Page 1: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS
Page 2: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

2 Mariakani 400/220kV Substation

This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows:

I. CLARIFICATIONS

S.No. Clause/Paragraph/Item No. Clarification/Query Response

2 Bid data sheet (Commercial)

In the bid data sheet of Volume I, the name of the project is: Mombasa Nairobi Transmission Line Project, but the name of the bidding process is Construction of Mariakani 400/220kV Substation. Please clarify which one is the Contract Name required in the Form – Bank Guarantee

Project Name is Mombasa – Nairobi Transmission Project - 400/220kV Mariakani Substation

3 Volume 2 Appendix A (Drawings)

Kindly confirm the Appendix A – Bid drawings in Volume 2, the drawings should be provided but actually are not

Please refer to the attached Drawings listed below-: PB-KET-2012-D-223 Mariakani 220kV Single Line Diagram

PB-KET-2012-D-224 Mariakani 400kV Single Line Diagram

PB-KET-2012-L-234 Mariakani 220kV Layout

PB-KET-2012-L-235 Mariakani 220kV Elevations

PB-KET-2012-P-287 Mariakani 400/220kV Substation SCS Single Line Diagram

PB-KET-2012-P-288 Mariakani 400/220kV Substation LVAC Single Line Diagram

PB-KET-2012-P-289 Mariakani 400/220kV Substation 110V DC Single Line Diagram

PB-KET-2012-L-201 400kV Double Tension H/Ware fittings for Quad ACSR Lark

Conductor

PB-KET-2012-L-203 Tension clamp with Al encasing suitable for ACS Earthwire

(7/3.26)

Page 3: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

3 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response PB-KET-2012-L-205 Jumper Spacer for ACSR Lark Conductor (400kV)

PB-KET-2012-L-206 Single Suspension (Pilot) H/Ware fittings for Single ACSR Canary

Conductor (220kV)

PB-KET-2012-L-207 Quad Spacer Damper for ACSR Lark Conductor (400kV)

PB-KET-2012-L-208 400kV Pilot Suspension H/Ware fittings suitable for ACSR Quad

Lark Conductor

PB-KET-2012-L-209 Single Tension H/Ware fittings for Single ACSR Canary Conductor

(220kV)

PB-KET-2012-L-217 Double dead end set passing for OPGW cable diameter 19.6 –

20.6mm - 28110225 (F-0887)

PB-KET-2012-L-218 Single dead end set for OPGW cable diameter 19.6 – 20.6mm –

28110224 (F-0886)

PB-KET-2012-L-219 Tower Hinge for double tension hardware fittings suitable for

quad ACSR lark conductor (400kV)

6861162 Confirmed Outline Drawing (Shunt Reactor)

182AKPDE2006A Clearance diagram for Existing 220kV Tower- to be dismantled

182AKPDE2006A Clearance diagram for Existing 220kV Terminal Tower

182AKPDE40010 Clearance diagram for Existing 400kV Terminal Tower

SDH-1/2- Single Unit Staff Housing for senior staff (Annex 21.5 .1)

DDH-2/2- Double Unit Staff Housing for sub-ordinate staff (Annex 21.5.2)

Page 4: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

4 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response 1KHD636398 Sheet 504 Telecommunication System - System Layouts Legend

1KHD636398 Sheet 500 Telecommunication System – Western Region

1KHD636398 Sheet 501 Telecommunication System – Mount Kenya Region

1KHD636398 Sheet 502 Telecommunication System – Coastal Region

1KHD636398 Sheet 503 Telecommunication System – Nairobi Region

1KSE 000 535D410 Sheet 1 to 9 Block Diagram Network Manager

PB-KET-2012-D-233 Mariakani Overall Layout

PB-KET-2012-D-236 Mariakani 400kV Layout

PB-KET-2012-L-237 Mariakani 400kV Elevations

PB-KET-2012-P-280 Protection Single Line Diagram – Mariakani 400/220kV Substation 400kV Diameter 1

PB-KET-2012-P-281 Protection Single Line Diagram – Mariakani 400/220kV Substation 400kV Diameter 2

PB-KET-2012-P-282 Protection Single Line Diagram – Mariakani 400/220kV Substation 400kV Diameter 3

PB-KET-2012-P-283 Protection Single Line Diagram – Mariakani 400/220kV Substation 400kV Diameter 4

PB-KET-2012-P-284 Protection Single Line Diagram – Mariakani 400/220kV Substation 220kV Diameter 1

PB-KET-2012-P-285 Protection Single Line Diagram – Mariakani 400/220kV Substation 220kV Diameter 2

PB-KET-2012-P-286 Protection Single Line Diagram – Mariakani 400/220kV Substation 220kV Diameter 3

64161A-PBP-L-0016 Mariakani Substation Layout

Page 5: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

5 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

4 Pre-bid Schedule Approach to site: As per tender pre-bid meeting is scheduled on 3rd September, 2013 (10.00 hrs Kenyan standard time) at Nairobi and as per information received from your good office the project site i.e. Marikani is located about 400 KMs far from Nairobi city. So please inform the most suitable mode of transportation from Nairobi to Marikani site (by Air/ by Train / by Car) and the expected time to reach at the site. Will KETRACO be facilitating in arranging the local transportation?

Please refer to the Program Schedule

5 Pre-bid Schedule Programme for site visit- At what time the site visit will start? Will it be last till 3rd September only or also be extended up to 4th September. Please also provide the contact details of official/s who might be accompanying the bidder’s team for site visit. We would also like to request KETRACO to arrange a meeting with reputed local civil contractors/ Erection agencies/ Logistics agencies / vendors for local purchase, if any.

Please refer to Clarification no. 4 KETRACO shall not arrange any such meeting.

6 Pre-bid Schedule Also inform the hotels available in Nairobi City & near Marikani project site (in the range of USD 80-90 per day).

Please refer to Clarification no. 4

7

Volume 2 Appendix A (Drawings)

Please also arrange to send the tender drawings ( layout & single line diagram) as the same are not available with the tender documents uploaded

Please refer to Clarification no.3

Page 6: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

6 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

on site.

8 Section I, paragraph 4. Eligible Bidders, point 4.2 (Commercial) Section V – Eligible Countries; particulary section A, point 1.6 (Commercial)

Section I, paragraph 4. Eligible Bidders, point 4.2 A Bidder, and all parties constituting the Bidder, shall have the nationality of an eligible country, in accordance with the Bank’s Rules and Procedures for Procurement of Goods and Works, and as listed in Section V, Eligible Countries.8 A Bidder shall be deemed to have the nationality of a country if the Bidder is a citizen or is constituted, incorporated, or registered and operates in conformity with the provisions of the laws of that country. This criterion shall also apply to the determination of the nationality of proposed subcontractors or suppliers for any part of the Contract including Related Services. Section V – Eligible Countries; particulary section A, point 1.6 1.6 The African Development Fund permits firms and individuals from all countries to offer goods, works and services for ADF funded projects. However, the proceeds of any Financing undertaken in the operations of the African Development Bank and the Nigeria Trust Fund shall be used for procurement of goods and works, including the related services, provided by bidders from Eligible13 Countries.14 Any conditions for participation shall be limited to those that are essential to ensure the firm’s capability to fulfill the contract in question. In the

The African Development Fund permits firms and individuals from all countries to offer goods, works and services for ADF funded projects. For a list of debarred firms refer to: http://www.afdb.org/en/projects-and-operations/procurement/debarment-and-sanctions-procedures/

Page 7: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

7 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

case of ADB and NTF, bidders from non-Member Countries offering goods, works and related services (including transportation and insurance) are not eligible even if they offer these from Eligible Member Countries. Any waiver to this rule will be in accordance with the Articles 17(1) (d) of the Agreement Establishing the African Development Bank and 4.1 of the Agreement Establishing the Nigeria Trust Fund. From above mentioned it is not clear to

us if this tender is open to the bidders

from all countries, as this tender is

financed by the African Development

Fund and, as per section V, African

Development Fund permits firms and

individuals from all countries to offer

goods, works and services for ADF

funded projects or this tender is open

only to the bidders from the countries

that are members of the African

Development Bank.

