I !i'l BUFFALO & FORT ERIE -...
Transcript of I !i'l BUFFALO & FORT ERIE -...
�I
!i'l R.F. Willson Building - Renovations -�1=========================================================================================================================1
ii ul ""
i
�
j
BUFFALO & FORT ERIE
PUBLIC BRIDGE AUTHORITY f1==========================================================================================================================l 0
Lfi
.. :ll ii:
m 0 N
�
i
Peace Bridge Plaza
DRAWING LIST
GENERAL P001
0011 G100 C100 C101 S100 S101
S102 A101 A102 A201 A202 A301 A302 A303 A401 A402 A501 M001 MD100 MD101 MD102 MD103 M200 M201 M202 M203 M300
PD100 TITLE SHEET, SYMBOLS &ABBREVIATIONS PD101 STAGING PLANS & NOTES P200 SITE PLAN P201 TYPICAL SITE DETAILS E001 GENERAL STRUCTURAL NOTES, LOADS, AND SCHEDULES ED100 ELECTRICAL ROOM FOUNDATION, FRAMING PLAN AND DETAILS ROOF MECH. UNIT FRAMING PLAN AND DETAILS FIRST FLOOR PLAN FIRST FLOOR REFLECTED CEILING PLAN PARTIAL SECOND FLOOR PLANS PARTIAL SECOND FLOOR REFLECTED CEILING PLANS ELECTRICAL ROOM PLANS AND ELEVATIONS ELECTRICAL ROOM WALL SECTIONS AND DETAILS STAIR DETAILS ROOF PLAN AND ROOF DETAILS ROOF DETAILS SCHEDULES AND DETAILS MECHANICAL LEGEND AND SCHEDULES MECHANICAL BASEMENT DEMOLITION PLAN MECHANICAL FIRST FLOOR DEMOLITION PLAN MECHANICAL SECOND FLOOR DEMOLITION PLAN MECHANICAL ROOF DEMOLITION PLAN MECHANICAL BASEMENT PLAN MECHANICAL FIRST FLOOR PLAN MECHANICAL SECOND FLOOR PLAN MECHANICAL ROOF PLAN MECHANICAL HYDRONIC SYSTEM SCHEMATIC
ED101 ED102 ED103 E100 E101 E102 E103 E104 E105 E201 E202 E300 E401 E501 E502 E503 E504 E601 E602 E603
PLUMBING DETAILS, SCHEDULES AND NOTES CRAWL SPACE PLUMBING DEMOLITION PLAN SECOND FLOOR PLUMBING DEMOLITION PLAN CRAWL SPACE PLUMBING PLAN SECOND FLOOR PLUMBING PLAN ELECTRICAL LEGEND, NOTES AND DIAGRAMS BASEMENT AND CRAWL SPACE ELECTRICAL REMOVALS PLAN FIRST FLOOR ELECTRICAL REMOVALS PLAN SECOND FLOOR ELECTRICAL REMOVALS PLAN ROOF ELECTRICAL REMOVALS PLAN BASEMENT AND CRAWL SPACE - POWER PLAN FIRST FLOOR - POWER PLAN SECOND FLOOR - POWER PLAN ROOF - POWER PLAN ENLARGED PLANS VAULT ELECTRICAL REMOVALS AND NEW WORK PLANS FIRST FLOOR - LIGHTING PLAN SECOND FLOOR - LIGHTING PLAN SITE PRIMARY FEEDER PLAN ELECTRICAL DETAILS ONE LINE DIAGRAM- ELECTRICAL REMOVALS ONE LINE DIAGRAM PARTIAL POWER RISER DIAGRAMS PARTIAL POWER RISER DIAGRAMS PANEL SCHEDULES PANEL AND MISCELLANEOUS SCHEDULES PANEL SCHEDULES EXISTING (FOR INFORMATION ONLY)
Buffalo, New York 14213-2494
GENERAL NOTES
A. OWNER TO REMOVE ALL FURNITURE AS NECESSARY FOR WORK RELATED TO MECHANICAL AND ELECTRICAL UPGRADES. CONTRACTORTO REMOVE ALL MATERIALS AND PARTITIONS AS INDICATED ON DRAWINGS AND SHALL COORDINATE WITH OWNER FOR WORK AREAS ASDICTATED IN THE CONSTRUCTION SCHEDULE.
B. ALL DIMENSIONS ARE DIMENSIONED TO THE FACE OF THE PARTITION.C. DO NOT SCALE DRAWINGS: NOTIFY THE ARCHITECT IF ADDITIONAL DIMENSIONS ARE REQUIRED. WALL, PARTITION, AND STRUCTURAL
DIMENSIONS ARE ACTUAL. CONTRACTORS SHALL VERIFY ALL DIMENSIONS IN THE FIELD AND NOTIFY THE ARCHITECT OF ANY DISCREPANCIES.
D. THE CONTRACTOR SHALL PROVIDE ALL MATERIALS INDICATED GRAPHICALLY OR AS NOTED. CONTRACTOR SHALL NOTIFY ARCHITECTOF ANY DISCREPANCIES IN IDENTIFICATION OF MATERIALS REQUIRED.
E. THE CONTRACTOR(S) SHALL FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS AT THE SITE AND REPORT ANYDISCREPANCIES BETWEEN DRAWINGS AND ACTUAL FIELD CONDITIONS TO THE ARCHITECT PRIOR TO CONSTRUCTION. THIS INCLUDESBUT IS NOT LIMITED TO EXISTING UTILITIES.
F. CONTRACTOR(S) FOR SPECIFIC WORK SHALL BE RESPONSIBLE TO PROVIDE PROTECTION AS REQUIRED FOR NEW WORK AND EXISTINGCONSTRUCTION FINISHES SCHEDULED TO REMAIN.
G. INSTALL ALL MATERIALS TO THE MANUFACTURES RECOMMENDATIONS AND TO ACCEPTABLE PROFESSIONAL TRADE INDUSTRYSTANDARDS UNLESS INDICATED OTHERWISE.
H. PROVIDE ALL INCIDENTAL WOOD BLOCKING AS REQUIRED FOR ATTACHMENT OF EQUIPMENT, FINISHES AND ACCESSORIES.I. ALL CONSTRUCTION SHALL CONFORM TO THE LATEST EDITION OF ALL BUILDING CODES AND ORDINANCES. THE BUILDING CODE OF NEW
YORK STATE, THE ADA CODE, THE AISC CODE, THE ACJ CODE, THE WELDING SOCIETY CODE, ALL APPLICABLE ASTM, SMACNA, AND NRCA STANDARDS. IN CASE OF CONFLICT THE MOST STRINGENT SHALL GOVERN.
J. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OF ALL HOLLOW METAL FRAMES.K. THE GENERAL CONTRACTOR WILL BE RESPONSIBLE FOR MAKING ARRANGEMENTS FOR ALL REQUIRED INSPECTIONS.L. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE WORK OF ALL TRADES AND SUBCONTRACTORS.M. SUBSTITUTIONS: PRODUCTS, MATERIALS AND MANUFACTURERS ARE IDENTIFIED ON THE DRAWINGS AND IN THE SPECIFICATION.
SUBSTITUTIONS WILL BE CONSIDERED ONLY IF SIGNIFICANT SAVINGS IN TIME OR COST TO THE PROJECT CAN BE DEMONSTRATED BYTHE CONTRACTOR. ONCE SUBMITTED, SUBSTITUTIONS WILL BE CONSIDERED OR REJECTED AT THE SOLE DISCRETION OF THEARCHITECT.
N. CONTRACTOR SAFETY PERSONNEL TO EVALUATE EXISTING CONFINED SPACE CONDITIONS ALONG WITH SCHEDULED WORK ANDDETERMINE SAFETY PRECAUTIONS NECESSARY IN ORDER TO WORK IN CONFINED SPACE.
ABBREVIATIONS
ADD'TL ADJ. ALUM. A.F.F. CBP CLO. CMU CONG. CONSTR. CONT. DIMS EA. ELECT. E.T.R. EXIST F.F. GA. GALV. GPDW HD GALV. HDGP HGT INSUL. JAN. LT. M.O.N.I.C.N.I.T.PNTS
o.c.O.H. OIT PLUMB. REINF. / REIN. R.C.P.RM.SCHD.SGFT
ADDITIONAL ADJUSTABLE ALUMINUM ABOVE FINISHED FLOOR CUSTOMS BORDER PROTECTION CLOSET CONCRETE MASONRY UNIT(S) CONCRETE CONSTRUCTION CONTINUOUS DIMENSION(S) EACH ELECTRICAL EXISTING TO REMAIN EXISTING FINISHED FLOOR GAUGE GALVANIZED GYPSUM PANEL DRY WALL HOT DIPPED GALVANIZED HIGH DENSITY GYPSUM PANEL HEIGHT INSULATION / INSULATED JANITOR LIGHT MASONRY OPENING NOT IN CONTRACT NOT IN THIS PHASE NOT TO SCALE (AREA CIRCLED) ON CENTER OPPOSITE HAND OPERATIONS INFORMATION TECHNOLOGY PLUMBING REINFORCED / REINFORCING REFLECTED CEILING PLAN ROOM SCHEDULE
GENERAL ASBESTOS AWARENESS LOCATION MAP GENERAL LEAD AWARENESS S.S.STO.
STRUCTURAL GLAZED FACING TILE STAINLESS STEEL STORAGE
ALL ASBESTOS ABATEMENT IS TO BE DONE BY OTHERS UNDER SEPARATE CONTRACT EXCEPT FOR 9" X 9" ACT FLOOR TILE, INCLUDING MASTIC, AND RESILIENT BASE REMOVALS
AS INDICATED ON THE DRAWINGS SHALL BE REMOVED BY THE GENERAL CONTRACTOR. ANY DISTURBANCE OF ASBESTOS CONTAINING MATERIALS SHALL BE PERFORMED BY A LICENSED ASBESTOS ABATEMENT CONTRACTOR EMPLOYING CERTIFIED WORKERS.
ASBESTOS-CONTAINING MATERIALS (ACM) ARE KNOWN TO BE PRESENT WITHIN THE WORK SITE. IT IS EXPECTED THAT WORK ASSOCIATED WITH THIS PROJECT WILL RESULT IN THE DISTURBANCE OF KNOWN ASBESTOS-CONTAINING MATERIALS.
ANY QUESTIONABLE MATERIAL OR MATERIAL SUSPECTED TO CONTAIN ASBESTOS SHALL NOT BE DISTURBED AND SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER OR THE OWNER'S REPRESENTATIVE FOR AN ACCURATE INTERPRETATION AND/OR SAMPLING AND ANALYSIS.
ALL CONTRACTORS ARE RESPONSIBLE FOR MAKING THEMSELVES AND THEIR EMPLOYEES AWARE OF THE PRESENCE, LOCATION, AND QUANTITY OF EXISTING ASBESTOS CONTAINING BUILDING MATERIALS, AND TO WARN THEIR EMPLOYEES OF THE POTENTIAL DANGERS OF EXPOSURE TO ASBESTOS. ANY DISTURBANCE OF ASBESTOS CONTAINING MATERIALS SHALL BE PERFORMED BY A LICENSED ASBESTOS ABATEMENT CONTRACTOR EMPLOYING CERTIFIED WORKERS.
5 IT E ------
I I
'
I I
I
I
,1
I
EACH CONTRACTOR SHALL BE RESPONSIBLE FOR COMPLYING WITH OSHA 29 CFR 1926.62: LEAD EXPOSURE IN CONSTRUCTION; INTERIM FINAL RULE FOR ALL ACTIVITIES
DURING WHICH AN EMPLOYEE MAY BE OCCUPATIONALLY EXPOSED TO LEAD.
THE CONTRACTOR IS RESPONSIBLE UNDER OSHA TO DETERMINE THE PRESENCE, LOCATION, AND QUANTITY OF EXISTING LEAD-CONTAINING MATERIALS THAT THEIR EMPLOYEES MAY BE EXPOSED TO, AND TO WARN THEIR EMPLOYEES OF THE POTENTIAL DANGERS OF THE DISTURBANCE OF LEAD-CONTAINING MATERIALS.
TECH.TlT.
TYP. UNO VEST. VIF VOiP
TECHNOLOGY TOILET TYPICAL UNLESS NOTED OTHERWISE VESTIBULE VERIFY IN FIELD VOICE OVER INTERNET PROTOCOL
SYMBOLS
11111
' BUILDING SECTION NUMBER
-------S"HEET ON WHICH BUILDING SECTION IS DRAWN
...L:il"'ELEVATION NUMBER °V-- SHEET NUMBER WHERE
ELEVATION IS DRAWN
4 INTERIOR ELEV. SYMBOL
o O o IYINTERIOR ELEV. LETTERSHEET NUMBER c WHERE ELEV. IS DRAWN
e WINDOW NUMBER
0 DOOR NUMBER
==:::i EXISTING PARTITION
c===:::i EXISTING PARTITION TO BE REMOVED
IIXMXX/\/111 NEW MASONRY PARTITION OR INFILL
l!llil!IE&!lllll!iil NEW PARTIAL HEIGHT MASONRY PARTITION
,uuuuua NEW METAL STUD AND DRYWALL PARTITION OR INFILL
NEW DOOR
EXISTING DOOR TO REMAIN
EXISTING DOOR TO BE REMOVED
��----------------------------------------------------------------------------------------------------------------------•
Consultants:
Signature & Seal:
Client:
Project:
Project Address:
TRAUTMAN ASSOCIATES
ARCHITECTS/ ENGINEERS
37 Franklin Street, Suite 100
Buffa lo, New York 14202
P 716 883 4400
F 716 883 4268
Tra utma nAssociates.com
WARNING: AL TERA TIONS TO THS DOCUMENT NOT CONFORMING TO SECTION 7209.2 OR 69.5(B) STATE EDUCATION LAW, ARE PROHIBITED. NOT PUBLISHED. ALL RIGHTS RESERVED.
