ICEC25 July 7~11, 2014, Enschede, Netherlands Design of ... · 4. Flow distribution results lower...

1
Design of ITER thermal shield cooling network considering flow distribution and thermal load Kwanwoo Nam 1 , Youn-Kyu Kim 2 , Wooho Chung 1 , Craig Hamlyn-Harris 3 , Namil Her 3 1. ITER Korea, National Fusion Research Institute, Daejeon 305-333, Republic of Korea 2. Mecha T&S, Jinju 660-808, Republic of Korea 3. ITER Organization, Route de Vinon sur Verdon, 13115 Saint Paul Lez Durance, France ICEC25 July 7~11, 2014, Enschede, Netherlands Abstract Thermal Shield (TS) in the ITER tokamak cuts off the radiation heat load from the vacuum vessel/cryostat transferring to the magnets operating at 4.5 K. The TS will be cooled down by 80 K helium gas supplied from cryoplant. The helium goes through the cooling tubes attached on the TS. The TS consists of a lot of panels, which are to be connected by bolted joints. The panels have their own cooling tube routings and they are connected to the end of cryo-distribution lines by manifold piping. As the composed piping for the TS cooling is complex, the flow distribution is one of the major concerns for the design of TS cooling network. This paper describes the design of TS cooling tube and manifold, taking the flow distribution and the thermal load into account. The TS hydraulic network was modeled in details by a dedicated program. Frictional pressure drop in the pipes and local losses at all piping components in the TS were considered in the model. It was found that coolant flow rates in some panels were insufficient compared with its design values. Orifice installation was proposed in order to improve the flow distribution in the cooling tubes. Thermal analysis was also performed for the manifold feeder and ring, the surfaces of which are exposed to the warm surface. The helium temperature rise through the manifold feeder and ring due to incident radiation was obtained and its effect on the radiation shielding performance of the TS was evaluated. 1. Introduction Acknowledgement: This work is supported by Ministry of Science, ICT and Future Planning of Republic of Korea under an ITER Project Contract. The TS specifications Main material : SS304LN Panel thickness : 10 mm, 20 mm Emissivity : < 0.05 (silver coated) Helium coolant : 80 ~ 100 K, 1.8 MPa Cooling tube: 13.72 OD, 2.24t, welded on the panel The ITER Thermal Shield (TS) is to be located between the vacuum vessel/the cryostat and the magnet for minimizing radiation heat load for the successful operation of the magnet. Cooling network The TS manifolds (TSM) connect all the cooling tubes in the TS panels to the cold valve box (CVB). The TSM consists of rings (circular pipe adjacent to the CTS body) and feeders (straight pipe which connects the ring to the CVB). The ring and the feeder are attached on the CTS and the cryostat by supports. The sizes of the ring and the feeder: DN65, DN50 3. Flow Analysis Method The cooling network consists of 8 sub-circuits; each sub-circuit has cooling tubes in parallel connection. The TS cooling tube network has 100% redundancy; all the active (operating) cooling tube has identical one for redundant purpose in the case of accident in the operating tubes. Each sub-circuit has its control valve; the flow rate in each circuit can be regulated by the control valve. Introduction The flow analysis for the TS cooling network was performed using AFT Fathom TM . Fathom is a graphical platform for modeling incompressible flow in pipe networks. Temperature of helium is assumed as constant in the cooling network. The sub-circuits are independent each other, hence analyzed separately. The control valve in the CVB is not included in the model. Total flow rate is assigned to the sub-circuit as a input. TSM #1 Bernoulli equation neglecting potential energy Theory Energy conservation in piping Pressure drops - Pipe - Elbow and tee branch: data from Crane (1988)*, Idelchik (1994)* - Orifice l P gh v P gh v P 2 2 2 2 1 2 1 1 2 1 2 1 2 2 1 v D L f P l 2 2 1 v K P l * Ref: AFT Fathom 7.0 Users Guide vD Re Modeling in Fathom Properties Helium density: 9.3574 kg/m 3 , viscosity: 9.3789 μPa-s (@ 1.8 MPa, 90 K) Pipe roughness (ε) = 1.54 μm 4. Flow distribution results lower VVTS (TSM #6) Lower VVTS manifold (TSM #6) and lower ECTS manifold (TSM #5) are presented as typical cases. Orifices are installed at the tube routing where the flow rate is larger than the design value. VVTS cooling tube CTS cooling tube ITER thermal shield TS manifolds TS flow diagram Simplification of bend modeling Many