the following list as a minim-um. The control card version is displayed in the heatpump's display upon start-up.

Software versionProduct

55F2015

55F2016

55F2025

55F2026

all versionsF2030

all versionsF2040

55F2300

Further option information is available at www.nibe.euand in the respective assembly instructions for the ac-cessories used. See page 60 for a list of the accessoriesthat can be used with VVM 500.

Extra hot water heaters

The indoor module can be supplemented with anelectric water heater, if a hot tub or other significantconsumer of hot water is installed. A mixing valve isthen installed on outgoing hot water from the heater.

Water heater without immersion heater

If there is a need for an additional hot water heater aNIBE VPB 200 type heater or VPBS 300 (prepared forsolar docking) are used. The docking kit accessory isnot required. VPB 200 is best placed to the left of VVM500. VPBS 300 requires pipe routing behind the units,which requires 60 mm of free space to the wall.

kv

vv

Water heater with immersion heater

If it is possible to use a water heater with an immersionheater, NIBE COMPACT or EMINENT type water heaterscan be used.

If the heater is equipped with a valve connector Ø 15mm this should be replaced with a corresponding Ø22 mm.

Kv

Vv från värmepump

BackventilBlandningsventil

NIBE™ VVM 500Chapter 4 | Pipe connections14

Page 17: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Connecting to heat pumpAll outdoor pipes must be thermally insulated with atleast 20mm thick pipe insulation.

VVM 500 is not equipped with shut off valves; thesemust be installed outside the indoor module to facilit-ate any future servicing.

-FL2

-CM1

-EB15

XL9

XL8

-RN10-EB101

XL2

XL1-HQ1

-QM1

-QM41

-FL10

-QM40

-EB101

Connection as electric boilerConnect the pipe for docking in from the heat pump(XL8) with the pipe out to the heat pump (XL9).

-FL2-CM1

-EB15

XL8 XL9

Connecting cold and hot waterThe mixing valve must be installed if the factory settingis changed so that the temperature can exceed 60 °C.If the factory setting is changed, national regulationsmust be observed. The setting is made in menu 5.1.1(See page 50).

-FL2-CM1

-EB15

XL3

XL4-FL1

-QM40-RM1

Connecting the climate systemWhen connecting to a system with thermostats on allradiators/underfloor heating coils, a relief valve mustbe fitted, or a thermostat must be removed to ensuresufficient flow.

-FL2-CM1

-EB15

XL1

XL2

15Chapter 4 | Pipe connectionsNIBE™ VVM 500

Page 18: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Two or more climate systemsWhen more than one climate system is to be heated,the following connection can be used.

The ECS 40/ECS 41. accessory is required for this con-nection.

-FL2-CM1

-EB15

XL2

XL1

-GP20

-BT3

-BT2

-QN25

-EP21-AA25

Connection of external heat sourceFor connection to a gas/electric/oil boiler, the DEH 500accessory is required, see "Accessories" on page 60.

-FL2-CM1

-EB15

-BT52-EM1-AA25

-EM1

-GP15XL18

XL19

Connecting hot water circulationTo reduce the risk of bacterial growth in systems withhot water circulation, the temperature of the circulatingwater should not fall below 50 °C. There should not beany non-circulatory hot water pipes. Adjust the hotwater system so that the temperature does not fallbelow 50 °C at the ends of the system.

-FL2-CM1

-EB15

-FL1

-QM40-RM1

-GP9

XL3

XL4

Connecting ACS 310For connection of active cooling, ACS 310, see "Accessor-ies" on page 60.

-FL2-CM1

-EB15

-RN10-EB101

XL2

XL1-HQ1

-QM1

-QM41

-FL10

-QM40

-EB101

-EB1

-CP10

-BT64-QN12

-AA25

-EQ1

-GP13

-GP12

NIBE™ VVM 500Chapter 4 | Pipe connections16

Page 19: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Connecting to solar installationFor connection to solar installation, the SCA 30 accessory is required, see "Accessories" on page 60.

-FL2-CM1

-EB15

XL13

XL14

-BT53

-EP8

-AA25-CM5

-GP4

-QM45

-RM3

-QM43

-QM44

T P-FL4

-RM4 T

-GP30

-EP30

-RN10-EB101

XL2

XL1-HQ1

-QM1

-QM41

-FL10

-QM40

-EB101

Connecting poolCharging of the pool is controlled by the pool sensor. In the case of low pool temperatures, the reversing valve reversesdirection and opens towards the pool exchanger. The POOL500 accessory is required for this connection.

-FL2-CM1

-EB15

-EB15

XL39

-RN10-EB101

XL2

XL1-HQ1

-QM1

-QM41

-FL10

-QM40

-EB101

-GP9 -BT51 -HQ4

-EP5

-AA25

-CL11

-CL11-QN19

POOL

17Chapter 4 | Pipe connectionsNIBE™ VVM 500

Page 20: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

GeneralAll electrical equipment, except the outdoor sensors,room sensors and the current sensors are ready connec-ted at the factory.

Disconnect the indoor module before insulationtesting the house wiring.If the building is equipped with an earth-faultbreaker, VVM 500 should be equipped with a separ-ate one.For the indoor module wiring diagram, see page 64.Communication and sensor cables to external con-nections must not be laid close to high current cables.The minimum area of communication and sensorcables to external connections must be 0.5 mm² upto 50 m, for example EKKX or LiYY or equivalent.When cable routing in VVM 500, cable grommetsUB1and UB2, (marked in image) must be used. InUB1 and UB2 the cables are inserted through the in-door module from the back to the front.

APH

VVM 500

BAB

NOTE

The switch (SF1) must not be moved to "" or" " until the boiler has been filled with waterand the radiator system vented. Otherwise thetemperature limiter, thermostat and the im-mersion heater can be damaged.

NOTE

If the supply cable is damaged, only NIBE, itsservice representative or similar authorisedperson may replace it to prevent any dangerand damage.

NOTE

Electrical installation and service must be car-ried out under the supervision of a qualifiedelectrician. Cut the current with the circuitbreaker before carrying out any servicing.Electrical installation and wiring must be car-ried out in accordance with the stipulations inforce.

APH

VVM 500

Miniature circuit-breakerThe indoor module and a large proportion of its intern-al components are internally fused by a miniature cir-cuit breaker ((FA1)).

Temperature limiterThe temperature limiter (FD1) cuts the current supplyto the electrical addition if the temperature risesbetween 90 and 100°C and can be manually reset.

Resetting

The temperature limiter (FD1) is accessible behind thefront cover. Reset the temperature limiter by pressingthe button (FD1-SF2) using a small screwdriver. Pressthe button lightly, max 15 N (approx. 1.5 kg).

LEK

FD1

FD1-SF2

Accessibility, electrical connectionThe plastic cap of the electrical boxes is opened usinga screwdriver.

NIBE™ VVM 500Chapter 5 | Electrical connections18

5 Electrical connections

Page 21: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

NOTE

The cover for the input card is opened withouta tool.

Removing the cover, input circuit board

APH

VVM 500

1

2

1. Push the catch down.2. Angle out the cover and remove it.

Removing the cover, immersionheater circuit board

APH

VVM 500

1

2

A

B

1. Insert the screwdriver (A) and pry the catch care-fully downwards (B).

2. Angle out the cover and remove it.

Removing the cover, base board

Caution

To remove the cover for the base board, thecover for the input circuit board must first beremoved.

APH

VVM 500

1

A

B

2

1. Insert the screwdriver (A) and pry the catch care-fully downwards (B).

2. Angle out the cover and remove it.

Cable lockUse a suitable tool to release/lock cables in the indoormodule terminal blocks.

2

1

2

3

LEK

3

4

1

2

19Chapter 5 | Electrical connectionsNIBE™ VVM 500

Page 22: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

ConnectionsNOTE

To prevent interference, unscreened commu-nication and/or sensor to external connectionscables must not be laid closer than 20 cm tohigh voltage cable when cable routing.

Power connectionVVM 500 must be installed via an isolator switch witha minimum breaking gap of 3 mm. Minimum cablearea must be dimensioned according to the fuse ratingused. Supplied cable (length approx. 2 m) for incomingelectricity is connected to terminal block X1 on theimmersion heater card (AA1). The connection cablecan be found on the reverse of VVM 500. (See dimen-sions diagram below.)

140

60 30

1690

Connection

PE1

L1 1 L2 L3PE0N

APH

VVM 500

Tariff controlIf the voltage to the immersion heater disappears dur-ing a certain period, there must also be blocking viathe AU-input, see "Connection options- Possible selec-tion for AU inputs".

Outside sensorInstall the outside temperature sensor (BT1) in theshade on a wall facing north or north-west, so it is un-affected by the morning sun.

Connect the sensor to terminal block X6:1 and X6:2 onthe input card (AA3). Use a twin core cable of at least0.5 mm² cable area.

If a conduit is used it must be sealed to prevent con-densation in the sensor capsule.

123456

NIBE™ VVM 500Chapter 5 | Electrical connections20

Page 23: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Room sensorVVM 500 is delivered with a room sensor supplied(BT50). The room temperature sensor has up to threefunctions:1. Show current room temperature in VVM 500's

display.2. Option of changing the room temperature in °C.3. Makes it possible to change/stabilise the room

temperature.

Install the sensor in a neutral position where the settemperature is required. A suitable location is on a freeinner wall in a hall approx. 1.5 m above the floor. It isimportant that the sensor is not obstructed frommeasuring the correct room temperature by beinglocated, for example, in a recess, between shelves, be-hind a curtain, above or close to a heat source, in adraft from an external door or in direct sunlight. Closedradiator thermostats can also cause problems.

The indoor module operates without the sensor, butif one wishes to read off the accommodation's indoortemperature in VVM 500's display the sensor must beinstalled. Connect the room sensor to X6:3 and X6:4on the input circuit board (AA3).

If the sensor is to be used to change the room temper-ature in °C and/or to stabilise the room temperature,the sensor must be activated in menu 1.9.4.

If the room sensor is used in a room with under floorheating it should only have an indicatory function, notcontrol of the room temperature.

123456789

F1245RG 05

Caution

Changes of temperature in accommodationtake time. For example, short time periods incombination with underfloor heating will notgive a noticeable difference in room temperat-ure.

CommunicationIf VVM 500 is to be connected to the heat pump, it isconnected to terminals X4:13, X4:14 and X4:15 on theinput card (AA3).

15

14

13

12

11

10

VVM500F20XX

GND

B-

A+

APH

VVM 500

AA3-X4

56

42

31

VVM500F2026

151413121110987

21Chapter 5 | Electrical connectionsNIBE™ VVM 500

Page 24: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Settings

APH

VVM 500

Electrical addition - maximum outputThe immersion heater can be set up to a maximum of9 kW. Delivery setting is 9 kW.

The immersion heater output is divided into 4 steps,according to the table.

Setting maximum output in the electrical addition isdone in menu 5.1.12.

Power steps of the immersion heater

Max (A) L3Max (A) L2Max (A) L1Electricaladdition(kW)

0.00.00.000.08.70.028.78.70.048.78.78.7616.216.28.79

The table displays the maximum phase current for therelevant electrical step for the indoor module.

If the current sensors are connected, the indoor modulemonitors the phase currents. In the event of a phaseoverload, the power is reconnected to another/otherphases.

Emergency modeWhen the indoor module is set to emergency mode(SF1 is set to ) only the most necessary functions areactivated.

The hot water capacity is reduced.The load monitor is not connected.Fixed temperature in the flow line, see chapterEmergency mode thermostat on page 22.

Power in emergency mode

The immersion heater’s output in emergency mode isset with the dipswitch (SF1) on the immersion heatercircuit board (AA1) according to the table below.Factory setting is 6 kW.

654321kW

offonoffoffoffoff2offonoffonoffoff4offonoffonoffon6ononononoffon9

1 2

3 4

5 6

ON

The image shows the dip-switch (AA1-SF1) in the fact-ory setting, that is 6 kW.

Emergency mode thermostat

The supply temperature is set in emergency mode usinga thermostat (FD1-BT30). It can be set to 35 (pre-set,for example underfloor heating) or 45 °C (for exampleradiators).

LEK

Output lockingVVM 500 follows applicable building regulations (BBR).This means that the maximum power output (maxim-um installed electrical output for heating) can be lockedin menu 5.1.13. To then change the maximum poweroutput, parts of the product must be replaced.

NIBE™ VVM 500Chapter 5 | Electrical connections22

Page 25: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Optional connectionsLoad monitorWhen many power consumers are connected in theproperty at the same time as the electric additionalheat is operating, there is a risk of the property's mainfuse tripping. The indoor module has integrated loadmonitors that control the electrical steps for the elec-trical addition by redistributing the power betweenthe different phases or disengaging in event of over-load in a phase. Reconnection occurs when other cur-rent consumption is reduced.

