[IEEE 2014 IEEE 15th Workshop on Control and Modeling for Power Electronics (COMPEL) - Santander,...
Transcript of [IEEE 2014 IEEE 15th Workshop on Control and Modeling for Power Electronics (COMPEL) - Santander,...
Split-Phase Control: Achieving Complete
Soft-Charging Operation of a Dickson
Switched-Capacitor Converter
Yutian Lei1, Ryan May1,2 and Robert C.N. Pilawa-Podgurski1
1University of Illinois at Urbana-Champaign, 2Texas Instruments
Abstract—Switched-capacitor (SC) converters are gaining pop-ularity due to their high power density and suitability for on-chipintegration. Soft-charging techniques can be used to eliminatethe current transient during the phase switching instances, andimprove the power density and efficiency of SC converters. In thispaper, we propose a split-phase control scheme that enables theDickson converter to achieve complete soft-charging operation,which is not possible using the conventional two-phase control.An analytical method is extended to understand and design split-phase controlled Dickson converters. The proposed technique andanalysis are verified by both simulation and experimental results.An 8-to-1 step-down Dickson converter is built to demonstratethe reduction in output impedance and improvement in efficiencyas a result of the split-phase controlled soft-charging operation.
I. INTRODUCTION
INDUCTORS and transformers are essential in conven-
tional switch-mode power converters. Due to the relatively
low energy density of the magnetic components, they often
dominate the size and cost of a converter. On the other
hand, switched-capacitor (SC) converters use only capaci-
tors to transfer energy and consequently can have higher
power density and greater suitability for on-chip integration
compared to magnetic-based converters. They also tend to
achieve a higher efficiency at large voltage conversion ratios
compared to their magnetic counterparts [1]. These advantages
make SC converters desirable for a broad range of appli-
cations, including voltage balancing [2], CMOS integrated
power conversion [3]–[5] and renewable energy harvesting [6].
However, SC converters also have some drawbacks, which
limit their performance in some applications [7]. Since the
capacitors are directly charged/discharged by other capacitors
or voltage sources, large transient current spikes can occur,
which reduce the efficiency of the converter. Moreover, these
transient effects increase the device stress and can cause
undesirable Electromagnetic Interference (EMI) problems. To
mitigate the current spikes, either large capacitors or higher
switching frequency has to be employed, neither of which is a
satisfactory solution. Interleaved designs [8]–[10] can reduce
the current spike at the output and input terminals, but do not
solve the fundamental efficiency concerns.
Merged two-stage converters can eliminate the current
transient using soft-charging operation, while improving the
efficiency at the same time [11], [12]. In this architecture, the
output capacitor of the SC converter stage is removed and a
second-stage buck converter is cascaded to the output of the
SC converter to act as a controlled current load. As a result,
the SC stage is allowed to operate with a larger capacitor
voltage ripple without adversely affecting the efficiency, which
improves the energy utilization of the capacitors. The second-
stage buck converter operates with a low voltage stress, en-
abling an increase in the switching frequency, thereby reducing
the magnetic component size. The soft-charging technique can
result in significant power density and efficiency improvements
[12]–[14]. A formal method was presented in [15] to aid in
the design of such soft-charging SC converters.
Among the various SC converter topologies, the Dickson
converter [3], [16], [17] has efficient utilization of switches
but poor utilization of capacitors [18], and thus would benefit
significantly from soft-charging operation. However, it has
been demonstrated that the Dickson SC converter cannot
achieve full soft-charging operation with conventional, two-
phase control [15]. In this paper, the operation of the Dickson
converter is examined and the reasons for its inability to
achieve soft-charging are analyzed. Moreover, it is shown
that full soft-charging operation is possible for the Dickson
converter, something that to date has not been demonstrated. A
technique to achieve full soft-charging operation is proposed,
by splitting the original two switching phases into four [19].
Existing analytical methods are expanded to help understand
and design split-phase Dickson converters. The proposed tech-
nique does not introduce any additional component to the
original soft-charging operation, and can be realized with a
small additional control effort. The proposed technique and
analysis are confirmed by simulation as well as experimental
measurements of a converter prototype.
II. SOFT-CHARGING DICKSON CONVERTER
A 4-to-1 step-down Dickson SC converter is shown in Fig. 1
and the two conventional switching phases are shown in Fig. 2.
