Industrial Ventilation vs. IAQ
Heating
Ventilation
Air
Conditioning
![Page 2: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/2.jpg)
Industrial Ventilation vs. IAQ
HVAC System Functions
Heating
Cooling
Ventilation
Filtration
Dehumidification
Humidification
Distribution
![Page 3: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/3.jpg)
Industrial Ventilation vs. IAQ
![Page 4: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/4.jpg)
Industrial Ventilation vs. IAQ
![Page 5: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/5.jpg)
Routes of Entry
• Inhalation
• Ingestion
• Absorption
• Injection
![Page 6: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/6.jpg)
Control Options
• Process change
• Substitution
• Isolation
• Ventilation
• Administrative control
• Personal protective equipment
![Page 7: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/7.jpg)
Problem Characterization
BURTON 2-1
EMISSION SOURCE
AIRFLOW
![Page 8: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/8.jpg)
Burton Ex. 2-1
BURTON 2-4
GROUP EXERCISE
Study the figure on page 2-4 and discuss potential control measures that you might use to correct the problem.
![Page 9: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/9.jpg)
THE BEHAVIOR OF AIR
![Page 10: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/10.jpg)
The Atmosphere
• Reaches 50 miles into space.
• Pressure = 14.7 pounds per square inch.
![Page 11: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/11.jpg)
Composition of Air
Percentage Composition by Volume
Nitrogen
Oxygen
Argon
![Page 12: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/12.jpg)
Pressure Measurement
VacuumAtmospheric Pressure14.7 psia
![Page 13: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/13.jpg)
Pressure Measurement
14.7 psia =407in. Water
14.7 psia =29.92 in. Mercury (Hg.)
![Page 14: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/14.jpg)
How Do We Make Air Move ?
![Page 15: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/15.jpg)
Pressure
• Differences in air pressure cause movement.
![Page 16: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/16.jpg)
Pressure Differential Causes Movement
BURTON 3-6
FLOW LOW HIGH
FAN
![Page 17: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/17.jpg)
Negative Pressure = Less Than Atmospheric
![Page 18: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/18.jpg)
Positive Pressure = Greater Than Atmospheric
![Page 19: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/19.jpg)
Pressure Relationships
![Page 20: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/20.jpg)
Pressure Terms
• Static Pressure
• Velocity Pressure
• Total Pressure
![Page 21: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/21.jpg)
Static Pressure
SPFlow
Static pressure (SP) isexerted in all directions.
![Page 22: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/22.jpg)
Velocity Pressure
SPFlow
Velocity Pressure (VP) iskinetic (moving pressure) resulting from air flow.
VP
![Page 23: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/23.jpg)
Total Pressure
SPFlow
Total pressure (TP) is the algebraic sum of the VP and SP.
VP
TP
![Page 24: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/24.jpg)
Pressure Upstream and Downstream of the Fan
BURTON 3-8
TP SP VP
Up-stream - - +
Down-stream + + +
![Page 25: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/25.jpg)
What is use of the term “Velocity Pressure” ?
• Determine the air flow.
• To design the system.
• V = 4005(VP)1/2
![Page 26: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/26.jpg)
What is use of the term “Static Pressure” ?
• Accelerate the air.
• Overcome resistance to friction.
![Page 27: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/27.jpg)
Static Pressure and Velocity Pressure are Mutually
ConvertibleWhen air is accelerated, the static pressure is converted to velocity pressure.
When air is decelerated, the velocity pressure can be transformed back into static pressure.
=
![Page 28: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/28.jpg)
Conservation of Mass
• Mass in = Mass out.
• Air speeds up when the duct area is smaller.