Connecting current sensors

A current sensor should be installed on each incomingphase conductor in to the distribution box to measurethe current. The distribution box is an appropriate in-stallation point.

Connect the current sensors to a multi-core cable in anenclosure next to the distribution box. Use a multi-corecable of at least 0.5 mm2 from the enclosure to theindoor module.

Connect the cable to the input card (AA3) on terminalblock X4:1-4 where X4:1 is the common terminal blockfor the three current sensors.

The size of the property’s main fuse is set in menu5.1.12.

Inkommande elLPEN 1 L2 L3

Elcentral

Värmepump

APH

VVM 500

AA3-X4 AA3-X4

Electricaldistribution unitVVM 500

Incoming electricity

1 2 3 4

-T1 -T2 -T3

External connection optionsVVM 500 has software controlled inputs and outputson the input card (AA3), for connecting the externswitch function or sensor. This means that when anexternal switch function or sensor is connected to oneof six special connections, the correct function must beselected to the correct connection in the software inVVM 500.

Caution

If an external switch function or sensor is con-nected to VVM 500, the function to use inputor output must be selected in menu 5.4, seepage 53.

Selectable inputs on the input card for these functionsare AUX1 (X6:9-10), AUX2 (X6:11-12), AUX3 (X6:13-14), AUX4 (X6:15-16) and AUX5 (X6:17-18). Selectableoutputs are AA3:X7.

910111213141516

B

A

APH

VVM 500

AA3-X6

The example above uses the inputs AUX1 (X6:9-10) andAUX2(X6:11-12) on the input circuit board (AA3).

Caution

Some of the following functions can also beactivated and scheduled via menu settings.

Possible selection for AUX inputs

Switch for external blocking of addition and/orcompressor

In those cases external blocking of addition and/orcompressor is wanted, this can be connected to termin-al block X6 on the input card (AA3), which is positionedbehind the front cover.

The additional heat and/or the compressor are discon-nected by connecting a potential free switch functionto the input selected in menu 5.4, see page 53.

External blocking of addition and compressor can becombined.

A closed contact results in the electrical output beingdisconnected.

Contact for external tariff blocking

In those cases external tariff blocking is used, this canbe connected to terminal block X6 on the input card(AA3), which is positioned behind the front cover.

23Chapter 5 | Electrical connectionsNIBE™ VVM 500

Page 26: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Tariff blocking means that the additional heat, thecompressor and heating are disconnected by connect-ing a potential free switch function to the input selec-ted in menu 5.4, see page 53.

A closed contact results in the electrical output beingdisconnected.

NOTE

When tariff blocking is activated, the min.supply line does not apply.

Switch for external blocking heating

In those cases external blocking of heat is used, thiscan be connected to terminal block X6 on the inputcard (AA3), which is positioned behind the front cover.

Heating operation is disconnected by connecting apotential free switch function to the input selected inmenu 5.4, see page 53.

A closed switch results in blocked heating operation.

NOTE

When heat blocking is activated, the min.supply line does not apply.

Switch for external alarm (NC)

If ”switch for external alarm (NC)” is selected as functionon a soft input, infolarm 995 appears if the connectedexternal circuit for selected soft input is open.

Switch for external alarm (NO)

If ”switch for external alarm (NO)” is selected as func-tion on a soft input, infolarm 995 appears if the connec-ted external circuit for selected soft input is closed.

Contact for activation of “temporary lux"

An external contact function can be connected to VVM500 for activation of the hot water function“temporarylux". The switch must be potential free and connectedto the selected input (menu 5.4, see page 53) on ter-minal block X6 on the input circuit board (AA3).

"temporary lux" is activated for the time that the con-tact is connected.

Contact for activation of “external adjustment"

An external contact function can be connected to VVM500 to change the supply temperature and the roomtemperature.

When the switch is closed the temperature changes in°C (if the room sensor is connected and activated). If aroom sensor is not connected or not activated, the de-sired offset of "temperature" (heating curve offset) isset with the number of steps selected. The value is ad-justable between -10 and +10.climate system 1

The switch must be potential free and connected tothe selected input (menu 5.4, see page 53) on termin-al block X6 on the input circuit board (AA3).

The value for the change is set in menu 1.9.2, "extern-al adjustment".climate system 2 to 4

External adjustment for climate systems 2 to 4 requireaccessory (ECS 40).

See the accessory’s installer handbook for installationinstructions.

Switch for "SG ready"

NOTE

This function can only be used in mains net-works that support the "SG Ready"-standard(Germany).

"SG Ready" requires two AUX inputs.

In cases where this function is required it must beconnected to terminal block X6 on the input card (AA3).

"SG Ready" is a smart form of tariff control where yourelectricity supplier can affect the indoor, hot waterand/or pool temperatures (if applicable) or simply blockthe additional heat and/or compressor in the heatpump at certain times of the day (can be selected inmenu 4.1.5 after the function is activated). Activate thefunction by connecting potential free switch functionsto two inputs selected in menu 5.4 (SG Ready A andSG Ready B), see page 53.

Closed or open switch means one of the following(A = SG Ready A and B = SG Ready B ):Blocking (A: Closed, B: Open)

"SG Ready" is active. The compressor in the heatpump and additional heat is blocked like the day'stariff blocking.Normal mode (A: Open, B: Open)

"SG Ready" is not active. No effect on the system.Low price mode (A: Open, B: Closed)

"SG Ready" is active. The system focuses on costssavings and can for example exploit a low tariff fromthe electricity supplier or over capacity from any ownpower source (effect on the system can be adjustedin the menu 4.1.5).Overcapacity mode (A: Closed, B: Closed)

"SG Ready" is active. The system is permitted to runat full capacity at over capacity with the electricitysupplier (effect on the system is settable in menu4.1.5).

Switch for +Adjust

Using +Adjust, the installation communicates with theunderfloor heating's control centre* and adjusts theheat curve and calculated supply temperature accord-ing to the underfloor heating system's reconnection.

Activate the climate system you want +Adjust to affectby highlighting the function and pressing the OK but-ton.

*Support for +Adjust required

NOTE

+Adjust must first be selected in menu 5.4 ”softinputs/outputs”.

NIBE™ VVM 500Chapter 5 | Electrical connections24

Page 27: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

NOTE

Circuit board AA3 in the installation must haveat least ”input version” 34 and the softwareversion must have ”display version 5539 orlater for +Adjust to work. Version can bechecked in menu 3.1 under ”input version”respectively ”display version”. New softwarecan be downloaded for free fromwww.nibeuplink.com.

NOTE

In systems with both underfloor heating andradiators, NIBE ECS 40/41 should be used foroptimum operation.

Possible selection for AUXoutput (potentialfree variable relay)It is possible to have an external connection throughthe relay function via a potential free variable relay(max 2 A) on the input circuit board (AA3), terminalblock X7.

Optional functions for external connection:Indication of buzzer alarm.Cooling mode indication (only applies if accessoriesfor cooling are present or if the heat pump has theintegrated cooling function).Control of circulation pump for hot water circulation.External circulation pump (for heating medium).External, reversing valve for hot water.External circulation pump, for example external pumpand shunt group.

If any of the above is installed to terminal block X7 itmust be selected in menu 5.4, see page 53.

The common alarm is preselected at the factory.

NOTE

An accessory card is required if several func-tions are connected to terminal block X7 atthe same time that the buzzer alarm is activ-ated (see page 60).

APH

VVM 500

AA3-X7

The picture shows the relay in the alarm position.

When switch (SF1) is in the " " or “ ” position therelay is in the alarm position.

External circulation pump or hot water circulationpump connected to the buzzer alarm relay as illustratedbelow.

NOTE

Mark up any junction boxes with warnings forexternal voltage.

L

L

N

N

PE

PE

F1X45

Externt

APH

VVM 500

AA3-X7

Caution

The relay outputs can have a max load of 2 A(230 V AC) in total.

25Chapter 5 | Electrical connectionsNIBE™ VVM 500

Page 28: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Connecting accessoriesInstructions for connecting accessories are provided inthe manual accompanying the accessory. See page 60for the list of the accessories that can be used with VVM500.

NIBE™ VVM 500Chapter 5 | Electrical connections26

Page 29: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Preparations1. Check that the switch (SF1) is in position " ".2. Check that the drain valve is fully closed and that

the temperature limiter (FD1) has not deployed.3. Compatible NIBE air/water heat pumps must be

equipped with a control card with display that hasat least the software version given in the list onpage 14. The control card version is displayed inthe heat pump's display upon start-up.

Filling and ventingFilling the hot water coil

1. Open a hot water tap in the house.2. Open the externally mounted shut-off valve. This

valve should then be fully open during operations.3. When water comes out of the hot water tap, the

hot water coil is full and the tap can be closed.

Filling the climate system

1. Open the vent valves (QM20).2. Open the externally mounted filler valve. The boiler

section and the rest of the climate system are filledwith water.

3. When the water that exits the vent valves (QM20)is not mixed with air, close the vent valves. After awhile the pressure rises on the externally mountedpressure gauge. When the pressure for the extern-ally mounted safety valve has been reached, itstarts to release water. Close the filler valve.

4. Open the externally mounted safety valve until thepressure in VVM 500 falls to the normal workingrange (approx. 1 bar) and check that there is notair in the system by turning the vent valves (QM20).

Venting the climate system

1. Turn off the power supply to VVM 500.2. Vent VVM 500 through the vent valves (QM20)

and other climate system through their relevantvent valves.

3. Keep topping up and venting until all air has beenremoved and the pressure is correct.

APH

VVM 500

27Chapter 6 | Commissioning and adjustingNIBE™ VVM 500

6 Commissioning and adjusting

Page 30: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Start-up and inspectionStart guide

NOTE

There must be water in the climate systembefore the switch is set to " ".

1. Set the indoor module switch (SF1) to mode "".2. Follow the instructions in the start guide in the in-

door module display. If the start guide does notstart when you start the indoor module, start itmanually in menu 5.7.

TIP

See page 30 for a more in-depth introductionto the installation’s control system (operation,menus etc.).

Commissioning

The first time the installation is started a start guide isstarted. The start guide instructions state what needsto carried out at the first start together with a runthrough of the installation’s basic settings.

The start guide ensures that the start-up is carried outcorrectly and cannot be bypassed. The start guide canbe started later in menu 5.7.

During the start up guide the reversing valves and theshunt valve are run backward and forwards to helpvent VVM 500.

Caution

As long as the start guide is active, no functionin the heat pump will start automatically.

The guide will appear at each heat pump re-start until it is deselected on the last page.

Operation in the start guide

A.

D.C.

B.

A. Page

Here you can see how far you have come in the startguide.

Scroll between the pages of the start guide as follows:1. Turn the control knob until one of the arrows in

the top left corner (at the page number) has beenmarked.

2. Press the OK button to skip between the pages inthe start guide.

B. Name and menu number

Read what menu in the control system this page of thestart guide is based on. The digits in brackets refer tothe menu number in the control system.

If you want to read more about affected menus eitherread off in the sub-menu or in the installation manualfrom page 34.

C. Option / setting

Make settings for the system here.

D. Help menu

In many menus there is a symbol that indicatesthat extra help is available.

To access the help text:1. Use the control knob to select the help symbol.2. Press the OK button.

The help text often consists of several windows thatyou can scroll between using the control knob.

NIBE™ VVM 500Chapter 6 | Commissioning and adjusting28

Page 31: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Commissioning without heat pumpThe indoor module can be run without heat pump, asonly an electric boiler, to produce heat and hot water,for example before the heat pump is installed.

Connect the pipe for docking in from the heat pump(XL8) with the pipe out from the heat pump (XL9).

Enter menu 5.2.2 System settings and deactivate theheat pump.

NOTE

Select operating mode auto or manual whenthe indoor module is to run with the heatpump.

Pump speedBoth the circulation pumps in VVM 500 are frequencycontrolled and set themselves using control and extern-al heating requirement.

LEK

Capacity circulation pumpTillgängligt tryck

(Pa)

Luftflöde (l/s)

0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,80

10

20

30

40

50

60

70

100%

25%

Pressure(kPa)

Flow (l/s)

Available pressure, circulation pump, GP1

Capacity circulation pumpTillgängligt tryck

(Pa)

Luftflöde (l/s)

0

10

20

30

40

50

60

70

0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8

100%

25%

Pressure(kPa)

Flow (l/s)

Available pressure, charge pump, GP12

Post-adjustment, ventingAir is initially released from the hot water and ventingmay be necessary. If gurgling sounds can be heard fromthe climate system, the entire system will require addi-tional venting. Vent the installation through the ventingvalves (QM20). When venting, VVM 500 must be off.