Question: Please confirm that Croatia

is Eligible Country.

9 Volume 2 Appendix A (Drawings)

From Page 364 of Volume 2 Appendix A, it

mentioned “The following drawings are provided

with this bid document”. Pls refer the annex.

Please refer to Clarification no.3

Page 8: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

8 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

Volume 2 Appendix B (Drawings)

The problem is we can’t find the drawing in the

bid document, the same for the Appendix B

“Existing Telecommunications and OPGW

System”. Please advise if the diagrams are in the

hard copy?

10 Volume 2 Appendix A and Appendix B (Drawings)

Appendix A – Bid drawings & Appendix B- Existing

Telcom and OPGW are missing.

Please refer to Clarification no.3

11 Volume 2 Appendix A (Drawings)

We have noticed that the drawings “Appendix A”

of the Employer’s requirements are not included

in the package received. Could you please send

us the drawings so that our technical team can

start working promptly.

In addition, I would like to know the agenda of

the pre bid meeting. As the site is near Mombasa,

do you plan to have the site visit the same day ?

What is the organization ?

Please refer to Clarification no.3 Please refer to Clarification no. 4

12 Technical Specifications, Section 1.2.1 (Technical)

Tender Drawings and Scope of Works

From the Section 1.2.1 Mariakani 400/220kV

Substation in the Technical Specifications, it has

mentioned that the scope of work consists of six

partially equipped breaker-and-a-half scheme

diameters for the 400kV substation. However, in

the invitation to bid, mentioned scope of only

This has been corrected in this TAC Item 1.2.1 below

Page 9: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

9 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

Volume 2 Appendix A, Appendix B (Drawings)

four diameters. Kindly clarify the scope.

Furthermore, it is mentioned in Appendix A and B

a list of drawings related to the tender, however

these are not attached to the documents. We

kindly request these drawings to be provided to

give clarity to the scope.

Please refer to Clarification no. 3

13 Technical Specifications, (Technical)

Shunt Reactor Dimension Drawings

From the scope of works, it is mentioned that we

must install Line Shunt Reactors that are from the

Rabai SS to Mariakani SS. In order for us to

consider dimensions of foundations and space in

Mariakani, kindly provide us the “Dimensional

Drawings” of the existing Shunt Reactors which

shall show the physical dimensions and weight of

the reactor.

Furthermore, we would like to inquire if

transport of the Shunt Reactors from Rabai to

Mariakani shall also be part of this Tender Scope.

Please refer to Clarification no. 3 Shunt reactor transportation is part of the scope.

14 Technical Specifications / Technical Data Schedule (Technical)

Transformer Capacity Requirement

We notice as follows:

Invitation to bid shows – 200MVA Transformers

The 400/220kV autotransformers shall be 200MVA rated.

Page 10: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

10 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

Technical Specification shows – 200 MVA, 3-

phase Autotransformer or 66.6 MVA 1-phase

Transformer (1.3 of the overall MVA)

Technical Data Schedule shows – 500 MVA

Transformers

We kindly ask for a clarification on the required

rating of the Transformers.

15 Submission Date Extension (Commercial)

Tender Submission Extension

In view of the above questions, we find that the

submission date on the 11th October shall be tight

for us to meet and we will need more time for

preparation of a comprehensive bid. We kindly

ask for your consideration to extend the

submission date to four (4) weeks.

Please refer to TAC 1 Clarification no. 1

16 General

Bid drawings listed in Appendix -A is not received.

Please furnish the same.

Please refer to Clarification no. 3

17 Technical Specification for

substation & OHL Termination -

Section VI. Clause no: 1.2.1

The 220kV substation’s configuration is a

‘breaker-and –a –third’ however the numbers of

bays are not clear in scope, hence please provide

the requirement of 220kV system.

Please refer to Clarification no. 3

18

General

We presume that the switchyard equipments,

earthing, lightning protection, main bus bars,

lighting cable, AC & DC auxiliary system shall be

considered only for the present scope. We have

not considered for the same for the future scope.

Please refer to Pre-bid meeting minutes page 3 under comments by the Consultant (Allan Burns) paragraph 7. The 48V DC shall have 50% extra capacity for future (refer 9.4.3.1 of the Technical Specification) and the 110V DC shall have 30% extra capacity for future (refer 11.3.2.2 of the Technical Specification). The AC auxiliary system shall

Page 11: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

11 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

Please confirm. be constructed now for all future diameters (refer 11.1 of the Technical Specification). Also refer to this TAC Item 1.2.1 below

19 Technical Specification for

substation & OHL Termination -

Section VI. Clause no: 19

Technical specification indicates that the 11kV

cable connections need to be provided, however

the scope of 11kV cables are not clear, please

provide the same.

Please refer to this TAC Item 1.2.1. 11kV cable below. Requirements are left to the bidders discretion but shall conform to IEC Standards. Also refer to this TAC additional statement covering Item 21.1.1 below

20 Technical Specification for

substation & OHL Termination -

Section VI.

Existing Telecommunication system and OPGW

system drawings as listed in appendix- B is not

received. Please furnish the same.

Please refer to Clarification no. 3 drawings no.: 1KHD636398 Sheet 504; 1KHD636398 Sheet 500; 1KHD636398 Sheet 501;1KHD636398 Sheet 502; 1KHD636398 Sheet 503

21 General Please provide the soil resistivity of Mariakani SS. There is no soil investigations report. Refer to Site Visit Notes under Mariakani site visit to proposed substation site: paragraph 4

22 General Please provide the SAS architecture drawings. Please refer to Clarification no. 3

23 Technical Specification for

substation & OHL Termination -

Section VI.

Please clarify whether the DG sets shall be Indoor

type or outdoor type. Also please clarify whether

separate DG set room is to be provided.

Diesel generator set to meet the specification requirements in the

Technical Specification for substation & OHL Termination under

Clause 20. The Generator will be located in a separate building

complete with fire protection. The rating shall be, as a minimum

1MVA. The actual rating of the generator proposed by the bidder

shall ensure the generator is able to power the entire control building,

switchyard lighting and street lighting, and suitable for the ultimate

design of the Mariakani substation.

24 Technical Specification for

substation & OHL Termination -

Section VI. Clause no:20.

Please furnish the Current rating, ratio, class,

burden & number of cores for 400kV & 220kV

current transformer & capacitive voltage

transformer.

Please refer to Clarification no. 3 drawing no.: PB-KET-2012-P-280; PB-KET-2012-P-281; PB-KET-2012-P-282; PB-KET-2012-P-283; PB-KET-2012-P-284; PB-KET-2012-P-285; PB-KET-2012-P-286

25 Technical Specification for The rated current in the Technical data sheet is The 4000A and 2000A ratings are the ratings of the respective air

Page 12: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

12 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

substation & OHL Termination -

Section VI. Technical

schedules(General):-

Clause no: 1.10 & Clause no:1.9

indicated as 4000A for 400kV & 2000A for 220kV.