BUFFALO & FORT
ERIE PUBLIC BRIDGE
AUTHORITY
R.F. WILLSON MECH.
AND ELEC. UPGRADES
1 PEACE BRIDGE PLAZA, BUFFALO, NEW YORK 14213
Drawing History: # Date Description
Project status: ISSUED FOR TENDER
Date: 0312512019
Project Number: 18023
Sheet Title: COVER SHEET,
GENERAL NOTES AND
DETAILS
Sheet Number:
Goo 1
,. 0.. � 0 .;;
al C, N
� IE
CJ �
ACCESS TO 2ND
FLOOR MECHANICAL
ROOM AND ROOF
WORK AREAS
E.V. ''® '\.
_,--TEMPORARY STAGING AREAS
AND LIFT ACCESS
- - - -�z�---·r -
�//_/@ + �I\ ' ' 'I '\
i
_.J-----
\ ,./ _.,
..,..,
.. _.-
8)
\ \.
'\.
FLUE
voo voo
0 0
,w,
D
EXISTRIJ
E.F.
0 (C/:
2 STAGING ROOF PLAN/ SECOND FLOOR 1/16" = 1'-0
ft
PROVIDE TEMPORARY PROTECTION AT
FENCED AREA DURING CONSTRUCTION
PERIOD - MAINTAIN EXIT REQUIREMENTS
PBA TO REMOVE EXISTING -�
SHRUBS AND PLANTS PRIOR
TO INITIATING DEMO WORK
8) 0 ���GING SITE PLAN
I I
"·
0
------ ·--·--·-·-·-·-
E.F.
WILLSON BUILDING:
MECHANICAL AND ELECTRICAL
UPGRADES WORK AREA
0
11 I
ElOSTRD
:;-:i�'.1 fL\)E
STAGING AREA FOR MATERIALS--
UNDER BRIDGE
8) 0 ��EAL VIEW
CONTRACTOR PERSONNEL PARKING ALONG
BUSTI AVENUE AS PERMITTED BY THE CITY
OF BUFFALO PARKING ENFORCEMENT
GENERAL FENCED STAGING AREA
ELECTRICAL
EQUIPMENT
ENCLOSURE
BAR SCALE
\
40 0 20 40
b-.•.•.•:-! ' ' 1 inch = 40 ft.
GENERAL STAGING NOTES:
A. ALL CONTRACTOR PERSONNEL PARKING SHALL BE AT BUSTI AVENUE. CONTRACTORS
SHALL INFORM ALL THEIR PERSONNEL AND SHALL ABIDE BY CITY OF BUFFALO PARKING
REGULATIONS.
I L_ ________________________________________________________________________________________________________________ _
Consultants:
Signature & Seal:
TRAUTMAN ASSOCIATES
ARCHITECTS/ ENGINEERS
37 Franklin Street, Suite 100
Buffa lo, New York 14202
P 716 883 4400
F 716 883 4268
Tra utma nAssociates.com
WARNING: AL TERA TIONS TO THS DOCUMENT NOT CONFORMING TO SECTION 7209.2 OR 69.5(B) STATE EDUCATION LAW, ARE PROHIBITED. NOT PUBLISHED. ALL RIGHTS RESERVED.
Client: BUFFALO & FORT
ERIE PUBLIC BRIDGE
AUTHORITY
Project:
Project Address:
R.F. WILLSON MECH.
AND ELEC. UPGRADES
1 PEACE BRIDGE PLAZA, BUFFALO, NEW YORK 14213
Drawing History: # Date Description
Project status: ISSUED FOR TENDER
Date: 0312512019
Project Number: 18023
SheetTitle: STAGING PLANS
& NOTES
Sheet Number:
G 1 o o
ELECTRIC EQPM.
ENCLOSURE ON
CONC. PAD
LAWN
FC-1
1-STORY ELECTRICAL
EQUIP. BUILDING
F.F.E. 0'-0" (638.63± V.I.F.)
RIM 638.25
8'-9
"
(M.E
.)
70'-6"± V.I.F. (CONC. S.W.)
14'-012"±
M.E
.
638.06
637.94 TC
637.44 BC
638.11
637.93
TC&BC
638.05638.03
2'-0" TO
DOOR OPNG.
5'-0
"
26'-9
"± V
.I.F
. (F
EN
CE
)
638.11±
637.94 TC
637.70 BC±
M.E
.
CB
RIM 637.44
YD
C.J
.
CO
90°±
638.35 638.50
638.35
638.05
DS
DS
6'-0
"±
FC-1
CR
15
G
17
1-STORY ELECTRICAL
EQUIP. BUILDING
F.F.E. 0'-0" (638.63± V.I.F.)
6" DIA. 34 L.F.
P
P
6" DIA.
47 L.F.
RIM 638.25
INV. 635.25
YD
CBRIM 637.44
E&W INV. 634.66± (ME)
S INV. 634.16± (ME)
5KV FEEDER
PCO
EXISTING ELEC.
PULL BOX
EXIST. & PROPOSED
ELEC. CONDUITS -
REFER TO ELEC.
DWGS. (TYP.)DS
DS
FC-1
CR
Consultants:
Signature & Seal:
WARNING: ALTERATIONS TO THISDOCUMENT NOT CONFORMING TOSECTION 7209.2 OR 69.5(B) STATEEDUCATION LAW, ARE PROHIBITED.NOT PUBLISHED. ALL RIGHTS RESERVED.
Project Number:
Sheet Title:
Sheet Number:
Date:
Project Status:
Drawing History:
Client:
Project:
Project Address:
# Date Description
P:\B
flo &
For
t Erie
Pbl
c B
ridge
Aut
h\18
023
Will
son
Bld
g M
ech
& E
lec
Upg
rade
s\D
raw
ings
\Civ
il\18
023_
C10
0.dw
gW
edne
sday
, Mar
ch 2
0, 2
019
- 1:
46 P
M
1 PEACE BRIDGE PLAZA,BUFFALO, NEW YORK 14213
03/25/2019
18023
ISSUED FOR TENDER
BUFFALO & FORTERIE PUBLIC BRIDGEAUTHORITY
R.F. WILLSON MECH.AND ELEC. UPGRADES
SITE PLAN
PREPARATION PLAN1" = 10.0'
SITE LAYOUT & GRADING PLAN1" = 10.0'
BAR SCALE
1 inch = ft.
10 0 5 10 20
10
C100
1, 2,3
NOTE: EXISTING SITE PLAN IS BASED UPON PLANS BY OTHERS AND A
2018 SITE INSPECTION. EXACT DEPTHS AND LOCATION OF ALL UTILITIES
IS UNKNOWN. UTILITY AND ELEVATION INFORMATION AS SHOWN HAS
BEEN OBTAINED FROM EXISTING CONSTRUCTION DOCUMENTS AND
ERDMAN ANTHONY SURVEY #FB2016-03 DATED AUGUST, 2016.
WILLSON BLDG. - SITE KEY PLANNTS
SHERIDAN TERRACE
PEACE BRIDGE
SITE UTILTIY PLAN1" = 10.0'
DRAWING NOTES1. CAREFULLY REMOVE AND SALVAGE LANDSCAPED BED PLANTS AND SHRUBS FOR FUTURE
TRANSPLANTING. FIELD VERIFY QUANTITY AND LOCATIONS BEFORE REMOVALS AND PROTECT AND
STORE PER DIRECTION OF OWNER.
2. REMOVE AND DISPOSE OF CONCRETE SIDEWALK, CURB AND CONCRETE STEPPING STONES. SAWCUT
SIDEWALK AND CURB AT NEAREST SIDEWALK JOINT WHERE CONCRETE REMOVAL ABUTS EXISTING
CONCRETE TO REMAIN. REFER TO LAYOUT PLAN FOR EXTENT.
3. REMOVE AND DISPOSE OF EXISTING BRICK AND CONCRETE STORM STRUCTURE, GRATE AND COVER.
FIELD VERIFY LOCATIONS AND INVERTS OF EXISTING STORM PIPES FOR CONNECTION TO PROPOSED
STORM STRUCTURE. PROTECT EXISTING STORM PIPES TO REMAIN. PROVIDE SEDIMENT PROTECTION
THROUGHOUT DEMOLITION AND CONSTRUCTION ACTIVITIES.
4. CONCRETE SIDEWALK. MATCH EXISTING WIDTHS AND ELEVATIONS WHEN ABUTTING EXISTING.
5. CONCRETE CURB. MATCH EXISTING PROFILE AND ELEVATIONS WHEN ABUTTING EXISTING.
6. 8'-0" HIGH GALVANIZED CHAINLINK FENCE AND LOCKABLE SWING GATE WITH SECURITY SYSTEM.
LOCATE 8'-0" FENCE IN LINE WITH EXISTING 4'-0" CHAINLINK FENCE POST AND NEAR CORNER OF
BUILDING AS SHOWN ON PLAN.
7. PRECAST CONCRETE STORM STRUCTURE, CURB FRAME AND GRATE.
8. YARD DRAIN.
9. 6" DIAMETER PERFORATED HDPE PIPE WITH SOCK, 0.5% MINIMUM SLOPE.
10. 6" DIAMETER PVC STORM PIPE. FIELD VERIFY AND MATCH EXISTING INVERTS.
11. SCOPE STORM PIPE FROM CATCHBASIN TO NEXT NEAREST DOWNSTREAM STORM SEWER
STRUCTURE(S). FLUSH AND CLEAN STORM PIPES TO FREE FLOWING CONDITION. VERIFY INVERT
ELEVATIONS FOR NEW POINTS OF CONNECTION. IMMEDIATELY REPORT TO ARCHITECT ANY
ENCOUNTERED DAMAGE AND/OR CONDITIONS THAT CONFLICT WITH PLANS.
12. RESTORE LAWN ADJACENT TO NEW SIDEWALK, MINIMUM 4" TOPSOIL, SEED AND HYDROMULCH.
GRADE ADJACENT LAWN TO MEET SIDEWALK DESIGN SLOPES AND PROVIDE SMOOTH TRANSITION TO
EXISTING LAWN AREAS, TYPICAL.
13. WEED BARRIER AND 4" MIN. DEEP NO. 1 WASHED STONE.
14. PROTECT UTILITY TO REMAIN, USE CAUTION WORKING NEAR ELECTRICAL EQUIPMENT & CONDUITS.
15. APPROXIMATE OUTLINE OF EXISTING ENCLOSURE. EQUIPMENT, ENCLOSURE, CONCRETE PAD, AND
CONDUITS TO BE REMOVED IN ENTIRETY, REFER TO ELECTRICAL DRAWINGS.
16. ELECTRIC DUCT BANK, CONDUITS & HANDHOLES (N.I.C.). REFER TO AND COORDINATE PROPOSED SITE
WORK WITH EXISTING CONDITIONS PER VAULT ELECTRIC SERVICE UPGRADE PROJECT (TA #17046.01).
17. PROPOSED CONDUITS FOR POWER AND COMMUNICATIONS ARE SHOWN FOR REFERENCE. REFER TO
ELECTRICAL DRAWINGS AND COORDINATE WORK SHOWN ON THIS SHEET WITH UTILITIES SHOWN ON
ELECTRICAL DRAWINGS.
18. PROTECT EXISTING TREE TO REMAIN, TYPICAL.
NOTE: FOR TYPICAL DETAILS SEE DRAWING C101.
5
A303
1
15
3
CIVIL LEGEND
PROPOSED SPOT ELEVATION
UNIFORM SLOPING FINISH GRADE
CONTROL JOINT - TOOLED & SAWCUT
EXPANSION JOINT/ DOWELED
CONCRETE SIDEWALK
YARD DRAINYD
P UTILITY POINT OF CONNECTION
TREE / SHRUB
E.J./ E.J.D.
UNDERGROUND ELECTRIC
EXISTING SITE FEATURES
ABBREVIATIONS
CLR. CLEAR
CO CLEANOUT
CONC. CONCRETE
CONT. CONTINUOUS
CL CENTERLINE
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CPP CORRUGATED PLASTIC PIPE
DIA. DIAMETER
DWG. DRAWING
DS ROOF LEADER/ DOWNSPOUT
ELEC. ELECTRICAL
ELEV. ELEVATION
ENT. ENTRANCE
EQ. EQUAL
E.W. EACH WAY
E.J. EXPANSION JOINT
E.J.D. EXPANSION JOINT W/DOWEL
ELEV. ELEVATION
EXIST. EXISTING
FND. FOUNDATION
F.F.A. FINISH FLOOR ELEVATION
GALV. GALVANIZED
H.D. HOT DIP
I.D. INSIDE DIAMETER
INV. INVERT
L.F. LINEAR FEET
M.E. MATCH EXISTING
MAX. MAXIMUM
MIN. MINIMUM
N.I.C. NOT IN CONTRACT
N.F.V. NOT FIELD VERIFIED
N.T.S. NOT TO SCALE
O.D. OUTSIDE DIAMETER
O.C. ON CENTER
PL PROPERTY LINE
RCP REINFORCED CONCRETE PIPE
R. RADIUS
SS SANITARY SEWER
ST STORM SEWER
R.O.W. RIGHT OF WAY
S.J. SAWCUT JOINT
T.J. TOOLED CONTRACTION JOINT
TC/ BC TOP OF CURB/ BOTTOM OF CURB
TYP. TYPICAL
V.I.F. VERIFY IN FIELD
W/ WITH
YD YARD DRAIN
PROPOSED
STORM SEWER
A. CONTINUOUS OPERATION OF THIS FACILITY IS MANDATORY. THE CONTRACTOR SHALL
PHASE AND COORDINATE WORK WITH THE BUFFALO AND FORT ERIE PUBLIC BRIDGE
AUTHORITY TO PREVENT DISRUPTION TO NORMAL OPERATIONS. PROVIDE MINIMUM 48
HOUR WRITTEN NOTICE PRIOR TO NECESSARY UTILITY INTERRUPTIONS.
B. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL SUBMIT A PROPOSED PROJECT
SCHEDULE FOR APPROVAL.
C. FIELD VERIFY ALL DIMENSIONS AND CONDITIONS OF ALL PERTINENT BUILDING
CONDITIONS, SURFACE AND SUBSURFACE FEATURES, UTILITIES, AND GRADES SHOWN
PRIOR TO PREPARING SUBMITTALS, PURCHASING PRODUCTS AND STARTING
CONSTRUCTION. PROMPTLY NOTIFY THE ARCHITECT IN WRITING OF ANY
DISCREPANCIES, QUESTIONS OF INTENT OR CLARITY IN THE DOCUMENTS.
D. THE DEPTHS AND LOCATIONS OF EXISTING UTILITIES ARE NOT KNOWN. NOTIFY UTILITY
COMPANIES AND UNDERGROUND UTILITY LOCATING SERVICES. ACTUAL LOCATIONS
ARE TO BE DETERMINED IN THE FIELD BY THE CONTRACTOR. CONTRACTOR SHALL USE
ALL MEANS POSSIBLE, INCLUDING METAL DETECTORS, ELECTRONIC SENSORS,
PRODDING AND HAND EXCAVATION TO AVOID DISTURBING EXISTING BURIED UTILITIES.
REPAIR UTILITIES DAMAGED BY CONSTRUCTION.
E. DO NOT SCALE THE DRAWINGS. NOTIFY THE ARCHITECT IF ADDITIONAL DIMENSIONING
IS REQUIRED. UNLESS INDICATED OTHERWISE, DIMENSIONS ARE ACTUAL.
G. PROVIDE PRODUCTS AND MATERIALS INDICATED GRAPHICALLY AND NOTED. SUBMIT
DOCUMENTATION THAT ALL PROPOSED PRODUCTS AND MATERIALS CONFORM WITH
THE CONSTRUCTION DOCUMENTS. THIS INCLUDES BUT IS NOT LIMITED TO
MANUFACTURER'S PRODUCT DATA, COLOR CHARTS, AND ACTUAL SAMPLES FOR
VERIFICATION BY THE ARCHITECT AND/OR OWNER.
H. SUBMIT SHOP DRAWINGS OR PRODUCT SUBMITTALS COVERING ALL PRODUCTS
PROPOSED FOR INCORPORATION INTO THE PROJECT.
I. PRODUCT SUBSTITUTIONS WILL ONLY BE CONSIDERED IF SIGNIFICANT SAVINGS IN
TIME OR COST TO THE PROJECT CAN BE DEMONSTRATED.
J. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL NECESSARY PERMITS AND MAKE
ARRANGEMENTS FOR ALL REQUIRED INSPECTIONS. SUBMIT REPORTS AND
CERTIFICATES COVERING INSPECTIONS.
K. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL NECESSARY PERMITS AND MAKE
ARRANGEMENTS FOR ALL REQUIRED INSPECTIONS.
G. COORDINATE THE WORK OF ALL TRADES AND SUBCONTRACTORS AND WITH THE
OWNER.
H. WORK SHALL BE EXECUTED BY PERSONS EXPERIENCED IN THE TRADE THEY ARE
PERFORMING. PRODUCTS SHALL BE INSTALLED IN CONFORMANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS, INSTRUCTIONS, SPECIFICATIONS, AND
ACCEPTABLE TRADE INDUSTRY STANDARDS.
I. THE STABILITY OF BUILDING SLAB, STRUCTURE AND PAVEMENT SUBGRADE IS
DEPENDENT ON THE PRESENCE OF OPTIMAL MOISTURE CONTENT IN THE SOIL.
CONTRACTOR IS ADVISED THAT THE NATURAL MOISTURE CONTENT MAY FLUCTUATE
SEASONALLY AND, TO THE EXTENT FEASIBLE, CONSTRUCTION SHALL BE SCHEDULED
TO TAKE FULL ADVANTAGE OF NORMALLY DRY SUMMER MONTHS. WORK SHALL BE
SCHEDULED SUCH THAT SUBGRADE ESTABLISHMENT, SEAL ROLLING AND DRAINAGE
SYSTEM INSTALLATION IS COMPLETED FIRST. SUBSEQUENT CONSTRUCTION SHALL BE
DELAYED IF NECESSARY TO ALLOW SUBGRADES TO DRY AND STABILIZE.
J. WHERE EXISTING UTILITIES, STRUCTURES AND FOUNDATIONS (LIGHT POLE
FOUNDATIONS, PLAYGROUND EQUIPMENT, PLANTERS, ETC.) ARE REMOVED, BACKFILL
THE EXCAVATION WITH COMPACTED MATERIAL PLACED IN APPROPRIATE LIFTS
ACCORDING TO THE SPECIFICATIONS. COMPACTION TESTING BY QUALITY CONTROL
TESTING AGENCY REQUIRED.
K. CONTINUOUSLY MAINTAIN THE WORK AREA IN A CLEAN AND SAFE CONDITION.
CONTRACTOR IS RESPONSIBLE FOR DUST CONTROL.
L. WORK AREAS SHALL BE MADE WATERTIGHT AT THE END OF EACH WORK DAY AND AS
NECESSARY IN THE EVENT OF RAIN.
M. SUITABLE EXISTING TOPSOIL TO BE STRIPPED, STOCKPILED ON SITE, AND REUSED FOR
FINAL GRADING. SUPPLEMENT WITH APPROVED BORROW TOPSOIL MATERIAL AS
REQUIRED.
N. ALL EXCESS OR NON-SATISFACTORY EXCAVATED MATERIAL SHALL BE REMOVED FROM
SITE. (EXCESS STOCKPILED TOPSOIL TO REMAIN FOR SCHOOL USE.) ( EXCESS TOPSOIL
SHALL BE LEGALLY TRANSPORTED TO LOCATIONS IN ACCORCANCE WITH LOCAL
ORDINANCES.)
O. PROVIDE POSITIVE SURFACE DRAINAGE AWAY FROM ALL BUILDINGS AND
FOUNDATIONS AND IN ALL PLANTED AND PAVED AREAS TOWARD DRAINAGE
STRUCTURES. PROVIDE A MINIMUM OF 2% AWAY FROM ALL BUILDING FOUNDATIONS.
P. PLANTED AREAS TO BE GRADED SMOOTH WITH EVEN GRADIENTS. FILL IN HOLES AND
LOW SPOTS. EASE TOP AND BOTTOM OF SLOPES FOR EVEN TRANSITION BETWEEN
GROUND PLANES.
Q. PERFORM EXPLORATORY EXCAVATION AT ALL PROPOSED UTILITY CROSSINGS TO
CONFIRM PROPER CLEARANCES AND ALL UTILITY CONNECTION CONDITIONS PRIOR TO
INSTALLING PROPOSED UTILITY.
R. ADJUST ALL UTILITY MANHOLES, DRAINAGE STRUCTURES, CLEANOUTS, VENTS, AS
NECESSARY TO MEET PROPOSED GRADES.
S. SUBMIT MATERIAL DELIVERY TICKETS.
T. ALL MATERIALS AND CONSTRUCTION SHALL CONFORM TO NEW YORK STATE
DEPARTMENT OF TRANSPORTATION STANDARD SPECIFICATIONS.
U. ALL WORK SHALL CONFORM TO THE LATEST EDITIONS OF ALL BUILDING CODES AND
ORDINANCES INCLUDING THE BUILDING CODE OF NEW YORK STATE, THE ACI CODE,
ADA CODE, THE AISC CODE, THE NEC CODE, ALL APPLICABLE ASTM, SMACNA, AND
NCRA STANDARDS. IN CASE OF CONFLICT, THE MOST STRINGENT SHALL GOVERN.
V. REPAIR EXISTING CONSTRUCTION AND FINISHES DISTURBED BY CONSTRUCTION
ACTIVITY TO MATCH EXISTING ADJACENT CONDITIONS. RECONSTRUCT ALL SIDEWALKS,
PAVEMENTS, CURBS AND TURF AREAS DISTURBED BY SITE WORK CONSTRUCTION
ACTIVITY.
W. PROVIDE DETAILED RECORD DRAWINGS COVERING NEW CONSTRUCTION,
ENCOUNTERED CONDITIONS AND UTILITIES. FOR BURIED BENDS AND CONNECTIONS
PROVIDE DIMENSIONS TO TWO FIXED OBJECTS. INDICATE ACTUAL ELEVATIONS OF
NEW AND ENCOUNTERED UTILITIES.
GENERAL CIVIL NOTES:
LOCATIONS AND DEPTHS OF UNDERGOUND UTILITIES IS
UNKNOWN. ALL UNDERGROUND UTILITY LOCATIONS SHOWN ON
PLANS ARE APPROXIMATE. BEFORE YOU DIG, DRILL, OR BLAST,
CALL DIG SAFELY NEW YORK AT 1-800-962-7962
1
14
3
6
18
13
2
4
5
638.00
EXISTING SPOT ELEVATION
CATCH BASINCB
ELECTRIC PULL BOXE
PERFORATED STORM PIPE
PROPOSED SITE FEATURES
9
10
12
11
17
14 16
1
12
18
APPROX. LOCATION OF
EXIST. FENCE POST, V.I.F.
EXISTING SITE AND
17
EXISTING CONTOUR
14 16
CLEANOUTCO
18
14 17
18
� g '
-
0
�-i f m�
NOTES:
1. REFER TO PLAN FOR SIDEWALK WIDTH.
COMPACTED SUBBASE MATERIAL
' --.___ SOIL STABILIZATION FABRIC
"-..___ COMPACTED SUBGRADE PITCHED TO MATCH DRAINAGE DESIGN
2. PROVIDE CONTROL JOINTS AT 5'-0"±. REFER CONTROL JOINT LAYOUT INDICATED ON PLAN.3. PROVIDE EXPANSION JOINTS AT A MAXIMUM 50'--0 0.C. TYPICAL UNLESS NOTED OR SHOWN
OTHERWISE ON PLANS.4. PROVIDE 1/2" DIA SMOOTH DOWEL X 1'-6" LONG AT 2'-0' O.C. WHEN MATCHING EXISTING
SLABS OR FOUNDATIONS, DRILL & GROUT INTO EXISTING AND GREASE ONE END.5. FORM DEPTHS SHALL MATCH DESIGN DEPTH OF CONCRETE SIDEWALK.
0 �;P. CONCRETE SIDEWALK
��0. � UJ "' UJ 0 ";' u. "' :zUJ -- "' �b > ·' �
6" BEDDING MATL.
FINISH GRADE
MIN. 6" TOPSOIL, SEED, AND MULCH IN LAWN AREAS - REFER TO PLAN
DETECTABLE WARNING TAPE 1'-6" BELOW GRADE
<:;_*.---- PROVIDE TEMPORARY SHORING AS REQUIRED UNDER OSHA REGULATIONS
----+-,�;.:..__ COMPACTED BACKFILL
1'-�' PIPE 1'-0" O.D.
USE SUBBASE MATERIAL AT PAVED AREAS, SIDEWALKS, AND EXISTING UTILITIES. USE SATISFACTORY EXCAVATED MATERIAL ELSEWHERE
PIPE EMBEDMENT MATERIAL
NEW CONDUIT OR PIPE
0 TYPICAL UTILITY TRENCH
4"MAX. (TYP.)
4"MAX. (TYP.)
EXIST. 4'-0"± HIGH FENCE AND
CONCRETE WALL
N.T.S.
1'-0"
. ' .•
. '
..
END CLOSURE WELDED ASSEMBLY. HOT DIP GALV. (CAP PIPE END)
TYPICAL CHAIN LINK FENCE
TENSION BAND AT 1'-0" O.C. MAX. (TYP.)
111-�- TENSION BAR
I I I I I I I I JI.
END PCST (TYP.)
ADJUSTABLE TRUSS ROD ASSEMBLY
'--�-cl _Ill
1'--0" DIA. (TYP.)
I I I I I I I I J I
I I LJ /
1/2" RADIUS DIM. VARIES·
r AT FORMED CURB: _. - 1/4" RADIUS IT,/ NO EXPANSION JOINT
2% MAX. 6" (TYP.)
SLOPE TRANSITION TO MEET EXISTING FINISH GRADE (TYP.)
MATCH EXIST. 6" MAX. PREFERRED (SEE PLAN) ELEVATION & DRAINAGE
PATffll1Wtl
_,, " ·=t
NEW BUILDING FOUNDATION - REFER
-.X �--X.�X--X --X--. . ., .
