Icpe Actel - Presentation of Sratn

download Icpe Actel - Presentation of Sratn

of 18

Transcript of Icpe Actel - Presentation of Sratn

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    1/18

    STATIC EXCITATION EQUIPMENT

    SRATN

    made by S.C. ICPE ACTEL S.A., ROMANIA, Bucharest

    (Research Institute for Electrical Engineering - Electric Drives)

    CATEGORY CODE

    SRATNIEN/UENUPL - 1/2 - 3

    S = systemR = regulationA = automatic

    T = voltageN = digitalIEN = Excitation system rated current (Adc) - direct current at the excitation output

    terminals which the excitation system can supply under defined conditions of

    operation (taking in account the most demanding excitation requirements ofthe machine);

    UEN = Excitation system rated voltage (Vdc) - direct voltage at the excitation outputterminals which the excitation system can provide when delivering excitation

    rated field current;UP = Excitation ceiling voltage (Vdc) - The maximum direct voltage which the

    excitation system is able to provide from its terminals under defined

    conditions;1 = one rectifying bridge (without redundancy in the power circuit)

    2 = two rectifying bridges (100% redundancy)3 = excitation transformer (installed in cubicle), for excitation current over 50ADC.

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    2/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    2

    The parametrization range offered by ICPE ACTEL for Static ExcitationEquipment is:

    Three-phase supply voltage (Usupply) +10%, -15%: 3x400Vac or another

    voltage, by means of a transformer.

    Rated power (PN). Generator: 3...330MW; Motor: 100kW...8MW.

    Maximum rated excitation current (IEN max). Generator: 3200Adc; Motor:

    1600Adc.

    Rated excitation voltage (UEN): related to synchronous machine excitation

    parameters.

    Control accuracy: 0,5%.Maximum forcing coefficient for current and voltage: 2.

    Based on the support of its highly qualified specialists, ICPE ACTEL has focused

    its activities on offering not only products, but also complete solutions, custom

    made to meet the clients requirements, for normal and extreme climate.

    Our products are always accompanied by technical assistance and additionalservices throughout their entire lifespan, from drawing-up of then application

    up to the client training.

    SRATN is found in almost all hydro and steam power plants in Romania. ICPE

    ACTEL has also exported such equipment in: France, Turkey, India, Republic of

    Moldavia, Kenya, Thailand and Vietnam.

    Concerning the applications ofSRATN for synchronous motors, some references

    are as follows: Iraq, Republic of Moldavia, Arcelor Mittal- Galati, Romgaz

    Medias, Hidroelectrica and SNCF (Railway National Society) in Romania.

    ICPE ACTEL is a reliable long-term partner.

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    3/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    3

    Static excitation equipment provides supply, control and protection ofsynchronous machine excitation: generators in hydro and steam power plants and

    synchronous motors for various applications.

    They ensure a stable and safe operation of synchronous machines, especially

    relevant when these machines are connected to the public mains, characterized by alot of perturbations due to connecting and disconnecting of important loads, short-

    circuit, etc.

    Common applications are:

    - supply of the generator's field windings in hydro and steam power plants,connected to a public mains;

    - supply of synchronous motor's field windings for applications such as fans,air compressors, debit pumps, water feed pumps.

    The excitation system provides the dc power supply required by the

    synchronous machine field circuit to meet the specified ratings and operating ranges

    of the generator/motor for all operating condition.

    The excitation system is a static type. Its main power device consists in 3-

    phase full wave thyristor rectifier bridges supplied from the ac terminals of the

    synchronous generator/ motor or from an independent power supply.

    The excitation system has a microproccesor based digital type automaticvoltage regulator and rectifier control that brings the suitable operating stability for

    the synchronous generator/motor.

    ADVANTAGES

    Static excitation equipment, fitted with a digital control solution, ensures:

    - higher stability of parameters related to electromagnetically perturbations andenvironmental condition variations;

    - user friendly interface, with many settings and diagnosis options;- strict monitoring of internal and external failures, that lead to equipment

    tripping;

    - possibility of complete remote control;- enhanced reliability;

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    4/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    4

    WHY ICPE ACTEL?