It should be clarified that the phase in this paper refers to the
state of the switching circuit and should not be confused with
’multi-phase’, which is sometimes used to mean interleaved
designs [10]. For conventional (hard-charging) operation, the
output capacitance Co is large and the load acts as a voltage-
source load. Thus, a large transient current occurs during
the phase switching instances due to the capacitor voltages
mismatch. This is the characteristic of the slow switching limit
Paper O8-1 Workshop on Control and Modeling for Power Electronics (COMPEL) 1U.S. Government work not protected by U.S. copyright
+−Vin
C2
C3
C1
Iload
S8 S7 S6 S5
S4 S1
S2S3
Vsc
Co
Fig. 1: 4-to-1 Dickson topology.
+−Vin Iload
C1
C3
C2
(a) Phase 1.
IloadC1
C3
C2
(b) Phase 2.
Fig. 2: Two-phase operation of a 4-to-1 Dickson converter.
(SSL) of SC converters [1]. The current through one of the
capacitors (C2) is shown in Fig. 3. It can be seen that there is a
large impulse current at phase transitions in the conventional,
hard-charging case (top plot). To minimize this impulse, large
capacitors or high switching frequency have to be employed
such that the converter operates in the fast switching limit
(FSL) [1]. In soft-charging operation, the output capacitance
is removed and a constant current load is used so that the
output voltage can change instantaneously to compensate for
the difference in capacitor voltages. By eliminating the voltage
mismatch and the resultant current impulse, the soft-charging
SC converter exhibit the same behavior as in FSL. Practical
implementations of the constant current load can be either a
magnetic converter [11] or an LC filter [18], [20], but for the
purpose of clear illustration, an ideal constant current load is
used in this section.
A. Conventional two-phase control
In addition to the current load, complete soft-charging op-
eration also requires that there is no voltage mismatch among
the parallel capacitor connections. For the two-phase control,
by applying KVL to the circuits in Fig. 2, the following
requirements can be found.
Start of Phase 1: Vin − VC3= VC2
− VC1(1)
Start of Phase 2: VC3− VC2
= VC1(2)
However, constraints (1) and (2) cannot be satisfied when
the Dickson converter is operated with a conventional, two-
phase control scheme. This can be seen from the following
simplified example. Let the capacitor voltages be VC3, VC2
and VC1respectively. At the start of Phase 1, we have⎡
⎢⎢⎣Vin
VC3
VC2
VC1
⎤⎥⎥⎦ =
⎡⎢⎢⎣4Vc
3Vc
2Vc
Vc
⎤⎥⎥⎦ , (3)
0 5 10 15 20
−25
0
25
Cur
rent
(A
)
Hard−charging
0 5 10 15 20
−25
0
25
Cur
rent
(A
)
Two−phase soft−charging
0 5 10 15 20−5
0
5
Time (μs)
Cur
rent
(A
)
Split−phase soft−charging
Fig. 3: Current waveform of capacitor C2 of the Dickson SC
converter. Simulation parameters: C1 = C2 = C3 = 10 μF,
fsw =100 kHz, Iload = 2 A.
where Vc is the smallest of the capacitor voltages. It can be
seen that (3) satisfies both (1) and (2). At the end of Phase
1, assuming equal capacitor values, the capacitor voltages
become ⎡⎣V ′
C3
V ′
C2
V ′
C1
⎤⎦ =
⎡⎣3Vc +ΔVc
2Vc −ΔVc
Vc +ΔVc
⎤⎦ , (4)
where ΔVc is the change in capacitor voltage due to charges
delivered to the load, and can be obtained by inspection or
KCL [18]. Testing constraint (2), we have
V ′
C3− V ′
C2= Vc + 2ΔVc �= V ′
C1. (5)
It should be noted that the preceding example only shows
a particular case chosen for simplicity, and a more rigorous
proof is presented in [15], which more rigorously analyzes why
the Dickson converter is unable to operate in soft-charging
mode with only two phases.. Due to the charge flow in each
phase, the voltages of the capacitors do not satisfy the KVL
for the next phase, and thus capacitor charge redistribution
loss is unavoidable, even with a current load at the output.
