INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and...

46
INSTALLATION AND OPERATION MANUAL ProtoCessor FPC-ED2 and ProtoCessor FPC-ED4 Condair LINKS 2587516_D_EN_2001

Transcript of INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and...

Page 1: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

INSTALLATION AND OPERATION MANUAL ProtoCessor FPC-ED2 and ProtoCessor FPC-ED4 Condair LINKS

2587

516_

D_E

N_2

001

Page 2: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Humidification and Evaporative Cooling For Interfacing Condair Products: Nortec… NH-EL, GS, EL, RS To Building Automation Systems: BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks Technical Support

Thank you for purchasing the ProtoCessor for Condair. Please call Condair for Technical support of the ProtoCessor product. Sierra Monitor Corporation does not provide direct support. If Condair needs to escalate the concern, they will contact Sierra Monitor Corporation for assistance. Support Contact Information: U.S.A. Condair Inc. 2700 90th Street Sturtevant, WI 53177 USA Canada Condair Ltd. 2740 Fenton Rd Ottawa, Ontario K1T 3T7 Condair Service: 1.866.667.8321 Fax: 1.613.822.9764 Email: [email protected] Website: www.condair.com APPLICABILITY & EFFECTIVITY Explains ProtoCessor FPC-ED2 hardware and how to install it.

The instructions are effective for the above as of OCT 2018.

Document Revision: 2.I Web Configurator

Template Revision: 60

Page 3: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

INSTALLATION AND OPERATION MANUAL

Condair LINKS ProtoCessor FPC-ED2 and ProtoCessor FPC-ED4 2587516_D_EN_2001

Page 4: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Thank you for choosing Condair

Installation date (DD/MM/YYYY):

Commissioning date (DD/MM/YYYY):

Site:

Model:

Serial number:

Manufacturer Condair Ltd. 2740 Fenton Road, Ottawa, ON, Canada K1T 3T7 Tel. 1.866.667.8321, Fax 613.822.7964 [email protected], www.condair.com Proprietary Notice This document and the information disclosed herein are proprietary data of Condair Ltd. Neither this docu-ment, nor the information contained herein shall be reproduced, used, or disclosed to others without the written authorization of Condair Ltd., except to the extent required for installation, operation or maintenance of the customer's equipment. Liability Notice Condair Ltd. does not accept any liability due to incorrect installation, maintenance or operation of the equipment, or due to the use of parts/components/equipment that are not authorized by Condair Ltd. Copyright Notice Copyright 2019, Condair Ltd, All rights reserved. Technical modification rights reserved.

Page 5: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 I V

Contents

1 Quick Start Guide ........................................................................................................ 7

2 Certifications ................................................................................................................ 8

3 Introduction .................................................................................................................. 9 3.1 ProtoCessor Gateway ................................................................................................... 9

4 Setup for ProtoCessor ...............................................................................................10 4.1 Record Identification Data ............................................................................................10 4.2 Point Count Capacity and Registers per Device ...........................................................10 4.3 Configuring Device Communications ............................................................................10 4.3.1 Input COM Settings for Device with an Inserted ProtoCessor ..................................10 4.3.2 Set Modbus RTU Node-ID for the Device ................................................................11

5 Interfacing ProtoCessor to Device ............................................................................12 5.1 ProtoCessor FPC-ED2 and FPC-ED4 Mounted onto Board .........................................12 5.2 ProtoCessor FPC-ED2 and FPC-ED4 Showing Connection Ports................................13 5.3 BACnet MS/TP or Metasys N2: Wiring Field Port to RS-485 Network ..........................14 5.4 LonWorks (FPC-ED4): Wiring Field Port to LonWorks Network ....................................14

6 Use ProtoCessor Web Configurator to Setup the Gateway .....................................15 6.1 Connect the PC to ProtoCessor via the Ethernet Port ..................................................15 6.2 Connecting to ProtoCessor Web Configurator ..............................................................16 6.3 Selecting Profiles for Device Connected to ProtoCessor ..............................................16 6.4 BACnet/IP Setting IP Address for Field Network ..........................................................19 6.5 Select Field Protocol ....................................................................................................21 6.5.1 BACnet MS/TP Configuration ..................................................................................21 6.5.2 BACnet/IP Configuration .........................................................................................22 6.5.3 Metasys N2 Configuration .......................................................................................23

7 BACnet MS/TP and BACnet/IP: Setting Node_Offset to Assign Specific Device Instances ...........................................................................................25

8 How to Start the Installation Over: Clearing Profiles ...............................................26

9 LonWorks (FPC-ED4): Commissioning ProtoCessor on a lonworks Network .......27 9.1 Commissioning ProtoCessor FPC-ED4 on a LonWorks Network .................................27 9.1.1 Instructions to Download XIF File from ProtoCessor FPC-ED4 Using Browser........27

A Troubleshooting ........................................................................................................... i A.1 Lost or Incorrect IP Address ............................................................................................ i A.2 Viewing Diagnostic information ...................................................................................... ii A.3 Check Wiring and Settings ............................................................................................. ii A.4 LED Diagnostics for Communications Between ProtoCessor and Device ..................... iii A.5 Take Diagnostic Capture With the FieldServer Utilities .................................................. iv

Page 6: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

VI | 2587516_D_EN_1909 Condair LINKS

A.6 Update Firmware .......................................................................................................... vii A.7 BACnet: Setting Network_Number for more than one ProtoCessor on Subnet ............. vii A.8 Securing the ProtoCessor with Passwords .................................................................. viii B Vendor Information - Condair ................................................................................... viii B.1 NHEL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks ....................... viii B.2 GS Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks ............................. ix B.3 EL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks ............................... x B.4 EL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks .............................. xi

C Reference ................................................................................................................... xiii C.1 Specifications .............................................................................................................. xiii C.2 Compliance with UL Regulations ................................................................................. xiii