29Chapter 6 | Commissioning and adjustingNIBE™ VVM 500

Page 32: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Display unit

DisplayInstructions, settings and operational informa-tion are shown on the display. The easy-to-readdisplay and menu system, facilitates navigationbetween the different menus and options toset the comfort or obtain the information yourequire.

A

Status lampThe status lamp indicates the status of the in-door module. It:

lights green during normal operation.lights yellow in emergency mode.lights red in the event of a deployed alarm.

B

OK buttonThe OK button is used to:

confirm selections of sub menus/options/setvalues/page in the start guide.

C

Back buttonThe back button is used to:

go back to the previous menu.change a setting that has not been con-firmed.

D

Control knobThe control knob can be turned to the right orleft. You can:

scroll in menus and between options.increase and decrease the values.change page in multiple page instructions(for example help text and service info).

E

Switch (SF1)The switch assumes three positions:

On ()

Standby ( )

Emergency mode ( )

Emergency mode must only be used in theevent of a fault on the indoor module. In thismode, the compressor switches off and theimmersion heater engages. The indoor moduledisplay is not illuminated and the status lampilluminates yellow.

F

NIBE™ VVM 500Chapter 7 | Control - Introduction30

7 Control - Introduction

Page 33: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Menu systemWhen the door to the indoor module is opened, themenu system’s four main menus are shown in the dis-play as well as certain basic information.

Menu 1 - INDOOR CLIMATESetting and scheduling the indoor climate. See page34.

Menu 2 - HOT WATERSetting and scheduling hot water production. See page40.

Menu 3 - INFODisplay of temperature and other operating informa-tion and access to the alarm log. See page 42.

Menu 4 - MY SYSTEMSetting time, date, language, display, operating modeetc. See page 43.

Menu 5 - SERVICEAdvanced settings. These settings are not available tothe end user. The menu is visible by pressing the Backbutton for 7 seconds. See page 49.

Symbols in the displayThe following symbols can appear in the display duringoperation.

DescriptionSymbol

This symbol appears by the informationsign if there is information in menu 3.1that you should note.

These two symbols indicate whether thecompressor in the outdoor unit or addi-tional heat is blocked in VVM 500.

These can, for example, be blocked de-pending on which operating mode is se-lected in menu 4.2, if blocking is sched-uled in menu 4.9.5 or if an alarm has oc-curred that blocks one of them.

Blocking the compressor.

Blocking additional heat.

This symbol appears if lux mode for thehot water is activated.

This symbol indicates whether VVM 500has contact with NIBE Uplink™.

This symbol indicates whether solarheating is active.

Accessory needed.

This symbol indicates whether "holidaysetting" is activated in menu 4.7.

31Chapter 7 | Control - IntroductionNIBE™ VVM 500

Page 34: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Marked mainmenu

Menu number – marked sub menu Name and menu number – main menu

Symbol –main menu

Status information – submenus

Name – sub menusSymbols – sub menus

OperationTo move the cursor, turn the control knob tothe left or the right. The marked position iswhite and/or has a turned up tab.

Selecting menuTo advance in the menu system select a main menu bymarking it and then pressing the OK button. A newwindow then opens with sub menus.

Select one of the sub menus by marking it and thenpressing the OK button.

Selecting options

In an options menu the current selected option isindicated by a green tick.

To select another option:1. Mark the applicable option. One of the options

is pre-selected (white).2. Press the OK button to confirm the selected

option. The selected option has a green tick.

Setting a value

time & date4.4time

day

year

month

24 hrs

12 h

date

Values to be changed

To set a value:1. Mark the value you want to set using the

control knob.2. Press the OK button. The background of the

value becomes green, which means that youhave accessed the setting mode.

3. Turn the control knob to the right to increasethe value and to the left to reduce the value.

4. Press the OK button to confirm the value youhave set. To change and return to the originalvalue, press the Back button.

NIBE™ VVM 500Chapter 7 | Control - Introduction32

Page 35: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Use the virtual keyboard

In some menus where text may require entering, a vir-tual keyboard is available.

Depending on the menu, you can gain access to differ-ent character sets which you can select using the con-trol knob. To change character table, press the Backbutton. If a menu only has one character set the key-board is displayed directly.

When you have finished writing, mark "OK" and pressthe OK button.

Scroll through the windowsA menu can consist of several windows. Turn the con-trol knob to scroll between the windows.

Scroll through the windows in the start guide

1. Turn the control knob until one of the arrows inthe top left corner (at the page number) has beenmarked.

2. Press the OK button to skip between the steps inthe start guide.

Help menuIn many menus there is a symbol that indicatesthat extra help is available.

To access the help text:1. Use the control knob to select the help symbol.2. Press the OK button.

The help text often consists of several windows thatyou can scroll between using the control knob.

33Chapter 7 | Control - IntroductionNIBE™ VVM 500

Page 36: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Menu 1 - INDOOR CLIMATEOverview

1.1 - temperature1 - INDOOR CLIMATE

1.3.1 - heating1.3 - scheduling

1.3.2 - cooling *

1.9.1 - heating curve1.9 - advanced

1.9.2 - external adjustment

1.9.3 - min. flow line temp.

1.9.4 - room sensor settings

1.9.7 - own curve

1.9.8 - point offset

1.9.11 - +Adjust

* Accessories are needed.

Sub-menus

For the menu INDOOR CLIMATE there are several sub-menus. Status information for the relevant menu canbe found on the display to the right of the menus.

temperature Setting the temperature for the climatesystem. The status information shows the set valuesfor the climate system.

scheduling Scheduling heating and cooling. Statusinformation "set" is displayed if you set a schedule butit is not active now, "holiday setting" is displayed if thevacation schedule is active at the same time as theschedule (the vacation function is prioritised), "active"displays if any part of the schedule is active, otherwiseit displays " off".

advanced Setting of heat curve, adjusting with extern-al contact, minimum value for supply temperature,own curve, point offset and +Adjust.

Menu 1.1 - temperature

Set the temperature (with room sensors installedand activated):

heating

Setting range: 5 - 30 °C

Default value: 20

cooling (accessory required)

Setting range: 5 - 30 °C

Default value: 25

The value in the display appears as a temperature in°C if the climate system is controlled by a room sensor.

To change the room temperature, use the control knobto set the desired temperature in the display. Confirmthe new setting by pressing the OK button. The newtemperature is shown on the right-hand side of thesymbol in the display.

Setting the temperature (without room sensorsactivated):

Setting range: -10 to +10

Default value: 0

The display shows the set values for heating (curveoffset). To increase or reduce the indoor temperature,increase or reduce the value on the display.

Use the control knob to set a new value. Confirm thenew setting by pressing the OK button.

The number of steps the value has to be changed toachieve a degree change of the indoor temperaturedepends on the heating installation. One step is usuallyenough but in some cases several steps may be re-quired.

Setting the desired value. The new value is shown onthe right-hand side of the symbol in the display.

Caution

An increase in the room temperature can beslowed by the thermostats for the radiators orunder floor heating. Therefore, open thethermostats fully, except in those rooms wherea cooler temperature is required, e.g. bed-rooms.

NIBE™ VVM 500Chapter 8 | Control - Menus34

8 Control - Menus

Page 37: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

TIP

Wait 24 hours before making a new setting,so that the room temperature has time tostabilise.

If it is cold outdoors and the room temperatureis too low, increase the curve slope in menu1.9.1 by one increment.

If it is cold outdoors and the room temperatureis too high, lower the curve slope menu 1.9.1by one increment.

If it is warm outdoors and the room temperat-ure is too low, increase the value in menu 1.1by one increment.

If it is warm outdoors and the room temperat-ure is too high, reduce the value in menu 1.1by one increment.

Menu 1.3 - schedulingIn the menu scheduling indoor climate (heating/cool-ing) is scheduled for each weekday.

You can also schedule a longer period during a selectedperiod (vacation) in menu 4.7.

Menu 1.3.1 - heatingIncreases or decreases in the accommodation temper-ature can be scheduled here for up to three time peri-ods per day. If a room sensor is installed and activatedthe desired room temperature (°C) is set during thetime period. Without an activated room sensor thedesired change is set (of setting in menu 1.1). One stepis usually enough to change the room temperature byone degree, but in some cases several steps may berequired.

Schedule: The schedule to be changed is selected here.

Activated: Scheduling for the selected period is activ-ated here. Set times are not affected at deactivation.

System: Which climate system the schedule is for isselected here. This alternative is only displayed if morethan one climate system is present.

Day: Select which day or days of the week the scheduleis to apply to here. To remove the scheduling for aparticular day, the time for that day must be reset bysetting the start time to the same as the stop time. Ifthe line "all" is used, all days in the period are set forthese times.

Time period: The start and stop time for the selectedday for scheduling are selected here.

Adjusting:How much the heating curve is to be offsetin relation to menu 1.1 during scheduling is set here.If the rooms sensor is installed the desired room tem-perature is set in °C.

Conflict: If two settings conflict with each other a redexclamation mark is displayed.

TIP

If you wish to set similar scheduling for everyday of the week start by filling in “all” and thenchanging the desired days.

TIP

Set the stop time earlier than the start time sothat the period extends beyond midnight.Scheduling then stops at the set stop time theday after.

Scheduling always starts on the date that thestart time is set for.

Caution

Changes of temperature in accommodationtake time. For example, short time periods incombination with underfloor heating will notgive a noticeable difference in room temperat-ure.

Menu 1.3.2 - cooling (accessory required)Here you can schedule when cooling is permitted inthe accommodation for up to two different time peri-ods per day.

Schedule: The schedule to be changed is selected here.

35Chapter 8 | Control - MenusNIBE™ VVM 500

Page 38: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Activated: Scheduling for the selected period is activ-ated here. Set times are not affected at deactivation.

Day: Select which day or days of the week the scheduleis to apply to here. To remove the scheduling for aparticular day, the time for that day must be reset bysetting the start time to the same as the stop time. Ifthe line "all" is used, all days in the period are set forthese times.

Time period: The start and stop time for the selectedday for scheduling are selected here.

Adjusting:Whether or not cooling is permitted duringscheduling is set here.

Conflict: If two settings conflict with each other a redexclamation mark is displayed.

TIP

If you wish to set similar scheduling for everyday of the week start by filling in “all” and thenchanging the desired days.

TIP

Set the stop time earlier than the start time sothat the period extends beyond midnight.Scheduling then stops at the set stop time theday after.

Scheduling always starts on the date that thestart time is set for.

Menu 1.9 - advancedMenu advanced has orange text and is intended forthe advanced user. This menu has several sub-menus.

curve Setting the curve slope for heating and cooling.

external adjustment Setting the heat curve offsetwhen the external contact is connected.

min. flow line temp. Setting minimum permitted flowline temperature.

room sensor settings Settings regarding the roomsensor.

own curve Setting own curve for heating and cooling.

point offset Setting the offset of the heating curve orcooling curve at a specific outdoor temperature.

+Adjust Setting how much effect +Adjust will haveon calculated supply temperature for underfloorheating. The higher the value is the greater the effect.

Menu 1.9.1 - curveheating curve 1.9.1.1

system

outdoor temp. °C

flow temperature °C

heating

Setting range: 0 - 15

Default value: 9

cooling (accessory required)

Setting range: 0 - 9

Default value: 0

The prescribed heating curve for your house can beviewed in the menu curve . The task of the heatingcurve is to give an even indoor temperature, regardlessof the outdoor temperature, and thereby energy effi-cient operation. It is from this heating curve that theindoor module’s control computer determines thetemperature of the water to the heating system, supplytemperature, and therefore the indoor temperature.Select the heating curve and read off how the supplytemperature changes at different outdoor temperat-ures here. If there is access to cooling the same settingscan be made for the cooling curve.

Curve coefficient

The slopes of the heating /cooling curves indicate howmany degrees the supply temperature is to be in-creased/reduced when the outdoor temperaturedrops/increases. A steeper slope means a higher supplytemperature for heating or a lower supply temperaturefor cooling at a certain outdoor temperature.

30

40

50

60

70°C

- 40°CUTETEMPERATUR

- 10010 - 20 - 30

Brantare kurvlutning

The optimum slope depends on the climate conditionsin your location, if the house has radiators or underfloor heating and how well insulated the house is.

The curve is set when the heating installation is in-stalled, but may need adjusting later. Normally, thecurve will not need further adjustment.

NIBE™ VVM 500Chapter 8 | Control - Menus36

Page 39: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Caution

In the event of making fine adjustments of theindoor temperature, the curve must be offsetup or down instead, this is done in menu 1.1temperature .

