HYDRAULIC CALCULATIONS Alberta Street Public House

26
VIKING AUTOMATIC SPRINKLER COMPANY 3245 NW Front Avenue Portland, OR 97210 T: 503-227-1171 F: 503-227-1552 HYDRAULIC CALCULATIONS Alberta Street Public House 1028 NE Alberta Street Portland, OR Viking Job # OPC-3146 Contents: Water Curtain hydraulic calculation Flow test data Material for hydraulic reference: o 3” Wilkins ADA-BGVIC double check detector assembly o 3” Viking F-2 Dry Pipe Valve o Viking VK300 “microfast” upright fire sprinkler

Transcript of HYDRAULIC CALCULATIONS Alberta Street Public House

Page 1: HYDRAULIC CALCULATIONS Alberta Street Public House

VIKING AUTOMATIC SPRINKLER COMPANY

3245 NW Front Avenue Portland, OR 97210

T: 503-227-1171 F: 503-227-1552

HYDRAULIC CALCULATIONS

Alberta Street Public House 1028 NE Alberta Street Portland, OR Viking Job # OPC-3146 Contents: Water Curtain hydraulic calculation Flow test data Material for hydraulic reference:

o 3” Wilkins ADA-BGVIC double check detector assembly o 3” Viking F-2 Dry Pipe Valve o Viking VK300 “microfast” upright fire sprinkler

Page 2: HYDRAULIC CALCULATIONS Alberta Street Public House

SPRINKLER SYSTEM HYDRAULIC ANAL YSIS Page 1DATE: 2/28/2013GOOGLE DRIVE\_JOBS - ACTIVE\ALBERTA PUBLIC HOUSE\PATIO.SDFJOB TITLE: Alberta St Public House WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. T OTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ D EMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) ( GPM) (PSI) SOURCE 49.0 39.0 1283.0 47.7 4 26.6 46.4

AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 426.6 GPMTOTAL HOSE STREAM ALLOWANCE AT SOURCE 250.0 GPMOTHER HOSE STREAM ALLOWANCES 0.0 GPMTOTAL DISCHARGE FROM ACTIVE SPRINKLERS 176.6 GPM

NODE ANALYSIS DATANODE TAG ELEVATION NODE TYPE PRESSURE D ISCHARGE (FT) (PSI) (GPM)

10 11.3 K= 5.60 10.3 18.011 10.3 K= 5.60 10.8 18.412 9.3 K= 5.60 11.3 18.813 8.3 K= 5.60 11.9 19.314 7.5 K= 5.60 12.6 19.915 7.5 K= 5.60 13.1 20.216 7.5 K= 5.60 13.3 20.417 7.5 K= 5.60 13.6 20.618 7.5 K= 5.60 14.0 20.91 11.0 - - - - 20.2 - - -A 11.0 - - - - 22.9 - - -TR -2.0 - - - - 30.6 - - -BF1 -5.5 - - - - 32.6 - - -BF2 -5.5 - - - - 39.6 - - -FLG -4.0 - - - - 39.3 - - -SOURCE -4.0 SOURCE 46.4 176.6

Page 3: HYDRAULIC CALCULATIONS Alberta Street Public House

SPRINKLER SYSTEM HYDRAULIC ANAL YSIS Page 2DATE: 2/28/2013GOOGLE DRIVE\_JOBS - ACTIVE\ALBERTA PUBLIC HOUSE\PATIO.SDFJOB TITLE: Alberta St Public House PIPE DATA

PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)

Pipe: 1 -18.0 2.157 P L 6.10 PF 0.010 11.3 5.6 10.3 18.0 1.6 120 F TG ---- PE 0.411 10.3 5.6 10.8 18.4 0.003 T L 6.10 PV

Pipe: 2 -36.4 2.157 P L 6.10 PF 0.111 10.3 5.6 10.8 18.4 3.2 120 F TG ---- PE 0.412 9.3 5.6 11.3 18.8 0.012 T L 6.10 PV

Pipe: 3 -55.2 2.157 P L 6.10 PF 0.212 9.3 5.6 11.3 18.8 4.8 120 F TG ---- PE 0.413 8.3 5.6 11.9 19.3 0.025 T L 6.10 PV

Pipe: 4 -74.5 2.157 P L 5.75 PF 0.413 8.3 5.6 11.9 19.3 6.5 120 F TG E PE 0.414 7.5 5.6 12.6 19.9 0.044 T L 9.25 PV

Pipe: 5 -94.4 2.157 P L 6.00 PF 0.414 7.5 5.6 12.6 19.9 8.3 120 F TG ---- PE 0.015 7.5 5.6 13.1 20.2 0.069 T L 6.00 PV

Pipe: 6 -114.6 2.635 P L 6.00 PF 0.215 7.5 5.6 13.1 20.2 6.7 120 F TG ---- PE 0.016 7.5 5.6 13.3 20.4 0.037 T L 6.00 PV

Pipe: 7 -135.1 2.635 P L 6.00 PF 0.316 7.5 5.6 13.3 20.4 7.9 120 F TG ---- PE 0.017 7.5 5.6 13.6 20.6 0.050 T L 6.00 PV

Pipe: 8 -155.7 2.635 P L 6.00 PF 0.417 7.5 5.6 13.6 20.6 9.2 120 F TG ---- PE 0.018 7.5 5.6 14.0 20.9 0.065 T L 6.00 PV

Pipe: 9 -176.6 2.635 P L 64.00 PF 7.818 7.5 5.6 14.0 20.9 10.4 120 F TG 7E PE -1.51 11.0 0.0 20.2 0.0 0.082 T L 94.10 PV

Pipe: 16 -176.6 2.635 P L 22.16 PF 2.71 11.0 0.0 20.2 0.0 10.4 120 F TG T PE 0.0A 11.0 0.0 22.9 0.0 0.082 T L 32.96 PV

Pipe: 21 -176.6 3.260 P L 32.33 PF 2.0A 11.0 0.0 22.9 0.0 6.8 120 F TG 2E2T PE 5.6TR -2.0 0.0 30.6 0.0 0.029 T L 68.33 PV

Pipe: 22 -176.6 3.260 P L 3.50 PF 0.5TR -2.0 0.0 30.6 0.0 6.8 120 F TG TD PE 1.5BF1 -5.5 0.0 32.6 0.0 0.029 T L 18.10 PV

Pipe: 23 FIXED PRES SURE LOSS DEVICEBF2 -5.5 0.0 39.6 0.0 7.0 psi, 176.6 gpmBF1 -5.5 0.0 32.6 0.0

Page 4: HYDRAULIC CALCULATIONS Alberta Street Public House

SPRINKLER SYSTEM HYDRAULIC ANAL YSIS Page 3DATE: 2/28/2013GOOGLE DRIVE\_JOBS - ACTIVE\ALBERTA PUBLIC HOUSE\PATIO.SDFJOB TITLE: Alberta St Public House PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS. END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM. NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)

Pipe: 24 -176.6 3.260 P L 1.50 PF 0.3BF2 -5.5 0.0 39.6 0.0 6.8 120 F TG 2E PE -0.6FLG -4.0 0.0 39.3 0.0 0.029 T L 11.50 PV

Pipe: 25 -176.6 2.000 P L 20.00 PF 7.1FLG -4.0 0.0 39.3 0.0 18.0 150 F TG TG PE 0.0SOURCE -4.0 SRCE 46.4 (N/A) 0.209 T L 34.16 PV

NOTES (HASS):

(1) Calculations were performed by the HASS 8.3 co mputer program under license no. 38030713 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760

(2) The system has been calculated to provide an a verage imbalance at each node of 0.003 gpm and a maxi mum imbalance at any node of 0.051 gpm.

(3) Total pressure at each node is used in balanci ng the system. Maximum water velocity is 18.0 ft/sec at pipe 25.

(4) Items listed in bold print on the cover sheet

are automatically transferred from the calculat ion report.

(5) Available pressure at source node SOURCE under full flow conditions is 47.68 psi compared to the minimum required pressure of 20.00 psi.