bends in the real tube routing The tube routing is simplified as the tube with single equivalent bend. K of the single bend is calculated by the summation of those of all bends. Design flow rate for the TS panel = Incident radiation divided by helium enthalpy change between inlet and outlet Analyzed flow rate through the TS panel should be as close to its design flow rate as possible. Pressure drop shall be lower than 100 kPa. Maximum temperature of TS panel should be lower than 140 K (equivalent to ~ 1 W/m 2 heat load to magnet). Design criteria T C Q m p rad To improve the design of TS manifold by avoiding flow mal-distribution To check the effect of flow distribution on the TS thermal characteristics 2. Objectives Data from Idelchik (1994)* Sharp-edged orifice 2 375 . 0 2 1 1 707 . 0 p orifice p orifice orifice p orifice 5. Thermal effects 6. Conclusion Effect of flow distribution on VVTS panel temperature Design flow rate - Outboard upper: 4.69 g/s - Outboard lower: 6.54 g/s - Upper port: 5.79 g/s - EQ port: 4.64 g/s - Lower port: 5.09 g/s - He temp: inlet = 80 K, outlet = 100 K Calculated flow rate (orifice installed) - Outboard upper: 4.69 g/s (not consider excessive flow) - Outboard lower: 5.6 g/s, He outlet temp = 103.4 K - Upper port: 5.0 g/s, He outlet temp = 103.2 K - EQ port: 4.64 g/s (not consider excessive flow) - Lower port: 5.09 g/s (not consider excessive flow) T max = 115.1 K Hot spot temperature is still below 140 K (design recommendation) in spite of local small flow. T max = 116.7 K Flow analysis model CATIA model A1 B C D E A2 - A1: lower ECTS ring + lower ECTS cylinder + side STS ring, A2: lower ECTS ring + lower ECTS cylinder - B,D: Irr. lower ECTS ring + lower ECTS cylinder, C,E: Irr. lower ECTS ring + lower ECTS cylinder + side STS ring - ST: VVTS EQ regular port Branch line 0 1 2 3 4 5 6 7 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 E D C B A1 Calculated flow rate (g/s) Design flow rate (g/s) 0 1 2 3 4 5 ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST Calculated flow rate (g/s) Design flow rate (g/s) 0 1 2 3 4 5 ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST Calculated flow rate (g/s) Design flow rate (g/s) 0 1 2 3 4 5 6 7 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 E D C B A1 Calculated flow rate (g/s) Design flow rate (g/s) Reference Orifice* Reference Orifice* P = 24 kPa P = 21 kPa Lower ECTS ring + cyl + side STS VVTS EQ port *Location: A2 (9 ea), size: 3.2 mm Branch line Coolant temperature rise in the feeder and the ring - Feeder/ring outside the CTS are exposed to radiation from cryostat. - Maximum length of ring: ~ 80 m (for the ECTS) - Maximum length of feeder: ~ 36 m (for the lower CTS) - Flow distribution result from the flow analysis was used for the temperature calculation. - Local heat load increase is acceptable because total heat load to magnet has about 20% margin*. Ring pipe outside CTS ECTS manifold ring 80.3 K, End of feeder 80.0 K End of ring, 82.3 K Connected to the end of ring Inlet/outlet temperature Heat load (W) Heat load increase (%) Max. temp. ECTS 20 O sector 80 K – 100 K (reference) 24.08 - 127.4 K 82 K – 102 K 25.56 6.2 128.9 K 1 1 1 1 c m e e e F where ) ( ) ( 4 4 300 i e i o P T A F T T C m , A = πDL/2 e m = 0.15 (manifold emissivity) e c = 0.5 (cryostat emissivity) Heat load to feeder/ring CATIA model sector-3 TYPE-A TYPE-B sector-2 sector-1 sector-4 sector-5 sector-6 sector-7 Feeder Collector Feeder ring TYPE-A TYPE-B sector-3 sector-2 sector-1 sector-4 sector-5 sector-6 sector-7 Branch line Flow analysis model Result lower ECTS (TSM #5) 2 6 5 8 4 1 3 9 7 10 11 0 1 2 3 4 5 6 7 8 Calculated flow rate (g/s) Design flow rate (g/s) 0 1 2 3 4 5 6 7 8 Calculated flow rate (g/s) Design flow rate (g/s) Reference Orifice* P = 86 kPa P = 78 kPa *Location: S1, S7 (18 ea), size: 3.0 mm Flow distribution along 360 degree sector Variation: ~ 3.94% Branch line A B S-3 S-2 S-1 S-4 S-5 S-6 S-7 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 Result Effect of coolant temperature rise on the local heat load to magnet Flow distribution in the ITER TS cooling network is simulated and its thermal effect is investigated. Orifice installation is proposed to improve the flow distribution. The flow balancing design by the orifice is satisfactory from the view point of the ITER TS thermal performance. The selected emissivity of manifold feeder and ring is acceptable due to moderate coolant temperature rise. *K. Nam et al, Thermal analysis on detailed 3D models of ITER thermal shield, Fusion Eng Design, 2014, in press.

