Implications of Renewable Generation on the Power System Performance in Great Britain Professor William Hung MBA, PhD, BSc, CEng FIET Director/WH Power Systems Consultant Ltd Honorary Professor/ University of Warwick Technical Director/ Cardiff University Supergen Offshore Renewable Energy Hub - Annual Assembly – 6 Nov 2019 University of Strathclyde, The Technology and Innovation Centre

Transcript of Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from...

Page 1: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Implications of Renewable Generation on the Power System Performance in Great Britain

Professor William Hung MBA, PhD, BSc, CEng FIETDirector/WH Power Systems Consultant LtdHonorary Professor/ University of WarwickTechnical Director/ Cardiff University

Supergen Offshore Renewable Energy Hub - Annual Assembly – 6 Nov 2019University of Strathclyde, The Technology and Innovation Centre

Page 2: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Presentation Overview

• Background to the change of generation mix

• Power system challenges

• Transmission licence obligations

• Development of frequency control services since industry privatisation

• Background to the RoCoF risk

• Balancing services use of system costs

• Low frequency demand disconnection incidents

• Conclusion

• Way forward

10/15/2015WH PSCL 2

Page 3: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Drivers for Renewable Obligations

Page 4: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Indicative Generation Mix Trend

0

5

10

15

20

25

30

35

40

GW

Gas

Coal

CCS

Wind

Other R

enewable

Nuclear

Interconnectors

Total Connected Generation (GW)

2010 2020 2030 2050

In 2018, wind provides 17.1% of

the UK’s electricity (9.1% from

onshore wind and 8% from offshore

wind, both new annual records).

Overall, renewables generated a

record 33.3%. Low carbon

generation (renewables and

nuclear) reached a record 52.8%.

Nuclear provided 19.5%, with gas

generating 39.4%, and coal

generation dropped to a record

annual low of 5%.

In 2017, wind provided 14.8% of

the UK’s electricity

Page 5: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Power System Challenges -associated with Renewable Generation

• Reduction of system fault level - Protection co-ordination problems

- Excessive voltage dip

- Power quality concerns

- LCC HVDC commutation failure

… But today’s presentation is focus on

• Reduction of system inertia

- Frequency control implications

- Rate of change of frequency (RoCoF) risk

6/11/2019WH PSCL 5

Page 6: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Transmission License Obligations

• Maintain standard of security and quality of supply

• Manage constraints

• Control system frequency and voltage performance

• Maintain system stability

• Limit harmonics and flickers disturbances

• Economic purchase obligations

• Mandatory/commercial services

• System users/service provider commitment

• Grid Code/CUSC compliance

• Mandatory/Commercial Service Agreement

Page 7: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Frequency Control Background

• Frequency control requirements• Statutory limits +/- 0.5 Hz

• Operational limits +/- 0.2 Hz (standard deviations 0.07 Hz)

• Cover instant generation loss was up to 1800MW

• Avoid low frequency demand disconnections (LFDD)• First setting at 48.8 Hz

• If triggered - could be up to 9 stages and 60% load disconnection

• System needs reliable responsive and flexible plant

Page 8: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Typical Frequency Incidents

49.20

49.30

49.40

49.50

49.60

49.70

49.80

49.90

50.00

50.10

12

:24

:00

12

:25

:00

12

:26

:00

12

:27

:00

12

:28

:00

12

:29

:00

Primary Response 0 - 30 secs

Secondary Response 30 secs - 30 mins

freqcont.ppt 009 24/02/99

Page 9: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Frequency Control Analogy

Page 10: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Frequency Control/ Wheel Pulling Analogy

Generators Vehicles

Frequency Wheel speed

Demand level Slope gradient

Load variations Bumpy road

TV pickup Big rock

Largest generation loss Largest truck stalled

Blackout Wheel run away

Page 11: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Improve Frequency Service Provision

• Define frequency services• Primary, Secondary and High Frequency Response services

• Enhanced frequency response and dynamic demand services introduced

• Establish transparent contract format and payment mechanism

• Validate response capability through modelling and testing

• On-line monitoring – gain confidence on service delivery

• Liaise with main plant suppliers and service providers to improve service performance

10/15/2015WH PSCL 11

Page 12: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Primary, Secondary & High Frequency Benchmark Responses

10s 30s 30 mintime

Fre

qu

ency

Ch

ang

e (H

z)P

lan

t R

esp

on

se (M

W)

P

-0.5 Hz

Fre

qu

ency

Ch

ang

e (H

z)P

lan

t R

esp

on

se (M

W)

Frequency fall event

+0.5 Hz

S

H

10s time

Page 13: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

On-line Monitoring Example

Page 14: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Forecast of RoCoF up to 2020

GCRP WG

Traditional Roof protection setting of 0.125 Hz/s but changing to 1 Hz/ is in progress

Page 15: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Balancing Services Use of System Costs

Annual cost of energy balancing, response, reserve and RoCoF could be up to £500m

Page 16: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

System Incident 9 Aug 2019 – overview

• Loss Hornsea 737MW

• Little Barford ST tripped 244MW

• Embedded gen LoM tripped ~500MW

• Frequency fall captured at 49.1 Hz in 25s

• But, Little Barford GT tripped 210MW

• Embedded gen tripped at 49 Hz~200MW

• Freq felt again to 48.8 Hz causing LFDD

• Disconnected 930 MW to restore system

Page 17: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

System Incident 9 Aug 2019 – sequence of events

• Add your first bullet point here

• Add your second bullet point here

• Add your third bullet point here

Page 18: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Low Frequency Automatic Demand Disconnection Incident - 27th May 2008

Page 19: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Conclusion

• The recent frequency incident has raised the public awareness of the importance of a secured power supply system.

• Significant collaborative effort has been made since privatisation between the industry led by National Grid to develop and improve frequency response services through benchmarking, testing and monitoring means.

• The services have therefore been reliable and well defined and I believe the two events discussed here are the only two LFDD incidents within the past 30 years.

• However, the continuous change in system dynamics arising from renewable generation will require more join-up thinking and collaborative effort between the electricity supply utilities, wind farm stakeholder communities and academic researchers to resolve these issues.

10/15/2015WH PSCL 19

Page 20: Implications of Renewable Generation on the Power System ... · the UK’s electricity (9.1% from onshore wind and 8% from offshore wind, both new annual records). Overall, renewables

Way Forward• The Transmission System Operator will continue to maintain a safe, secure,

sustainable and efficient electricity system.

• This is achieved by the effective management of system balancing and operability through encouragement of new innovative service products and competitive market (eg enhanced frequency service from battery energy storage systems, dynamic demand, etc).

• For frequency control management, the erosion of system inertia is one of the main challenges.

• The RoCoF risk could be reduced by the acceleration of the setting change programme. In a longer term, the LoM protection should be replaced by a more reliable and stable alternative or if possible removed.

• For effective frequency containment, the wind farm communities/ academic researchers are invited to address the issue and provide effective solutions .

10/15/2015WH PSCL 20