TYPICAL CONCRETE SIDEWALK CONSTRUCTION MACHINE FORMED CURB CONTRACTORS OPTION:
7" MIN. "TYP.
CONSTRUCT INTEGRAL CURB, 1'-4" DEEP WITH 1" R. AND CONTINUOUS 1-1/2" DEEP TOOLED & SAWCUT JOINT 6" FROM EDGE
COMPACTED SUBBASE MATERIAL
CONCRETE CURB NOTES:
1. PROVIDE TOOLED CONTROL JOINTS AT 10'--0 O.C.2. PROVIDE EXPANSION JOINTS AT A MAXIMUM 50'-0 0.C.3. PROVIDE FINE BROOM FINISH TO EXPOSED PORTION OF CONCRETE CURB.4. FOR FURTHER INFORMATION REFER TO TYPICAL SIDEWALK DETAIL.5. WHERE CURB ABUTS EXISTING CURB, MATCH EXISTING PROFILE AND
ELEVATIONS.
TYPICAL CONCRETE 0 S.�RB & S.W. SECTION
ROOF LEADER
PVC DOWNSPOUT EXTENSION W/ INTEGRAL CLEANOUT FINISH GRADE
MIN. 1.5% (TYP.) -2-.
- --K--X� t-" , .a
J·½f),5'),c,f'.)qq�·
SAW-CUT CONTROL JOINT ( S.J. )
EXPANSION JOINT MATERIAL STOP STEEL REINFORCING
EXPANSION JOINT ( E.J.)
TYPICAL FOR CONCRETE SIDEWALKS
CONTROL JOINT ( C.J. )
112",jf-
EXPANSION JOINT MATERIAL NEW OR EXIST. CONG.
1/4" RADIUS "'JI / ,-.t TOOLED ED""G
--'E'--'-ifc-�·
.. "";�,i;�� :�OOTH DOWEL - 1/2" DIA. X 1'-6"LONG @2'-0" O.C., DRILL & GROUT INTO EXIST. AND GREASE ONE END
EXPANSION JOINT W/ DOWEL ( E.J.D.)
0 �;P. CONCRETE JOINTS
CAST IRON SLOTTED GRATE FINISH GRADE - SEE PLAN
I :'f')-V>' .. B" DIA. RISER
EXTERIOR CLEANOUT@ GRADE J.R. SMITH #4251-U OR APPROVED EQUAL,
COVER TO BE INSCRIBED "STORM" PVC CAP END
,__ FRAME 00+2' TO STRUCTURAL -----
� SATISFACTORY EXCAVATED MATERIAL
-->-� ���;l����=�:T
�:�PING;gs:.q.-- EMBEDMENT MATERIAL
NYSDOT 1A CRUSHED STONE
90" ELBOW
PRECAST CONCRETE THRUST BLOCK
6"STORM 1 % SLOPE MIN.
BEDDING COURSE
INVERT PER PLAN � _/ PERFORATED PIPE PER PLAN
0. --'l------+-'----r-._, ______ �
� NOTE: rn CONTRACTOR'S OPTION: USE OF � ..,�r"'J$
3� CAP END COMMERCIAL PVC OR HOPE YARD
� L _J
_....,,_ DRAIN CATCH BASIN UNITS WITH POSITIVE GRATE ANCHORAGE PERMITTED
--¥--¥-- 6' (TYP.) COMPACTED
SUBBASE MATERIAL
:'l!=!'I� ---� ffi � 1-- w<C C
"' :r:1-- u zzw UJ "' "' C t--W c,: "'"'"' "'w
f--+-- 6" PVC RISER PIPE FOR IN-LINE CLEANOUT
\�----.-45• PVC BEND STANDARD PVC WYE FITTING
PIPE PER PLAN
© TYP. ROOF LEADER6 TO STORM SEWER
N.T.S.
0 �;P. YARD DRAIN cm.4PACTED SUBGRADE
0 �;P. CLEANOUT
I I I I I I I I I I
'I I 10~--+-JJ
1"
.- 2" MAX.
BOTTOM EDGE OF FABRIC AT FINISH GRADE
J--14 1'-0" DIA. (TYP.)
8'--0" MAX.
FACE OF EXIST. MASONRY WALL �---2"- 9 GAUGE ZINC COATED
CHAIN LINK FABRIC WITH KNUCKLED SELVAGES TOP& BOTTOM 4'-0" CLEAR GATE OPENING END POST & CAP
(TYP.) END CLOSURE
WELDED ASSEMBLY, HOT DIP GALV.
(CAP PIPE END) _,,- - TOP RAIL 180" OFFSET _,,-- LINE POST CAP HINGE (TYP.)
LINE POST
__,_-TIES
INTERMEDIATE RAIL
LINE POST CONNECTOR BOTTOM RAIL 3"GROUND
CLEARANCE
" .
I I I I I I I I
I I "
FINISH GRADE -SEE PLAN
1/8' WASH (TYP.)
CAST IN PLACE CONCRETE ( TYP. )
I I Il-l I I I
.. 1 I II.
--'lc-- --+- u
CONCRETE SIDEWALK& CURB (SEE PLAN)
� 1'-0" DIA (TYP.)
CHAINLINK FENCE &GATE NOTES : 1. ALL FENCING POSTS AND FITTINGS SHALL BE GALVANIZED.2. STEP FENCE POSTS AND RAILS AS REQUIRED TO FOLLOW SLOPE OF FINISH GRADE.2. CONTRACTOR SHALL SUBMIT DETAIL DRAWING INCLUDING ELEVATION WITH POST
LOCATIONS. NO FENCE SHALL BE ERECTED PRIOR TO APPROVAL.
REFER TO TYP. CHAIN LINK FENCE DETAIL
TENSION BAND AT 1'-0" O.C. MAX. (TYP.) SURFACE MOUNTED GATE SECURITY LOCK & CONTROLS -REFER TO SPECIFICATIONS & ELEC. DRAWINGS FOR HARDWARE AND MOUNTING REQUIREMENTS
_,___.-TENSION BAR GATE FRAME ADJUSTABLE TRUSS ROD ASSEMBLY (TYP.)
FINISH GRADE REFER TO PLAN
I I
- n �-->I,._� ,-.___ SIDEWALK WIDENED FORI I GATE & SECURITY EQUIP. -I I REFER TO PLAN I I REFER TO ELECTRICAL . I l DRAWINGS AND
I . LJ COORDINATE LOCATION OF GATE POSTS WITH
l= . SECURITY EQUIPMENT . 1=-
FACE OF EXIST.
BUILDING FOUNDATION
-II '-rn---'
CAST IN PLACE CONCRETE (TYP.)
"JT=' I1'-0"DIA.�
4" MAX. (TYP.)
4" MAX. (TYP.)
;-2:. 0
u
z .; +I
0
STORM PIPE BEYOND
6"
== == =c:;::::::::::J
: -�
-
�� -== ==
PLAN
NEENAH (OR EQUIVALENT) HEAVY DUTY CAST-IRON FRAME, GRATE AND BARRED CURB BOX: FRAME 3070-001 GRATE 3070-0002 BARRED CURB BOX 30700006-2
PRECAST CONCRETE STORM STRUCTURE
CAST IN PLACE IN-LINE WITH FACE OF CONCRETE CURB
CAST-IRON CURBBOX
MAINTAIN POSITIVE SLOPE TO DRAIN (TYP.)
CONCRETE SIDEWALK PER PLAN
PRECAST CONCRETE STRUCTURE
==--t--t---;r6" DIA. PLASTIC FITTINGS &
6"
3'-0" SQUARE
SECTION
CLEANOUT CAP
GROUT SOLID
EXIST. TILE STORM PIPE COUPLING PER SPEC. TYPICAL AT CONNECTIONS TO EXISTING STORM PIPE
COMPACTED SUBBASE MATERIAL
0 �.TORM CATCH BASIN
CHAINLINK FENCE 0 �-�D CLOSURE ASSY. @YrYPICAL CHAIN LINK FENCE @9,�AINLINK SWING GATE
CHAINLINK FENCE @ �-�D CLOSURE ASSY.
WILLSON
BUILDING �---------------------------------------------------------------------------------------------------------------------�-----------------------------------
Consultants:
Signature & Seal:
TRAUTMAN ASSOCIATES
ARCHITECTS/ ENGINEERS
37 Franklin Street, Suite 100
Buffa lo, New York 14202
P 716 883 4400
F 716 883 4268
Tra utma nAssociates.com
WARNING: AL TERA TIONS TO THIS DOCUMENT NOT CONFORMING TO SECTION 7209.2 OR 69.5(B) STATE EDUCATION LAW, ARE PROHIBITED. NOT PUBLISHED. ALL RIGHTS RESERVED.
Client: BUFFALO & FORT
ERIE PUBLIC BRIDGE
AUTHORITY
Project:
Project Address:
Drawing History:
Project Status:
Date:
R.F. WILLSON MECH.
AND ELEC. UPGRADES
1 PEACE BRIDGE PLAZA, BUFFALO, NEW YORK 14213
# Date Description
ISSUED FOR TENDER
03/25/2019
Project Number: 1ao23
sheet Title: TYPICAL SITE DETAILS
Sheet Number:
C101
TYP. SLAB-ON-GRADEN.T.S.
RE
FE
R
TO
PLA
N
(DE
PT
H
"D")
8"
REINFORCEMENT
CONCRETE
VAPOR BARRIER PER SPEC.
COMPACTED SUBBASE
NYSDOT TYPE 2
COMPACTED SUBGRADE
1 3 X
"D
"
Consultants:
Signature & Seal:
WARNING: ALTERATIONS TO THISDOCUMENT NOT CONFORMING TOSECTION 7209.2 OR 69.5(B) STATEEDUCATION LAW, ARE PROHIBITED.NOT PUBLISHED. ALL RIGHTS RESERVED.
Project Number:
Sheet Title:
Sheet Number:
Date:
Project Status:
Drawing History:
Client:
Project:
Project Address:
# Date Description
P:\B
flo &
For
t Erie
Pbl
c B
ridge
Aut
h\18
023
Will
son
Bld
g M
ech
& E
lec
Upg
rade
s\D
raw
ings
\Str
uc\1
8023
_S10
0.dw
gW
edne
sday
, Feb
ruar
y 20
, 201
9 -
4:32
PM
1 PEACE BRIDGE PLAZA,BUFFALO, NEW YORK 14213
03/25/2019
18023
ISSUED FOR TENDER
BUFFALO & FORTERIE PUBLIC BRIDGEAUTHORITY
R.F. WILLSON MECH.AND ELEC. UPGRADES
WILLSON
BUILDING
GENERAL STRUCTURAL
NOTES, LOADS, AND
SCHEDULES
GOVERNING BUILDING CODES 2015 INTERNATIONAL BUILDING CODE
2017 NEW YORK STATE UNIFORM CODE SUPPLEMENT
BUILDING RISK CATEGORY IV
DESIGN SOIL BEARING CAPACITY "ASSUMED" 1500 PSF
FLOOR LIVE LOADS
ELECTRICAL ROOM 250 PSF
ROOF LIVE LOAD
ROOF CONSTRUCTION LOAD 20 PSF
COLLATERAL LOADS
MECHANICAL, ELECTRICAL, PLUMBING ALLOWANCE 5 PSF
SNOW LOAD
GROUND SNOW LOAD, Pg 50 PSF
SNOW LOAD IMPORTANCE FACTOR, Is 1.20
SNOW EXPOSURE FACTOR, Ce 1.00
THERMAL FACTOR, Ct 1.00
FLAT ROOF SNOW LOAD, Pf 42.0 PSF
SNOW DRIFT SURCHARGE, Pd 72.8 PSF
SNOW DRIFT WIDTH, w 14.2 FT
WIND LOAD
ULTIMATE DESIGN WIND SPEED, VULT 120 MPH
NOMINAL DESIGN WIND SPEED, VASD 93 MPH
WIND EXPOSURE D
INTERNAL PRESSURE COEFFICIENT, GCpi
+/- 0.15
COMPONENTS AND CLADDING1,2,3
DESIGN WIND PRESSURE - PSF (BASED ON AN EFFECTIVE AREA OF 10 SQ. FT.)
WALLS - INTERIOR ZONE / END ZONE 38.1, -41.3 / 38.1,-51.1
ROOF - INTERIOR ZONE / END ZONE / CORNER ZONE 15.5,-38.1 / 15.5,-64.0 / 15.5,-96.2
NOTES:
1. POSITIVE AND NEGATIVE NUMBERS INDICATE FORCES/PRESSURES ACTING TOWARD AND AWAY FROM THE
SURFACES RESPECTIVELY.
2. WIDTH OF END AND CORNER ZONES SHALL EXTEND FROM DEFINED BUILDING CORNERS A DISTANCE IS EQUAL TO 2
TIMES THE LESSER OF 10% OF THE LEAST HORIZONTAL DIMENSION OR 0.4 x MEAN ROOF HEIGHT, BUT SHALL NOT BE
LESS TAKEN THAN THE LESSER OF 4% OF THE LEAST HORIZONTAL DIMENSION OR 3 FEET.
