What makes a “Good Pile”?To perform successfully, a pile

should:

•• Have adequate soil resistanceHave adequate soil resistance

•• Be structurally soundBe structurally sound

These are two separate requirements both must be satisfied

Page 3: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Assess Loads

Site Investigation

Select Pile Type

SPT, Cone, Pressuremeter

Estimate Pile Length

ExperienceAvailable EquipmentEnvironment

Quality Assurance of FoundationsQuality Assurance of Foundations-- Design AspectsDesign Aspects

Page 4: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Estimate Pile Length

QA/QC Program• Initial• Production

Static Analysis MethodApplicable CodesDrivabilityConstructabilityServiceability

Static Load TestDynamic Load TestPile Integrity Test

Factor of SafetyFactor of SafetyFactor of Safety

RiskRiskRisk

FactsFactsFacts

Quality Assurance of Deep Foundations Quality Assurance of Deep Foundations Design AspectsDesign Aspects

Page 5: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

On most sites, the reality is quite different

Bored Pile Quality: Do the piles Always look Bored Pile Quality: Do the piles Always look like this?like this?

Page 6: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

How can we test the quality of bored piles?How can we test the quality of bored piles?

Any of these piles could have major defectsAny of these piles could have major defects

Page 7: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

QA/QC:

Unplanned TestingIn response to something gone wrongExtra costs & project delays

Planned Testing (PreferredPreferred)Included in project specificationsPlanned costs - normal pay item

Page 8: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Quality Assurance by Load Tests

Installation Monitoring during construction

Pile Load Testing – using dead load or anchor piles

Load carrying capacity – Geotechnical Quality

But these tests only confirm the safe load carrying But these tests only confirm the safe load carrying capacity of the tested piles.capacity of the tested piles.

How to ensure that all piles are of desired How to ensure that all piles are of desired quality?quality?

Page 9: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Quality Assurance – Modern ToolsPulse Echo Method / Low Strain Pile Integrity Testing (PIT)- For Pile Integrity, structural qualityFor Pile Integrity, structural quality

Sonic Logging / Tomography Test- For Pile Integrity, For Pile Integrity, structural qualitystructural quality

Parallel Seismic Test- For Determining Unknown For Determining Unknown Foundation DepthFoundation Depth

High Strain Dynamic Load Testing ForFor Structural Structural Quality, Assess Load Carrying CapacityQuality, Assess Load Carrying Capacity

Page 10: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Load TestingLoad Testing

PDA / CAPWAPPDA / CAPWAP-- 19701970(ASTM D4945)(ASTM D4945)

Dynamic Load TestingDynamic Load Testing

Dyn. Formula Dyn. Formula -- 18901890

Wave Equation Wave Equation -- 19501950

Static Load TestingStatic Load Testing

Dead load TestingDead load Testing

React. piles/anchorsReact. piles/anchors

Bottom AppliedBottom Applied--OsterbergOsterberg CellsCells

Page 11: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Static tests are costly and time consuming,so they are not Static tests are costly and time consuming,so they are not always the best answeralways the best answer

Page 12: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Pile Load Test using Anchor Piles – 700 tonnes capacity

At Commonwealth GamesAt Commonwealth GamesVillage Complex, DelhiVillage Complex, Delhi

Page 13: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...
Page 14: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Low Strain Integrity MethodsPILE INTEGRITY TESTING (PIT)

Measure Pile Top Motion, Reflections from Defects

CROSS-HOLE SONIC LOGGING (CSL)

Determines Concrete Quality Between Tubes in Shaft

For large diameter bored piles

PARALLEL SEISMIC (PS)

Hit Pile, Measure Hydrophone in Parallel Tube

Determines only Pile Length

Page 15: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Why Do Pile Integrity Testing?• prime function is to locate major defects (to evaluate questionable shafts)• inexpensive, can test many piles (good for quality assurance)• no advance selection required (good for forensic purposes)

Page 16: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Low Strain Pile Integrity Testing (PIT)

Page 17: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Grinding top surface to make flat spotGrinding top surface to make flat spot

Pile top preparation is key to good data which is the key to Pile top preparation is key to good data which is the key to best interpretation. Shortcuts cause questionable data.best interpretation. Shortcuts cause questionable data.