Transcript of ICEC25 July 7~11, 2014, Enschede, Netherlands Design of ... · 4. Flow distribution results lower...

  • Design of ITER thermal shield cooling network considering flow distribution and thermal load Kwanwoo Nam1 , Youn-Kyu Kim2, Wooho Chung1, Craig Hamlyn-Harris3, Namil Her3

    1. ITER Korea, National Fusion Research Institute, Daejeon 305-333, Republic of Korea 2. Mecha T&S, Jinju 660-808, Republic of Korea 3. ITER Organization, Route de Vinon sur Verdon, 13115 Saint Paul Lez Durance, France

    ICEC25 July 7~11, 2014, Enschede, Netherlands

    Abstract Thermal Shield (TS) in the ITER tokamak cuts off the radiation heat load from the vacuum vessel/cryostat transferring to the magnets operating at 4.5 K. The TS will be cooled down by 80 K helium gas supplied from cryoplant. The helium goes through the cooling tubes attached on the TS. The TS consists of a lot of panels, which are to be connected by bolted joints. The panels have their own cooling tube routings and they are connected to the end of cryo-distribution lines by manifold piping. As the composed piping for the TS cooling is complex, the flow distribution is one of the major concerns for the design of TS cooling network. This paper describes the design of TS cooling tube and manifold, taking the flow distribution and the thermal load into account. The TS hydraulic network was modeled in details by a dedicated program. Frictional pressure drop in the pipes and local losses at all piping components in the TS were considered in the model. It was found that coolant flow rates in some panels were insufficient compared with its design values. Orifice installation was proposed in order to improve the flow distribution in the cooling tubes. Thermal analysis was also performed for the manifold feeder and ring, the surfaces of which are exposed to the warm surface. The helium temperature rise through the manifold feeder and ring due to incident radiation was obtained and its effect on the radiation shielding performance of the TS was evaluated.

    1. Introduction

    Acknowledgement: This work is supported by Ministry of Science, ICT and Future Planning of Republic of Korea under an ITER Project Contract.

    The TS specifications

    Main material : SS304LN

    Panel thickness : 10 mm, 20 mm

    Emissivity : < 0.05 (silver coated)

    Helium coolant : 80 ~ 100 K, 1.8 MPa

    Cooling tube: 13.72 OD, 2.24t, welded on the panel

    The ITER Thermal Shield (TS) is to be located between the vacuum vessel/the cryostat and the magnet for minimizing radiation heat load for the successful operation of the magnet.