    - Higher safety of the operating process, due to digital control and significantsubassembly redundancy;

    - Enhanced availability and competence in custom-made equipment (functions,special environment conditions, new design alternatives on demand);

    - Possibility of intervention, software programming and license granting for theoperating mode parameter setting;

    - Enhanced efficiency;- Higher availability through additional preset options;- Advanced diagnostic capabilities for failure analysis;- Cost saving and oriented solution in accordance with the clients budget;- Technical assistance throughout the entire product lifespan from mounting to

    post guarantee service.

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    5/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    5

    FUNCTIONAL DESCRIPTION

    Static excitation equipment, especially in hydro and steam power plants

    represents a complex type of product, meant to provide the control and protection of

    synchronous machine excitation in a large range of perturbations and in compliance

    with the requirements of electric generators correct running.The technology of public mains is, by itself, a complex process, which has to face

    several specific perturbations, such as the connecting and disconnecting of

    important inductive loads, local and remote short-circuits, sudden unloading,

    automatic turn-on of stand-by equipment.

    The power supply systems, with static excitation equipment as their core,have to operate very stably and safety, in the event of such perturbations.

    Static excitation equipment is meant to preserve generator set-points with high

    accuracy, in strict respect of its stability diagrams (synchronous machine limit

    values, cross current criterion, line drop compensation criterion, etc.) and provide avery accurate dynamic regime.

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    6/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    6

    SRATNBloc Diagram (example)

    3x...kV/3x...V

    TTA...kVA

    3x...kV/....V

    3x...kV/3x...V

    10VA

    I

    =........A

    x

    ne

    U

    =......V

    nex

    Pn=.....MW

    Un=.....kV

    In=........A

    cos

    =......

    +Ex

    Fieldflash

    voltagedc/ac

    Digitalinput

    signals

    SRATNEXCITATION

    SYSTEM

    10VA

    GeneratorCircuitBreaker

    BRIDGE1

    BRIDGE2

    DCGN=Digitalfiringpulsesboard

    DCGN

    PLC

    AVR1

    Measuring

    Board

    PLC

    AVR2

    BRIDGE1,BRIDGE2-fullwaveth

    yristorrectifiers

    AVR1,AVR2-PLCwithAutomaticV

    oltageRegulator

    MAN1,MAN2-PLCwithFieldCurrentRegulator

    FFC-FieldFlashCircuit

    FDC-FieldDischargeCircuit

    ......A/....A

    DCGN

    DCGN

    PLC

    MAN1

    Operating

    panel

    Measuring

    Board

    Measuring

    Board

    PLC

    MAN2

    Measuring

    Board

    Optionaldevices

    FFC

    FDC+

    Crowbar

    DCGN

    TTA...kVA

    3x...V/....V

    Auxilia

    ry

    power

    supply

    dc/ac

    Digitaloutput

    signals

    Analogoutput

    signals

    Comunication

    forSCADA

    RS232

    RS485

    RJ45

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    7/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    7

    Rectifier power supply voltage : Max 3 x 750V AC. +20% , -20%

    Power supply frequency: 50Hz 5%

    Field flash power supply: - from the power plant battery

    - from the auxiliary ac power supply

    Control electronics power supply

    voltage

    - 3 x 400V/ 230 (Vac)// max 10A

    - power plant battery 24/ 110/ 200 (Vdc) // max10AMaximum output voltage: Minimum 1,2*U supply

    Forcing in current: Minimum 1.8*In excitation for 30 sec

    Forcing in voltage: Minimum 1.8*Un excitation

    Control Modes: AVRVOLTAGE REGULATOR

    POWER FACTOR REGULATOR

    REACTIVE POWER REGULATOR

    MANUAL:

    CURRENT REGULATOR (FCR)

    VOLTAGE REGULATOR (AVR)

    mode has the following control

    loops:

    - control for machine voltage

    - maximum field current limitation with inverse time

    delay characteristic;

    - stator current limitation with inverse time delay

    characteristic for leading or lagging working of the

    machine;

    - lead or lag reactive power working limitation,

    according to the real power;

    - V/Hz limiter

    - load (cross) current compensation;- soft start;

    - power system stabilizer - PSS1A/ PSS2A;

    POWER FACTOR REGULATOR

    (APFC) mode has the following

    control loops:

    - control for (cos)

    - maximum field current limitation with inverse time

    delay characteristic;

    - stator current limitation with inverse time delay

    characteristic for leading or lagging working of the

    machine;

    - limitation of the minimum and maximum generator

    voltage;

    REACTIVE POWER

    REGULATOR (kVAR) mode has

    the following control loops:

    - control for reactive power

    - maximum field current limitation with inverse time

    delay characteristic;

    - stator current limitation with inverse time delay

    characteristic for leading or lagging working of the

    machine;

    - limitation of the minimum and maximum generator

    voltage;

    CURRENT REGULATOR (FCR)

    mode mode has the following

    control loops:

    - control for field current

    - limitation of the regulator output

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    8/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    8

    Starting sequence in case of field

    flash

    After the generator reaches 90% of its rated speed the

    start command is followed by the following actions:

    - the field is supplied from an auxiliary powersupply until the generator voltage reaches over

    50% of the rated value then the excitation

    equipment is supplied from the excitationtransformer connected to generator terminals.

    Starting sequence of synchronous

    motors

    - Asynchronous mode start on a starting resistor with

    adjustable final level of sliding.

    Field discharging - During operational shut-down the field is discharged

    by inverter operation of the thyristor converter;

    - In case of excitation or machine fault, the synchronous

    machine will be de-energized using the field discharge

    circuit.Protections

    by bimetallic switch Field discharge breaker fault (field discharge resistor

    over-temperature)

    by PLC Generator over-voltage

    Excitation over-current

    Loss of field excitation current

    by Earth Fault Relay Generator field ground protection

    by Overcurrent Relays Transformer over-current

    Cooling Natural/ 2 fans for each rectifier.

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    9/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    9

    A. The Power circuit contains (depending of the synchronous machine type):

    1. Excitation transformerThe excitation transformer can be fed from the synchronous machine terminals or

    from another power supply. The excitation transformer equipment can be fitted with

    protection devices and/or switching devices.

    2. Full wave thyristor rectifier bridge (1 or more);The rectifier equipment includes the following:

    - Rectifier firing circuits;

    - High speed over-current fuses to protect the thyristors in the event of short-circuit;- Transient voltage surge protection on the rectifier (resistor-capacitance circuit);

    - Cooling equipment (if applicable);

    - Optional: disconnecting switches on the input and output of the rectifiers;

    3. Field discharge circuit.The field discharge circuit includes the following:- Static breaker for field discharging and crowbar for dc voltage surge protection;

    - Field discharge resistor connected across the field to de-energize the generator as

    fast as possible.

    - Optional: DC circuit breaker one-pole or two-poles with field discharge contact.

    4.

    Field flashing circuit.The field discharge circuit can be feed from the power plant battery or from an AC

    auxiliary power supply. The circuit consists in:

    - Transformer and rectifier (AC power supply type field flash circuit);

    - DC contactor;

    - Blocking diode;

    - Field flashing current limiting resistor;

    5. Synchronous motor starting circuit.- Starting resistor;

    - Short circuiting contactor for the starting resistor;- Synchronism sensing device;

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    10/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    10

    B. The Control circuits are divided in:- Internal power supply circuits

    - Regulating circuits (inside PLC): set points circuits; control loops and limitation

    circuits in AUTOMATIC mode: AVR/APFC/kVAR; control loop and limitation

    circuits in MANUAL mode- Measurement circuits

    - Thyristors firing pulses generation circuits

    - Protection circuits for the rectifier and control devices (by protection relays and

    PLC)

    - Internal power supplies circuitsThe supply of the PLC and the other control devices is made with the constant

    voltage: +24V.