We presume that there are busbar rating. Please

confirm.

Also please furnish the equipment rating for

400kV & 220kV circuit breakers and

disconnectors.

insulated switchgear.

The respective air insulated equipment rating (including circuit

breakers) is stated with Section A. “1. General” of the Technical

Schedules.

26 Technical Specification for

substation & OHL Termination -

Section VI. Clause no:1.2.1 &

Technical schedule(Power

Transformer):- Clause no:1.20 &

1.21

The Power Transformer rating shown as 200MVA

in the clause no: 1.2.1 , whereas in Technical data

sheets(400/220kV Power transformer)the MVA

rating is shown as 500/√3 MVA/ 300/√3 MVA.

Hence please clarify& confirm the Transformer's

rating.

The IBT is required as a three phase unit with a MVA rating of 200MVA.

27 Technical Specification for

substation & OHL Termination -

Section VI. Clause no:21.5.1

Please furnish the Annexure 21.5.1& Annexure

21.5.2. for Staff housing .

Please refer to Clarification no. 3 drawings no.: SDH-1/2 (Annex 21.5 .1); DDH-2/2 (Annex 21.5.2).

28 Technical Specification for

substation & OHL Termination -

Section VI. Clause no: 22

As per specification ACSR Lark conductor is

specified for 400kV and ACSR Canery for 220kV

Transmission line. Please clarify whether can use

the same type of conductor for Substation also.

ACSR Lark conductor or ACSR Canery may be used for substation conductors provided the design meets clause 3.3.1 of the Technical Specification and the required rating of 4000A and 2000A for the 400kV and 220kV switchyards respectively.

29 Technical Specification for

substation & OHL Termination -

Section VI. Clause no: 8.2.1.1

Please confirm that whether the existing

Protection relay panel for reactor in Rabai SS can

be shifted to Mariakani.

The existing shunt reactor panel shall be decommissioned under this work scope with a new panel required within the Mariakani substation scope. Refer to Site Visit Notes under Rabai Site visit to view Shunt Reactor: paragraph 3.

30 Technical Specification for

substation & OHL Termination -

Section VI. Clause no: 21.5.2

Kindly provide the height of the store which is to

be provided.

The height of the store room shall be sufficient to accommodate all spares. As a minimum the store height shall be not less than 5m.

Page 13: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

13 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

Store

31 Technical Specification for

substation & OHL Termination -

Section VI. Clause no: 21.7.1

Topographical Survey and

details

Kindly provide the approximate distance between

the existing ground level and the proposed

finished ground level inorder to assess the depth

of foundation.

There is no topographic survey report. Bidders were taken to site and all topographic aspects shall be at the bidders risk.

32 General

Kindly provide the finished ground level for the

substations.

The Contractor shall design this based on ground conditions.

33 General

Kindly provide the out fall point for storm water

drains.

Refer to this TAC Additional Statement covering Item no. 21.17.12 below

34

General

Kindly clarify whether the substation shall be

made in multiple levels in case needed to reduce

the filling/cutting quantities.

NO. There will be no multiple levels.

35 General

Kindly provide the High Floor level for fixing the

Finished Ground Level.

Refer to Clarification No. 32

36

General Kindly provide the location for construction of

the staff housing units for the substation.

Housing location is at bidders’ discretion but shall be submitted for approval. It shall be within the Ketraco’s site boundary, not under the transmission line and not a hindrance to the construction or operation of the substation.

37 Technical Specification for

substation & OHL Termination -

Section VI.

Generator rating, capacity & type (with canopy or without canopy).

Refer to Clarification No. 23

Page 14: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

14 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

38

SLD & Electrical layout of proposed substation (Mariakani 400/220 kV substation)

Refer to Clarification No. 3

39

Details of civil drawings of control room building,

Koisk, Guard room & other required residential &

office accommodation

Floor area for the control room building and no. of rooms shall be designed by the contractor to meet the requirements of the Technical Specification based on three 400kV diameters, four IBT’s and three 220kV diameters and allow space for future panels. Civil design shall meet the Employer’s Requirements- other details at the discretion of the bidder. For the Layout Drawings of residential houses, refer to the attached Tender Drawing

40

Bid documents Appendix A & B provides for drawing list & existing telecommunication/ OPGW Systems & in clarifications it is stated that drawing shall be provided during pre-bid meeting. Please arrange to provide drawing and details along with soft copy.

Please refer to Clarification no. 3

41

In BOQ( Item No 8. Schedule-1), it provides for 220kv buried cable with accessories, but quantity shown as zero. Similarly item no 13 & 16 for 220 KV Line & 400 KV Line respectively, has been shown as zero. It is presumed that Zero items are not covered in the present scope of Supply. It need to be confirmed that all Zero items in BOQ are not covered in present scope & need not to quote by bidder.

For items 13.4, 13.5, 15.1, 16.4, 16.5 and 18.1 the Estimated Quantity should be one (1). For all other zero items, do not quote.

42

In the Schedule -4 of the BOQ for installation, item no 28 provides for installation of 220 KV Buried cable with accessories, but shown as zero. Item no 28.9 to 28.17, site clearance, leveling, soil

For items 35.4, 35.5, 37.1, 38.4, 38.5 and 40.1 the Estimated Quantity should be one (1). For all other zero items, do not quote.

Page 15: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

15 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

investigation/testing, survey, grading road crossing etc has been provided but quantity shown is zero. Site clearance. Similarly item no 35 &38 shown as zero. It need to be confirmed that all Zero items in BOQ in services , are not covered in present scope & need not to quote by bidder.

43

Item no 28.14 of Schedule -4 , Provides for trenches , excavation etc for existing services and shown as Zero. If is it considered as not in present scope as per above point, than please clarify, where is the provision for trenches for new substation in the BOQ, and provision for trenches for new substation need to be provided in the schedule-4

Refer to the updated price schedule within this TAC below. Trenches are stated within Section 30.45 of Schedule No.4.

44

Earthing type A, B, C for towers has been provided in BOQ, its details / drawing need to be provided.

Item 19 of Price Schedule No. 1. “Counterpoise Cable (220kV and

400kV Line)” is not required and shall be removed from the Price

Schedule No. 1.

Item 41 of Price Schedule No. 4. “Counterpoise Cable (220kV and 400kV Line)” is not required and shall be removed from the Price Schedule No. 4.

45

Tentative distance of IBT to Auxiliary –x- former may be provided.

To be based on the Bidder’s designs

46

Staff quarter/ store layout plan / drawing need to be provided; otherwise there will be ambiguity between bid submissions.

Refer to Clarification No.3 The store layout plan at Bidders discretion and also refer to Clarification S. No 30

Page 16: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

16 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

47

Please confirm, if valid type test report is available for main equipment I.e Transformers, Switch gears, is there is any requirement to re conduct the Type test at the time of Supply. In the technical specifications (volume-2), for most of equipment it is mentioned that type test need to be conducted, if such a case there is no provision / schedule for type test charges. This need confirmation / clarity

Type tests are required to meet the Employer’s Requirement. If a type test certificate is valid and meets Employer’s Requirements then no additional type test is required.

48

In outside trenches, trays are required or not on the cable racks. Same may also be confirmed for control room trenches also.