Q = VA
Q = Cubic Feet Per MinuteV = VelocityA = Area
![Page 29: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/29.jpg)
Dilution Ventilation
BURTON 4-1
YES• non-hazardous
• gas, vapor, respirable particle
• uniform time emission
• emissions not close to people
• moderate climate
NO• toxic material
• large particulate
• emission varies widely over time
• large, point source emissions
• people in vicinity
• severe climate
• irritation or complaints
![Page 30: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/30.jpg)
Volume Vapor Flow Rate
BURTON 4-3
![Page 31: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/31.jpg)
Estimating Dilution Air Volume
BURTON 4-5
![Page 32: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/32.jpg)
Poor Dilution
![Page 33: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/33.jpg)
Good Dilution
![Page 34: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/34.jpg)
Example 4-1
BURTON 4-6
What is q, the volume flow rate of vapor formed, if 0.5 gallons of toluene are evaporated uniformly over an 8-hr. shift? What volume flow rate Qd is required for dilution to 10 ppm, if Kmixing = 2 ? (Assume STP; d = 1.0)
What is the average face velocity of air in a room 10ft. * 8ft. * 40ft for these conditions?
![Page 35: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/35.jpg)
Strategy Ex. 4-2
Step 1: Calculate the volume flow rate of the vapor
emitted q.
q = (387 * lbs. evaporated)/ (MW * t * d)
Note:lbs. Evaporated = gal. * 8.31 * SG
Step 2. Calculate the dilution air volume flow rate
Qd.
Qd = q * 106 * K mixing
Ca (ppm)
Step 3: Calculate the face velocity.
V face = Qd/A
Step 4: Calculate the air changes/ hour.
N = (Qd * 60)/Vr
![Page 36: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/36.jpg)
Purge and Buildup
BURTON 4-9
• Purge and buildup - predict contaminant buildup or purge rate.
• Steady state -equilibrium maintained.
![Page 37: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/37.jpg)
Example 4-5
An automobile garage was severely contaminated with carbon monoxide.
How long will it take to purge the garage?
BURTON 4-11
![Page 38: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/38.jpg)
BURTON 11-1
Chapter 11 - Makeup Air Balance
• Exhausted air must be replaced.
• Negative pressure without makeup air.
![Page 39: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/39.jpg)
Make up Air
• Fresh air supplied into the breathing zone of the associate.
![Page 40: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/40.jpg)
Overcoming Negative Static Pressure
BURTON 11-2
• Changes in static pressure involving radial (squirrel cage) fans cause a small change in the volumetric flow rate.
• Changes in static pressure involving axial (propeller) fans cause a large change in the volumetric flow rate.
![Page 41: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/41.jpg)
Good Makeup Air
INDUSTRIAL VENTILATION 2-4
![Page 42: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/42.jpg)
Bad Makeup Air
INDUSTRIAL VENTILATION 2-4
![Page 43: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/43.jpg)
Reentrainment
BURTON 11-9
![Page 44: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/44.jpg)
Reentrainment
BURTON 11-9
![Page 45: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/45.jpg)
Avoiding Reentrainment10-50-3000 RULE
BURTON 14-5
![Page 46: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/46.jpg)
Recirculation of Exhaust Air
BURTON 12-1
• Good for non-toxic particulate control.
• Can recover 40-60% of heat energy.
![Page 47: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/47.jpg)
Types of Ventilation Systems
BURTON 5-1
![Page 48: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/48.jpg)
Why Choose Local Ventilation?
BURTON 5-2
• No other controls • Containment• Employee in vicinity• Emissions vary with
time• Sources large and
few• Fixed source• Codes
![Page 49: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/49.jpg)
Exercise 5-3
BURTON 5-3
Form your group and try exercise 5-3. Compare the operation to the parameters listed below:
• No other controls available
• Hazardous contaminant
• Employee in immediate vicinity
• Emissions vary with time
• Emission sources large and few
• Fixed emission source
• Codes & standards
![Page 50: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/50.jpg)
Components of a Local Exhaust System
BURTON 5-4
![Page 51: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/51.jpg)
Static Pressure Review
BURTON 5-5
![Page 52: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/52.jpg)
Energy Conservation
BURTON 5-6
![Page 53: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/53.jpg)
Basic Air Flow Equations
BURTON 5-7
• Q = V * A
• TP = SP + VP
• V = 4005(VP/d)0.5
![Page 54: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/54.jpg)
Static Pressure Loss
BURTON 5-8
• Static Pressure Loss = Kloss * VP * d
![Page 55: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/55.jpg)
Elbow Loss
BURTON 5-9
Air moving through elbows spends static pressure because of:
• directional change • friction • shock losses• turbulent mixing• air bunching up • SP(loss) = K(elbow )* VP * d
![Page 56: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/56.jpg)
Elbow Loss Ex. 5-8
BURTON 5-9
What is the elbow loss factor K(elbow) where the elbow radius of curvature is R/D = 2.0 in a smooth transition elbow.
