IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND...
Transcript of IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND...
![Page 1: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/1.jpg)
IEEE DESIGN TEST REPORT
Report No. TD 01 057 E00
Type PDV 65 ND Distribution Class
Surge Arrester This report records the results of the design tests made on Type PDV65 Normal Duty Distribution
Class surge arresters in accordance with IEEE Standard C62.11-2012 “IEEE Standard for Metal
Oxide Surge Arresters for AC Power Circuits (> 1kV)”.
Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the
relevant clauses of the referenced standard and apply to all Hubbell PDV65 ND Distribution
arresters of this design manufactured and assembled at the following ISO 9001:2008 certified
Hubbell locations:
Hubbell Power Systems Hubbell Electric (Wuhu) Company, Ltd.
1850 Richland Avenue, East Exports Processing Zone, No 68
Aiken, South Carolina North Jiuhua Road, Wuhu City
29801 Anhui Province, PR China
The above locations manufacture, assemble, and test utilizing manufacturing, quality, and
calibration procedures developed from Hubbell Engineering Department Specifications.
Engineering Department Specifications are controlled by Arrester Business Unit design
engineering in the USA.
Dennis W. Lenk
Principal Engineer
Date: 4/01/2016
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
Separate reports provide details of the tests, according to the following table:
Report No. Description Clause Issue Date
TD 01 057 E01 Insulation Withstand 8.1 4/01/2016
TD 01 057 E02 Discharge Voltage 8.2 4/01/2016
TD 01 057 E03 Disc Accelerated Aging 8.5 4/01/2016
TD 01 057 E04 Polymer Accelerated Aging 8.6 4/01/2016
TD 01 057 E05 Salt Fog Accelerated Aging 8.7 4/01/2016
TD 01 057 E06 Verification of Thermally Prorated Section 7.2.2 4/01/2016
TD 01 057 E07 Arrester Seal Integrity Test 8.9 4/01/2016
TD 01 057 E08 Partial Discharge 8.11 4/01/2016
TD 01 057-E09 High Current, Short Duration 8.12 4/01/2016
TD 01 057 E10 Low Current, Long Duration 8.13 4/01/2016
TD 01 057-E11 Duty Cycle 8.16 4/01/2016
TD 01 057 E12 Temporary Overvoltage 8.17 4/01/2016
TD 01 057 E13 Short Circuit for Polymer-Housed Arrester 8.18 4/01/2016
TD 01 057 E14 Arrester Disconnector Tests 8.21 4/01/2016
TD 01 057 E15 Maximum Design Cantilever Load-Static 8.22 4/01/2016
![Page 2: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/2.jpg)
TD 01 057 E01 - 2 -
IEEE TYPE TEST REPORT
Report No. TD 01 057 E01
Type PDV65
ND Distribution Class Arrester
Insulation Withstand Test
CERTIFICATION
This is to certify that the polymer accelerated aging design tests have been successfully
performed on Ohio Brass Type PDV65 Normal Duty Distribution Class surge arresters.
Dennis W. Lenk
Principal Engineer
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
Date: 4/01/2016
Attachment
Type PDV65 Normal Duty Distribution Arrester
![Page 3: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/3.jpg)
TD 01 057 E02 - 3 -
Insulation Withstand Clause 8.1
Introduction: Table 1 summarizes polymer housing minimum leakage and strike
distances for each arrester rating, and 60 Hz and impulse withstand requirements for each
housing size as specified in Section 8.1.2.1a) and b) of C62.11-2012. In all cases, the
actual withstand values of each arrester housing exceed the minimum values specified in
the Standard. Table 1
Insulation Withstand Voltage Requirements of PDV-65 Arresters.
Catalog #
Rating kV rms
MCOV kV rms
Arrester Strike
w/Brkt mm
Arr Total
Ht W/Brkt
US Hrdwr-
mm
8/20 20 kA IR kVc
Reqd BIL WS kVc
Actual Imp WS
Arr w/Brkt
kVc
Reqd 10 second
wet power
frequency WS kVc
Actual 10 second wet WS
Arr W/Brkt
kVc
217253 3 2.55 200 236 12 17 125 7 34
217255 6 5.1 200 236 24 34 125 14 34
217258 9 7.65 200 236 34.9 50 125 21 34
217259 10 8.4 200 236 38.8 55 125 23 34
217560 12 10.2 200 236 46.5 66 125 28 34
213263 15 12.7 290 312 58.9 84 175 35 55
213265 18 15.3 290 312 69.7 99 175 42 55
213267 21 17 290 312 78.5 111 175 46 55
217570 24 19.5 330 373 92.9 132 195 53 65
213272 27 22 405 450 104.6 149 230 60 85
213274 30 24.4 405 450 116.2 165 230 67 85
213279 36 29 450 527 139.4 198 250 79 100
Per Section 8.1.2.1c), the insulating support bracket exceeded the required 10 second wet
withstand requirements per Table 2.
Table 2
Bracket Assy
Part #
Arrester
MCOV
Bracket
size
Required 10 second wet
withstand kVrms
Actual 10 second wet
withstand kVrms
273206 2.55-10.2 Small 15.3 30
274334 12.7-17 Medium 25.5 35
273207 19.5-29 Large 43.5 45
Conclusion: In all cases, the actual withstand values shown for each arrester rating
exceed the minimum values specified in the Standard.
![Page 4: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/4.jpg)
TD 01 057 E02 - 4 -
IEEE Type Test Report
Report No. TD 01 057 E02
Type PDV65
ND Distribution Class Arrester
Residual Voltage Test
CERTIFICATION
This is to certify that the polymer accelerated aging design tests have been successfully
performed on Ohio Brass Type PDV65 Normal Duty Distribution Class surge arresters.
Dennis W. Lenk
Principal Engineer
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
Date: 4/01/2016
Attachment
IEC Type Test Report
![Page 5: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/5.jpg)
TD 01 057 E03 5
RESIDUAL VOLTAGE TESTS
IEEE CLAUSE 8.2
Sample Preparation
Residual voltage tests were performed on three 29mm x 42.8 mm MOV discs.
Test Procedure
The following tests were performed per Section 8.2 of C62.11-2012 on each sample.
Each sample was allowed to cool to ambient temperature between discharges.
1. Steep Current Impulse Residual Voltage Test: 1/2 µs, 5 kA;
2. Lightning Impulse Residual Voltage Test: 8/20 µs, 1.5, 3, 5, 10, 20 kA;
3. Switching Impulse Residual Voltage Test: 30-100/60-200 µs and 500 A.
Test Results
Each of the three test samples was subjected to a 5 kA, 1/2 µs steep current impulse with
and without an aluminum disc with the same geometry of the MOV disc. The difference
in the residual voltages is the inductive drop across the MOV disc. Figures 1a and 1b
show the oscillograms of the measured FOW residual voltage discharges of Sample 2
without and with an aluminum spacer, respectively.
Figure 1a: Sample 2, 5.036 kA, 18.836 kV w/o Aluminum spacer.
![Page 6: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/6.jpg)
TD 01 057 E03 6
Figure 1b: Sample 2, 5.059 kA, 18.885 kV with Aluminum spacer.