Refer to this TAC for addendum that updates Section 11 of the Technical Specification with 11.6 LV Cables, 11.7 Low Voltage Power Cables and 11.8 Inspection and Tests particular 11.7.3 for installation requirements below.

49

Volume -2 , para 4.2.2.1 provides for Gas handling & storage unit. Please provide clarification whether it is evacuation & gas filling device, or gas handling with storage unit.

Refer to volume 2 clause 4.2.2.1 and volume 1 Schedules item 12.9

50

The main Protection at Isinya 1 &2 , their make and type of protection details may be provided for matching with new substation protection.

The bidder to provide Main Protection 1 & 2 which meets Employer’s Requirements

51

It is stated houses to the KETRACO Staff to be fully furnished, with provision of AC, furnishing details need to be provided for room wise including AC.

Please refer to Clarification no.3

52 Substation / line towers need to be type tested or not.

Line tower type tests not required

Page 17: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

17 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

53

In the Bidding documents have two ICB No. One

on the cover of the tender documents is

KETRACO/PT/012/2013 and another in the BDS is

KETRACO/PT/012/2012. Please clarify it.

Correct ICB no is KETRACO/PT/012/2013

54

In the bidding documents ITB 13. The alternative

bids are not permitted, for technical bid, could we

provide two or three manufacture documents for

the same equipment with same technical

response in the parameter datasheet

The provision of three different manufacturers for the same equipment is not an alternative bid.

55 Please provide the outlet direction of substation Bidders were taken to site

56

Please clear the style of gantry and support struct

ures.

Gantry is lattice combined with angles, support is

lattice combined with angles or gantry is steel

tube pole, support is lattice combined with

angles.

The use of steel lattice or steel tube is at the bidders discretion (providing the Employer’s Requirements are met). To give a cost effective installation it is well known in the industry when to use steel lattice and when to use steel tube.

57

Whether the relocation of the reactor protection

devices? Please clarify it.

Could you provide the existing 400kV substation

control room panels and MK photos?

Refer to Clarification no. 29

58

Please provide the routing channel organization

between the new Mariakani substation and the

National Control Centre (NCC) and the Regional

Control Centre (RCC) respectively.

Please refer to Clarification no. 3

Page 18: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

18 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

59

Please provide the geographical position wiring

diagram of the substation related to this project,

so that the geographical position of the

substation and the wiring length between the

substations can be seen in it.

Please refer to Clarification no. 3

60

Please provide the communication network

operation situation and the channel diagram in

where the new substation located.

Please refer to Clarification no. 3

61

Please provide the topographic map of surveying

and mapping of substation position(1:500)

Refer to Clarification no. 31

62

Please provide the scope of land can be used in

this phase.

Refer to Clarification no. 3

63

Please Confirm flood stage of 100 years, and

water logging water level of the substation.

This is the bidders responsibility

64

Please confirm the source of domestic water and

fire control station water.

Refer to this TAC that updates clause 21.11 of the Technical Specification below

65

Please provide the local substation drainage

system.

This is the bidders responsibility

66

Please provide Construction drawings of Similar

substation. (Including general layout plan, layout

plan of drainage system, gantry installation

drawings and foundation construction drawings,

equipment support installation drawings and

foundation construction drawings, cable trench

construction drawings and control house

The Mariakani substation shall be built to meet the Employer’s Requirement.

Page 19: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

19 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

construction drawings).

67

In section II BDS, ITB 11.1(h), iii. Testing materials

and equipment in Type Test Reports shall have

the same code/ country / manufacturer and

technical parameters as offered materials and

equipment. Type tests of non-conforming

materials/equipment shall not be accepted. You

are pleased to clarify whether the test report of

the testing materials and equipment which are

high voltage or higher capacity than the offered

type can be accepted for bidding?

Type test is required for the specific equipment being installed.

68

In section VI, 1.5 Details of transmission line / HV

cable routes, The Contractor shall propose the

required modifications to the existing overhead

line to route the lines into and out of the new

Mariakani substation together with the

transmission line works required to

decommission and dismantle the existing 220kV

substation bypass. You are pleased to clarify

whether the line modification work will be done

by contractor

Section 22.1.1 of the Technical Specification states that the scope of

works includes for the provision of the overhead line entries into and

out of the substation.

Refer to Price Schedule No. 4 Item 43 for reusing disconnected conductors for rerouted connection into Mariakani substation.

69

In section II BDS, ITB16.2, The Bidder shall submit

with its bid, the Manufacturer’s Authorization for

the following part or component: 4. Composite

insulators 10. 220kV HV cable, We understand

that there is no transmission line work and 220kV

HV cable will be supplied in the contact. Whether

it will also provide the Manufacturer’s

Connection of 400kV and 220kV lines from the terminal towers to the substation is required in the scope. If the bidder’s design requires the use of 220kV cable then the Manufacturer’s Authorization for the cable would be required.

Page 20: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

20 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

Authorization form those manufacturer?

70

Section VI, TECHNICAL

SCHEDULES

In section VI, TECHNICAL SCHEDULES, M sub-

divisions 400kV OVERHEAD LINE and N sub-

divisions 220 kV OVERHEAD LINE, You are pleased

to clarify that these Technical Schedules will not

be filled up due to there is no scope of work.

The technical Schedules in Volume 2 of 2: Supplementary Information are require to be filled in. Where the contractor is not supplying equipment when reusing the existing conductor then the respective part of the Technical Schedule shall not be filled in.

71

In section VI, Appendix A – Bid Drawings

Appendix B – Existing Telecommunications and

OPGW System, We have not found these

drawings in the bid documentation. You are

pleased to provide these drawings.

Please refer to Clarification no.3

72

For Auto transformers, the capacity is 200MVA in BOQ, but it is 500/√3 in technical schedules, which parameter is right? If 200MVA is right, is there any change for other parameters in technical schedule?

Refer to Addendum for updated Technical data sheet included within this TAC below. The IBT is required as a three phase unit with a MVA rating of 200MVA.

73

There are two different tender no. references

KETRACO/PT/012/2013 and

KETRACO/PT/012/2012. We understand that the

tender no. is KETRACO/PT/012/2013. Please

confirm

The ICB No. is KETRACO/PT/012/2013

74

We have not found appendix-A & B in tender

specification. Please provide appendix-A & B.

Please refer to Clarification no.3

75

Please provide following drawings/documents.

1. Single Line Diagram of 400/220kV SS.

Please refer to Clarification no. 3 for No. 1,2,3 and 9. The rest are the bidders responsibility

Page 21: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

21 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

2. Layout and Section drawing. 3. Plot Plan 4. Contour map. 5. Soil Investigation report. 6. Soil resistivity report. 7. Route and details of existing transmission

line/tower. 8. Structure drawing of tower and

equipment. 9. Civil drawing of tower and equipment. 10. Drawing and finishing details of building. 11. FGL of 400/220kV Substation.

76

We are considering PVC pipe for interpole

cabling & cabling from equipment to trenches.

Please confirm.

This is acceptable practice providing it meets section 3.2.10 of the Technical Specification.

77

We are considering only space provision for

future bays only. Any work(supply, gravelling,

earthmat, foundation, tower etc) for future bays

is not in bidder’s scope.

Refer to Clarification no. 18

78

Please specify(HCB/HDB) the type of isolator. The disconnectors can be centre break or double break providing the design meets the requirements of Section 4.4.3. of the Technical Specification and the ultimate design’s spacing fits within the required layout area.