![Page 57: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/57.jpg)
Elbow Loss Exercise 5-9
BURTON 5-10
What is the actual loss in inches of water of air flowing through a 60-degree, 3-piece elbow at V = 3440 fpm? R/D = 1.5, STP, d=1.
![Page 58: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/58.jpg)
Elbow Loss Exercise 5-9
• SPloss = K * VP * d
• Use Chart 13, Appendix pg. 25 for information on a 90-degree 3- piece elbow with R/D = 1.5
• Let K = (angle/90) * K 90
• VP = (V/4005)2
![Page 59: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/59.jpg)
Friction Loss as a Function of Duct Length
BURTON 5-11
Friction Loss = K * VP * L * R * d• K is a value taken from Chart #5,
appendix page 9 • VP is duct velocity pressure, in w.g.• L is the length of the duct in feet• d is the density correction factor• R is roughness correction factor
![Page 60: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/60.jpg)
Exercise 5-10
What is the friction loss for a length of galvanized duct with the following parameters? D = 8in., Q = 1000scfm, L = 43 ft. R = 1.
![Page 61: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/61.jpg)
Tee Losses
BURTON 5-11
![Page 62: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/62.jpg)
Tee Losses Ex. 5-12
BURTON 5-12
What is the estimated static pressure loss in inches of water for a branch entry of 30 degrees where the branch entry velocity is 4500 fpm?
![Page 63: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/63.jpg)
Converting Static Pressure To Velocity Pressure
BURTON 6-2
At the hood, all of the available static pressure is converted to velocity pressure and hood entry loss.
SPh = VP + he
![Page 64: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/64.jpg)
Measuring Hood Static Pressure
BURTON 6-2
Measure hood static pressure 4-6 duct diameters downstream from the hood.
4-6 D
![Page 65: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/65.jpg)
Hood Entry Losses
BURTON 6-2
The hood entry loss is the sum total of all losses from the hood face to the point of measurement in the duct.
SP(loss) = K * VP * d
he = K * VP * d
![Page 66: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/66.jpg)
BURTON 6-3
Example 6-1
What is the hood static pressure when the duct velocity pressure is VP = 1.10 in. w.g. and the hood entry loss is
he = 1.00 in w.g.
SPh = VP + he
SPh = 1.10+ 1.00
= -2.10 in w.g.
![Page 67: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/67.jpg)
Vena Contracta
BURTON 6-3
The greatest loss normally occurs at the entrance to the duct, due to the vena contracta formed in the throat of the duct.
![Page 68: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/68.jpg)
Hood Efficiency
BURTON 6-4
A hood’s efficiency can be described by the ratio of actual to ideal flow. This ratio is called the Coefficient of Entry, Ce.
