    New features of IA-NT sw V2.0 Page 1 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    1. Available firmware, archives and documentation

    Firmware

    Mhx file

    IA-NT-STD-2.0.mhxIA-NT-PWR-2.0.mhx

    Archives

    Archives

    IA-NT-STD-2.0.ail

    IA-NT-PWR-2.0.ail

    IA-NT-PWR-StarterKit-2.0.ail

    Documentation

    PDF files Description

    IA-NT-STD-2.0-Reference Guide.pdf Manual for InteliATSNT

    STD controller

    IA-NT-PWR-2.0-Reference Guide.pdf Manual for InteliATSNTPWR controller

    IA-NT-2.0 New features.pdf List of new features for software update version 2.0

    2. Main changes in IA-NT 2.0

    New features

    Two equivalent power sources (STD & PWR)ATS controller can be now used also for MAINS-MAINSapplications and not only for MAINS-GEN applications. The system recognizes application type according to Gen Start/Stop andGen ReadyToLoad logicalbinary output and input configuration. If both configured/used(default setting) it tells controller that MAINS-GEN application type is to be used. If not

    configured, MAINS-MAINSapplication type takes place. In this case stop-fail protection andgenerator current protection are not evaluated.

    Passive synchronization (PWR)Controller has been enhanced by feature called passive synchronization. Passive sync (synccheck) offers possibility to synchronize mains and gen-set without need to use speedregulation or - better to say - it offers possibility to wait for both sources to get in phase.System is evaluated as to be in sync according to predefined parameters voltage andfrequency difference if both sources will get in-phase before synchronization timeout expires.Parameters defining breaker delay are taken into account when system computes/predicts exactmoment when both sources are in phase.

    Above mentioned parameters can be set via following new setpoints:

    Sync Ctrl: Voltage Window [%]This setpoint adjusts maximum allowed difference between generator and mains/bus voltage inrespective phases for passive synchronizing:Step: 1 %Range: 0 30 %Default: 10 %

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    2/23

    New features of IA-NT sw V2.0 Page 2 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    Sync Ctrl: Freq Window [Hz]This setpoint adjusts maximum allowed difference between generator and mains/bus frequencyin respective phases for passive synchronizing:Step: 0.1 HzRange: 0.0 2.0 Hz (0.0 0.2 Hz for CLOSED transition)

    Default: 0.2 Hz

    HINT:This setpoint depends on transition type selected (setpoint Transit ion). If Closed transitiontakes place Frequency Windowsetpoint values above 0.3 Hz are internally limited to value of0.3 Hz.

    Sync Ctrl: Sync Timeout [min]This setpoint adjusts maximum time interval when system waits for both sources to getsynchronized. After that time synchronization timeout alarm is activated and either changeoveris interrupted or continues as open delayed transition. See Transitionsetpoint description formore details, please.Step: 1 minRange: 1 60 min

    Default: 1 min

    Basic Settings: GCB Delay [s]By means of this setpoint system gets information about breaker/contactor switching time. Thisvalue is needed for exact sync moment/ time prediction.Step: 0.01 sRange: 0.01 60.00 sDefault: 0.05 s

    Basic Settings: MCB Delay [s]By means of this setpoint system gets information about breaker/contactor switching time. Thisvalue is needed for exact sync moment/ time prediction.Step: 0.01 sRange: 0.01 60.00 sDefault: 0.05 s

    HINT:Value of breaker switching time MUSTcontain all the parts of breaker delay (i.e. breakerswitching time plus switching time of relay used for breaker control).The more exact value is given, the more exact is the sync result.

    HINT:Setpoints AMF Settings:MCBFeedbackDel& MCBFeedbackDelwere removed from system

    Open Delayed, Open In-phase and Closed Transition support

    Ability to perform passive synchronization dramatically enhances controller function and bringspossibility to provide Open In-phase Transition and Closed Transition (short time parallel).

    Controller provides below described types of changeover between Mains and Gen-set powersources depending on following setpoint value:

    Basic Settings: Transition [OPEN/INPHASE/CLOSED/INPH-OPEN/CLOS-OPEN]

    1. Open Delayed Transition (PWR & STD)

    If setpointTransitionis set to [OPEN] thenOpen Delayed Transition takes place.

