Implementing ISA101
A Case Study: High Performance,
High Resolution, High Availability
HMI Upgrade
![Page 2: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/2.jpg)
Sunday, June 25, 2017
ISA 101 Overview: The HMI of the Past• Provided an overview of the process
• Many trends throughout Trends Process Values
Alarms Status
![Page 3: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/3.jpg)
Sunday, June 25, 2017
DCS effect on the HMI
• Early DCS displays lost the big picture
• Control via alarms
![Page 4: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/4.jpg)
Sunday, June 25, 2017
DCS graphics evolved
![Page 5: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/5.jpg)
Sunday, June 25, 2017
The HMI Evolves
![Page 6: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/6.jpg)
Sunday, June 25, 2017
What’s so bad about P&ID based graphics?
• Color use inconsistent and unhelpful
• Trends are relegated to a separate screen
• All data no information
• No way to scan screen and determine state of the plant
• Distracting, low value 3D or animated elements
![Page 7: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/7.jpg)
Sunday, June 25, 2017
High performance: Data in context is information
Alarm
High Alarm range
Desired range
Low alarm range
![Page 8: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/8.jpg)
Sunday, June 25, 2017
High Performance: Data in context is information
![Page 9: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/9.jpg)
Sunday, June 25, 2017
High Performance: Trends
![Page 10: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/10.jpg)
Sunday, June 25, 2017
High Performance: Level example
![Page 11: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/11.jpg)
Sunday, June 25, 2017
High Performance: Use of color
• Gray backgrounds are used to minimize glare and provide low contrast depiction to allow alarms to be obvious
• Bright colors are only used for alarms and abnormal situations
• Colors used for alarms are not used elsewhere
![Page 12: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/12.jpg)
Sunday, June 25, 2017
High Performance: Status indication example
RUNNING
RUNNING
RUNNING
![Page 13: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/13.jpg)
Sunday, June 25, 2017
High Performance: Faceplates
PSI
![Page 14: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/14.jpg)
Sunday, June 25, 2017
High Resolution
• Implemented on 43” - 3840 × 2160 monitors
1920 x 1080 1920 x 1080
1920 x 1080 1920 x 1080
![Page 15: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/15.jpg)
Sunday, June 25, 2017
High Resolution
• Each operator will use two
1920 x 1080
1920 x 1080
1920 x 1080
1920 x 1080
1920 x 1080
1920 x 1080
1920 x 1080
1920 x 1080
![Page 16: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/16.jpg)
Sunday, June 25, 2017
HP HMI - Hierarchy
• Level 1 – Process area overview
– At a glance display
• Level 2 – Process Control Unit
– Controllers, Values, Alarms, Trends, Status
• Level 3 – Process Unit Detail
– Small equipment groups
• Level 4 – Diagnostic, Interlocks, First-Outs, Procedures, Documentation
![Page 17: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/17.jpg)
Sunday, June 25, 2017
![Page 18: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/18.jpg)
Sunday, June 25, 2017
High Resolution• Navigation:
![Page 19: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/19.jpg)
Sunday, June 25, 2017
Level 1
![Page 20: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/20.jpg)
Sunday, June 25, 2017
Level 2
![Page 21: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/21.jpg)
Sunday, June 25, 2017
Level 3
![Page 22: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/22.jpg)
Sunday, June 25, 2017
High Availability
Loop 15
CIU - 2LOOP 15
CIU - 1LOOP 15
![Page 23: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/23.jpg)
Sunday, June 25, 2017
High Availability
Loop 15
SCSI SCSI
CIU - 2LOOP 15
CIU - 1LOOP 15
Interface Server:
OPC90 – AInterface Server:
OPC90 – B
COM Redundancy3 CIUs: CIU15A, CIU1A,
CIU11A
![Page 24: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/24.jpg)
Sunday, June 25, 2017
High Availability
Loop 15
SCSI SCSI
OPC Redundancy managed by FTView
CIU - 2LOOP 15
CIU - 1LOOP 15
Horizon View-------------
IDC 1-------------
FT View
Horizon View-------------
IDC 2-------------
FT ViewFT View Server Redundancy managed by FT View
Thin Client Server Redundancy managed by Horizon View
Interface Server:
OPC90 – AInterface Server:
OPC90 – B
COM Redundancy3 CIUs: CIU15A, CIU1A,
CIU11A
![Page 25: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/25.jpg)
Sunday, June 25, 2017
High Availability
Loop 15
SCSI SCSI
Thin Client
Thin Client
Thin Client NIC Redundancy managed by OS
OPC Redundancy managed by FTView
CIU - 2LOOP 15
CIU - 1LOOP 15
Horizon View-------------
IDC 1-------------
FT View
Horizon View-------------
IDC 2-------------
FT ViewFT View Server Redundancy managed by FT View
Thin Client Server Redundancy managed by Horizon View
Horizon View-------------
IDC 1-------------
FT View
Horizon View-------------
IDC 2-------------
FT ViewFT View Server Redundancy managed by FT View
Thin Client Server Redundancy managed by Horizon View
Interface Server:
OPC90 – AInterface Server:
OPC90 – AInterface Server:
OPC90 – BInterface Server:
OPC90 – B
COM Redundancy3 CIUs: CIU15A, CIU1A,
CIU11A
![Page 26: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/26.jpg)
Sunday, June 25, 2017
Operator Buy-in
• Operators miss the color
• Project performed in phases
• Solicit feedback throughout and after project
![Page 27: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/27.jpg)
Sunday, June 25, 2017
Wrap-up
• High Performance
• High Resolution
• High Availability
![Page 28: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/28.jpg)
Sunday, June 25, 2017
For more information
• ANSI/ISA-101.01-2015 - Human Machine Interfaces for Process Automation Systems
![Page 29: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/29.jpg)
Sunday, June 25, 2017
Acknowledgements
• Hollifield, B. R. (2008). The high performance HMI handbook: A comprehensive guide to designing, implementing and maintaining effective HMIs for industrial plant operations. Houston, TX: PAS.
![Page 30: Implementing ISA101 - District Energy](https://reader033.fdocuments.net/reader033/viewer/2022041903/6254c65fbc3655536446effe/html5/thumbnails/30.jpg)
Thank you