(6) PIPE FITTINGS TABLE

Pipe Table Name: VIKINGFM.PIP

PAGE: * MATERIAL: S40 HWC: 120Diameter Equivalent Fitting Lengths in Fee t (in) E T L C B G A D N Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee 2.067 5.00 10.00 3.00 11.00 6.00 1.0 0 10.00 10.00 10.00

Page 5: HYDRAULIC CALCULATIONS Alberta Street Public House

SPRINKLER SYSTEM HYDRAULIC ANAL YSIS Page 4DATE: 2/28/2013GOOGLE DRIVE\_JOBS - ACTIVE\ALBERTA PUBLIC HOUSE\PATIO.SDFJOB TITLE: Alberta St Public House PAGE: B MATERIAL: SCH10 HWC: 120Diameter Equivalent Fitting Lengths in Fee t (in) E T F B G C A D U Ell Tee 45ell Bfyvlv Gatvlv Chkvlv Almvlv Dryvlv Udelug --------------------------------------- ----------------- V R Viccup Runtee 2.157 3.50 8.50 1.80 8.00 1.00 11.0 0 10.00 0.10 18.00 2.00 2.00 2.635 4.30 10.80 2.20 5.00 1.00 6.0 0 10.00 0.10 0.00 2.00 2.00 3.260 5.00 13.00 2.60 5.00 1.00 10.0 0 10.00 1.60 29.00 2.00 2.00

Page 6: HYDRAULIC CALCULATIONS Alberta Street Public House

SP

RIN

KL

ER

SY

ST

EM

HY

DR

AU

LIC

AN

AL

YS

IS P

ag

e 5

DA

TE

: 2/2

8/2

01

3G

OO

GL

E D

RIV

E\_

JO

BS

- AC

TIV

E\A

LB

ER

TA

P

UB

LIC

HO

US

E\P

AT

IO.S

DF

JO

B T

ITL

E: A

lbe

rta S

t Pu

blic

Ho

use

WATER SUPPLY ANALYSIS

Static: 49.00 psi Resid: 39.00 psi Flow: 1283.0 gpm

-14.7

0.0

10.0

20.0

30.0

40.0

50.0

60.0

400 600 800 1000 1200 1400 1600 1800 2000

FLOW (GPM)

GAUGE PRESSURE (psi)

A 12

B

LEGEND

1 Available pressure47.70 psi @ 426.6 gpm

2 Required pressure 46.44 psi @ 426.6 gpmA. Source Supply CurveB. System Demand Curve

Page 7: HYDRAULIC CALCULATIONS Alberta Street Public House

SPRINKLER SYSTEM HYDRAULIC ANAL YSIS Page 6DATE: 2/28/2013GOOGLE DRIVE\_JOBS - ACTIVE\ALBERTA PUBLIC HOUSE\PATIO.SDFJOB TITLE: Alberta St Public House WATER SUPPLY CURVE 60+ | | | 55+ | | | 50+ *\\\ | 0\\\ | X \\\ 45+ \\\\ | \\\\ | \\\ | \\\\ P 40+ \\\ R | * <-39.0 psi @ 12 83 gpm E | Flow Test Po int S | S 35+ U | R | E | 30+ ( | P | S | I 25+ ) | | | 20+ | | | 15+ | | |============================== 10+ LEGEND " | " | X = Required Water Supply " | 46.44 psi @ 426.6 gpm " 5+ " | 0 = Available Water Supply " | 47.70 psi @ 426.6 gpm " | " 0++-+---+----+-----+------+--------+--------+-- -------+-----------+ 400 600 800 1000 1200 1400 1600 1800 2000 FLOW (GPM)

Page 8: HYDRAULIC CALCULATIONS Alberta Street Public House

Portland Water Bureau

TO: Grant laine FROM: Jamie Wilde COMPANY: Viking Automatic Sprinkler Portland Water Bureau FAX: 503-227-1552 EMAIL: [email protected] PHONE: 503-227-1171 DATE: 10/16/2012 EMAIL: [email protected] # PAGES: 0

RE: 1028 NE Alberta St

Design for a static pressure of 49 psi (80% of nomin al max static pressure). Assume 1283 gpm is available at 39 psi (80% of nomi nal max static pressure minus observed drop at monitor hydrant).

Flow Test Results Flow Test ID #: 937 Map #: 2531 Date of 2/3/2004 Monitor Hydrant Port Info: Total Flow (gpm): 1283 Monitor Hydrant: NE Alberta St wwl 13th Ave Max Static HGL (ft): 362 Static Pressure (psi): 60 Hydrant Elevation (ft): 221 Residual Pressure 50 Nominal Max Static Pressure 61 Observed Drop (psi): 10

Flow Hydrant(s) Hydrant Location: NE Alberta St wwl 12th Ave Port 1 Size (in): 2 1/2" Port 1 Pitot Reading (psi): 16 Port 2 Size (in): 2 1/2" Port 2 Pitot Reading (psi): 13 Elevation (ft): 220 Main Size (in): 6 Flow (gpm): 1283

This test is a snapshot of system performance. Flow and pressure are affected by a variety of factors including: tank and reservoir levels, pump and valve settings, demand variations, and future changes to operational settings. The static pressure at this location may be as low as 80% of the maximum static pressure as calculated using the Max Static HGL.

Page 9: HYDRAULIC CALCULATIONS Alberta Street Public House

SPECIFICATION SUBMITTAL SHEET

a company

®

®

DOCUMENT #: REVISION:BF-350ADA 11/12(Patent No. 5,913,331)

Page 1 of 2

Model 350ADADouble Check Detector Assembly

FEATURES

Sizes: 2 1/2"* 3"* 4" 6" 8" 10"

Maximum working water pressure 175 PSI

Maximum working water temperature 140°F

Hydrostatic test pressure 350 PSI

End connections (Grooved for steel pipe) AWWA C606

(Flanged) ANSI B16.1

Class 125

*2 1/2" & 3" sizes use 4" body & reducer couplings

OPTIONS

(Sufixes can be combined) - with langed end OS & Y gate valves (standard) L - less shut-off valves (grooved body connections)

LM - less water meter

- with remote reading meter

- with gallon meter (standard)

CFM - with cu ft meter

CMM - with cu meter meter

G - with grooved end OS&Y gate valves FG - with langed inlet gate connection and grooved outlet gate connection

PI - with Post Indicator Gate Valves (4"-10")

BGVIC - with grooved end butterly valves valves with

integral supervisory switches

ACCESSORIES

Repair kit (rubber only)

Thermal expansion tank (Model XT)

OS & Y Gate valve tamper switch (OSY-40) Test Cock Lock (Model TCL24)

DIMENSIONS & WEIGHTS (do not include pkg.)

MODEL

350 ADA

SIZE

DIMENSION (approximate)

A

A WITH

BUTTERFLYVALVES

B LESS

GATE

VALVES

C DE

OS&Y OPEN

E

OS&Y

CLOSED

E WITH

BUTTERFLY

VALVES

F G

in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm

2 1/2 65 35 1/8 892 32 1/8 816 20 1/8 511 4 1/2 114 9 229 16 3/8 416 13 7/8 352 8 203 6 152 7 1/4 184

3 80 36 1/8 918 33 838 20 1/8 511 4 1/2 114 9 229 18 7/8 479 15 5/8 397 8 203 6 152 7 1/4 184

4 100 38 1/4 972 33 1/4 845 19 7/8 505 4 1/2 114 9 229 22 3/4 578 18 1/4 464 9 1/8 232 6 152 8 203

6 150 47 1/4 1200 40 1/4 1022 25 7/8 657 5 1/2 140 10 1/2 267 30 1/8 765 23 3/4 603 10 1/8 257 7 178 10 254

8 200 62 1575 55 1397 38 1/2 978 10 254 12 305 37 3/4 959 29 1/4 743 11 15/16 303 8 1/2 216 11 279

10 250 64 5/8 1642 58 1/2 1485 38 1/2 978 10 254 12 305 45 3/4 1162 35 3/8 899 13 5/16 338 81/2 216 12 305

MODEL

350ADA

SIZE

WEIGHT

WITHOUT

GATES

WITH OS&Y

GATES (GXF)

WITH OS&Y

GATES (GXG)

WITH

BUTTERFLY VALVES (GXG)

in. mm lbs. kg lbs. kg lbs. kg lbs. kg

2 1/2 65 105 47.5 207 94 199 90.3 123.8 56.2

3 80 104 47 224 101.5 214 97 124.4 56.5

4 100 91 41.3 245 111 219 99.4 123 55.8

6 150 141 64 377 171 347 158 193 87.6

8 200 302 137 778 353.2 754 342.3 410 186

10 250 355 161 1040 472.7 918 416.5 527 239.3

APPLICATION

Designed for installation on potable water lines connections in

ire sprinkler systems to protect against both backsiphonage and backpressure of polluted water into the potable water supply.

Model 350ADA shall provide protection where a potential health

hazard does not exist. Incorporates metered by-pass to detect

leaks and unauthorized water use.

STANDARDS COMPLIANCE (HORIZONTAL & VERTICAL)

● ASSE® Listed 1048

● AWWA Compliant C510 (with gates only), and C550

● CSA® Certiied ● UL® Classiied ● C-UL® Classiied ● FM® Approved

● Approved by the Foundation for Cross Connection

Control and Hydraulic Research at the University of

Southern California

● NYC MEA 221-04M-2 (2 1/2" - 8")

MATERIALS

Main valve body Ductile Iron ASTM A 536 Grade 4

Access covers Ductile Iron ASTM A 536 Grade 4

Coatings FDA Approved electrostatic epoxy inishInternals Stainless steel, 300 Series

NORYL™, NSF ListedFasteners & springs Stainless Steel, 300 Series

Elastomers EPDM (FDA approved)

Buna Nitrile (FDA approved)

Polymers NORYL™, NSF Listed

MODEL 350ADA

with OS&Y option

MODEL 350ADA with

BGVIC option

Attention:

Model 3 5 0 A D A

(grooved body)

and Model 350DA

( f l a n g e b o d y )

have different lay

lengths.