Page 7: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 I 7

1 Quick Start Guide

1. Record the information about the unit. (Section 4.1)

2. Set the device’s Modbus RTU serial settings (i.e. baud rate, parity, stop bits) and Modbus Node-ID’s for the device that will be connected to ProtoCessor FPC-ED2 or FPC-ED4. (Section 4.3)

3. Metasys N2 (FPC-ED2): Set the Node-ID. (Section 4.3.2)

4. BACnet MS/TP or BACnet/IP: Set the BACnet Device Instance. (Section 7)

5. Connect ProtoCessor FPC-ED2’s 3 pin RS-485 port to the Field Protocol cabling, (Section 5.3) or connect ProtoCessor FPC-ED4’s 2 pin LonWorks port to the Field Protocol cabling. (Section 5.4)

6. Use a browser to access the ProtoCessor’s embedded tool, which is referred to in this manual as the Web Configurator, to select the device that will be attached to ProtoCessor and set the Modbus Node-ID. Once the device is selected, the ProtoCessor Automatically builds and loads the Configuration. (Section 6)

7. BACnet/IP (FPC-ED2): Use a browser to access the ProtoCessor Web Configurator to change the IP Address. No changes to the configuration are necessary. (Section 6.4)

8. LonWorks (FPC-ED4): The ProtoCessor must be commissioned on the LonWorks Network. This needs to be done by the LonWorks administrator using a LonWorks Commissioning tool. (Section 9)

Page 8: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

8 | 2587516_D_EN_1909 Condair LINKS

2 Certifications

BTL MARK – BACNET TESTING LABORATORY

LONMARK CERTIFICATION

The BTL Mark on ProtoCessor is a symbol that indicates that a product has passed a series of rigorous tests conducted by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing. The mark is a symbol of a high-quality BACnet product. Go to http://www.BACnetInternational.net/btl/ for more information about the BACnet Testing Laboratory. Click here for BACnet PIC Statement.

LonMark International is the recognized authority for certification, education, and promotion of interoperability standards for the benefit of manufacturers, integrators and end users. LonMark International has developed extensive product certification standards and tests to provide the integrator and user with confidence that products from multiple manufacturers utilizing LonMark devices work together. Sierra Monitor has more LonMark Certified gateways than any other gateway manufacturer, including the ProtoCessor, ProtoCarrier and ProtoCessor for OEM applications and the full featured, configurable gateways.

Page 9: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 I 9

3 Introduction

3.1 ProtoCessor Gateway

ProtoCessor is an external, high performance Building Automation multi-protocol gateway that is preconfigured to automatically communicate between Condair’s products (hereafter called “device”) connected to the ProtoCessor and automatically configures them for BACnet®1MS/TP, BACnet/IP, Metasys®2 N2 by JCI or LonWorks®3. It is not necessary to download any configuration files to support the required applications. The ProtoCessor is pre-loaded with tested Profiles/Configurations for the supported devices.

1 BACnet is a registered trademark of ASHRAE 2 Metasys is a registered trademark of Johnson Controls Inc. 3 LonWorks is a registered trademark of Echelon Corporation

Page 10: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

10 | 2587516_D_EN_1909 Condair LINKS

4 Setup for ProtoCessor

4.1 Record Identification Data

Each ProtoCessor has a unique part number located on the side or the back of the unit. This number should be recorded, as it may be required for technical support. The numbers are as follows: Table 1: ProtoCessor Part Numbers

Model Part Number

ProtoCessor FPC-ED2 FPC-ED2-1409 ProtoCessor FPC-ED4 FPC-ED4-1410

− FPC-ED2 units have the following 2 ports: RS-485 + Ethernet

− FPC-ED4 units have the following 2 ports: LonWorks + Ethernet

4.2 Point Count Capacity and Registers per Device

The total number of Registers presented by the device attached to the ProtoCessor cannot exceed:

Table 2: Supported Point Count Capacity

Part Number Total Registers FPC-ED2-1409 1500 FPC-ED4-1410 1500

Table 3: Registers per Device

Devices Registers per Device

Nortec NHEL 35 Nortec GS 22 Nortec EL 35 Nortec RS 59

4.3 Configuring Device Communications

4.3.1 Input COM Settings for Device with an Inserted ProtoCessor

− Set the serial device that the ProtoCessor is plugged into to have the same Baud Rate, Data Bits, Stop Bits, and Parity settings as the ProtoCessor.

− Table 4: COM Settings specifies the device serial port settings required to communicate with the ProtoCessor.

Page 11: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 I 11

Table 4: COM Settings

Serial Port Setting Device Protocol 35

Baud Rate 9600 Parity Even

Data Bits 8 Stop Bits 1

4.3.2 Set Modbus RTU Node-ID for the Device

− Set Modbus Node-ID for the device the ProtoCessor is plugged into. (See Section 6.5 to input Node-ID)

− The Modbus Node-ID needs to be uniquely assigned between 1 and 255.

o The Modbus Node-ID that is assigned for the device needs to be documented

The Modbus Node-ID assigned is used for designating the Device Instance for BACnet/IP and BACnet MS/TP

− The Metasys N2 and Modbus TCP/IP field protocol Node-IDs are automatically set to be the same value as the Node-ID of the Modbus RTU device.

Page 12: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

12 | 2587516_D_EN_1909 Condair LINKS

5 Interfacing ProtoCessor to Device

5.1 ProtoCessor FPC-ED2 and FPC-ED4 Mounted onto Board

Figure 1: Mounted ProtoCessor BACnet FPC-ED2 (upper) and ProtoCessor FPC-ED4 (lower)

Page 13: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 I 13

5.2 ProtoCessor FPC-ED2 and FPC-ED4 Showing Connection Ports

Figure 2: ProtoCessor FPC-ED2 (upper) and ProtoCessor FPC-ED4 (lower)

Page 14: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

14 | 2587516_D_EN_1909 Condair LINKS

5.3 BACnet MS/TP or Metasys N2: Wiring Field Port to RS-485 Network

− Connect the BACnet MS/TP or Metasys N2 RS-485 network wires to the 3-pin RS-485 connector on ProtoCessor ED2 as shown below in

− Figure 3.

o The RS-485 GND (Pin 3) is not typically connected

− See Section 7 for information on connecting to BACnet/IP network.