Ce = Q(actual)/Q(ideal)
![Page 69: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/69.jpg)
Hood Static Pressure and Entry Losses Example 6-5
BURTON 6-5
The average velocity in a duct serving a hood is V = 2000 fpm. The loss factor for the hood has been obtained from the manufacturer as Khood = 2.2. What are the he and SPh? (Assume STP, d = 1)
![Page 70: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/70.jpg)
Hand Grinding Table Example 6-6
BURTON 6-6
Assume that a special hand grinding table hood has been built and the following data have been measured:
SPh = -2.50 in w.g., V = 4000fpm, and the duct diameter is 18 in. (Assume STP, d=1)
![Page 71: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/71.jpg)
Types of Hoods
• Receiving
• Capturing
• Enclosing
BURTON 6-10
![Page 72: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/72.jpg)
Hood Types
• SLOTTED HOOD
![Page 73: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/73.jpg)
Hood Types
• ENCLOSED HOOD
![Page 74: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/74.jpg)
Hood Types
• ENCLOSING HOOD
![Page 75: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/75.jpg)
Hood Types
• CAPTURING HOOD
![Page 76: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/76.jpg)
Grinding Wheel Hood Example Example 6-9
BURTON 6-12
Determine the volume flow rate, transport velocity, duct diameter, loss factor K, Ce, he, and SPh, for a grinding wheel hood, wheel diameter = 13in. (low surface speed), straight take off [sto], STP)
![Page 77: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/77.jpg)
EXERCISE 6-10USEFUL FORMULAS
Q = V * A
V = 4005(VP)1/2
VP = (V/4005)2
he = K * VP
SPh = VP + he
BURTON 6-12 AND 6-13
![Page 78: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/78.jpg)
Exercise 6-10a Where appropriate, determine the volume flow rate,
transport velocity, duct diameter, loss factor K, Ce, he, and SPh for a grinding wheel hood with a wheel diameter of 14 in. (low surface speed, tapered takeoff [tto]. Note: the picture in the book is for a buffing hood.
BURTON 6-12
![Page 79: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/79.jpg)
Exercise 6-10a Strategy
1. Use Chart 11C, appendix pg. 18 to find Q, Vtrans., K, and Ce.
2. Use Chart 5A in appendix pg. 9 to find the diameter of the pipe needed and it’s area.
3. Calculate Vactual = Q/A
4. VP = (Vactual/4005)2
5. he = K * VP
6. SPh = VP + he
![Page 80: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/80.jpg)
Exercise 6-10b
Where appropriate, determine the volume flow rate, transport velocity, duct diameter, loss factor K, Ce, he, and SPh for a hand grinding table 10 feet long by 2 feet wide.
BURTON 6-13
![Page 81: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/81.jpg)
Exercise 6-10b Strategy1. Use Chart 11C, appendix
pg. 18 to find Q, Vtrans., K, and Ce.
2. Use Chart 5A in appendix pg. 9 to find the diameter of the pipe needed and it’s area.
3. Calculate Vactual = Q/A
4. VP = (Vactual/4005)2
5. he = K * VP
6. SPh = VP + he
![Page 82: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/82.jpg)
Exercise 6-10c
Where appropriate, determine the volume flow rate, transport velocity, duct diameter, loss factor K, Ce, he, and SPh for a band saw used to cut wood that has a blade width of 1 inch.
BURTON 6-13
![Page 83: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/83.jpg)
Exercise 6-10c Strategy
1. Use Chart 11E, appendix pg. 20 to find Q, Vtrans., K, and Ce.
2. Use Chart 5A in appendix pg. 9 to find the diameter of the pipe needed and it’s area.
3. Calculate Vactual = Q/A
4. VP = (Vactual/4005)2
5. he = K * VP
6. SPh = VP + he
![Page 84: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/84.jpg)
Exercise 6-10d
Where appropriate, determine the volume flow rate, transport velocity, duct diameter, loss factor K, Ce, he, and SPh for a bell-mouthed hood used for welding. X=10 in., Vc = 100 fpm, Vtrans = 3000 fpm.
BURTON 6-13
![Page 85: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/85.jpg)
Exercise 6-10d Strategy
1. Use Chart 11A, appendix pg. 16 to find Q, K, and Ce.
2. Use Chart 5A in appendix pg. 9 to find the diameter of the pipe needed and it’s area.
3. Calculate Vactual = Q/A
4. VP = (Vactual/4005)2
5. he = K * VP
6. SPh = VP + he
![Page 86: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/86.jpg)
Exercise 6-10e Where appropriate,
determine the volume flow rate, transport velocity, duct diameter, loss factor K, Ce, he, and SPh for a canopy hood used for a hot-liquid open surfaced tank. P = 16 ft., X = 3 ft., Vcontrol = 125 fpm, Vtrans = 2000fpm.