(with BGVIC valves)(with OS&Y gates)

E

F

DCB

A

B

A

E

F

C D

G

G

Page 10: HYDRAULIC CALCULATIONS Alberta Street Public House

Page 2 of 2

WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805-238-7100 Fax:805-238-5766

IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905-405-8272 Fax:905-405-1292

Product Support Help Line: 877-BACKFLOW (877-222-5356) • Website: http://www.zurn.com

TYPICAL INSTALLATION

Local codes shall govern installation requirements. Unless

otherwise speciied, the assembly shall be mounted at a mini-mum of 12" (305mm) and a maximum of 30" (762mm) above

adequate drains with suficient side clearance for testing and maintenance. The installation shall be made so that no part of

the unit can be submerged.

Capacity thru Schedule 40 Pipe (GPM)

Pipe size 5 ft/sec 7.5 ft/sec 10ft/sec 15 ft/sec

2 1/2" 75 112 149 224

3" 115 173 230 346

4" 198 298 397 595

6" 450 675 900 1351

8" 780 1169 1559 2339

10" 1229 1843 2458 3687

12" 1763 2644 3525 5288

SPECIFICATIONS

The Double Check Detector Backlow Prevention Assembly shall be ASSE® Listed 1048, and supplied with full port gate valves. The main body and access cover shall be epoxy coated ductile iron (ASTM A 536 Grade 4), the seat ring and check valve shall be

Noryl™ (NSF Listed), the stem shall be stainless steel (ASTM A 276) and the seat disc elastomers shall be EPDM. The irst and second check valves shall be accessible for maintenance without removing the device from the line. The Double Check Detector

Backlow Prevention Assembly shall be a WILKINS Model 350ADA.

MODEL 350ADA (OUTDOOR INSTALLATION)MODEL 350ADABGVIC (VERTICAL INSTALLATION)

⃟ Rated Flow (Established by approval agencies)

PROTECTIVE

ENCLOSURE

12" MIN.

30" MAX.

DIRECTION OF FLOW

DIR

EC

TIO

N O

F F

LO

W

MODEL 350ADA 6", 8" & 10" (STANDARD & METRIC)

0

5

10

15

0 1000 2000 3000 4000

FLOW RATES (GPM)

PR

ES

SU

RE

LO

SS

(P

SIG

)

0

35

69

104

0.0 63.1 126.2 189.3 252.4

FLOW RATES (l/s)

PR

ES

SU

RE

LO

SS

(kp

a)

MODEL 350ADA 2 1/2", 3" & 4" (STANDARD & METRIC)

0

5

10

15

0 200 400 600 800

FLOW RATES (GPM)

PR

ES

SU

RE

LO

SS

(P

SIG

)

0

35

69

104

0.0 12.6 25.2 37.9 50.5

FLOW RATES (l/s)

PR

ES

SU

RE

LO

SS

(kp

a)

2 1/2" (65mm)

3" (80mm)

4" (100mm)

6" (150mm) 8" (200mm) 10" (250mm)

FLOW CHARACTERISTICS

Page 11: HYDRAULIC CALCULATIONS Alberta Street Public House

TECHNICAL DATA

February 25, 2011 Dry 135a

DRY VALVEMODEL F-2

GROOVE/GROOVE

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

1. DESCRIPTIONThe Viking Model F-2 Dry Pipe Valve is a latching differential valve used to separate the water supply

from the dry pipe sprinkler system. The valve combines a positive latching clapper and air plate assem-

bly, with a differential air to water seat design. The latching clapper and air plate assembly provides a

positive mechanical seal for the air pressure in the dry pipe system. The differential design allows an air

supply of moderate pressure to control a higher water supply pressure. When the air pressure in the dry

pipe system is lowered suffi ciently to destroy the pressure differential, the valve opens allowing water

to enter the dry pipe system.

The valve is also designed to operate a water motor alarm and/or an electric pressure alarm switch.

The Viking accelerator with external Anti-fl ood Device can be used to speed the operation of the valve

on large capacity systems or where faster action is required.

2. LISTINGS AND APPROVALSUL Listed: VPZVcUL Listed: VPZVCFM Approved: Dry Pipe ValvesNYC Department of Buildings: MEA 89-92-E Vol. 39

3. TECHNICAL DATASpecifications:Rated to - 175 PSI (12.1 bar) Water Working Pressure.Factory tested hydrostatically - 350 PSI (24.1 bar) with the clapper open.

Air pressure to water pressure area differential: Approximately 6 to 1.

Material Specifications: Refer to Figure 3

Ordering Information:Part Number - Refer to Table 1

Available Since 2007

Accessories: Note: When viewing this Page online, blue text represents hyper links and will open the desired data page.

Model F Dry Valve Conventional Trim Package: For use when the Dry Valve is used on systems with fresh water supplies. 3” Part No. 10158 (galvanized steel) 4” Part No. 08395 (galvanized steel) 6” Part No. 08395 (galvanized steel)

Model F Dry Valve Accessory Package: This package is needed when Viking Trim Packages are not used.Part No. 08397

D-2 Accelerator:Part No. 09881

D-2 Accelerator Trim Kit: Package includes trim components and air gauge required to install the Viking Model D-2 AcceleratorPart No. 09730

E-1 Accelerator and B-1 Anti-Flood Assembly Package: Includes: Model E-1 Accelerator and Model B-1 Anti- fl ood Device.Part No. 08116

E-1 Accelerator Trim Kit: Package includes trim components and air gauge required to install the Viking Model E-1 Accelerator and B-1 Anti- fl ood Device.

Part No. 08264 (galvanized steel)

Additional accessories are available and may be required for operation or supervision. Refer to the system description for complete operating trim requirements.

���

Revised page replaces page 135a-j, dated November 29, 2010.

(Added new item 26 to the Replacement Parts list.)

Form No. F_011507

Viking Technical Data may be found on The Viking Corporation’s Web site at

http://www.vikinggroupinc.com.The Web site may include a more recent

edition of this Technical Data Page.

Table 1 - Part Numbers and SpecificationsDESCRIPTION

NOMINAL SIZE

PART NUMBER

FRICTION LOSS*

CV FACTOR

SHIPPING WEIGHT

Groove/Groove Pipe OD89 mm 3" 13764 3 ft (0,91 m) 800 125 lbs (57 kg)

114 mm 4" 13765 5 ft (1,52 m) 821 125 lbs (57 kg)

168 mm 6" 13766 49 ft (14,9 m) 780 188 lbs (85 kg)

165 mm 6” 13767 49 ft (14,9 m) 780 188 lbs (85 kg)

* Expressed in equivalent length of Schedule 40 pipe based on Hazen & Williams formula: C=120

Q= Cv √ ∆P

S

Q= Flow

Cv= Flow Factor (GPM/1 PSI ∆P)

∆P= Pressure Loss through Valve

S= Specifi c Gravity of Fluid

Page 12: HYDRAULIC CALCULATIONS Alberta Street Public House

TECHNICAL DATA

February 25, 2011Dry 135b

DRY VALVEMODEL F-2

GROOVE/GROOVE

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

4. INSTALLATION For proper operation and approval, the valve must be trimmed in accordance with Viking Model F Dry Valve Trim Charts.

The Model F-2 Dry Valve must be installed in the vertical position as shown in Figure 2.

Air or nitrogen supply to the dry pipe system must be clean, dry, and oil free.

Automatic air supplies must be regulated, restricted, and from a continuous source. (Refer to Table 2) A Viking Air Maintenance Device

should be installed on each system equipped with an automatic air supply. Never exceed 60 PSI (4.1 bar) pressure in the system pip-

ing with the dry valve clapper closed.

The dry valve must be installed in an area not subject to freezing temperatures or physical damage. If required, provide a valve house

(enclosure) with adequate heat around the dry valve and trim. Freezing temperatures and/or excessive pressure will damage the dry

valve member assembly.

When corrosive atmospheres and/or contaminated water supplies are present, it is the owner’s responsibility to verify compatibility

with the Model F-2 Dry Valve and associated equipment.

Consider installation of the Viking Accelerator and Anti-fl ood Device. An accelerator (quick opening device) is recommended on all

differential dry pipe valves and is required on dry pipe systems of certain capacities. Refer to Installation Standards and Authorities

Having Jurisdiction. If an accelerator is to be installed, verify that the appropriate Trim Chart is used. Prior to installing the valve, thor-

oughly fl ush the water supply piping to verify that no foreign matter is present.

A. General Installation InstructionsVerify that necessary Trim Charts and Technical Data for the dry valve and associated equipment are available.

Remove all plastic thread protectors from the openings of the dry valve.

Apply a small amount of pipe-joint compound or tape to the external threads of all pipe connections required. Take care not

to allow any compound, tape, or other foreign matter inside any of the nipples or openings of the dry valve or trim compo-

nents.

