Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for ....

82
Installation Instruction Transit Time Sensors ® Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 1 Installation Instruction for Transit Time Sensors (Original Installation Instruction – German) NIVUS GmbH Im Taele 2 D – 75031 Eppingen , Germany Tel. +49 (0) 72 62 / 91 91 - 0 Fax +49 (0) 72 62 / 91 91 - 999 E-Mail: [email protected] Internet: www.nivus.com

Transcript of Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for ....

Page 1: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 1

Installation Instruction for Transit Time Sensors

(Original Installation Instruction – German)

NIVUS GmbH Im Taele 2 D – 75031 Eppingen , Germany Tel. +49 (0) 72 62 / 91 91 - 0 Fax +49 (0) 72 62 / 91 91 - 999 E-Mail: [email protected] Internet: www.nivus.com

Page 2: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Branch Offices

Page 2

NIVUS AG Hauptstrasse 49 8750 Glarus, Switzerland Phone: +41 (0)55 6452066 Fax: +41 (0)55 6452014 E-Mail: [email protected] Internet: www.nivus.com NIVUS Austria Mühlbergstraße 33B 3382 Loosdorf, Austria Phone: +43 (2754) 567 63 21 Fax: +43 (2754) 567 63 20 E-Mail: [email protected] Internet: www.nivus.com NIVUS France 14, rue de la Paix 67770 Sessenheim, France Phone: +33 (0)3 88071696 Fax: +33 (0)3 88071697 E-Mail: [email protected] Internet: www.nivus.com NIVUS U.K. Wedgewood Rugby Road Weston under Wetherley Royal Leamington Spa CV33 9BW, Warwickshire Phone: +44 (0)1926 632470 E-Mail: [email protected] Internet: www.nivus.com NIVUS U.K. 1 Arisaig Close Eaglescliffe Stockton on Tees Cleveland, TS16 9EY Phone: +44 (0)1642 659294 E-Mail: [email protected] Internet: www.nivus.com

NIVUS Sp. z o.o. ul. Hutnicza 3 / B-18 81-212 Gdynia, Poland Phone: +48 (0) 58 7602015 Fax: +48 (0) 58 7602014 E-Mail: [email protected] Internet: www.nivus.pl NIVUS Middle East (FZE) Building Q 1-1 ap. 055 P.O. Box: 9217 Sharjah Airport International Free Zone Phone: +971 6 55 78 224 Fax: +971 6 55 78 225 E-Mail: [email protected] Internet: www.nivus.com NIVUS Korea Co. Ltd. #411 EZEN Techno Zone, 1L EB Yangchon Industrial Complex, Gimpo-Si Gyeonggi-Do 415-843, Phone: +82 31 999 5920 Fax. +82 31 999 5923 E-Mail: [email protected] Internet: www.nivus.com

Page 3: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 3

Translation If the device is sold to a country in the European Economic Area (EEA) this instruction handbook must be translated into the language of the country in which the device is to be used. Should the translated text be unclear, the original instruction handbook (German) must be consulted or the manufacturer contacted for clarifica-tion. Copyright No part of this publication may be reproduced, transmitted, sold or dis-closed without prior permission. Damages will be claimed for violations. All rights reserved. Names The use of general descriptive names, trade names, trademarks and the like in this handbook does not entitle the reader to assume they may be used freely by everyone. They are often protected registered trademarks even if not marked as such.

Page 4: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 4 Transit Time Sensors - Rev. 00 as of 23.01.2013

1 Contents 1.1 Table of Contents

1 Contents ............................................................................... 4

1.1 Table of Contents .......................................................................... 4 2 Sensor Overview.................................................................. 6

3 General Notes on Safety and Danger ................................. 7

3.1 Danger Notes ................................................................................ 7 3.1.1 Special Danger Notes ................................................................... 7 3.2 Markings ........................................................................................ 7 3.3 User’s Responsibilities .................................................................. 8

4 Installation and Fastening of the Sensors ......................... 9

4.1 General Rules for Sensor Fastening ............................................. 9 4.2 Choosing Calming Sections ....................................................... 10 4.2.1 General Notes ............................................................................. 10 4.2.2 Conditions in closed Pipes and Channels ................................... 11 4.2.3 Conditions in waters and open channels .................................... 11 4.2.4 Influence to the flow velocity measurement ................................ 11 4.2.5 Sensors in partial filling ............................................................... 14 4.2.6 Sensors in full Pipes .................................................................... 17 4.3 Sensor Installation and positioning ............................................. 19 4.3.1 General Notes ............................................................................. 19 4.3.2 Allocation of the sensors ............................................................. 20 4.3.3 Possibilities of the System Configuration .................................... 22 4.3.4 Calculation of Minimum Water depth of the Application ............. 25 4.3.5 Rod sensors type NOS................................................................ 26 4.3.6 Hemisphere sensor type Typ NOS ............................................. 30 4.3.7 Wedge sensor type NIS .............................................................. 30 4.3.8 Pipe sensors type NIS ................................................................. 34 4.3.9 Screw-in and plug-in sensors type NOS ..................................... 47 4.3.10 Clamp-On Sensors type NIC0 ..................................................... 55 4.4 Sensor Alignment ........................................................................ 59 4.4.1 General ........................................................................................ 59 4.4.2 Rod Sensors ................................................................................ 62 4.4.3 Wedge Sensors ........................................................................... 62 4.4.4 Hemisphere ................................................................................. 63 4.4.5 Pipe sensors, screw-in and plug-in sensors ............................... 63

5 Accessories and Installation Aid...................................... 64

5.1 Holder bracket for rod sensors .................................................... 64 5.2 Protective sheet for Rod sensors ................................................ 67 5.3 Protective sheet for Hemisphere sensors ................................... 68 5.4 Welding Nozzle ........................................................................... 69 5.5 Tapping Saddle ........................................................................... 70 5.6 Stop ball valve ............................................................................. 75 5.7 Drill Bit and Extension ................................................................. 77 5.8 Cable Cover ................................................................................ 78 5.9 Rail system for Clamp on sensors .............................................. 79

Page 5: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 5

6 Table of Pictures ................................................................ 80

7 References ......................................................................... 81

8 Index ................................................................................... 82

Page 6: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction

Transit Time Sensors

page 6 Transit Time Sensors - Rev. 00 as of 23.01.2013

2 Sensor Overview

This installation instruction is an addendum to the Instruction Manuals of the re-

spective flow measurement transmitters or sensors. It solely relates to the

mounting of the sensors and cable layout. Following sensors are described:

− NIS Wedge and Pipe sensor (NivuSonic)

− NOS Rod and Hemisphere sensors (NivuChannel)

− NOS Screw-in and Plug-in sensors (NivuChannel)

− NIC0 Clamp-on Sensors (NivuSonic CO, PCO)

Please find connection drawings as well as specifications and Declarations of

Conformity of sensors and transmitters in the respective instruction manuals.

1 2 3 4

5

6

8

7

9

1 Pipe sensor type NIS-V200RS

2 Screw-in sensor type NOS-V2E00

3 Plug-in sensor type NOS-V2S00

4 Hemisphere sensor with 40 mm CFK sensor face, type NOS-V30BX incl. holder bracket

5 Rod sensor with 65 mm CFK sensor face (200 KHz), type NOS-V40

6 Wedge sensor type NIS-V300KS

7 Clamp-on sensor pair type NIC0

8 Rod sensor with 20 mm CFK sensor face, type NOS-V20 with extension

9 Rod sensor with 40 mm CFK sensor face, type NOS-V30

Fig. 2-1 Sensor overview

Page 7: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 7

3 General Notes on Safety and Danger 3.1 Danger Notes

Cautions are framed and labelled with a warning triangle.

Notes are framed and labelled with a “hand“.

Danger by electric voltage is framed and labelled with the Symbol on the left.

Warnings are framed and labelled with a “STOP“-sign.

3.1.1 Special Danger Notes

Auf Grund der häufigen Anwendung der Sensoren im Abwasserbereich, der mit gefährlichen Krankheitskeimen oder Schadstoffen belastet sein könnte; müssen beim Kontakt mit Kabeln und Sensoren entsprechend geeignete Vor-sichtsmaßnahmen getroffen werden.

3.2 Markings The safety hints on the sensor cable are part of the delivery and must not be removed due to reasons of risk prevention!

Fig. 3-1 Safety hints on the sensor cable

Page 8: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 8 Transit Time Sensors - Rev. 00 as of 23.01.2013

3.3 User’s Responsibilities

In the EEA (European Economic Area) national implementation of the frame-work directive 89/391/EEC and corresponding individual directives, in particu-lar the directive 89/655/EEC concerning the minimum safety and health re-quirements for the use of work equipment by workers at work, as amended, are to be observed and adhered to.

In Germany the Industrial Safety Ordinance must be observed.

The customer must (where necessary) obtain any local operating permits re-quired and observe the provisions contained therein. In addition to this, he must observe local laws and regulations on:

− personnel safety (accident prevention regulations)

− safety of work materials and tools (safety equipment and maintenance)

− disposal of products (laws on wastes)

− disposal of materials (laws on wastes)

− cleaning (cleansing agents and disposal)

− environmental protection.

Page 9: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 9

4 Installation and Fastening of the Sensors 4.1 General Rules for Sensor Fastening

Prior to beginning installation please necessarily read the general hints and the general rules for sensor fastening. Disregarding may result in measurement disturbances. The manufacturer explic-itly states that all permissions and process specifications shall be obtained or observed.