For the Dickson converter, this is due to the asymmetry in the
capacitor connection, particularly for the outer most (C3) and
inner most capacitor (C1). As can be seen in Fig. 2, these two
capacitors are in series with another capacitor in one phase
but not in the other phase. It can be shown that at the start of
Phase 1, VC2−VC1
is always greater than Vin−VC3. Similarly,
at the start of Phase 2, VC3−VC2
is always greater than VC1.
The resultant difference in capacitor voltages is present across
the switches during the phase transitions and creates large
transient current. Therefore, as can be seen in the middle plot
of Fig. 3, while the magnitude and width of the current impulse
Paper O8-1 Workshop on Control and Modeling for Power Electronics (COMPEL) 2
+−Vin Iload
C1
C3
C2
(a) Phase 1a.
IloadC1
C3
C2
(b) Phase 2a.
Iload
C1
C2
(c) Phase 1b.
IloadC3
C2
(d) Phase 2b.
Fig. 4: Split-phase operation of a 4-to-1 Dickson converter.
TABLE I: The RMS, average and peak values of current of
capacitor C2 in a single half period. Simulation parameters
are as in Fig. 3.
Configuration RMS (A) Average (A) Peak (A)
Hard-charging 3.52 1.00 27.3Soft-charging two-phase 1.91 1.00 15.8Soft-charging split-phase 1.15 1.00 2.00
are reduced with two-phase soft-charging operation, there is
still significant transient effect and associated losses.
B. Split-phase control
To ensure that the capacitor network results in the same
voltage at the output node, we propose the split-phase control
of the Dickson converter, with two secondary phases intro-
duced [19], as shown in Fig. 4. Phase 1a and 2a are the same
as Phase 1 and 2 in the original operation, while the Phase
1b configuration is a subset of Phase 1 and the Phase 2b
configuration is a subset of Phase 2. The switching sequence
is Phase 1b → Phase 1a → Phase 2b → Phase 2a. In Phase 1b,
C2 discharges and C1 charges, and thus VC2− VC1
decreases
while Vin−VC3stays the same. The circuit will transition from
Phase 1b to Phase 1a when VC2− VC1
equals Vin − VC1, i.e.
when (1) is satisfied. Similarly, the circuit will transition from
Phase 2b to Phase 2a when (2) is satisfied. Therefore, with the
introduction of these ’buffer’ phases, KVL is satisfied during
phase transitions and current transient can be eliminated. The
effect can be seen in the bottom plot of Fig. 3, which shows
the simulated split-phase results. With the proposed split-phase
operation, the current waveform has no transient component
at all, and is a constant value in each phase. To quantify the
improvement in the power transfer, the RMS, average and
peak values of capacitor current for a half-period duration are
calculated and tabulated in Table I. It can be seen that both
the RMS values and peak values can be greatly reduced with
split-phase control. By eliminating the current transient, the
converter efficiency can be improved and the current stress of
the devices can be reduced.
The control signals for both the original two-phase and the
TABLE II: Control of switches.
Switches S8 S7 S6 S5 S4 S3 S2 S1
Two-phase q1 q2 q1 q2 q1 q2 q1 q2Split-phase q
3q2 q1 q
4q1 q2 q1 q2
t=0 TT
2
q1
q2
q3
q4
Fig. 5: Control diagrams.
proposed split-phase operations are shown in Table II and
Fig. 5. It can be seen that the proposed switching sequence
only delays the turn-on of two switches (S5 and S8). Thus,
generating the extra phases in the split-phase operation does
not increase the switching frequency of the switches, ensuring
no added switching loss. Practical implementation of the
control can be duty ratio based or hysteresis based. In addition,
even though the technique is illustrated with a 4-to-1 Dickson
converter with only three flying capacitors, the technique is
applicable to Dickson converters with larger conversion ratios
without introducing more secondary phases [19].
III. ANALYSIS
While the preceding section presents an intuitive under-
standing why the split-phase control enables full soft-charging
operation of the Dickson converter, it is beneficial to formulate
a general analysis. The analytical method presented in [15]
applies to an SC converter with two phases, but for the
proposed split-phase control, a total of four different circuit
states are present. Hence, the method in [15] is extended to a
higher number of phases and presented in this section.
Complete soft-charging is achieved if and only if the ideal
capacitor network satisfies KVL at all times, including during
phase transitions. The aim of the analysis is to find the set of
charge flow vectors such that KVL is satisfied during phase
transitions. The charge vectors need to satisfy KCL while the
charge vector and the voltage change vector are related by the
capacitor values.