BURTON 6-13
![Page 87: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/87.jpg)
Exercise 6-10e Strategy
1. Use Chart 11B, appendix pg. 17 to find Q, K, and Ce.
2. Use Chart 5A in appendix pg. 9 to find the diameter of the pipe needed and it’s area.
3. Calculate Vactual = Q/A
4. VP = (Vactual/4005)2
5. he = K * VP
6. SPh = VP + he
![Page 88: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/88.jpg)
Factors Influencing Hood Performance
• Competition• Mixing• Work practices
BURTON 6-17
![Page 89: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/89.jpg)
Canopy Hoods
BURTON 6-19
• Use only for hot processes with rising air.
• Estimate initial and terminal velocities of rising air stream.
• The volume of air exhausted from the hood must exceed the volume of air arriving at the hood face.
• Warm rising air expands as it rises. Make the cross-sectional area of the hood face 125% larger than the plume of hot air.
• Avoid canopy hoods if an employee must work over the source.
![Page 90: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/90.jpg)
Chapter 7Selection and Design of
Ductwork
BURTON 7-1
![Page 91: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/91.jpg)
Exercise 7-2
BURTON 7-4
Standard air (d=1) moves through an 8 in. galvanized duct system at 4000 fpm. Estimate VP, find the loss factors K from the Charts, and then estimate static pressure loss for each component in each branch. (Note: treat the branch entry as two 45-degree entries and use the ACGIH value for K on Chart 14.)
![Page 92: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/92.jpg)
Exercise 7-2a, Flanged Hood
BURTON 7-4
![Page 93: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/93.jpg)
Exercise 7-2b, Plain Duct Hood
BURTON 7-4
![Page 94: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/94.jpg)
Exercise 7-2c, Elbow, 3-piece
BURTON 7-4
![Page 95: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/95.jpg)
Exercise 7-2d, Elbow, 5-piece
BURTON 7-4
![Page 96: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/96.jpg)
Exercise7-2e, Elbow, 4-piece
BURTON 7-4
![Page 97: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/97.jpg)
Exercise 7-2f, Branch Entry
BURTON 7-4
![Page 98: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/98.jpg)
Exercise 7-2g, 50 ft. of Duct
BURTON 7-4
![Page 99: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/99.jpg)
BURTON 7-5
RoughnessExample 7-1
Standard air is flowing in 40 feet of a 24 in. concrete pipe at the 4000 fpm. What is the correction factor, R? The loss factor K?
![Page 100: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/100.jpg)
Duct Shapes
BURTON 7-6
Use round duct whenever possible, it resists collapsing, provides better aerosol transport conditions, and may be less expensive.
![Page 101: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/101.jpg)
Pressure Diagrams
BURTON 7-11
![Page 102: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/102.jpg)
Chapter 8 Fan Selection and Operation
AXIAL FANS• propeller fans
CENTRIFUGAL FANS• radial fans
• forward inclined
• backward inclined
BURTON 8-2
![Page 103: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/103.jpg)
Fan Total Pressure
BURTON 8-3
The fan total pressure (FTP) represents all energy requirements for moving air through the ventilation system.
The fan total pressure is often referred to as the fan total static pressure drop.
FTP = TP outlet - TP inlet
FTP = SPout - VP out - SPin - VP in
FTP = SPout - SPin
![Page 104: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/104.jpg)
Exercise 8-1
BURTON 8-3
Find the Fan Total Pressure given that the SPin = -5.0 in w.g, SPout = +0.40 in w.g.
VPin = VPout = 1.0 in. w.g.
FTP = SPout - SPin =
0.40 - (-5.0) = 5.4 in w.g.
![Page 105: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/105.jpg)
Exercise 8-2Fan Static Pressure
BURTON 8-4
The fan static pressure out of the fan is defined as the fan total pressure minus the average velocity pressure out of the fan.
FSP = Fan TP - VPout
![Page 106: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/106.jpg)
SOP and Fan Curves
BURTON 8-5
To develop a system curve, the fan should be turned at different rpms and the flow and the absolute values of the static pressures at the fan are plotted.
![Page 107: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/107.jpg)
Developing Fan Curves
BURTON 8-6
![Page 108: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/108.jpg)
SOP on Steep Part of Curve
BURTON 8-7
![Page 109: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/109.jpg)
Example 8-1
BURTON 8-8
Choose an appropriate fan for a system operating point of Q = 10,000 scfm and FTP = 1.5 in. w.g.