3. DELEGATED DESIGN ELEMENTS - FOR EFFECTIVE AREAS GREATER THAN 10 SQ. FT., THE DELEGATED-DESIGN
ENGINEER SHALL CONSULT ASCE 7-10 TO DETERMINE DESIGN WIND PRESSURES BASED ON THE WIND LOAD DESIGN
CRITERIA PROVIDED. FOR EFFECTIVE AREAS 10 SQ. FT. OR LESS USE THE APPROPRIATE DESIGN WIND PRESSURE
INDICATED.
SEISMIC LOAD
SEISMIC IMPORTANCE FACTOR, IE 1.50
SITE SOIL CLASSIFICATION "ASSUMED" D
MAPPED SHORT PERIOD SPECTRAL ACCELERATION, SS 0.209 g
MAPPED ONE-SECOND PERIOD SPECTRAL ACCELERATION, S1 0.060 g
SHORT PERIOD SPECTRAL DESIGN ACCELERATION, SDS 0.223 g
ONE-SECOND PERIOD SPECTRAL DESIGN ACCELERATION, SD1 0.096 g
SEISMIC DESIGN CATEGORY C
BASIC SEISMIC-FORCE-RESISTING SYSTEM (ASCE 7-10 T12.2-1) TYPE A.9
RESPONSE MODIFICATION COEFFICIENT, R 2.0
DEFLECTION AMPLIFICATION FACTOR, Cd 1.75
SEISMIC RESPONSE COEFFICIENT, CS 0.167
DESIGN BASE SHEAR, V 9.1 KIPS
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
SYSTEMS AND COMPONENTS REQUIRING SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE (2015 IBC, CHAPTER 17)
NOT REQUIRED
SYSTEMS AND COMPONENTS REQUIRING STRUCTURAL TESTING FOR SEISMIC RESISTANCE (2015 IBC, CHAPTER 17)
1. ANCHORAGE OF ELECTRICAL EQUIPMENT FOR EMERGENCY AND/OR STANDBY POWER SYSTEMS.
2. INSTALLATION AND ANCHORAGE OF VIBRATION ISOLATION SYSTEMS.
3. ANY OTHER MECHANICAL, ELECTRICAL, OR PLUMBING SYSTEM ASSIGNED WITH A COMPONENT IMPORTANCE FACTOR, IP, OF 1.5.
ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING COMPONENTS REQUIRING SEISMIC BRACING (ASCE 7-10,
CHAPTER 13)
ARCHITECTURAL COMPONENTS
IMPORTANCE FACTOR, IP = 1.0 REQUIRED
IMPORTANCE FACTOR, IP = 1.5 REQUIRED
M/E/P COMPONENTS
IMPORTANCE FACTOR, IP = 1.0 EXEMPT
IMPORTANCE FACTOR, IP = 1.5 REQUIRED
FOUNDATIONS
F1 FOUNDATION DESIGN AND SEISMIC LOADING CRITERIA, INDICATED ON THE DRAWING, IS BASED ON AN ASSUMED SITE CLASS DESIGNATION OF "D" INACCORDANCE WITH THE BUILDING CODE OF NEW YORK STATE, SECTION 1615.5.2.
F2 EXTERIOR CONSTRUCTION SHALL BE CARRIED DOWN TO SUBGRADE NOT LESS THAN FOUR FEET BELOW FINISHED EXTERIOR GRADE.
F3 FOOTINGS MUST BE CARRIED DOWN TO UNDISTURBED NATURAL SUBGRADE MATERIAL HAVING A MINIMUM ASSUMED NET ALLOWABLE BEARING CAPACITYOF 1.5 KIPS PER SQUARE FOOT. BEARING ELEVATIONS GIVEN ARE ESTIMATED DEPTHS. EXACT BEARING ELEVATIONS AND SOIL BEARING CAPACITIESSHALL BE FIELD DETERMINED BY THE TESTING AGENCY'S NEW YORK STATE LICENSED PROFESSIONAL GEOTECHNICAL ENGINEER.
F4 NO FOUNDATION OR SOIL-SUPPORTED SLABS SHALL BE PLACED IN WATER OR ON OR AGAINST FROZEN GROUND.
F5 THE EXPOSED SUBGRADE IS READILY DISTURBED AND DEGRADED BY GROUND OR SURFACE WATER. WATER MUST NOT BE ALLOWED TO POND ON ANYSUBGRADE SURFACE. PROTECT EXPOSED SUBGRADES FROM CONSTRUCTION TRAFFIC. GROUND WATER SHALL BE CONTROLLED BY PROPER SITEGRADING AND DEWATERING TECHNIQUES SUCH AS SUMP AND PUMP OR WELLPOINT METHODS OF DEWATERING. ALL DEWATERING MEANS ANDMETHODS SHALL BE THE COMPLETE RESPONSIBILITY OF THE CONTRACTOR.
F6 FOUNDATION SUBGRADES SHALL BE HAND TRIMMED.
F7 FINISHED EXCAVATIONS AND BEARING GRADES SHALL BE INSPECTED AND APPROVED BY THE TESTING AGENCY'S GEOTECHNICAL ENGINEERIMMEDIATELY BEFORE ANY CONCRETE IS PLACED.
F8 THE ARCHITECT ASSUMES NO RESPONSIBILITY FOR THE VALIDITY OF THE SUBSURFACE CONDITIONS DESCRIBED ON THE DRAWINGS, TEST BORINGS ORTEST PITS. THESE DATA DESCRIBE CONDITIONS ONLY AT THE SPECIFIC LOCATIONS AND PARTICULAR TIMES SUCH SUBSURFACE EXPLORATIONS WEREPERFORMED.
F9 CONCRETE FOR EACH INDIVIDUAL FOOTING SHALL BE PLACED IN A SINGLE CONTINUOUS POUR.
F10 BRACE FOUNDATION WALLS AND GRADE BEAMS DURING BACKFILLING AND COMPACTION PROCEDURES. DO NOT REMOVE TEMPORARY BRACING UNTILPERMANENT SUPPORTS ARE INSTALLED.
F11 PROTECT ADJACENT STRUCTURES FROM CONSTRUCTION ACTIVITIES AND LOADS.
CONCRETE
C1 CONCRETE MATERIALS AND CONSTRUCTION SHALL CONFORM TO ACI-318 AND ACI-301, LATEST EDITIONS.
C2 CONCRETE SHALL HAVE THE FOLLOWING MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS:
ELEMENTS STRENGTH UNIT WEIGHTFOUNDATIONS, WALLS 4,500 PSI 145 PCFFOUNDATION FOOTINGS 4,000 PSI 145 PCFINTERIOR SLAB-ON-GRADE 4,000 PSI 145 PCFEXTERIOR SLAB-ON-GRADE 4,500 PSI 145 PCFSIDEWALKS AND CURBS 4,500 PSI 145 PCFEQUIPMENT/HOUSEKEEPING PADS 3,000 PSI 145 PCFALL OTHER CONCRETE 4,000 PSI 145 PCF
C3 PROVIDE CONSTRUCTION JOINTS WHERE SHOWN. SUBMIT DRAWINGS SHOWING ALL PROPOSED CONSTRUCTION JOINT LOCATIONS FOR APPROVALPRIOR TO PREPARATION OF AFFECTED REINFORCEMENT SHOP DRAWINGS.
C4 SIZES OF CONCRETE PLACEMENT SHALL NOT EXCEED THE FOLLOWING:
WALLS: PLACE IN SECTIONS, 24 FOOT MINIMUM LENGTH, AND 90 FOOT MAXIMUM LENGTH.SLAB-ON-GRADE: AS SHOWN ON PLAN.
C5 CONCRETE SLABS SHALL BE CAST SO THAT THE SLAB THICKNESS IS AT NO POINT LESS THAN THAT INDICATED ON THE DRAWINGS. FOR STEEL AND METALDECK FRAMED FLOORS, ALLOW AT LEAST 1/2” AVERAGE ADDITIONAL CONCRETE OVER FRAMED AREAS TO ACCOUNT FOR BEAM AND SLAB DEFLECTIONS.
C7 MINIMUM ELAPSED TIME BETWEEN ADJACENT CONCRETE PLACEMENTS SHALL BE 48 HOURS.
C8 INTERIOR SLABS SHALL BE PLACED AFTER ROOF DECK INSTALLATION HAS BEEN COMPLETED.
C9 NOTE SPECIFICATION REQUIREMENTS FOR SPECIAL INSPECTION OF CONCRETE CONSTRUCTION.
REINFORCEMENT
R1 BAR REINFORCEMENT SHALL CONFORM TO ASTM 615 GRADE 60.
R2 REINFORCEMENT SHALL BE CONTINUOUS THROUGH ALL CONSTRUCTION JOINTS UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
R3 WHERE REINFORCEMENT IS NOT SHOWN ON THE DRAWINGS, PROVIDE REINFORCEMENT IN ACCORDANCE WITH APPLICABLE TYPICAL DETAILS OR SIMILARTO THAT SHOWN FOR MOST NEARLY SIMILAR SITUATIONS AS DETERMINED BY THE ARCHITECT. IN NO CASE SHALL REINFORCEMENT BE LESS THANMINIMUM REINFORCEMENT PERMITTED BY THE AMERICAN CONCRETE INSTITUTE (ACI) BUILDING CODE.
R4 REINFORCEMENT SHALL BE INSPECTED AND APPROVED BY THE TESTING AGENCY BEFORE CONCRETE IS PLACED.
R5 WELDED WIRE FABRIC SHALL BE LAPPED TWO FULL MESH PANELS OR 1'-0 MINIMUM.
R6 REINFORCEMENT SHALL BE LAPPED AS PER SPLICE SCHEDULE.
R7 SLABS AND WALLS SHALL NOT BE SLEEVED OR BOXED OUT OR HAVE THEIR REINFORCEMENT INTERRUPTED EXCEPT AS SPECIFICALLY NOTED ON THEDRAWINGS. PROVIDE ADDITIONAL REINFORCEMENT AROUND OPENINGS AS SHOWN IN THE DETAILS.
R8 NOTE SPECIFICATION REQUIREMENTS FOR SPECIAL INSPECTION OF REINFORCEMENT.
MASONRY
CM1 CONCRETE MASONRY UNITS SHALL HAVE THE FOLLOWING MINIMUM STRENGTHS:
COMPRESSIVE STRENGTH (NET AREA): 2000 PSIF'm OF PRISM: 2000 PSI
CM2 WORK SHALL CONFORM TO THE “BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES” (ACI 530) AND SPECIFICATIONS (ACI 530.1), LATESTEDITIONS.
CM3 TEMPORARY SHORING SHALL BE PROVIDED TO SUPPORT ALL SLABS AND PORTIONS OF WALLS REMAINING ABOVE NEW OPENINGS UNTIL PERMANENTSUPPORT SYSTEMS ARE INSTALLED AND HAVE REACHED 28-DAY STRENGTH.
CM4 USE FLUID GROUT, NOT MASONRY MORTAR, FOR FILLING ALL VERTICAL AND HORIZONTAL CELLS CONTAINING REINFORCING BARS AND/OR ANCHORBOLTS. PLACE GROUT USING THE LOW LIFT GROUTING METHOD IN MAXIMUM 4'-0” LIFTS AND CONSOLIDATE GROUT IN PLACE BY VIBRATION TO ENSURECOMPLETE FILLING OF CELLS. PROVIDE GROUT CONFORMING TO ASTM C 476, WITH A MINIMUM 28-DAY STRENGTH OF 2000 PSI.
CM5 REINFORCEMENT BARS IN MASONRY SHALL BE LAPPED 48 BAR DIAMETERS MINIMUM.
CM6 MASONRY UNITS SHALL BE PLACED IN RUNNING BOND. TOOL EXPOSED JOINTS CONCAVE UNLESS OTHERWISE INDICATED.
CM7 MORTAR SHALL CONFORM TO THE REQUIREMENTS OF ASTM C270 AS FOLLOWS:
REINFORCED MASONRY: TYPE S
CM8 COMPLETELY COVER ALL WALLS EACH DAY TO PREVENT WATER FROM ENTERING TOP OF WALL.
CM9 WIRE REINFORCEMENT AND WALL ANCHORS AT EXTERIOR WALLS SHALL BE HOT DIP GALVANIZED.
CM10 PROVIDE HOT AND COLD WEATHER PROTECTION PER SPECIFICATIONS.
CM11 NOTE SPECIFICATION REQUIREMENTS FOR SPECIAL INSPECTION OF MASONRY CONSTRUCTION.
STRUCTURAL STEEL
S1 STRUCTURAL STEEL SHALL BE NEW STEEL CONFORMING TO THE FOLLOWING REQUIREMENTS:
W-SHAPES: ASTM A992/ASTM A572 GRADE 50CHANNELS: ASTM A36/ASTM A572 GRADE 50ANGLES: ASTM A36MISC. SHAPES, PLATES, & BARS: ASTM A36
S2 HIGH STRENGTH BOLTS, NUTS AND WASHERS SHALL CONFORM TO THE REQUIREMENT OF ASTM A325 OR A490 (3/4” MINIMUM DIAMETER).
S3 ALL WELD MATERIAL SHALL BE 70 KSI.
S4 WELDING WORK SHALL BE PERFORMED BY CERTIFIED WELDERS, SUBMIT DOCUMENTATION.
S5 WHERE NO CAMBER IS INDICATED, FABRICATE BEAMS WITH NATURAL CAMBER UPWARD.