Curve offset

An offset of the curve means that the supply temperat-ure changes as much for all the outdoor temperatures,e.g. that a curve offset of +2 steps increases the supplytemperature by 5 C at all outdoor temperatures.

Flow line temperature– maximum and minimumvalues

Because the flow line temperature cannot be calculatedhigher than the set maximum value or lower than theset minimum value the heating curve flattens out atthese temperatures.

Caution

Underfloor heating systems are normally maxflow line temperature set between 35 and 45°C.

Must be restricted with underfloor coolingmin. flow line temp. to prevent condensation.

Check the max temperature for your floor withyour installer/floor supplier.

The figure at the end of the curve indicates the curveslope. The figure beside the thermometer gives thecurve offset. Use the control knob to set a new value.Confirm the new setting by pressing the OK button.

Curve 0 is an own curve created in menu 1.9.7.

To select another curve (slope):

NOTE

If you only have one climate system, the num-ber of the curve is already marked when themenu window opens.

1. Select the climate system (if more than one) forwhich the curve is to be changed.

2. When the climate system selection has been con-firmed, the curve number is marked.

3. Press the OK button to access the setting mode4. Select a new curve. The curves are numbered from

0 to 15, the greater the number, the steeper theslope and the greater the supply temperature.Curve 0 means that own curve (menu 1.9.7) isused.

5. Press the OK button to exit the setting.

To read off a curve:1. Turn the control knob so that the ring on the shaft

with the outdoor temperature is marked.2. Press the OK button.3. Follow the grey line up to the curve and out to the

left to read off the value for the supply temperatureat the selected outdoor temperature.

4. You can now select to take read outs for differentoutdoor temperatures by turning the control knobto the right or left and read off the correspondingflow temperature.

5. Press the OK or Back button to exit read off mode.

TIP

Wait 24 hours before making a new setting,so that the room temperature has time tostabilise.

If it is cold outdoors and the room temperatureis too low, increase the curve slope by one in-crement.

If it is cold outdoors and the room temperatureis too high, lower the curve slope by one incre-ment.

If it is warm outdoors and the room temperat-ure is too low, increase the curve offset by oneincrement.

If it is warm outdoors and the room temperat-ure is too high, lower the curve offset by oneincrement.

Menu 1.9.2 - external adjustment

climate system

Setting range: -10 to +10 or desired room temperat-ure if the room sensor is installed.

Default value: 0

Connecting an external contact, for example, a roomthermostat or a timer allows you to temporarily orperiodically raise or lower the room temperature whileheating. When the contact is on, the heat curve offsetis changed by the number of steps selected in themenu. If a room sensor is installed and activated thedesired room temperature (°C) is set.

If there is more than one climate system the settingcan be made separately for each system.

Menu 1.9.3 - min. flow line temp.

heating

Setting range: 5-70 °C

Default value: 20 °C

cooling (accessory required)

Setting range: 5-30 °C

Default value: 18 °C

In menu 1.9.3 you select heating or cooling, in the nextmenu (min. supply temp.heating/cooling) set theminimum temperature on the supply temperature tothe climate system. This means that VVM 500 nevercalculates a temperature lower than that set here.

If there is more than one climate system the settingcan be made separately for each system.

37Chapter 8 | Control - MenusNIBE™ VVM 500

Page 40: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

TIP

The value can be increased if you have, for ex-ample, a cellar that you always want to heat,even in summer.

You may also need to increase the value in"stop heating" menu 4.9.2 "auto mode set-ting".

Menu 1.9.4 - room sensor settings

factor system

heating

Setting range: 0.0 - 6.0

Factory setting heating: 2.0

cooling (accessory required)

Setting range: 0.0 - 6.0

Factory setting cooling: 1.0

Room sensors to control the room temperature can beactivated here.

Here you can set a factor (a numerical value) that de-termines how much an over or sub normal temperature(the difference between the desired and actual roomtemperature) in the room is to affect the supply tem-perature to the climate system. A higher value gives agreater and faster change of the heating curve's setoffset.

NOTE

Too high a set value for "factor system" can(depending on your climate system) producean unstable room temperature.

If several climate systems are installed the above set-tings can be made for the relevant systems.

Menu 1.9.7 - own curve

supply temperature

heating

Setting range: 0 – 80 °C

cooling (accessory required)

Setting range: 5 – 40 °C

Create your own heating or cooling curve here, bysetting the desired supply temperatures for differentoutdoor temperatures.

Caution

Curve 0 in menu 1.9.1 must be selected forown curve to apply.

Menu 1.9.8 - point offset

outdoor temp. point

Setting range: -40 – 30 °C

Default value: 0 °C

change in curve

Setting range: -10 – 10 °C

Default value: 0 °C

Select a change in the heating curve at a certain out-door temperature here. One step is usually enough tochange the room temperature by one degree, but insome cases several steps may be required.

The heat curve is affected at ± 5 °C from set outdoortemp. point.

It is important that the correct heating curve is selectedso that the room temperature is experienced as even.

TIP

If it is cold in the house, at, for example -2 °C,"outdoor temp. point" is set to "-2" and"change in curve" is increased until the desiredroom temperature is maintained.

Caution

Wait 24 hours before making a new setting,so that the room temperature has time tostabilise.

Menu 1.9.11 - +AdjustUsing +Adjust, the installation communicates with theunderfloor heating's control centre* and adjusts theheat curve and calculated supply temperature accord-ing to the underfloor heating system's reconnection.

Activate the climate system you want +Adjust to affectby highlighting the function and pressing the OK but-ton.

*Support for +Adjust required

Degree of effect

Here you can set how much effect +Adjust is to haveon calculated supply temperature. The higher the valueis the greater the effect.

Setting range: 0.1 – 1.0

Default value: 0.5

- degree of effect

climate system 1

+adjust 1.9.11

NIBE™ VVM 500Chapter 8 | Control - Menus38

Page 41: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

NOTE

+Adjust must first be selected in menu 5.4 ”softinputs/outputs”.

NOTE

Circuit board AA3 in the installation must haveat least ”input version” 34 and the softwareversion must have ”display version 5539 orlater for +Adjust to work. Version can bechecked in menu 3.1 under ”input version”respectively ”display version”. New softwarecan be downloaded for free fromwww.nibeuplink.com.

NOTE

In systems with both underfloor heating andradiators, NIBE ECS 40/41 should be used foroptimum operation.

39Chapter 8 | Control - MenusNIBE™ VVM 500

Page 42: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Menu 2 - HOT WATEROverview

2.1 - temporary lux2 - HOT WATER

2.2 - comfort mode

2.3 - scheduling

2.9.2 - hot water recirc.2.9 - advanced

Sub-menus

For the menu HOT WATER there are several sub-menus. Status information for the relevant menu canbe found on the display to the right of the menus.

temporary lux Activation of temporary increase in thehot water temperature. Status information displays“off" or what length of time of the temporary temper-ature increase remains.

comfort mode Setting hot water comfort. The statusinformation displays what mode is selected, "economy","normal" or "luxury".

scheduling Scheduling hot water comfort. The statusinformation "set" appears if you have set schedulingbut it is not currently active, "holiday setting" appearsif holiday setting is active at the same time as schedul-ing (when the holiday function is prioritised), "active"appears if any part of scheduling is active, otherwise"off" appears.

advanced Setting hot water circulation (accessory isrequired)

Menu 2.1 - temporary lux

Setting range: 3, 6 and 12 hours and mode "off"

Default value: "off"

When hot water requirement has temporarily increasedthis menu can be used to select an increase in the hotwater temperature to lux mode for a selectable time.

Caution

If comfort mode "luxury" is selected in menu2.2 no further increase can be carried out.

The function is activated immediately when a timeperiod is selected and confirmed using the OK button.The remaining time for the selected setting is shownto the right.

When the time has run out VVM 500 returns to themode set in menu 2.2.

Select “off" to switch off temporary lux .

Menu 2.2 - comfort mode

Setting range: economy, normal, luxury

Default value: normal

The difference between the selectable modes is thetemperature of the hot tap water. Higher temperaturemeans that the hot water lasts longer.

economy: This mode gives less hot water than theothers, but is more economical. This mode can be usedin smaller households with a small hot water require-ment.

normal: Normal mode gives a larger amount of hotwater and is suitable for most households.

luxury: Lux mode gives the greatest possible amountof hot water. In this mode, the immersion heater, aswell as the compressor, is used to heat hot water, whichmay increase operating costs.

Menu 2.3 - schedulingWhat hot water comfort the indoor module is to workwith can be scheduled here for up to two different timeperiods per day.

Scheduling is activated/deactivated by ticking/untick-ing"activated". Set times are not affected at deactiva-tion.

all

mon

tues

we

thur

fri

sat

sun

activated

schedule 2schedule 1

SCHEDULING HOT WATER 2.3

normal

Time period AdjustingDay

Activated Schedule

Conflict

Schedule: The schedule to be changed is selected here.

Activated: Scheduling for the selected period is activ-ated here. Set times are not affected at deactivation.

Day: Select which day or days of the week the scheduleis to apply to here. To remove the scheduling for aparticular day, the time for that day must be reset bysetting the start time to the same as the stop time. Ifthe line "all" is used, all days in the period are set forthese times.

Time period: The start and stop time for the selectedday for scheduling are selected here.

Adjusting: Set the hot water comfort that is to applyduring scheduling here.

NIBE™ VVM 500Chapter 8 | Control - Menus40

Page 43: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Conflict: If two settings conflict with each other a redexclamation mark is displayed.

TIP

If you wish to set similar scheduling for everyday of the week start by filling in “all” and thenchanging the desired days.

TIP

Set the stop time earlier than the start time sothat the period extends beyond midnight.Scheduling then stops at the set stop time theday after.

Scheduling always starts on the date that thestart time is set for.

Menu 2.9 - advancedMenu advanced has orange text and is intended forthe advanced user. This menu has a sub-menu.

Menu 2.9.2 - hot water recirc.

operating time

Setting range: 1 - 60 min

Default value: 60 min

downtime

Setting range: 0 - 60 min

Default value: 0 min

Set the hot water circulation for up to three periodsper day here. During the set periods the hot water cir-culation pump will run according to the settings above.

"operating time" decide how long the hot water circu-lation pump must run per operating instance.

"downtime" decide how long the hot water circulationpump must be stationary between operating instances.

NOTE

Hot water circulation is activated in menu 5.4"soft inputs and outputs".

41Chapter 8 | Control - MenusNIBE™ VVM 500

Page 44: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Menu 3 - INFOOverview

3.1 - service info3 - INFO

3.2 - compressor info

3.3 - add. heat info

3.4 - alarm log

3.5 - indoor temp. log

Sub-menus

For the menu INFO there are several sub-menus. Nosettings can be made in these menus, they just displayinformation. Status information for the relevant menucan be found on the display to the right of the menus.

service info shows temperature levels and settings inthe installation.

compressor info shows operating times, number ofstarts etc for the compressor in the heat pump.

add. heat info displays information about the addi-tional heat's operating times etc.

alarm log shows the latest alarms.

indoor temp. log the average temperature indoorsweek by week during the past year.

Menu 3.1 - service infoThe information is on several pages. Turn the controlknob to scroll between the pages.

A QR code appears on one side. This QR code indicatesserial number, product name and limited operatingdata.

Symbols in this menu:HeatingCompressor

Hot waterAddition

PoolCooling

Heating mediumpump (orange)

Menu 3.2 - compressor infoInformation about the compressor’s operating statusand statistics can be obtained here. No changes canbe made.

The information is on several pages. Turn the controlknob to scroll between the pages.

Menu 3.3 - add. heat infoInformation about the additional heat's settings, oper-ating status and statistics can be obtained here. Nochanges can be made.

The information is on several pages. Turn the controlknob to scroll between the pages.

Menu 3.4 - alarm logTo facilitate fault-finding the installation's operatingstatus at alarm alerts is stored here. You can see inform-ation for the 10 most recent alarms.

To view the run status in the event of an alarm, markthe alarm and press the OK button.

Menu 3.5 - indoor temp. logHere you can see the average temperature indoorsweek by week during the past year. The dotted lineindicates the annual average temperature.

The average outdoor temperature is only shown if aroom temperature sensor/room unit is installed.

To read off an average temperature1. Turn the control knob so that the ring on the shaft

with the week number is marked.2. Press the OK button.3. Follow the grey line up to the graph and out to the

left to read off the average indoor temperature atthe selected week.

4. You can now select to take read outs for differentweeks by turning the control knob to the right orleft and read off the average temperature.

