WG PC37.011 - Meeting May 2011 1 1 IEEE WG Revision C37.011 Application Guide for TRV for High-Voltage Circuit Breakers Agenda of WG meeting in Orlando/Lake Buena Vista, May 18 th 2011 Introduction of Members & Guests IEEE SA Bylaws on Patents Minutes of meeting in Las Vegas Reminder: ballot of draft D7 Resolution of comment 76 (TRV interpolation) Resolution of non critical comments (input by e mail) Resolution of remaining comments Next steps Denis Dufournet Chair WG C37.011

Transcript of IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011...

Page 1: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 20111 1

IEEE WG Revision C37.011Application Guide for TRV for High-Voltage Circuit Breakers

Agenda of WG meeting in Orlando/Lake Buena Vista, May 18th 2011

Introduction of Members & Guests

IEEE SA Bylaws on Patents

Minutes of meeting in Las Vegas

Reminder: ballot of draft D7

Resolution of comment 76 (TRV interpolation)

Resolution of non critical comments (input by e mail)

Resolution of remaining comments

Next steps

Denis Dufournet

Chair WG C37.011

Page 2: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 20112 2

(First) Ballot Open Date:02-Jul-2010

Ballot Close Date:08-Aug-2010

112 eligible people in the ballot group (72 in 2004, previous revision)

98 votes received = 87% returned, > 75%: requirement is met

89 affirmative votes 92% affirmative, requirement is met

7 negative votes with comments

0 negative votes without comments

2 abstention votes

Ballot of draft D7

Page 3: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 20113 3

General overview on negative votes

4 mainly based on minor technical / editorial comments

1 with technical comments that can be easily accepted

2 with comments that need a WG discussion

Main issue

Interpolation of TRV withstand capabilities between T30 and T60

Comments

181 comments

Ballot of draft D7

Page 4: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 20114 4

Discussion of Comments on D7

Comment # 76

Subclause 4.2

Comment

This subclause talks about Circuit breaker capability. it is assumed to be

the required TRV as defined by the system. This is understood and technically sound for the interpolation between T10 and T30 as well as for the interpolation between T60 and T100. However the transition from 2 parameter ( T30) to 4 parameter (T60) is not understood. It is understood

that the first freq. is defined by a transformer, inductance close to the breaker while the second freq. is given by the traveling wave. In this case the peak voltage of the first frequency ( u1) should be always in the same order of magnitude, while the time to Uc may change

Proposed change

Develop a more technical sound method to interpolate between T30 and

T60.

Page 5: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 20115 5

Discussion of Comments on D7

Comment # 76

Resolution

Two methods to interpolate TRVs between T30 and T60, selected during the meeting in Las Vegas (see next slide)

Approach 1 as defined in the present draft (u1 is interpolated between u1 of T60 and uc of T30)

Approach 2 as discussed in Las Vegas, with u1 constant between T30 and T60

Discussion done by WG in November-December 2010 and April-May

2011

Page 6: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 20116 6

Discussion of Comments on D7

Resolution of Comment # 76

Approach 1

Page 7: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 20117 7

Discussion of Comments on D7

Resolution of Comment # 76

Approach 2

Page 8: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 20118 8

Discussion of Comments on D7

Resolution of Comment # 76

What is the issue?

It is the TRV withstand by a circuit breaker that can be expected after current zero until a time up to (approximately) t3 for T30.

0

50

100

150

200

250

300

0 10 20 30 40 50 60

Comparison of the approaches

in case of T40 145kV kpp =1.5

T(µs)

TRV withstand

(kV)

Approach 1

Approach 2

Page 9: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 20119 9

Discussion of Comments on D7

Resolution of Comment # 76

Comparison of the TRV for T30 and the two approaches for T40

0

50

100

150

200

250

300

0 10 20 30 40 50 60

Comparison of the approaches

in case of T40 145kV kpp =1.5

T(µs)

TRV withstand

(kV)

T40 Approach

1

T40 Approach

2

T30

Page 10: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201110 10

Discussion of Comments on D7

Comment # 76

Resolution by WG vote

17 in favour to keep the approach 1 of Draft 7

1 in favour to adopt approach 2 with a constant u1 between T30 and T60

1 abstention

Approach 1 will be kept in the next draft.