Preparation..

Page 18: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

FF

ΔΔLL

Compressed Zone, racesalong pile at wave speed c

c is the wave speed of the pile material c is the wave speed of the pile material

In a time In a time ““ΔΔtt”” the wave travels a distance the wave travels a distance ΔΔL = c L = c ΔΔtt

Wave Propagation

Page 19: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Pile Integrity Tester: PITPulse Echo Method

Accelerometer measures response

defectdefect

Good

Bad

Small hammer impact device

(defect)

Page 20: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Good PileGood Pile

800 mm bored cast in-situ pile

L = 25 m (L/D = 31)

Bad PileBad Pile

Normal test (pile top “free”)

PIT - Basic Interpretations

Page 21: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Any of these piles could have a defect….

How many piles should I test?

PIT is fast & cheap- test ALL piles for best results!!

Page 22: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

PIT LimitationsAs per published literature, piles with L/D ratio upto

30 give reasonably good results

Highly non-uniform piles may be difficult to interpret

Cracks or mechanical joints block waves

Small defects or short length hard to find

Not always applicable: inconsistent or non-ideal

data may be difficult to interpret

No direct correlation to pile capacity; but can help to

identify which piles to load-test

Page 23: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...
Page 24: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

High Strain Dynamic Pile Testingwith the Pile Driving Analyzer ®

Page 25: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

PDA Benefits to Project

•Confirms safe pile capacity

•Great savings in time and cost – test more piles at the

same cost, in less time

•Improves quality assurancePDA can test piles to reduce costs and save PDA can test piles to reduce costs and save timetime

Page 26: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Motion is measured Motion is measured by accelerometersby accelerometers

strainstraingaugegauge

FF(t)(t)

accelerometeraccelerometer

vv(t(t))

Load is appliedLoad is appliedby impacting ramby impacting ram

Load is measured byLoad is measured bystrain transducersstrain transducers

Dynamic Pile TestingDynamic Pile Testing

Page 27: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Attach sensors to concrete Attach sensors to concrete on a flat surfaceon a flat surface

4 sets of sensors4 sets of sensors

Page 28: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Ram: concrete filled pipeRam: concrete filled pipe

Page 29: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Dynamic Pile Monitoring

For each blow, determine:– Safe Pile Capacity– Pile Integrity– Pile Stresses– Hammer Performance

Last three items detect or prevent problems in the piles as-installed

Page 30: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Dynamic Pile TestRecognized by ASTM, IRC Codes. Soon to be included in IS Codes. Uses available or easy-to-make drop hammers and minimal pile preparationConfirms safe pile capacity, even at large loadsReduced testing time with large cost savings (cost may be 5 to 20 times less than static load tests)8 Channel PDA preferred for bored pilesResults must be analyzed by trained PDA professionals!!Use in conjunction with static load tests

Page 31: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Cross-hole Sonic Logging&3D Tomography

Page 32: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Cross-hole Sonic Logging (CSL)ASTM D6760

Stress Waves, emitted in one tube are receivedin another one if concretequality is satisfactoryTransmit Receive

Place probes in bottom of

tubes.

(Same test for each tube

pair)

Page 33: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

2D horiz. slice of a defect

2D horiz. slice of a defect

3D body view3D body view 2D vert. slice2D vert. slice

Page 34: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Parallel Seismic Test

Page 35: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...
Page 36: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Parallel Seismic Test2. Lower Hydrophone in PVC pipe within 3 m of pile

•Determines unknown pile length •Requires parallel bore installed•Does not determine integrity

Time

1. Impact Foundation

3. Pick first arrival waves

4. Break in slope indicates foundation depth

Page 37: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...
Page 38: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Project Details66-story residential tower- 240 m highDouble Basement (9m below grade)3,400 m2 circular footprintFoundation System

Piled-raft; 2.5m thick Raft @ 9m depth298 bored piles of 1m dia and 48m length

Construction is presently Construction is presently underway!underway!