Measures to avert danger

Please ensure to observe all regulations regarding safety at work as well as danger due to explosive gases prior to beginning of installation works. Re-spective measures to avert danger shall be taken if required.

Norms and Standards

The knowledge of standards is an indispensable requirement for a safe and proper measurement site selection and sensor fastening in waters or rivers.

See DIN EN-ISO 748 and DIN EN ISO 6416.

The executing company shall have extensive expertise and a sufficient back-ground on installation and commissioning of ultrasonic measurement systems in part filled applications.

In other cases either contact the NIVUS startup service or an authorised ex-pert company.

Safety Regulations at Work

Using divers can be necessary for the sensor mounting. Diving works require compliance with particular regulations on safety at work. Carefully prepare this measure and consult the respective bodies for according approvals.

A company executing installation shall have expertise as well as all valid ap-provals required for underwater installation.

Written authorisations :

Prior to the sensors installation at bridge piers, embankments, groynes etc.; at the laying of cables as well as the operation of the facilities in public waters, a written authorisation from the competent authority must be obtained.

The sensors shall be durably and reliably fastened in a way that the flow velocity sensor faces of each path are aligned to be exactly facing each other. Use only non-corrosive fastening material!

Page 10: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 10 Transit Time Sensors - Rev. 00 as of 23.01.2013

The optional fastening material is designed for normal flow conditions at the measurement place. In water bodies or channels featuring very high flow veloci-ties the applicable conditions vary. In such cases the fastening material shall be chosen to remain intact even under the mechanical stress prevailing at the measurement point. To mechanically protect the sensors in case of increased stress additional pro-tection against flow upstream of the sensors or recessed sensor installation shall be considered. The construction for sensor fastening should ensure the following points:

− the horizontal level adjustment must be independent from the vertical level adjustment

− during alignment ensure proper indication of direction with a max. permissi-ble deviation of ±1° above the water surface (e.g. by using a portable in-strument)

− easy removal of sensors for maintenance or cleaning, no divers or special equipment should be required if possible. Realignment after maintenance shall be avoided if possible.

4.2 Choosing Calming Sections 4.2.1 General Notes

Clear and defined hydraulic conditions are indispensable prerequisites for accu-rate measurements. This is why one has to be especially attentive to the re-quired hydraulic calming sections.

− If measuring in open channels and rivers please observe that measurement places should have a defined wetted cross-sectional area and a well formed flow profile with a constant flow velocity. The measurement place generally should be such to comply with DIN EN-ISO 748, DIN EN ISO 6416 and the German Level Rule Appendix D.

− Strictly avoid falls, steps or obstructions, fittings, changes of the channel pro-files or supplies from the side upstream as well as downstream of the mea-surement point!

The drawings Fig. 4-7 to Fig. 4-11 give an example of appropriate, ill-suited and problematic applications. In case of being uncertain regarding choice or as-sessment of planned measurement sections please send your drawings/photos and the completed questionnaire to your NIVUS representative or the flow de-partment ([email protected]) at NIVUS GmbH in Eppingen.

Page 11: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 11

4.2.2 Conditions in closed Pipes and Channels

− When measuring in pipes the measurement sections have to be selected in a way that there is no sedimentation (sand, grit, sludge) arising under stand-ard operating conditions.

− As from a filling level of approx. 80 % of the nominal diameter closed pipes are tending to sudden short-term impoundage. To avoid pulsation within the measurement section due to that circumstance construct the required diame-ter in a way that the filling level never exceeds 80 % independent from Qmin or Qmax in case of standard discharge (2 QTW)..

− Avoid changes of slopes within the measurement section.

− The length of the approach channel must be min. 5x nominal diameter, the length of the discharge channel must be min. 2x nominal diameter. Longer sections may be required however in case of disturbed hydraulic conditions and distorted flow profiles resulting from these conditions.

4.2.3 Conditions in waters and open channels In waters the following criteria must be respected:

− The water bed shall be stable and shall be free of sedimentation or scour holes

− The bank should have a definite shape and a stable formation and do not have a disposition to changes

− There should be no weeds, stones, piles, steps, sills or similar within the measurement path

− Do not position the measurement place below cooling water inlets or inlets from oxbow lakes (temperature gradient)

− Silt, sludge or sedimentation being disposed must not disturb the ultrasonic path.

4.2.4 Influence to the flow velocity measurement Suspended particles If an ultrasonic signal transmitted through the water a part of the ultrasonic wave’s energy is lost and the signal is attenuated. A result of this attenuation is a drop of intensity compared to the original signal. The measurement may fail If this signal attenuation becomes too high. There are two reasons for the attenuation of the ultrasonic waves: Friction: Transformation of acoustic energy to frictional heat as a result of water viscosity. Stray: When impinging on a solid particle (suspended solid) in water a part of the acoustic energy is scattered.

Page 12: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 12 Transit Time Sensors - Rev. 00 as of 23.01.2013

1

2

3

1 Sent signal 2 Scattering by particles 3 Subdued/attenuated signal

Fig. 4-1 Signal attenuation by suspended particles

Air bubbles Air bubbles e.g. intrude into water below weirs with free overfall. Plants produc-ing oxygen or biogas rising from the water bed will attenuate the acoustic signal. In case of high solar irradiation the measurement due to biologic oxygen may be disturbed in a way that the measurement fails during daytime and resumes after sunset. A ship’s propeller wash will interrupt the propagation of sound as well by bringing air bubbles into the water. Temperature and salt content The sound velocity in water will vary depending on density variations caused by the gradients of temperature or salt content. High temperature differences be-tween water and air will cause an exchange of energy at the water surface. This generates a temperature gradient in the water, deflecting the acoustic signal from its normal horizontal path. In the worst case the deflection prevents the sig-nal from reaching the receiving sensor. There may be similar effects caused by the salt content gradient.

Fig. 4-2 No vertical density difference of the signal

Changes in temperature of 1 °C/m or more can be found mostly at the water sur-face of slowly moving waters reaching to a depth of approx. 0.5 m. Temperature changes in the water layers situated below are lower.

Page 13: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 13

Fig. 4-3 Significant vertical density difference caused by solar irradia-tion

Fig. 4-4 Extreme vertical density difference caused by solar irradiation

Changes in temperature are of importance, among other things, at cooling water inlet as well as places where much warmer water flows from cutting off mean-ders of rivers.

1

1 Flow direction

Fig. 4-5 Significant vertical density difference caused by solar irradia-tion

Page 14: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 14 Transit Time Sensors - Rev. 00 as of 23.01.2013

1

2

KALT / cold

WARM

3

3

1 Flow direction 2 Temperature gradient 3 Converter (sensors)

Fig. 4-6 Horizontal density difference caused by discharge of hot water

4.2.5 Sensors in partial filling

These examples apply for rod sensors, hemispheres or wedge sensors.

α

DN

L

v <1 m/s v >1 m/s α <15° L > min. 3 x DN L > min. 5 x DN α <45° L > min. 5 x DN L > min. 10 x DN α <90° L > min. 10 x DN L > min. 15-20 x DN

Fig. 4-7 Sensor position behind curves or elbows

Page 15: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 15

= Error! Indefinable flow conditions = Sufficient distance to obtain straight flow (10 ... 50 x diameter depending on application)

Fig. 4-8 Measuring behind fall – turbulence

= Error! Alternation of slope = alternation of flow profile

= Distance depending on slope and flow velocity value l = min. 20 x diameter

Fig. 4-9 Error caused by alternation of slope

Page 16: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 16 Transit Time Sensors - Rev. 00 as of 23.01.2013

l

h

= Error! Transition from flowing to shooting Faulty level and velocity measurement

? = Critical measurement point, not recommended! Begin of sinking flow

= Distance l = min. 5 x hmax at place of installation

Fig. 4-10 Error caused by alternation of flow profile in front of slope al-ternation or fall

l1 l2

2

1

(1) = Fixtures (such as samplers or similar)

(2) = Obstruction

Hmax = max. level/height

= Error caused by vortex formation!

= Distance l1 (upstream of obstruction) = min. 5 x hmax Distance l2 (downstream of obstruction) = min. 10 x hmax in case of flow velocities >1 m/s

Fig. 4-11 Errors caused by fixtures or obstructions (top view)

Page 17: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 17

4.2.6 Sensors in full Pipes These installation suggestions are valid for the sensor types NOS-V2E, NOS-V2S, NIS-V200 and NIC0.

h < 5% of DN L > min. 3x DN h > 5% of DN L > min. 5x DN h > 30% of DN L > min. 10x DN

Fig. 4-12 Sensor position after change of profile (side view)

In case of horizontally laid pipes avoid pipe top and pipe bottom as mounting place (risk of soiling or air bubbles resulting in measurement failure). NIVUS recommends a mounting position of -45° ... +45° to the horizontal.

X

X

X+45°+45°

-45°-45°X

1

2

90°

X = Recommended sensor installation positions 1 = Risk of air-bubbles 2 = Risk of sludge deposits

Fig. 4-13 Recommended installation angles

Page 18: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 18 Transit Time Sensors - Rev. 00 as of 23.01.2013

At pipes laid vertically the danger of swamping / air does not appear in which case any arbitrary mounting place for the sensor can be selected. A correct and reliable measurement can be performed only in full filled pipes. For this reason do not install measurements in downpipes or at the highest point of the pipeline Fig. 4-14).