![Page 110: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/110.jpg)
Exercise 8-3
BURTON 8-8
Find a fan and appropriate rpm for a fan exhausting 15,000 cfm at a fan TP = 2.0 in. w.g.
![Page 111: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/111.jpg)
Exercise8-4
BURTON 8-8
Find a suitable fan and the appropriate rpm for a ventilation system exhausting 480 cfm at a fan TP = 13.8 in. w.g.
![Page 112: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/112.jpg)
Commercial Fan Curves
BURTON 8-9
![Page 113: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/113.jpg)
Commercial Fan Curves
BURTON 8-10
![Page 114: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/114.jpg)
Commercial Fan Curves
BURTON 8-11
![Page 115: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/115.jpg)
System Effect Losses
BURTON 8-12
![Page 116: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/116.jpg)
Six-and-Three Rule
BURTON 8-13
![Page 117: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/117.jpg)
Air Horsepower
BURTON 8-14
Air horsepower refers to the minimum amount of power to move a volume of air against the fan total pressure. It represents the power to get the air through the duct system.
ahp = ( FTP * Q * d)/6356
![Page 118: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/118.jpg)
Brake Horsepower
BURTON 8-15
Brake horsepower refers to the actual power required to operate the fan so that it fulfills the job of moving the specified cfm against the FTP. It takes into account fan inefficiencies, i.e. losses in the fan.
bhp = ahp/ME
![Page 119: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/119.jpg)
Shaft Horsepower
BURTON 8-15
Shaft horsepower is bhp plus any power required for drive losses, bearing losses, and pulley losses between the fan and the shaft of the motor.
shp = bhp * Kdl
![Page 120: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/120.jpg)
Rated Horsepower
• Rated horsepower is the nameplate horsepower on the motor.
BURTON 8-15
![Page 121: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/121.jpg)
Example 8-4
BURTON 8-16
What is the required power for the system and what rated power motor would you use?
FTP = 5.0 in. w.g. ,
Q = 12000 scfm
ME = 0.60, Kdl = 1.10, d = 1,
f = 6356
![Page 122: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/122.jpg)
Exercise 8-7
BURTON 8-17
Estimate the ahp, bhp, shp, and the rated power motor you would choose for the following system.
Fan TP = 10.0 in. w.g.,
Q = 5000 scfm
Kdl = 1.15, STP(d=1),
f = 6356, ME = 0.65
![Page 123: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/123.jpg)
Fan Laws
BURTON 8-19
![Page 124: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/124.jpg)
Local Exhaust Ventilation Design
BURTON 9-1
![Page 125: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/125.jpg)
Plenum Design
BURTON 9-3
![Page 126: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/126.jpg)
BALANCING
BURTON 9-4
Balancing during the design phase means adjusting losses in duct runs leading to a junction that the predicted loss in each run is essentially equal.
![Page 127: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/127.jpg)
Example 9-2
BURTON 9-5
Design an local exhaust system based on the criteria listed in the example.
![Page 128: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/128.jpg)
Name: Project: Example 9-2 8 in. duct 7 in. duct
Row Item Source Units (US)
PLANS 1. Duct ID Plans FROM -TO A-B A-B
2. Design Q Chart 11 cfm 1000 1000
3. Transport vel. Chart 9, 11 cfm 3000 3000
4. Slotted hood? Y-R5, N-R12 NO NO
5. Slot velocity Chart 11 fpm
6. Slot area R2/R5 sq. ft.
SLOTS/ 7. Slot VP Chart 7 in. w .g.