Each sample was then subjected to 1.5, 3, 5, 10, 20 and 40 kA lightning surge impulses.
Figures 2 thru 7 show the oscillogram for each of the referenced 8/20 discharge current
levels on Sample 2.
Figure 2: Sample 2 , 1.513 kA, 15.108 kV.
![Page 7: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/7.jpg)
TD 01 057 E03 7
Figure 3: Sample 2 , 3.044 kA, 16.179 kV.
Figure 4: Sample 2 , 5.022 kA, 17.304 kV.
![Page 8: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/8.jpg)
TD 01 057 E03 8
Figure 5: Sample 2 , 10.017 kA, 19.367 kV.
Figure 6: Sample 2 , 19.987 kA, 22.447 kV.
![Page 9: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/9.jpg)
TD 01 057 E03 9
Figure 7: Sample 2 , 39.906 kA, 27.912kV.
Each sample was then subjected to 500 A switching surge impulse. Figure 8 shows the
oscillogram of the switching surge discharge of Sample 2.
Figure 8: Sample 2, 507.7 A, 13.608 kV.
Table 1 shows the 5 kA IRs of the steep front wave measured on the three test samples
with and without the aluminum disc. Since the measured spacer inductive drop is less
than 2% of the MOV disc recorded FOW residual voltage, the inductive drop of the
MOV disc can be disregarded
![Page 10: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/10.jpg)
TD 01 057 E03 10
Table 1: Measurement of Inductive effect on MOV discs
Sample No. I (kA) IR (KVpk)
with Al disc
IR (KVpk)
w/o Al disc
Al disc
L(di/dt)
effect (kV)
Recorded MOV disc
FOW voltage drop
(kV)
1
5
18.918 18.918 0 18.918
2 18.885 18.836 .049 18.885
3 18.902 18.853 .049 18.902
Table 2 summarizes the design factors used to extrapolate the 1.5 through 40 kA 8/20
residual voltage, the 500 amp switching surge residual voltage, and MOV disc .5
microsecond FOW residual voltage. The highest factor for each wave shape is shown
bolded and is multiplied by the 5 kA residual voltage of each rating to develop the family
of residual voltage values. Table 3 summarizes the residual voltage values measured and
claimed for each arrester rating.
Table 2: Residual Voltage Test.
Impulse
Current
(kA)
Wave
Shape
(µs)
Discharge Voltage (kVpk)
Discharge Voltage Ratio
(IR/10kV IR)
Sample
1
Sample
2
Sample
3
Sample
1
Sample
2
Sample
3
0.5 43/91 13.608 13.608 13.581 0.788 0.786 0.784
1.5 8/20 15.215 15.108 15.161 0.881 0.873 0.875
3 8/20 16.206 16.179 16.179 0.938 0.935 0.934
5 8/20 17.277 17.304 17.331 1.000 1.000 1.000
10 8/20 19.447 19.367 19.447 1.126 1.119 1.122
20 8/20 22.474 22.447 22.34 1.301 1.297 1.289
40 8/20 28.046 27.912 28.18 1.623 1.613 1.626
5
1/2
(w/o
inducti
ve
effect) 18.918 18.885 18.902
1.095 1.091 1.091
Table 3: Summary of Arrester Discharge Voltages
Uc Ur
IR Factors 0.788 0.881 0.938 1 1.126 1.301 1.626 1.095
5
Wave 44/98 8/20 8/20 8/20 8/20 8/20 8/20 1/2
Unit
Ht
5 kA
Induct
Drop
Total
FOW
I (kA) 0.5 1.5 3 5 10 20 40 5 m kV 5
2.55 3 Measured
IR 6.93 7.75 8.25 8.80 9.91 11.45 14.31 9.64
0.076 0.38 10.0
![Page 11: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/11.jpg)
TD 01 057 E03 11
Catalog IR 7.3 8.1 8.7 9.2 10.4 12.0 15.0 10.1 0.076 0.38 10.5
5.1 6 Measured
IR 13.87 15.51 16.51 17.60 19.82 22.90 28.62 19.27
0.096 0.48 19.8
Catalog IR 14.6 16.3 17.3 18.5 20.8 24.0 30.0 20.2 0.096 0.48 20.7
7.65 9 Measured
IR 20.80 23.26 24.76 26.40 29.73 34.35 42.93 28.91
0.124 0.62 29.5
Catalog IR 21.1 23.6 25.1 26.8 30.2 34.9 43.6 29.3 0.124 0.62 30.0
8.4 10 Measured
IR 23.14 25.87 27.54 29.36 33.06 38.20 47.74 32.15
0.124 0.62 32.8
Catalog IR 23.5 26.3 28.0 29.8 33.6 38.8 48.5 32.6 0.124 0.62 33.3
10.2 12 Measured IR
27.73 31.00 33.01 35.19 39.62 45.78 57.22 38.53 0.139 0.695 39.2
Catalog IR 28.1 31.5 33.5 35.7 40.2 46.5 58.1 39.1 0.139 0.695 39.8
12.7 15 Measured IR
35.18 39.33 41.87 44.64 50.26 58.08 72.58 48.88 0.198 0.99 49.9
Catalog IR 35.7 39.9 42.5 45.3 51.0 58.9 73.7 49.6 0.198 0.99 50.6
15.3 18 Measured IR
41.61 46.52 49.53 52.80 59.45 68.69 85.85 57.82 0.198 0.99 58.8
Catalog IR 42.2 47.2 50.3 53.6 60.3 69.7 87.1 58.7 0.198 0.99 59.7
17 21 Measured
IR 46.85 52.38 55.76 59.45 66.94 77.34 96.67 65.10
0.218 1.09 66.2
Catalog IR 47.5 53.2 56.6 60.3 67.9 78.5 98.1 66.1 0.218 1.09 67.2
19.5 24 Measured
IR 55.46 62.00 66.02 70.38 79.25 91.56 114.44 77.07
0.292 1.46 78.5
Catalog IR 56.3 62.9 67.0 71.4 80.4 92.9 116.2 78.2 0.292 1.46 79.7
22 27 Measured
IR 62.41 69.78 74.29 79.20 89.18 103.04 128.78 86.72
0.32 1.6 88.3
Catalog IR 63.3 70.8 75.4 80.4 90.5 104.6 130.7 88.0 0.32 1.6 89.6
24.4 30 Measured
IR 69.34 77.52 82.53 87.99 99.08 114.47 143.07 96.35
0.332 1.66 98.0
Catalog IR 70.4 78.7 83.8 89.3 100.6 116.2 145.2 97.8 0.332 1.66 99.5
29 36 Measured
IR 83.21 93.03 99.05 105.60 118.91 137.39 171.71 115.63
0.393 1.965 117.6
Catalog IR 84.5 94.4 100.5 107.2 120.7 139.4 174.3 117.4 0.393 1.965 119.3
Test Summary
Table 1 summarizes the result of FOW discharge testing performed, per the standard,
with and without an aluminum spacer. The MOV disc FOW residual voltage is combined
with the inductive drop (associated with the arrester height) to develop each rated
arrester’s Total FOW residual voltage.