3

4

1

2

X

X

X+45°+45°

-45°-45°X

90°

1 = recommended range in almost horizontal position (sensor can be installed on the side) 2 = recommended range in vertical pipe 3 = not recommended due to part filling/idling 4 = measuring impossible due to idling

Fig. 4-14 Comparison of installation places

In case of planning measurements in horizontal pipelines we recommend to consider a slightly inclined section or an inverted siphon (sensor installation as depicted in Fig. 4-15).

X

X

X+45°+45°

-45°-45°X

90°

Fig. 4-15 Horizontal pipe with inverted siphon

Page 19: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 19

Shut-off valves and control fittings shall be installed always downstream of flow velocity sensors.

mind. 3 x DN

X

X

X+45°+45°

-45°-45°X

90°

Fig. 4-16 Using shut-off valves and control fittings

Never install sensors on vibrating pipe lines since this may result in measure-ment errors!

4.3 Sensor Installation and positioning 4.3.1 General Notes

Prior to beginning installation please necessarily verify compliance with regu-lations on safety at work.

To avoid disturbances from electrical interferences, the sensor cable must not be laid close to engine (motor) lines or main power lines.

The installation of sensors in open channels or water bodies always requires previous planning. A measuring point inspection is required. Mounting options might be very individual.

Both sensors of each path must be mounted according to the geometry and must be aligned to face each other. Use optical aids to achieve this (laser dis-tance meter or similar) (see chapter 4.4).

High accurate, vibration-free and firm installation and sensor alignment are necessarily required to ensure the measurement to operate properly!

Page 20: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 20 Transit Time Sensors - Rev. 00 as of 23.01.2013

4.3.2 Allocation of the sensors There are additional markings on the sensor cables to assign the sensors cor-rectly.

Each sensor pair is adjusted to each other by default and hence always shall be installed as a pair within the path.

The sensors must not be interchanged! The sensors can be connected directly to the transmitter if the measurement does not require more than two paths. The designations are G, F, E, D.

Designation on the sensor Sensor type

G Sensor 1 (path 1)

F Sensor 2 (path 1)

E Sensor 1 (path 2)

D Sensor 2 (path 2)

F

G E

D

Fig. 4-17 Sensor assignment to the transducer

Page 21: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 21

The sensors are designated with numbers in case of connecting via adapter box: 1.1 and 1.2, 2.1 and 2.2, 3.1 and 3.2, 4.1 and 4.2 ...etc.

Designation on the sensor Sensor type

1.1 Sensor 1 (path 1)

1.2 Sensor 2 (path 1)

2.1 Sensor 1 (path 2)

2.2 Sensor 2 (path 2)

3.1 Sensor 1 (path 3)

3.2 Sensor 2 (path 3)

4.1 Sensor 1 (path 4)

4.2 Sensor 2 (path 4)

3.2

3.1 4.1

4.21.2

1.1 2.1

2.2

Fig. 4-18 Sensor allocation to the adapter box

Page 22: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction

Transit Time Sensors

page 22 Transit Time Sensors - Rev. 00 as of 23.01.2013

4.3.3 Possibilities of the System Configuration

The arrangement of the sensors is dependent on the hydraulic conditions, water

body geometry and the infrastructure of the respective measurement place as

well as the accuracy of measurement.

Single path system

The most simple ultrasonic sensor arrangement consists of two hydro-acoustic

sensors facing each other diagonally. A prerequisite is that the flow is running

parallel to the banks.

Such prerequisites can be mostly found in channels and canal-like straightened

courses of flowing waters.

1

2

Fig. 4-19 Single path system

The sensors operate alternately as transmitter and receiver. The transmission

direction of the ultrasonic signal is 1-2 in flow direction or 2-1 towards the flow di-

rection.

Page 23: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction

Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 23

Multi path system (crossed paths)

In natural waters the main flow direction only occasionally is parallel to the

banks. Bends and curves within the watercourse sustainably influence the main

flow direction at varying flow levels.

In such cases two measurement paths are arranged crosswise, where the se-

cond path is used to additionally calculate the angle between the main flow di-

rection and one of the banks.

1

2

3

4

Fig. 4-20 Multi path system (crossed paths)

This arrangement alternately measures the transit time within the measurement

paths 1-2 and 3-4.

Multi-layer system

In measurement sections featuring extremely fluctuating water levels or exten-

sive geometries (divided cross sections) it is recommended to use multiple lay-

ers.

4 3

2 1

Fig. 4-21 Multi-layer system

Each layer can be configured as single path or multi path measurement.

As soon as the entire cross-sectional area is detected by using an appropriate

number of measurement paths arranged above each other, the hydrometric cali-

bration as base for flow measurement can be neglected since the flow profile is

known properly thanks to using multiple layers for measuring.

Page 24: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 24 Transit Time Sensors - Rev. 00 as of 23.01.2013

The highest accuracy can be achieved by using a crosswise multi-layer ar-rangement since this configurations reduces the influence of uncertainties re-garding the main flow direction and the flow profile on the result of the calcula-tion.

D Inner diameter / channel width

Fig. 4-22 General path positioning, 2-path measuring

Page 25: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 25

4.3.4 Calculation of Minimum Water depth of the Application The channel or the water body must have a minimum water depth in order to eliminate errors caused by reflections of the ultrasonic signal at the water sur-face. This factor can be calculated by using the formula below:

fLD 27min =

Dmin: Minimum water depth above the path and minimum distance between channel bottom and path - each in meters

− L: the path length in meter

− f: the converter frequency in Hertz

1

2

L

Fig. 4-23 graphical representation path length

Dmin

Dmin

Fig. 4-24 graphical representation Minimum water depth

Page 26: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 26 Transit Time Sensors - Rev. 00 as of 23.01.2013

Examples of the minimum water level for different converter frequencies and path lengths.

path length L (m) Converter frequency F (kHz)

minimum depth above and below the path

Dmin (m) 1 1000 0,03 3 1000 0,045

10 200 0,19 30 200 0,33 50 200 0,43 100 200 0,60

Similar restrictions are valid for very smooth water beds which rather reflect than absorb the acoustic signal. Frequencies of NIVUS-Sensors:

− 1000 kHz: NOS-V2, NOS-V3, NIS

− 200 kHz: NOS-V4

4.3.5 Rod sensors type NOS Install the holder bracket for the tube holder (stainless steel tube) of the sensor head horizontally or vertically above the water surface (NIVUS recommends to use wedge anchors and key screws with M12 metric thread). It is necessarily re-quired to install the holder bracket in a way which enables to accurately adjust the sensors to one another after installation (recommended angle 45° horizontal-ly). This can be achieved by visible adjustment and by analysing the impulse signal. Adjust the sensor faces (carbon surfaces) exactly to one another since other-wise measurement is not guaranteed to operate without any problems. Please carefully check the sensor positions. Since sensor installation on measurement places extremely depends on local conditions it is necessary to let trained expert personnel choose sensor type as well as installation method prior to installation. For installation of rod sensors on vertical water embankments or channel walls we recommend to use the NIVUS sensor holder for vertical or horizontal sensor adjustment type NOZ00HAL0 or NOZ00HAL90. In case of expecting heavy flow conditions we recommend to install a flow-optimised baffle plate (see accessories list) at the sensor holder. This may avoid sensor vibration as well as damage caused by debris/flotsam or similar.

Page 27: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 27

Fig. 4-25 Fixing the angle bracket on a wall

Fig. 4-26 Fixing the wall mount on a straight wall

Page 28: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 28 Transit Time Sensors - Rev. 00 as of 23.01.2013

45° 45° 45° 45°

45° 45° 45° 45°

L1L1

L11

1 Flow direction L1 Channel width complies with sensor distance

Fig. 4-27 Installation example Rod sensors 2 levels/4 paths (top view)

hmax

hmin

L1L1

1

1 Flow direction L1 Channel width complies with sensor distance at 45° mounting angle

Fig. 4-28 Installation example Rod sensors 2 levels/4 paths (side view)

Page 29: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 29

Positioning the measurement paths in different levels depends on the main measurement task. Example: minimum, average and maximum discharge. To determine the level positions please refer to the directives contained in DIN 6416 or contact NIVUS.

1 bottom path(s) / 40 % of haverage 2 upper path(s) / 80 % of haverage

Fig. 4-29 Allocation of level when measuring average discharge

Page 30: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 30 Transit Time Sensors - Rev. 00 as of 23.01.2013

4.3.6 Hemisphere sensor type NOS Holder bracket for hemisphere type NOZ00HALHK for the flow velocity sensor type NOS has been designed for use on vertical and non-vertical water body boundaries (slopes or similar). It allows to adjust angles in two different levels which enables to adjust sensors to one another. Its shape has almost no effect on the flow behaviour and helps to avoid the risk of build-up caused by debris or solids (such as algae, leafs, foliage, grass or similar). To connect the sensors use the optional underwater plug connectors (NOS sen-sor connection A or B). These connectors can be used up to 12 m water column. After installation visibly align the hemisphere sensors as depicted below (see chapter 4.4)

Fig. 4-30 Installation example hemisphere sensors 2 layers/ 2 paths

4.3.7 Wedge sensor type NIS To install the wedge sensor on the channel wall 4 stainless steel screws with a countersunk head (size M5, length 30-70 mm; 1.18-2.76 in) as well as the ac-companying dowels are required. Choose the screw length in a way that safe and durable sensor fastening is en-sured under any operational conditions. In order to reduce vorticity formation or the risk of build-up use well-fitting coun-ter-sunk screws and screw them into the mounting plate completely. NIVUS does not recommend the use of stud bolts or similar.