    This voltage is obtained from 230VAC (auxiliary power supply) and from 110 (220)Vdc (battery supply), using switch mode power supplies. The switch mode power

    supplies output are connected in parallel separated through diodes (common

    cathode).

    - Regulating circuits (inside PLC)set points circuits

    Set point value in the AUTOMATIC or MANUAL mode is computed inside the

    PLC. Every regulator has a register in the PLC that represents the set point value.

    The range of the set point is between a minimum and a maximum value. Thesevalues can be set from the PLCs operating panel (HMI).

    The variation speed of the set point between minimum and maximum value, on the

    increase or decrease command, can be set from the PLCs operating panel (HMI).

    control loops and limiting functions in AUTOMATIC mode

    - control of the machine voltage regulator (AVR with load/ cross current correction

    of the voltage set point)- control of the machine reactive powerQ regulator

    - control of the machine power angle (factor)

    (cos ) regulator

    - time limitation of the maximum field current - field current limitation is activated

    when field current is higher than a threshold value (usually 1.15Iex rated) . PLC

    begins to compute the diagram (I2t) and when the time exceeds the calculated time,

    the regulator output is modified so that the field current will be lowered to the rated

    value. The threshold current value, the ceiling current definite time and the time

    break after a forcing can be set as parameters.

    - instantaneous limitation of the maximum field current (for synchronous

    generators) - field current limitation is activated when the generator is connected to

    the grid and the generator voltage in lower than the grid voltage in case of a near

    short-circuit (at generator terminals or generator transformer).

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    11/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    11

    - time limitation of the maximum stator current - stator current limitation is

    activated when the stator current is higher than a threshold value (between 0.8 ...

    1.5Is rated). PLC begins to compute the diagram (I2t) and when the time exceeds the

    calculated time, the regulator output is modified trying to lower down the stator

    current below the rated value. The threshold current value, the ceiling currentdefinite time and the time break after a forcing can be set as parameters.

    - limitation of the reactive power (only in AVR mode)- the reactive power value can

    be compute with the following formula:

    QM - Qm

    Q* = QM - P -------------- ,

    Pn

    Qm = the reactive power value at rated active

    power;QM - the reactive power value at active power= 0.

    These values can be set from HMI for both leading and lagging working.

    If the reactive power is higher (in lagging working) or lower (in leading working)

    than Q* value, the PLC modifies the regulator output, so that the reactive power tochange to the Q* value.

    - voltage matching (for synchronous generators) in order to start the

    synchronization and the paralleling process the excitation system can performed the

    voltage matching between the generator and line voltages.

    - V/HZ limiter (for synchronous generators) to cause the regulated voltage to

    decrease in proportion with the ferquency reduction, if frequency falls below a

    predetermined value.

    control loop and limiting in MANUAL mode

    - control of the field current - excitation current regulator

    tracking and switching between functioning (control) modes(AUTO-MANUAL)

    The tracking between the 2 control modes is made thus:

    - if the equipment functioning mode is MANUAL, in the AUTOmatic

    regulator (AVR, Q, cos ) set point register is written all time the feedback motor

    voltage value (Q or cos ). This value is the set point for the AUTOC regulator that

    is not in function. When the switching command is received from MANUAL to

    AUTO mode, it is done with a special care for the AUTO regulator output to be the

    same with MANUAL set point register.

    - if the equipment functioning mode is AUTO mode, in the MANUAL setpoint register is written all time the feedback field current. The switch to MANUAL

    mode can be done any time without any cautions.

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    12/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    12

    At switching command, the HMI displays the selected mode and enables or disablesthe corresponding control loops of the chosen mode.