Install the Model F-2 Dry Valve and trim piping according to the current Model F-2 Dry Valve Trim Chart provided with the

Trim Package and the Viking Engineering and Design Data book. The Model F-2 Dry Valve must be installed in the vertical

position.

When installing a Viking Accelerator and Anti-flood Device in conjunction with the Model F-2 Dry Valve, refer to the appropri-

ate Viking E-1 Accelerator Trim Chart provided with the Accelerator Trim Package and the Viking Engineering and Design

Data book.

When a Viking Accelerator is installed on the Model F-2 Dry Valve, the dry system air supply must be connected as shown

on the Model E-1 Accelerator Trim Chart.

The Viking external Anti-flood Device is required when a Viking Accelerator is installed on a Dry Valve according to the

Model E-1 Accelerator Trim Chart.

Hydrostatic Test:CAUTION: THE DRY VALVE CLAPPER MUST BE LATCHED OPEN DURING PERFORMANCE OF THE HYDROSTATIC TEST.

Do not perform a 200 PSI (13.8 bar) hydrostatic system test with the dry valve clapper in the closed (set) position.

Never exceed 60 PSI (4.1 bar) air pressure in the system piping with the dry valve clapper closed.

DO NOT expose the Viking Accelerator to the hydrostatic test. For warnings and considerations regarding hydrostatic testing of the

Viking Accelerator and other system components, refer to Technical Data for the equipment used.

B. Placing the Valve in Service(Refer to Figure 2)

1.

2.

3.

4.

5.

a.

b.

Figure 1 - Take Out Dimensions

3”

(DN80)

4”

(DN100)

6”

(DN150)A 18-1/2”

(470)

18-3/4”

(476)

20-5/16”

(516)

B 8-1/16”

(2058)

7-1/16”

(179)

7-5/16”

(186)

C 16-3/4”

(425)

13-5/16”

(338)

13-7/16”

(332)

D 9-1/16”

(230)

9-1/16”

(230)

9-5/16”

(237)

E 11-13/16”

(300)

13-5/16”

(338)

13-7/16”

(332)

F 21-11/16”

(551)

21-7/8”

(556)

22-5/16”

(567)

G 35-7/8”

(911)

36-1/16”

(916)

36-13/16”

(936)

Page 13: HYDRAULIC CALCULATIONS Alberta Street Public House

TECHNICAL DATA

February 25, 2011 Dry 135c

DRY VALVEMODEL F-2

GROOVE/GROOVE

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

When the dry pipe system is ready to be placed in service, verify that all equipment is adequately heated and protected to prevent

freezing and physical damage.

Verify that the water supply main control valve supplying the dry valve is closed.

Open the main drain valve (located on the inlet of the dry valve).

Drain all water from the dry pipe system. If the system has operated, or if water has entered the system, open all auxiliary

drains and the system test valve. Allow enough time to completely drain the system. Perform steps 4 through 10 to set the

dry valve and/or inspect the internal operating parts of the dry valve.

Verify that the dry pipe system is not pressurized.

Use the Dry Valve Reset Bar/Wrench, part number 02977BM, to loosen and remove hand-hole cover bolts (21). Remove

hand-hole cover (24).

CAUTION: CLAPPER ARM ASSEMBLY (8) AND CLAPPER ASSEMBLY (5) ARE SPRING LOADED TO OPEN. NEVER PLACE HANDS INSIDE THE DRY VALVE IF THE CLAPPER ASSEMBLY IS LATCHED CLOSED.

To release a latched clapper assembly for service:

Insert the re-setting tool through the hole in hook assembly (15), across the fulcrum cast on top of clapper arm assembly

(8) until the re-setting tool contacts the stopping boss on top of clapper arm assembly (8) (see Figure 2C).

Apply a downward force on the end (outside the valve) of the re-setting tool. Hook assembly (15) will slide toward the hand-

hole and off clapper arm assembly (8). Clapper arm assembly (8) and clapper assembly (5) will forcefully open, impact

against latch (2), and latch in the open position.

NOTE: INSPECTION AND CLEANING PROCEDURE STEP 7 BELOW IS CONSIDERED PART OF THE ANNUAL TRIP TEST.

Inspect and clean the internal parts of the valve. Give special consideration to the water seat (16), air seat (20) and clapper

rubber (19). Wipe away all contaminants, dirt, and mineral deposits. Do not use solvents or abrasives. Operate all parts to

test freedom of movement. Renew or replace damaged or worn parts as required.

CAUTION: NEVER APPLY ANY LUBRICANT TO SEATS, GASKETS, OR ANY INTERNAL OPERATING PARTS OF THE DRY VALVE. PETROLEUM BASED GREASE OR OIL WILL DAMAGE RUBBER COMPONENTS AND MAY PREVENT PROPER OPERATION OF THE DRY VALVE.

To set the dry valve clapper. (Refer to figures 2 & 3)

Raise the latch (2) to release spring loaded clapper arm assembly (8) from the latched open position.

Move the clapper arm assembly (8) down toward the horizontal position (see Figure

2-B).

While holding spring loaded clapper arm assembly (8) down, insert the re-setting

tool through the hole in hook assembly (15), across the fulcrum cast on top of clap-

per arm assembly (8) until the re-setting tool contacts the stopping boss as shown

in Figure 2-C.

Apply a sharp upward force at the end of the re-setting tool. Hook (15) will slide

forward on the re-setting bar and latch the clapper closed with a positive setting

action (see Figure 2-C).

Priming water is not required and may not be desirable where clean, good quality fresh

water is not available. If priming water is desired, fill the dry valve with water to the bot-

tom of the hand-hole. Verify that the intermediate chamber of the dry valve is free of

water. No water should fl ow from the drip check when the plunger is pushed.

1.

2.

3.

4.

5.

6.

a.

b.

7.

8.

a.

b.

c.

d.

9.

Table 2 - Air Pressure SettingsMaximum

Water Pressure

Air Pressure Setting

Minimum Maximum

PSI bar PSI bar PSI bar

50 3.45 15 1.03 25 1.72

75 5.17 20 1.38 30 2.07

100 6.90 25 1.72 35 2.41

125 8.62 30 2.07 45 3.10

150 10.34 35 2.41 50 3.45

175 12.07 45 3.10 60 4.14

Figure 2 - Resetting the Dry Valve

Page 14: HYDRAULIC CALCULATIONS Alberta Street Public House

TECHNICAL DATA

February 25, 2011Dry 135d

DRY VALVEMODEL F-2

GROOVE/GROOVE

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

Visually inspect hand-hole cover gasket (25). Verify that it is in good condition.

Re-install hand-hole cover (24), gasket (25), and hand-hole cover bolts (21). Tighten the bolts using the Dry Valve Reset

Bar/Wrench, part number 02977BM.

Close all auxiliary drains, the system test valve, and the priming water level test valve on the dry valve trim. The main drain

(located on the inlet of the dry valve) should remain open.

If equipped with a Viking Accelerator and external Anti-flood Device:

Close the ½” (15 mm) anti-flood isolation valve.

Observe the air pressure gauge on top of the accelerator. The gauge must read zero before the accelerator will auto-

matically reset. It may be necessary to loosen, remove, and re-install (use the appropriate wrench) the air gauge to vent

trapped air pressure from the upper chamber.

Open the dry system air supply and establish desired system pressure. See Table 2 for suggested air pressure to water pres-

sure settings. NEVER EXCEED 60 PSI (4.1 bar) AIR PRESSURE.

Verify that the intermediate chamber of the dry valve is free of water. No water should flow from the drip check when the

plunger is pushed.

If equipped with a Viking Accelerator and external Anti-flood Device: When pressure on the accelerator air pressure gauge

equals the system set pressure, OPEN and secure the ½” (15 mm) anti-flood isolation valve.

Slowly open the water supply main control valve.

When flow is developed from the main drain, CLOSE the main drain valve.

Fully open the water supply main control valve.

Secure all valves in their normal operating position.

Notify Authorities Having Jurisdiction and those in the affected area that the system is in service.

5. OPERATION (Refer to Figure 2)

The clapper (5) and air plate (11) assemblies combine to form a fl oating member assembly. With the clapper assembly (5) latched

closed, system air pressure forces the member assembly down, sealing the water seat (16) from the intermediate chamber. When

a sprinkler operates, the system air pressure is reduced. When system air pressure is reduced to the differential tripping point of the

valve, water supply pressure in the inlet chamber lifts the member assembly off the water seat (16) and fl ows into the intermediate

chamber. As the member assembly continues to rise, the latching hook (15) is forced against operating pin (23), which causes the

hook (15) to pivot on hook rod (6b) and unlatch the clapper. The clapper is spring loaded and swings to a full-open locked position

(See Figure 2-A).

When equipped with the optional Accelerator and external Anti-fl ood Device, a drop in system air pressure causes the Accelerator to

operate. Operation of the Accelerator causes the Anti-fl ood Device to open allowing system air pressure to enter the dry valve interme-

diate chamber. This immediately destroys the pressure differential, causing the member assembly to rise faster.