5. Press the OK or Back button to exit read off mode.

NIBE™ VVM 500Chapter 8 | Control - Menus42

Page 45: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Menu 4 - MY SYSTEMOverview

4.1.1 - pool *4.1 - plus functions4 - MY SYSTEM

4.1.3.1 - nibe uplink4.1.3 - internet

4.1.3.8 - tcp/ip settings

4.1.3.9 - proxy settings

4.1.4 - sms *

4.1.5 - SG Ready

4.1.6 - smart price adaption

4.2 - operating mode

4.3 - my icons

4.4 - time & date

4.6 - language

4.7 - holiday setting

4.9.1 - op. prioritisation4.9 - advanced

4.9.2 - auto mode setting

4.9.3 - degree minute setting

4.9.4 - factory setting user

4.9.5 - schedule blocking

4.9.6 - schedule silent mode

* Accessory needed.

Sub-menus

For the menu MY SYSTEM there are several sub-menus. Status information for the relevant menu canbe found on the display to the right of the menus.

plus functions Settings applying to any installed extrafunctions in the heating system.

operating mode Activation of manual or automaticoperating mode. The status information shows the se-lected operating mode.

my icons Settings regarding which icons in the indoormodule's user interface that are to appear on the hatchwhen the door is closed.

time & date Setting current time and date.

language Select the language for the display here.The status information shows the selected language.

holiday setting Vacation scheduling heating and hotwater comfort. Status information "set" is displayed ifyou set a vacation schedule but it is not active at themoment, "active" is displayed if any part of the vacationschedule is active, otherwise it displays " off".

advanced Settings of indoor module work mode.

Menu 4.1 - plus functionsSettings for any additional functions installed in VVM500 can be made in the sub menus.

Menu 4.1.1 - pool (accessory is required)

start temp

Setting range: 5.0 - 80.0 °C

Default value: 22.0 °C

stop temperature

Setting range: 5.0 - 80.0 °C

Default value: 24.0 °C

Select whether the pool control is to be activated andwithin what temperatures (start and stop temperature)pool heating must occur.

When the pool temperature drops below the set starttemperature and there is no hot water or heating re-quirement, VVM 500 starts pool heating.

Untick "activated" to switch off the pool heating.

Caution

The start temperature cannot be set to a valuethat is higher than the stop temperature.

Menu 4.1.3 - internetHere you make settings for connecting VVM 500 to theinternet.

43Chapter 8 | Control - MenusNIBE™ VVM 500

Page 46: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

NOTE

For these functions to work the network cablemust be connected.

Menu 4.1.3.1 - nibe uplinkHere you can manage the installation's connection toNIBE Uplink™ (http://www.nibeuplink.com) and seethe number of users connected to the installation viathe internet.

A connected user has a user account in NIBE Uplink™which have been given permission to control and/ormonitor your installation.

Request new connection string

To connect a user account on NIBE Uplink™ to yourinstallation, you must request a unique connectionstring.1. Mark “request new connection string" and press

the OK button.2. The installation now communicates with NIBE Up-

link™ to create a connection string.3. When a connection string has been received, it is

shown in this menu at "connection string" and isvalid for 60 minutes.

Disconnect all users1. Mark “switch off all users" and press the OK button.2. The installation now communicates with NIBE Up-

link™ to release your installation from all connec-ted users via the internet.

NOTE

After disconnecting all users none of them canmonitor or control your installation via NIBEUplink™ without requesting a new connectionstring.

Menu 4.1.3.8 - tcp/ip settingsYou can set TCP/IP settings for your installation here.

Automatic setting (DHCP)1. Tick “automatic". The installation now receives the

TCP/IP settings using DHCP.2. Mark “confirm" and press the OK button.

Manual setting1. Untick "automatic", you now have access to several

setting options.2. Mark “ip-address" and press the OK button.3. Enter the correct details via the virtual keypad.4. Mark “OK" and press the OK button.5. Repeat 1 - 3 for "net mask", "gateway" and "dns".6. Mark “confirm" and press the OK button.

Caution

The installation cannot connect to the internetwithout the correct TCP/IP settings. If unsureabout applicable settings use the automaticmode or contact your network administrator(or similar) for further information.

TIP

All settings made since opening the menu canbe reset by marking "reset" and pressing theOK button.

Menu 4.1.3.9 - proxy settingsYou can set proxy settings for your installation here.

Proxy settings are used to give connection informationto a intermediate server (proxy server) between theinstallation and Internet. These settings are primarilyused when the installation connects to the Internet viaa company network. The installation supports proxyauthentication of the HTTP Basic and HTTP Digest type.

If unsure about applicable settings use the preset set-tings or contact your network administrator (or similar)for further information.

Setting1. Tick “use proxy" if you do not want to use a proxy.2. Mark “server" and press the OK button.3. Enter the correct details via the virtual keypad.4. Mark “OK" and press the OK button.5. Repeat 1 - 3 for "port", "user name" and "pass-

word".6. Mark “confirm" and press the OK button.

TIP

All settings made since opening the menu canbe reset by marking "reset" and pressing theOK button.

Menu 4.1.4 - sms (accessory is required)Make settings for the accessory SMS 40 here.

Add the mobile numbers that are to have access tochange and receive status information from the indoormodule. Mobile numbers must include country codee.g. +46 XXXXXXXX.

If you want to receive an SMS message in the event ofthe alarm mark the box to the right of the telephonenumber.

NOTE

Telephone numbers provided must be able toreceive SMS messages.

Menu 4.1.5 - SG ReadyThis function can only be used in mains networks thatsupport the "SG Ready"-standard.

Make settings for the function "SG Ready" here.

NIBE™ VVM 500Chapter 8 | Control - Menus44

Page 47: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

affect room temperature

Here you set whether room temperature should beaffected when activating "SG Ready".

With low price mode of "SG Ready" the parallel offsetof the indoor temperature is increased by "+1". If aroom sensor is installed and activated, the desired roomtemperature increases by 1 °C.

With over capacity mode of "SG Ready" the paralleloffset for the indoor temperature is increased by"+2".If a room sensor is installed and activated, the desiredroom temperature increases by 2 °C.

affect hot water

Here you set whether the temperature of the hot watershould be affected when activating "SG Ready".

With low price mode on "SG Ready" the stop temper-ature of the hot water is set as high as possible at onlycompressor operation (immersion heater not permit-ted).

With over capacity mode of "SG Ready" the hot wateris set to "luxury" (immersion heater permitted).

affect cooling (accessories required)

Here you set whether room temperature during coolingoperation should be affected when activating "SGReady".

With low price mode of "SG Ready" and cooling oper-ation the indoor temperature is not affected.

With over capacity mode of "SG Ready" and coolingoperation the parallel offset for the indoor temperatureis reduced by"-1". If a room sensor is installed and ac-tivated, the desired room temperature decreases by 1°C.

affect pool temperature (accessories required)

Here you set whether pool temperature should be af-fected when activating "SG Ready".

With low price mode of "SG Ready" the desired pooltemperature (start and stop temperature) is increasedby 1 °C.

With over capacity mode of "SG Ready" the desiredpool temperature (start and stop temperature) is in-creased by 2 °C.

NOTE

The function must be connected to two AUXinputs and activated in menu 5.4.

Menu 4.1.6 - smart price adaptionSmart price adaption moves the heat pump's consump-tion over 24 hours to periods with the cheapest electri-city tariff, which gives savings for hourly rate basedelectricity contracts. The function is based on hourlyrates for the next 24 hours being retrieved via NIBEUplink™ and therefore an internet connection and anaccount for NIBE Uplink™ are required.

Heating, pool and any cooling are controlled so thatthe energy supply over 24 hours is unchanged but thesupply occurs when the price is as low as possible. Thehot water uses the same function but also has a learn-ing function that learns the household's hot water

needs and adapts to it. When the effect on the hotwater is active, it is no longer possible to control thehot water's comfort mode in menu 2.2.

Activate smart price adaption by highlighting thefunction and pressing the OK button. When smart priceadaption has been activated, the settings that can bemade are displayed. To select which selectable func-tions are to be permitted or not you highlight thefunction using the control knob and press the OK but-ton.

Price of electricity overview

Here you can obtain information on how the electricityprice varies over up to three days.

Range

Set your electricity price area here.

Affect room temperature

How much the room temperature is to be affected bythe electricity price is set here. The greater the value,the greater the effect the electricity price has and thesavings are larger, but at the same time there is an in-creased risk of affecting comfort.

Setting range: 1–10

Default value: 5

Affect hot water

How much the hot water is to be affected by the elec-tricity price is set here. The greater the value, thegreater the effect the electricity price has and the pos-sible savings are larger, but at the same time there isan increased risk of affecting comfort.

Setting range: 1–4

Default value: 2

Affect pool temperature

How much the pool temperature is to be affected bythe electricity price is set here. The greater the value,the greater the effect the electricity price has and thepossible savings are larger, but at the same time thereis an increased risk of affecting comfort.

Setting range: 1–10

Default value: 2

Affect cooling

How much the cooling temperature is to be affectedby the electricity price is set here. The greater the value,the greater the effect the electricity price has and thepossible savings are larger, but at the same time thereis an increased risk of affecting comfort.

Setting range: 1–10

Default value: 3

45Chapter 8 | Control - MenusNIBE™ VVM 500

Page 48: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Menu 4.2 - operating mode

operating mode

Setting range: auto, manual, add. heat only

Default value: auto

functions

Setting range: compressor, addition, heating, cooling

The indoor module operating mode is usually set to"auto". It is also possible to set the indoor module to"add. heat only", but only when an addition is used, or"manual" the select yourself what functions are to bepermitted.

Change the operating mode by marking the desiredmode and pressing the OK button. When an operatingmode is selected it shows what in the indoor moduleis permitted (crossed out = not permitted) and select-able alternatives to the right. To select selectablefunctions that are permitted or not you mark thefunction using the control knob and press the OK but-ton.

Operating mode auto

In this operating mode the indoor module automatic-ally selects what functions are permitted.

Operating mode manual

In this operating mode you can select what functionsare permitted. You cannot deselect "compressor" inmanual mode.

Operating mode add. heat only

In this operating mode the compressor is not activeand only additional heating is used.

Caution

If you choose mode "add. heat only" the com-pressor is deselected and there is a higher op-erating cost.

Caution

You cannot change from only additional heatif you do not have a heat pump connected(see Menu 5.2.2).

Functions

"compressor" is that which produces heating and hotwater for the accommodation. If "compressor" isdeselected, a symbol in the main menu on the symbolfor the indoor module. You cannot deselect "com-pressor" in manual mode.

"addition" is what helps the compressor to heat theaccommodation and/or the hot water when it cannotmanage the whole requirement alone.

"heating" means that you get heat in the accommod-ation. You can deselect the function when you do notwish to have heating running.

"cooling" means that you get cooling in the accommod-ation in hot weather. You can deselect the functionwhen you do not wish to have the cooling running.

This alternative requires an accessory for cooling orthat the heat pump has a built in function for coolingand is activated in the menu.

Menu 4.3 - my iconsYou can select what icon should be visible when thedoor to VVM 500 is closed. You can select up to 3 icons.If you select more, the ones you selected first will disap-pear. The icons are displayed in the order you selectedthem.

Menu 4.4 - time & dateSet time and date, display mode and time zone here.

TIP

Time and date are set automatically if the heatpump is connected to NIBE Uplink™. To obtainthe correct time, the time zone must be set.

Menu 4.6 - languageChoose the language that you want the informationto be displayed in here.

Menu 4.7 - holiday settingTo reduce energy consumption during a holiday youcan schedule a reduction in heating and hot watertemperature. Cooling, pool and solar panel cooling canalso be scheduled if the functions are connected.

If a room sensor is installed and activated the desiredroom temperature (°C) is set during the time period.This setting applies to all climate systems with roomsensors.

If a room sensor is not activated, the desired offset ofthe heating curve is set. This setting applies to all cli-mate systems without room sensors. One step is usuallyenough to change the room temperature by one de-gree, but in some cases several steps may be required.

Vacation scheduling starts at 00:00 on the start dateand stops at 23:59 on the stop date.

TIP

Complete holiday setting about a day beforeyour return so that room temperature and hotwater have time to regain usual levels.

TIP

Set the vacation setting in advance and activ-ate just before departure in order to maintainthe comfort.

Menu 4.9 - advancedMenu advanced has orange text and is intended forthe advanced user. This menu has several sub-menus.

NIBE™ VVM 500Chapter 8 | Control - Menus46

Page 49: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Menu 4.9.1 - op. prioritisation

op. prioritisation

Setting range: 0 or 10 – 180 min

Default value: 30 min

Choose here how long the installation should workwith each requirement if there are several requirementsat the same time. If there is only one requirement theinstallation only works with that requirement.

The indicator marks where in the cycle the installationis.

If 0 minutes is selected it means that requirement isnot prioritised, but will only be activated when thereis no other requirement.