− If the ProtoCessor is the last device on the BACnet MS/TP or Metasys N2 trunk, then the End-Of-Line Termination Switch needs to be enabled (Figure 4).

o The default setting from the factory is OFF (switch position = right side)

o To enable the EOL Termination, turn the EOL switch ON (switch position = left side)

Figure 3: Connection from ProtoCessor to RS-485 Field Network

Figure 4: RS-485 BMS Network EOL Switch

5.4 LonWorks (FPC-ED4): Wiring Field Port to LonWorks Network

− Connect ProtoCessor to the field network with the LonWorks terminal using approved cable per the FT-10 installation guidelines. LonWorks has no polarity.

Figure 5: LonWorks Terminal Connector

BMS RS-485 Wiring

ProtoCessor Pin #

Pin Assignment

RS-485 + Pin 1 RS-485 + RS-485 - Pin 2 RS-485 - - Pin 3 RS-485 GND

+

End-of-Line Switch

Page 15: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 I 15

6 Use ProtoCessor Web Configurator to Setup the Gateway

6.1 Connect the PC to ProtoCessor via the Ethernet Port

− Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the local PC and ProtoCessor.

− The Default IP Address of ProtoCessor is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and ProtoCessor are on different IP Networks, assign a static IP Address to the PC on the 192.168.168.xxx network.

For Windows XP:

Go to > > Right-click on Local Area Connection > Properties

Highlight >

For Windows 7:

Go to > >

> > Right-click on Local Area Connection > Properties

Highlight >

For Windows XP and Windows 7, use the following IP Address:

Click twice.

Page 16: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

16 | 2587516_D_EN_1909 Condair LINKS

6.2 Connecting to ProtoCessor Web Configurator

− After setting a local PC on the same subnet as the ProtoCessor (Section 6.1), open a web browser on the PC and enter the IP Address of the ProtoCessor; the default address is 192.168.1.24. NOTE: If the IP Address of the ProtoCessor has been changed by previous

configuration, the assigned IP Address must be gathered from the network administrator.

6.3 Selecting Profiles for Device Connected to ProtoCessor

− In the Web Configurator, the Active Profiles section is shown on the lower left side of the screen.

− The Active Profiles section lists the currently active device profiles, including previous Web Configurator additions. This list will be empty for new installations, or after clearing all configurations. (

− − − Figure 6) − To add an active profile to support a device, click the ADD button under Active Profiles.

This will present a drop-down box underneath the Current Profile column that lists all the available profiles. (

− − Figure 7) − For every device that is added, assign a unique Modbus Node-ID. This specification

must match the device’s network settings.

Page 17: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 I 17

Figure 6: Web Configurator Showing no Active Profiles

− Once the Profile for the device has been selected from the drop-down list, enter the value of the device’s Modbus Node-ID which was assigned in Section 4.3.2.

Page 18: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

18 | 2587516_D_EN_1909 Condair LINKS

Figure 7: Web Configurator Showing Available Profiles for Selection

− Then press the “Submit” button to add the Profile as a device to be configured.

− Completed additions will be listed under “Active Profiles” as shown in

− Figure 8.

Page 19: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 I 19

Figure 8: Web Configurator Showing Active Profile Additions

6.4 BACnet/IP Setting IP Address for Field Network

After setting a local PC to the same subnet as the ProtoCessor (Section 6.1), open a web browser on the PC and enter the IP Address of the ProtoCessor; the default address is 192.168.1.24. The Web Configurator is displayed as the landing page. (Figure 9) To access the Web GUI, click on the “Diagnostics & Debugging” button in the bottom right side of the page.

Page 20: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

20 | 2587516_D_EN_1909 Condair LINKS

Figure 9: Web Configurator Screen

From the Web GUI landing page, click on “Setup” to expand the navigation tree and then select “Network Settings” to access the IP Settings menu. (Figure 10)

Figure 10: Changing IP Address via Web GUI

− Modify the IP Address (N1 IP Address field) of the ProtoCessor Ethernet port.

− If necessary, change the Netmask (N1 Netmask field).

− Type in a new Subnet Mask.

− If necessary, change the IP Gateway (Default Gateway field).

− Type in a new IP Gateway.

− NOTE: If the ProtoCessor is connected to a router, the IP Gateway of the ProtoCessor should be set to the IP Address of that router.

− Reset ProtoCessor.

− Unplug Ethernet cable from PC and connect it to the network hub or router.

− Record the IP Address assigned to the ProtoCessor for future reference.

Page 21: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 I 21

6.5 Select Field Protocol

For ED2 – Use the Protocol Selector by typing in the corresponding number next to the desired protocol:

o BACnet MS/TP 1 o BACnet/IP 2 o Metasys N2 3

Then click “System Restart” to bring up options to configure the desired protocol.

For ED4 – There are no device details to be entered for this protocol combination.

6.5.1 BACnet MS/TP Configuration

− Enter the appropriate details for BACnet MS/TP (

− Figure 11):

Page 22: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

22 | 2587516_D_EN_1909 Condair LINKS

Figure 11: Web Configurator Showing BACnet MS/TP Configuration

6.5.2 BACnet/IP Configuration

− Enter the appropriate details for BACnet/IP (Figure 12):

Page 23: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 I 23

Figure 12: Web Configurator Showing BACnet/IP Configuration

6.5.3 Metasys N2 Configuration

− Enter the appropriate details for Metasys N2 (Figure 13):

Page 24: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

24 | 2587516_D_EN_1909 Condair LINKS

Figure 13: Web Configurator Showing Metasys N2 Configuration

Page 25: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 I 25

7 BACnet MS/TP and BACnet/IP: Setting Node_Offset to Assign Specific Device Instances

− After setting a local PC to the same subnet as the ProtoNode (Section 6.1), open a web browser on the PC and enter the IP Address of the ProtoNode; the default address is 192.168.1.24.

o The Web Configurator will be displayed as the landing page. (

o

o Figure 11 or Figure 12)

− The Node_Offset field shows the current value (default = 50,000). o The values allowed for a BACnet Device Instance can range from 1 to 4,194,303.