The intermediate chamber is normally at atmospheric pressure and is connected to the alarm line. When the valve trips, the intermedi-

ate chamber and alarm line are pressurized with system water pressure, activating alarms connected to the dry valve trim.

ABNORMAL CONDITIONSSee Table 3

6. INSPECTIONS, TESTS AND MAINTENANCENOTICE: THE OWNER IS RESPONSIBLE FOR MAINTAINING THE FIRE PROTECTION SYSTEM AND DEVICES IN PROPER OPERAT-ING CONDITION.

The Viking Model F-2 Dry Valve and trim must be kept free of foreign matter, freezing conditions, corrosive atmospheres, contaminated

water supplies, and any condition that could impair its operation or damage the device.

It is imperative that the system be inspected and tested on a regular basis. The frequency of the inspections may vary due to con-

taminated water supplies, corrosive water supplies, corrosive atmospheres, as well as the condition of the air supply to the system.

For minimum maintenance and inspection requirements, refer to NFPA 25. In addition, the Authority Having Jurisdiction may have

additional maintenance, testing, and inspection requirements that must be followed.

WARNING: ANY SYSTEM MAINTENANCE WHICH INVOLVES PLACING A CONTROL VALVE OR DETECTION SYSTEM OUT OF SER-VICE MAY ELIMINATE THE FIRE PROTECTION CAPABILITIES OF THAT SYSTEM. PRIOR TO PROCEEDING, NOTIFY ALL AUTHORI-TIES HAVING JURISDICTION. CONSIDERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AR-EAS.

I. INSPECTIONWeekly inspection is recommended. If the system is equipped with a low air (or nitrogen) alarm, monthly inspections may be ad-

equate.

10.

11.

12.

13.

a.

b.

14.

15.

16.

17.

18.

19.

20.

21.

Page 15: HYDRAULIC CALCULATIONS Alberta Street Public House

TECHNICAL DATA

February 25, 2011 Dry 135e

DRY VALVEMODEL F-2

GROOVE/GROOVE

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

Check pressure gauges located on the supply side and system side of the dry valve. Verify that the proper ratio of air (or

nitrogen) pressure to water supply pressure is being maintained. Refer to Table 2.

Verify that the intermediate chamber of the dry valve is free of water. No water should flow from the drip check when the

plunger is pushed.

If equipped with a Viking Accelerator:

Check the air pressure gauge located on the top of the Accelerator. Air pressure in the upper chamber of the accelerator

should equal the pneumatic pressure maintained in the system.

NOTE: STANDARD TOLERANCE ALLOWANCE IN PRESSURE GAUGE CALIBRATION MAY RESULT IN A SLIGHT VARIATION WHEN PRESSURE READINGS FROM ANY TWO GAUGES ARE COMPARED. A DIFFERENCE IN PRESSURES OTHER THAN SLIGHT VARIA-TION DUE TO GAUGE CALIBRATION TOLERANCE MAY INDICATE MAINTENANCE IS REQUIRED. REFER TO TECHNICAL DATA FOR THE ACCELERATOR USED.

For dry systems with Viking Accelerators installed according to the Viking Model E-1 Accelerator Trim Chart, verify that the

½” (15 mm) anti-flood isolation valve is OPEN and secured.

Verify that the water supply main control valve is open and all trim valves are in their normal operating position.

Check for signs of mechanical damage and/or corrosive activity. If detected, perform maintenance as required or, if necessary,

replace the device.

Verify that dry valve and trim are adequately heated and protected from freezing and physical damage.

II. TESTSQUARTERLY TESTS A. Water Flow Alarm TestQuarterly testing of water fl ow alarms is recommended and may be required by the Authority Having Jurisdiction.

Notify the Authority Having Jurisdiction and those in the area affected by the test.

NOTE: VIKING CONVENTIONAL TRIM PROVIDES A CONNECTION FOR INSTALLATION OF A NON-INTERRUPTIBLE PRESSURE SWITCH. ALARMS AND/OR ELECTRIC PANELS CONTROLLED BY AN ALARM PRESSURE SWITCH INSTALLED IN THAT CONNEC-TION CANNOT BE INTERRUPTED.

Fully open the main drain (located on the base of the dry valve) to flush away any accumulation of foreign material.

Close the main drain.

To test the local electric alarm (if provided) and/or mechanical water motor gong (if provided), OPEN the alarm test valve in

the dry valve trim.

Electric alarm pressure switches (if provided) should activate.

Electric local alarms should be audible.

The local water motor gong should be audible.

Verify that (if provided) remote station alarm signals were received.

When testing is complete, close the alarm test valve.

Verify:

All local alarms stop sounding and alarm panels (if provided) reset.

All remote station alarms reset.

All supply piping to water motor properly drains.

Verify that the alarm shut-off valve in the dry valve trim is OPEN, and the alarm test valve is CLOSED.

Verify that the intermediate chamber of the dry valve is free of water. No water should flow from the drip check when the

plunger is pushed.

Notify the Authority Having Jurisdiction and those in the affected area that testing is complete.

B. Main Drain TestQuarterly performance of the Main Drain Test is recommended and may be required by Authorities Having Jurisdiction to verify integrity

of the water supply.

Notify the Authority Having Jurisdiction and those in the area affected by the test.

Record pressure reading from the water supply pressure gauge.

Verify that the intermediate chamber of the dry valve is free of water. No water should flow from the drip check when the

plunger is pushed.

Verify that the dry pipe system is pressurized at or above the minimum pressure recommended in Table 2 for the water supply

pressure available.

Fully OPEN the main drain located on the base of the dry valve.

When a full flow is developed from the main drain, record the residual pressure from the water supply pressure gauge.

When the test is complete, SLOWLY CLOSE the main drain.

1.

2.

3.

a.

b.

4.

5.

6.

1.

2.

3.

4.

a.

b.

c.

d.

5.

6.

a.

b.

c.

7.

8.

9.

1.

2.

3.

4.

5.

6.

7.

Page 16: HYDRAULIC CALCULATIONS Alberta Street Public House

TECHNICAL DATA

February 25, 2011Dry 135f

DRY VALVEMODEL F-2

GROOVE/GROOVE

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

Compare test results with previous flow information. If deterioration of the water supply is detected, take appropriate steps to

restore adequate water supply.

Verify that normal water supply pressure and system pneumatic pressure have been restored, and that all alarm devices and

valves are secured in normal operating position.

Notify the Authority Having Jurisdiction that the test is complete. Record and/or provide notification of test results as required

by the Authority Having Jurisdiction.

C: Priming Water Level, and Low Air Alarm TestQuarterly testing is recommended to verify that water is not present above the Priming Level Test Valve in the dry valve trim.

Quarterly testing of low air alarms is recommended.

Notify the Authority Having Jurisdiction and those in the area affected by the test.

Fully open the main drain (located on the base of the dry valve) to flush away any accumulation of foreign material.

Close the main drain.

Close the water supply Main Control Valve supplying the dry valve.

Open the Main Drain Valve (located on the inlet of the dry valve).

If the dry valve being tested is equipped with a Viking Accelerator and external Anti-fl ood Device installed according to Viking Model

E-1 Accelerator Trim Charts, performing steps 6 or 7 of this test will cause the accelerator to operate. A burst of air from the vent in the

bottom of the accelerator will indicate operation of the accelerator. However, with the water supply Main Control Valve CLOSED and

the Main Drain Valve OPEN, operation of the accelerator should not trip the dry valve.

Dry Valve Priming Water Level Test:

Verify that the water supply main control valve is closed and the main drain valve is open.

Fully open the Priming Level Test Valve in the dry valve trim to check for the presence of water. If the presence of water

is detected, the system may not have been properly drained. Perform steps 1 through 3, and 11 through 15 of paragraph

10, PLACING DRY VALVE IN SERVICE, and repeat this Dry Valve Priming Water Level Test.

If/when no water is detected and the test is complete, continue to step 8.

Low Air Alarm Test:

Verify that the water supply main control valve is closed and the main drain valve is open.

Gradually open the Priming Level Test Valve in the trim of the dry valve to simulate operation of the Dry System. Observe

and record the pressure at which the low air alarm operates.

Close the Priming Level Test Valve.

If the dry valve being tested is equipped with a Viking Accelerator and external Anti-flood Device:

Close the ½” (15 mm) NPT Anti-flood Isolation Valve. Air will continue to flow from the accelerator after it has operated

until step “b” below is performed.

Loosen (use the appropriate wrench), and remove the Accelerator Air Gauge to release pressure from the upper chamber

of the accelerator. When the accelerator re-sets, re-install the accelerator air gauge.

Perform steps 13 through 20 of paragraph 4-B INSTALLATION, Placing the Valve in Service.

TRIP TESTSPartial Flow Trip Tests are conducted with the water supply main control valve partially closed to minimize the amount of water enter-

ing the system during the test. Performance of a Partial Flow Trip Test is recommended during warm weather at least annually except

when a Full Flow Trip Test is conducted. Partial Flow Trip Tests may verify operation of equipment and devices but do not simulate

operation of the system in fi re conditions.