79 Please provide rating of Diesel Generator set. Refer to Clarification no. 23

80

Please specify type and rating of lumination for

indoor and outdoor illumination.

Lighting shall be suitable to meet the Employer’s requirements refer 21.18.1.2.

Page 22: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

22 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

81

Please provide following information for

earthmat design.

1. Soil resistivity 2. Type & Size of underground conductor. 3. Depth of earthmat. 4. Type & Size of conductor for equipment

earthing

Refer to the Technical Specifications clause 3.3.1

82

Please specify type of structure(Lattice/Pipe) for

equipments.

The use of steel lattice or steel tube is at the bidders discretion (providing the Employer’s Requirements are met).

83

We have not found any list of special tools

&equipment and spare part.

Please furnish following list.

1. Spare part list. 2. Maintenance tools & tackles. 3. Erection, Installation & commissioning

tools.

The Employer shall provide an Addendum for Schedule 1: Mandatory Spares

84

Confirm that level land shall be provided for

400/220kV Substation.

Please also provide FGL of Substation.

Refer to Clarification No. 32

85

We are considering only racks in outdoor

trenches of 400/220kV Substation and in control

room for LT cable support

Refer to this TAC Clause 11.6 LV Cables (below).

Page 23: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

23 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

86

Please provide specification of following

1. LT Power and control cable 2. Portable earthing equipment.

Refer to Clarification no. 85

87

Except main equipment BIS (Bureau of Indian

Standard) may be allowed. Please confirm.

NO. Only Internationally recognized standards can be used.

88

Please reduce the guarantee period form 5 year

to 2 year.

Refer to this TAC Item 1.22 below for updated guarantee period

89

Employer’s Requirements

Clause 2.11

Please specify thickness of zinc coating for

galvanizing on structure.

All equipment and design shall meet the standards as stated within

the Section 2.11 of the Technical Specification and suitable to meet

the local environment. The thickness of coating shall however be not

less than 610gm of zinc per square meter.

90

We shall submit only type test reports.

Conducting of any type test is not considered.

Also confirm that all type test, routine test and

site test shall be as per respective IEC.

Refer to Clarification No.47

91

Please provide details (Make and type) of shunt

reactor protection scheme for checking

compatibility.

The shunt reactor control and protection at Mariakani are new panels and shall be designed by the Contractor.

92 Please provide lead for surplus material. Refer to refer to clause 19.5.2 and 21.17.7.9

93

For 400kV pole discrepancy shall be

<3.3ms for closing and <3.3 ms for opening.

Refer to Technical Specification volume 2 of 2 clause 4.2.1

Page 24: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

24 Mariakani 400/220kV Substation

S.No. Clause/Paragraph/Item No. Clarification/Query Response

For 220kV pole discrepancy shall be

<5ms for closing and <3.3 ms for opening.

Please confirm.

Page 25: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

25 Mariakani 400/220kV Substation

The following Addendums to Procurement of Mariakani 400/220kV substation

document Volume 2 of 2 are as follows:

Item 1.22 Maintenance, shall be replaced with: “The contractor shall guarantee the

efficient and good working of the Plant under the Contract for a period of 2 years from

the date on which the Project Manager takes over the Plant in accordance with General

Conditions of Contract.”

Additional section to 1.15 Planning and Progress Reports as follows:

1.15.1 Joint Review Meeting

Following the issuing of the Contractor’s preliminary design there shall be a Joint Review meeting. This meeting will include the Contractor’s respective designers, KETRACO and the Consultant engineers.

The Joint review meeting shall be held within the Contractor’s office.

The Contractor shall arrange all transport and accommodation during the time of the joint review meeting for KETRACO’s staff and the Consultant’s engineers.

It is expected that 5 KETRACO engineers shall attend this meeting and 5 Consultant engineers.

The Contractor shall allow a period of 5 days for the joint review meeting and schedule this within the programme.

Item 1.2.1 Mariakani 400/220kV Substation fourth and fifth paragraph shall be

replaced with: The 400kV design is to comprise of six ‘breaker-and-a-half’ diameters.

Two fully equipped diameters will be fed from the Isinya 400kV double circuit

transmission line which is to be diverted into the substation and also connect to two

interbus transformers (IBT 4 and 3). A further two partially equipped diameters will

provide single circuit connections into the 220kV switchyard via 200MVA (IBT 2 and 1).

An 11kV cable connection will be provided from each IBT tertiary winding to each

auxiliary/ earthing transformer.

The proposed substation layout makes provision for future circuits. Two of which have

been identified by KETRACO as double future thermal power plant connections. The

substation design is also to incorporate space for the future double circuit feeders from

Markn Power Plant. The future bays shall be constructed as ‘Skeleton bays’, i.e. full

gantry structures but no electrical equipment (or associated electrical plant foundations)

except the following is required;

The overhead conductors, i.e. earth wire, bus 1 and 2 and the respective high

level transfer conductors

Earth wire

Earth grid

Drainage

Page 26: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

26 Mariakani 400/220kV Substation

Cable trenches

Levelled site complete with stone chip

Section VI, K 400/220kV Power Transformers (AIS-AIS) Clause 1.74, shall be

replaced with: “Maximum sound pressure level (NEMA TR1 – 5dB(A)) 83dB(A).”

Section III, Bid Data Sheet, the following shall be inserted: “ITB 12.1” “The choice of

currencies shall be as follows: Any freely convertible currency or combination of up to

three freely convertible currencies”

Additional statement covering item 21.17.12 shall read, “All drainage (excluding

waste water) from the substation shall meet section 21.17.12 of the Employer’s

Requirements in addition soak pits are to be constructed by the Contractor suitable to

meet all drainage needs from the substation.”

Additional statement covering item 21.11 shall read, “Local voltage connection at

11kV shall require cable connection (the cable route shall follow the road, allow 2km

cable route length) to be arranged and constructed by the Contractor. Local water

connection point is 2km distance, to be arranged and constructed by the Contractor.”

Additional statement covering item 21.17.15 PERMANENT ACCESS ROADS

Main Access Road from substation to Mombasa Road

Provide for the design and construction of a 2 Km access road. The road shall be of

permanent construction of concrete type, connecting the main road to the substation.

The road will be a 12m wide road with two lanes of 3.5m with shoulders of 1.5m and

provision for the drainage facilities.

The design is to be done in accordance with the Standard specifications for road and

bridge construction or any other acceptable equivalent design standard to the approval

of the Client. The road will also be designed suitable to transport all the anticipated

equipment to site and sufficient to accommodate a sufficient bending radii of 26m truck

and trailer rigs.

Access Roads within the Substation

The roads shall be of permanent construction of concrete type. The road shall be a 5m

wide road and provision for the drainage facilities as described in the Technical

Specifications. These roads include the access to the permanent housing.

The design is to be done in accordance with the Standard specifications for road and

bridge construction or any other acceptable equivalent design standard to the approval

of the Client.