Page 11: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201111 11

Discussion of Comments on D7

Comment # 142

Subclause Table 2 page 32

Comment

On page 31 it explains that the first-pole-to-clear factors considered in

Table 2 are 1.5 for 120 and 161 kV and 1.3 for 230, 315 and 735 kV. This should be in a note for Table 2 so the user can quickly see this detail without have to look in the text for it.

Proposed change

Add a NOTE to Table 2: "The first-pole-to-clear factors considered are 1.5 for 120 kV and 161 kV, and 1.3 for 230 kV, 315 kV and 735 kV."

Resolution status

Accepted

Resolution detail

a note will be added to give the values of the first-pole-to-clear and to explain the meaning of d and Z. Rated voltages will be used.

Page 12: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201112 12

Discussion of Comments on D7

Comment # 144

Subclause 4.2.4.7

Comment

In line 16 the term "short-line fault" is spelled out and in line 18 the abbreviation SLF is used. Not sure when SLF is defined for the first time, but the term should be handled consistently.

Proposed change

Consistantly use "short-line fault" of SLF within the text.

Resolution status

Accepted

Resolution detail

“short-line fault” will be used here.

The use of SLF will be checked in the document.

Page 13: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201113 13

Discussion of Comments on D7

Comment # 153

Subclause Annex A.2 Table A.2

Comment

Add typical surge impedance for 170kV overhead lines in Table A.2.

Proposed change

Here are surge impedance values for 3 different 161kV line configurations.

161-kV Horizontal config on steel towers:

Xseries = 0.7366 ohms/mile

Yshunt = 5.800/10^6 = mhos/mile

Zc = sqrt(0.7366/[5.800/10^6]) = 356.37 ohms

161 kV H-frame steel-pole line:

Xseries = 0.7390 ohms/mile

Yshunt = 5.849/10^6 = mhos/mile

Zc = sqrt(0.7390/[5.849/10^6]) = 355.45 ohms

161 kV Double circuit steel-pole line with both sides strung:

Xseries = 0.7417 ohms/mile

Yshunt = 5.779/10^6 = mhos/mile

Zc = sqrt(0.7417/[5.779/10^6]) = 358.25 ohms

Page 14: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201114 14

Discussion of Comments on D7

Comment # 153 (Cont’d)

Resolution status

Accepted in principle

Resolution detail

In the second column 145kV will be replaced by 145/170 kV

Page 15: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201115 15

Discussion of Comments on D7

Comment # 154

Subclause Annex B page 70

Comment

Add capacitance values for other voltage CVTs.

Proposed change

Capacitances of commercially available 170kV CVTs range from 4000 to 16000 pF. I'll provide info to the WG Chair for available CVTs.

Resolution status

Accepted

Resolution detail

Values for 170kV will be added and values will be updated.

Page 16: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201116 16

Discussion of Comments on D7

Comment # 157

Subclause Figure 2 page 5

Comment

add "at T100" after "cable-system TRV"

Proposed change

change to "Figure 2-Comparison of line-system TRV and cable-system TRV at T100"

Resolution status

Not accepted

Resolution detail

It will be indicated that time is in µs and TRV is in kV

Page 17: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201117 17

Discussion of Comments on D7

Comment # 158

Subclause 4.2.1 page 13

Comment

In the top figure, change "2.106" to "2.107" to be consistent with the multiplier Ku1 at T30 for 100 kV and above breakers in Table 1.

Proposed change

In the top figure, change "2.106" to "2.107" to be consistent with the multiplier Ku1 at T30 for 100 kV and above breakers in Table 1

Resolution status

Accepted in principle.

Resolution detail

The numbers will be given with 3 significant digits.