Table 2 summarizes residual voltage measurements for the three test samples across the
range of specified wave shapes and current values. The residual voltage of each MOV
disc is measured as a routine test with a discharge current of 5 kA, 8/20 s. The MOV
discs of each arrester are accumulated within 5 kA residual voltage ranges as specified
for each arrester rating. To verify the catalog maximum residual voltage levels, a
discharge voltage ratio was established at each current level based on the 5 kA residual
![Page 12: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/12.jpg)
TD 01 057 E03 12
voltage of each test sample, as shown in Table 2. This ratio was multiplied by the
maximum 5-kA residual voltage accumulation specified for each rating.
As summarized on Table 3, the residual voltage calculated (based on the prorated test
sample data) was less than the maximum declared catalog levels for each rated arrester.
![Page 13: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/13.jpg)
TD 01 057 E03 13
IEC Type Test Report
Report No. TD 01 057 E03
Type PDV65
Normal Duty Distribution Class Arrester
Disc Accelerated Aging
CERTIFICATION
This is to certify that the polymer accelerated aging design tests have been successfully
performed on Ohio Brass Type PDV65 Normal Duty Distribution Class surge arresters.
Dennis W. Lenk
Principal Engineer
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
Date: 4/01/2016
Attachment
![Page 14: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/14.jpg)
TD 01 057 E04 14
DESIGN TEST REPORT
PDV65 IEEE Normal Duty Distribution Class Surge Arrester
TITLE: MOV Disc Accelerated aging procedure
TEST PROCEDURE: Tests were performed to verify that the varistors remain stable
and do not increase in power dissipation at MCOV during their expected lifetime.
TEST SAMPLES: Six arrester sections were prepared. Three sections consisted of the
longest 29mm diameter disc and three consisted of a shorter 29mm diameter disc. Each
section also consisted of a spring, end terminals, barrier film and fiberglass/epoxy wrap
using standard module construction.
TEST PROCEDURE: Tests were performed per section 8.4 of the standard. Samples
were placed inside a 115 C ±2 C. oven and energized for 1,000 hours at Uct, a voltage
level greater than MCOV, for 1,000 hours.
TEST RESULTS: Watts loss for each sample was measured at Uct two hours after
energization and at the completion of the 1000 hour test duration. The table below
summarizes test results. Watts loss was periodically monitored at Uct during the 1000
hour test duration to identify the minimum watts loss value recorded during the test.
Accelerated aging test data
Watts
Loss
Watts
Loss
Watts Loss Reqd ratio Reqd ratio
at 2 Hr minimum at 1000 Hr <1.1 <1.3
Sample @Uc @Uc @Ur Measured Measured
No. -length Pstart (w) Pmin (w) Pend (w) Pend / Pmin Pend / Pstart
1-29x21 .42 .23 .23 1 .55
2-29x21 .46 .25 .25 1 .54
3-29x21 .59 .26 .26 1 .44
4-29x42 .59 .48 .48 1 .81
5-29x42 .62 .49 .49 1 .79
6-29x42 .57 .45 .45 1 .70
CONCLUSION: Over the 1000 hour test duration, each test sample demonstrated
decreasing watts loss at Uct, successfully completing the disc accelerated
aging test.
![Page 15: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/15.jpg)
TD 01 057 E04 15
TYPE TEST REPORT No. TD 01 057 E04
Polymer Accelerated Aging
CERTIFICATION
This is to certify that the polymer accelerated aging design tests have been successfully
performed on Ohio Brass Type PDV 65 Normal Duty Distribution Class surge arresters.
Dennis W. Lenk
Principal Engineer
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
Date: 4/01/2016
Attachments
![Page 16: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/16.jpg)
TD 01 057 E05
DESIGN TEST REPORT
PDV 65 Distribution Class Surge arrester
TITLE: Accelerated aging tests of external polymeric insulating systems for distribution
Arresters.
TEST PROCEDURE: These tests were performed per clause 8.6 of IEEE Standard
C62.11-2012. Accelerated aging tests by exposure to light were performed per clause
8.6.1 test method 8.6.1.2.c. Tests on polymer housing and insulating bracket material
using the fluorescent UV technique described in ASTM G53-1996. Test duration was
1000 hours on three samples of each material. Accelerated aging tests by exposure to
electrical stress were performed per clause 8.6.2.
TEST SAMPLES: Three PDV-65 10.2 kV MCOV and three PDV-65 17 kV MCOV
arresters were tested. These represent the highest MCOV stress based on leakage
distance and arcing distance. Tests were performed by attaching arresters to a vertical
Ferris wheel, where the arresters are continuously energized. As the wheel rotates, each
arrester is sequentially sprayed with a 400 ohm-centimeter water spray. As the energized
arrester rotates around the wheel, the arrester housing goes through a dry band arcing
condition. The test continues until each arrester has reached 1000 hours of energized test
time. Prior to and after the 1000 hour test, each arrester is subjected to a 5 kA 8/20
discharge to confirm its electrical integrity.
The final portion of the test procedure consists of subjecting each arrester insulating
bracket to 20 hours on voltage with the insulating bracket energized at MCOV. At the
completion of the above tests, the arresters are examined to ensure there is no evidence of
surface tracking.
CONCLUSION: Both polymer housing and insulating bracket materials passed the test
requirements of clause 8.6.1.3, as there were no cracks greater than the allowed depth of
.1 mm. The arresters also passed the requirements of clause 8.6.2.4, as the arrester
discharge voltage changed by less than 1 % as a result of the 1000 hour Ferris wheel test.
There was no evidence of external flashovers, punctures, or internal breakdowns during
the described tests. There was no evidence of surface tracking on the arrester housings
after the 1000 hour on-voltage test or on the insulating bracket after the 20 hour on-
voltage test.
![Page 17: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/17.jpg)
TD 01 057 E05
TYPE TEST REPORT
Report No. TD 01 057 E05
Type PDV65
IEEE ND Distribution Class Arrester
Salt Fog Polymer Aging Test
CERTIFICATION
This is to certify that the polymer accelerated aging design tests have been successfully
performed on Ohio Brass Type PDV65 Normal Duty Distribution Class surge arresters.
Dennis W. Lenk
Principal Engineer
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
Date: 4/01/2016
Attachment
![Page 18: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/18.jpg)
TD 01 057 E06 18
Type PDV65 ND Distribution Class Surge Arrester
Salt Fog test
TEST OBJECTIVE: Perform 1000 hour salt fog exposure test per section 8.7 of C62.11
– 2012 Standard.
TEST SAMPLE: Two 29 kV MCOV arresters were tested. Arrester #1 was tested
without its insulating support bracket attached to the base end of the arrester. Arrester #2
was tested with the insulating support bracket.
TEST PROCEDURE: The arresters were mounted vertically inside the salt fog
chamber. Prior to and after the 1000 hour test, the reference voltage and partial discharge
of the sample were measured. The 1000 hour test was performed with a spray having an
NaCl salt content of 10 kg/m3 per the procedure specified in section 8.7.3 of the standard
TEST RESULTS: The test arrester passed the 1000 hour salt exposure. The physical
condition of the polymer housings showed no signs of surface tracking or surface erosion.
There was no evidence of housing or shed punctures. The following table summarizes the
results of the electrical testing.
