IEM1101 ELECTRICAL MULTITASKING
FOR INSTRUMENTATION
![Page 2: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/2.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
IEM1101 Chapter 2
SOCKET OUTLET
![Page 3: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/3.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
LEARNING OBJECTIVES
• At the end of the session, trainees will be able to: a) Identify different types of socket outlets used in
domestic and industrial installation.
b) Perform wiring of a BS 1363 plug and socket outlet.
c) Identify the difference between A1 ring circuit, A2 radial circuit and A3 radial circuit.
d) Perform testing and maintenance of power socket outlets.
![Page 4: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/4.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
All rights reserved. No part of this document may be reproduced, stored in a retrieval system or transmitted in a form or by any means (electronic, mechanical,
photocopying, recording or otherwise) without the permission of the copyright owner. This document has been produced by PETRONAS whether by itself or
through third party consultants and the manner in which this document is used is strictly controlled by PETRONAS.
1. INTRODUCTION
2. DOMESTIC SOCKET OUTLET
3. INDUSTRIAL SOCKET OUTLETS
4. SOCKET OUTLET CIRCUIT
5. TYPES OF CIRCUIT
6. SPURS
7. TESTING OF SOCKET OUTLET
![Page 5: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/5.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
INTRODUCTION
• Socket outlets
– to connect power supply to the load.
– to provide a means of manually remove and connect their appliance.
– can be switched or un-switched.
![Page 6: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/6.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
All rights reserved. No part of this document may be reproduced, stored in a retrieval system or transmitted in a form or by any means (electronic, mechanical,
photocopying, recording or otherwise) without the permission of the copyright owner. This document has been produced by PETRONAS whether by itself or
through third party consultants and the manner in which this document is used is strictly controlled by PETRONAS.
1. INTRODUCTION
2. DOMESTIC SOCKET OUTLET
3. INDUSTRIAL SOCKET OUTLETS
4. SOCKET OUTLET CIRCUIT
5. TYPES OF CIRCUIT
6. SPURS
7. TESTING OF SOCKET OUTLET
![Page 7: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/7.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
DOMESTIC SOCKET OUTLET
• Loads are connected to individual final circuits inside a DB.
• Each of the final circuits will deliver power to lighting circuits, motor circuits and socket outlet circuits.
• Plug and socket outlets are used to connect our daily loads to the final loads.
![Page 8: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/8.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
DOMESTIC SOCKET OUTLET
• BS 1363 socket
– Socket for the fused 13 A rectangular pin plug.
– Widely in domestic and commercial installation in Malaysia.
– The maximum rated - 240 V, 3 kW.
– Suitable for AC supply only.
![Page 9: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/9.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
DOMESTIC SOCKET OUTLET
13 A Socket outlet with plug
![Page 10: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/10.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
DOMESTIC SOCKET OUTLET
• BS 1363 plug
—Plug pins are solid rectangular pins
—Marked with L, N and E
—13 A fuse (BS 1362) connected between the live terminal and the connection point for the live cable.
—No BS 1363 plug with no fuse fitted
—Fuse for appliance’s protection
![Page 11: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/11.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
DOMESTIC SOCKET OUTLET
The internal wiring diagram of a BS 1363 plug
![Page 12: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/12.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
DOMESTIC SOCKET OUTLET
• Socket outlets and plugs
– Switched or un-switched version
– Provide AC supply for domestic installation with rated values of 2 A, 5 A, 13 A and 15 A.
2A socket outlet with plugs and 5A socket outlet with plugs
![Page 13: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/13.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
DOMESTIC SOCKET OUTLET
15 A Socket Outlet and Plug
5 A Socket Outlet and Plug
![Page 14: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/14.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
All rights reserved. No part of this document may be reproduced, stored in a retrieval system or transmitted in a form or by any means (electronic, mechanical,
photocopying, recording or otherwise) without the permission of the copyright owner. This document has been produced by PETRONAS whether by itself or
through third party consultants and the manner in which this document is used is strictly controlled by PETRONAS.