For a general SC circuit, a voltage vector can be defined
for the circuit elements as
v =[vin vc
T vout]T
, (6)
where vc is a column vector of the capacitor voltages. In each
phase of Fig. 4, the circuit consists of a number of closed
loops, where a KVL equation can be written for each loop.
These KVL equations can be lumped into a matrix-vector
product form [21] as
Aivi = 0, (7)
where Ai is called the reduced loop matrix for the ith phase.
In this paper, the entries of the loop matrices are positive if
Paper O8-1 Workshop on Control and Modeling for Power Electronics (COMPEL) 3
the circuit element is traversed from the negative terminal to
the positive terminal and vice versa. At the end of phase i, the
voltage vector becomes vi +Δvi, giving
Ai(vi +Δvi) = 0, (8)
where Δv represents the change in voltage due to charge
being delivered to the load. From (7) and (8), we have
AiΔvi = 0. (9)
Similarly, a charge flow vector is defined as the vector of
charge that flows into the positive terminal of each element in
the circuit and is given in the form of
q =[qin qc
T qout]T
. (10)
It should be noted that in some work, the charge vector is
normalized with respect the total charge delivered to the output
[1], but the unnormalized convention is used in this paper. In
each phase, KCL equations can be expressed by
Biqi = 0, (11)
where Bi represents the reduced incidence matrix [21]. More-
over, for a capacitor, the change in voltage and the charge flow
is related by
q = CΔvc , (12)
In addition, for periodic steady-state operation, there is also a
condition that the net charge that flows into a capacitor in a
period is zero: ∑phases
qi
c= 0. (13)
Combining the constraints given by equation (9) (11) (12)
and (13), the charge vectors (qi) required for soft-charging
operation can be obtained. A detailed derivation of the charge
flow vectors for the 4-phase Dickson converter in Fig. 4 is
provided in the appendix and only the result is given in
this section. Assuming equal flying capacitor values, the final
charge vectors are found to be
q1a
=
⎡⎢⎢⎣−2
2
−1
1
3
⎤⎥⎥⎦ , q
2a=
⎡⎢⎢⎣
0
−1
1
−2
3
⎤⎥⎥⎦ , q
1b=
⎡⎢⎢⎣
0
0
1
−1
1
⎤⎥⎥⎦ , q
2b=
⎡⎢⎢⎣
0
1
−1
0
1
⎤⎥⎥⎦ .
(14)
From the definition in (10), the last entries in the charge
vectors are the amount of charge delivered to the load.
Assuming a constant current load, the last entry of each of
the charge vector is thus equivalent to the relative duration of
each phase. Since the total charge delivered to the load in a
period is 8 units (3 + 3 + 1 + 1), we derive that for complete
soft-charging operation of the Dickson converter with equal
flying capacitance, the duty ratio of each phase is
T 1a =3
8, T 2a =
3
8, T 1b =
1
8, T 2b =
1
8. (15)
Another powerful result that can be obtained from the anal-
ysis is that soft-charging operation can be achieved regardless
of the order of the switching phases, since the preceding
derivation does not depend on the sequence of the phases. With
0 5 10 15 20−5
0
5
Cur
rent
(A
)
Split−phase sequence 1
0 5 10 15 20−5
0
5
Cur
rent
(A
)
Split−phase sequence 2
0 5 10 15 20−5
0
5
Time (μs)
Cur
rent
(A
)
Split−phase sequence 3
Fig. 6: Current waveform of capacitor C2 of the Dickson SC
converter. Simulation parameters are as in Fig. 3.
the proposed split-phase control, there are six total possible
sequences and 3 representative phases are shown below. While
sequence 1 is the same as found intuitively in Section II,
sequence 2 is the reverse of sequence 1; and in sequence 3, the
two original phases (Phase 1a and 2a) are adjacent instead of
being separated. The duration of each phase obeys that given
by (15).
Switching sequences:
1) Phase 1b → Phase 1a → Phase 2b → Phase 2a
2) Phase 2a → Phase 2b → Phase 1a → Phase 1b
3) Phase 1a → Phase 2a → Phase 1b → Phase 2b
Figure 6 shows simulated current waveforms for these switch-
ing sequences. It can be seen that all three of the switch-
ing sequences result in a non-impulse current, showing that
complete soft-charging operation is achieved. While all six
sequences are equivalent from the point of achieving soft-
charging operation, they have some different implications in
practical implementations, which will be discussed in Section
IV.