Page 27: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

27 Mariakani 400/220kV Substation

Section VI, K 400/220kV Power Transformers items 1.1 to 1.24 replaced with

400/220kV POWER TRANSFORMERS (AIS-AIS)

UNIT DATA

Required Offered

1. POWER TRANSFORMER

1.1 Manufacturer & Place of manufacturing

1.2 Type designation

1.3 Type

Three-phase Autotransformer, oil-immersed, core type

with tertiary winding

Yes

1.4 Standards

IEC 60076, 60137,

60214

1.5 Altitude

m 216

1.6 Ambient temperature

- Maximum

- Annual average

oC

oC

40

30

1.7 Mounting

Outdoor

1.8 Rated voltage ratio

kV 400

220

11

1.9 Rated frequency

Hz 50

1.10 Vector group (3 phase group connection)

YNa0d11

1.11 Cooling – 2-stage

ONAN/ONAF1/ONAF

2 or

ONAN/ONAF/OFAF

1.12 Function of tertiary winding (TV)

Aux. supply

1.13 Method of earthing

- HV winding Solid

- LV winding Solid

- TV winding _

1.14 Type of windings (graded/non-graded)

- HV winding (Series) Graded

- LV winding (Common) Graded

- TV winding Non-graded

1.15 Rated voltage of windings (Ur)

- HV winding kV 400

- LV winding

- TV winding

Note*: approximate; to manufacturer’s preference

kV

kV

220

11

1.16 Highest voltage for equipment (Um)

Page 28: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

28 Mariakani 400/220kV Substation

400/220kV POWER TRANSFORMERS (AIS-AIS)

UNIT DATA

Required Offered

- HV winding kV 420

- LV winding kV 245

- TV winding kV 12

1.17 Rated lightning impulse withstand voltage at:

- HV terminal kV 1425

- LV terminal kV 1050

- Neutral terminal kV 170

- TV winding 75

1.18 Rated switching impulse voltage

- HV terminals

- LV terminals

kV

kV

1050

850

1.19 Rated power frequency withstand voltage at

- HV terminal (design value)

- HV test value (ACLD U1)

- HV test value (ACLD U2 PD measurement))

kV

kV

kV

630

436

388

- LV terminal (design value) kV 460

- Neutral terminal kV 70

- TV terminal kV 28

1.20 Rated power at site conditions (ONAF2 or OFAF), HV &

LV

MVA

200

1.21 Rated power at site conditions (ONAN)

MVA 120

1.22 Rated power of tertiary at site conditions (Full cooling)

MVA 70

1.23 Maximum temperature rise at rated power at:

- Windings

Marikani

K

55

- Hot spot of windings

Marikani

K

68

- Top oil

Marikani

K

50

- Oil at inlet of cooler K

- Oil at outlet of cooler K

- Core K

1.24 Temperature of winding due to short circuit duration of 2

s at rated load

- HV side short circuit rating of 31.5kA oC 250

- LV side short circuit rating of 31.5kA oC 250

The following items are to be added to the Volume 1, Pricing Schedules, Schedule

No 4, Civil Works

Page 29: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

29 Mariakani 400/220kV Substation

Item

No

Description Estimated

Quantity

Unit

30.34 Site survey 1 Lot

30.35 Site clearance and earth works 1 Lot

30.36 Temporary works 1 Lot

30.37 Grading and landscaping on completion 1 Lot

30.38 Surface chippings 1 Lot

30.39 Main Access Road from substation to

Mombasa Road

1 Lot

30.40 Access Roads within the Substation 1 Lot

30.41 Drainage system 1 Lot

30.42 Substation perimeter fence including

security

1 Lot

30.43 Substation gates 1 Lot

30.45 Cable trenching / ducts 1 Lot

30.46 Substation road lighting 1 Lot

30.47 Substation compound lighting 1 Lot

30.48 Substation gatehouse 1 Lot

30.49 Substation control / relay building 1 Lot

The following section shall be added to the Procurement documents volume 2 of

after section 11.5

Page 30: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

30 Mariakani 400/220kV Substation

11.6 LV CABLES

11.6.1 General

The LV Cable system installed in the substation shall be designed to support auxiliary power,

monitoring and control functions of the substation. The selection of materials, design and installation

shall ensure a high level of availability, minimise damage or disruption to other systems in the event of

a fault and minimise the risk to personnel. Wherever any part of an LV cable circuit is installed within

a room or enclosure containing electrical control or protection equipment or where personnel are

normally present cables employing insulation and sheathing which minimises the production of smoke

and toxic fumes shall be used. Cable installed wholly outdoors may be of a PVC insulated type.

11.6.2 Scope of Works

The supply and services to be performed by the Contractor shall comprise the design, manufacture,

shop testing, packing, transport, insurance, unloading, storage on Site, construction works and

erection, corrosion protection, site testing, submission of documentation, commissioning, and

warranty of the works.

The Contractor is bound to provide complete works, even if the equipment or services to be provided

are not specifically mentioned in the specification.

11.6.3 LV Power and Multicore Cables

The scope of supply shall include the following:

Power cables used for the connection between auxiliary supply system and consumers

such as motors, chargers, sub-distribution boards, local control cubicles,

protection panels, substation control systems, marshalling cubicles, equipment

cabinets and all other users directly fed from the switchgear shall be sized

according to the continuous site rating calculation. These calculations shall be

submitted for approval.

Power cables used for the connection between 500kVA or 315kVA, 11/0.415kV

auxiliary/earthing transformers and L.V.A.C. switchboard; between batteries,

chargers and DC Boards.

Multicore control cables for 110 V D.C. system,

Multicore (control, protection, measuring, alarm and indication) cables used for the

connection of various individual control boards or equipment cabinets to the

remote control panels, protection panels, substation control system, marshalling

cubicles, equipment and consumers, connection between the elements of control

cubicles, connection between telemetry marshalling cubicles and control cubicles

and all other connections.

Cable racks trays and fixing devices for all LV cables.

Cable terminating material for all LV cables.

Corrosion protection.

Page 31: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

31 Mariakani 400/220kV Substation

Special equipment, tools and spare parts shall be included as required for proper

maintenance.

11.6.4 Technical Data

Rated voltage 0.6/1 kV

Conductor material Copper

Core insulation Thermosetting or PVC

Protective sheath Galvanized steel-wire armoured and LSOH or PVC

over-sheath.

All parts of the cable installation shall comply with this Specification and the latest revisions of the

relevant IEC standards except where otherwise stated.

11.6.5 General Design Requirements

The low voltage power and multicore cables shall comply with these specifications and the

requirements of the latest revision of the following IEC Standards, except where otherwise stated:

IEC 60189-1/1986, IEC 60189-2/1981 and 60189-3/1988 "Low Frequency Cables and

Wires with PVC Insulation and Sheath".

IEC 60227 "PVC Insulated Cables on Rated Voltages up to and including 450/750 V.

IEC 60228 "Conductors of Insulated Cables".

IEC 60287 "Calculation of the continuous current rating of cables (100% load factor)".

IEC 60724 "Guide to the Short-Circuit Temperature Limits of Electric Cables with a Rated

Voltage Not Exceeding 0,6/1 kV".

IEC 60811 "Common Test Methods for Insulating and Sheathing Materials of Electric

Cables and Optical Cables ".

IEC 60885 "Electric Test Methods for Electric Cables ".

BS 6724 Specification for 600/1000 V and 1900/3300 V armoured electric cables having

thermosetting insulation and low emission of smoke and corrosive gases when affected

by fire

BS EN 50265 “Common Test Methods for Cables under Fire Conditions”

All cables shall be suitable for continuous operation under climatic conditions prevailing on site.

All transient and abnormal conditions, such as overload and short circuits shall be withstood without

detrimental effects.

The cables shall have copper conductor with either PVC insulation and PVC over sheath or

thermosetting insulation with LSOH characteristics as determined by the application.