S6 BEAM-TO-BEAM AND BEAM-TO-COLUMN CONNECTIONS SHALL BE SIMPLE SHEAR CONNECTIONS CAPABLE OF END ROTATIONS PER AISC “SPECIFICATIONFOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL BUILDINGS” SECTION J1.2 - SIMPLE CONNECTIONS UNLESS NOTEDOTHERWISE. CONNECTIONS SHALL UTILIZE HIGH STRENGTH BOLTS IN “SNUG-TIGHT” BEARING CONNECTIONS UNLESS OTHERWISE NOTED, WITH THETHREADS EXCLUDED FROM THE SHEAR PLANE. DESIGN ALL CONNECTIONS FOR THE FOLLOWING MINIMUM REACTIONS, UNLESS NOTED OTHERWISE:
W27 - 95 KIPS W18 - 60 KIPS W12 - 30 KIPSW24 - 85 KIPS W16 - 45 KIPS W10 - 15 KIPSW21 - 75 KIPS W14 - 45 KIPS W8 - 12 KIPS
S7 THE MINIMUM SIZE OF FILLET WELDS SHALL BE AS REQUIRED BY THE AISC SPECIFICATION SECTION J2 - WELDS, BUT SHALL NOT BE LESS THAN ¼” UNLESSSPECIFICALLY NOTED ON THE DRAWINGS.
S8 CONNECTION TO THE EXISTING STRUCTURE SHALL BE AS DETAILED ON THE DRAWINGS OR AS APPROVED BY THE ARCHITECT. THE CONTRACTOR SHALLMAKE ALL NECESSARY FIELD MEASUREMENTS OF, COORDINATE DETAILS WITH AND FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO THE PREPARATIONOF SHOP DRAWINGS.
S9 THERE SHALL BE NO FIELD CUTTING OF STRUCTURAL STEEL WITHOUT PRIOR REVIEW AND ACCEPTANCE BY THE ARCHITECT.
S10 TEMPORARY ERECTION BRACING SHALL BE PROVIDED AS REQUIRED TO HOLD STRUCTURAL STEEL SECURELY IN POSITION. IT SHALL NOT BE REMOVEDUNTIL PERMANENT BRACING HAS BEEN INSTALLED. THE BUILDING SHALL BE TRUE AND PLUMB BEFORE CONNECTIONS MAY BE FINALLY BOLTED ORWELDED.
S11 NOTE SPECIFICATION REQUIREMENTS FOR SPECIAL INSPECTION OF STRUCTURAL STEEL.
STEEL DECK
SD1 STEEL DECK SHALL BE DESIGNED, FURNISHED, FABRICATED, AND ERECTED IN ACCORDANCE WITH THE FOLLOWING STANDARDS: AISI “SPECIFICATIONSFOR THE DESIGN OF LIGHT GAGE, COLD-FORMED STRUCTURAL STEEL MEMBERS,” AND STEEL DECK INSTITUTE SPECIFICATIONS, DESIGN OF LIGHTGAGE, COLD-FORMED STRUCTURAL STEEL MEMBERS.”
SD2 STEEL DECK SHALL BE FABRICATED FROM SHEET STEEL MEETING THE REQUIREMENTS OF ASTM A653, STRUCTURAL STEEL, GRADE 33, HAVING A MINIMUMG60 GALVANIZED COATING, UNLESS NOTED OTHERWISE.
SD3 PROVIDE STEEL DECK OF THE DEPTH, PROFILE, AND THICKNESS AS INDICATED.
SD4 PROVIDE PREMOLDED RUBBER CLOSURE AND FINISH STRIPS AT PERIMETER OF ROOF DECK AND OPENINGS, ATTACHED DIRECTLY TO THE STEEL DECK TOPROVIDE A FINISHED SURFACE FOR THE APPLICATION OF INSULATION AND ROOFING.
SD5 INSTALL DECK PANELS AND ACCESSORIES ACCORDING TO APPLICABLE SPECIFICATIONS AND COMMENTARY IN SDI PUBLICATION NO. 30,MANUFACTURER'S WRITTEN INSTRUCTIONS AND REQUIREMENTS OF THE SPECIFICATIONS.
SD6 INSTALL DECK ENDS OVER SUPPORTING FRAMING WITH A MINMUM END BEARING OF 1-1/2”. END JOINTS MAY BE BUTTED OR LAPPED 2” MINIMUM AT THECONTRACTOR'S OPTION. STAGGER ADJACENT STEEL DECK END JOINTS.
SD7 INSTALL STEEL DECK OVER A MINIMUM OF 3-SPANS IN THE DIRECTION INDICATED. SINGLE SPAN CONDITIONS ARE NOT PERMITTED UNLESS SPECIFICALLYINDICATED. WHERE INDICATED, SINGLE SPAN DECK SHALL BE ADEQUATELY SHORED DURING CONSTRUCTION.
SD8 FASTEN STEEL DECK PANELS TO SUPPORTING FRAMING WITH ARC SPOT (PUDDLE) WELDS INDICATED BELOW, FASTENED THROUGH THREESHEET-THICKNESSES MINIMUM:
ROOF DECK: 5/8” DIA. - 36 / 4 PATTERN
SD9 FASTEN STEEL DECK SIDE LAPS AS FOLLOWS:
ROOF DECK: #10 TEK SCREWS AT 12” O.C. MAXIMUM
SD10 WELDING SHALL BE PERFORMED BY CERTIFIED WELDERS USING PRE-QUALIFIED METHODS, SUBMIT DOCUMENTATION. MECHANICAL FASTENERS MAY BESUBSTITUTED FOR WELDS IF INFORMATION IS PROVIDED TO THE ARCHITECT DEMONSTRATING EQUIVALENT DIAPHRAGM STRENGTH AND STIFFNESS.
SD11 LOADS SUSPENDED FROM STEEL ROOF DECK SHALL NOT EXCEED 50 POUNDS. LOADS SUSPENDED FROM COMPOSITE STEEL DECK SHALL NOT EXCEED400 POUNDS IN ANY 40 SQUARE-FOOT AREA.
SD12 SUPPORT ALL DUCTWORK, PIPING, CONDUIT SUPPLEMENTAL FRAMING, AND TOEHR LARGE LOADS DIRECTLY FROM STRUCTURAL STEEL FRAMING.
SD13 NOTE SPECIFICATION REQUIREMENTS FOR SPECIAL INSPECTION OF STEEL DECK.
MISCELLANEOUS
M1 CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS ON THE JOB. REPORT DISCREPANCIES TO THE ARCHITECT IMMEDIATELY. VERIFICATIONOF EXISTING DIMENSIONS AND CONDITIONS SHALL BE DONE PRIOR TO THE PREPARATION OF SHOP DRAWINGS.
M2 REFER TO THE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR VERIFICATION OF LOCATIONS AND DIMENSIONS OF CHASES, INSERTS,OPENINGS, SLEEVES, WASHES, REVEALS, DEPRESSIONS AND OTHER PROJECT REQUIREMENTS.
M3 TYPICAL DETAILS SHALL APPLY TO ALL DRAWINGS AND SHALL BE USED EXCEPT WHERE OTHERWISE SHOWN OR NOTED.
M4 WORK SHALL CONFORM TO THE LATEST EDITIONS OF THE BUILDING CODE OF NEW YORK STATE, THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION(AISC) STANDARD SPECIFICATION, THE AMERICAN CONCRETE INSTITUTE (ACI) BUILDING CODE, THE AMERICAN WELDING SOCIETY (AWS) CODE AND ALLAPPLICABLE ASTM STANDARDS. IN CASES OF CONFLICT, THE MOST STRINGENT SHALL GOVERN.
M5 REPRODUCTION OF ARCHITECT'S DRAWINGS SHALL NOT BE USED AS SHOP DRAWINGS OR ERECTION DRAWINGS.
M6 THIS PROJECT REQURIES STRUCTURAL TESTS AND SPECIAL INSPECTIONS AS DEFINED IN CHAPTER 17 OF THE 2010 BUILDING CODE OF NEW YORK STATE.IT IS THE CONTRACTOR'S RESPONSIBILITY TO BECOME FAMILIAR WITH THE STATEMENT OF SPECIAL INSPECTIONS, SUBMIT ALL REQUIREDDOCUMENTATION, AND ALLOW THE OWNER'S TESTING AND INSPECTION AGENCY ACCESS TO PERFORM ALL REQUIRED TESTS AND INSPECTIONS. AS PARTOF THIS PROGRAM, THE CONTRACTOR SHALL ALSO SUBMIT A COPY OF THEIR QUALITY CONTROL PROCEDURES AND CONTACT INFORMATION FOR ALLPERSONNEL RESPONSIBLE FOR EXECUTION OF SAME.
M7 REFER TO DRAWING G-001 FOR ADDITIONAL NOTES AND PROJECT REQUIREMENTS.
GENERAL STRUCTURAL NOTES STRUCTURAL DESIGN LOADS & PARAMETERSBCNY SECTION 1603: CONSTRUCTION DOCUMENTS ELECTRICAL ROOM ADDITION
MINIMUM SPLICE LENGTH
41"
33"
49'
81"
71"
TOP BARS
113"
102"
91"
SIZE
5
4
6
8
7
BAR
11
10
9
31"
37"
62"
70"
54"
25"
f'c = 4,000 PSI F'y = 60,000 PSI
BOTTOM BARS
87"
78"
REINF. LAP SPLICE SCHEDULES
MINIMUM SPLICE LENGTH
38"
31"
46"
76"
67"
TOP BARS
107"
96"
86"
SIZE
5
4
6
8
7
BAR
11
10
9
30"
35"
59"
66"
51"
24"
f'c = 4,500 PSI F'y = 60,000 PSI
BOTTOM BARS
82"
74"
TYP. WALL JOINTSN.T.S.
N.T.S.
ADD # 5 x 4'-0 EACH
FACE, AT EACH CORNER
OF OPENING (TYP.)
ADD 1/2 THE NUMBER OF BARS
INTERRUPTED BY THE OPENING
PLUS ONE ADDITIONAL BAR, EACH
SIDE OF OPENING AT 3" O.C.
NOTE: ROUND OPENING SIMILAR
TENSION DEVELOPMENT
LENGTH (TYP)
OPENING IN SLAB OR WALLN.T.S.
TYPICAL UNFRAMED
OPEN
LAP PER
SPLICE
SCHEDULE
2" M
IN.
CO
VE
R (
TY
P. )
CORNER BARS TO MATCH SIZE
AND SPACING OF HORIZONTAL
REINFORCING OR BEND
HORIZONTAL REINFORCING
HORIZONTAL WALL
REINFORCING
LAP PER
SPLICE
SCHEDULE
LAP
PE
R
SP
LIC
E
SC
HE
DU
LE
LAP PER
SPLICE SCHEDULE
OR CONTINUOUS
3/8" TAPERED JOINT
WITH SEALANT
T / 6
WA
LL "
T"
T /
3T
/ 3
CONSTRUCTION JOINT
( EXTERIOR )
T /
3
CONTROL JOINT
1'-0" 1'-0"
6"
1" (TYP.)1"
EQ. EQ.
1" MIN.
1/4
GROUT C.M.U.
SOLID
TYP. BEAM BEARING ON MASONRY WALLN.T.S.
TYP. BEARING PL 3/4"x 8"x 5"
(UNLESS NOTED ON PLAN)
(2) 34" DIA. x 6" LONG
HEADED STUDS
FLANGE WIDTHGROUT
SOLID
L4 x 4 x 3/8 x 4"
EACH SIDE OF
BEAM WEB
2'-0
"
3/4" MIN. NON-SHRINK GROUT
TYP. INTERIOR CONC. PADN.T.S.
VARIES
4" ±
NOTES:
1. REFER TO ARCHITECTURAL, MECHANICAL, AND ELECTRICAL
DRAWINGS FOR HOUSEKEEPING PAD SIZE AND LAYOUT.
2. WHERE PAD ABUTTS WALL, ELIMINATE CHAMFER AND
PROVIDE FULL DEPTH 12" ISOLATION JOINT.
ROUGHEN CONCRETE
SURFACE BETWEEN
CONCRETE PLACEMENTS
# 4 WITH STD. HOOK
@ 16" O.C. ALONG PERIMETER
DRILL & EPOXY GROUT INTO SLAB
TYPICAL SLAB ON GRADE
CONSTRUCTION (SEE S100)
4" MIN.
1 LAYER 6 x 6 - 2.9 x 2.9 WWF
CENTERED
TYP. SLAB-ON-GRADE JOINTSN.T.S.
1/8"
T /
5
T
REINFORCING TO BE
CONTINUOUS
SAW CUT WITH SEALANT
SAW-CUT CONTROL JOINT ( S.J. )
GROUT SOLID
( MORTAR NOT
PERMITTED )
EXTEND VERTICAL REINF.
THRU BOND BEAM
INTEGRATION OF MAX. 2"
DIA. VERTICAL ELECTRICAL
CONDUITS PERMITTED
UNLESS OTHERWISE
NOTED
CONTINUOUS HORIZ.
REINFORCING
PER PLANS - 12" SPLICE
TO BE LOCATED AT
CONTROL JOINTS
CONTINUOUS VERTICAL
REINFORCEMENT PER PLAN40 DIA. LAP
(TYP.)
40 D
IA. L
AP
(TY
P.)
REINFORCEMENT PER PLAN
PLAN (INTERSECTIONS) PLAN (CORNERS)
NOTE:
REFER TO PLAN & TYPICAL
DETAILS FOR CONTROL JOINTS
FULL HEIGHT SOLID
GROUTED CELLS AT ALL
VERT. REINF. (TYP.)