Page 39: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Field Investigation

1 BH1 PMT1 CHST

Page 40: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Borehole Data

Medium dense to dense

alluvial sand to 37m depth

Hard clay to 41-50m depth

Very dense sands / silt

(N>100) to 60 m depth

GW at 11m depth below

OGL

Page 41: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Pressure meter Test Data

Page 42: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Cross-hole Seismic Test Results

Page 43: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Theoretical Pile CapacitiesBoundary Conditions:

1m dia bored pilesCOL @ 10m depth (Basement Level)GWT considered @ COL

Pile length below COL, m

Ultimate Pile Capacity, MN

Compression Pullout

44 11.6 4.046 12.2 4.348 13.2 4.5

Page 44: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Initial (Static Load Tests)

1m dia

25m long test piles

COL ~ 2-3m below GL as

against 10 m for working

piles

Pile Settlement < 25mm at

10 MN compressive load

Page 45: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Routine Static Load Tests

Concrete blocks used as kentledge

1m dia, 48m long production piles @ COL of 10m Hydraulic Jacks

with synchronized pumping unit

Page 46: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

High-Strain Dynamic Load Tests

20 MT drop hammer0.5-3m drop heights4-strain transducers, 2 accelerometersrecommended

6 HSDLT were performed using PDA

Page 47: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Routine Pile Load Test Results

Load test results are fairly consistent

However, pile performance is very poor as compared to theoretical estimates (13MN) and initial pile load test results on 25m long piles

Settlement of 48m long piles is almost twice as much as 25m test piles

Structural defects & ‘soft-toe condition’ suspected

Very Good Match!!!

Page 48: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Low-Strain Pile Integrity Tests (PIT)

298 Piles

8 lbshand-held hammer

Page 49: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

PIT ResultsPIT on 298 production pilesGenerally speaking:

Significant impedance changes along the pile shaftBulging at shallow depths (2.5-4.5m)-confirmed by pile exposuresWeak toe response-possible ‘soft toe condition’ and low pile end bearing

Pile 1103

Page 50: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

PIT: Profile Analysis- Pile 1079

Pile No. 1079

Page 51: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Pile Coring- 1079

0m to 7.5m depth

0 m

7.5 m

Page 52: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Pile Coring- 1079

7.5m to 13.5m depth

Nil recovery 11.5mNil recovery 11.5m--12m12m

7.5 m

13.5 m

Page 53: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Pile Coring- 1079

13.5m to 19.5m depth

13.5 m

19.5 m

Page 54: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Pile Coring- 1079

19.5m to 28.5m depth

19.5 m

28.5 m

Page 55: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Pile Coring- 1079

28.5m to 35.0m depth

28.5 m

35.0 m

Page 56: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Pile Coring- 1079

35.0m to 44.5m depth

Slush encountered below 44.5m depthSlush encountered below 44.5m depth-- confirms confirms suspected suspected ‘‘soft toesoft toe’’ conditioncondition

35.0 m

44.5 m

Page 57: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

PIT vs. Pile Coring- 1079

NeckingNecking

‘Soft Toe’

NeckingNecking

Page 58: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Design Ramifications

Lowered pile stiffness was considered in the analysis

(nil end bearing)

Final design of the piled-raft system was updated with

reduced ultimate pile capacities / stiffness

Additional piles were constructed under the raft

Page 59: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...
Page 60: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Layout Plan

Page 61: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Commercial Complex / Hotel at Dwarka, New Delhi