To assign a specific Device Instance (or range), change the Node_Offset value accordingly.

o Given that: Node_Offset + Modbus Node_ID = Device Instance o Then: Node_Offset (required) = Device Instance (desired) – Modbus

Node_ID

For example, if the desired Device Instance for the device is 1,001: o Device has a Modbus Node-ID of 1 o Node_Offset (required) = 1,001 – (Modbus Node_ID) = 1,001 – 1 = 1,000

NOTE: The Node_Offset value will be applied to the device.

o Device Instance will then be = 1,000 + Modbus Node_ID = 1,000 + 1 = 1,001

− Click “Submit” once the desired value is entered.

Figure 14: Active Profiles with Node-ID

Page 26: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

26 | 2587516_D_EN_1909 Condair LINKS

8 How to Start the Installation Over: Clearing Profiles

− After setting a local PC to the same subnet as the ProtoCessor (Section 6.1), open a web browser on the PC and enter the IP Address of the ProtoCessor; the default address is 192.168.1.24.

− If the IP Address of the ProtoCessor has been changed by previous configuration,

the assigned IP Address must be gathered from the network administrator.

− The Web Configurator is displayed as the landing page.

− At the bottom-left of the page, click the “Clear Profiles and Restart” button.

− Once restart is complete, all past profiles discovered and/or added via Web configurator are deleted. The unit can now be reinstalled.

Page 27: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 I 27

9 LonWorks (FPC-ED4): Commissioning ProtoCessor on a lonworks Network

Note: Commissioning may only be performed by the LonWorks administrator

9.1 Commissioning ProtoCessor FPC-ED4 on a LonWorks Network

The User will be prompted by the LonWorks Administrator to hit the Service Pin on the ProtoCessor FPC-ED4 at the correct step of the Commissioning process which is different for each LonWorks Network Management Tool.

• If an XIF file is required, see steps in Section 9.1.1 to generate XIF.

Figure 15: LonWorks Service Pin Location

9.1.1 Instructions to Download XIF File from ProtoCessor FPC-ED4 Using Browser

− Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the PC and ProtoCessor.

− The Default IP Address of ProtoCessor is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC and ProtoCessor are on different IP Networks, assign a static IP Address to the PC on the 192.168.1.xxx network. For Windows XP:

Go to > > Right-click on Local Area Connection > Properties

Highlight >

Page 28: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

28 | 2587516_D_EN_1909 Condair LINKS

For Windows 7 or later:

Go to > >

> > Right-click on Local Area Connection > Properties

Highlight >

For Windows XP and Windows 7, use the following IP Address:

Click twice.

− Open a web browser and go to the following address: [IP Address of ProtoCessor]/fserver.xif

− Example: 192.168.1.24/fserver.xif

− If the web browser prompts to save the file, save the file onto the PC. If the web browser displays the xif file as a web page, save the file onto the local PC as “fserver.xif”.

Figure 16: Sample of Fserver.XIF File Generated

Page 29: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 I 29

This page intentionally left blank

Page 30: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor
Page 31: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 Appendix I i

A TROUBLESHOOTING

A.1 Lost or Incorrect IP Address

− Ensure that FieldServer Toolbox is loaded onto the local PC. If not, download FieldServer-Toolbox.zip on the Sierra Monitor webpage, under Customer Care-Resource Center, Software Downloads: http://www.sierramonitor.com/customer-care/resource-center?filters=software-downloads

− Extract the executable file and complete the installation.

Figure 17: Ethernet Port Location

− Disable any wireless Ethernet adapters on the PC/Laptop. − Disable firewall and virus protection software if possible. − Connect a standard CAT5 Ethernet cable between the PC and ProtoCessor. − Double click on the FS Toolbox Utility.

− Check IP Addresses from the Device listings.

Correct IP Address(es) by right clicking the settings icon and changing the IP Address.

Ethernet Port

Page 32: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

ii | Appendix 2587516_D_EN_2001 Condair LINKS

A.2 Viewing Diagnostic information

− Type the IP Address of the ProtoCessor into the web browser or use the FieldServer Toolbox to connect to the ProtoCessor.

− Click on Diagnostics and Debugging Button, then click on view, and then on connections.

− If there are any errors showing on the Connection page, please refer to A.3 for the relevant wiring and settings.

Figure 18: Error messages screen

A.3 Check Wiring and Settings

− No COMS on Modbus RTU side. If the Tx/Rx LEDs are not flashing rapidly then there is a COM issue. To fix, check the following:

o Visual observations of LEDs on ProtoCessor (A.4) o Check baud rate, parity, data bits, stop bits o Check device address o Verify wiring

− Field COM problems: o Visual observations of LEDs on ProtoCessor (A.4) o Check dipswitch settings (using correct baud rate and device instance)

Page 33: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 Appendix I iii

o Verify IP Address setting o Verify wiring

NOTE: If the problem persists, a Diagnostic Capture needs to be taken and sent to support. (A.5)

A.4 LED Diagnostics for Communications Between ProtoCessor and Device

Please see the diagram below for ProtoCessor FPC-ED2 (left) and FPC-ED4 (right) LED Locations.

Figure 19: Diagnostic LEDs

Page 34: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

iv | Appendix 2587516_D_EN_2001 Condair LINKS

Table 5 :Diagnostic LEDs

Tag Description Run The Run LED will start flashing 20 seconds after power indicating normal

operation. The Heat Beat LED has the same functionality but flashes more rapidly.

Sys/Config Error

The Sys/Config Error LED will go on solid 15 seconds after power up. It will turn off after 5 seconds. A steady red light will indicate there is a system error on ProtoCessor. If this occurs, immediately report the related “system error” shown in the error screen of the GUI interface to Sierra Monitor Corporation for evaluation.