    Open Delayed Transition is standard type of changeover provided by most common AMF orATS controllers supplied by other vendors. Controllers perform load transfer between bothpower sources with break (blackout). Delayed Transition means there is delay between sourcebreaker opening and target breaker closing.

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    3/23

    New features of IA-NT sw V2.0 Page 3 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    Two or three position ATS switch or two independent breakers/contactors can be used asswitching mechanism.

    Bellow you can see how is Open Delay Transition implemented by IA-NT controllers (PWR &STD model). Our controllers offer possibility to setup load transfer delay via Transfer Delsetpoint.

    HINT:

    This transition can perform fastest possible changeover if Transfer Delis set to zero value.Overall blackout time then equals to 20 ms + breaker reaction time.

    HINT:Use longer delay time to avoid problems with motor starters. (Motor starts prefer to see break ofa few seconds so they can initialize properly).

    HINT:To avoid issues with contactor mechanical interlocks use delay 0.75s or longer (mech. interlockon contactors takes some time to clear). If you try to close one contactor before interlock hascleared it can jam and you end up with out supply to load).

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    4/23

    New features of IA-NT sw V2.0 Page 4 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    2. Open In-phase Transition (PWR)

    SetpointTransitionset to [IN-PHASE] bringsOpen In-phase Transition.

    Open In-phase Transition represents special kind of Open Delayed Transition where delayduring changeover is reduced to minimal possible value and transition initiates only when both

    power sources are in sync. Transfer Delsetpoint value is ignored (equals to zero). Seedescription of passive synchronization for more info.

    This kind of transition is suitable for such systems where fast changeover (very short blackout) isrequired, huge inductive load (e.g. large electric motor) is involved and it is not possible to useClosed Transition due to some reason.

    Two or three position ATS switch or two independent breakers/contactors can be used asswitching element. Reaction time of whole switching mechanism (including control relays)affects overall changeover time and in-phase transfer accuracy.

    It is recommended to use as fast switches as possible (overall switching time once sync moment is calculated andsource is disconnected from load, electrical parameters of load are changing dynamically and

    could fall out of sync rapidly. Real phase difference depends on that switching time.

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    5/23

    New features of IA-NT sw V2.0 Page 5 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    Picture above shows how is Open In-phase Transition implemented by IA-NT controllers (PWRmodel).

    In case of system using two separate breakers/contactors controller ensures no overlapbetween both switches during changeover however mechanical interlock can still be useful.Two or three position ATS switches ensure this by its nature.

    HINT:It is necessary to use fast breakers with known closing/opening time when Open In-phaseTransition takes place. Breaker switching time is used as parameter (MCB Delay, GCB Delay)for calculation/prediction of exact in-sync moment.Overall blackout time equals to 100 ms + one breaker reaction time (incl. control relay delay).

    HINT:In case of source (e.g. mains) failure changeover from source is always performed as opendelayed, not as in-phase.

    HINT:

    During system tests two separate breakers/contactors with switching time below 50ms wereused along with fast ATS switches (e.g. SOCOMEC ATyS M 3s, switching time 180 ms). We do not recommend usage of switching elements their reaction time exceeds these values!

    HINT:Breaker delay default value for both breakers (MCB Delay, GCB Delay) is set to 50ms. ATSswitch delay consists of both delays.

    3. Closed Transition (PWR)

    If SetpointTransitionequals to [CLOSED],Closed Transition is used.

    Closed Transition presents transition type where both breakers/contactors overlap for 100 msand transition initiates only when both power sources are in sync. This kind of transition issuitable for such systems where no break (no blackout) changeover is required. Transfer Delsetpoint value is ignored (equals to zero).

    See description of passive synchronization for more info.

    Two independent breakers/contactors are required as switching elements. Reaction time ofwhole switching mechanism (including control relays) affects overall changeover time.

    It is required to use as fast switches as possible (breaker opening time < 100 ms includingcontrol relay). If parallel run exceeds 200 ms both breakers are opened and alarm is activated. Ifparallel run still continues (breakers are closed for at least 100 additional milliseconds), binaryoutput Shunt Trip is activated (if configured).