Menu 4.9.2 - auto mode setting

start cooling (accessory required)

Setting range: -20 – 40 °C

Default value: 25

stop heating

Setting range: -20 – 40 °C

Default values: 15

stop additional heat

Setting range: -25 – 40 °C

Default values: 5

filtering time

Setting range: 0 – 48 h

Default value: 24 h

When the operating mode is set to "auto", the indoormodule selects when start and stop of additional heatand heat production is permitted, dependent on theaverage outdoor temperature. If accessories for coolingare present or if the heat pump has the integratedcooling function and it is activated in the menu youcan also select the start temperature for cooling.

Select the average outdoor temperatures in this menu.

You can also set the time over which (filtering time)the average temperature is calculated. If you select 0,the present outdoor temperature is used.

Caution

It cannot be set "stop additional heat" higherthan "stop heating".

Caution

In systems where heating and cooling sharethe same pipes "stop heating" cannot be sethigher than "start cooling" if there is not acooling/heating sensor.

Menu 4.9.3 - degree minute setting

current value

Setting range: -3000 – 3000

start compressor

Setting range: -1000 – -30

Default value: -60

start diff additional heat

Setting range: 100 – 1000

Default value: 700

diff. between additional steps

Setting range: 0 – 1000

Default value: 100

Degree minutes are a measurement of the currentheating requirement in the house and determine whenthe compressor respectively additional heat willstart/stop.

Caution

Higher value on "start compressor" gives morecompressor starts, which increase wear on thecompressor. Too low value can give unevenindoor temperatures.

Menu 4.9.4 - factory setting userAll settings that are available to the user (includingadvanced menus) can be reset to default values here.

Caution

After factory setting, personal settings such asheating curves must be reset.

Menu 4.9.5 - schedule blockingThe compressor and/or addition in the indoor modulecan be scheduled to be blocked for up to two differenttime periods here.

When scheduling is active the relevant blocking symbolis shown in the main menu on the symbol for the in-door module.

47Chapter 8 | Control - MenusNIBE™ VVM 500

Page 50: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Schedule: The period to be changed is selected here.

Activated: Scheduling for the selected period is activ-ated here. Set times are not affected at deactivation.

Day: Select which day or days of the week the scheduleis to apply to here. To remove the scheduling for aparticular day, the time for that day must be reset bysetting the start time to the same as the stop time. Ifthe line "all" is used, all days in the period are set forthese times.

Time period: The start and stop time for the selectedday for scheduling are selected here.

Blocking: The desired blocking is selected here.

Conflict: If two settings conflict with each other a redexclamation mark is displayed.

Blocking the compressor in the outdoor unit.

Blocking additional heat.

TIP

If you wish to set similar scheduling for everyday of the week start by filling in “all” and thenchanging the desired days.

TIP

Set the stop time earlier than the start time sothat the period extends beyond midnight.Scheduling then stops at the set stop time theday after.

Scheduling always starts on the date that thestart time is set for.

Caution

Long term blocking can cause reduced comfortand operating economy.

Menu 4.9.6 - schedule silent modeThe compressor can be scheduled to be set to "quietmode" (the heat pump must support this) for up totwo different time periods here.

When scheduling is active the "quiet mode" symbol isshown in the main menu on the symbol for the indoormodule.

Schedule: The period to be changed is selected here.

Activated: Scheduling for the selected period is activ-ated here. Set times are not affected at deactivation.

Day: Select which day or days of the week the scheduleis to apply to here. To remove the scheduling for aparticular day, the time for that day must be reset bysetting the start time to the same as the stop time. Ifthe line "all" is used, all days in the period are set forthese times.

Time period: The start and stop time for the selectedday for scheduling are selected here.

Conflict: If two settings conflict with each other a redexclamation mark is displayed.

TIP

If you wish to set similar scheduling for everyday of the week start by filling in “all” and thenchanging the desired days.

TIP

Set the stop time earlier than the start time sothat the period extends beyond midnight.Scheduling then stops at the set stop time theday after.

Scheduling always starts on the date that thestart time is set for.

Caution

Long term scheduling of "quiet mode" cancause reduced comfort and operating eco-nomy.

NIBE™ VVM 500Chapter 8 | Control - Menus48

Page 51: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Menu 5 - SERVICEOverview

5.1.1 - hot water settings5.1 - operating settings5 - SERVICE

5.1.2 - max flow line temperat-ure

5.1.3 - max diff flow line temp.

5.1.4 - alarm actions

5.1.11 - pump speed heatingmedium

5.1.12 - internal electrical addi-tion

5.1.13 - max inst. el.pwr (BBR)

5.1.14 - flow set. climate sys-tem

5.1.18 - flow setting chargepump

5.1.22 - heat pump testing

5.1.23 - compressor curve

5.2.2 - installed heat pump5.2 - system settings

5.2.4 - accessories

5.3.3 - extra climate system *5.3 - accessory settings

5.3.4 - solar heating *

5.3.7 - external addition

5.4 - soft in/outputs

5.5 - factory setting service

5.6 - forced control

5.7 - start guide

5.8 - quick start

5.9 - floor drying function

5.10 - change log

5.11.1.1 - heat pump5.11.1 - EB1015.11 -heat pump settings

5.11.1.2 - charge pump

* Accessory needed.

Go to the main menu and hold the Back button in for7 seconds to access the Service menu.

Sub-menus

Menu SERVICE has orange text and is intended forthe advanced user. This menu has several sub-menus.Status information for the relevant menu can be foundon the display to the right of the menus.

operating settings Operating settings for the indoormodule.

system settings System settings for the indoor module,activating accessories etc.

accessory settings Operational settings for differentaccessories.

soft in/outputs Setting software controlled in andoutputs on the input circuit board (AA3).

factory setting service Total reset of all settings (includ-ing settings available to the user ) to default values.

forced control Forced control of the different compon-ents in the indoor module.

start guide Manual start of the start guide which isrun the first time when the indoor module is started.

quick start Quick starting the compressor.

NOTE

Incorrect settings in the service menus candamage the installation.

49Chapter 8 | Control - MenusNIBE™ VVM 500

Page 52: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Menu 5.1 - operating settingsOperating settings can be made for the indoor modulein the sub menus.

Menu 5.1.1 - hot water settings

economy

Setting range start temp. economy: 5 – 55 °C

Factory setting start temp. economy: 44 °C

Setting range stop temp. economy: 5 – 60 °C

Factory setting stop temp. economy: 47 °C

normal

Setting range start temp. normal: 5 – 55 °C

Factory setting start temp. normal: 47 °C

Setting range stop temp. normal: 5 – 60 °C

Factory setting stop temp. normal: 50 °C

luxury

Setting range start temp. lux: 5 – 70 °C

Factory setting start temp. lux: 52 °C

Setting range stop temp. lux: 5 – 70 °C

Factory setting stop temp. lux: 55 °C

Here you set the start and stop temperature of the hotwater for the different comfort options in menu 2.2.

With "high power" activated the hot water is chargedwith greater power than standard mode and thereforehas a greater hot water capacity

Menu 5.1.2 - max flow line temperature

climate system

Setting range: 5-70 °C

Default value: 60 °C

Set the maximum supply temperature for the climatesystem here. If the installation has more than one cli-mate system, individual maximum flow temperaturescan be set for each system.

Caution

Underfloor heating systems are normally maxflow line temperature set between 35 and 45°C.

Check the max floor temperature with yourfloor supplier.

Menu 5.1.3 - max diff flow line temp.

max diff compressor

Setting range: 1 – 25 °C

Default value: 10 °C

max diff addition

Setting range: 1 – 24 °C

Default value: 7 °C

Here you set the maximum permitted differencebetween the calculated and actual supply temperatureduring compressor respectively add. heat mode. Maxdiff. additional heat can never exceed max diff. com-pressor

max diff compressor

When the current supply temperature deviates fromthe set value compared to that calculated, the heatpump is forced to stop irrespective of the degree-minute value.

If the current supply temperature exceeds the calcu-lated flow with set value, the degree minute value isset to 0. The compressor in the heat pump stops whenthere is only a heating demand.

max diff addition

If "addition” is selected and activated in menu 4.2 andthe present supply temp exceeds the calculated withset value, the additional heat is forced to stop.

Menu 5.1.4 - alarm actionsSelect if you want the indoor module to alert you thatthere is an alarm in the display here.

Caution

If no alarm action is selected, it can result inhigher energy consumption in the event of analarm.

Menu 5.1.11 - pump speed heatingmedium

operating mode

Setting range: auto / manual

Default value: auto

auto: The heating medium pump controls the speedfor optimum operation.

manual: The speed of the heating medium pump isadjustable between 0 and 100%.

NIBE™ VVM 500Chapter 8 | Control - Menus50

Page 53: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Menu 5.1.12 - internal electrical addition

max connected el. add.

Setting range: 0–9

Default values: 9 kW

fuse size

Setting range: 1 - 200 A

Default values: 16 A

Here you set the max. electrical output of the internalelectrical addition in VVM 500 and the fuse size for theinstallation.

The results of these checks appear just below wherethe checks were activated.

Menu 5.1.13 - max inst. el.pwr (BBR)

max installed el.pwr (only this machine)

Setting range: 0.000 - 30.000 kW

Default values: 15.000 kW

In order to meet certain building regulations, it is pos-sible to lock the device's maximum power output. Inthis menu you can set the value corresponding to theheat pump's maximum power connection for heating,hot water and cooling, if applicable Note whether thereare also external electrical components that are to beincluded. After the value has been locked, a weekscooling-off period starts. After this period, parts in themachine must be replaced in order to obtain greaterpower. If the above building regulations are not applic-able, do not use this setting.

Menu 5.1.14 - flow set. climate system

presettings

Setting range: radiator, floor heat., rad. + floor heat.,DOT °C

Default value: radiator

Setting range DOT: -40,0 - 20,0 °C

Factory setting DOT: -18,0 °C

own setting

Setting range dT at DOT: 0,0-25,0

Factory setting dT at DOT: 10,0

Setting range DOT: -40,0 - 20,0 °C

Factory setting DOT: -18,0 °C

The type of heating distribution system the heatingmedium pump (GP1) works towards is set here.

dT at DOT is the difference in degrees between flowand return temperatures at dimensioned outdoortemperature.

Menu 5.1.18 - flow setting charge pumpSet the flow for the charge pump here. Activate theflow test to measure delta (the difference between theflow and return line temperatures from the heat pump).

The test is OK if delta lies between the two parametersshown in the display.

Menu 5.1.22 - heat pump testing

NOTE

This menu is intended for testing VVM 500according to different standards.

Use of this menu for other reasons may resultin your installation not functioning as inten-ded.

This menu contains several sub-menus, one for eachstandard.

Menu 5.1.23 - compressor curveSet whether the compressor in the heat pump shouldwork to a particular curve or if it should work by degreeminutes etc.

You set a curve for a demand (heat, hot water etc.) byunticking "auto", turning the control knob until atemperature is marked and pressing OK. You can nowset at what temperatures the max. and min. frequen-cies, respectively will occur.

This menu can consist of several windows (one for eachavailable demand), use the navigation arrows in thetop left corner to change between the windows.

NOTE

This menu is only displayed if VVM 500 is con-nected to a heat pump with inverter controlledcompressor.

Menu 5.2 - system settingsMake different system settings for your installationhere, e.g. activate the connected heat pump and whichaccessories are installed.

Menu 5.2.2 - installed heat pumpIf a heat pump is connected to the master installation,set it here.

There are two ways of activating a connected heatpump. You can either highlight the alternative in thelist or use the automatic function "Searching for in-stalled heat pumps. Please wait.".

"Searching for installed heat pumps. Please wait.''

Highlight "Searching for installed heat pumps. Pleasewait." and press the OK button to automatically findconnected heat pumps for the master heat pump.

Menu 5.2.4 - accessoriesSet which accessories are installed on the installationhere.

There are two ways of activating connected accessories.You can either mark the alternative in the list or usethe automatic function "search installed acc.".

51Chapter 8 | Control - MenusNIBE™ VVM 500

Page 54: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

search installed acc.

Mark “search installed acc." and press the OK buttonto automatically find connected accessories for VVM500.

Menu 5.3 - accessory settingsThe operating settings for accessories that are installedand activated are made in the sub-menus for this.

Menu 5.3.3 - extra climate system

use in cooling mode

Setting range: on/off

Factory setting: off

mixing valve amplifier

Setting range: 0.1 –10.0

Default value: 1.0

mixing valve step delay

Setting range: 10 – 300 s

Default values: 30 s

Here you set which climate system (2 - 4) you wish toset. In the next menu you can make settings for theclimate system that you have selected. If this functionis activated, you can set "cooling flow temp. at +20°C"and "cooling flow temp. at +40°C" for each climatesystem where the function is activated.