Sample # Reference
Voltage kVc
Before Salt Fog
Reference
Voltage kVc
After Salt Fog
Reference
Voltage %
Change
Partial
Discharge After
Salt Fog PC
1 44.3 45.0 +1.6 <1
2 44.6 45.0 +0.9 <1
Photographs #1 and 32 show the salt-contaminated surfaces of the two arresters after
completion of the 1000 hour duration salt fog test. There was no evidence of surface
tracking, erosion, or shed punctures.
CONCLUSION: The physical condition of the test arrester and the electrical testing
confirmed that the PDV65 arrester successfully passed the 1000 hour salt fog exposure
test.
![Page 19: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/19.jpg)
TD 01 057 E06 19
Photograph #1
Photograph #2
IEEE Type Test Report
Report No.TD 01 057 E06
Type PDV65
IEEE ND Distribution Class Arrester
Thermal Equivalency
![Page 20: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/20.jpg)
TD 01 057 E06 20
CERTIFICATION
This is to certify that the polymer accelerated aging design tests have been successfully
performed on Ohio Brass Type PDV 65 Normal Duty Distribution Class surge arresters.
Dennis W. Lenk
Principal Engineer
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
Date: 4/01/2016
Attachment
PDV65 IEEE Normal Duty Distribution Class Surge Arrester
Thermal Equivalency Test
INTRODUCTION: Tests were performed as required per Section 7.2.2.3 of the IEEE
C62.11-2012 Standard, to compare the cooling characteristics of the prorated test sections
used for type tests with that of a full-size arrester unit.
![Page 21: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/21.jpg)
TD 01 057 E07 21
PURPOSE: The purpose of this test is to verify that the thermal cooling curve for the
Type PDV65 prorated sections, when internally heated, will cool slower than that of a
full size 21 kV rated arrester unit.
PROCEDURE: A full size single unit 21 kV rated Type PDV65 arrester and a 12 kV
and a 6 kV prorated section were heated up by applying a temporary overvoltage to the
test samples. All samples (the arrester and the prorated sections) were energized in
approximately 10 minutes to a starting temperature of 140 ºC, at which time the voltage
was removed. The full size arrester and the two prorated sections were instrumented with
(1) fiber-optic sensors located in the middle of the MOV disc stack. During the cooling
portion of the test, the temperatures of the arrester and the test sections were monitored at
5 minute intervals to develop the cooling curve for each sample.
SUMMARY: As allowed in Section 7.2.2.3.5, the cooling curves for the 12 kV and 6
kV prorated sections can be adjusted higher to assure that, at no time during the 120
minute cooling period, do the section cooling curves drop below that of the full size
arrester. The adjusted temperature shown for each rated section was added to the
durability tests requiring a 60 degree C. preheat.
The cooling curve (Figure 1 below) confirms that the cooling rate of the 12 kV prorated
section is slower than that of the full size 21 kV Rated Type PDV 65 arrester unit,
confirming the thermal equivalency of the prorated sections to the full size arrester. Also
shown in Figure 1, the 6 kV prorated section starting temperature for durability design
testing needs to be increased 6 degrees C. above 60 degree C, prior to performing
durability tests. The 12 kV rated section needs no additional heating above 60 deg C.
Figure 1
COOLING CURVES FOR PDV65 29MM 21 KV RATED ARR VERSUS 6 KV
AND 12 KV PRORATED THERMAL SECTIONS
![Page 22: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/22.jpg)
TD 01 057 E07 22
![Page 23: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/23.jpg)
TD 01 057 E07 23
TYPE TEST REPORT NO. TD 01 057 E07
SEAL INTEGRITY TEST
CERTIFICATION
This is to certify that the seal integrity design test has been successfully performed on
Ohio Brass Type PDV 65 Normal Duty Distribution Class surge arrester.
Dennis W. Lenk
Principal Engineer
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
Date: 4/01/2016
Attachments
DESIGN TEST REPORT
![Page 24: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/24.jpg)
TD 01 057 E08 24
PDV 65 Distribution Class Surge Arrester
TITLE: Distribution class surge arrester seal integrity design test:
OBJECTIVE: Seal integrity tests were performed per IEEE Standard.
TEST SAMPLES: Tests were run on three 18 kV rated arresters, catalog number
213265, constructed with single 18 kV rated modules.
TEST PROCEDURE: The seal integrity test consisted of the following steps:
a) Initial Electric Test: Each arrester was energized at rating, watts loss and IIV was
measured.
b) Terminal Torquing: A ¼” diameter hard lead was inserted between the wire clamp
and arrester end stud on one side only. The clamping nut was torqued to 22 ft-lb.
c) Thermal Conditioning: Each arrester was placed in a 70 C 3 C environment for
14 days, after which the arresters were stabilized at ambient room temperature and
watts was measured.
d) Seal Pumping: The arresters were heated to 60 °C 3 °C for one hour, then placed
into a 4 °C 3 °C water bath for two hours, after which the samples were returned
to the 60 °C oven. Each arrester was subjected to ten repetitions of this cycle. The
transfer time between media was 1-2 minutes.
e) Final Electric Test: Procedure (a) was repeated.
f) Final Inspection: The arresters were disassembled to verify no moisture penetration
was evident.
Table 1 Seal Test Data Summary- Single Module 10 kV arrester
Sample Number
Applied Voltage (kV) rms
Initial Watts Loss
Final Watts Loss
Partial Discharge Before (pc)
Partial Discharge After (pc)
1 18 1.0 1.1 0.9 0.6 2 18 1.1 1.1 1.0 0.6 3 18 1.1 1.2 0.9 0.6
Table 2 Seal Test Data Summary-Two Module 18 kV Arrester
Sample Number
Applied Voltage (kV) rms
Initial Watts Loss
Final Watts Loss
Partial Discharge Before (pc)
Partial Discharge After (pc)
1 18 0.56 0.58 0.5 0.5 2 18 0.58 0.62 0.5 0.5 3 18 0.76 0.84 0.5 0.5
![Page 25: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/25.jpg)
TD 01 057 E08 25
CONCLUSION: As indicated on Tables 1 and 2, all arresters demonstrated proper
sealing with no evidence of internal moisture or change in watts loss or Pd. It should be
noted that the noise levels measured represent background noise at the test location. This
test confirms that the PDV 65 18 kV rated arrester, constructed with 2 short modules or a
single long module, successfully passes the Normal Duty Distribution Class arrester seal
integrity test.
![Page 26: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/26.jpg)
TD 01 057 E08 26
TYPE TEST REPORT No. TD 01 057 E08
Partial Discharge Test
CERTIFICATION
This is to certify that the RIV and partial discharge design tests have been successfully
performed on Ohio Brass Type PDV 65 Distribution Class surge arrester.
Dennis W. Lenk
Principal Engineer
Fayaz Khatri Fayaz Khatri
Design Engineering Supervisor
Date: 4/01/2016
Attachments
DESIGN TEST REPORT
PDV 65 Distribution Class Surge Arrester
TITLE: Partial discharge test:
![Page 27: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/27.jpg)
TD 01 057 E09 27
TEST PROCEDURE AND SAMPLE: Partial discharge testing was performed per IEEE
Standard C62.11-2012. The test was performed on a 36 kV rated, 29.0 kV MCOV PDV-65
arrester.