IV. SIMULATION AND EXPERIMENTAL RESULTS
To illustrate the benefit of the split-phase soft-charging
operation, the 4-to-1 step-down Dickson converter shown in
Fig. 1 is simulated using LTSpice with simulation parameters
given in Table III. Again, a constant current load at the output
is used for simplicity. In the hard-charging operation, the duty
ratio is fixed to 0.5 (as is convention) while the duty ratio of
the split-phase operation is found analytically as in Section
III.
The output referred impedance of a SC converter encapsu-
lates both the capacitor charge transfer loss and the conduction
Paper O8-1 Workshop on Control and Modeling for Power Electronics (COMPEL) 4
TABLE III: Simulation parameters.
Vin 40 V
Iload 2 A
Rds,on 10 mΩRESR 1 mΩ
C1, C2, C3 10 μF
Co,hard−charging 100 μF
Co,soft−charging None
104
105
106
107
10−2
10−1
100
Frequency (Hz)
Out
put i
mpe
danc
e (Ω
)
Two phase, hard−chargingTwo phase, soft−chargingSplit phase, soft−charging
Fig. 7: Simulated output impedance of the Dickson converter.
loss of the converter and is widely used to characterize
the performance of such converters [22]–[24]. The output
impedance for the Dickson converter is plotted in Fig. 7.
It can be seen that the conventional hard-charging Dickson
converter shows two regions of asymptotic behaviors as found
in previous literature [1]. At low frequencies (SSL), when
the power loss due to the current transient dominates, the
impedance decreases as switching frequency increases. The
impedance reaches a constant at high frequencies (FSL), when
the conduction loss dominates. As can be seen in Fig. 7,
with two-phase soft-charging operation, the impedance in the
SSL region is reduced significantly. This means that the soft-
charging converter is able to use smaller flying capacitance
while having the same output impedance at the same switching
frequency. However, there is still non-negligible frequency
dependent behavior since complete soft-charing operation can-
not be achieved on a conventional Dickson converter. With
the proposed split-phase control however, it can be seen that
now the output impedance is independent of the switching
frequency, due to the complete elimination of the charge
transfer losses. It should be noted that the impedance at high
frequencies is slightly higher than the FSL impedance of the
conventional two-phase operation. This is due to the fact that
in the added phases (Phase 1b and Phase 2b), there is one path
fewer that delivers current to the load, and hence a slightly
increased effective switch resistance. However, this increase
in conduction loss will be less noticeable as the converter
conversion ratio increases.
A hardware prototype has been implemented for the pro-
posed split-phase controlled soft-charging Dickson SC con-
verter, with a voltage step-down ratio of 8 to 1. The prototype
Fig. 8: Hardware prototype of the proposed converter.
TABLE IV: Design specifications.
Vin 200 V DC
Iload 3 A
Vout 25 V DC
fsw 50-500 kHz
uses 12 GaN switches and 7 flying capacitors. A photo of the
prototype is shown in Fig. 8 while the design specification
and component listing are provided in Table IV and Table V
respectively. The same converter is used for hard-charging as
well as soft-charging operation. The difference is that in soft-
charging operation, there is an extra inductor added to act as
a current load. Since the same capacitor values are used for
both hard-charging and soft-charging operation, the prototype
focuses on the improvement in efficiency at low switching
frequencies. It is also possible to optimize the hardware design
for power density improvement, or both. Even though the
additional inductor incurs an approximately 20% increase in
the components volume of the power stage, the total enclosed
box volume of the power stage increases to a lesser extent.
The voltage Vsc (as seen in Fig. 1) as well as the switching
functions are shown in Fig. 9. The switching signals are
slightly different from what is used in simulation (Fig. 5). This
is because using the original sequence (1b → 1a → 2b → 2a)
results in negative Vds voltages across some of the switches,
and bidirectional blocking switches would have to be used.
Since it has been shown by the analysis in Section III, that
the switching sequence does not matter, the actual sequence
used in practice is sequence 2 in Section III (i.e. 2a → 2b
TABLE V: Component listing of the proposed converter.