Page 18: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201118 18

Discussion of Comments on D7

Comment # 166

Subclause Figures 22a and 22b page 33

Comment

In Figure 22a, change one of the solid red curves and one of the solid blue curves to dash lines for easier identifications.

Proposed change

In Figure 22a, change one of the solid red curves and one of the solid blue curves to dash lines for easier identifications

Resolution status

Accepted

Resolution detail

The figure will be modified as proposed.

Page 19: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201119 19

Discussion of Comments on D7

Comment # 167

Subclause 4.2.4.10 page 34

Comment

change "special customized tests or other means may be required" to "special customized tests or other means should be required". This is consistent with CIGRE WG A3.19 report that "Utilities for whom this position is unacceptable should request special type tests for the particular conditions" and is consistent with our company's emphasis on safety.

Proposed change

change "special customized tests or other means may be required" to "special customized tests or other means should be required". This is consistent with CIGRE WG A3.19 report that "Utilities for whom this

position is unacceptable should request special type tests for the particular conditions" and is consistent with our company's emphasis on safety.

Page 20: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201120 20

Discussion of Comments on D7

Comment # 167 (Cont’d)

Resolution status

Not accepted

Resolution detail

The text will be changed to "special customized tests or other means can be specified"

Page 21: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201121 21

Discussion of Comments on D7

Comment # 173

Subclause 1.1 page 10

Comment

calculation should be plural

Proposed change

change "calculation" to "calculations"

Resolution status

Not accepted

Resolution detail

The scope cannot be changed (without changing the PAR). The wording is

taken from the existing standard.

Page 22: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201122 22

Discussion of Comments on D7

Comment # 86

Subclause 3.3.1

Comment

C37.04 Subclause 5.9 states "At the rated maximum voltage, each circuit breaker shall be capable of interrupting three phase grounded and ungrounded terminal faults at the rated short circuit current in any circuit in which the TRV does not exceed the rated TRV envelope." The document needs a statement related to terminal faults in a three phase common gas-insulated switchgear enclosure.

Proposed change

In the case of a three phase common gas-insulated switchgear enclosure, an arc between phase and ground will, within a few milliseconds, evolve into a three phase fault between conductors, owing to the ionization of the gap between the conductors, and at the same time the phase to ground arc will extinguish. Consequently, an enclosure burn-through is not likely. Since within the range of 20-50ms the fault has evolved into a three phase ungrounded fault, and since the breaker contacts typically begin to part at or after 50ms, then the three phase ungrounded fault should be considered in TRV analysis for three phase common gas-insulated switchgear enclosures.

Page 23: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201123 23

Discussion of Comments on D7

Comment # 86

Subclause 3.3.1

Resolution

Accepted in principle

Resolution detail

The following text will be added:

For GIS with all three phases in one enclosure a grounded fault can

evolve into a three-phase ungrounded fault prior to interruption. The user should choose the appropriate first pole to clear factor i.e. kpp=1.5 for three-phase ungrounded faults.

Page 24: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201124 24

Discussion of Comments on D7

Comment # 102

Subclause 4.2.4.1 page 21

Comment

I have not seen any documentation that relates the 450ohm surge impedance with conductor clashing. Many tests have been done to cause conductor clashing without success. It is very rare and therefore the 450ohm surge impedance has no relevance to clashing.

Proposed change

Remove all instances where the 450ohm surge impedance is related to conductor clashing.

Resolution status

Not accepted

Page 25: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201125 25

Discussion of Comments on D7

Comment # 102

Resolution detail

Early editions of international standards (ANSI/IEEE and IEC) for HV circuit breakers have values of (line) surge impedance that were lower

than 400 ohms in case of bundle conductors, due to their geometry. Studies made at the end of the 1960's-beginning of the 1970's showed that if conductors clash during a short-circuit then the surge impedance rise to a value approaching 450 ohm as the bundle can then approximated by a single conductor. This studies lead to the generalization of the 450

ohm value in the full voltage range, in both IEC and ANSI/IEEE standards (previously IEC had 375 Ω for 2 conductors/phase and 330 Ω for 3 or 4 conductors per phase, ANSI/IEEE had similar values for bundled conductors: 360 ohm for 362kV and above).