Caution

This setting option only appears if "activecooling 2 pipe" is activated in menu 5.2.4.

The shunt amplification and shunt waiting time for thedifferent extra climate systems that are installed arealso set here.

See the accessory installation instructions for functiondescription.

Menu 5.3.4 - solar heating

start delta-T

Setting range: 1 - 40 °C

Default value: 8 °C

stop delta-T

Setting range: 0 - 40 °C

Default value: 4 °C

max. tank temperature

Setting range: 70 - 85 °C

Default value: 85 °C

max. solar collector temp.

Setting range: 80 - 200 °C

Default value: 125 °C

max solar pool temperature

Setting range: 10 - 80 °C

Default value: 30 °C

anti-freeze temperature

Setting range: -20 - +20 °C

Default value: 2 °C

start solar collector cooling

Setting range: 80 - 200 °C

Default value: 110 °C

start delta-T, stop delta-T: Here you can set the tem-perature difference between solar panel and solar tankat which the circulation pump is to start and stop.

max. tank temperature, max. solar collector temp.:Here you can set the maximum temperatures in tankrespectively solar panel at which the circulation pumpis to stop. This is to protect against excess temperaturesin the solar tank.

max solar pool temperature: Here you can set themaximum temperature where the solar panel stopsheating pool (if the unit is made up in such a way). Poolheating can only occur if there is a heat surplus whenheating and/or the hot water demand is met.

If the unit has an anti-freeze function and/or solarpanel cooling you can activate them here. When thefunction has been activated, you can make settings forthem.

freeze protection

anti-freeze temperature: Here you can set the temper-ature in the solar panel at which the circulation pumpis to start to prevent freezing.

solar panel cooling

start solar collector cooling: If the temperature in thesolar panel is greater than this setting at the same timethat the temperature in the solar tank is greater thanthe set maximum temperature, the external functionfor cooling is activated.

NIBE™ VVM 500Chapter 8 | Control - Menus52

Page 55: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Menu 5.3.7 - external additionMake settings for external addition here. External addi-tion is for example external oil, gas or electric boiler.

If the external addition is not step controlled, in addi-tion to selecting when this should start also set the runtime for the addition.

If the external addition is step controlled you can selectwhen the addition is to start, set the maximum numberof permitted steps and whether binary stepping is tobe used.

See the accessory installation instructions for functiondescription.

Menu 5.4 - soft in/outputsHere you can select which in/output on the input circuitboard (AA3) the external contact function (page 23)is to be connected to.

Selectable inputs on terminal block AUX1-5 (AA3-X6:9-18) and output AA3-X7 (on the input circuit board).

Menu 5.5 - factory setting serviceAll settings can be reset (including settings availableto the user) to default values here.

NOTE

When resetting, the start guide is displayedthe next time the indoor module is restarted.

Menu 5.6 - forced controlYou can force control the different components in theindoor module and any connected accessories here.

Menu 5.7 - start guideWhen the indoor module is started for the first timethe start guide starts automatically. Start it manuallyhere.

See page 28 for more information about the startguide.

Menu 5.8 - quick startIt is possible to start the compressor from here.

Caution

There must be a heating or hot water demandto start the compressor.

Caution

Do not quick start the compressor too manytimes over a short period of time as this maydamage the compressor and its surroundingequipment.

Menu 5.9 - floor drying function

length of period 1 - 3, 5-7

Setting range: 0 - 30 days

Default value: 2 days

temp. period 1 - 3, 5-7

Setting range: 15 - 70 °C

Default value:20 °Ctemp. period 130 °Ctemp. period 240 °Ctemp. period 340 °Ctemp. period 530 °Ctemp. period 620 °Ctemp. period 7

length of period 4

Setting range: 0 - 30 days

Default value: 3 days

temp. period 4

Setting range: 15 - 70 °C

Default value: 45 °C

Set the function for under floor drying here.

You can set up to seven period times with differentcalculated flow temperatures. If less than seven periodsare to be used, set the remaining period times to 0days.

Mark the active window to activate the underfloordrying function. A counter at the bottom shows thenumber of days the function has been active.

NOTE

During floor drying the heating medium pumpin 100% runs regardless of the setting in menu5.1.10.

TIP

If operating mode "add. heat only" is to beused, select it in menu 4.2.

Menu 5.10 - change logRead off any previous changes to the control systemhere.

The date, time and ID no. (unique to certain settings)and the new set value is shown for every change.

NOTE

The change log is saved at restart and remainsunchanged after factory setting.

Menu 5.11 - heat pump settingsSettings for installed heat pump can be made in thesubmenus.

53Chapter 8 | Control - MenusNIBE™ VVM 500

Page 56: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Menu 5.11.1 - EB101Make settings specifically for the installed heat pumpand charge pump here.

Menu 5.11.1.1 - heat pumpMake settings for the installed heat pump here. To seewhat settings you can make, see installation manualfor the heat pump.

Menu 5.11.1.2 - charge pump

operating mode

Setting range: auto / intermittent

Default value: auto

Set the operating mode for the charge pump here.

auto: The charge pump runs according to the currentoperating mode for VVM 500.

intermittent: The charge pump starts and stops 20seconds before and after the compressor in the heatpump.

speed during operation

heating, hot water, pool, cooling

Setting range: auto / manual

Default value: auto

Manual setting

Setting range: 1–100 %

Default values: 70 %

max. allowed speed

Setting range: 80–100 %

Default values: 100 %

speed in wait mode

Setting range: 1–100 %

Default values: 30 %

Set the speed at which the charge pump is to operatein the present operating mode. Select "auto" if thespeed of the charge pump is to be regulated automat-ically (factory setting) for optimal operation.

If "auto" is activated for heating operation, you canalso make the setting "max. allowed speed" which re-stricts the charge pump and does not allow it to run ata higher speed than the set value.

For manual operation of the charge pump deactivate"auto" for the current operating mode and set the valueto between 1 and 100 % (the previously set value for"max. allowed speed" no longer applies).

waitmodemeans heating or cooling operating modesfor the charge pump, when the heat pump has neithera need for compressor operation nor electrical additionand slows down.

NIBE™ VVM 500Chapter 8 | Control - Menus54

Page 57: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Service actionsNOTE

Servicing should only be carried out by personswith the necessary expertise.

When replacing components on VVM 500 onlyreplacement parts from NIBE may be used.

Emergency modeEmergency mode is used in event of operational inter-ference and in conjunction with service. Hot water ca-pacity is reduced in this mode.

Emergency mode is activated by setting switch (SF1)to ” ”. This means that:

The status lamp illuminates yellow.The display is not lit and the control computer is notconnected.The temperature at the immersion heater is con-trolled by the thermostat (FD1-BT30). It can be setto 35 or 45 °C.Only the circulation pumps and electrical additionare active. The electrical addition power in emergencymode is set in the immersion heater card (AA1). Seepage 22 for instructions.

Emptying the hot water coilThe hot water coil is most easily drained by detachingthe cold water pipe at the coils's entry to the reservoir.

Draining the climate systemIn order to carry out service on the climate system, itmay be easier to drain the system first using drain valve(QM1).

NOTE

There may be some hot water when drainingthe heating medium side/climate system.There is a risk of scalding.

Temperature sensor data

Voltage (VDC)Resistance(kOhm)

Temperature(°C)

3.256351.0-403.240251.6-353.218182.5-303.189133.8-253.15099.22-203.10574.32-153.04756.20-102.97642.89-52.88933.0202.78925.6152.67320.02102.54115.77152.39912.51202.24510.00252.0838.045301.9166.514351.7525.306401.5874.348451.4263.583501.2782.968551.1362.467601.0072.068650.8911.739700.7851.469750.6911.246800.6071.061850.5330.908900.4690.779950.4140.672100

USB service outlet

LEK

55Chapter 9 | ServiceNIBE™ VVM 500

9 Service

Page 58: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

VVM 500 is equipped with a USB socket in the displayunit. This USB socket can be used to connect a USBmemory to update the software, save logged informa-tion and handle the settings in VVM 500.

INDOOR CLIMATE

MY SYSTEM INFO

HOT WATER

USB

When a USB memory is connected a new menu (menu7) appears in the display.

Menu 7.1 - update firmware

This allows you to update the software in VVM 500.

NOTE

For the following functions to work the USBmemory must contain files with software forVVM 500 from NIBE.

The fact box at the top of the display shows information(always in English) of the most probable update thatthe update software has selected form the USBmemory.

This information states which product the software isintended for, the software version and general inform-ation about them. If you wish to select another file than

the one selected, the correct file can be selected by"choose another file".

start updating

Select “start updating" if you want to start the update.You are asked whether you really want to update thesoftware. Respond "yes" to continue or "no" to undo.

If you responded"yes" to the previous question theupdate starts and you can now follow the progress ofthe update on the display. When the update is com-plete VVM 500 restarts.

NOTE

A software update does not reset the menusettings in VVM 500.

NOTE

If the update is interrupted before it is com-plete (for example power cut etc.) the softwarecan be reset to the previous version if the OKbutton is held in during start up until the greenlamp starts to illuminate (takes about 10seconds).

choose another file

Select “choose another file" if you do not want to usethe suggested software. When you scroll through thefiles, information about the marked software is shownin a fact box just as before. When you have selected afile with the OK button you will return to the previouspage (menu 7.1) where you can choose to start theupdate.

Menu 7.2 - logging

Setting range: 1 s – 60 min

Default setting range: 5 s

NIBE™ VVM 500Chapter 9 | Service56

Page 59: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Set whether the present measurement values fromVVM 500 are to be saved in a log on the USB memory.

Log for longer periods1. Set the desired interval between loggings.2. Tick “activated".3. The present values from VVM 500 are saved in a

file in the USB memory at the set interval until“activated" is unticked.

Caution

Untick "activated" before removing the USBmemory.

Menu 7.3 - manage settings

Here you can manage (save as or retrieve from) all themenu settings (user and service menus) in VVM 500with a USB memory.

Via "save settings" you save the menu settings to theUSB memory in order to restore them later or to copythe settings to another VVM 500.

NOTE

When you save the menu settings to the USBmemory you replace any previously saved set-tings on the USB memory.

Via "recover settings" you reset all menu settings fromthe USB memory.

NOTE

Reset of the menu settings from the USBmemory cannot be undone.

57Chapter 9 | ServiceNIBE™ VVM 500

Page 60: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

In most cases, the indoor module notes operationalinterference (operational interference can lead to dis-turbance in comfort) and indicates this with alarms andshows action instructions in the display.

Info-menuAll the indoor module measurement values aregathered under menu 3.1 in the indoor module menusystem. Looking through the values in this menu canoften simplify finding the fault source.

Manage alarm

In the event of an alarm, some kind of malfunction hasoccurred, which is indicated by the status lamp chan-ging from green continuously to red continuously. Inaddition, an alarm bell appears in the informationwindow.

AlarmIn the event of an alarm with a red status lamp a mal-function has occurred that the indoor module cannotremedy itself. In the display, by turning the control knoband pressing the OK button, you can see the type ofalarm it is and reset it. You can also choose to set theindoor module to aid mode.

info / action Here you can read what the alarm meansand receive tips on what you can do to correct theproblem that caused the alarm.

reset alarm In most cases it is enough to select "resetalarm" to correct the problem that caused the alarm.If a green light illuminates after selecting "reset alarm"the alarm has been remedied. If a red light is still visibleand a menu called ”alarm” is visible in the display, theproblem that caused the alarm remains. If the alarmdisappears and then returns, see the troubleshootingsection (page 58).

aid mode ”aid mode” is a type of emergency mode.This means that the indoor module produces heatand/or hot water despite there being some kind ofproblem. This can mean that the indoor module'scompressor is not running. In this case the immersionheater produces heat and/or hot water.

NOTE

To select aid mode an alarm action must beselected in menu 5.1.4.

Caution

Selecting "aid mode” is not the same as correct-ing the problem that caused the alarm. Thestatus lamp will therefore continue to be red.

TroubleshootingIf the operational interference is not shown in the dis-play the following tips can be used:

Basic actionsStart by checking the following possible fault sources:

The switch's (SF1) position.Group and main fuses of the accommodation.The property's earth circuit breaker.The indoor module's miniature circuit breaker (FA1).The indoor module's temperature limiter (FD1).Correctly set load monitor (if installed).

Low hot water temperature or a lack of hotwater

Too high domestic water flow.Reduce the domestic water flow, see diagram ofhot water capacity on page 62.

Indoor module in incorrect operating mode.If mode "manual" is selected, select "addition".