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    6/23

    New features of IA-NT sw V2.0 Page 6 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    HINT:

    It is necessary to use fast breakers with known closing/opening time when Closed Transitiontakes place. Breaker switching time is used as parameter (MCB Delay / GCB Delay) forcalculation/prediction of exact in-sync moment.

    HINT:In case of source (e.g. mains) failure changeover from source is always performed as opendelayed, not as closed.

    HINT:During system tests two separate breakers/contactors with switching time below 50ms wereused. We do not recommend usage of switching elements their reaction time exceeds thesevalues.

    HINT:Breaker delay default value for both breakers (MCB Delay, GCB Delay) is set to 50ms.

    4. Closed + Open Delayed Transition, Closed + Open Delayed Transition, (PWR)

    If SetpointTransitionequals to [INPH-OPEN] or[CLOS-OPEN], system continues with Open

    Delayed Transition after requested synchronized transition failed (sync timeout expired soonerthan both sources reached synchronized state)

    Controllers cascading (STD & PWR)Controllers are suitable for Cascading ATS applications allowing load to be split into moresections.

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    7/23

    New features of IA-NT sw V2.0 Page 7 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    Specification

    Automatic remote gen-set start when the mains fails (AUT mode)

    Cascade controlled by Master

    Consequent changeover on slave controllers

    Simple wiring

    Hardware requirements1 x IA-NT PWR (STD), (1 to n) x IA-NT PWR (STD)

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    8/23

    New features of IA-NT sw V2.0 Page 8 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    Cascade1, wiring A, Mains Fail

    Cascade1, wiring A, Mains Return

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    9/23

    New features of IA-NT sw V2.0 Page 9 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    Cascade1, wiring B, Mains Fail

    Cascade1, wiring B, Mains Return

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    10/23

    New features of IA-NT sw V2.0 Page 10 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    Current measurement (PWR)It is possible to set the location of CT s.

    There are two options of CT location.a) Loadb) Gen-Set

    According to the connection you use you should set either CT location: Load or CT location:Gen-Set.

    New setpoint:

    CT Location [Load / GenSet]

    Load: CT (current measurement) is located next to the load.GenSet: CT (current measurement) is located next to the gen-set.

    For more details about current measurement location see Current measurement: CT location.

    Voltage measurement and generator connection types (STD & PWR)There are 4 voltage measurement Connect ionType (setpoint ConnectionTyp e [3Ph4Wire /3Ph3Wire / Split Ph / Mono Ph])options. Every type matches to corresponding generatorconnection type:

    1. Connect ionType: 3 Phase 4 Wires

    Three phase wye measurement 3PY

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    11/23

    New features of IA-NT sw V2.0 Page 11 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    3 Phase 4 Wires - STAR Connection

    2. Connect ionType: 3 Phase 3 Wires

    Three phase delta measurement 3PD

    3 Phase 3 Wires DELTA Connection HI-LEG (wild-leg, red-leg) DELTA Connection

    Hint:Only L1, L2 and L3 wires should be connected. In case of HI-LEG DELTA connection the N(neutral) wire (in the diagram connected between T6 and T9) has to be disconnected.No separation transformers for three wires voltage connection (without N) are needed.

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    12/23

    New features of IA-NT sw V2.0 Page 12 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    3. Connect ionType: Split Phase

    Single-phase measurement 1PH

    Split Phase DOUBLE DELTA Connection ZIG ZAG (DOG LEG) Connection

    4. Connect ionType: Mono Phase

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    13/23

    New features of IA-NT sw V2.0 Page 13 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    Single-phase measurement 1PH

    Mono Phase MONOPHASE Connection

    Hint:Switchboard lighting strike protection according standard regulation is expected for all 4connectiontypes!!!

    Hint:

    Phase sequence check is not possible to evaluate under voltage 50V what causes that ifmeasured voltage 50V is within the allowed range, controller will not allow to close the GCB,even if relevant LED diod on front panel of IL-NT lits.

    New setpoint:

    ConnectionType [3Ph4Wire / 3Ph3Wire / Split Ph / Mono Ph]Generator winding connection.