CMU PER PLAN
SECTION
BOND BEAM REINFORCINGN.T.S.
TYPICAL MASONRY
1" CHAMFER AT
EXPOSED EDGES
(TYP.)
CONTROL JOINTN.T.S.
PLAN VIEW
BACKER ROD AND SEALANT
STOP HORIZONTAL WALL
REINFORCING AT CONTROL JOINT
PREFORMED TEE
SASH BLOCK
TYPICAL CMU
COMPRESSIBLE
JOINT FILLER
12" CONTROL JOINT (CJ)
STOP HORIZONTAL WALL
REINFORCEMENT AT
CONTROL JOINT (TYP.)
1. REFER TO PLAN FOR CMU CONTROL JOINT LOCATIONS.
2. LOCATE 24 FT. ON CENTER MAXIMUM SPACING AT ALL
INTERIOR AND EXTERIOR WALLS UNLESS INDICATED
OTHERWISE ON PLANS AND DETAILS.
3. EXACT LOCATIONS SHALL BE APPROVED BY ARCHITECT.
AT CONTROL JOINTN.T.S.
TYP. CMU BOND BEAM
1. RAKE OUT CONTROL JOINT TO INSURE THERE IS NO CONTAMINATION
FROM MORTAR OR DEBRIS.
2. REFER TO PLAN FOR CMU CONTROL JOINT LOCATIONS.
PLAN VIEW
(1) #5 VERTICAL AT EACH
SIDE OF CONTROL JOINTFULLY GROUTED
CMU BOND BEAM
(2) #5 SLEEVED DOWELS
THROUGH CONTROL JOINT
(LAP 24" MIN.)
PREFORMED TEE &
COMPRESSIBLE JOINT FILLER BACKER ROD AND SEALANT
REINFORCEMENT
PER PLAN (TYP.)
LINTEL
W8 x 15 + CONT. PL 12" x 712"
W12 PER PLAN
BEARING PL 1" x 6" x 4"
4"
1/4
1/4
1/4
LINTEL L1 SECTION 1" = 1'-0"
T/ STEEL - SEE PLAN
℄LINTEL & WALL
NOTE:
PROVIDE BEARING PLATES, 1/2" X 6" X 6" WITH (2) 3/4" DIA. x 6" LONG
HEADED STUDS, TYPICAL EACH END OF LINTEL.
20'-0
"
20'-0"6"
FACE OF EXIST.
FND. WALL
EXIST. CONC. FND.
WALL & FOOTING
8" WALL
2'-0" FTG.
ISOLATION JOINT
TYP.@ PERIMETER
SAWCUT CONTROL
JOINT (TYP.)
EXIST.
STAIRS
EXTERIOR FACE
OF WALL ABOVE2"±
1'-0"± EXIST. CONC.
FOUNDATION WALL
8"±
22'-1
1"±
FN
D.
1'-3"± EXIST.
FND. WALL
2'-2
"±
2"±
APPROX. LOCATION OF
EXIST. ELEC. EQUIPMENT -
REFER TO DEMO PLANS
1"±
6" SLAB ON GRADE
F.F.E. 0'-0"
-4'-6" V.I.F.
T/ WALL EL. +0'-3"
TYPICAL U.N.O.
T/ WALL EL. -0'-8"
5
A302
3
A302
1
A302
2
A302
1
A302
MATCH EXIST. BOT. OF FTG.
DO NOT UNDERMINE
11'-1034"±
10'-0
"± (
V.I.
F.)
EXTERIOR FACE
OF WALL ABOVE
S.J.
S.J
.
3'-0"± EXIST.
CONC. FOOTING
W12
x16
W12
x16
W12
x16
W12
x16
W12
x16
4"
4" 20'-0"
4" (4) EQ. SP @ 4'-6" = 18'-0"
20'-0
"
OUTSIDE FACE
OF EXIST. WALL
23'-0
"±
2'-4
"±8"
OUTSIDE FACE
OF EXIST. WALL
R
OUTSIDE FACE OF
WALL - SEE ARCH.
8" CMU (TYP.)
5
A3024
A302
1
A302
1
A302
T/ WALL EL.
+10'-11" (TYP.)
10 TYP.
S101
3/4" BRG. PL
(TYP. U.N.O.)
C.J. C.J.
C.J. C.J.
C.J.C.J.
C.J. C.J.
6'-4" M.O. 7'-0"
L1
11
S101
1/2" BRG. PL
(TYP. EA END)
1" BRG. PL
ATOP LINTEL
Consultants:
Signature & Seal:
WARNING: ALTERATIONS TO THISDOCUMENT NOT CONFORMING TOSECTION 7209.2 OR 69.5(B) STATEEDUCATION LAW, ARE PROHIBITED.NOT PUBLISHED. ALL RIGHTS RESERVED.
Project Number:
Sheet Title:
Sheet Number:
Date:
Project Status:
Drawing History:
Client:
Project:
Project Address:
# Date Description
P:\B
flo &
For
t Erie
Pbl
c B
ridge
Aut
h\18
023
Will
son
Bld
g M
ech
& E
lec
Upg
rade
s\D
raw
ings
\Str
uc\1
8023
_S10
1.dw
gT
uesd
ay, F
ebru
ary
05, 2
019
- 8:
33 P
M
1 PEACE BRIDGE PLAZA,BUFFALO, NEW YORK 14213
03/25/2019
18023
ISSUED FOR TENDER
BUFFALO & FORTERIE PUBLIC BRIDGEAUTHORITY
R.F. WILLSON MECH.AND ELEC. UPGRADES
WILLSON
BUILDING
ELECTRCAL ROOM
FOUNDATION, FRAMING
PLAN & DETAILS
FOUNDATION PLAN - ELECTRICAL ROOM 1/4" = 1'-0"
ROOF FRAMING PLAN - ELECTRICAL ROOM 1/4" = 1'-0"
FOUNDATION PLAN NOTES:
1. TOP OF SLAB ON GRADE 0'-0" TO MATCH EXISTING BUILDING FINISH FLOOR ELEVATION (FIELD VERIFY).
2. BOTTOM OF FOOTING TO BE ELEV. -4'-6"± FROM FINISH FLOOR ELEVATION 0'-0". MATCH NEW AND
EXISTING BOTTOM OF FOOTING ELEVATIONS - DO NOT UNDERMINE EXISTING BUILDING FOOTINGS.
3. TOP FOUNDATION WALL TO BE ELEV. +0'-3" FROM FIN. FLR. ELEV. 0'-0" UNLESS NOTED OTHERWISE.
4. FLOOR SLAB TO BE 6" THICK 4,000 PSI CONCRETE WITH #4 BARS AT 18" O.C. EACH WAY OVER VAPOR
RETARDER, 8" COMPACTED SUBBASE AND COMPACTED EXISTING SUBGRADE.
11. PROVIDE DOWELS FOR ALL VERTICAL REINFORCING. MATCH SIZE, QUANTITY, AND LOCATION.
12. FOR UNDERGROUND UTILITY LOCATIONS, SLEEVE LOCATIONS AND INVERTS, REFER TO CIVIL,
ARCHITECTURAL AND ELECTRICAL DRAWINGS.
13. SEE DRAWING S100 FOR GENERAL STRUCTURAL NOTES,, TYPICAL DETAILS, LOADS AND SCHEDULES.
14. DRAWING SYMBOLS:
BOTTOM OF FOOTING ELEVATION BELOW FINISH FLOOR.
DOOR DEPRESSION.
SLAB ON GRADE CONTROL JOINT.S.J.
0.000'
S101
1,2
FRAMING NOTES:
1. TYPICAL TOP OF STEEL TO BE ELEVATION +10'-1" FROM FINISH FLOOR ELEVATION 0'-0".
2. WALLS TO BE REINFORCED 8" CMU WITH #5 VERTICALS AT 48" O.C. AND (2) #5 HORIZONTAL IN SOLID GROUTED BOND BEAMS AT 48" O.C.
MAXIMUM. PROVIDE (1) ADDITIONAL VERTICAL BAR AT CORNERS, WITHIN 4" OF EACH SIDE OF OPENINGS AND WITHIN 8" OF WALL ENDS.
3. SEE DRAWING S100 FOR GENERAL STRUCTURAL NOTES, LOADS AND SCHEDULES.
4. REFER TO ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
5. DRAWINGS SYMBOLS:
INDICATES SPAN OF 1 12" X 20 GAUGE TYPE B STEEL ROOF DECK.
INDICATES MASONRY CONTROL JOINT. SEE DETAIL 7 & 8/ S101.
R
C.J.
MECHANICAL UNIT SUPPORTN.T.S. TYPICAL ON EXISTING STEEL ROOF DECK
EXISTING JOIST OR BEAM SPACING
( MAXIMUM 6'-0 )
1/4TYP.
1/4TYP.
NEW UNIT - REFER TO
MECHANICAL
ROOF UNIT CURB
EXISTING ROOF DECK
L 6 x 4 x 3/8 x 0'-4" ( LLV ) FIT
BETWEEN FLUTES OF
EXISTING ROOF DECK ( TYP. )
EXISTING ROOF JOIST OR
STEEL BEAM
CLIP L 3 x 3 x 5/16 x 0'-6"
( TYP. )
L 5 x 3 1/2 x 5/16 ( LLV ) WELDED
ANGLE FRAME ( TYP. )
PROVIDE L 5 x 3 1/2 x 5/16 AT
UNIT PERIMETER AND EACHSIDE OF ROOF
PENETRATIONS, COORDINATE
EXACT FRAME
REQUIREMENTS WITH UNIT
MANUFACTURER.
FLEX
CONNECTION
NEW ROOF
PENETRATION
NOTES:
1. REFER TO MECHANICAL DRAWINGS FOR
UNIT SIZE & LOCATIONS2. SUBMIT SHOP DRAWINGS TO ARCHITECT
FOR REVIEW PRIOR TO FABRICATION.
1/4TYP.
OPENING IN METAL ROOF DECKN.T.S.
TYP. REINFORCEMENT AT
6'-0
MA
X.
6'-0 MAX.
EXIST. STEEL ROOFBEAM OR ROOF JOIST
CLIP L5 x 3 1/2 x 5/16 x 0'-6" LONG
(LLV) TYP.
ANGLE FRAME - TYPICAL ON FOUR SIDES
UNLESS INDICATED OTHERWISE ON PLANL 5 x 3 1/2 x 5/16 ( LLV ) U.N.O.
NOTE: COORDINATE EXACT SIZE ANDLOCATION OF ALL OPENINGS WITH
MECHANICAL AND ARCHITECTURAL
DRAWINGS AND ACTUAL EQUIPMENT TO
BE USED
SPAN OF ROOF DECK
1/4TYP.
1'-11" OPENING MAX
EXIST. CONCRETE DECK OPENINGN.T.S.
EXIST CONCRETE
DECK VIF.
1/4" STEEL PLATE WITH MIN.
6" BEARING ALL SIDES. VIF
OPENING SIZE. PROVIDE14"Ø S.S. CONCRETESCREWS AT EA. CORNER,TYP.
EXIST. STEEL DECK OPENINGN.T.S.
EXIST MIN. L4 x 4 x 14 PERIMETERANGLE TO REMAIN (TYP.). **NOTIFY
ARCHITECT IF ANGLE IS LESS THAN
SHOWN.
EXIST STEEL DECK, VIF.
NEW 112" x 20 GAUGE TYPE B G60 GALV.
STEEL DECK (SPAN DECK IN SHORTDIRECTION) FASTEN TO ANGLE W/
HILTI X-ENP-19 POWDER ACTUATED
FASTNERS @ 12" O.C. (MIN. (2) PER
EDGE) ; FASTEN SIDE - LAPS W/ #10
SELF DRILLING SCREWS @ 18" OCMAX.
1'-11" TO 4'-0"
OPENING
1'-0"
OVERLAP
TYP. INFILL @
TYP. INFILL @
#10 SELF DRILLING
SCREWS @ 12" OC MAX.
EXIST MIN. L4 x 4 x 14 PERIMETERANGLE TO REMAIN (TYP.). **NOTIFY
ARCHITECT IF ANGLE IS LESS THAN
SHOWN.
NOTES:
1. FOR OPENINGS SMALLER THAN 2'-0" PROVIDE DETAIL SIM. 5/S102.
AT OPENING IN CONCRETE ROOF DECKN.T.S.
TYP. REINFORCEMENT
6'-0
MA
X.
EXIST. STEEL ROOFBEAM
ANGLE FRAME - TYPICAL ON
FOUR SIDES UNLESS
INDICATED OTHERWISE ON
PLAN L 5 x 3 1/2 x 5/16 ( LLV )U.N.O.
NOTE: COORDINATE EXACT SIZE AND
LOCATION OF ALL OPENINGS WITHMECHANICAL AND ARCHITECTURAL
DRAWINGS AND ACTUAL EQUIPMENT TO BE
USED
SPAN OF ROOF DECK
3/16TYP.
EXIST. STEEL
ROOF BEAM ANGLE FRAME - TYPICAL ON FOUR SIDESUNLESS INDICATED OTHERWISE ON PLAN
L 5 x 3 1/2 x 5/16 ( LLV ) U.N.O.
VERTICAL L 5 x 3 1/2 x 5/16
3/16TYP.
1/4TYP.