Node Offline

The Node Offline LED will turn on and stay solid if there is no communication with the device.

RX The RX LED will flash when a message is received on the field port. TX The TX LED will flash when a message is sent on the field port. PWR This is the power light and should show steady green at all times when

ProtoCessor is powered.

A.5 Take Diagnostic Capture With the FieldServer Utilities

Once the Diagnostic Capture is complete, email it to [email protected]. The Diagnostic Capture will accelerate diagnosis of the problem. Ensure that FieldServer Toolbox is Loaded on the PC that is currently being used, or download FieldServer-Toolbox.zip on the Sierra Monitor webpage, under Customer Care: Resource Center, Software Downloads: http://www.sierramonitor.com/customer-care/resource-center?filters=software-downloads Extract the executable file and complete the installation.

Figure 20: Ethernet Port Location

− Disable any wireless Ethernet adapters on the PC/Laptop.

− Disable firewall and virus protection software if possible.

− Connect a standard CAT5 Ethernet cable between the PC and ProtoCessor.

− Double click on the FS Toolbox Utility.

Ethernet Port

Page 35: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 Appendix I v

Step 1: Take a Log

o Click on the diagnose icon of the desired device

o Select “Full Diagnostic"

NOTE: If desired, the default capture period can be changed

o Click on “Start Diagnostic”

Page 36: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

vi | Appendix 2587516_D_EN_2001 Condair LINKS

o When the capture period is finished, the “Diagnostic Test Complete” window will appear

Step 2: Send Log o Once the diagnostic test is complete, a .zip file will be saved on the PC

o Click “Open” to launch explorer and have it point directly at the correct folder, then email the diagnostic zip file to [email protected]

o

Page 37: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 Appendix I vii

A.6 Update Firmware

To load a new version of the firmware, follow these instructions: 1. Extract and save the new file onto the local PC. 2. Open a web browser and type the IP Address of the FieldServer in the address bar.

NOTE: Default IP Address is 192.168.1.24 NOTE: Use the FS Toolbox utility if you do not know the IP Address (A.1)

3. Click on the “Diagnostics & Debugging” button. 4. In the Navigation Tree on the left hand side, do the following:

a. Click on “Setup” b. Click on “File Transfer” c. Click on the “Firmware” tab

5. In the Firmware tab, click on “Choose Files” and select the firmware file extracted in step1.

6. Click on the orange “Submit” button. 7. When the download is complete, click on the “System Restart” button.

A.7 BACnet: Setting Network_Number for more than one ProtoCessor on Subnet

For both BACnet MS/TP and BACnet/IP, if more than one ProtoCessor is connected to the same subnet, they must be assigned unique Network_Number values.

On the main Web Configuration screen, update the Network Number with the “network_nr” field and click submit. The default value is 50.

Figure 21: Configuration Parameters – Setting Network Number for BACnet

Page 38: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

viii | Appendix 2587516_D_EN_2001 Condair LINKS

A.8 Securing the ProtoCessor with Passwords

Access to the ProtoCessor can be restricted by enabling a password. There are 2 access levels defined by 2 account names: Admin and User.

• The Admin account has unrestricted access to the ProtoCessor.

• The User account can view any ProtoCessor information, but cannot make any changes or

restart the ProtoCessor.

The password needs to be a minimum of eight characters and is case sensitive. If the password is lost, click cancel on the password authentication popup window, and email the password recovery token to [email protected] to receive a temporary password from the support team. Access the ProtoCessor to set a new password.