    3Ph4Wire: STAR Connection, 3 phases and neutral - 4 wires,Three phase wye measurement 3PY, 3x CT

    3Ph3Wire: DELTA Connection, 3 Phase without neutral - 3 Wires,

    Three phase delta measurement 3PD, 3x CTSplit Phase: DOUBLE DELTA Connection, Split Phase,

    Single-phase measurement 1PH, 1xCTMono Phase: MONOPHASE,

    Single-phase measurement 1PH, 1x CT

    Renamed setpointold setpoint Nominal Volts to NomVolts Ph-N New setpoint NomVolts Ph-Ph

    HW extension - 4 binary inputs (STD)One more physical binary output has been added to controller HW. Each newly produced IA-NTSTD controller will have four binary inputs.

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    14/23

    New features of IA-NT sw V2.0 Page 14 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    Web server for IB-Lite supported (STD & PWR)New secured way of monitoring and controlling the gen-set from any point in world using yourweb browser! Clear overview and control of the state of engine, its settings and history. Userfriendly.

    Scada window:

    Measurement window:

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    15/23

    New features of IA-NT sw V2.0 Page 15 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    Setpoints window:

    History window:

    HINT:This feature requires IB-Lite optional plug-in module and visible connection of controller toEthernet.

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    16/23

    New features of IA-NT sw V2.0 Page 16 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    IL-NT BIO8 Hybrid binary input/output module available (STD & PWR)IL-NT BIO8 is optional plug-in card. Through this card controller can accommodate up to 8 binaryinputs or outputs. In LiteEdit PC configuration tool (version 4.4 and higher) it is possible to easilychoose if particular I/O will be binary input or output.

    To insert the module, you must open the cover first (use screwdriver to open) and then insert themodule into slot. Once you have inserted it, the module will snap under plastic teeth. It issupposed to be installed permanently. Should you need to remove it, the safest way is to removewhole back cover and than remove module manually.Installing IL-NT BIO8 module is similar to installing RS 232 module. The difference is thatmodule fits to extension module slot and after installing IL-NT BIO8 you do not put back thesmall cover.

    Technical details:

    IL-NT BIO8 plugs into the controllers EXTENSION MODULE port.8 dedicated pins of the plug-in cards terminal can be configured as binary inputs or outputs.

    Binary inputsNumber of inputs 8Input resistance 4.7 kInput range 0-36 VDCVoltage level for close contact indication (Logical 1) < 0.8 VDCVoltage level for open contact indication (Logical 0) > 2 VDCMax voltage level for open contact indication 8-36 VDC

    Binary open collector outputsNumber of outputs 8Maximum current per pin 0.5 AMaximum switching common current 2 AMaximum switching voltage 36 VDC

    HINT:Binary inputs are not galvanically isolated.

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    17/23

    New features of IA-NT sw V2.0 Page 17 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    Timer1..2Function [No Func/TEST/TEST OnLd/MFail Blk/Mode OFF] (PWR)It is possible to choose out of 5 following Timer functions. Binary output Exerc Timer X is alwaysactivated when Timer is active regardless of chosen Timer function. Timer functions requirecontroller running in AUT mode.

    No Func: There is no any other function, but binary output Timer1..2 activation.TEST: When this option is chosen then the Timer output is also internally connected to

    the Remote TEST binary input.TEST OnLd: When this option is chosen then the Timer output is also internally connected to

    the Rem TEST OnLd binary input.MFail Blk: When this option is chosen then the Timer output is also internally connected to

    the MainsFailBlock binary input.Mode OFF: When this option is chosen then the Timer output is also internally connected to

    the Remote OFF binary input.

    Power switch function (PWR)This switch is assigned to the gen-set active power. The setpoints PowerSwitch ON [kW] andPowerSwitch OFF [kW] for on and off level adjustment are located in the setpoint group EngineParams. Typical usage for this binary output can be switching of dummy load. The outputbehaves based on the setpoint adjustment as described on picture lower:

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    18/23

    New features of IA-NT sw V2.0 Page 18 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    New setpoints:PowerSwitch ON [kW]Threshold level for switching the binary output Power Switch on.Step: 1Range: 0 32000 kW

    PowerSwitchOFF [kW]Threshold level for switching the binary output Power Switch off.Step: 1Range: 0 32000 kW

    Faul t Resetbinary output added (STD & PWR)Logical binary output Fault Resethas been added.