Component Part number Parameters
S12, S5 - S1 EPC2014 40 V, 16 mΩ, 10 AS11 - S6 EPC2007 100 V, 30 mΩ, 6 A
C4 - C7 C1812X224K2RACTU 250 V,2.2 μFC2, C3 C3216X7S2A225K160AB 100 V, 2.2 μF
C1 C3225X7R1H225K250AB 50 V, 2.2 μFCo C3216X5R1V226M160AC 35 V, 22 μF
Inductor XAL5050-562 5.6 μH
Level-shifting ADUM5210Micro-controller STM32f051
Paper O8-1 Workshop on Control and Modeling for Power Electronics (COMPEL) 5
Fig. 9: Output voltage (Vsc in Fig. 1) (upper) and switching
functions (lower).
→ 1a → 1b). This switching sequence results in no negative
Vds voltage and the converter operates without issues using
the GaN FETs.
The output impedance is plotted against the switching
frequency in Fig. 10, and is calculated from the measured
data using
Rout =Vin
N− Vout
Iout,
where N = 8 is the conversion ratio. It can be seen that
similar to the simulation results, the output impedance in hard-
charging operation increases as frequency decreases. Two-
phase soft-charging operation reduces the impedance at low
switching frequencies while the proposed split-phase operation
results in the lowest output impedance. For example, to achieve
the same output impedance as the split-phase operation at 100
kHz, the hard-charging converter has to switch at over 500
kHz. This means that the split-phase converter can reduce the
capacitor values by a factor of 5 if switching at 500 kHz.
Consequently, the reduced capacitor requirement more than
compensates for the additional volume of the added inductor.
In addition, the efficiencies of the converter in the SSL
region are plotted in Fig. 11. It can be seen that soft-charging
operation brings significant efficiency improvement while the
proposed split-phase control has the highest efficiency. The
split-phase soft-charging operation also has the smallest drop
in efficiency as the load increases, due to its smallest output
impedance. The hardware results also confirm that indeed the
split-phase control is effective for a Dickson converter with
high conversion ratios. It should be noted that both the output
impedance measurements and the efficiency measurements are
obtained using reduced input voltage and output current than
the rated values. This is to prevent the converter from breaking
because of the heat produced by the inefficient hard-charging
operation in the SSL region.
V. CONCLUSIONS
In this paper, we proposed a split-phase control method
that enables the Dickson SC converter to operate in soft-
charging mode. With complete soft-charging operation, the
proposed converter has no current transient and thus can
104
105
106
10−1
100
Frequency (Hz)
Out
put i
mpe
danc
e (Ω
)
Hard−chargingSoft−charging two−phaseSoft−charging split−phase
Fig. 10: Output impedance calculated from measured data.
0 0.5 1 1.5 280
85
90
95
100
Load current (A)
Effi
cien
cy (
%)
Hard−chargingSoft−charging, two−phaseSoft−charging, split−phase
Fig. 11: Measured efficiency of the Dickson converter in deep
SSL region. Vin = 40 V, fsw = 100 kHz.
achieve superior efficiency and/or power density compared to
conventional SC converters. The existing analysis is extended
to account for the split-phase and the desired duty ratio for
each phase is found. Besides supporting simulation results,
the proposed technique was experimentally verified with an
8-to-1 Dickson converter. The hardware prototype in soft-
charging operation has been shown to exhibit significantly
lower output impedance and higher efficiency in SSL region
than conventional SC converters.