    If the excitation equipment is ON, a fault in the feedbacks measurement circuit (U,

    Is or cos ) doesn't allow the equipment to function in the AUTOMATIC control

    mode. The control mode will be switched to MANUAL mode or the switch to

    AUTO mode will not be allowed

    - Measurement circuitsIn order to obtain the feed-back for UM, IM, Q, P, f, the equipment receives from the

    machine the following signals:

    -3x100 (110) Vac - UM (star or V connection diagram);-3x5(1) Aac - IM (star or V connection diagram);

    The excitation system has processor based devices that adjust and compute the

    electric feedback measures needed for the control loops of the AVR and FCR.

    - Thyristors firing pulses generation circuitsUsually the excitation equipment has 2 thyristor firing pulses generating devices.The equipment automatically switches on the channel 2 if channel 1 is in fault.

    The thyristors firing pulses are generated to be synchronous with the power supply

    voltage. The firing pulses are moving in accordance with the command voltage U .

    The thyristor firing pulse generating devices are equipped with a processor that

    supervises thyristors firing pulses (their presence), the synchronization voltages andthe presence of the power supply.

    - Protections circuitsThe PLC receives signals from different devices that supervise the high speed fuses,

    the fans, the rectifier and transformer temperature, the field discharging circuit and

    the field flashing circuit, etc.

    Machine protections

    a. Stator overvoltageb. Excitation overvoltage (59F)c. Excitation overcurrent (overexcitation 40)d. Loss of field excitation current (40)

    Synchronous motor protections

    e. Elapsing synchronism time (stall time)f. Asynchronous working protection (pull out)g. Restarting protectionh. AVR feedback measurement loss protection with switching on the MANUAL

    control mode (field current regulator)

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    13/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    13

    C. Sundries features- Local commands (increase, decrease, functioning modes selections, test

    functions) and Local signalizations are performed using a HMI key-pad or touch

    screen operating panel and/or push buttons and pilot lights.

    On the HMI there are also displayed the fault log, the parameters set, the electric

    measurements.

    HMI screens example

    - The discrete input and output signals for remote control are isolated by control

    relays.

    - On the Excitation System the following Internal Tests can be performed with

    equipment switched off.

    - Static Breaker Test (indicates if static breaker is healthy)

    - Rectifier Test (indicates weather the rectifier bridges and the thyristors firing pulse

    generation boards are healthy).

    - Communication facilities:Ports: RS232/ RS485, RJ45

    Communication protocols: ModbusRTU, Profibus, Ethernet TCP/IP, DF1.

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    14/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    14

    CONSTRUCTIVE DESCRIPTION

    The equipment is usually manufactured as a metal cabinet with front and back

    doors. The colour, dimmensions and protection degree are depending of the

    custommer requirements.

    OVERALL DIMENSIONS

    The overall dimensions depend on the rated field current of the synchronous

    machine and the requested custom design.

    For standard types, the dimensions (L x l x H) are:- for current up to 50Amps 800x800x(17002300)mm- for current over 50Amps with 100% redundancy in rectifying bridges

    2400x800x2100mm

    ENVIRONMENTAL CONDITIONS

    operating temperature range: -100C...+40

    0C

    storage temperature range: -250C...+55

    0C

    maximum relative humidity: 80% (at 300C)

    maximum altitude: 1000m above sea level (over 1000m, the current decreases

    by 0,5% at each extra 100m)

    PROTECTION DEGREE

    The protection degree is: IP20IP54

    ELECTRIC and ELECTRONIC DEVICES

    The control circuits are developed using the resources of the PLC's

    (Micrologix made by Allen Bradley or 313C made by Siemens)The thyristor bridge is designed and built at our company using Semikron

    thyristors.

    Inside the equipment it can be found several PCB's designed and planted at

    our plant facilities.

    Also it can be found electric devices as transducers, different protectionrelays, synchronization relay, relays, switch breakers, circuit breakers made by

    Phoenix Contact, Deif, ABB, Schneider Electrique, Aeton, Siemens, Microelettrica

    Scientifica, Bender, etc.

    The HMI can be a key-button or/and touchscreen type, a color, grayscale, or

    monochrome display, available in 315 in. size.