1. INTRODUCTION
2. DOMESTIC SOCKET OUTLET
3. INDUSTRIAL SOCKET OUTLETS
4. SOCKET OUTLET CIRCUIT
5. TYPES OF CIRCUIT
6. SPURS
7. TESTING OF SOCKET OUTLET
![Page 15: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/15.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
INDUSTRIAL SOCKET OUTLET
• BS 196 – Two-pin, non-reversible, with a scraping earth
connection.
– The fuse in the plug - can apply to either pole, or unfused.
– Interchangeability - is prevented by a keyway which may have any of eighteen different positions.
– Available with current ratings of 5 A, 15 A and 30 A.
![Page 16: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/16.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
INDUSTRIAL SOCKET OUTLET
• IBS EN 60309-2
– For industrial application
– Rated at 16A, 30A, 32A, 63A and 125 A.
![Page 17: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/17.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
INDUSTRIAL SOCKET OUTLET
BS EN 60309-2 Industrial Plug and Socket
BS 196 Industrial Pin
![Page 18: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/18.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
SOCKET OUTLET
• Important Points a) All socket outlets in one room must be connected with
the same phase. b) If it is not possible to do so, then the socket outlets must
be grouped together within the same phase. c) The minimum distance between socket outlets from
different phase should be 2 m. d) In order to avoid the socket outlets from being damaged
by cleaning machines, etc., the recommended minimum mounting height is 150 mm above working area.
e) Socket outlets in kitchen area must be covered with lid cover to avoid the sockets from being exposed to splash water.
![Page 19: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/19.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
SOCKET OUTLET
Basic Requirement of Socket Outlet installation
![Page 20: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/20.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
All rights reserved. No part of this document may be reproduced, stored in a retrieval system or transmitted in a form or by any means (electronic, mechanical,
photocopying, recording or otherwise) without the permission of the copyright owner. This document has been produced by PETRONAS whether by itself or
through third party consultants and the manner in which this document is used is strictly controlled by PETRONAS.
1. INTRODUCTION
2. DOMESTIC SOCKET OUTLET
3. INDUSTRIAL SOCKET OUTLETS
4. SOCKET OUTLET CIRCUIT
5. TYPES OF CIRCUIT
6. SPURS
7. TESTING OF SOCKET OUTLET
![Page 21: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/21.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
SOCKET OUTLET CIRCUIT
• The final circuits for 13 A socket outlets fitted with fused plug can be divided into three categories, which are:
a) A1 Ring circuit
b) A2 Radial circuit
c) A3 Radial circuit
![Page 22: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/22.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
SOCKET OUTLET CIRCUIT – RADIAL CIRCUIT
Radial Circuit
![Page 23: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/23.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
SOCKET OUTLET CIRCUIT – RING CIRCUIT
Ring Circuit
![Page 24: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/24.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
All rights reserved. No part of this document may be reproduced, stored in a retrieval system or transmitted in a form or by any means (electronic, mechanical,
photocopying, recording or otherwise) without the permission of the copyright owner. This document has been produced by PETRONAS whether by itself or
through third party consultants and the manner in which this document is used is strictly controlled by PETRONAS.
1. INTRODUCTION
2. DOMESTIC SOCKET OUTLET
3. INDUSTRIAL SOCKET OUTLETS
4. SOCKET OUTLET CIRCUIT
5. TYPES OF CIRCUIT
6. SPURS
7. TESTING OF SOCKET OUTLET
![Page 25: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/25.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
TYPES OF CIRCUIT – A1 RING CIRCUIT
• Requirements
a) Maximum floor area of 100 m2
b) Circuit protection by 30 A or 32 A fuse or MCB
c) The minimum conductor size will 2.5 mm2 for PVC/PVC cable and 1.5 mm2 for MIMS cable.
d) No limit in number of socket outlets and fused spurs used.