APPENDIX
For the 4-to-1 Dickson converter in Fig. 4, The reducedloop matrices are
A1a =
[1 −1 0 0 −1
0 0 1 −1 −1
]A2a =
[0 1 −1 0 −1
0 0 0 1 −1
]A1b =
[0 0 1 −1 −1
]A2b =
[0 1 −1 0 −1
](16)
and the reduced incidence matrices are
B1a =
[0 1 0 1 −1
1 0 1 0 1
−1 −1 0 0 0
]B2a =
[0 1 1 0 0
0 1 0 1 1
1 0 0 0 0
]
B1b =
⎡⎢⎣0 0 1 1 0
0 0 0 1 1
1 0 0 0 0
0 1 0 0 0
⎤⎥⎦ B2b =
⎡⎢⎣0 1 1 0 0
0 0 1 0 1
1 0 0 0 0
0 0 0 1 0
⎤⎥⎦(17)
Paper O8-1 Workshop on Control and Modeling for Power Electronics (COMPEL) 6
In addition, since ΔVin is zero for constant voltage-source
input, another row of[1 0 0 0 0
]can be added to each
reduced loop matrix. Following this, the null space of each
matrix can be found and the basis of the capacitor voltage
change vectors that satisfy (9) and (16) are found to be
w1a
c=
⎡⎣0.12250.63250.7550
⎤⎦⎡⎣−0.6205
0.4472−0.1733
⎤⎦ w2a
c=
⎡⎣−0.2124−0.69680.4844
⎤⎦⎡⎣0.74490.33830.4066
⎤⎦
w1b
c=
⎡⎣100
⎤⎦⎡⎣010
⎤⎦⎡⎣001
⎤⎦ w2b
c=
⎡⎣100
⎤⎦⎡⎣010
⎤⎦⎡⎣001
⎤⎦ (18)
The basis for the possible charge vectors that satisfy (11) and
(17) are found to be
u1a
c=
⎡⎣−0.2443−0.61090.6109
⎤⎦⎡⎣ 0.5615−0.04320.0432
⎤⎦ u2a
c=
⎡⎣−0.4472
0.44720.7236
⎤⎦⎡⎣−0.4472
0.4472−0.2764
⎤⎦
u1b
c=
⎡⎣ 0−0.57740.5774
⎤⎦ u2b
c=
⎡⎣−0.5774
0.57740
⎤⎦ (19)
Each basis in (18) can be multiplied by the respective capacitor
values. The resulting basis can then be represented by
c ∗wi
c, (20)
where ∗ represents element-wise multiplication and c is given
by
c =
⎡⎣C3
C2
C1
⎤⎦ . (21)
To find the actual charge flow, the common space spanned by
(20) and (19) are then found to be
q1a
c=
⎡⎣ 0.3714−0.18570.1857
⎤⎦ q2a
c=
⎡⎣−0.2000
0.20000.4000
⎤⎦
q1b
c=
⎡⎣ 0−0.57740.5774
⎤⎦ q2b
c=
⎡⎣−0.5774
0.57740
⎤⎦ .
These are the basis for the charge vectors which satisfy KCL
and that results in a capacitor voltage change that satisfies
KVL. Finally, using the steady-state condition given in (13),
the overall charge flow vectors are found as in (14).
REFERENCES
[1] M. Seeman and S. Sanders, “Analysis and optimization of switched-capacitor dc-dc converters,” Power Electronics, IEEE Transactions on,vol. 23, no. 2, pp. 841–851, March 2008.
[2] K. Sano and H. Fujita, “Voltage-Balancing Circuit Based on a ResonantSwitched-Capacitor Converter for Multilevel Inverters,” IEEE Transac-
tions on Industry Applications, vol. 44, no. 6, pp. 1768–1776, 2008.
[3] J. Dickson, “On-chip high-voltage generation in mnos integrated circuitsusing an improved voltage multiplier technique,” Solid-State Circuits,
IEEE Journal of, vol. 11, no. 3, pp. 374–378, Jun 1976.
[4] V. Ng, M. Seeman, and S. Sanders, “Minimum pcb footprint point-of-load dc-dc converter realized with switched-capacitor architecture,” inEnergy Conversion Congress and Exposition, 2009. ECCE 2009. IEEE,Sept 2009, pp. 1575–1581.
[5] Y. Ramadass and A. Chandrakasan, “Voltage scalable switched capacitordc-dc converter for ultra-low-power on-chip applications,” in Power
Electronics Specialists Conference, 2007. PESC 2007. IEEE, June 2007,pp. 2353–2359.
[6] J. Stauth, M. Seeman, and K. Kesarwani, “Resonant switched-capacitorconverters for sub-module distributed photovoltaic power management,”Power Electronics, IEEE Transactions on, vol. 28, no. 3, pp. 1189–1198,2013.
[7] S. Sanders, E. Alon, H.-P. Le, M. Seeman, M. John, and V. Ng, “Theroad to fully integrated dc-dc conversion via the switched-capacitorapproach,” Power Electronics, IEEE Transactions on, vol. 28, no. 9,pp. 4146–4155, 2013.