Page 32: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

32 Mariakani 400/220kV Substation

The cables shall be identified at both terminations with stainless steel metallic ferrules engraved with

the reference number, the number and size of cores, the type of cable and the designation.

At those points of interconnection between the wiring carried out by separate contractors where a

change of number cannot be avoided double ferrules shall be provided on each wire. The change of

numbering shall be shown on the appropriate diagram of the equipment.

The Contractor shall provide a complete set of cable schedules listing all cables required for

connecting the equipment supplied under this Contract.

Cable schedules listing all cables and their points of termination including details of cable, number of

cores, core reference, core size, number of cores in use and cable length etc. shall be provided.

The Contractor shall ensure that the core identification at their terminals corresponds to the above-

mentioned schedule.

The cables shall be laid on trays in single layers in such a manner that they can be replaced or added

to without difficulty.

In general, the cables for double in-feeds from the switchgear, transformers, distribution boards and

cubicles shall be laid separately so that in the event of a short-circuit in one in-feed, the other is not

affected.

All AC and DC control and power circuits shall be segregated from one another and the circuits to

main protective gear shall be segregated from those for back up protection.

The cable sheaths must be resistant to solar radiation, the effect of oil, bacterial action, insects and

rodents. They must be suitable for laying indoors, outdoors, underground and in water.

All cables installed in concrete troughs within the substation shall have anti-termite protection applied

to the outer covering in the form of a chemical additive. The chemical used, percentage strength and

the changes in electrical and mechanical properties of the outer covering shall be stated in the

Technical Schedules.

The screen of the shielded cables shall be brought out and earthed at one end. The armouring of the

cables shall be earthed at both ends.

When laying the cables on trays, vertical runs, in cable ducts, etc. and when choosing the sizes of

cables, care must be taken to ensure that adequate ventilation is guaranteed and that there is no risk

of thermal overloading, undue pressure or distortions of the cables.

11.7 Low Voltage Power Cables

The conductors for power supply cables at voltages up to 600/1000 V AC shall be plain annealed

copper wire complying with IEC 60228 as applicable, with circular or shaped conductors. All cores

shall be identified by phase colours.

The conductor sizes shall be in accordance with loading of the individual circuits under the site

conditions and to the approval of KETRACO.

Page 33: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

33 Mariakani 400/220kV Substation

During motor starting or re-acceleration in groups, the voltage at the motor terminals shall not fall

below 80% of the rated voltage. Cables and systems shall be sized to meet these criteria.

The basis of voltage drop calculations shall be for worst case, i.e. minimum fault level and outage of

supply feeders or transformers.

The maximum permissible volt drop in cables shall be:

Feeders and sub-feeders 1%,

Motors branch circuits 2.5% (from power centre to load terminals),

Lighting sub-circuits 2.5% (from lighting switchboard to furthest fitting).

A derating factor based on the manufacturer’s recommendations shall be applied to cable

vendors stated current capacities, taking into account grouping factor, ambient

temperature and environmental conditions.

Cable shall be sized by consideration of:

Nameplate full load current of equipment,

Current carrying capacity after de-rating,

Voltage drop,

Short circuit rating.

The minimum cross-section of standard conductors shall be 2.5 mm².

The low voltage power cables shall consist of single, two, three and four core-cables.

On the low-voltage side, the cable connection between the station service transformers and the 0.4

kV infeed cubicles shall consist of single conductor power cables.

The connections between batteries or rectifiers respectively and the DC distribution board shall

generally consist of single core power cables.

11.7.1 Low Voltage Multicore Cables

The conductors for power supply cables at voltages up to 600/1000 V AC and for all 110 V DC

protection, control, alarm and indication shall be plain annealed copper wire complying with IEC

60228 as applicable or equivalent and all cores shall be clearly identified by printed numbers at

regular intervals.

The minimum conductor size shall be not less than seven strands of 0.67 mm diameter wire and the

minimum cross-sectional area shall be not less than 2.5mm². In special cases for light current

installations single strand, annealed copper conductors with a cross section of 1.5mm² may be used.

Also, conductor sizes less than 2.5mm² may be used for specific electronic circuits (e.g. ribbon cable)

subject to KETRACO’s approval.

Page 34: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

34 Mariakani 400/220kV Substation

All multicore cables shall have stranded copper conductors.

Multicore cables of 7 cores and above shall have a minimum of ten percent (10%) spare cores over

the original design requirements.

The number of cores in multicore cables shall be selected from the following numbers: 2, 3, 4, 7, 12,

19, 27 and 37.

The multicore cable tails shall be so bound that each wire may be traced to its cable without difficulty.

The screens of screened pairs of multipair cables shall be earthed at one end of the cable only. The

position of the earthing connections shall be shown clearly on the diagram.

All spare cores shall be earthed at both ends of the multicore cable.

The Contractor shall submit full details of all cable loads and in the case of interposing current

transformer connections, the loop resistance of each circuit.

An instrument transformer cable may transmit the current or voltage from only one transformer. If the

same voltage is required for different purposes (e.g. protection, measurement, metering) each voltage

transformer circuit must be wired via a separate MCB to the switchgear control cabinets.

11.7.2 Termination of Cables and Wires

All cables shall be terminated in accordance with the manufacturer’s recommendations and the cable

cores shall be long enough to be terminated to any terminal in an enclosure without extension. All

cables shall enter cubicles and boxes from bottom side.

PVC sheathed cables shall be terminated by compression glands complying with BS 6121 (or

equivalent).

Where cable cores are liable to be in contact with oil or oil vapour the insulation shall be unaffected by

oil.

The Contractor must terminate all power and control cables inside the appropriate cubicle. The spare

cores of all multicore cables shall be numbered and terminated at a terminal block in the cubicle.

AC terminals shall be clearly colour coded and shrouded.

Colours shall be marked on cable box, cable tail ends and single core cables at all connecting points

and/or any positions KETRACO may determine. Cable boxes shall be marked with stamped stainless

steel labels indicating the purpose of the supply where such supply is not obvious.

11.7.3 Installation Requirements

The following requirements shall apply:

HV Power Cables shall be routed in separate cable troughs.

Page 35: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

35 Mariakani 400/220kV Substation

LV power cables, multicore cables and telecommunication cables shall each be routed in

separate trays, racks, ducts, troughs or compartments separated by steel sheet

barriers.

Fibre optic cable shall be routed and installed such that they are protected from

deformation or damage by auxiliary power or control cables throughout their

installed length.

Sufficient space shall be allowed to run in each duct or compartment the necessary draw

wires, being of non-corrosive metal and having devices for securing the

conductors,

A spare capacity of 20% shall be provided on cable trays, ladder racks, ducts,

compartments, or openings in walls and floors,

Openings in floors and foundation pads shall be large enough to permit free movement of

cables during installation,

Channels and ducts shall be sealed where they enter a building to prevent the ingress of

moisture, gases and vermin,

Openings in walls and floors shall be sealed after the cable installation with a fireproof

barrier,

Cabling and wiring installations shall be arranged to minimize the risk of fire and damage

which might be caused in the event of fire,

Only one layer of cables shall be laid on one tray or in one cable channel,

All cables leaving buildings for outside plant shall be laid in cable ducts,

Where cables emerge from grade they shall be protected by a section of steel pipe

extending 150 mm above grade,

Cables above ground shall be run on galvanized cable racks, trays or supports, suitably

clipped to prevent movement. Care shall be taken to provide for differential

movement between the structures.