Full Flow Trip Tests are conducted with the water supply main control valve fully open. The dry valve is operated by opening the system

test valve to simulate the opening of a sprinkler in fi re conditions. When the dry valve operates, the sprinkler piping will be fl ooded with

water.

Performance of a Full Flow Trip Test is recommended during warm weather at least once every three years. More frequent testing may

be required by the Authority Having Jurisdiction.

A. Full Flow Trip TestNotify the Authority Having Jurisdiction and those in the area affected by the test.

NOTE: ALARMS AND ELECTRIC PANELS CONTROLLED BY AN ALARM PRESSURE SWITCH INSTALLED IN THE “ELECTRIC ALARM PANEL CONNECTION”, CANNOT BE INTERRUPTED (SEE DRY VALVE TRIM CART).

Fully open the main drain (located on the base of the dry valve) to flush away any accumulation of foreign material.

Close the main drain.

Record water supply pressure and system pneumatic pressure.

Open the remote system test valve to simulate operation of the dry system. Record:

Elapsed time from opening of the test valve to operation of the dry valve.

System pressure when the dry valve operated.

Elapsed time from opening of the test valve to development of full flow of water from the system test connection.

Any other information required by the Authority Having Jurisdiction.

8.

9.

10.

1.

2.

3.

4.

5.

6.

a.

b.

c.

7.

a.

b.

8.

9.

a.

b.

10.

1.

2.

3.

4.

5.

a.

b.

c.

d.

Page 17: HYDRAULIC CALCULATIONS Alberta Street Public House

TECHNICAL DATA

February 25, 2011 Dry 135g

DRY VALVEMODEL F-2

GROOVE/GROOVE

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

Verify that alarms operate properly.

Allow water to flow from the system test connection until it appears clear and clean.

When test is complete, close the water supply main control valve.

Perform steps 1 through 20 of paragraph 4-B INSTALLATION, Placing the Valve in Service.

Verify that the water supply main control valve is open, and all other valves are in their normal operating position. If equipped

with an external Anti-flood Device, the ½” Anti-flood Isolation Valve must be OPEN and secured.

B: Partial Flow Trip TestNotify the Authority Having Jurisdiction and those in the area affected by the test.

NOTE: VIKING CONVENTIONAL TRIM PROVIDES A CONNECTION FOR INSTALLATION OF A NON-INTERRUPTIBLE PRESSURE SWITCH. ALARMS AND ELECTRIC PANELS CONTROLLED BY AN ALARM PRESSURE SWITCH INSTALLED IN THE “ELECTRIC ALARM PANEL CONNECTION”, CANNOT BE INTERRUPTED (SEE DRY VALVE TRIM CART).

Record water supply pressure and system pneumatic pressure.

Fully open the main drain (located on the base of the dry valve) to flush away any accumulation of foreign material.

CLOSE the water supply main control valve as far as possible while maintaining full flow from the main drain. CLOSE the

main drain.

Open the priming level test valve to simulate operation of the system.

Note (for records) water supply pressure and system pneumatic pressure when the dry valve operates.

CLOSE the water supply main control valve and OPEN the main drain IMMEDIATELY, when test is complete.

Perform steps 1 through 20 of paragraph 4-B INSTALLATION, Placing the Valve in Service.

Verify that the water supply main control valve is open, all other valves are in their normal operating position. If equipped with

an external Anti-flood Device, the ½” anti-flood isolation valve must be OPEN and secured.

III. MAINTENANCE (See Figure 3)

WARNING: PRIOR TO SERVICING INTERNAL OPERATING PARTS OF THE DRY VALVE, TAKE THE FOLLOWING PRECAUTIONS.

Close the water supply main control valve, placing the system out of service.

Open the main drain located in the base of the dry valve.

Close the air (or nitrogen) supply to the dry system piping.

Relieve all pressure from the dry system piping. If the system has operated, open all auxiliary drains and the system Test Valve

to allow the system to drain completely.

Use the Dry Valve Reset Bar/Wrench, part number 02977BM, to loosen and remove hand-hole cover bolts (21) and remove

hand-hole cover (24).

CAUTION: CLAPPER ARM ASSEMBLY (8) AND CLAPPER ASSEMBLY (5) IS SPRING LOADED TO OPEN. NEVER PLACE HANDS INSIDE THE DRY VALVE IF THE CLAPPER ASSEMBLY IS LATCHED CLOSED.

Release latched (set) clapper assembly for service:

Insert the re-setting tool through the hole in hook assembly (15), across the cast fulcrum on top of clapper arm assembly

(8) until the re-setting tool contacts the stopping boss on top of clapper arm assembly (8).

Apply a downward force on the end (outside the valve) of the re-setting tool. Hook assembly (15) will slide toward the

hand-hole and off clapper arm assembly (8). The clapper arm assembly (8) and clapper assembly (5) will forcefully open,

impact against latch (2), and be trapped in the open position.

CAUTION: NEVER APPLY ANY LUBRICANT TO SEATS, GASKETS, OR ANY INTERNAL OPERATING PARTS OF THE DRY VALVE. PETROLEUM-BASED GREASE OR OIL WILL DAMAGE RUBBER COMPONENTS AND MAY PREVENT PROPER OPERATION OF THE DRY VALVE.

Recommended practice: When performing maintenance inside the dry valve with the clapper in the open position, cover the opening

to prevent tools or parts from dropping onto the seat or into the waterway.

To remove Clapper Rubber (19):

Use a 9/16” wrench to remove hex-head screw (17) and rubber retainer (18).

Remove clapper rubber (19) for inspection. If the clapper rubber shows signs of wear, such as cracking, cuts, or exces-

sively deep grooves where the rubber contacts the air or water seat, replace the rubber.

To re-install Clapper Rubber (19):

Place a new clapper rubber (19), over the center hub of rubber retainer (18).

Position retainer (18) (with rubber in place) against clapper assembly (5).

Replace and tighten hex-head screw (17). Do not over-tighten.

To remove Clapper Assembly (5):

While holding spring loaded clapper arm assembly (8) down, remove a retaining ring (7) from one end of clapper rod

(6a).

Release spring loaded clapper arm assembly (8) and allow it to latch in the open position.

6.

7.

8.

9.

10.

1.

2.

3.

4.

5.

6.

7.

8.

9.

1.

2.

3.

4.

5.

6.

a.

b.

7.

a.

b.

8.

a.

b.

c.

9.

a.

b.

Page 18: HYDRAULIC CALCULATIONS Alberta Street Public House

TECHNICAL DATA

February 25, 2011Dry 135h

DRY VALVEMODEL F-2

GROOVE/GROOVE

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

Slide rod (6a) out of clapper arm assembly (8) to free clapper assembly (5).

Remove clapper assembly (5) for inspection or replacement.

To re-install Clapper Assembly (5):

Reverse disassembly procedures a through d in step 9 above.

To remove Latch (2):

Remove ½” NPT pipe plug (4) (outside of valve) to expose latch pin (3).

While holding latch (2) with one hand, remove latch pin (3).

Remove latch (2).

To re-install Latch (2) and Latch Pin (3), reverse disassembly procedures a through c in step 11 above.

The internal member assembly of the dry valve consists of several sub-assemblies. To service these sub-assemblies, it is necessary

to disassemble the dry valve.

To disassemble The Dry Valve:

Disconnect the trim and remove the valve from the system piping.

Use the Dry Valve Reset Bar/Wrench, part number 02977BM, to remove hand-hole cover bolts (21) from base (22).

Remove housing (1) from base (22). Member assembly components (5-15), and (17-19, 21, 25) are accessible for replace-

ment.

When inspection and/or replacement of Member assembly components is complete Re-assemble the dry valve.

To re-assemble the dry valve:

Reverse disassembly procedures a through c in step 13 above.

Socket-set screw (23) will need adjustment. After the valve has been completely reassembled, latch the clapper in place.

With a 1/4” (6,35 mm) Allen wrench, turn the screw clockwise until it contacts the hook (24). Then, turn the screw one

complete turn counter-clockwise. Set the system and trip test the valve to verify proper operation of the valve.

To remove Hook Assembly (15):

Remove a retaining ring (7) from one end of hook rod (6b).

Slide rod (6b) out of the bushings in air plate assembly (11) to free hook assembly (15).

Remove hook assembly (15).

To re-install Hook Assembly (15):

Reverse disassembly procedures a through c in step 15 above.

To remove Clapper Arm Assembly (8) and Spring (9):

Remove a retaining ring (7) from one end of clapper arm rod (10).

Slide clapper arm rod (10) out of the bushings in air plate assembly (11) to free clapper arm assembly (8) taking care to

retrieve spring (9).

Remove clapper arm assembly (8), and spring (9).

To re-install Clapper Arm Assembly (8):

Reverse disassembly procedures a through c in step 17 above.

To remove Diaphragm (12) and Diaphragm Retainer (13):

Use a 9/16” wrench to remove hex-head screws (14).