Information on conductor clashing can be found in particular in "Surge impedance of overhead lines with bundle conductors during short-line

fault". Electra N°17 , published in April 1971. The conclusion of the paper is as follows: "When the conductors are clashed together, these surge impedances will take a value of approximately 450 ohm whatever the number of conductor in bundle may be".

Page 26: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201126 26

Discussion of Comments on D7

Comment # 102

Resolution detail (Cont’d)

Link between the generalization of 450ohm and bundle contraction can also be found in CIGRE Technical Brochure 305 (page 37).

This matter has been recently reviewed by CIGRE WG A3-22 for the specification of the surge impedance of lines in 1100 kV networks. Due to

their large geometry and weight it has been concluded that conductor clashing cannot occur in this case, so that the surge impedance had to be reduced to 330 ohm.

In case of multi-conductors per phase, conductor clashing is the assumption behind the 450 ohm value, the guide presents the existing situation, if later on standards are revised with a different assumption (leading to a lower value of the surge impedance) then this guide will be

aligned.

Page 27: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201127 27

Discussion of Comments on D7

Comment # 103

Subclause 4.2.4.1 page 17

Comment

An assumption is implied that the majority of cases has short lines with X0 being 2 to 3 times larger than X1. This is not necessarily true and should be removed.

Proposed change

Remove this assumption.

Resolution status

Not accepted

Resolution detail

The text is correct, this is generally true. It should be reminded that effectively grounded systems have by definition a ratio X0/X1 equal or lower than 3.

Page 28: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201128 28

Discussion of Comments on D7

Comment # 104

Subclause 4.2.4.4 page 28

Comment

Remove reference to bundle clashing, it is not a proven phenomenon that affects these calculations.

Proposed change

Remove the reference to bundle clashing.

Resolution status

Not accepted

Resolution detail

See resolution to comment 102.

Page 29: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201129 29

Discussion of Comments on D7

Comment # 105

Subclause 4.2.4.5 page 30

Comment

450ohm surge impedance is not over-specified and is bundle clashing is not common and should not be referenced to the 450ohm surge impedance.

Proposed change

Remove this whole paragraph as it does not provide any useful information.

Resolution status

Not accepted

Resolution detail

See resolution to comment 102.

Page 30: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201130 30

Discussion of Comments on D7

Comment # 106

Subclause 4.2.4.7 page 32

Comment

The CIGRE study referenced is highly controversial and it conclusion are not widely accepted by users who would be using this guide. Thisdocument is not written to show that testing is sufficient for all cases and therefore all references to that effect should be removed. In reading this document it appears to be pointing to tests that cover certain fault cases. This guide is to help evaluate the system and not testing.

Proposed change

Remove the reference and conclusions of the highly controversial CIGRE study.

Resolution status

Not accepted

Page 31: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201131 31

Discussion of Comments on D7

Comment # 106

Resolution detail

Concerning the reference to CIGRE: see resolution to comment #109

This subclause explains the influence of the short-circuit power of the source on the TRV for a given current. There is nothing controversial about this as explained in the answer to comment #107.

When the short-circuit power of the source is reduced, a given fault current, e.g. 90% or 75% of rated short-circuit current, is obtained with a

shorter length of line, as a consequence the TRV peak is lower (RRRV is the same but the time to peak related to the travel time of the wave is shorter). When the short-circuit power of the source is reduced, for the same length of faulted line the fault current is lower and as a consequence the TRV peak is lower (RRRV is lower as it is proportional to current, and

the time to peak is unchanged). This subclause could be developed further to explain this. What is explained here is pure physics and cannot be contested.

Page 32: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201132 32

Discussion of Comments on D7

Comment # 107

Subclause Figures 22a & 22b page 33

Comment

These graphs are relevant in C37.09 not in an application guide. These are conclusions drawn by a highly controversial CIGRE study.