Fastening elements for wedge sensors should be as flush as possible with the mounting plate. There is a risk of build-up due to grass, algae or similar and hence the risk of measurement failure if any screws or other fastening parts should extend into the measurement medium. This can cause disturbances or may lead to measurement failures.

The sensor pairs of each path must be fastened according to the geometry and shall be aligned facing each other. For direction finding of signals optical aids such as Laser distance meter can be used (see chapter 4.4).

Page 31: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 31

To reduce the risk of build-up the wedge sensor has been optimised for flow conditions. Nevertheless there may be a certain kind of risk of build-up on the sensor mounting plate. This is the reason why there is no gap allowed to be left between sensor mounting plate and channel bottom! Any gap or seam which might have been emerged in the area around the sensor tip due to installation has to be sealed with silicone or similar material.

For sensor installation on the channel bottom the ground has to be absolutely flat (plane surface)! Otherwise the sensor may break and leak (water is leak-ing into electronic components causing irreversible damage).

Do not deform the ground plate neither during installation nor dismantling. Never enlarge installation boreholes.

Always use an appropriate screwdriver for sensor dismantling. Never use prybars, chisels, hammers, levers, crowbars, hammer drills or similar tools.

It is not allowed to use any kind of force during dismantling procedures.

Removing or loosening ground plate and/or cable glands on the sensor results in leakage and causes a failure in the measurement / the sensor.

No sensor parts are allowed to be removed on principle! The sensor cable must be laid on the channel ground from behind the wedge sensor to the channel wall. In order to avoid the risk of build-up cover the cable with a thin stainless steel sheet or lays it into a slot which has to be sealed with permanently elastic material subsequently. It is also allowed to lay the cables in armoured conduits and similar robust cable protection systems. Appropriate covers are available from NIVUS.

1 2 32 245

1 Stainless steel sheet/cable cover, e.g. type ZMS 140 2 Cable 3 Permanently elastic material (silicone or similar) 4 Empty conduit 5 Pipe clamp

Fig. 4-31 Installation suggestion for cable extension

Never run the cable slackly, uncovered or across the medium! Risk of build-up, sensor or cable tear-off!

Page 32: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 32 Transit Time Sensors - Rev. 00 as of 23.01.2013

1

1 Protective cover

Fig. 4-32 Hints on cable layout

The minimum bending radius of the standard signal cable is 10 cm (3.94 in). Smaller radii may result in cable break!

Do not lay the sensor cable close (or parallel) to motor power supply lines and power lines in order to avoid disturbances caused by electric interference.

Example of a 2-path measurement in permanent filled pipe.

45°

60°

Fig. 4-33 2-path measuring in full pipe using wedge sensors

Page 33: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 33

Example of a 2-path measurement in part filled pipes.

1 path

2 path2000

500

NIS Gwedge sensor

NIS Ewedge sensorNIS wedge sensor D

NIS Fwedge sensorwedge base wedge base

1 path 1 2 path 2 3 mounting wedge 4 pair of sensors 1st path 5 pair of sensors 2nd path

Fig. 4-34 2-path measuring in part filled pipe with wedge sensors

30°

30°

Fig. 4-35 Top view of figure 4-34

Page 34: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 34 Transit Time Sensors - Rev. 00 as of 23.01.2013

4.3.8 Pipe sensors type NIS The sensors have to be fastened hard and tight in a way that the bevelled side of the sensor 1 with its integrated flow velocity sensor must “look“ (face) against the flow direction of the medium. The installation aid (see Fig. 5-19) shall look towards the flow direction. The flow velocity sensor integrated in sensor 2 must exact look towards sensor 1 in flow direction. Use only non-corrosive fastening material! The pipe sensors type NIS are to be screwed tightly into the 1½“ nozzle by using a gasket ring and the retaining element (additional option: ball valve for removal without pressure). It is important that the horizontal part of the sensor is installed flush with the pipe wall.

Correct installation Error: faulty measurement values

If nozzles should not be posi-tioned exactly (installation slight-ly too narrow) this can be com-pensated by inserting the sen-

sors a bit deeper.

Fig. 4-36 Hints on pipe sensor installation

NIS sensors generally are suitable for 1-path and 2-path applications only. In full pipes always direct the measurement path(s) across the center of the pipe.

Page 35: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 35

2

1

1 Sensor face towards the flow direction - sensor 2 2 Sensor face in flow direction - sensor 1

Fig. 4-37 Hints on pipe sensor installation

Please note whilst installation in pipes: - Weld on the 1½“ nozzle in an angle of 90°. - Place the pipe sensors in a way that the bevelled side of sensor 1 is

looking exactly towards the flow direction. Sensor 2 must be aligned in flow direction and towards sensor 1.

The sensor block must be welded, depending on material (steel, stainless steel 1.4571); be glued on (PVC); welded on (HDPE) or laminated (PVC). For upgrading purposes we recommend to use a tapping saddle (see chapter 5.5). If using cast or concrete pipes it is possible to screw a steel or stainless steel clamp with weld-on nozzle and sealing onto the pipe. If in doubt please contact the pipe manufacturer in order to install the sensor nozzles. In order to drill into steel or stainless steel pipelines, NIVUS recom-mend to use a carbide hole cutter with a diameter of 38 mm and a low-speed drilling machine with friction clutch. We furthermore recommend to additionally use cutting paste for drill bit cooling.

Please check the maximum possible wall strength of the pipe prior to drilling It might be necessary to use extended drill bits since standard drill bits might be too short to drill through the pipe wall.

Page 36: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 36 Transit Time Sensors - Rev. 00 as of 23.01.2013

In order to install the sensors in a concrete conduit core drills featuring a diame-ter of min. 45 mm should be available. The diamond tool used shall be cooled accordingly. Flush with a coolant to remove debris. The drilling should be carried out by an expert company. If it is necessary to drill through a ball valve use a drill bit with a diameter of 36 mm as well as the accompanying extension (see Fig. 5-21). Drill bits, extensions and cutting paste may be purchased from NIVUS if re-quired. Ideally weld, glue or laminate the welding nozzle after the hole has been drilled.

Risk of accident!

Use only in a low pressure condition depending on pipe material and wall strength. A blocking of the drill can be possible.

Do not step over the indicated drill speed!

Risk of accident!

Remember to always use a mobile safety circuit breaker in case of working in wet environs and/or drilling into filled pipes!

Please observe unobstructed removal of turnings. If necessary, interrupt drill-ing and remove turnings before proceeding. Remove burrs with a file after drilling since otherwise measurement errors might occur.

Never burn pipes with welding torches!

Weld seam burn may cause swirls and hence lead to measurement errors (see Fig. 4-38).

v

1

2

Error: faulty measurement values

1 = whirls/chips

2 = weld seam burn

Fig. 4-38 Disturbances caused by weld seam burn

Page 37: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 37

45°

L1

45°

1L1

1 = inner thread 1¼” (type NOS) or 1½” (type NIS)

2 = inside diameter complies to the sensor distance

Fig. 4-39 Example of an 1 path measuring in a pipe (side view)

1

45°

L1

L1

1 = inner thread 1¼” (type NOS) or 1½” (type NIS)

2 = inside diameter complies to the sensor distance

Fig. 4-40 Example of an 1 path measuring in a pipe (top view)

Page 38: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 38 Transit Time Sensors - Rev. 00 as of 23.01.2013

45°

L1

45°

1L1

45°

1 = inner thread 1¼” (type NOS) or 1½” (type NIS)

2 = inside diameter complies to the sensor distance

Fig. 4-41 Example of 2 path measuring in a pipe (side view)

45°

L1L1

2 = inside diameter complies to the sensor distance (x2)

Fig. 4-42 Example of a 1-path reflection measurement in a small metal pipe

When assembling the insertion sensor, a special grease paste must be used for the stainless steel couplings, specified to DIN 2353 (or equivalent).

The cap nut thread, threads and cone as well as the cutting ring of the pipe sensor type NIS must be slightly greased when pre-assembling the insertion sensor!

The screw joints are greased on delivery. Additional grease can be purchased from NIVUS.

Page 39: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 39

1 Gasket ring 2 Thread 3 Inner cone 4 Inner thread of spigot nut 5 O-Ring inside of sensor screw

connections

Fig. 4-43 Using grease on sensors type NIS

The screw joint shall be greased on all points shown in Fig. 4-43 prior to installa-tion. Install the sensor according to DIN 3859-2. Screw the screw joint into the welding nozzle, ball valve or the nozzle of the tap-ping saddle using a pipe wrench or an open-end wrench (width across flats 55 mm). Subsequently pull spigot nut and gasket ring over the flow velocity sensor and insert the sensor into the screw joint as deep as required (depending on applica-tion) (see Fig. 4-37). Afterwards put the gasket ring into the screw connection, tighten the spigot nut manually. Then (in order to be capable of controlling the number of turns) apply a marker on the spigot nut and tighten the nut by approx. 0.5 turns using an open-end spanner with a spanner width of SW 50. The retaining element is an indispensable part of the pipe sensors. It safely re-tains the sensor in position and, if installed correctly, prevents the sensor from being thrown out.