TEST RESULTS: With the unshielded 36 kV arrester placed in the circuit, the partial discharge
measured 0 picocoulomb at 30.5 kVrms.
CONCLUSION: The 36 kV rated PDV-65 arrester passed test requirements as the measured
partial discharge was below the allowed 10 picocoulomb limit.
![Page 28: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/28.jpg)
TD 01 057 E09 28
TYPE TEST REPORT No. TD 01 057 E09
HIGH CURRENT, SHORT DURATION TEST
Type PDV65 Normal Duty Distribution Arrester
CERTIFICATION
This is to certify that the high current, short duration design test has been successfully
performed on Ohio Brass Type PDV 65 ND Distribution Class surge arrester.
Dennis W. Lenk
Principal Engineer
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
Date: 4/01/2016
Attachments
![Page 29: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/29.jpg)
TD 01 057 E10 29
DESIGN TEST REPORT
PDV 65 Distribution Class Surge Arrester
TITLE: High Current, Short Duration Discharge Withstand Tests:
OBJECTIVE: High current, short duration discharge withstand tests were performed per
IEEE Standard C62.11-2012. Tests were performed per Normal Duty distribution arrester
requirements. TEST SAMPLE: As required by the standard, prorated samples contained the minimum
MOV mass per specified for the design. MCOV voltage was also prorated per unit Vref
to reflect the lowest margin case of the standard voltage ratings offered in this design.
TEST PROCEDURE: Per Section 8.12.2 of the C62.11-2012 Standard, test samples
were subjected to two 65 kA, 4/10 s discharges. Sufficient time was allowed between
discharges for the sample to cool to ambient temperature 23 C. Within 100 milliseconds
after the second high current discharge, samples were energized at the prorated MCOV
recovery voltage. Watts loss was monitored over a 30 minute period demonstrating
thermal stability.
TEST RESULTS: Figures #1 and #2 show the oscillograms of the two 65 kA shots
applied to Sample #1
![Page 30: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/30.jpg)
TD 01 057 E10 30
Figure 1: Sample 1, Shot 1, 69.3 kA, 4.8/11.4
Figure 2: Sample #1, Shot 2, 66.3 kA, 4.8/11.4
![Page 31: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/31.jpg)
TD 01 057 E10 31
Figures #3 through #5 show the recovery oscillograms for Sample 31 after the 2nd high
current shot.
FIGURE 3 THERMAL RECOVERY @ TIME = 0 FOR SAMPLE #1
![Page 32: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/32.jpg)
TD 01 057 E10 32
FIGURE 4 THERMAL RECOVERY @ TIME = 1 MINUTE FOR SAMPLE #1
FIGURE 5 THERMAL RECOVERY @ TIME = 30 MINUTE FOR SAMPLE #1
Table 1 summarizes the results of high current tests performed on the three test samples.
![Page 33: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/33.jpg)
TD 01 057 E10 33
Table 1
High Current Short Duration
Discharge Withstand Test Summary
Sample #1 Sample #2 Sample #3
HC Shot 1 69.3 kA 66.2 kA 66 kA
HC Shot 2 66.3 kA 66.7 kA 66.7 kA
delay 84msec 84 msec 84 msec
Watts @
0 34.5 35.4 40.7
1 minutes 1.48 1.51 1.56
2 minutes 0.82 0.86 0.9
5 minutes 0.48 0.51 0.49
10 minutes 0.35 0.38 0.35
20 minutes 0.26 0.26 0.25
30 minutes 0.22 0.21 0.21
CONCLUSIONS: All prorated test samples successfully completed the high current test
and demonstrated thermal stability during the recovery test. Disassembly revealed no
evidence of physical damage to the test samples, confirming the PDV65 arrester
successfully passed the Normal Duty Distribution Class arrester high current, short
duration requirement as specified in the IEEE C62.11-2012 Standard.
TYPE TEST REPORT No. TD 01 057 E10
LOW CURRENT, LONG DURATION TEST
PDV65 Normal Duty Distribution Class Arrester
![Page 34: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/34.jpg)
TD 01 057 E10 34
CERTIFICATION
This is to certify that the low current, long duration design test has been successfully
performed on Ohio Brass Type PDV65 Normal Duty Distribution Class surge arrester.
Dennis W. Lenk
Principal Engineer
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
Date: 4/01/2016
Attachments
DESIGN TEST REPORT
PDV65 Normal Duty Distribution Class Surge Arrester
Low Current, Long Duration Discharge Withstand Tests
Introduction: The low current, long duration discharge withstand test was performed per
clause 8.13 IEEE Standard C62.11-2012. Tests were performed per normal duty
distribution arrester requirements using 6 kV rated test samples.
Test Samples: Per section 8.21.2.1, a ground lead disconnector (GLD) was connected in
series with each of the three LCLD 6 kV rated test samples.
Procedure: Per section 8.13.3, each test sample was subjected to six sets of three
nominal 2000 s duration discharges greater than 75 amps. Sufficient time was allowed
between sets of discharges for the section to cool to room ambient temperature. Per
![Page 35: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/35.jpg)
TD 01 057 E11 35
section 8.13.4, the 5 kA residual voltage of each MOV disc section was measured prior to
and after the (18) shot LCLD test.
Results: Table 1 summarizes the results of the 18 shot test performed on the three test
samples.
Table 1
Sample #1 Sample #2 Sample #3
Shot No. Amps Coul KJ/Shot Amps Coul KJ/Shot Amps Coul KJ/Shot
1 84.3 0.18 2.26 88.3 0.19 2.35 85.9 0.19 2.29
2 86.9 0.19 2.32 87.9 0.19 2.35 85.9 0.19 2.33
3 78.2 0.17 2.1 86.6 0.19 2.36 88.3 0.19 2.37
4 85.6 0.18 2.28 84.3 0.18 2.28 87.3 0.19 2.33
5 81.6 0.18 2.21 84.6 0.18 2.28 86.3 0.19 2.31
6 85.9 0.18 2.31 87.6 0.19 2.38 86.9 0.19 2.36
7 83.2 0.18 2.25 84.3 0.18 2.27 84.9 0.18 2.28
8 83.6 0.18 2.23 87.9 0.19 2.35 83.2 0.18 2.26
9 85.6 0.18 2.3 86.6 0.19 2.32 86.6 0.19 2.32
10 85.6 0.18 2.28 90.3 0.2 2.46 86.6 0.19 2.31
11 84.3 0.18 2.25 84.6 0.19 2.28 87.3 0.19 2.33
12 81.6 0.18 2.21 88.3 0.19 2.4 86.6 0.19 2.32
13 84.6 0.18 2.28 86.6 0.19 2.34 85.6 0.18 2.28
14 82.9 0.18 2.24 86.6 0.19 2.36 85.6 0.18 2.28
15 86.3 0.19 2.36 87.3 0.19 2.37 84.6 0.19 2.3
16 82.6 0.18 2.23 82.9 0.18 2.24 81.9 0.18 2.17
17 83.9 0.18 2.28 85.3 0.19 2.32 83.9 0.18 2.24
18 85.3 0.18 2.31 85.9 0.18 2.3 85.6 0.19 2.34
Figures 1 and 2, respectively show oscillograms of the 3rd and 18th shots performed on
sample #1. These oscillograms are typical for all three test samples.