Large hot water consumption.Wait until the hot water has heated up. Temporar-ily increased hot water capacity (temporary lux)can be activated in menu 2.1.

Too low hot water setting.Enter menu 2.2 and select a higher comfort mode.

Low room temperatureClosed thermostats in several rooms.Indoor module in incorrect operating mode.

Enter menu 4.2. If mode "auto" is selected, selecta higher value on "stop heating“ in menu 4.9.2.If mode "manual" is selected, select "heating". Ifthis is not enough, select "addition".

Too low set value on the automatic heating control.Enter menu 1.1 "temperature" and adjust the offsetof the heating curve. If the room temperature isonly low in cold weather the curve slope in menu1.9.1 "heating curve" needs adjusting up.

"Holiday mode" activated in menu 4.7.Enter menu 4.7 and select “Off”.

External switch for changing the room heating activ-ated.

Check any external switches.Air in the climate system.

Vent the climate system (see page 27).Closed valves (QM20), (QM32)to the climate system.

Open the valves.

NIBE™ VVM 500Chapter 10 | Disturbances in comfort58

10 Disturbances in comfort

Page 61: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

High room temperatureToo high set value on the automatic heating control.

Enter menu 1.1 (temperature) and adjust the heatcurve offset downwards. If the room temperatureis only high in cold weather the curve slope in menu1.9.1 (heating curve) needs to be adjusted down.

External switch for changing the room heating activ-ated.

Check any external switches.

Low system pressureNot enough water in the climate system.

Fill the climate system with water and check forleaks (see page 27).

The compressor does not startThere is no heating requirement.

The indoor module does not call on heating norhot water.

Temperature conditions tripped.Wait until the temperature condition has been re-set.

Minimum time between compressor starts has notbeen reached.

Wait 30 minutes and check if the compressor hasstarted.

Alarm tripped.Follow the display instructions.

59Chapter 10 | Disturbances in comfortNIBE™ VVM 500

Page 62: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Active cooling. ACS 310Part no. 067 248

Auxiliary relay HR 10Part no. 067 309

Communications module MODBUS 40MODBUS 40 enables VVM 500 to be controlled andmonitored using a DUC (computer sub-center) in thebuilding. Communication occurs using MODBUS-RTU.

Part no. 067 144

Communications module SMS 40SMS 40 enables VVM 500 to be controlled and mon-itored via SMS messages. The mobile application ”NIBEMobile App” can be used with a mobile telephone withthe Android operating system .

Part no. 067 073

Energy measurement kit EMK 500Part no. 067 178

External electrical addition ELKThese accessories require accessory DEH 500 (stepcontrolled addition).

ELK 15

Immersion heater

15 kW, 3 x 400 V

Part no. 069 022

ELK 26

Immersion heater

26 kW, 3 x 400 V

Part no. 067 074

Extra shunt group ECS 40/ECS 41This accessory is used when VVM 500 is installed inhouses with two or more di erent climate systems thatrequire di erent supply temperatures.

Part no. 067 287ECS 40 (Max 80 m²)Part no. 067 288ECS 41 (Min 80 m²)

Gas boiler GBM 10-15This accessory requires accessory DEH 500.Part no. 069 122

Heat pump

F2026

6 kW Part no. 064 084

8 kW Part no. 064 085

10 kW Part no. 064 086

F2030

7 kW Part no. 064 099

9 kW Part no. 064 070

F2040

8 kW Part no. 064 109

12 kW Part no. 064 092

16 kW Part no. 064 108

F2300

14 kW Part no. 064 063

20 kW Part no. 064 064

Pipe for external heat source

DEH 500 (oil/electricity/gas)

Part no. 067 180

Pool heating POOL 500POOL 500 is an accessory that enables pool heatingwith VVM 500.

Part no. 067 181

Room sensor RTS 40Part no. 067 065

Room unit RMU 40RMU 40

Part no. 067 064

SCA 30SCA 30 means that VVM 500 can be connected to solarheating.

Part no. 067 179

Top cabinetTop cabinet to room height 2060, 2160, 2200-2450mm.

2060 mm

Part no. 056 177

2160 mm

Part no. 056 178

2200-2450 mm

Part no. 056 179

NIBE™ VVM 500Chapter 11 | Accessories60

11 Accessories

Page 63: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Dimensions and setting-out coordinates

19

28

43

1788

691

725

791

900

734

756

66

85

382

763

296

154

73

6157

660 381 290

64825-50

61Chapter 12 | Technical dataNIBE™ VVM 500

12 Technical data

Page 64: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Hot water capacity

Capacity circulation pump

10

12

14

16

18

20

22

24

26

28

30

100 150 200 250 300 350

(l/min)Tap flow

(l/min)

Flow

(litres)

Hot water capacity VVM 500

LuxNormalEconomy

NIBE™ VVM 500Chapter 12 | Technical data62

Page 65: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Technical specifications

IP 21

3x400V

3x400V

20kWMax heat pump output 1)

9kWAdditional powerElectrical data

400V 3NAC 50Hz

Rated voltage

16.2AMax operating current16AFuse

3 – 76WOutput, Heating medium pump3 – 76WOutput, charge pump

IP 21IP classHeating medium circuit

low energyEnergy class circ-pumplow energyEnergy class charge pump

0.3 (3bar)

MPaMax system pressure heating medium

500l/hMin flow70°CMax HM temp

Pipe connectionsint.G25Heating medium, CU pipeint.G25Hot water connectionint.G25Cold water connectionint.G25Heat pump connections

Miscellaneous

Indoor module22.8lVolume loop500lVolume, total indoor module80lVolume buffer vessel2lVolume, solar coil

1.0MPaCut-off pressure, loop

((10 bar)0.3 (3 bar)MPaMax permitted pressure in indoor module

Capacity hot water heating According to EN 255-3

235lTap volume 40 °C at Eco- comfort303lTap volume 40 °C at Normal comfort378lTap volume 40 °C at Lux comfort116WIdle loss according to DIN 4753-8.

Dimensions and weight760mmWidth900mmDepth

1900mmHeight2000mmRequired ceiling height240kgWeight (excl packaging)

069 400Part no.

1)Applies with an outdoor air heat pump at 7/45 °C (outdoor temperature/flow line temperature)

63Chapter 12 | Technical dataNIBE™ VVM 500

Page 66: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Electrical circuit diagram, 3 x 400V

NIBE™ VVM 500Chapter 12 | Technical data64

Page 67: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

65Chapter 12 | Technical dataNIBE™ VVM 500

Page 68: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

NIBE™ VVM 500Chapter 12 | Technical data66

Page 69: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

67Chapter 12 | Technical dataNIBE™ VVM 500

Page 70: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

NIBE™ VVM 500Chapter 12 | Technical data68

Page 71: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

Item register

AAccessibility, electrical connection, 18Accessories, 60Alarm, 58Assembly, 5

BBack button, 30

CCable lock, 19Commissioning and adjusting, 27

Commissioning without heat pump, 29Filling and venting, 27Post-adjustment, venting, 29Preparations, 27Start guide, 28Start-up and inspection, 28

Commissioning without heat pump, 29Connecting accessories, 26Connecting ACS 310, 16Connecting cold and hot water, 15, 17Connecting current sensors, 23Connecting hot water circulation, 16Connecting pool, 17Connecting the climate system, 15Connecting to heat pump, 15Connection as electric boiler, 15Connection of external heat source, 16Connections, 20Contact for activation of “external adjustment", 24Contact for activation of “temporary lux", 24Contact for external tariff blocking, 23Contact information, 4Control, 30, 34

Control - Introduction, 30Control - Menus, 34

Control - Introduction, 30Display unit, 30Menu system, 31

Control knob, 30Control - Menus, 34

Menu 1 - INDOOR CLIMATE, 34Menu 2 - HOT WATER, 40Menu 3 - INFO, 42Menu 4 - MY SYSTEM, 43Menu 5 - SERVICE, 49

DDelivery and handling, 5

Assembly, 5Installation area, 5Removing the covers, 7Supplied components, 6Transport, 5

Dimensions and pipe connections, 11Dimensions and setting-out coordinates, 61Display, 30Display unit, 30

Back button, 30Control knob, 30Display, 30OK button, 30Status lamp, 30Switch, 30

Disturbances in comfort, 58Alarm, 58Manage alarm, 58Troubleshooting, 58

Draining the climate system, 55Draining the hot water heater, 55

EElectrical addition - maximum output, 22

Power steps of the immersion heater, 22Electrical circuit diagram, 3 x 400 V, 64Electrical connections, 18

Accessibility, electrical connection, 18Cable lock, 19Connecting accessories, 26Connections, 20Electrical addition - maximum output, 22External connection options, 23General, 18Load monitor, 23Miniature circuit-breaker, 18Outdoor sensor, 20Power connection, 20Removing the cover, base board, 19Removing the cover, immersion heater circuit board, 19Removing the hatch, input circuit board, 19Room sensor, 21Settings, 22Temperature limiter, 18

External connection options, 23Contact for activation of “external adjustment", 24Contact for activation of “temporary lux", 24Contact for external tariff blocking, 23Possible selection for AUX inputs, 23Possible selection for AUX output (potential free variable re-lay), 25Switch for external blocking of heating, 24

FFilling and venting, 27

Filling the climate system, 27Filling the hot water coil, 27Venting the climate system, 27

Filling the climate system, 27Filling the hot water coil, 27

HHelp menu, 28, 33Hot water capacity, 62

IImportant information, 2

Safety information, 2Indoor module's design, 8

Component locations, 8List of components, 9

Initial pressure, 10Inspection of the installation, 3Installation alternative, 14

Connecting ACS 310, 16Connecting cold and hot water, 15, 17Connecting hot water circulation, 16Connecting pool, 17Connecting the climate system, 15Connecting to heat pump, 15Connection as electric boiler, 15Connection of external heat source, 16Extra hot water heaters, 14Two or more climate systems, 16Water heater with immersion heater, 14Water heater without immersion heater, 14

Installation area, 5

69Chapter 13 | Item registerNIBE™ VVM 500

13 Item register

Page 72: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

MManage alarm, 58Marking, 2Menu 1 - INDOOR CLIMATE, 34Menu 2 - HOT WATER, 40Menu 3 - INFO, 42Menu 4 - MY SYSTEM, 43Menu 5 - SERVICE, 49Menu system, 31

Help menu, 28, 33Operation, 32Scroll through the windows, 33Selecting menu, 32Selecting options, 32Setting a value, 32Use the virtual keyboard, 33

Miniature circuit-breaker, 18

OOK button, 30Operation, 32Outdoor sensor, 20

PPipe connections, 10

Dimensions and pipe connections, 11General pipe connections, 10Installation alternative, 14Maximum boiler and radiator volumes, 10Symbol key, 11System diagram, 10

Possible selection for AUX inputs, 23Possible selection for AUX output (potential free variable relay), 25Post-adjustment, venting, 29Power connection, 20Preparations, 27Pump speed, 29

RRemoving the cover, base board, 19Removing the cover, immersion heater circuit board, 19Removing the covers, 7Removing the hatch, input circuit board, 19Room sensor, 21

SSafety information, 2

Contact information, 4Inspection of the installation, 3Marking, 2Serial number, 2

Symbols, 2Scroll through the windows, 33Selecting menu, 32Selecting options, 32Serial number, 2Service, 55

Service actions, 55Service actions, 55

Draining the climate system, 55Draining the hot water heater, 55Standby mode, 55Temperature sensor data, 55USB service outlet, 55

Setting a value, 32Settings, 22

Emergency mode, 22Standby mode, 22, 55

Power in emergency mode, 22Start guide, 28Start-up and inspection, 28

Pump speed, 29Status lamp, 30Supplied components, 6Switch, 30Switch for external blocking of heating, 24Symbol key, 11Symbols, 2System description

System diagram, 13System diagram, 10, 13

TTechnical data, 61

Dimensions and setting-out coordinates, 61Electrical circuit diagram, 3 x 400V, 64Hot water capacity, 62Technical Data, 63

Technical Data, 63Temperature limiter, 18

Resetting, 18Temperature sensor data, 55Transport, 5Troubleshooting, 58Two or more climate systems, 16

UUSB service outlet, 55Use the virtual keyboard, 33

VVenting the climate system, 27

NIBE™ VVM 500Chapter 13 | Item register70

Page 73: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith
Page 74: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith
Page 75: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith
Page 76: Installer manual - nibeenergysystems.lt · standard IEC 81346-1 and 81346-2. NIBE™ VVM 500 Chapter 3 | Indoor module's design 9. General pipe connections Pipeinstallationmustbecarriedoutinaccordancewith

031991

NIBE AB Sweden Hannabadsvägen 5Box 14 SE-285 21 [email protected]