Risk of accident!

It is not allowed to operate the sensor without retaining element! The gasket ring used is merely for sealing purposes and does not have any fastening capabilities at all.

Page 40: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 40 Transit Time Sensors - Rev. 00 as of 23.01.2013

1

2

3

4

5

1 Welding nozzle 2 Stop ball valve 3 Sensor screw connection 4 Sensor retaining element 5 Installation aid (screw M4)

Fig. 4-44 Components of pipe sensor mounting

Risk of accident!

Flow velocity sensors without retaining element may detach from the screw joint and hence may be dangerous to persons as well as to parts of the facili-ty!!

Ejected sensors may cause the medium to flow out of the screw connection and flood the facility!

In order to ensure safe clamping, degrease the rear area of the pipe sensor as well as the clamping area (half-round milling groove) of the upper and lower rear clamp elements by using appropriate means. Sensor shaft and clamping area of the clamp elements must be dry.

Without degreasing and drying both components and the sensor shaft, the stiction between sensor and sensor retaining element will reduce by an un-known extent. In this case, it is no longer guaranteed to reliably secure the sensor.

The retaining element for pipe sensor as delivered by NIVUS has been tested by an independent testing laboratory using a long-term stress test applying 4 Bar constant load and 8.0 Bar impact load (30 sec.). Higher pressures can-not be compensated safely!

Page 41: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 41

The retaining element for pipe sensors consists of the parts below:

1 Upper front clamp element (1x) 2 Lower front clamp element (1x) 3 Upper rear clamp element (1x) 4 Lower rear clamp element (1x) 5 Allen® head screw M5 (2x) 6 Allen® head screw M4 (2x) 7 Welded headless screw (as additional clamp lock) 8 Allen® head screw M5 (2x) 9 Allen key® 1x 3 mm 10 Allen key® 1x 2,5 mm 11 O-Ring, spare part for sensor screw connection,

Fig. 4-45 Exploded assembly drawing of sensor retaining element

Page 42: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 42 Transit Time Sensors - Rev. 00 as of 23.01.2013

For installation proceed as follows:

1. Apply a small amount of grease to the O-ring on the inside of the sensor screw connection

Fig. 4-46 Greasing the sensor screw connection

2. Screw the sensor screw connection into the welded nozzle or into the stop ball valve.

Fig. 4-47 Fixing the sensor screw connection to the stop ball valve

Page 43: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 43

3. Put the pipe sensor in the correct position as described in Chapter 4.3.8.

Fig. 4-48 Positioning the sensor

4. Fasten the sensor by slightly tightening the union nut manually (plus ½ turn).

Fig. 4-49 Fastening the sensor

Page 44: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 44 Transit Time Sensors - Rev. 00 as of 23.01.2013

5. Screw upper and lower front clamp elements together behind the spigot nut of the sensor screw connection by using two M4 Allen® head screws (see Fig. 4-45, No. 7).

Fig. 4-50 Attaching lower front clamp element

6. Screw the upper rear clamp element (see Fig. 4-45, No. 3) to the upper front clamp element using both M5 Allen® head screws.

Fig. 4-51 Connecting upper rear and upper front clamp element

Page 45: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 45

7. Subsequently attach the lower rear clamp element to the upper rear clamp element by using the two remaining M5 Allen® head screws. Please use a minimum torque of 6 Nm to tighten the screws in order to ensure proven se-curity. Check the tightness of the complete screw joint. In case of liquids leaking under process conditions ensure proper tightening of the respective screw joints or shut down the entire facility if required and replace damaged gas-kets, Teflon tapes and similar.

Fig. 4-52 Attaching the final clamp element

8. The sensor retaining element furthermore facilitates to exactly reposition the sensors after maintenance or control measures.

9. To do this, first unscrew the spigot nut as well as both hexagon socket screws (Allen screws) M5 (see Fig. 4-51)

Fig. 4-53 Unscrewing procedure for sensor removal

Page 46: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 46 Transit Time Sensors - Rev. 00 as of 23.01.2013

10. Then remove the sensor. The screwed rear clamp elements remain in their position on the pipe sensor body.

Fig. 4-54 Removing the sensor (maintenance/control)

11. Now it is possible to clean or to inspect the sensor if necessary. The sensor can be reinserted into the screw connection again as soon has the cutting ring has been replaced. Use the rear clamp elements left on the sensor body as detent or positioning aid (see Fig. 4-51).

12. Subsequently tighten spigot nut and M5 Allen® head screws again.

Fig. 4-55 Lock the sensor again after reinstallation

Page 47: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 47

4.3.9 Screw-in and plug-in sensors type NOS Positioning of the sensors on the pipe In order to determine the pipe center it is necessary to have a spirit level with additional spacers available. Put the level onto the pipe perpendicular to the pipe run. The spacers on both sides of the spirit level shall be positioned as far as possi-ble towards the ends of the level so that the level does not touch the pipe any-more. Now only the spacers touch the pipe. Now exactly level the water level and assign the respective markings to the pipe. Use a pencil, chalk, crayon or similar. Repeat this procedure in a distance of pipe diameter x2 or x3 and connect the resulting marks. The pipe axis is located along this mark. To obtain higher accuracy the repeat the procedure described above on the other side of the pipe.

Fig. 4-56 Determining the center of the pipe

Determine the sensor positions by using a laser level such as "Lasermark Giz-mo-Lite" or similar. Position 1 (front side) Point the laser to the horizontal line (pipe center, (Fig. 4-57) and draw the verti-cal line onto the pipe. The topmost point is important to allocate the vertical line to the reverse pipe half. Position 2 (front side) Use the pipe diameter "d" as distance from position 1 to mark position 2 on the horizontal line. Here it is important as well to allocate the topmost point of the vertical line to the reverse pipe half.

Page 48: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 48 Transit Time Sensors - Rev. 00 as of 23.01.2013

d

12

3

1 Sensor position 1 2 Sensor position 2 3 Laser level

Fig. 4-57 Determining the sensor positions front side / rear side

Position 1 (reverse side) Point the laser to the previously drawn horizontal and vertical lines and draw the vertical line. Position 2 (reverse side) See Position 1. Between position 1 and Position 2 the distance "d" must be measured.

A

B

C

D

Fig. 4-58 Distances verification of the sensor positions

Page 49: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 49

The distances of the circumference between AB and CB must be identical. As soon as this should not be the case the procedure described above must be repeated. If the pipe is accessible from all sides, please additionally check whether the dis-tances between AD and CD are the same as between AB and CB. If not please repeat the measurement as described before. Positioning of a multi-path measuring inside the pipe Using a multi-path measurement featuring more than 2 paths within the pipe and multiple levels, the screw-in or plug-in sensors need to be installed in angles of 18°, 30°, 45° and 54°.

502

600

645

(54°

)

(30°

)(1

8°)

(45°

)

Fig. 4-59 Several sensor angles inside the pipe

The following example presents the different sensor distances of each path in a pipe with a diameter of 508 mm.

Page 50: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 50 Transit Time Sensors - Rev. 00 as of 23.01.2013

Fig. 4-60 Example of a multi-path measurement

When using Type NOS screw-in and plug-in sensors the same selection criteria are valid as described for Type NIS pipe sensors described in chapter 4.3.8. Type NOS screw-in and plug-in sensors are installed and adjusted by using 1¼“ nozzles. The drill hole shall not be smaller than 43 mm. It is recommended to wrap Teflon cord or Teflon tape around the sensor thread and to apply assembly paste prior to screwing in. This avoids the sensor to >corrode< into the nozzle and moreover ensures seal-ing.

Page 51: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation InstructionTransit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 51

Fig. 4-61 preparation for installing screw-in sensor

When assembling the screw-in or plug-in sensor, a special grease paste must be used for the stainless steel couplings, specified to DIN 2353 (or equiva-lent).This paste shall be used to slightly grease the thread! Additional grease can be purchased from NIVUS.

When installing the screw-in or plug-in sensors please observe that the sensors are flush with the inner pipe wall. To achieve this e.g. use a yardstick and re-spectively mark the sensor thread (see Fig. 4-62). After screwing in protect the sensor from getting loose by using a lock nut.

Do not connect the sensor before it is completely adjusted as described in Fig. 4-65.

Page 52: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 52 Transit Time Sensors - Rev. 00 as of 23.01.2013

2

1

1 Plug-in sensor with position ring (to be installed from the inside)

2 Screw-in sensor flush with inner pipe wall

Fig. 4-62 Determination of the sensor position - plug-in and screw-in sensors

Screw in the sensor all the way to the stop or to the mark and bring it into a suit-able position for radiating. Then for the time being adjust the sensor head to an approximate position in or towards the flow direction (see Fig. 4-63).

1

1 1¼“ nozzle

Fig. 4-63 Positioning the screw-in sensor

A longitudinal slot can be found on the bottom of the sensor. This slot is aligned exactly parallel to the sensor head and can be used to adjust the sensor head direction by e.g. using a soft tip marker.

Fig. 4-64 Mark the alignment aid on the screw-in sensor

Page 53: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 53

Then align the sensor head by using a lever or similar. During this procedure please observe to accurately adjust the sensors facing each other. To do so slightly loosen the lock nut again if required.