![Page 26: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/26.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
TYPES OF CIRCUIT – A2 RADIAL CIRCUIT
• Requirements
a) Maximum floor area of 50 m2
b) Circuit protection by 30 A or 32 A fuse or MCB
c) The minimum conductor size will 4 mm2 for PVC/PVC cable and 2.5 mm2 for MIMS cable.
d) No limit in number of socket outlets and fused spurs used.
![Page 27: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/27.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
TYPES OF CIRCUIT – A3 RADIAL CIRCUIT
• Requirements
a) Maximum floor area of 20 m2
b) Circuit protection by 20 A fuse or MCB
c) The minimum conductor size will 2.5 mm2 for PVC/PVC cable and 1.5 mm2 for MIMS cable.
d) No limit in number of socket outlets and fused spurs used.
![Page 28: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/28.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
TYPES OF CIRCUIT
Type of Circuit
Protective Device
Minimum Conductor (Copper conductor)
Rating PVC/PVC Mineral Insulated
Max. Floor
Area (m2)
A1 Ring 30/32 2.5 1.5 100
A2 Radial 30/32 4 2.5 50
A3 Radial 20 2.5 1.5 20
![Page 29: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/29.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
All rights reserved. No part of this document may be reproduced, stored in a retrieval system or transmitted in a form or by any means (electronic, mechanical,
photocopying, recording or otherwise) without the permission of the copyright owner. This document has been produced by PETRONAS whether by itself or
through third party consultants and the manner in which this document is used is strictly controlled by PETRONAS.
1. INTRODUCTION
2. DOMESTIC SOCKET OUTLET
3. INDUSTRIAL SOCKET OUTLETS
4. SOCKET OUTLET CIRCUIT
5. TYPES OF CIRCUIT
6. SPURS
7. TESTING OF SOCKET OUTLET
![Page 30: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/30.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
SPURS
• Used where a socket is required at a point away from the run of the ring circuit cables
• Can be of fused spur and non-fused spur.
• For non-fused spur, it must not supply more than:
a) Two single socket outlets
b) One double socket outlet
c) One stationary appliance
![Page 31: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/31.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
SPURS
• The number of spurs must not exceed the number of socket outlets in the main ring.
• For non-fused spurs, they can be connected from:
a) A socket outlet on the ring circuit.
b) A junction box connected to the ring
c) The consumer unit or DB
![Page 32: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/32.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
SPURS
Non-fused spur connected from a 13 A socket outlet
![Page 33: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/33.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
SPURS
Non-fused spur connected from a junction box
![Page 34: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/34.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
SPURS
Non-fused spur from a distribution board
![Page 35: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/35.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
Example of Spurs connection
![Page 36: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/36.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
All rights reserved. No part of this document may be reproduced, stored in a retrieval system or transmitted in a form or by any means (electronic, mechanical,
photocopying, recording or otherwise) without the permission of the copyright owner. This document has been produced by PETRONAS whether by itself or
through third party consultants and the manner in which this document is used is strictly controlled by PETRONAS.
1. INTRODUCTION
2. DOMESTIC SOCKET OUTLET
3. INDUSTRIAL SOCKET OUTLETS
4. SOCKET OUTLET CIRCUIT
5. TYPES OF CIRCUIT
6. SPURS
7. TESTING OF SOCKET OUTLET
![Page 37: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/37.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
TESTING OF SOCKET OUTLET
• To ensure that the equipment is up to its relevant standard.
• To ensure the equipment is not damaged and accidents due to faulty equipment can be avoided.
![Page 38: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/38.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
TESTING OF SOCKET OUTLET
• Electrical tests - live test and dead test.
• Live test – On energized equipment/connected to the supply
– Involved in circuit ratings and parameters(e.g current, voltage and power)
• Dead test – Before the equipment connected to the supply
– Checks for the integrity of the circuit( e.g continuity test)
![Page 39: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/39.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
TESTING OF SOCKET OUTLET
• Power socket outlet tests are:
a) Continuity test (dead test)
b) Polarity test (live test)
![Page 40: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/40.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
CONTINUITY TEST
• is a dead test
• to check the integrity of all conductors, including the earth continuity conductor.
