IBX+ TECHNICAL SPECIFICATIONS SH5 SHANGHAI IBX+ …disaster recovery center in Shanghai. Equinix...
Transcript of IBX+ TECHNICAL SPECIFICATIONS SH5 SHANGHAI IBX+ …disaster recovery center in Shanghai. Equinix...
ABOUT
Equinix, Inc. (Nasdaq: EQIX), connects more than 4,750 companies directly to their customers and partners inside the world’s most networked data centers. Today, enterprise, cloud, networking, digital media and financial services companies leverage the Equinix interconnection platform in 33 strategic markets across the Americas, EMEA and Asia-Pacific. By connecting directly to their strategic partners and end users, customers are forming dynamic ecosystems inside Equinix. These interconnected ecosystems enable companies to optimize the performance of their content and applications and protect their vital digital assets.
Equinix operates four International Business ExchangeTM (IBX®) data centers and one disaster recovery center in Shanghai. Equinix Shanghai SH5 IBX+ data center occupies a 4-story dedicated building located in the Yangpu district, just north of the Lujiazui Finance and Trade Zone and the Bund. This is one of many state of the art IBX centers in key metropolitan areas throughout Asia-Pacific that offers premium colocation and Smart Hands™ services.
LOCATION
Building No. 9 No. 619 Longchang Road Yangpu District Shanghai 200090 PRC
From Airports – 14.8 miles (23.9 km) from Shanghai Hongqiao International Airport (SHA); 23.4 miles (37.7 km) from Shanghai Pudong International Airport (PVG) Location Orientation – 5.5 miles (8.9 km) from Lujiazui Financial District Parking – Paid parking available on campus
PROFILE
Phone – +86 21 5156 7242Email – [email protected]
GLOBAL SLA
� 99.999+% Power availability � 99.99+% Temperature and
Humidity availability � 99.99+% Cross Connect availability
POWER
Electrical Capacity (Critical Customer Load) – 3 kVA per cabinetElectrical Capacity (Uninterruptible Power System) –2 x (2 x 400) kVA + 2 x (3 x 400) kVA + 2 x (3 x 400) kVA (N+N)Utility Feeders – 2 x 6.6 kVPower Transformers – 6 x 2 MVA (6.6 kV / 400 V)Standby Power – Diesel Generators 4 x 1,000 kVA + 2 x 2,000 kVA + 2 x 2,250 kVA ATS (Automatic Transfer Switch) – For CRAC cooling system
COOLING
Cooling Capacity – 3 kVA per cabinetCooling Plant – Computer Room Air Conditioners 29 x 100 kW (N+1, DX Units) + 18 x 77 kW (N+2, DX Units with ESM)
SECURITY
Physical – Dedicated data center building within secured campus; physical access control lists manage ingress and egress; multi-layered defenseHuman – 24x7x365 security officersElectronic – 24x7x365 CCTV recordings (90 days of video recording), proximity card access control and two factors authentication for private suite/cage (optional)
Equinix.cn
SH5 SHANGHAI IBX+ DATA CENTER IBX+ TECHNICAL SPECIFICATIONS
Square Footage BreakdownLeased Area 57,344 ft2 (5,327 m2)Colocation Area 25,327 ft2 (2,353 m2)IBXflex Space Custom Request
© 2015 Equinix, Inc.
BUILDING
Construction Type – Reinforced concreteindustrial structure Building Type – 4-story leased building withraised floorsFloor Load – 10 kN/m²Slab-to-ceiling Height – 4.5 m
FIRE PROTECTION
Fire Detection – Smoke detectors & Very Early Smoke Detection Apparatus (VESDA)Fire Suppression – FM200 gas suppression (Phase 1 & 2) and Inergen (Phase 3)Fire Rating – Minimum 2 hours rating
CERTIFICATIONS
� ISO/IEC 27001: 2013 � SSAE16 SOC-1 Type II
CABLING AVAILABLE
System – Multi-layer fiber runner & copper cable ladder Cross Connects – Cat5e/6, COAX and Fiber
IBX+ TECHNICAL SPECIFICATIONS
SH5 SHANGHAI IBX+ DATA CENTER
SEATTLE
DENVER
ATLANTA
BOSTON
PHILADELPHIA
MIAMI
TORONTO
DUSSELDORF
MUNICH
ZURICH MILAN
GENEVA
DUBAI
PARIS
LONDON
RIO DE JANEIRO
SÃO PAULO
AMSTERDAM
FRANKFURTSILICONVALLEY
LOS ANGELES
CHICAGO
NEW YORK
DALLASWASHINGTON, DC
SINGAPORE
HONG KONG
SHANGHAI
TOKYOOSAKA
JAKARTA
SYDNEY
Equinix locations
Partner Data Center
AMERICAS EMEA ASIA-PACIFIC
MELBOURNE
EQUINIX IBX DATA CENTER LOCATIONS
Located in 33 strategic markets across the Americas, EMEA, and Asia-Pacific.
SH5 IBX Site Spec (A4) v0315 DS-EN PT-BL Q414