6
8 9
10
11 12
B
C
F
G
I
7
EX
IST
. W
12x1
4
16'-9"± 16'-734"± 10'-01
4"± 18'-1134"± 7'-01
4"±1'-01
4"±
(TYP.)
16'-9"± 6'-714"± 10'-11
4"±
712"±
9'-1112"± 15'-01
2"± 10'-1112"±
6 107
1'-014"±
6'-1
01 2"±91
4"±
5'-3"±
A
D
E
H
J
11'-1
1"±
11'-4
3 4"±
3'-3
"±6'
-111 2"
±9'
-2"±
2'-4
1 2"±
3'-0
"±5'
-1"±
13'-1
1"±
16'-0
"±
10'-2"±10'-512"±11'-31
2"±
2'-134"±
10'-512"±
21'-714"±
54321
29'-1114"±
2 54
5'-0"*
3'-1
01 2"±
14'-0
"*3'
-101 2"
±
5'-6"±
*RTU-1
3653 LBS
EXIST. W14x22
EXIST. W14x22
EX
IST
. W
12x1
4APPROX.OUTLINE
OF RTU (TYP.)
UNIT SUPPORT
SEE 2/S102 (SIM.)
EX
IST
. W
12x1
4
EXIST. W8x10
OUTRIGGER
BEAM (TYP.)
(+8'-7 34"±)
EX
IST
. W
12x1
9
EX
IST
. W
12x1
4
EX
IST
. W
12x1
9
EX
IST
. W
12x1
9
EX
IST
. W
12x1
9
EX
IST
. W
12x1
9
EX
IST
. W
12x1
4
EX
IST
. W
12x1
9
EX
IST
. W
12x1
4
EX
IST
. W
12x1
4
EX
IST
. W
12x1
6
EX
IST
. W
12x1
6
EX
IST
. W
12x1
6
EX
IST
. W
12x1
6
EX
IST
. W
12x1
6
EX
IST
. W
12x1
6
EX
IST
. W
12x1
6
EX
IST
. W
12x1
6
EXIST. W14x22
EXIST. W14x22
L 4"
x 3
" x
1 4" L
LV.
EXIST.
W8x10
EXIST.
W8x10
L 5"
x 3
1 2" x
5 16"
LLV
. CO
NT
.EXIST. W14x30
EX
IST
. W
12x1
4
EX
IST
. W
12x1
4
EX
IST
. W
12x1
4
EX
IST
. W
12x1
4
EX
IST
. W
12x1
6
EX
IST
. W
10x1
2
EX
IST
. W
10x1
2
EX
IST
. W
10x1
2
EX
IST
. W
10x1
2
EX
IST
. W
10x1
2
EX
IST
. W
10x1
2
EXIST. W12x16
EXIST. W14x53 (+8'-5 34"± LEVEL)
EX
IST
. 10
B15
EX
IST
. 10
B15
EXIST. 14WF34
EX
IST
. 10
B17
L 5"
x 3
1 2" x
5 16"
LLV
. CO
NT
.
EX
IST
. 10
B17
EX
IST
. 12
WF
31
EX
IST
. 10
B15
EXIST.
14WF34
EXIST.
10B15
EXIST.
12W
F27
EXIST.
12W
F27
EXIST.
12W
F27
EXIST.
12W
F27
EXIST.
12W
F27
EXIST.
12W
F27
EXIST.
12W
F27
EXIST.
12W
F27
EXIST.
12W
F27
EXIST.
12W
F27
EXIST.
10W
F21
EXIST.
10W
F21
EXIST.
8BL1
5
EXIST.
8BL1
5
EXIST.
8BL1
3
EXIST.
8BL1
3
EXIST.
8BL1
3
EX
IST
. 10
B15
HIGH ROOF
LOW ROOF
EDGE OF
HIGH ROOF
EXISTING 58" DIA. SAGRODS (DO NOT
DISTURB)
SEE TYP. REINFORCING FOR
OPENING IN CONCRETE DECK(TYP.) DETAIL 3/S102
EXIST. 1 12"METAL ROOFDECK
EXIST. 2"
CONCRETE
PLANK ROOFDECK
(+8'-7 34"±) LEVEL
(+8'-5 34"±)
4 BMS
L 4"
x 3
" x
1 4" L
LV.
EX
IST
. W
12x1
4 (+8'
-7 3 4"
±)
L 5" x 3 12" x 516" ANGLE
SUPPORT AT 4'-0" O.C.
(MAX).
EXIST.
8BL1
3
EXIST. C6x8.2
EXIST. C6x8.2
(+8'-7 34"±) LEVEL (+8'-7 34"±) LEVEL
(+8'-7 34"±) LEVEL
(+8'-7 34"±) LEVEL
(+8'
-7 3 4"
±)
(+8'
-7 3 4"
±)
(+8'-5 34"±)
4 BMS
(+8'-5 34"±)
4 BMS
(+8'
-7 3 4"
±)
(+8'
-7 3 4"
±)
(+8'
-7 3 4"
±)
10'-5
1 2"±
21'-9
"±22
'-0"±
13'-2
1 2"±
23'-3
3 4"±
EXIST. 10B15
SEE TYP. REINFORCING FOR
OPENING IN METAL DECK (TYP.)DETAIL 4/S102
EF-1
Consultants:
Signature & Seal:
WARNING: ALTERATIONS TO THISDOCUMENT NOT CONFORMING TOSECTION 7209.2 OR 69.5(B) STATEEDUCATION LAW, ARE PROHIBITED.NOT PUBLISHED. ALL RIGHTS RESERVED.
Project Number:
Sheet Title:
Sheet Number:
Date:
Project Status:
Drawing History:
Client:
Project:
Project Address:
# Date Description
P:\B
flo &
For
t Erie
Pbl
c B
ridge
Aut
h\18
023
Will
son
Bld
g M
ech
& E
lec
Upg
rade
s\D
raw
ings
\Str
uc\1
8023
_S10
2.dw
gM
onda
y, N
ovem
ber
05, 2
018
- 10
:11
AM
1 PEACE BRIDGE PLAZA,BUFFALO, NEW YORK 14213
03/25/2019
18023
ISSUED FOR TENDER
BUFFALO & FORTERIE PUBLIC BRIDGEAUTHORITY
R.F. WILLSON MECH.AND ELEC. UPGRADES
WILLSON
BUILDING
ROOF MECH. UNIT
FRAMING PLAN AND
DETAILS
PARTIAL ROOF FRAMING PLAN1/8" = 1'-0"
S102
1
STRUCTURAL DESIGN LOADS & PARAMETERSBCNYS SECTION 1603: CONSTRUCTION DOCUMENTS
GOVERNING BUILDING CODES 2015 INTERNATIONAL BUILDING CODE
2017 NEW YORK STATE UNIFORM CODE SUPPLEMENT
BUILDING RISK CATEGORY IV
DESIGN SOIL BEARING CAPACITY "ASSUMED" 1500 PSF
FLOOR LIVE LOADS
OFFICE 50 PSF
CORRIDORS 100 PSF
BOILER ROOM 100 PSF
CHILLER ROOM 85 PSF
ROOF LIVE LOAD
ROOF CONSTRUCTION LOAD 20 PSF
COLLATERAL LOADS
MECHANICAL, ELECTRICAL, PLUMBING ALLOWANCE 5 PSF
SUSPENDED CEILINGS 3 PSF
SNOW LOAD
GROUND SNOW LOAD, Pg 50 PSF
SNOW LOAD IMPORTANCE FACTOR, Is 1.2
SNOW EXPOSURE FACTOR, Ce 0.9
THERMAL FACTOR, Ct 1.0
FLAT ROOF SNOW LOAD, Pf 37.8 PSF
SNOW DRIFT SURCHARGE, Pd 103 PSF
SNOW DRIFT WIDTH, W 20 FT
WIND LOAD
ULTIMATE DESIGN WIND SPEED, VULT 120 MPH
NOMINAL DESIGN WIND SPEED, VASD 93 MPH
WIND EXPOSURE D
INTERNAL PRESSURE COEFFICIENT, GCpi
+/- 0.55
COMPONENTS AND CLADDING
MAXIMUM WIND PRESSURE - PSF (BASED ON AN EFFECTIVE AREA OF 10 SQ. FT.)
WALLS - INTERIOR ZONE / END ZONE 54.4, -57.9 / 54.4, -68.4
ROOF - INTERIOR ZONE / END ZONE / CORNER ZONE 29.8, -57.9 / 29.8, -75.5 / 29.8, -110.5
ROOF OVERHANG - INTERIOR ZONE / END ZONE / CORNER ZONE -79.0 / -79.0 / -117.6
NOTES:
1. POSITIVE AND NEGATIVE NUMBERS INDICATE FORCES/PRESSURES ACTING TOWARD AND AWAY FROM THE SURFACES RESPECTIVELY.
2. WIDTH OF END AND CORNER ZONES SHALL EXTEND FROM DEFINED BUILDING CORNERS A DISTANCE IS EQUAL TO 2 TIMES THE LESSER OF
10% OF THE LEAST HORIZONTAL DIMENSION OR 0.4 x MEAN ROOF HEIGHT, BUT SHALL NOT BE LESS TAKEN THAN THE LESSER OF 4% OF THE
LEAST HORIZONTAL DIMENSION OR 3 FEET.
3. DELEGATED DESIGN ELEMENTS - FOR EFFECTIVE AREAS GREATER THAN 10 SQ. FT., THE DELEGATED-DESIGN ENGINEER SHALL CONSULT
ASCE 7-10 TO DETERMINE DESIGN WIND PRESSURES BASED ON THE WIND LOAD DESIGN CRITERIA PROVIDED. FOR EFFECTIVE AREAS 10 SQ.
FT. OR LESS USE THE APPROPRIATE DESIGN WIND PRESSURE INDICATED.
SEISMIC LOAD
SEISMIC IMPORTANCE FACTOR, IE 1.25
SITE SOIL CLASSIFICATION D (ASSUMED)
MAPPED SHORT PERIOD SPECTRAL ACCELERATION, SS 0.209 g
MAPPED ONE SECOND PERIOD SPECTRAL ACCELERATION, S1 0.060 g
SHORT PERIOD SPECTRAL DESIGN ACCELERATION, SDS 0.223 g
ONE SECOND PERIOD SPECTRAL DESIGN ACCELERATION, SD1 0.096 g
SEISMIC DESIGN CATEGORY C
SYSTEMS AND COMPONENTS REQUIRING SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE (2015 IBC, CHAPTER 17)
1. ANCHORAGE OF ELECTRICAL EQUIPMENT FOR EMERGENCY AND/OR STANDBY POWER SYSTEMS.
2. INSTALLATION AND ANCHORAGE OF VIBRATION ISOLATION SYSTEMS.
SYSTEMS AND COMPONENTS REQUIRING STRUCTURAL TESTING FOR SEISMIC RESISTANCE (2015 IBC, CHAPTER 17)
1. ANCHORAGE OF ELECTRICAL EQUIPMENT FOR EMERGENCY AND/OR STANDBY POWER SYSTEMS.
2. INSTALLATION AND ANCHORAGE OF VIBRATION ISOLATION SYSTEMS.
3. ANY OTHER MECHANICAL, ELECTRICAL, OR PLUMBING SYSTEM ASSIGNED WITH A COMPONENT IMPORTANCE FACTOR, IP, OF 1.5.
ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING COMPONENTS REQUIRING SEISMIC BRACING (ASCE 7-10, CHAPTER 13)
ARCHITECTURAL COMPONENTS
IMPORTANCE FACTOR, IP = 1.0 REQUIRED
IMPORTANCE FACTOR, IP = 1.5 REQUIRED
M/E/P COMPONENTS
IMPORTANCE FACTOR, IP = 1.0 EXEMPT
IMPORTANCE FACTOR, IP = 1.5 REQUIRED
ROOF FRAMING NOTES:
1. EXISTING STEEL ELEVATION +14'-11 34" (V.I.F.) IS TYPICAL TOP OF STEEL/ JOIST BEARING ABOVE EXISTING FINISHFIRST FLOOR ELEVATION 0'-0" UNLESS NOTED OTHERWISE AS (+/-) FROM TYPICAL TOP OF STEEL ELEVATION.
2. SEE DRAWING S100 FOR GENERAL STRUCTURAL NOTES, LOADS AND SCHEDULES.
3. SEE MECHANICAL AND ARCHITECTURAL DRAWINGS FOR LOCATIONS OF ALL ROOF OPENINGS & ADDITIONALINFORMATION.
* NOTES:
1) FIELD VERIFY EXISTING DIMENSIONS.
COORDINATE EXACT SIZE AND LOCATION OF
FRAMING WITH ARCHITECTURAL DRAWINGS,
MECHANICAL DRAWINGS, AND ACTUAL
EQUIPMENT TO BE INSTALLED.
2) ACTUAL RTU EQUIPMENT & CURB INSTALLED
SHALL NOT EXCEED THE WEIGHTS OR DIFFER
IN DIMENSION BY MORE THAN 6 INCHES AS
INDICATED ON PLAN. COORDINATE WITH
ARCHITECT/ENGINEER IF EITHER OF THESE
ARE NOT MET & SUPPLY THE ACTUAL
EQUIPMENT INFORMATION FOR REVIEW.
DIFFERING FROM INFORMATION ON
STRUCTURAL DRAWINGS MAY RESULT IN A
STRUCTURAL REDESIGN AND/OR ADDITIONAL
STRUCTURAL REINFORCING.