Protection from direct sunlight shall be provided by means of suitable sunshades

continuously covering the cable and of the same materials as the rack/tray.

Cable straps shall be made of stainless steel.

11.8 Inspection And Tests

11.8.1 General

Tests shall be carried out in order to determine whether the material and equipment comply with the

required properties.

All tests on material and equipment shall be carried out in accordance with IEC Standards. If some

tests are not covered or if a method of testing is not specified in IEC Standards or if there are options

Page 36: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

36 Mariakani 400/220kV Substation

in relevant IEC Standards the Contractor shall submit the method by which he proposes to conduct

the tests to KETRACO for approval.

The following lists of tests do not restrict KETRACO’s right to call for further tests if considered

necessary.

11.8.2 Workshop Tests

11.8.2.1 Type Tests

Type tests shall be performed on each type and rating of the specified equipment with purpose of

proving its properties.

The following type tests shall be performed:

Partial discharge test at room temperature.

Bending test followed by partial discharge test.

Measurement of power factor depending on temperature.

Measurement of insulation resistance at room temperature and service temperature.

Impulse voltage withstand test.

Dielectric test by DC voltage preferably.

11.8.2.2 Routine Tests

Routine test shall be performed at each item of equipment to be supplied for the purpose of revealing

faults in material or construction. They shall not impair the properties and reliability of a test object or

reduce its lifetime.

The following routine tests shall be performed on all lengths of cables and all accessories to be

supplied:

General inspection.

Examination of sheath, armour and protective coverings, as well as examination of

insulation, to be performed after bending test.

Measurement of conductor resistance.

High voltage test.

High voltage test on outer sheath.

Page 37: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

37 Mariakani 400/220kV Substation

11.8.3 Site Tests

On arrival at site, during installation and after complete installation, all items of equipment shall be

inspected and tested in order to check quality, correct operation and correct installation of the

equipment.

The following tests shall be performed:

1. General inspection of the cable routes, verification of proper installation, fixing to

the racks, bending radius, etc.

2. Verification of proper earthing of the screen and armouring.

3. Measurement of cables insulation resistance.

4. Verification of proper condition of external surfaces.

11.8.4 Spare Parts

Works to be done under this section include the delivery of spare parts. Requirements for spare parts

are described in General Technical Requirements and quantities in Schedule of Prices.

Any additional spare parts recommended by the Tenderer shall be listed and priced.

11.8.5 Training

Works to be done under this section include training of KETRACO’s personnel to operate and

maintain equipment efficiently and safely.

11.8.6 Documentation

The Contractor shall provide all necessary drawings, design specifications, design details, operation

and maintenance manuals and other information in accordance with General Technical

Requirements.

11.8.7 Documentation With Tender

The Tender shall contain at least the following information and documents:

1. Outline drawings showing the overall dimensions of the proposed cables;

2. Manufacturing specification of the proposed cables;

3. Catalogues, literature and reference lists of proposed cables;

4. Type test certificates from an independent testing authority or independently

witnessed;

5. Quality Management System Manual and ISO Certificate of the equipment

manufacturer.

Page 38: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

38 Mariakani 400/220kV Substation

BID DRAWINGS ISSUED UNDER TAC2

The following drawings are provided with this addendum document:

PB-KET-2012-D-223 Mariakani 220kV Single Line Diagram

PB-KET-2012-D-224 Mariakani 400kV Single Line Diagram

PB-KET-2012-L-234 Mariakani 220kV Layout

PB-KET-2012-L-235 Mariakani 220kV Elevations

PB-KET-2012-P-287 Mariakani 400/220kV Substation SCS Single Line Diagram

PB-KET-2012-P-288 Mariakani 400/220kV Substation LVAC Single Line Diagram

PB-KET-2012-P-289 Mariakani 400/220kV Substation 110V DC Single Line Diagram

PB-KET-2012-L-201 400kV Double Tension H/Ware fittings for Quad ACSR Lark Conductor

PB-KET-2012-L-203 Tension clamp with Al encasing suitable for ACS Earthwire (7/3.26)

PB-KET-2012-L-205 Jumper Spacer for ACSR Lark Conductor (400kV)

PB-KET-2012-L-206 Single Suspension (Pilot) H/Ware fittings for Single ACSR Canary Conductor (220kV)

PB-KET-2012-L-207 Quad Spacer Damper for ACSR Lark Conductor (400kV)

PB-KET-2012-L-208 400kV Pilot Suspension H/Ware fittings suitable for ACSR Quad Lark Conductor

PB-KET-2012-L-209 Single Tension H/Ware fittings for Single ACSR Canary Conductor (220kV)

PB-KET-2012-L-217 Double dead end set passing for OPGW cable diameter 19.6 – 20.6mm - 28110225 (F-0887)

PB-KET-2012-L-218 Single dead end set for OPGW cable diameter 19.6 – 20.6mm – 28110224 (F-0886)

PB-KET-2012-L-219 Tower Hinge for double tension hardware fittings suitable for quad ACSR lark conductor (400kV)

Miscellaneous

Page 39: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

39 Mariakani 400/220kV Substation

Drawings

6861162 Confirmed Outline Drawing (Shunt Reactor)

182AKPDE2006A Clearance diagram for Existing 220kV Tower- to be dismantled

182AKPDE2006A Clearance diagram for Existing 220kV Terminal Tower

182AKPDE40010 Clearance diagram for Existing 400kV Terminal Tower

SDH-1/2- Single Unit Staff Housing for senior staff (Annex 21.5 .1)

DDH-2/2- Double Unit Staff Housing for sub-ordinate staff (Annex 21.5.2)

Existing Telecommunications and OPGW System

1KHD636398 Sheet 504 Telecommunication System - System Layouts Legend

1KHD636398 Sheet 500 Telecommunication System – Western Region

1KHD636398 Sheet 501 Telecommunication System – Mount Kenya Region

1KHD636398 Sheet 502 Telecommunication System – Coastal Region

1KHD636398 Sheet 503 Telecommunication System – Nairobi Region

1KSE 000 535D410 Sheet 1 to 9 Block Diagram Network Manager

PB-KET-2012-D-233 Mariakani Overall Layout

PB-KET-2012-D-236 Mariakani 400kV Layout

PB-KET-2012-L-237

PROTECTION DRAWINGS

Mariakani 400kV Elevations

PB-KET-2012-P-280 Protection Single Line Diagram – Mariakani 400/220kV Substation 400kV Diameter 1

PB-KET-2012-P-281 Protection Single Line Diagram – Mariakani 400/220kV Substation 400kV Diameter 2

PB-KET-2012-P-282 Protection Single Line Diagram – Mariakani 400/220kV Substation 400kV Diameter 3

Page 40: I.2 Mariakani 400/220kV Substation This tender addendum and clarification forms part of the Request for Proposal and Contract documents, and modifies them as follows: I. CLARIFICATIONS

40 Mariakani 400/220kV Substation

PB-KET-2012-P-283 Protection Single Line Diagram – Mariakani 400/220kV Substation 400kV Diameter 4

PB-KET-2012-P-284 Protection Single Line Diagram – Mariakani 400/220kV Substation 220kV Diameter 1

PB-KET-2012-P-285 Protection Single Line Diagram – Mariakani 400/220kV Substation 220kV Diameter 2

PB-KET-2012-P-286 Protection Single Line Diagram – Mariakani 400/220kV Substation 220kV Diameter 3

64161A-PBP-L-0016 Mariakani Substation Layout