B VENDOR INFORMATION - CONDAIR

B.1 Nortec NHEL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks

Point Name BACnet Object Type

BACnet Object ID

2Data Type

N2 Address LonWorks Name LonWorks

SNVT

nvoStatus AV 1 AO 1 nvoStatus_XXX SNVT_lev_percent

nviSigSource AV 2 AO 2 nvi/nvoSigSource_XXX

SNVT_lev_percent

nviCtrlMode AV 3 AO 3 nvi/nvoCtrlMode_XXX

SNVT_lev_percent

nviCtrlChannel AV 4 AO 4 nvi/nvoCtrlCh_XXX SNVT_lev_percent

nviBMStimeout AV 5 AO 5 nvi/nvoBMStmeout_XXX

SNVT_time_sec

nvoHourOpt_A AV 6 AO 6 nvoHrOpt_A_XXX SNVT_time_hour

nvoHourWeight_A AV 7 AO 7 nvoHrWght_A_XXX SNVT_time_hour

nvoRHDem_A1 AV 8 AO 8 nvoRHDem_A1_XXX SNVT_lev_percent

nvoRHDem_A2 AV 9 AO 9 nvoRHDem_A2_XXX SNVT_lev_percent

nvoSysDem_A AV 10 AO 10 nvoSysDem_A_XXX SNVT_lev_percent

nviManCapacity_A AV 11 AO 11 nvi/nvoManCap_A_XXX

SNVT_lev_percent

nviSetPoint_A1 AV 12 AO 12 nvi/nvoSetPnt_A1_XXX

SNVT_lev_percent

nviSetPoint_A2 AV 13 AO 13 nvi/nvoSetPnt_A2_XXX

SNVT_lev_percent

nviDRHDem_A1 AV 14 AO 14 nvi/nvoDRHDem_A1_XXX

SNVT_lev_percent

nviDRHDem_A2 AV 15 AO 15 nvi/nvoDRHDem_A2_XXX

SNVT_lev_percent

Page 39: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 Appendix I ix

nvoHourOpt_B AV 16 AO 16 nvoHrOpt_B_XXX SNVT_time_hour

nvoHourWeight_B AV 17 AO 17 nvoHrWght_B_XXX SNVT_time_hour

nvoRHDem_B1 AV 18 AO 18 nvoRHDem_B1_XXX SNVT_lev_percent

nvoRHDem_B2 AV 19 AO 19 nvoRHDem_B2_XXX SNVT_lev_percent

nvoSysDem_B AV 20 AO 20 nvoSysDem_B_XXX SNVT_lev_percent

nviManCapacity_B AV 21 AO 21 nvi/nvoManCap_B_XXX

SNVT_lev_percent

nviSetPoint_B1 AV 22 AO 22 nvi/nvoSetPnt_B1_XXX

SNVT_lev_percent

nviSetPoint_B2 AV 23 AO 23 nvi/nvoSetPnt_B2_XXX

SNVT_lev_percent

nviDRHDem_B1 AV 24 AO 24 nvi/nvoDRHDem_B1_XXX

SNVT_lev_percent

nviDRHDem_B2 AV 25 AO 25 nvi/nvoDRHDem_B2_XXX

SNVT_lev_percent

nvoConnection BV 1 DO 1 nvoConnectn_XXX SNVT_switch nvoService BV 2 DO 2 nvoService_XXX SNVT_switch nvoFault BV 3 DO 3 nvoFault_XXX SNVT_switch nviDisable BV 4 DO 4 nvi/nvoDisable_XXX SNVT_switch nvoSecurity_A BV 5 DO 5 nvoSecurty_A_XXX SNVT_switch nvoBlowerAct_A BV 6 DO 6 nvoBlwrAct_A_XXX SNVT_switch nvoFanAct_A BV 7 DO 7 nvoFanAct_A_XXX SNVT_switch nvoSecurity_B BV 8 DO 8 nvoSecurty_B_XXX SNVT_switch nvoBlowerAct_B BV 9 DO 9 nvoBlwrAct_B_XXX SNVT_switch nvoFanAct_B BV 10 DO 10 nvoFanAct_B_XXX SNVT_switch

B.2 Nortec GS Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks

Point Name BACnet Object Type

BACnet Object ID

N2 Data Type

N2 Address LonWorks Name LonWorks

SNVT

nvoStatus AV 1 AO 1 nvoStatus_XXX SNVT_lev_percent

nviSigSource AV 2 AO 2 nvi/nvoSigSource_XXX

SNVT_lev_percent

nviCtrlMode AV 3 AO 3 nvi/nvoCtrlMode_XXX

SNVT_lev_percent

nviCtrlChannel AV 4 AO 4 nvi/nvoCtrlCh_XXX SNVT_lev_percent

nviBMStimeout AV 5 AO 5 nvi/nvoBMStmeout_XXX

SNVT_time_sec

nvoHourOpt_A AV 6 AO 6 nvoHrOpt_A_XXX SNVT_time_hour

nvoHourWeight_A AV 7 AO 7 nvoHrWght_A_XXX SNVT_time_hour

nvoRHDem_A1 AV 8 AO 8 nvoRHDem_A1_XXX SNVT_lev_percent

nvoRHDem_A2 AV 9 AO 9 nvoRHDem_A2_XXX SNVT_lev_percent

Page 40: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

x | Appendix 2587516_D_EN_2001 Condair LINKS

nvoSysDem_A AV 10 AO 10 nvoSysDem_A_XXX SNVT_lev_percent

nviManCapacity_A AV 11 AO 11 nvi/nvoManCap_A_XXX

SNVT_lev_percent

nviSetPoint_A1 AV 12 AO 12 nvi/nvoSetPnt_A1_XXX

SNVT_lev_percent

nviSetPoint_A2 AV 13 AO 13 nvi/nvoSetPnt_A2_XXX

SNVT_lev_percent

nviDRHDem_A1 AV 14 AO 14 nvi/nvoDRHDem_A1_XXX

SNVT_lev_percent

nviDRHDem_A2 AV 15 AO 15 nvi/nvoDRHDem_A2_XXX

SNVT_lev_percent

nvoServInterval_A AV 16 AO 16 nvoSrvIntv_A_XXX SNVT_lev_percent

nvoDaysService_A AV 17 AO 17 nvoDaySrvc_A_XXX SNVT_count_f nvoConnection BV 18 DO 18 nvoConnectn_XXX SNVT_switch nvoService BV 19 DO 19 nvoSrvc_XXX SNVT_switch nvoFault BV 20 DO 20 nvoFault_XXX SNVT_switch nviDisable BV 21 DO 21 nvi/nvoDisable_XXX SNVT_switch nvoSecurity_A BV 22 DO 22 nvoSecurty_A_XXX SNVT_switch