[8] J. Han, A. Von Jouanne, and G. Temes, “A new approach to reducingoutput ripple in switched-capacitor-based step-down DC ndash;dc con-verters,” Power Electronics, IEEE Transactions on, vol. 21, no. 6, pp.1548–1555, 2006.
[9] M.-H. Huang, P.-C. Fan, and K.-H. Chen, “Low-ripple and dual-phasecharge pump circuit regulated by switched-capacitor-based bandgapreference,” Power Electronics, IEEE Transactions on, vol. 24, no. 5,pp. 1161–1172, May 2009.
[10] S. Kiratipongvoot, S.-C. Tan, and A. Ioinovici, “Switched-capacitorconverters with multiphase interleaving control,” in Energy Conversion
Congress and Exposition (ECCE), 2011 IEEE, Sept 2011, pp. 1156–1161.
[11] R. Pilawa-Podgurski, D. Giuliano, and D. Perreault, “Merged two-stage power converter architecture with soft-charging switched-capacitorenergy transfer,” in Power Electronics Specialists Conference, 2008.
PESC 2008. IEEE, Jun. 2008, pp. 4008–4015.[12] R. Pilawa-Podgurski and D. Perreault, “Merged two-stage power con-
verter with soft charging switched-capacitor stage in 180 nm cmos,”Solid-State Circuits, IEEE Journal of, vol. 47, no. 7, pp. 1557–1567,July 2012.
[13] M. Chen, K. Afridi, and D. Perreault, “A multilevel energy bufferand voltage modulator for grid-interfaced micro-inverters,” in Energy
Conversion Congress and Exposition (ECCE), 2013 IEEE, Sept 2013,pp. 3070–3080.
[14] S. Lim, D. M. Otten, and D. J. Perreault, “Power conversion architecturefor grid interface at high switching frequency,” in The Applied Power
Electronics Conference and Exposition (APEC), 2014 IEEE, 2014.[15] Y. Lei and R. Pilawa-Podgurski, “Analysis of switched-capacitor dc-
dc converters in soft-charging operation,” in Control and Modeling for
Power Electronics (COMPEL), 2013 IEEE 14th Workshop on, June2013, pp. 1–7.
[16] H. Greinacher, “ber eine methode, wechselstrom mittels elektrischer ven-tile und kondensatoren in hochgespannten gleichstrom umzuwandeln,”Zeitschrift fr Physik A Hadrons and Nuclei, vol. 4, pp. 195–205, 1921.
[17] J.-T. Wu and K.-L. Chang, “MOS charge pumps for low-voltageoperation,” Solid-State Circuits, IEEE Journal of, vol. 33, no. 4, pp.592–597, Apr. 1998.
[18] M. D. Seeman, “A design methodology for switched-capacitor dc-dc converters,” Ph.D. dissertation, EECS Department, University ofCalifornia, Berkeley, May 2009. [Online]. Available: http://www.eecs.berkeley.edu/Pubs/TechRpts/2009/EECS-2009-78.html
[19] R. May, “Analysis of soft charging switched capacitor power convert-ers,” Master’s thesis, ECE Department, University of Illinois, UrbanaChampaign, Aug. 2013.
[20] Y. Lei and R. Pilawa-Podgurski, “Soft-charging operation of switched-capacitor dc-dc converters with an inductive load,” in The Applied Power
Electronics Conference and Exposition (APEC), 2014 IEEE, 2014.[21] L. O. Chua, C. A. Desoer, and E. S. Kuh, Linear and Nonlinear Circuits.
Mcgraw-Hill College, 1987.[22] P. Lin and L. Chua, “Topological generation and analysis of voltage
multiplier circuits,” IEEE Transactions on Circuits and Systems, vol. 24,no. 10, pp. 517–530, Oct. 1977.
[23] M. Makowski and D. Maksimovic, “Performance limits of switched-capacitor dc-dc converters,” in Power Electronics Specialists Conference,
1995. PESC ’95 Record., 26th Annual IEEE, vol. 2, Jun 1995, pp. 1215–1221 vol.2.
[24] B. Arntzen and D. Maksimovic, “Switched-capacitor dc/dc converterswith resonant gate drive,” Power Electronics, IEEE Transactions on,vol. 13, no. 5, pp. 892–902, Sep 1998.
Paper O8-1 Workshop on Control and Modeling for Power Electronics (COMPEL) 7