1

1 Screw nut for adjustment and fixation

Fig. 4-65 Sensor alignment; screw-in sensor

1 31 2

3 4

2

1 Screw nut for adjustment and fixation

2 Connection board

3 Cover plate

Fig. 4-66 Screwing-on the conductor barrel

Screw the conductor barrel (without lock lid) onto the sensor all the way down to the stop. Now connect the sensor cables to the connection board as depicted in Fig. 4-68.

Page 54: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

® Installation InstructionTransit Time Sensors

page 54 Transit Time Sensors - Rev. 00 as of 23.01.2013

Fig. 4-67 Cable in Sensor conductor barrel

The sensor cable is lead through the cable gland.2

1

43

Sensor -

Sensor +

connection cable -

connection cable +

Clamp 1 = Sensor + (red/black)Clamp 2 = Sensor – (black)Clamp 3 = connection cable + (silver) – to the measurement transmitter Clamp 4 = connection cable – (copper) – to the measurement transmitter

Fig. 4-68 Connection board

Then put the connection board into the conductor barrel and fasten the lock lid by using the 2 screws on the barrel (see Fig. 4-66).

Page 55: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation InstructionTransit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 55

4.3.10 Clamp-On Sensors type NIC0The Clamp-On Sensors have to be fastened hard and tight. Use only non-corrosive fastening material!To ensure proper coupling of the acoustic signal into the medium it is necessary to use appropriate acoustic coupling paste. This paste must be applied between the sensor surface and the outer pipe wall. The sensors are shipped with a tube of coupling paste.The coupling paste can be purchased from NIVUS using Art.-No. E-PMA-SILIKFE1.

Layers of paint, zinc coating, corrosion space or similar can disturb the safe sig-nal coupling and shall be removed completely using an orbital sander and sand-paper, grinding brush, grinding wheels or similar appropriate tools prior to instal-lation.Before installing the sensor, please check material and wall thickness of the pipe. The material should be cast steel, steel or stainless steel. These materials can be selected directly from the start-up menu of the NivuSonic CO measure-ment transmitter. Before starting up please check with NIVUS if other pipe materials shall be used.

Before mounting the sensors, the transmitter must be programmed to make sure that the required sensor distance, which has been calculated by the transmitter, can be considered during the initial installation (see NivuSonic CO instruction manual).

Install the first sensor in flow direction according to the respective marking (ar-rows).Apply coupling paste to the surface touching the pipe, thread the clamp band and attach the sensors on the pipe with the arrow pointing in flow direction (ac-cording to path arrangement). Please observe to have a sufficient amount of coupling paste being applied to the sensor face.

1 Directional flow arrow2 Groove slot for tensioning belt fastening

Fig. 4-69 Sensor pair (sensor A and B)

Please use the optional delivered clamp bands or the rail system of NIVUS (mounting accessory) for mounting. The rail system can be ordered with costs at NIVUS with the part number ZUB0 CORAIL.

Page 56: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction

Transit Time Sensors

page 56 Transit Time Sensors - Rev. 00 as of 23.01.2013

First measure the pipe circumference and add 30 mm. The result is the required

length of the tensioning belt (part of the standard delivery).

Fig. 4-70 shows how to put the end of the belt from above through the slot of the

turnbuckle. Then bend the tensioning belt backwards by 30 mm at least (shorter

bends may not prevent the belt from slipping out when tightening the turnbuck-

le).

Fig. 4-70 Hook the clamp band into the lock

Apply coupling paste onto the sensor area touching the pipe. Put the tensioning

belt through the slot on the top of the sensor in a way that the arrow on the sen-

sor top is looking in the flow direction (see Fig. 4-69).

Now put the second end of the belt from above through the slot of the perforated

part of the turnbuckle and bend it backwards by approx. 30 mm as well (see

previous section).

Then put the belt around the pipe and lock the turnbuckle.

Page 57: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 57

Fig. 4-71 Insert the clamp band and lock the turnbuckle

Tighten the turnbuckle screw by using an Allen® key SW 5.

Page 58: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 58 Transit Time Sensors - Rev. 00 as of 23.01.2013

Fig. 4-72 Locking the turnbuckle

Attach the second sensor parallel to the pipeline. Install the sensor as described before (sensor 1).

The transmitter calculates the required distance between the sensors during the startup. Due to this reason first start the transmitter and place the sensors according to the distance indicated by the transmitter prior to final sensor fas-tening.

v

1 23

1 Sensor 1 2 Sensor 2 3 Required distance of the sensors to each other

Fig. 4-73 1 path measuring, path arrangement: next to each other (V- mounting)

Page 59: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 59

v

1

2

3

1 Sensor 1 2 Sensor 2 3 Required distance of the sensors to each other

Fig. 4-74 1 path measuring, path arrangement: diagonal (Z-mounting)

4.4 Sensor Alignment 4.4.1 General

A precise sensor alignment is very important for a correct function of the transit time measurement. The transmitting surfaces of the respective sensors have to “see” each other in both directions (with and against the flow direction).

The flow velocity sensors of each path must be precisely aligned with each other.

In case of measurement places where the sensor’s point of radiation is accessi-ble it is recommended to use a laser distance meter (such as Bosch DLE) or a theodolite system to align the sensors.

Page 60: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 60 Transit Time Sensors - Rev. 00 as of 23.01.2013

1

2

LASER1

2LASER

Fig. 4-75 Laser distance meter for sensor alignment

The laser distance meter must be placed exactly to the sensor face to make sure that the laser beam can be adjusted accurately to the sensor located at the opposite.

LASER

Fig. 4-76 Put the laser distance meter exact on the sensor face

Page 61: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 61

Repeat the same procedure for the 2. sensor. This is the only way to ensure the sensors to accurately face each other.

1

2 3

4

11

2 3

4

Installation: all 4 sensors are aligned with one another

Error: Sensors are not aligned with one another

Fig. 4-77 Schematic diagram sensor alignment

4

3

LASER 1

2

Fig. 4-78 Example of sensor alignment

At measurement places where the sensor’s point of radiation is not accessible, the measurement place must be measured very exactly and the sensor holders shall be installed very accurately.

Page 62: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 62 Transit Time Sensors - Rev. 00 as of 23.01.2013

4.4.2 Rod Sensors Rod sensors can be aligned to each other by slightly rotating or moving them up and down from above and by simultaneously observing the signal strength on the transmitter display.

Fig. 4-79 Sensor alignment of rod sensors horizontal and vertical

4.4.3 Wedge Sensors Wedge sensors cannot be aligned anymore once they have been installed. Such sensors hence must be installed in a way that the sensors accurately are facing each other. To achieve this it is recommended to use a laser distance meter as adjustment aid during installation.

Page 63: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 63

4.4.4 Hemisphere To adjust angle "α" loosen the 4 screws using a size 5 Allen® key. To adjust an-gle "β" an Allen® key size 4 is required.

α = Revolving sensor on ground plate β = Rotary sensor head 1 = Screws to adjust angle α 2 = Screws to adjust angle β

Fig. 4-80 Sensor alignment of Hemisphere

4.4.5 Pipe sensors, screw-in and plug-in sensors In closed pipelines both sensors of each path shall be aligned by slightly rotating them. If nozzles should be installed slightly too close to each other (distance too short) it may be possible to increase the signal strength by moving the sensor slightly deeper into the pipe (may compensate the inappropriate sensor dis-tance).

2

1

A

2

1

B

A Sensor alignment with appropriately installed nozzles B Sensor alignment with inappropriately installed nozzles

Fig. 4-81 Sensor alignment in pipes by inserting

Page 64: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 64 Transit Time Sensors - Rev. 00 as of 23.01.2013

5 Accessories and Installation Aid 5.1 Holder bracket for rod sensors

There are two holder bracket versions for fastening the MOS Rod Sensors available. One is for fastening to a vertical wall (Type NOZ00HAL0), the other one for mounting on a horizontal wall crown with a minimum width of 400 mm (Type NOZ00HAL90). Following mounting material is included with the holder bracket delivery:

− 4x hex head screws M12x30

− dowels „SX 12x60“

− washers To fasten the sensors safely:

− 4x M12 adjusting screws

− 4 x counter nuts

Please observe exact vertical installation. A level is recommended as a help-ing tool.

Fig. 5-1 Holder bracket for rod sensor type NOZ00HAL0/ NOZ00HAL90

Page 65: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 65

87,6

220

2276

310

1520

35mm

1300

170

350

35

254,85

Fig. 5-2 Holder bracket NOZ00HAL0 for rod sensor fastening on verti-cal walls with protective sheet

Page 66: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 66 Transit Time Sensors - Rev. 00 as of 23.01.2013

2276

30

170

100

180

35

1300

254,85

400

220

300

Fig. 5-3 Holder bracket NOZ00HAL90 for rod sensor fastening on hori-zontal surface with protective sheet

Page 67: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 67

5.2 Protective sheet for Rod sensors There are flow-optimised protective sheet for rod sensors; length 1300 – 3000 mm available. In case of expecting heavy flow conditions we recommend to install a protective sheet for rod sensors at the sensor holder. This may avoid sensor vibration as well as damage caused by debris/flotsam or similar. Fasten the sheet by using M8 hammer set anchors and an appropriate inserting tool.

60 50

254,8

5

1300

9

10

1013034

130

Fig. 5-4 protective sheet for Rod sensors

Page 68: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 68 Transit Time Sensors - Rev. 00 as of 23.01.2013

5.3 Holder bracket for Hemisphere sensors There are holder brackets with optimised flow conditions for hemispheres avail-able. For fastening the standard delivery includes cylinder head screws M8x40 with hexagon socket and flat heads made of stainless steel. For use as cable ducts, pre-punched cutouts can be found on 2 sides of the holder (remove with pliers or similar). Then fasten the accompanying edge protection on the removed parts of the holder.