Figure #1
![Page 36: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/36.jpg)
TD 01 057 E11 36
Figure #2
Residual voltage at 10 kA was measured prior to and following the 18-shot 75 A
discharge tests. Table 2 summarizes the results of the 5 kA discharge voltage testing.
Table 2
![Page 37: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/37.jpg)
TD 01 057 E11 37
Sample # 5 kA IR-kVc
(Before)
5 kA IR-kVc (After) 5 kA IR % Change
1 17.344 17.210 -0.77%
2 17.277 17.210 -0.39%
3 17.277 17.277 0%
Conclusion: The prorated test samples successfully completed the 18-shot low current,
long duration test. The sample discharge voltage was less than 1.0%, well below the 10%
change allowed in Section 8.13.4 of IEEE C62.11-2012 Standard. Disassembly revealed
no evidence of physical damage to the test samples. The ground lead disconnectors did
not detonate during the 18 shot test series. The PVR arrester successfully met the LCLD
requirements of the Heavy Duty Distribution Class arrester.
![Page 38: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/38.jpg)
TD 01 057 E11 38
TYPE TEST REPORT No. TD 01 057 E11
DUTY CYCLE TEST
Type PDV 65 Normal Duty Distribution Arrester
CERTIFICATION
This is to certify that the duty cycle design test has been successfully performed on the Ohio Brass Type PDV 65 Normal Duty Distribution Class surge arrester per Clause 8.16 of IEEE C62.11-2012 Standard.
Dennis W. Lenk
Principal Engineer
Date: 4/01/2016
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
DESIGN TEST REPORT
![Page 39: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/39.jpg)
39
PDV 65 Normal Duty Distribution Class Surge Arrester Duty Cycle Test
Introduction: Duty cycle tests were performed per clause 8.16 of IEEE Standard C62.11-2012. Tests were performed on the PDV 65 prorated sections per Normal Duty Distribution arrester requirements. As required by clause 8.21, tests were performed on three prorated sections with a ground lead disconnector (GLD) to demonstrate that the GLD does not detonate during the test procedure. Test Procedure: The prorated test section was energized at its rated voltage and subjected to twenty 5 kA, 8/20 μs discharges spaced at 1 minute intervals. Following the twentieth impulse, the test section was placed in an oven at 60°C. After reaching 60°C, the sample was subjected to two additional 5 kA, 8/20 μs discharges. Within 5 minutes after the second high current discharge, the sample was energized at the prorated recovery voltage. Watts loss was monitored over a 30 minute period demonstrating thermal stability.
Test Results: Tests were successfully completed on three prorated sections, each assembled with a GLD. The following data summarizes the results of tests performed on prorated section #1.
The following data summarizes the results of the duty cycle test performed on prorated section #1. Figures 1 and 2 show the 1st and 20th shot performed during the rated voltage portion of the duty cycle test.
Figure 1 1st Shot @ Rated Voltage
![Page 40: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/40.jpg)
40
Figure 2 20th Shot @ Rated Voltage
Figure 3 shows the oscillogram for the 2nd 5 kA impulse applied to the prorated section #1 during the recovery portion of the duty cycle test.
Figure 3 2nd 5 kA Discharge Prior to Recovery
![Page 41: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/41.jpg)
41
Figures 4 and 5 show oscillograms of the prorated section #1 grading current through the test section at time zero and 30 minutes after application of recovery voltage, demonstrating thermal recovery has occurred.
Figure 4
Recovery @ Time = 0 Minutes
Figure 5 Recovery @ Time = 30 Minutes
Prior to and after the duty cycle test, the 5 kA, 8/20 μs discharge voltage was measured on the three prorated sections. Table 1 summarizes this test data.
![Page 42: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/42.jpg)
42
Table 1
Section # 5 kA IR kVc
(Before) 5 kA IR kVc
(After) 5 kA IR % Change
1 36.028 36.286 +0.7
2 36.028 36.474 +1.2
3 36.095 36.312 +0.6
CONCLUSION: The Type PDV 65 prorated test samples successfully completed Duty Cycle testing and demonstrated thermal stability during the recovery test. The 10 kA discharge voltage increase ranged from 0.6-1.2%, less than the allowed 10% limit specified in Section 8.16.4 of the IEEE C62.11-2012 standard. Disassembly revealed no evidence of physical damage to the test samples. The ground lead disconnector (GLD) on each prorated section successfully withstood the duty cycle testing without detonating. The Type PDV 65 arrester successfully met the Normal Duty Distribution arrester Duty Cycle requirements.
IEEE TYPE TEST REPORT
Report No. TD 01 057 E12
TEMPORARY OVERVOLTAGE TEST
PDV 65 Normal Duty Distribution Arrester
CERTIFICATION
This is to certify that the temporary overvoltage design test has been successfully
performed on Ohio Brass Type PDV 65 Distribution Class surge arrester.
Dennis W. Lenk
Principal Engineer
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
![Page 43: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/43.jpg)
TD 01 058 E13 43
Date: 4/01/2016
Attachments
DESIGN TEST REPORT
PDV 65 Normal Duty Distribution Class Surge Arrester
TITLE: Temporary over-voltage tests (TOV) performed on arrester without
insulating bracket:
OBJECTIVE: Temporary over-voltage tests were performed per section 8.17 of IEEE
Standard C62.11-2012.
SAMPLES: Tests were performed per Normal Duty distribution arrester requirements
using four thermally prorated test sections. Prorated sections were used to facilitate
testing of the lowest MOV mass, highest stressed arrester rating at voltages within
available laboratory facility capabilities. These tests cover ratings 3 - 36 kV with
corresponding MCOV levels of 2.55 - 29.0 kV using both short and long module
construction. As required by clause 7.2.2, prorated samples contained the minimum
MOV mass per specified for the design. MCOV and Rated voltages were also prorated
per unit Vref to reflect the lowest margin case of the standard voltage ratings offered in
this design. Prorated arrester ratings were within the 6 to 12 kV range specified for
distribution arrester tests.
TEST PROCEDURE: Each prorated sample was tested within four of the six designated
time ranges a - f, spanning overvoltage durations of .01 - 10,000 seconds. The tests were
performed demonstrating TOV capability of the design under “no prior duty" conditions.
For each TOV voltage setting, the test circuit applied voltage to the sample (preheated to
60 oC) for a time duration sufficient to exceed that claimed on the "no prior duty" curve.
TOV voltage was superimposed over MCOV recovery voltage such that, when TOV was
removed, there was no delay prior to application of recovery voltage. Recovery voltage
was applied for 30 minutes to demonstrate thermal stability.
TEST RESULTS: The following table and figure summarize the no-prior duty TOV
capability points for the PDV 65 normal duty arrester design without the series-connected
insulating bracket.