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    15/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    15

    QUALITY ASSURANCE

    Static excitation equipment operates in compliance with "SR EN ISO 9001:2001"

    quality management system, concerning the design, development, production,

    installation and servicing.

    The company is also certified for SR EN ISO 14001:2005 environmental

    management system and OHSAS 18001:2004 occupational health and safetymanagement system.

    SERVICE

    consulting for application definition;

    custom solution design;

    technical assistance at mounting and commissioning;

    service within and post guarantee;

    customer personnel training;

    OPTIONALS

    stand-by equipment, as presented in the functional description;

    firing circuit, as presented in the functional description;

    exciter transformer, powered from generator terminals;

    rotor earth fault relay;

    stand-by rectifying bridges;

    AC and DC disconnecting switches for each rectifying bridge (in additional

    cubicle);

    Current balancing coils for two rectifier bridges power circuit;

    Communication circuit optical fiber for SCADA compatibility.

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    16/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    16

    FUNCTIONAL CHARACTERISTICS OF THE EXCITATION SYSTEM - SRATN

    1. Resolution for measures acquisition 14bits2. Regulation accuracy

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    17/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SA

    17

    INTERNAL FAULT SIGNALS MESSAGES DISPLAYED ON THE HMI

    1. Power supply missing or synchronisation voltages missing2. Thyristors firing fault3. High speed fuse fault4. Static breaker fault or overtemperature on the field discharge resistor5. Thyristors over temperature6. Fans power supply fault7. Measuring circuit fault8. Auxiliary power supply missing9. Excitation transformer overcurrent10. Fault on the AUTOMATIC control channel and switch on

    the MANUAL control channel

    ELECTRIC MEASURES DISPLAYED

    1. Field current2. Field voltage3. Stator voltage4. Stator current5. Power factor6. Active power7. Reactive power

    MINIMUM DIGITAL INPUTS

    1. Main Circuit Breaker position2. START commandlocal or remote3. STOP commandlocal or remote4. EMERGENCY STOP command from machine protections5. INCREASE SETPOINTlocal or remote6. DECREASE SETPOINTlocal or remote

    SUPPLEMENTARY for SYNCHRONOUS GENERATOR

    7. GENERATOR SPEED >90%

    MINIMUM DIGITAL OUTPUTS

    1. EXCITATION ON2. EXCITATION OFF3. INTERNAL FAULT4. INTERNAL WARNING5. Limitation functions activated

    OPTIONAL for SYNCHRONOUS MOTOR

    MCB SWITCH ON command

    MCB SWITCH OFF command(MCBmotor circuit breaker)

  • 7/30/2019 Icpe Actel - Presentation of Sratn

    18/18

    STATIC EXCITATION EQUIPMENTSRATN ICPE-ACTEL SAREFERENCE LIST:

    Excitation equipments for synchronous generators - export

    Someshwara - India - 3 pcs. SRAT-N 13A/48V 2004

    Ranganatha - India3 pcs. SRAT-N 11A/23V 2005Ambuthirtha - India2 pcs. SRAT-N 17A/36V 2005

    Middle Kollab - India2 pcs. SRAT-N 862A/85V 2006

    Varahi - India2 pcs. SRAT-N 862A/85V 2007

    Gezende - Turkey - 1pc. SRAT-N 883A/110V 2008

    Somanamaradi - India - 1pc. SRAT-N 16.8A/39V 2008

    Kang Krachan - Thailand - 1pc. SRAT-N 1000A/ 186V 2009

    Tana Kenya2 pcs.2 pcs.

    SRAT-N 17A/31VSRAT-N 20A/40V

    2009

    Motz France2 pcs. SRAT-N 16A/30V 2010

    Nam La - Vietnam - 3 pcs. SRAT-N 15A/30V 2011

    Om Power - India - 2 pcs. SRAT-N 15A/30V 2011

    Song Giang - Vietnam - 2 pcs. SRAT-N 871A/93V 2011