    The output is a copy of Fault Reset button on controller and binary input FaultResButton. Logical binary inputs MCB Feedback a GCB Feedback (STD)

    have been added to STD model:

    GCB FeedbackUse this input for indication, whether the generator circuit breaker is open or closed.If the feedback is not used, connect this input to the output GCB CLOSE/OPEN

    MCB FeedbackThis input indicates whether MCB is closed or opened.

    Logical binary inputs Mains On Load & Generator On load (STD & PWR)have been added. The meaning of these binary inputs is as follows:

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    19/23

    New features of IA-NT sw V2.0 Page 19 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    (LBO) Mains On Load

  • 8/13/2019 IA NT 2.0 New Features

    20/23

    New features of IA-NT sw V2.0 Page 20 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    Generator overload (shutdown) protection (PWR)has been added: Setpoints:

    Overload [%]Threshold for generator overload (in % of Nominal power)

    Step: 1% of Nominal powerRange: 0 200%

    Overload Del [s]Delay for generator overload alarm.Step: 0.1sRange: 0 600.0 s

    ModbusComSpeed setpoint (PWR)has been added: Setpoint:

    ModbusComSpeed [9600, 19200, 38400, 57600]If the Modbus mode is selected on COM1 or COM2 channels, the Modbus communicationspeed in bpscan be adjusted here.

    Programmable delay on alarms (PWR)Possibility to set programmable delay on alarms configured for binary output 6 and 7 has beenadded. If set, it blocks alarms of the respective binary input for the whole time the delay is active.If the reason for the alarm persists after the delay time expired, the alarm is activated. If not, thealarm does not appear. This feature allows the user to perform filtering of alarms within aspecified period of time.The delay length can be set via the following setpoints:

    BI6 Delay [s]Delay for alarm on binary input nr. 6Setpoint group: Gener ProtectStep: 0.1sRange: 0 360.0 s

    BI7 Delay [s]Delay for alarm on binary input nr. 7Setpoint group: Gener ProtectStep: 0.1sRange: 0 360.0 s

    Decimal switching for power measurement added (PWR)Possibility to select format for power measurement has been added.

    Format can be set via LiteEdit PC configuration tool version 4.4 and higher using itsUnits/Formats configuration dialog:

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    21/23

    New features of IA-NT sw V2.0 Page 21 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    22/23

    New features of IA-NT sw V2.0 Page 22 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp, spol. s r.o.Kundratka 2359/17180 00 Prague 8Czech Republic

    ISO 9001 Certif ied

    ComAps.r.o

    .

    QualityManagemen

    t

    Tel.: +420 246 012 111Fax: +420 246 316 647E-mail: [email protected]

    Internet: http://www.comap.cz

    Customer Welcome screen added (STD & PWR)Screen dedicated to information provided by customers such as contact numbers, servicetechnician contact and customer message for end users of gen-set has been added.Configuration of this screen is only done by LiteEdit PC software (v. 4.4 and higher).

    Information is displayed on so called Init Screens which are displayed after controller isswitched on or reprogrammed. It is also possible to call these screens from any measurementscreen by pressing ENTER and PAGE buttons concurrently and then only PAGE buttonseparately.

    Support for Hebrew font (STD & PWR)has been added

    DiagData (STD & PWR) value

    Has been added. The value is implemented for ComAp diagnostics purposes

    Unified Latin fonts of texts in Chinese language (STD & PWR)

    New available dictionaries and updated older dictionaries (STD & PWR)

    German, Spain, French, Hebrew, Chinese, Italian, Dutch, Portuguese and Russian

    mailto:[email protected]://www.comap.cz/http://www.comap.cz/mailto:[email protected]
  • 8/13/2019 IA NT 2.0 New Features

    23/23

    New features of IA-NT sw V2.0 Page 23 of 23

    IA-NT V2.0 New features / ComAp May 2010 / IA-NT-2.0 New features.pdf

    ComAp spol s r oCo

    mAps.r.o.

    Tel : +420 246 012 111

    Optional size of history (STD & PWR)based on configuration of additional peripheries like extension modules is available from now.Unnecessary columns are hidden in history.

    Context sensitive help (STD & PWR)

    New context sensitive helpsfor setpoints, binary inputs / outputs and valuesin LiteEdit