![Page 44: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/44.jpg)
TD 01 058 E13 44
TOV Duration-
Seconds
No Prior Duty TOV-PU
MCOV (Without Bracket)
.02 1.63
.1 1.57
1 1.49
10 1.42
100 1.35
1000 1.28
CONCLUSION (arrester without insulating bracket): Tests were successfully
completed on four prorated samples without an insulating bracket over five specified time
ranges. Each sample demonstrated thermal stability after TOV exposure having no signs
of physical damage during inspection. Additionally, a fifth 12 kV rated section with an
![Page 45: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/45.jpg)
TD 01 058 E13 45
Optima insulating bracket was energized for 10,000 seconds, followed by successful
thermal recovery. Residual voltage at 5 kA measured prior to and following the complete
TOV test series verified IR characteristics remained within the acceptable 10 % limits.
![Page 46: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/46.jpg)
TD 01 058 E13 46
DESIGN TEST REPORT
PDV 65 Optima Distribution Class Surge Arrester
TITLE: Temporary over-voltage tests (TOV) performed on arrester with Optima
insulating bracket):
OBJECTIVE: Laboratory testing reveals that attachment of the PDV 65 arrester to the
Optima insulating bracket significantly improves the long time TOV capability of the
arrester assembly. The degree of improvement is a function of the individual arrester
ratings. The following curves show the improved TOV characteristic of the various
arrester ratings mounted to the insulating bracket.
SAMPLES: Arresters ranging in rating from 3 thru 36 kV were assembled with the
insulating bracket and subjected to TOV testing.
TEST RESULTS: The following tables summarize the claimable temporary overvoltage
capability of the various PDV 65 Optima arrester ratings mounted on an insulating base
bracket.
CONCLUSION (Arrester Mounted On Insulating Bracket): The following family of
curves defines the overvoltage withstand capability of the various rated PDV 65 Optima
bracket-mounted arresters when subjected to overvoltages with time durations ranging
from .02 to 10,000 seconds duration.
![Page 47: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/47.jpg)
TD 01 058 E13 47
No Prior Duty Overvoltage Curve for PDV65 Optima 3 kV Rated Arrester Mounted on
Insulating Bracket
1.0
1.2
1.4
1.6
1.8
2.0
2.2
0.01 0.1 1 10 100 1000 10000
Time-seconds
Vo
ltag
e p
er
Un
it M
CO
V
3 kV rated
No Prior Duty Overvoltage Curve for PDV 65 Optima 6 kV Rated Arrester Mounted on
Insulating Bracket
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
0.01 0.1 1 10 100 1000 10000
Time- Seconds
Vo
ltag
e P
er
Un
it M
CO
V
6 kV Rated
![Page 48: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/48.jpg)
TD 01 058 E13 48
No Prior Duty Overvoltage Curve for PDV 65 Optima 9 kV Rated Arrester Mounted on
Insulating Bracket
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
0.01 0.1 1 10 100 1000 10000
Time- Seconds
Vo
ltag
e o
er
Un
it M
CO
V
9 kV Rated
No Prior Duty Curve for PDV 65 Optima 10 and 12 kV Rated Arresters Mounted on Insulating
Bracket
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
0.01 0.1 1 10 100 1000 10000
Time-Seconds
Vo
ltag
e p
er
Un
it M
CO
V
10 thru 12 kV rated
![Page 49: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/49.jpg)
TD 01 058 E13 49
No Prior Duty Overvoltage Curve for PDV 65 Optima 15 thru 21 kV Rated Arresters Mounted
on Insulating Bracket
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
0.01 0.1 1 10 100 1000 10000
Time-Seconds
Vo
ltag
e p
er
Un
it M
CO
V
15, 18, 21 kV Rated
No Prior Duty Overvoltage Curve for PDV 65 Optima 24 thru 27 kV Rated Arresters Mounted
on Insulating Bracket
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
0.01 0.1 1 10 100 1000 10000
Time- Seconds
Vo
ltag
e p
er
Un
it M
CO
V
24 thru 27 kV rated
![Page 50: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/50.jpg)
TD 01 058 E13 50
No Prior Duty Overvoltage Curve for PDV 65 Optima 30 thru 36 kV Rated Arresters Mounted
on Insulating Bracket
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
0.01 0.1 1 10 100 1000 10000
Time- Seconds
Vo
ltag
e p
er
Un
it M
CO
V
30 thru 36 kV rated
![Page 51: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/51.jpg)
TD 01 058 E13 51
TYPE TEST REPORT
Report No. TD 01 057 E13
SHORT CIRCUIT TEST
PDV65 Normal Duty Distribution Arrester
CERTIFICATION
This is to certify that the short circuit design test has been successfully performed on
Ohio Brass Type PDV65 Normal duty Distribution Class surge arrester.
Dennis W. Lenk
Principal Engineer
Date: 4/01/2016
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
![Page 52: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/52.jpg)
TD 01 058 E13 52
PDV65 Normal Duty Distribution Class Surge Arrester
Short Circuit Test
TEST OBJECTIVE: Short Circuit tests were performed on the PDV65 Normal Duty
Distribution Class Distribution arrester per ANNEX N of IEC 60099-4, 2005 standard.
TEST SAMPLES: Per Annex N, tests were performed on fusewire shorted and
overvoltage failed arresters as defined in Table N.2 of the referenced standard. Short
circuit tests were performed on the longest mechanical section, as required in Clause
N.8.7.2.2 of the standard.
TEST PROCEDURE: Per clause 10.8.10.2 of 60099-4, Ed. 3.0, 2014, the polymer-
housed PDV is a “Design B” arrester. As such, per Table 8 of 60099-4, Ed. 3.0, 2014,
four short circuit tests are required. All four short circuit tests are to be performed per
Table 7 and Table 8 on unfailed arresters using the 2-source test method.
As short circuit tests were originally performed per Annex N, two test samples for the
high current test were assembled with a fuse wire oriented axially between the mov disc
stack and the fiberglass-epoxy wrap. These samples were subjected to the full offset
current test. In addition, six samples represented standard production arresters. These
samples were failed using the specified 2-source failure mode procedure. All tests were
performed at full voltage. Therefore, the prospective fault current, as measured during the
bolted fault test on the generator, is the claimable short circuit capability of the design. It
should be noted that the IEC 60099-4, Ed. 3.0, 2014 short circuit test is similar to that
defined in Annex N of new IEC 60099-4-2005 standard, except reduced level high
current testing was performed only at 7.5 kA, instead of 6 kA and 3 kA as required in the
IEC 60099-4, Ed. 3.0, 2014, standard. Also note that the original IEC testing was
performed on (8) total arresters versus only (4) per IEC 60099-4 Ed. 3.0, 2014.
TEST RESULTS: The following table summarizes the results these tests which
validated the claimed maximum 15 kArms symmetrical, 12 cycle fault current withstand
capability of this design, with an applied ratio of 1.55 between total asymmetrical to
symmetrical rms currents. This corresponds to a 2.6 ratio, in the first half loop of fault
current, between the crest asymmetrical to rms symmetrical current, i.e., full offset. In
addition to testing at the claimed maximum capability, tests were also performed, using
the 2-source procedure, at half the claimed capability and at 600 amps as specified in
Table 14 of the standard.
All tests were performed at full voltage. Therefore, the prospective fault current, as
measured during the bolted fault test on the generator, is the claimable fault current
capability of the design.