• to ensure if there is a path between two points.
![Page 41: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/41.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
CONTINUITY TEST
Equipment Good continuity Bad continuity
(Open circuit)
Ohmmeter Low reading of ohm
(0 ~ 1 ohm)
High reading of ohm
(~ M ohm)
Buzzer tester Sound is produced No sound produced
Lamp tester Light is produced No light or a very dim
light is produced.
![Page 42: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/42.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
CONTINUITY TEST
A typical multimeter, with ohmmeter and buzzer tester
A typical lamp continuity tester.
![Page 43: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/43.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
RADIAL CIRCUIT CONTINUITY TEST
• Turn off the main supply • Identify the circuit breaker or fuse for the socket
outlet circuit. • Connect the outgoing live conductor with a
temporary link using a small cable to the neutral terminal block inside the installation’s DB.
• Connect one of the test probes to the live terminal of the tested socket, and the other to the neutral terminal of the socket.
• Repeat the tests for neutral-earth terminals and live-earth terminals.
![Page 44: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/44.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
RADIAL CIRCUIT CONTINUITY TEST
Radial circuit continuity test using an ohmmeter
![Page 45: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/45.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
RING CIRCUIT CONTINUITY TEST
Method 1 • Turn off the main supply. • Identify the circuit breaker or fuse for the socket
outlet circuit. • Disconnect and separate the live conductors for
the socket outlet circuit. • Using the appropriate tester, test the continuity
between the two conductors. • Repeat the test for neutral and earth conductors
for the socket outlet circuit.
![Page 46: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/46.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
RING CIRCUIT CONTINUITY TEST
Method 1 for ring circuit continuity test
![Page 47: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/47.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
RING CIRCUIT CONTINUITY TEST
Method 2 • Turn off the main supply. • Identify the circuit breaker or fuse for the socket outlet
circuit. • Disconnect and separate the live and neutral conductors for
the socket outlet circuit. • Cross connect the conductors. • Using the appropriate tester, test the continuity between
the live and neutral phase at each socket outlets. • Repeat the test for other conductors for the socket outlet
circuit.
![Page 48: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/48.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
RING CIRCUIT CONTINUITY TEST
Method 2 for ring circuit continuity test
![Page 49: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/49.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
POLARITY TEST
• Live test
• To verify the connections of the conductor connected to the equipment.
• For socket outlet - to ensure the terminals are connected to the correct conductors to avoid accidents.
• Using a socket outlet tester, or a voltmeter,
![Page 50: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/50.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
POLARITY TEST – SOCKET OUTLET TESTER
• Ensure the power is supplied to the socket outlet circuits.
• Connect the socket outlet tester to the socket.
• Turn on the switch of the socket outlet (for switched socket outlets).
• Record the observation indicated by the socket outlet tester.
• Repeat for other socket outlets.
![Page 51: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/51.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
POLARITY TEST – SOCKET OUTLET TESTER
Socket Outlet Tester
![Page 52: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/52.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
POLARITY TEST – VOLTMETER
• Ensure the power is supplied to the socket outlet circuits.
• Set the voltmeter to AC voltage range
• Connect the probes to the live and neutral terminals of the socket outlet. The voltage reading should be around 230 V ~ 240 V.
• Connect the probes to the live and earth terminals of the socket outlet. The voltage reading should be around 230 V ~ 240 V.
• Connect the probes to the earth and neutral terminals of the socket outlet. The voltage reading should be around 0 V.
![Page 53: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/53.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)
POLARITY TEST – VOLTMETER
Connection of Voltmeter
![Page 54: Iem 1101 Ch2 (Socket Outlet_edit)](https://reader034.fdocuments.net/reader034/viewer/2022042717/563db8d9550346aa9a978878/html5/thumbnails/54.jpg)
© 2012 PETROLIAM NASIONAL BERHAD (PETRONAS)