Remove diaphragm retainer (13) and diaphragm (12) for replacement. If the diaphragm rubber shows signs of wear, such

as cracking or cuts, replace the rubber diaphragm.

To re-install Diaphragm (12) and Diaphragm Retainer (13):

Reverse disassembly procedures a and b in step 19 above.

When re-installing diaphragm retainer (13), cross tighten hex-head screws (14) to 20 ft. lbs. of torque for even compres-

sion of diaphragm (12).

When assembling base (22) to housing (1):

Invert housing (1) on work bench so holes for hand-hole cover bolts (21) are facing up.

Position complete member sub-assembly (5-15 & 17-19, 21, 25) with screw holes in diaphragm (12), aligned with

screw holes in inverted housing (1). Use care to align screw holes so hook assembly (15) properly aligns with set

screw (23).

Position base (22) over inverted housing (1) with member assembly (5-15 & 17-19, 21, 25). Align screw holes so ½”

(15 mm) NPT trim connection in base (22) aligns with ½” (15 mm) NPT trim connection in housing (1).

Install hand-hole cover bolts (21) finger tight only.

Cross-tighten all hand-hole cover bolts (21), to 90 ft. lbs. of torque to evenly compress diaphragm (12) and maintain

proper alignment of member sub-assembly (5-15 & 17-19, 21, 25).

7. AVAILABILITYThe Viking Model F-2 Dry Pipe Valve is available through a network of domestic and international distributors. See the Viking Corp.

Web site for closest distributor or contact The Viking Corporation.

c.

d.

10.

a.

11.

a.

b.

c.

12.

13.

a.

b.

c.

d.

14.

a.

b.

15.

a.

b.

c.

16.

a.

17.

a.

b.

c.

18.

a.

19.

a.

b.

20.

a.

b.

c.

i.

ii.

iii.

iv.

v.

Page 19: HYDRAULIC CALCULATIONS Alberta Street Public House

TECHNICAL DATA

February 25, 2011 Dry 135i

DRY VALVEMODEL F-2

GROOVE/GROOVE

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

Table 3 - Troubleshooting GuideCondition: Possible causes: Suggested action:

The valve trips when no

sprinkler has fused

Loss of air pressure in the

system

Check the system for leaks and check for proper air sup-

ply. A Viking Air Maintenance Device should be installed

on each system equipped with an automatic air supply.

Consider adding a maintenance air compressor.

An extreme pressure surge in

the water supply

Increase the air pressure on the system. The maximum

limit is 60 PSI (4.1 bar). Note: Increasing system pressure

may increase trip time of the dry valve.

Water constantly pass-

ing through the drip

check when the valve is

in the SET position

Water leaking over the wa-

ter seat into the intermediate

chamber

Inspect and clean the water seat and clapper rubber (see

step 5 of paragraph 4, Installation, Placing the Valve in

Service). Consider replacing the clapper rubber. If the wa-

ter seat has been pitted or damaged by debris, it may be

necessary to replace the base assembly.

Alarm test valve in the bypass

connection of the dry valve

trim not tightly closed

Verify that water is not getting past alarm test valve.

Air constantly passing

through the drip check

when the valve is in the

SET position

Air leaking over the air seat

into the intermediate cham-

ber

Inspect and clean the air seat and clapper rubber (see

step 5 of paragraph 4, Installation, Placing the Valve in

Service). Consider replacing the clapper rubber. If the air

seat has been pitted or damaged by debris, it may be

necessary to replace the air plate assembly.

Air leaking past the rubber

diaphragm

Inspect the rubber diaphragm for deterioration. If neces-

sary, replace the diaphragm.

Clapper will not latch

Incorrect resetting tool

Verify that the re-setting tool used is smooth and of the

proper strength and diameter* to provide the required

force at the appropriate angle to cause the latching hook

to slide over the clapper arm when setting the dry valve.*The Viking Re-setting tool is a 3/4” (19 mm) diameter cold rolled steel bar, chamfered at one end and a standard 15/16” hex-socket on other end. (PN 02977BM)

The hook not sliding on the

re-setting tool

File or grind the re-setting tool. Remove any rough spots

to provide a smooth sliding surface and proper clear-

ance.

Clapper rubber worn Replace the clapper rubber.

Internal parts damaged by

accidental application of high

pressure

Replace the valve member assembly.

The valve latches but

will not remain set

Improper resetting procedureSee paragraph 4, Installation, Placing the Valve in Serv-

ice

Inadequate air supplySee paragraph 4, Installation, Placing the Valve in Serv-

ice.

Air pressure and priming wa-

ter passing through the inter-

mediate chamber and out of

the drip check

Clean the air seat and the clapper rubber. Replace the

clapper rubber, if worn.

Page 20: HYDRAULIC CALCULATIONS Alberta Street Public House

TECHNICAL DATA

February 25, 2011Dry 135j

DRY VALVEMODEL F-2

GROOVE/GROOVE

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

Figure 3 -Replacement Parts

Form No. F_011507

ITEMNO.

3” & 4” 6” DESCRIPTION MATERIAL NO. REQ’D3” & 4” 6”

1 -- -- Housing Ductile Iron 65-45-12 1 1

2 07641 07641 Latch Brass UNS-C84400 1 1

3 08449 08449 Latch Pin Brass UNS-C36000 1 1

4 -- -- 1/2” NPT Pipe Plug Steel 1 1

5 * *Clapper Assembly Ductile Iron 65-45-12 1 1

(includes bushings) Tefl on® Coated Steel 2 2

6a * * Clapper Rod Brass UNS-C36000 1 1

6b * * Hook Rod Brass UNS-C36000 1 1

7 * * Retaining Ring Stainless Steel UNS-S15700 6 6

8 * *Clapper Arm Assembly Ductile Iron 65-45-12 1 1

(includes bushings) Tefl on® Coated Steel 4 4

9 * * Spring Type 302 Stn. Stl. Wire 1 1

10 * * Clapper Arm Rod Brass: UNS-C36000 1 1

11 * *Air Plate Assembly Ductile Iron 65-45-12 1 1

(includes bushings) Tefl on® Coated Steel 4 4

12 * * Diaphragm Nylon Reinforced EPDM 1 1

13 * * Diaphragm Retainer Ductile Iron 65-45-12 1 1

14 * * 3/8”-16 x 3/4” (19.1 mm) lg. Hex Head Cap Screw Zinc Plated Steel 10 12

15 * *Hook Assembly Ductile Iron 65-45-12 1 1

(includes bushings) Tefl on® Coated Steel 2 2

16 -- -- Water Seat Brass UNS-C84400 1 1

17 07932 07932 3/8”-16 x 1/2” (12.7 mm) lg. Hex Head Cap Screw Stainless Steel UNS-S30400 1 1

18 07659 07659 Rubber Retainer Stainless Steel UNS-S30400 1 1

19 07651 08487 Clapper Rubber Ethylene Propylene 1 1

20 * * Air Seat Brass UNS-C84400 1 1

21 02079A 02079A 5/8”-11 x 2” (50.8 mm) lg. Hex Head Cap Screw Steel 14 16

22 -- -- Base Ductile Iron 65-45-12 1 1

23 08056 08056 1/2”-13 x 1” (25.4 mm) lg. Socket Set Screw Brass UNS-C36000 1 1

24 05436C 05436C Cover Ductile Iron 65-45-12 1 1

25 04187B 04187B Cover Gasket EPDM, ASTM D2000 1 1

26 * * Square Cut Ring EPDM 1 1--Indicates replacement part not available* Indicates replacement part only available in a Sub-Assembly listed below.

SUB-ASSEMBLIES5-15, 17-19,

21, 25, 2614027 14028 Member Assembly Kit

15, 17-19 08324 08490 Clapper Assembly

Revised page replaces page 135a-j, dated November 29, 2010.

(Added new item 26 to the Replacement Parts list.)

Page 21: HYDRAULIC CALCULATIONS Alberta Street Public House

microfast® and microfastHP® quick

resPonse uPrigHt and conventional sPrinklers

tecHnical data

September 19, 2012

the viking corporation, 210 n industrial Park drive, Hastings mi 49058

telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: [email protected]

1. descriPtionViking Microfast® and MicrofastHP® Quick Response Upright and Conventional (Old

Style) Sprinklers are small, thermosensitive, glass-bulb spray sprinklers available

in several different finishes, temperature ratings, and K-Factors to meet design re-

quirements. The special Polyester, Polytetrafluoroethylene (PTFE), and Electroless

Nickel PTFE (ENT) coatings can be used in decorative applications where colors are

desired. In addition, these coatings have been investigated for installation in corrosive

atmospheres and are cULus listed as corrosion resistant as indicated in Approval

Chart 1. (Note: FM Global has no approval classification for PTFE and Polyester

coatings as corrosion resistant.)

2. listings and aPProvals

culus listed: Category VNIV

fm approved: Classes 2002 and 2020

nYc approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16

aBs certified: Certificate 04-HS407984B-PDA

vds approved: Certificates G4060054, G4060056, G4880046, G4930039, and G4980020

lPc approved: Ref. No. 096e/03, TE30401, and TE30872

ce certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40131,

0786-CPD-40171, and 0786-CPD-40278

med certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008

note: Other International approval certificates are available upon request.