Proposed change

Remove both figures.

Resolution status

Not accepted

Page 33: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201133 33

Discussion of Comments on D7

Comment # 107

Resolution detail

Figures are better than a thousand words, they illustrate in a clear way that for a given fault current, the amplitude of the first peak of TRV is

greatly influenced by the short-circuit power of the source. This is relevant in a Guide on TRVs in which the influence of different parameters on TRVs is explained. There is nothing controversial about this (as well as other parts of the CIGRE study), it could be proven also by a simplified calculation that the Chair will be happy to provide, if necessary.

These figures have nothing to do with testing and would be of no interest in C37.09.

Page 34: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201134 34

Discussion of Comments on D7

Comment # 108

Subclause 4.2.4.10 page 34

Comment

This clause appears to be the conclusion of the comparison added to the document. This is not the place to repeat a highly controversialconclusion. This guide should show how to calculate/determine the system TRV and compare it to the TRV testing. Anything beyond that uses assumptions and rationals that are controversial and not proven by tests.

Proposed change

Remove the clause.

Resolution status

Not accepted

Page 35: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201135 35

Discussion of Comments on D7

Comment # 108

Resolution detail

After the explanations given in the previous subclauses, the aim of this one is to draw the attention of the reader to a few important aspects that

need to be taken into consideration, in particular when writing specifications, to avoid unrealistic demands. Experience shows that there is some misunderstanding concerning the TRVs during three-phase terminal faults (kpp= 1.5 is not applicable to the last pole to clear), such misunderstanding must be avoided also in the case of three-phase line faults.

The reader of the guide must understand that a peak factor (d) higher than

2 is only possible when there is coupling between phases, and therefore cannot be requested for the last-pole-clear and the relevant arcing times (no coupling possible when the other lines are opened).

This has nothing to do with testing, but is about the understanding of thee-phase line fault TRVs. The wording can be improved but this must be covered here.

Page 36: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201136 36

Discussion of Comments on D7

Comment # 109

Subclause reference B19 page 81

Comment

This is highly controversial and does not belong in the document.

Proposed change

Remove this reference.

Resolution status

Not accepted

Page 37: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201137 37

Discussion of Comments on D7

Comment # 109

Resolution detail

The reference to CIGRE Technical Brochure 408 will be kept as itrepresents the most comprehensive and recent study on line fault

phenomena and their implications for 3-phase short and long line fault clearing. It is useful to the reader who wants to have a deep understanding of these phenomena.

CIGRE is a world renowned organization that thoroughly checks the content of its publications. The document was submitted to the members of the CIGRE study committee A3 and approved before publication.

In TB 408 CIGRE gives technical information and refrains from making recommendation on standardization work. The view expressed in the comment is personal and not accepted.

The reference is also needed as text and Figures are taken from [B18] (formerly B19).

Page 38: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201138 38

Discussion of Comments on D7

Next steps/Actions

The file of comments made during the ballot of Draft 7 will be updated with the resolutions decided during the meetings in Las Vegas and Lake Buena

Vista. It will be sent to WG members (Denis).

Prepare a new draft that takes into account the resolutions on comments (Denis)

The revised draft will be sent to WG members to check that the changes reflect the resolutions (All).

Helmut will send a proposal to revise the TLF section (Helmut).

Roy will provide a text to comment on range on CVT capacitance values in

Table B.4 (Roy).

The new draft for recirculation will be D9

Recirculate D9 preferably between mid-August and mid-September on order to have votes and comments available for the next WG meeting in October 2011 (Denis).

The comments made during recirculation will be sent before the next WG meeting in October (Denis).

Page 39: IEEE WG Revision C37.011 Application Guide for TRV for ...€¦ · 4 WG PC37.011 - Meeting May 2011 4 Discussion of Comments on D7 Comment # 76 Subclause 4.2 Comment This subclause

WG PC37.011 - Meeting May 201139 39

Thanks for your participation !

IEEE WG C37.011Application Guide for TRV for High-Voltage Circuit Breakers