152

1,15

0,3

45°

1

45 ±2

a2

a2

a2

a2

R10

9

120

43 200

260

310

330

9

R10

10x

290,48

Fig. 5-5 Holder bracket NOZ00HALK for hemisphere sensors

Page 69: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 69

5.4 Welding Nozzle There are welding nozzles made of steel or stainless steel available for mount-ing sensors type NIS. For special applications (e.g. very few space at place of installation) there is a welding nozzle with outer thread available on which a stop ball valve can be screwed on directly.

Fig. 5-6 Welding nozzle

Fig. 5-7 Welding nozzle installation

Page 70: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 70 Transit Time Sensors - Rev. 00 as of 23.01.2013

5.5 Tapping Saddle General A tapping saddle can be purchased from NIVUS for upgrading by using a pipe sensor type NIS. This saddle is available in 2 versions for pipe diameters from 100 mm to 1000 mm (see Fig. 5-8 and Fig. 5-9) At Fig. 5-8 all metal parts of the tapping saddle are made of stainless steel 1.4301 (V2A). The clamp is completely white pickled to avoid material corrosion and to restore original resistance to corrosion. The bolts are coated with Teflon to avoid cold-welding fusion. A rubber gasket ensures reliable sealing. The rubber gasket is treated with antioxidant / antiozo-nant, to increase lifetime

1 Thread bolt M12, (M14, M16) Teflon coated 2 Thread protection cap 3 Nut 4 Washer 5 Saddle part with 1½“ inner thread for cutting ring screw joint 6 Saddle part with thread bolt 7 Rubber gasket 8 Side bracket 9 Mounting bracket (holder) 10 Screw yoke

Fig. 5-8 Overview tapping saddle DN 100 – DN 400

Versions for diameters of 400 mm upwards consist of the components below:

− Two tensioning belts with clamping bolts and nuts

− A mounting plate with welded sensor nozzle with 1½“ inner thread. This plate additionally has an O-ring to seal it from the pipe wall.

All metal parts of the system are made of stainless steel, 1.4301 (V2A).

Page 71: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 71

1 Tensioning belts 2 Mounting plate with welding nozzle and O-ring on the inside 3 Clamping bolt 4 Nut and counter nut

Fig. 5-9 Overview tapping saddle DN 450 – DN 1000

Fig. 5-10 Installation example with tapping saddle DN 100 to DN 400

Page 72: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 72 Transit Time Sensors - Rev. 00 as of 23.01.2013

Fig. 5-11 Installation example with tapping saddle DN 450 to DN 1000

Preparation of installation

− Test pipe / mounting place for damaging

− Clean pipe from pollution / dirt such as grease

− Check pipe diameter and dimensions of tapping saddle

− Grease the nozzle thread using appropriate paste for stainless steel screw joints

− anti-seize such as soft soap (no oil or grease!) can be used for the rubber gasket

Installation of tapping saddle up to DN 400 1. Drill a hole with ø38 mm into the pipe section. We furthermore

recommend to additionally use cutting paste for drill bit cooling (see chap. 5.7).

2. To remove burrs from the drilling hole, use a rasp and remove chip-pings/turnings.

3. Remove thread protection from the thread bolts.

4. Loose/drive the nuts back to the end of the thread bolts. However do not remove them

Page 73: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 73

Fig. 5-12 Remove thread protection and loose the nut

5. Unfold the saddle parts

Fig. 5-13 Unfold the saddle parts

6. Screw in the sensor screw joint into the greased nozzle manually.

7. Insert the sensor and put the sensor screw joint in hand-tight condition.

8. Put the upper saddle part with the sensor onto the pipe and insert the sensor through the hole. Then put the other saddle part around the pipe.

Fig. 5-14 Attach the saddle piece

Page 74: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 74 Transit Time Sensors - Rev. 00 as of 23.01.2013

9. Put the mounting bracket (holder) on one side over the screw yokes and tighten the screws manually. The holder will hook into the side bracket by tightening the bolts firmly (Fig. 5-15).

Fig. 5-15 Hook the mounting bracket (holder)

Fig. 5-16 Tighten screws

10. Before tightening the tapping saddle please make sure that the pipe sensor is not wedged and can be slightly inserted into the pipe! Tighten all nuts smoothly using a wrench with a length of approx. 300 mm (see Fig. 5-17). Tightening the bolts will automatically press the mounting bracket (holder) into the side bracket.

Following torques are valid, if a dynamometric key is used:

− bolt M12, width across flat 19 mm: torque 65 Nm

− bolt M14, width across flat 22 mm: torque 85 Nm

− bolt M16, width across flat 24 mm: torque 110 Nm At plastic pipes the torque shall be decreased (please ask the pipe manufacturer about the maximum rate).

Page 75: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation InstructionTransit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 75

Fig. 5-17 Tighten the nuts

11. After fastening the tapping saddle, adjust the pipe sensor and tighten the screw joint (see chapter 4.3.8)

In case of installation on vibrating facility parts such as pipe lines from adja-cent pumps etc. observe to secure the nuts of the fixing bolts and clamping bolts by using counter nuts. Otherwise nuts might loosen due to vibration.

5.6 Stop ball valveUsing a corrosion-proof straight stop ball valve additionally enables to quickly and easily lock the sensor installation place after the pipe sensor type NIS has been removed from a pressureless pipeline.

Fig. 5-18 Stop ball valve

Page 76: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 76 Transit Time Sensors - Rev. 00 as of 23.01.2013

48

22

1

300

195

ø35

M16 x 1,5

93

2

3

4

5

6

7

1 Weld-on nozzle 2 Hexagonal double nipple SW50 3 Stop ball valve 4 Retaining element 5 Pipe sensor 6 Installation aid 7 Pipe wall

Fig. 5-19 Sensor installation using retaining element, ball valve and welding nozzle

Page 77: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation InstructionTransit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 77

5.7 Drill bit and extension To prepare the installation of type NIS pipe sensors in steel or stainless steel pipelines, a drill bit with a diameter of 36 and 38 mm is available. If it is neces-sary to drill through a ball valve use a drill bit with a diameter of 36 mm as well as the accompanying extension.

Fig. 5-20 Drill bit and extension

Page 78: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

® Installation InstructionTransit Time Sensors

page 78 Transit Time Sensors - Rev. 00 as of 23.01.2013

Fig. 5-21 Extended drill bit

5.8 Cable Cover In order to avoid the risk of build-up, cover the cable with a thin stainless steel sheet 1.4571 (V4A). Appropriate covers of one meter length are available from NIVUS. Use these covers to safely fasten sensor cables on horizontal surfaces.

1 2

1 Stainless steel sheet/cable cover, e.g. type ZMS 1402 Cable

Fig. 5-22 Cable layout with cable cover

Page 79: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 79

5.9 Rail system for Clamp on sensors For easier sensor installation (Clamp on sensors type NIC0) NIVUS offers a rail system consisting of:

− tensioning belt, length 10 m,

− 2 turnbuckles and split,

− movable sensor receptacles

− 2 scale rails in 2 lengths This rail system can be installed on pipes with inner diameters between 100 and 500 mm and serves as aid for easy installation and maintenance of Clamp-On sensors. For installation split the tensioning belt and adjust it to the pipe circumference (as described in chapter 4.3.10). The tensioning belt is fastened by using the screws on the sensor receptacles (see Fig. 5-23, No. 3). Use the short rails for inner pipe diameters between 100 and 250 mm, the long rails for inner pipe diameters between 250 and 500 mm.

1

2

3

5

4

1 Knurled screws for sensor fixation 2 Knurled screws for fixation on the scale (rail) 3 Tensioning belt fixed with a screw 4 Sensor receptacle 5 Scale rail

Fig. 5-23 Rail system for Clamp on sensors

Page 80: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 80 Transit Time Sensors - Rev. 00 as of 23.01.2013