B.3 Nortec EL Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks

Point Name BACnet Object Type

BACnet Object ID

N2 Data Type

N2 Address LonWorks Name LonWorks

SNVT

nvoStatus AV 1 AO 1 nvoStatus_XXX SNVT_lev_percent

nviSigSource AV 2 AO 2 nvi/nvoSigSource_XXX

SNVT_lev_percent

nviCtrlMode AV 3 AO 3 nvi/nvoCtrlMode_XXX

SNVT_lev_percent

nviCtrlChannel AV 4 AO 4 nvi/nvoCtrlCh_XXX SNVT_lev_percent

nviBMStimeout AV 5 AO 5 nvi/nvoBMStmeout_XXX

SNVT_time_sec

nvoHourOpt_A AV 6 AO 6 nvoHrOpt_A_XXX SNVT_time_hour

nvoHourWeight_A AV 7 AO 7 nvoHrWght_A_XXX SNVT_time_hour

nvoRHDem_A1 AV 8 AO 8 nvoRHDem_A1_XXX SNVT_lev_percent

nvoRHDem_A2 AV 9 AO 9 nvoRHDem_A2_XXX SNVT_lev_percent

nvoSysDem_A AV 10 AO 10 nvoSysDem_A_XXX SNVT_lev_percent

nviManCapacity_A AV 11 AO 11 nvi/nvoManCap_A_XXX

SNVT_lev_percent

nviSetPoint_A1 AV 12 AO 12 nvi/nvoSetPnt_A1_XXX

SNVT_lev_percent

nviSetPoint_A2 AV 13 AO 13 nvi/nvoSetPnt_A2_XXX

SNVT_lev_percent

nviDRHDem_A1 AV 14 AO 14 nvi/nvoDRHDem_A1_XXX

SNVT_lev_percent

nviDRHDem_A2 AV 15 AO 15 nvi/nvoDRHDem_A2_XXX

SNVT_lev_percent

Page 41: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 Appendix I xi

nvoHourOpt_B AV 16 AO 16 nvoHrOpt_B_XXX SNVT_time_hour

nvoHourWeight_B AV 17 AO 17 nvoHrWght_B_XXX SNVT_time_hour

nvoRHDem_B1 AV 18 AO 18 nvoRHDem_B1_XXX SNVT_lev_percent

nvoRHDem_B2 AV 19 AO 19 nvoRHDem_B2_XXX SNVT_lev_percent

nvoSysDem_B AV 20 AO 20 nvoSysDem_B_XXX SNVT_lev_percent

nviManCapacity_B AV 21 AO 21 nvi/nvoManCap_B_XXX

SNVT_lev_percent

nviSetPoint_B1 AV 22 AO 22 nvi/nvoSetPnt_B1_XXX

SNVT_lev_percent

nviSetPoint_B2 AV 23 AO 23 nvi/nvoSetPnt_B2_XXX

SNVT_lev_percent

nviDRHDem_B1 AV 24 AO 24 nvi/nvoDRHDem_B1_XXX

SNVT_lev_percent

nviDRHDem_B2 AV 25 AO 25 nvi/nvoDRHDem_B2_XXX

SNVT_lev_percent

nvoConnection BV 1 DO 1 nvoConnectn_XXX SNVT_switch nvoService BV 2 DO 2 nvoSrvc_XXX SNVT_switch nvoFault BV 3 DO 3 nvoFault_XXX SNVT_switch nviDisable BV 4 DO 4 nvi/nvoDisable_XXX SNVT_switch nvoSecurity_A BV 5 DO 5 nvoSecurty_A_XXX SNVT_switch nvoBlowerAct_A BV 6 DO 6 nvoBlwrAct_A_XXX SNVT_switch nvoFanAct_A BV 7 DO 7 nvoFanAct_A_XXX SNVT_switch nvoSecurity_B BV 8 DO 8 nvoSecurty_B_XXX SNVT_switch nvoBlowerAct_B BV 9 DO 9 nvoBlwrAct_B_XXX SNVT_switch nvoFanAct_B BV 10 DO 10 nvoFanAct_B_XXX SNVT_switch

B.4 Nortec RS Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks

Point Name BACnet Object Type

BACnet Object ID

N2 Data Type

N2 Address LonWorks Name LonWorks

SNVT

MI_UnitStatusA MI 1 ADI 1 nvoUnitStatA_XXX SNVT_count MI_UnitStatusB MI 2 ADI 2 nvoUnitStatB_XXX SNVT_count MI_ServStatusA MI 3 ADI 3 nvoServStatA_XXX SNVT_count MI_ServStatusB MI 4 ADI 4 nvoServStatB_XXX SNVT_count MI_HumType MI 5 ADI 5 nvoHumType_XXX SNVT_count MI_NomVoltage MI 6 ADI 6 nvoNomVolt_XXX SNVT_count MI_LevelA MI 7 ADI 7 nvoLevelA_XXX SNVT_count MI_LevelB MI 8 ADI 8 nvoLevelB_XXX SNVT_count AI_ErrorCode AI 1 AI 1 nvoErrorCode_XXX SNVT_count

AI_OperatHours AI 2 AI 2 nvoOperatHr_XXX SNVT_time_hour

AI_HoursToServA AI 3 AI 3 nvoHrToServA_XXX SNVT_time_hour

AI_HoursToServB AI 4 AI 4 nvoHrToServB_XXX SNVT_time_hour

AI_SystemDemandA AI 5 AI 5 nvoSysDem_XXX SNVT_count AI_InputA1 AI 6 AI 6 nvoInputA1_XXX SNVT_count AI_InputA2 AI 7 AI 7 nvoInputA2_XXX SNVT_count

Page 42: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

xii | Appendix 2587516_D_EN_2001 Condair LINKS

AI_MaxHumOut AI 8 AI 8 nvoMaxHumOut_XXX SNVT_count

AI_CylMaxCapA AI 9 AI 9 nvoCylMxCapA_XXX SNVT_count AI_CylMaxCapB AI 10 AI 10 nvoCylMxCapB_XXX SNVT_count AI_ActCapHum AI 11 AI 11 nvoAcCapHum_XXX SNVT_count AI_CylActCapA AI 12 AI 12 nvoCylAcCapA_XXX SNVT_count AI_CylActCapB AI 13 AI 13 nvoCylAcCapB_XXX SNVT_count