5 star hotel-cum-

commercial complex

Three basements –

basement floor at 15.5 m

depth

Planned as TOP-DOWN

construction to speed up

construction

Page 62: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

StratigraphyIndo-Gangetic AlluviumDeposits consist primarily of sandy silt (Delhi Silt) of low plasticity with minor siltysand layersSPT values:

0-7 m depth: 14-367-13 m depth: 30-4713-20 m depth: 39-6620-60 m depth: > 100

Groundwater Level: 21.2 m depth (Feb 2009)

Page 63: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Design Profile

Depth Stratum ckN/m2

φ◦ γ kN/m3

0.0 15.5 Sandy Silt/Clayey Silt

Above Cut-off Level

15.0 25.0 Very dense Sandy Silt/Clayey Silt

300 0 19

25.0 40.0 Very dense Sandy Silt/Clayey Silt

0 31 19.5

40.0 60.0 Very dense Sandy Silt

0 33 20

Design Water Table level considered at 15 m depth

Page 64: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Computed Static Pile Capacities

Pile Dia. (mm)

Pile Length Below Cut-Off Level1

(m)

Computed safe axial compressive pile capacity2 (MN)

1600 25 (40.5) 11.7927 (42.5) 12.4930 (45.5) 13.5432 (47.5) 14.23

1-Pile cut-off level is considered at 15.5 m below Ground Level. Pile lengths from ground level are presented in brackets

2-Design safe working loads include a Factor of Safety of 2.5

Page 65: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Construction Sequence

Install 1600 mm diameter deep bored cast in-situ piles from ground levelAfter piles are installed, excavation for basement shall be taken upPortion of pile above basement level shall act as column, that below basement shall contribute to pile capacityConstruction of superstructure shall be taken up simultaneously

Page 66: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Tests for Quality Assurance

TOTAL 55 PILES INSTALLED

1600 mm dia 47.5 m below EGL, 32 m below COL

No initial pile load test conducted

One Static Load Test conducted on working pile

37 Low Strain Pile Integrity Test (PIT)

5 High Strain Dynamic Load Test (HSDLT)

1 Osterberg Cell Load Test (O-Cell)

Page 67: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

PIT Results

Minor Impedance reduction at 15 m depth

Impedance reduction below 17.5 m depth. Toe Response WeakIntegrity Doubtful

Page 68: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Impedance reduction below 36 m depth. Weak Toe ResponseIntegrity Doubtful

Impedance reduction below 22 m depth. Integrity Doubtful

Page 69: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

High Strain Dynamic Load Tests

Pile No.

Pile Diameter

(mm)

Total Pile Length

(m)

Test Load 1(MN)

CAPWWAPUltimate Pile

Capacity 1 (MN)

Design Safe Working

Load (MN)

F.O.S

E41 1600 48.3 21.34 20.6 14.23 1.45

F51 1600 48.3 21.34 8.5 14.23 0.6

E52 1600 47.0 21.34 7.2 14.23 0.5

A41 1500 48.3 18.63 18.1 12.42 1.45

C1-43 1500 44.5 18.63 8.4 12.42 0.7

1 After eliminating shaft friction for the top 15.5 m to account for basement excavation

Page 70: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

CAPWAP Analysis: Pile E-52

Interpreted Ultimate Capacity: 7.2 MN

Page 71: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Osterberg Cell Bi-Directional Load Test

Test pile – boring done to 48.8

m depth, concreting done to

8.3 m depth below GL

Pile length 39.6 m, effectively

33.3 m below COL

O-Cells installed at 40.5 m

depth below GL i.e. 8.3 m

above pile toe

Page 72: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Interpreted Ultimate Capacity

Interpreted ultimate capacity of lower shaft and base =

7.38 MN

3.62 MN contribution of lower shaft,

3.76 MN contribution of base

Lower Shaft failed at 2.5 MN, net settlement 16 mm

Base carried 2.6 MN, settlement approaching 160 mm

Interpreted Ultimate Pile Capacity = 9 MNInterpreted Ultimate Pile Capacity = 9 MN