    Cooling network

    The TS manifolds (TSM) connect all the cooling tubes in the TS panels to the cold valve box (CVB).

    The TSM consists of rings (circular pipe adjacent to the CTS body) and feeders (straight pipe which connects the ring to the CVB).

    The ring and the feeder are attached on the CTS and the cryostat by supports.

    The sizes of the ring and the feeder: DN65, DN50

    3. Flow Analysis Method

    The cooling network consists of 8 sub-circuits; each sub-circuit has cooling tubes in parallel connection.

    The TS cooling tube network has 100% redundancy; all the active (operating) cooling tube has identical one for redundant purpose in the case of accident in the operating tubes.

    Each sub-circuit has its control valve; the flow rate in each circuit can be regulated by the control valve.

    Introduction

    The flow analysis for the TS cooling network was performed using AFT FathomTM.

    Fathom is a graphical platform for modeling incompressible flow in pipe networks.

    Temperature of helium is assumed as constant in the cooling network.

    The sub-circuits are independent each other, hence analyzed separately. The control valve in the CVB is not included in the model. Total flow rate is assigned to the sub-circuit as a input.

    TSM #1

    Bernoulli equation neglecting potential energy

    Theory

    Energy conservation in piping

    Pressure drops

    - Pipe

    - Elbow and tee branch: data from Crane (1988)*, Idelchik (1994)*

    - Orifice

    lPghvPghvP 22221

    211

    2

    1

    2

    1

    2

    2

    1v

    D

    LfPl

    2

    2

    1vKPl

    * Ref: AFT Fathom 7.0 Users Guide

    vDRe

    Modeling in Fathom

    Properties

    Helium density: 9.3574 kg/m3, viscosity: 9.3789 μPa-s (@ 1.8 MPa, 90 K)

    Pipe roughness (ε) = 1.54 µm

    4. Flow distribution results

    lower VVTS (TSM #6)

    Lower VVTS manifold (TSM #6) and lower ECTS manifold (TSM #5) are presented as typical cases. Orifices are installed at the tube routing where the flow rate is larger than the design value.

    VVTS cooling tube CTS cooling tube

    ITER thermal shield

    TS manifolds

    TS flow diagram

    Simplification of bend modeling

    Many bends in the real tube routing

    The tube routing is simplified as the tube with single equivalent bend.

    K of the single bend is calculated by the summation of those of all bends.

    Design flow rate for the TS panel = Incident radiation divided by helium enthalpy change between inlet and outlet

    Analyzed flow rate through the TS panel should be as close to its design flow rate as possible. Pressure drop shall be lower than 100 kPa. Maximum temperature of TS panel should be lower than 140 K (equivalent to ~ 1 W/m2 heat

    load to magnet).

    Design criteria

    TC

    Qm

    p

    rad

    To improve the design of TS manifold by avoiding flow mal-distribution

    To check the effect of flow distribution on the TS thermal characteristics

    2. Objectives

    Data from Idelchik (1994)* Sharp-edged orifice

    2375.02

    11707.0

    p

    orifice

    p

    orifice

    orifice

    p

    orifice

    5. Thermal effects

    6. Conclusion

    Effect of flow distribution on VVTS panel temperature

    Design flow rate - Outboard upper: 4.69 g/s - Outboard lower: 6.54 g/s - Upper port: 5.79 g/s - EQ port: 4.64 g/s - Lower port: 5.09 g/s - He temp: inlet = 80 K, outlet = 100 K

    Calculated flow rate (orifice installed) - Outboard upper: 4.69 g/s (not consider excessive flow) - Outboard lower: 5.6 g/s, He outlet temp = 103.4 K - Upper port: 5.0 g/s, He outlet temp = 103.2 K - EQ port: 4.64 g/s (not consider excessive flow) - Lower port: 5.09 g/s (not consider excessive flow)

    Tmax= 115.1 K

    Hot spot temperature is still below 140 K (design recommendation) in spite of local small flow.