AV_SetPointA1 AV 1 ADF 1 nvi/nvoSetPntA1_XXX SNVT_count

AV_SetPointA2 AV 2 ADF 2 nvi/nvoSetPntA2_XXX SNVT_count

AV_PropBandA1 AV 3 ADF 3 nvi/nvoPropBndA1_XXX SNVT_count

AV_PropBandA2 AV 4 ADF 4 nvi/nvoPropBndA2_XXX SNVT_count

AV_IntTimeA1 AV 5 ADF 5 nvi/nvoIntTimeA1_XXX SNVT_count

AV_DampTimeA2 AV 6 ADF 6 nvi/nvoDmpTimeA2_XXX SNVT_count

AV_CapLimitA AV 7 ADF 7 nvi/nvoCapLimitA_XXX SNVT_count

AV_RemoteDrain AV 8 ADF 8

AO_RemRHorDemA1 AO 1 AO 1 nvi/nvoRmRHrDmA1_XXX SNVT_count

AO_RemRHorDemA2 AO 2 AO 2 nvi/nvoRmRHrDmA2_XXX SNVT_count

BI_BlowerPackA BI 1 DI 1 nvoBlwrPackA_XXX SNVT_switch BI_BlowerPackB BI 2 DI 2 nvoBlwrPackB_XXX SNVT_switch BI_ExtSChStaA BI 3 DI 3 nvoExtSChStA_XXX SNVT_switch BI_ExtSChStaB BI 4 DI 4 nvoExtSChStB_XXX SNVT_switch BI_IntSChStaA BI 5 DI 5 nvoIntSChStA_XXX SNVT_switch BI_IntSChStaB BI 6 DI 6 nvoIntSChStB_XXX SNVT_switch BI_HeatVoltageA BI 7 DI 7 nvoHeatVoltA_XXX SNVT_switch BI_HeatVoltageB BI 8 DI 8 nvoHeatVoltB_XXX SNVT_switch BI_LevelSafetyA BI 9 DI 9 nvoLvlSaftyA_XXX SNVT_switch BI_LevelSafetyB BI 10 DI 10 nvoLvlSaftyB_XXX SNVT_switch BI_LeakA BI 11 DI 11 nvoPressureA_XXX SNVT_switch BI_LeakB BI 12 DI 12 nvoPressureB_XXX SNVT_switch BI_MainContactA BI 13 DI 13 nvoMainContA_XXX SNVT_switch BI_MainContactB BI 14 DI 14 nvoMainContB_XXX SNVT_switch BI_PumpA BI 15 DI 15 nvoPumpA_XXX SNVT_switch BI_PumpB BI 16 DI 16 nvoPumpB_XXX SNVT_switch BI_InletA1 BI 17 DI 17 nvoInletA1_XXX SNVT_switch BI_InletB1 BI 18 DI 18 nvoInletB1_XXX SNVT_switch BI_InletA2 BI 19 DI 19 nvoInletA2_XXX SNVT_switch BI_InletB2 BI 20 DI 20 nvoInletB2_XXX SNVT_switch BI_DrainA1 BI 21 DI 21 nvoDrainA1_XXX SNVT_switch BI_DrainB1 BI 22 DI 22 nvoDrainB1_XXX SNVT_switch BI_DrainA2 BI 23 DI 23 nvoDrainA2_XXX SNVT_switch BI_DrainB2 BI 24 DI 24 nvoDrainB2_XXX SNVT_switch BI_FanA BI 25 DI 25 nvoFanA_XXX SNVT_switch BI_FanB BI 26 DI 26 nvoFanB_XXX SNVT_switch BI_FlushValveA BI 27 DI 27 nvoFlushVlvA_XXX SNVT_switch BI_FlushValveB BI 28 DI 28 nvoFlushVlvB_XXX SNVT_switch

Page 43: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Condair LINKS 2587516_D_EN_2001 Appendix I xiii

C REFERENCE

C.1 Specifications

ProtoCessor FPC-ED2 ProtoCessor FPC-ED4

Electrical Connections

One 3-pin Phoenix connector with RS-485 port (+ / - / gnd)

One Ethernet 10/100 BaseT port

One 2-pin Phoenix connector with: One FTT-10 LonWorks port

One Ethernet 10/100 BaseT port

Approvals

CE Certified; TUV approved to UL 916, EN 60950-1, EN 50491-3 and CSA C22-2 standards; FCC Class A Part 15; DNP3 Conformance Tested; RoHS Compliant; CSA 205 Approved BTL Marked LonMark Certified

Power Requirements Multi-mode power adapter: 9-30VDC or 12 - 24VAC

Physical Dimensions

6.9 x 3.0 x 2.0 cm 2.7 x 1.2 x 0.8 in.

8.5 x 3.0 x 2.0 cm 3.3 x 1.2 x .08 in.

Weight 0.03 kg (0.07 lbs) Operating Temperature -40°C to 75°C (-40°F to167°F)

Surge Suppression EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT Humidity 5 - 90% RH (non-condensing) (Specifications subject to change without notice)

Figure 22: Specifications

C.2 Compliance with UL Regulations

For UL compliance, the following instructions must be met when operating ProtoCessor.The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature range.The interconnecting power connector and power cable shall:

− Comply with local electrical code

− Be suited to the expected operating temperature range

− Meet the current and voltage rating for ProtoCessor

− Furthermore, the interconnecting power cable shall:

− Be of length not exceeding 3.05m (118.3”)

− Be constructed of materials rated VW-1, FT-1 or better

− If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be installed in a Restricted Access Area requiring a key or a special tool to gain access.

− This device must not be connected to a LAN segment with outdoor wiring.

Page 44: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

xiv | Appendix 2587516_D_EN_2001 Condair LINKS

Page intentionally left blank

Page 45: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Warranty

Condair Inc. and/or Condair Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly warranted, are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations.

THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing replacement parts to the customer, F.O.B. THE COMPANY’s factory, provided that the defective part(s) is returned freight prepaid by the customer. The replacement parts are warranted for the balance of the term of the warranty on the original humidifier or 90 days, whichever is longer.

The warranties set forth herein are in lieu of all other warranties expressed or implied by law. No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in writing, signed by an officer of THE COMPANY.

THE COMPANY’s limited warranty on accessories, not manufactured by the COMPANY, such as controls, humidistats, pumps, etc., is limited to the warranty of the original equipment manufacturer from date of original shipment of humidifier.

THE COMPANY makes no warranty and assumes no liability unless the equipment is installed in strict accordance with a copy of the catalog and installation manual in effect at the date of purchase, and by a contractor approved by THE COMPANY to install such equipment.

THE COMPANY makes no warranty and assumes no liability whatsoever for consequential damage or damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the equipment.

THE COMPANY makes no warranty and assumes no liability whatsoever for damage to the humidifier, supply lines, drain lines, or steam distribution systems caused by freezing. THE COMPANY reserves the right to change the design, specifications and performance criteria of its products without notice or obligation.

Page 46: INSTALLATION AND OPERATION MANUAL - Condair€¦ · BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks . Document Revision: 2.I Technical Support Thank you for purchasing the ProtoCessor

Consulting, Sales and Service: U.S.A. 835 Commerce Park Ave Ogdensburg, NY 1366-2209 CANADA 2740 Fenton Road Ottawa, ON, K1T 3T7 Tel: 1.866.667.8321 Fax: 613.822.7964 Email: [email protected] Website: www.condair.com