Page 73: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Summary of Load Test Results

Method of Analysis Interpreted Ultimate Pile Capacity1

(MN)

Allowable Safe Working Pile Capacity2

(MN)

F.O.S3

Static Load Test 16 6.4 1.12Osterberg Cell

Load Test9.0 3.6 0.63

HS Dynamic Load Test

7.2 to 20.6 2.9 to 8.2 0.5 - 1.45

1 Based on Load test extrapolation of upper bound hyperbolic curve for upper portion of the pile2 Assuming a Factor of Safety of 2.5 on ultimate pile capacity3 Factor of Safety for estimated ultimate pile capacity against current safe working capacity (14.2 MN)

Page 74: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Pile Above Basement Level

FF--5151FF--5252

EE--5151

Page 75: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Quality of Piles Exposed above Basement Level

Pile diameter not uniform, substantial necking / bulging

observed in some piles

Reinforcement exposed, bent

Centre of pile / column at basement floor level was off

by over 500 mm in some cases

Some piles were visually out of plumb, so using as

column was aesthetically unpleasant

Page 76: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Reinforcement Exposed

Page 77: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Repair Work in Progress

Page 78: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Safe Pile Capacities De-Rated

Additional piles installed below basement levelPiled-Raft analysis done to assess the overall settlement and safety of the foundation systemOf course it led to contractual issues:

Blame all involved – soil consultant, structural consultant, building contractor, piling agency – all were under scrutinyClient suffered!!Client suffered!! – Project delayed, resulted in direct & indirect losses

Page 79: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...
Page 80: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Case Study 3: Noida Mall

800 mm dia Bored Cast in-situ piles in sandInitial Cyclic Pile Load Test:

Qult = 270 MTQsafe = 135 MT

14 PIT were performed on initial and routine piles

0

10

20

30

40

50

60

70

80

90

0 50 100 150 200 250 300 350

Load (MT)

Sett

lem

ent

(mm

)

Field Data

Extrapolated Values

Qsafe (MT) = 135.0

Plungi

ng

Failu

re

270 MT

Page 81: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Case Study 3: Noida Mall

7 m

Original Ground Level

Excavated Level, Pile COL

Pile Toe Level

27 m

Page 82: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Case Study 3: Noida Mall

Major defect at 16~18 m depth (or short pile)

Page 83: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...
Page 84: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

A view of the Bridge

Page 85: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Testing in Progress

Page 86: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Test Results

Page 87: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...
Page 88: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

““There is many a slip twixt the cup and the There is many a slip twixt the cup and the liplip””

A well-planned, comprehensive & robust QA program for the

foundations is essential to ensure adequate performance and

avert disaster

Keep the geotechnical engineer the and structural engineer

involved throughout the foundation construction process

More testing justifies lower F.S., leading to More testing justifies lower F.S., leading to significant significant cost savingscost savings

Page 89: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Just doing the tests is not enough! Just doing the tests is not enough!

Proper interpretation of the test results by an independent agencyCorrelate all information and test results -geotechnical data, pour card information, test results, etc.Improve the design as well as the construction methodology in parallel to get maximum benefitMany reliable test methods available, but Many reliable test methods available, but results are only as good as the testing results are only as good as the testing agency!!agency!!

Page 90: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

What are the consequences of insufficient testing?What are the consequences of insufficient What are the consequences of insufficient testing?testing?

•failed structure (loss of use, life??)

• high remediation costs

•increased insurance costs

Can we afford to skip installation monitoring and Can we afford to skip installation monitoring and eliminate followeliminate follow--up NDT?up NDT?

Page 91: Identifying Defects in Large Dia Piles for PDF · Small defects or short length hard to find Not always applicable: inconsistent or non-ideal data may be difficult to interpret ...

Let us strive to achieve quality in pile construction

THANK YOU…