6 Table of Pictures Fig. 2-1 Sensor overview .................................................................................................................................. 6 Fig. 3-1 Safety hints on the sensor cable ......................................................................................................... 7 Fig. 4-1 Signal attenuation by suspended particles ....................................................................................... 12 Fig. 4-2 No vertical density difference of the signal ....................................................................................... 12 Fig. 4-3 Significant vertical density difference caused by solar irradiation ..................................................... 13 Fig. 4-4 Extreme vertical density difference caused by solar irradiation ........................................................ 13 Fig. 4-5 Significant vertical density difference caused by solar irradiation ..................................................... 13 Fig. 4-6 Horizontal density difference caused by discharge of hot water ....................................................... 14 Fig. 4-7 Sensor position behind curves or elbows ......................................................................................... 14 Fig. 4-8 Measuring behind fall – turbulence ................................................................................................... 15 Fig. 4-9 Error caused by alternation of slope ................................................................................................. 15 Fig. 4-10 Error caused by alternation of flow profile in front of slope alternation or fall ................................... 16 Fig. 4-11 Errors caused by fixtures or obstructions (top view) ......................................................................... 16 Fig. 4-12 Sensor position after change of profile (side view) ........................................................................... 17 Fig. 4-13 Recommended installation angles .................................................................................................... 17 Fig. 4-14 Comparison of installation places ..................................................................................................... 18 Fig. 4-15 Horizontal pipe with inverted siphon ................................................................................................. 18 Fig. 4-16 Using shut-off valves and control fittings .......................................................................................... 19 Fig. 4-17 Sensor assignment to the transducer ............................................................................................... 20 Fig. 4-18 Sensor allocation to the adapter box................................................................................................. 21 Fig. 4-19 Single path system ............................................................................................................................ 22 Fig. 4-20 Multi path system (crossed paths) .................................................................................................... 23 Fig. 4-21 Multi-layer system ............................................................................................................................. 23 Fig. 4-22 General path positioning, 2-path measuring ..................................................................................... 24 Fig. 4-23 graphical representation path length ................................................................................................. 25 Fig. 4-24 graphical representation Minimum water depth ................................................................................ 25 Fig. 4-25 Fixing the angle bracket on a wall ..................................................................................................... 27 Fig. 4-26 Fixing the wall mount on a straight wall ............................................................................................ 27 Fig. 4-27 Installation example Rod sensors 2 levels/4 paths (top view) .......................................................... 28 Fig. 4-28 Installation example Rod sensors 2 levels/4 paths (side view) ......................................................... 28 Fig. 4-29 Allocation of level when measuring average discharge .................................................................... 29 Fig. 4-30 Installation example hemisphere sensors 2 layers/ 2 paths ............................................................. 30 Fig. 4-31 Installation suggestion for cable extension ....................................................................................... 31 Fig. 4-32 Hints on cable layout ......................................................................................................................... 32 Fig. 4-33 2-path measuring in full pipe using wedge sensors .......................................................................... 32 Fig. 4-34 2-path measuring in part filled pipe with wedge sensors .................................................................. 33 Fig. 4-35 Top view of figure 4-34 ...................................................................................................................... 33 Fig. 4-36 Hints on pipe sensor installation ....................................................................................................... 34 Fig. 4-37 Hints on pipe sensor installation ....................................................................................................... 35 Fig. 4-38 Disturbances caused by weld seam burn ......................................................................................... 36 Fig. 4-39 Example of an 1 path measuring in a pipe (side view) ..................................................................... 37 Fig. 4-40 Example of an 1 path measuring in a pipe (top view) ....................................................................... 37 Fig. 4-41 Example of 2 path measuring in a pipe (side view) .......................................................................... 38 Fig. 4-42 Example of a 1-path reflection measurement in a small metal pipe ................................................. 38 Fig. 4-43 Using grease on sensors type NIS.................................................................................................... 39 Fig. 4-44 Components of pipe sensor mounting .............................................................................................. 40 Fig. 4-45 Exploded assembly drawing of sensor retaining element ................................................................. 41 Fig. 4-46 Greasing the sensor screw connection ............................................................................................. 42 Fig. 4-47 Fixing the sensor screw connection to the stop ball valve ................................................................ 42 Fig. 4-48 Positioning the sensor ....................................................................................................................... 43 Fig. 4-49 Fastening the sensor ......................................................................................................................... 43 Fig. 4-50 Attaching lower front clamp element ................................................................................................. 44 Fig. 4-51 Connecting upper rear and upper front clamp element .................................................................... 44 Fig. 4-52 Attaching the final clamp element ..................................................................................................... 45 Fig. 4-53 Unscrewing procedure for sensor removal ....................................................................................... 45 Fig. 4-54 Removing the sensor (maintenance/control) .................................................................................... 46 Fig. 4-55 Lock the sensor again after reinstallation ......................................................................................... 46 Fig. 4-56 Determining the center of the pipe .................................................................................................... 47 Fig. 4-57 Determining the sensor positions front side / rear side ..................................................................... 48 Fig. 4-58 Distances verification of the sensor positions ................................................................................... 48

Page 81: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

Installation Instruction Transit Time Sensors

®

Transit Time Sensors - Rev. 00 as of 23.01.2013 Page 81

Fig. 4-59 Several sensor angles inside the pipe .............................................................................................. 49 Fig. 4-60 Example of a multi-path measurement ............................................................................................. 50 Fig. 4-61 preparation for installing screw-in sensor ......................................................................................... 51 Fig. 4-62 Determination of the sensor position - plug-in and screw-in sensors ............................................... 52 Fig. 4-63 Positioning the screw-in sensor ........................................................................................................ 52 Fig. 4-64 Mark the alignment aid on the screw-in sensor ................................................................................ 52 Fig. 4-65 Sensor alignment; screw-in sensor ................................................................................................... 53 Fig. 4-66 Screwing-on the conductor barrel ..................................................................................................... 53 Fig. 4-67 Cable in Sensor conductor barrel ...................................................................................................... 54 Fig. 4-68 Connection board .............................................................................................................................. 54 Fig. 4-69 Sensor pair (sensor A and B) ............................................................................................................ 55 Fig. 4-70 Hook the clamp band into the lock .................................................................................................... 56 Fig. 4-71 Insert the clamp band and lock the turnbuckle ................................................................................. 57 Fig. 4-72 Locking the turnbuckle ...................................................................................................................... 58 Fig. 4-73 1 path measuring, path arrangement: next to each other (V- mounting) .......................................... 58 Fig. 4-74 1 path measuring, path arrangement: diagonal (Z-mounting) .......................................................... 59 Fig. 4-75 Laser distance meter for sensor alignment ....................................................................................... 60 Fig. 4-76 Put the laser distance meter exact on the sensor face ..................................................................... 60 Fig. 4-77 Schematic diagram sensor alignment ............................................................................................... 61 Fig. 4-78 Example of sensor alignment ............................................................................................................ 61 Fig. 4-79 Sensor alignment of rod sensors horizontal and vertical .................................................................. 62 Fig. 4-80 Sensor alignment of Hemisphere ...................................................................................................... 63 Fig. 4-81 Sensor alignment in pipes by inserting ............................................................................................. 63 Fig. 5-1 Holder bracket for rod sensor type NOZ00HAL0/ NOZ00HAL90 ..................................................... 64 Fig. 5-2 Holder bracket NOZ00HAL0 for rod sensor fastening on vertical walls with protective sheet ......... 65 Fig. 5-3 Holder bracket NOZ00HAL90 for rod sensor fastening on horizontal surface with protective sheet 66 Fig. 5-4 protective sheet for Rod sensors ...................................................................................................... 67 Fig. 5-5 Holder bracket NOZ00HALK for hemisphere sensors ...................................................................... 68 Fig. 5-6 Welding nozzle .................................................................................................................................. 69 Fig. 5-7 Welding nozzle installation ................................................................................................................ 69 Fig. 5-8 Overview tapping saddle DN 100 – DN 400 ..................................................................................... 70 Fig. 5-9 Overview tapping saddle DN 450 – DN 1000 ................................................................................... 71 Fig. 5-10 Installation example with tapping saddle DN 100 to DN 400 ............................................................ 71 Fig. 5-11 Installation example with tapping saddle DN 450 to DN 1000 .......................................................... 72 Fig. 5-12 Remove thread protection and loose the nut .................................................................................... 73 Fig. 5-13 Unfold the saddle parts ..................................................................................................................... 73 Fig. 5-14 Attach the saddle piece ..................................................................................................................... 73 Fig. 5-15 Hook the mounting bracket (holder) .................................................................................................. 74 Fig. 5-16 Tighten screws .................................................................................................................................. 74 Fig. 5-17 Tighten the nuts................................................................................................................................. 75 Fig. 5-18 Stop ball valve ................................................................................................................................... 75 Fig. 5-19 Sensor installation using retaining element, ball valve and welding nozzle ..................................... 76 Fig. 5-20 Drill bit and extension ........................................................................................................................ 77 Fig. 5-21 Extended drill bit ................................................................................................................................ 78 Fig. 5-22 Cable layout with cable cover ........................................................................................................... 78 Fig. 5-23 Rail system for Clamp on sensors .................................................................................................... 79

7 References The following standards and regulations have been used as sources to create this instruction manual: DIN EN-ISO 748, DIN EN ISO 6416, Bau und Betrieb von Ultraschall-Durchflussmessanlagen (Lfu).

Page 82: Installation Instruction for Transit Time Sensors - nivus.com · Installation Instruction for . Transit Time Sensors ... This installation instruction is an addendum to the ... müssen

®

Installation Instruction Transit Time Sensors

page 82 Transit Time Sensors - Rev. 00 as of 23.01.2013

8 Index

A

Authorizations 9

B

Branch Offices 2

C

Cable Bending Radius 32

Cables Layout 31

Calming Section 10 Change of Profile 17 Clamp-On 55 Copyright 3 Crossed Path System 23

D

Danger by electric voltage 7 Determining the pipe center 47

F

Fall 15

G

Grease Paste 38, 51

H

Hints on pipe sensor 7 Holder Bracket Hemisphere Sensors 68

I Influences

Air Bubbles 12 Suspended Particles 11 Temperature and Salt Content 12

L

Laser Level 48

M

Measures to avert danger 9

N

Names 3

O

Operating permits 8

P

Partial Filling 14

R

Rail System 79 Recommended Installation Angles 17

S

Safety regulations at work 9 Sensor

Installation position 17 Recommended range 18

Sensor Alignment 59 Sensor Overview 6 Sensor Positioning 19 Sensors

Allocation 20 Single Path System 22 Slope 15 System Configuration 22

T

Translation 3

U

User’s Responsibilities 8