    Tmax= 116.7 K

    Flow analysis model

    CATIA model

    A1

    B C D

    E

    A2

    - A1: lower ECTS ring + lower ECTS cylinder + side STS ring, A2: lower ECTS ring + lower ECTS cylinder

    - B,D: Irr. lower ECTS ring + lower ECTS cylinder, C,E: Irr. lower ECTS ring + lower ECTS cylinder + side STS ring

    - ST: VVTS EQ regular port

    Branch line

    0

    1

    2

    3

    4

    5

    6

    7

    A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 E D C B A1

    Calculatedflow rate(g/s)

    Designflow rate(g/s)

    0

    1

    2

    3

    4

    5

    ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST

    Calculatedflow rate(g/s)

    Designflow rate(g/s)

    0

    1

    2

    3

    4

    5

    ST ST ST ST ST ST ST ST ST ST ST ST ST ST ST

    Calculatedflow rate(g/s)

    Design flowrate (g/s)

    0

    1

    2

    3

    4

    5

    6

    7

    A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 A1 A2 E D C B A1

    Calculatedflow rate(g/s)

    Design flowrate (g/s)

    Reference Orifice*

    Reference Orifice* △P = 24 kPa △P = 21 kPa

    Lower ECTS ring + cyl + side STS

    VVTS EQ port

    *Location: A2 (9 ea), size: 3.2 mm

    Branch line

    Coolant temperature rise in the feeder and the ring - Feeder/ring outside the CTS are exposed to radiation from cryostat.

    - Maximum length of ring: ~ 80 m (for the ECTS)

    - Maximum length of feeder: ~ 36 m (for the lower CTS)

    - Flow distribution result from the flow analysis was used for the

    temperature calculation.

    - Local heat load increase is acceptable because total heat load to

    magnet has about 20% margin*.

    Ring pipe outside CTS

    ECTS manifold ring

    80.3 K, End of feeder

    80.0 K

    End of ring, 82.3 K

    Connected to the end of ring

    Inlet/outlet temperature

    Heat load (W)

    Heat load increase (%) Max. temp.

    ECTS 20O sector 80 K – 100 K (reference) 24.08 - 127.4 K 82 K – 102 K 25.56 6.2 128.9 K

    1

    111

    cm

    e

    eeFwhere

    )()( 44300ieioP

    TAFTTCm

    , A = πDL/2

    em = 0.15 (manifold emissivity)

    ec = 0.5 (cryostat emissivity)

    Heat load to feeder/ring

    CATIA model

    sector-3

    TYPE-A

    TYPE-B

    sector-2

    sector-1

    sector-4 sector-5

    sector-6

    sector-7

    Feeder Collector

    Feeder

    ring

    TYPE-A TYPE-B sector-3 sector-2 sector-1 sector-4 sector-5 sector-6 sector-7

    Branch line

    Flow analysis model

    Result

    lower ECTS (TSM #5)

    2 6

    5

    8 4

    1

    3 9

    7

    10 11

    0

    1

    2

    3

    4

    5

    6

    7

    8

    Calculatedflow rate (g/s)

    Design flowrate (g/s)

    0

    1

    2

    3

    4

    5

    6

    7

    8

    Calculatedflow rate(g/s)

    Design flowrate (g/s)

    Reference Orifice*

    △P = 86 kPa △P = 78 kPa

    *Location: S1, S7 (18 ea), size: 3.0 mm Flow distribution along 360 degree sector

    Variation: ~ 3.94%

    Branch line

    A B S-3 S-2 S-1 S-4 S-5 S-6 S-7

    1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11

    Result

    Effect of coolant temperature rise on the local heat load to magnet

    Flow distribution in the ITER TS cooling network is simulated and its thermal effect is investigated. Orifice installation is proposed to improve the flow distribution. The flow balancing design by the orifice is satisfactory from the view point of the ITER TS thermal performance. The selected emissivity of manifold feeder and ring is acceptable due to moderate coolant temperature rise.

    *K. Nam et al, Thermal analysis on detailed 3D models of ITER thermal shield, Fusion Eng Design, 2014, in press.