PLENUM 8. Slot entry loss factor -1.78
9. Acceleration factor -1
10. Plenum loss factor -2.78
11. Plenum SP R7*R10
12. Duct diameter Chart 5 inches 8 7
13. Duct area Chart 5 sq. ft. 0.0391 0.2673
DUCT 14. Duct velocity R2/R13 fpm 2865 3740
15. Duct VP Chart 7 inches 0.51 0.87
16. Duct length from plans feet 25 25
17. Friction R, duct Chart 10 or from mfg 2.4 2.4
18. Friction K Chart 5 0.03 0.035
19. Friction K, duct R16*R17*R18 1.8 2.1
20. Hood entry Chart 11 0.25 0.25
LOSS 21. Acceleration 1.0 at hoods 1 1
FACTOR 22. Elbow s Chart 13 0.27 0.27
K 23. Branch entry Chart 14 ACGIH 0 0
24. System effect Chart 16 0 0
25. Other K loss 0 0
26. Total K sum R19-R25 3.32 3.62
27. Duct SP R26*R15 inch 1.69 3.15
STATIC 28. SP at FROM location R33 inch 0 0
PRESSURE 29. Jxn. VP change at FROM Chart 14 inch 0 0
30. Other SP loss inch 0 0
31. Total SP at TO R11+(R27toR30) inch 1.69 3.15
32. Is this Governing SP y/n
JUNCTION 33. Governing SP at TO location inch
34. Actual Q = [R2*(R33/R31)^0.5
35. SPh [R11+(R15*(R20+R21))]inch 0.64 1.09HOOD 36. Total slot length plans feet
37. Slot w idth 12(R6/R36) inch
![Page 129: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/129.jpg)
Example 9-3
BURTON 9-11
Design a local exhaust system based upon the criteria listed on this page.
![Page 130: Industrial Ventilation vs. IAQ H eating V entilation A ir C onditioning.](https://reader035.fdocuments.net/reader035/viewer/2022062421/56649d9d5503460f94a8682c/html5/thumbnails/130.jpg)
Name: Group Exercise Project: Example 9-3
Row Item Source Units (US)
PLANS 1. Duct ID Plans FROM -TO A-B B-C C-D D-E
2. Design Q Chart 11 cfm 2400 1000 3421 3421
3. Transport vel. Chart 9, 11 cfm 3000 3000 3000 3000
4. Slotted hood? Y-R5, N-R12 YES NO NO NO
5. Slot velocity Chart 11 fpm 2000
6. Slot area R2/R5 sq. ft. 1.2
SLOTS/ 7. Slot VP Chart 7 in. w .g. 0.25
PLENUM 8. Slot entry loss factor 1.78
9. Acceleration factor 1
10. Plenum loss factor 2.78
11. Plenum SP R7*R10 0.7
12. Duct diameter Chart 5 inches 12 8 14 14
13. Duct area Chart 5 sq. ft. 0.7854 0.3491 1.069 1.069
DUCT 14. Duct velocity R2/R13 fpm 3056 2865 3200 3200
15. Duct VP Chart 7 inches 0.58 0.51 0.64 0.64
16. Duct length from plans feet 25 25 40 20
17. Friction R, duct Chart 10 1 2.4 1 1
18. Friction K Chart 5 0.018 0.03 0.015 0.015
19. Friction K, duct R16*R17*R18 0.45 1.8 0.6 0.3
20. Hood entry Chart 11 0.25 0.5 0 0
LOSS 21. Acceleration 1.0 at hoods 1 1 0 0
FACTOR 22. Elbow s Chart 13 0.39 0 1.95 0
K 23. Branch entry Chart 14 ACGIH 0 0.28 0 0
24. System effect Chart 16 0 0 0 0
25. Other K loss 0 0 0 0
26. Total K sum R19-R25 2.09 3.58 2.55 0.3
27. Duct SP R26*R15 inch 1.21 1.83 1.63 0.19
STATIC 28. SP at FROM location R33 inch 0 0 1.91
PRESSURE 29. Jxn. VP change at FROMChart 14 inch 0 0 0.1
30. Other SP loss inch 0 0 4
31. Total SP at TO R11+(R27toR30) inch 1.93 1.83 7.64
32. Is this Governing SP y/n YES NO
JUNCTION 33. Governing SP at TO location inch 1.91
34. Actual Q = [R2*(R33/R31)^0.5 1021
35. SPh [R11+ (R15*(R20+R21))]inch 1.43 0.77HOOD 36. Total slot length plans feet 10
37. Slot w idth 12(R6/R36) inch 1.44