![Page 53: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/53.jpg)
TD 01 057 E14 53
Table 1
Calibration Test 15.0 kA Symmetrical RMS 40.0 kAc 1st Half Loop
Sample
#
Failure
Mode
Minimum Test
Duration-seconds
Condition of Module/Polymer
Housing After Test
1 Fuse Wire .2 Module Intact/Hsg Torn but in Place
2 Fuse Wire .2 Module Intact/Hsg Torn but in Place
3 2-Source .2 Module Intact/Hsg Torn but in Place
4 2-Source .2 Module Intact/Hsg Torn but in Place
Calibration Test 7.59 kA Symmetrical RMS No Asymmetrical Requirement
Sample
#
Failure
Mode
Minimum Test
Duration-seconds
Condition of Module/Polymer
Housing After Test
5 2-Source .2 Module Intact/Hsg Torn but in Place
6 2-Source .2 Module Intact/Hsg Torn but in Place
Calibration Test 600 Amp Symmetrical RMS No Asymmetrical Requirement
Sample
#
Failure
Mode
Minimum Test
Duration-seconds
Condition of Module/Polymer
Housing After Test
7 2-Source 1.0 Module Intact/Hsg Torn but in Place
8 2-Source 1.0 Module Intact/Hsg Torn but in Place
CONCLUSION: The eight test arresters assembled with the longest mechanical unit met
the test evaluation criteria as specified in the standard. In all tests, the arrester module
remained intact after the completion of each test. The flexible polymer housing wall
section split, as intended, on all samples to allow venting of internal arcing gases to the
outside of the arrester. In all cases, flames associated with the fault current test
extinguished immediately after completion of the test, well within the allowed 2 minute
duration. These tests have demonstrated the capability of the Type PDV65 Normal Duty
Distribution Class arrester design to successfully discharge a maximum claimable 15
kArms symmetrical fault current.
![Page 54: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/54.jpg)
TD 01 057 E14 54
TYPE TEST REPORT NO. TD 01 057 E14
DISCONNECTOR TESTS
CERTIFICATION
This is to certify that the disconnector tests have been successfully performed on Ohio
Brass Type PDV 65 Distribution Class surge arrester.
Dennis W. Lenk
Principal Engineer
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
Date: 4/01/2016
Attachments
![Page 55: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/55.jpg)
TD 01 057 E15 55
DESIGN TEST REPORT
PDV 65 Distribution Class Surge Arrester
TITLE: Distribution arrester disconnector tests:
OBJECTIVE: Tests were performed per clause 8.21 of IEEE Standard C62.11-2012.
TEST PROCEDURES: Per clause 8.21.2.1, high current short duration, low current
long duration, and duty cycle tests were performed on thermally prorated test sections
having the disconnector assembly connected in series. In all tests, the disconnectors
withstood the discharge duty without detonating.
Per clause 8.21.2.2, disconnector detonation testing was performed on five
bracket/isolator assemblies each at 20, 80, 200, and 800 Arms.
TEST RESULTS: Disconnectors did not operate when subjected to high current short
duration and low current long duration discharge duty tests and duty cycle tests on the
thermally prorated test sections.
In all cases, disconnectors separated during detonation tests at each of the required
current levels. Additionally, detonation tests were successfully performed at 5 and 1 amp
levels.
CONCLUSION: The disconnector passed all requirements of clause 8.21. The following
curve shows the claimed detonation curve for the PDV65 arrester disconnector.
![Page 56: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/56.jpg)
TD 01 057 E15 56
PDV 65 Optima Disconnector Detonation Curve
0.01
0.1
1
10
1 10 100 1000
Current-Amps
Deto
na
tio
n T
ime
-Se
co
nd
s
Isolator Detonation Points
![Page 57: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/57.jpg)
TD 01 057 E15 57
TYPE TEST REPORT No. TD 01 057 E15
MAXIMUM DESIGN CANTILEVER
AND
MOISTURE INGRESS TEST
PDV 65 Arrester
CERTIFICATION
This is to certify that the maximum design cantilever (MDCL) and moisture ingress test
has been successfully performed on the Ohio Brass Type PDV 65 Normal Duty
Distribution Class surge arrester.
Dennis W. Lenk
Principal Engineer
Fayaz Khatri Fayaz Khatri Design Engineering Supervisor
Date: 4/01/2016
Attachments
![Page 58: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/58.jpg)
TD 01 057 E15 58
DESIGN TEST REPORT
PDV65 Distribution Class Surge Arrester
TITLE: Maximum design cantilever (MDCL) and moisture ingress test:
TEST SAMPLES: The maximum design cantilever and moisture ingress test was
performed on a PDV 65 17 kV MCOV arrester, representing the longest mechanical unit.
Tests were performed on this 8.6” long arrester to validate the claimed 300 inch-pound
continuous cantilever rating.
TEST PROCEDURE: The test was performed per section 8.22 of C62.11-2012
Standard. The test arrester was subjected to PD, watts loss, and discharge voltage tests
prior to the bending moment and boiling water immersion test. The mechanical portion of
the test consisted of first applying a 20 ft-lb torque to the arrester end terminals for 30
second duration. The test arrester was then placed inside a thermal cycling oven and
mechanically loaded to its 300 in-lb continuous cantilever rating. The load application
and test temperature is shown on the attached figure.
TEST RESULTS: After completion of the thermal cycling under load test, the test
arrester was mechanically loaded in four directions and the top end deflection under load
and the residual deflection under no load were recorded. Table 1 summarizes the results
of this mechanical loading procedure.
Table 1
0o Load 90o Load 180o Load 270o Load
Deflection @load (in) .47 .37 .40 .43
Residual Deflection (in) .156 .031 .031 .125
At the completion of the mechanical loading test, the water immersion portion of the
bending moment test was performed per para. 8.22.3.3.b) and consists of placing the
![Page 59: IEEE DESIGN TEST REPORT Report No. TD 01 057 E00 Type PDV ... · Type tests performed on PDV65 ND Distribution arresters demonstrate full compliance with the relevant clauses of the](https://reader033.fdocuments.net/reader033/viewer/2022051815/6040e9b1e15f71764c1c59d2/html5/thumbnails/59.jpg)
TD 01 057 E15 59
mechanically stressed arrester into 80 degree C. salt water bath for 168 hours, after which
the arrester is cooled to room temperature and electrical tests are repeated. See Table 2
below for results.
Table 2
Sample
No.
Initial
Watts @
MCOV
Final
Watts @
MCOV
Initial PD
@ 1.05
times
MCOV
(pC)
Final PD
@ 1.05
times
MCOV
(pC
Initial 1.5
kA
Residual
Voltage
kVc
Final 1.5
kA
Residual
Voltage kVc
1 .168 .178 0 0 51.4 51.8
CONCLUSION: Per Section 8.22.4, the partial discharge levels were unchanged and the
watts loss changed 6%, less than the allowed 20% increase. The 10 kA IR changed 1%,
less than the allowed 10%. Visual examination revealed no evidence of mechanical
damage or moisture ingress inside the arrester as a result of the test procedure. The above
tests have validated the 300 inch-pound continuous cantilever rating of the base mounted
PDV65 normal duty Distribution Class arrester.