Refer to Approval Chart 1 and Design Criteria on pages 51c-d for cULus Listing requirements, and refer to Approval Chart 2 and

Design Criteria on page 51e for FM Approval requirements that must be followed.

3. tecHnical dataSpeciications:Available since 1987.

Minimum Operating Pressure: 7 psi (0.5 bar)*

maximum Working Pressure: sprinklers vk315 and vk340 are rated for

use with water working pressures ranging from the minimum 7 psi

(0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres-

sure (HP) sprinklers can be identified by locating “250” stamped on

the deflector. all other Part nos. not mentioned above are rated to a

maximum 175 psi (12 bar) wwp.

Factory tested hydrostatically to 500 psi (34.5 bar)

Testing: U.S.A. Patent No. 4,831,870

Thread size: Refer to the Approval Charts

Nominal K-Factor: Refer to the Approval Charts

Glass-bulb fluid temperature rated to -65 °F (-55 °C)

Overall Length: Refer to the Approval Charts

*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE

Approvals ONLY is 5 psi (0.35 bar).

material standards:Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 12978, 06766B, 07060, and 12281. Brass UNS-C84400 for all

other sprinklers.

Deflector: Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 12978, 06764B, and 12281. Copper UNS-C19500 for

Sprinklers 06665B, 07060, and 14817. Brass UNS-C26000 for all other Sprinklers.

Bushing (for Sprinklers 06719B, 06717B, and 12286): Brass UNS-C36000

Bulb: Glass, nominal 3 mm diameter

Form No. F_080488

viking technical data may be found on

the viking corporation’s Web site at

http://www.vikinggroupinc.com.

the Web site may include a more recent

edition of this technical data Page.

Sprinkler 51a

Replaces page 51a-e, dated July 12, 2012. (Added Electroless Nickel PTFE

Coating)

Page 22: HYDRAULIC CALCULATIONS Alberta Street Public House

tecHnical data

September 19, 2012

the viking corporation, 210 n industrial Park drive, Hastings mi 49058

telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: [email protected]

microfast® and microfastHP® quick

resPonse uPrigHt and conventional sPrinklers

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE TapeScrew: Brass UNS-C36000Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE CoatedFor Polyester Coated Sprinklers: Belleville Spring-ExposedFor ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap - ENT plated.ordering information: (Also refer to the current Viking price list.)Order Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers by first adding the appropriate suffix for

the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, Chrome-Enloy® = F, White Polyester = M-/W, Black Polyester = M-/B, and Black PTFE = N, ENT = JNTemperature Suffix (°F/°C): 135°/57° = A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = GFor example, sprinkler VK300 with a 1/2” thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 12978AB

available finishes and temperature ratings: Refer to Table 1.

accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.)

sprinkler Wrench: Standard Wrench: Part No. 10896W/B (available since 2000)

sprinkler cabinets:A. Six-head capacity: Part No. 01724A (available since 1971)B. Twelve-head capacity: Part No. 01725A (available since 1971)

4. installationRefer to appropriate NFPA Installation Standards.

5. oPerationDuring fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.

6. insPections, tests and maintenanceRefer to NFPA 25 for Inspection, Testing and Maintenance requirements.

7. availaBilitYThe Viking Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.

8. guaranteeFor details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

Sprinkler 51b

taBle 1: availaBle sPrinkler temPerature ratings and finisHes

sprinkler temperature classification

sprinkler nominal temperature rating1

maximum ambient ceiling temperature2 Bulb color

Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange

Ordinary 155 °F (68 °C) 100 °F (38 °C) Red

Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow

Intermediate 200 °F (93 °C) 150 °F (65 °C) Green

High 286 °F (141 °C) 225 °F (107 °C) Blue

sprinkler finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, Black PTFE, and ENT

corrosion-resistant coatings3: White Polyester, Black Polyester, and Black PTFE. ENT in all tempurature ratings except 135 °F (57 °C)

footnotes1 The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.

Refer to specific installation standards.3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on pages 51c-e. These tests

cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester, ENT, and PTFE coatings. For ENT coated automatic sprinklers, the waterway is coated.

Page 23: HYDRAULIC CALCULATIONS Alberta Street Public House

microfast® and microfastHP® quick

resPonse uPrigHt and conventional sPrinklers

tecHnical data

September 19, 2012

the viking corporation, 210 n industrial Park drive, Hastings mi 49058

telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: [email protected]

approval chart 1 (ul)microfast® and microfastHP® quick response

upright and conventional sprinklers

maximum 175 Psi (12 bar) WWP

Base Part

number1sin

thread size nominal k-factor overall length listings and approvals3

(refer also to design criteria on page 51d.)

nPt BsP u.s. metric2 inches mm culus4 nYc8 vds lPcB

upright-standard orifice

12978 VK300 1/2” 15 mm 5.6 80.6 2-3/16 56 A1, B4 See Footnote 7. -- -- -- --

07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 -- -- A2 A2 B212 B215

conventional-standard orifice

06766B VK310 1/2” 15 mm 5.6 80.6 2-3/16 56 A2 A2 -- A2 B212 B215

upright-large orifice

06665B VK350 3/4” -- 8.0 115.2 2-5/16 59 A1, B4 A1 A2 A2 B212 --

14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 A1, B4 A1 A2 A2 B212 --

06764B VK350 1/2” 15 mm 8.0 115.2 2-5/16 59 A1, B4 A1 A2 -- A213 --

conventional-large orifice

06768B VK354 3/4” 20 mm 8.0 115.2 2-5/16 59 A1 A2 -- A2 B212 --

upright-small orifice11

06717B11 VK325 1/2” 15 mm 2.8 40.3 2-3/16 56 A1 A1 -- -- -- --

06719B11 VK327 1/2” 15 mm 4.2 57 2-3/16 56 A1 A1 -- -- -- --

06931B11 VK327 -- 10 mm 4.2 57 2-3/16 56 -- -- A2 -- C314 --

maximum 250 Psi (17 bar) WWP

upright-standard orifice

Base Part

number1sin

thread size nominal k-factor overall length listings and approvals3

(refer also to design criteria on page 51d.)

nPt BsP u.s. metric2 inches mm culus4 nYc9 vds lPcB

12281 VK315 1/2” 15 mm 5.6 80.6 2-3/16 56 A1 A1 -- -- -- --

upright-small orifice10

1228611 VK340 1/2” 15 mm 2.8 40.3 2-3/16 56 A1 A1 -- -- -- --

approved temperature ratings

A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and

286 °F (141°C)

B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C)

C - 155 °F (68 °C)

approved finishes

1 - Brass, Chrome-Enloy®, White Polyester5,6, Black Polyester5,6,

and Black PTFE5

2 - Brass, Chrome-Enloy®, White Polyester5,6, and Black

Polyester5,6

3 - Brass and Chrome-Enloy®

4 - ENT5

footnotes1 Base part number is shown. For complete part number, refer to Viking’s current price schedule.2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.5 cULus Listed as corrosion resistant.6 Other colors are available on request with the same Listings and Approvals as the standard colors.7 Meets New York City requirements, effective July 1, 2008.8 Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA.9 Accepted for use, City of New York Department of Buildings, MEA 89-92-E, Vol. 16.10 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only.

exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized.11The sprinkler orifice is bushed.12 Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003.13 Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40278. 14 Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40131.15 MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008.

Sprinkler 51c

Page 24: HYDRAULIC CALCULATIONS Alberta Street Public House

tecHnical data

September 19, 2012

the viking corporation, 210 n industrial Park drive, Hastings mi 49058

telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: [email protected]

microfast® and microfastHP® quick

resPonse uPrigHt and conventional sPrinklers

Sprinkler 51d

figure 1:

standard sprinkler Wrench 10896W/B

design criteria - ul (Also refer to Approval Chart 1 on page 51c)

culus listing requirements:

Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in

accordance with the latest edition of NFPA 13 for standard spray sprinklers, or old style (conventional) sprinklers.

Designed for use in Light and Ordinary Hazard occupancies (exception: small orifice sprinklers are limited to Light Hazard where allowed by the

installation standards being applied, with hydraulically calculated wet systems only).

The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. For conventional sprinklers, refer to

the installation guidelines for old style (conventional) sprinklers.

imPortant: always refer to Bulletin form no. f_091699 - care and Handling of sprinklers. also refer to page

qr1-3 for general care, installation, and maintenance information. viking sprinklers are to be installed in accor-

dance with the latest edition of viking technical data, the appropriate standards of nfPa, lPcB, aPsad, vds

or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards,

whenever applicable.

Page 25: HYDRAULIC CALCULATIONS Alberta Street Public House

microfast® and microfastHP® quick

resPonse uPrigHt and conventional sPrinklers

tecHnical data

September 19, 2012

the viking corporation, 210 n industrial Park drive, Hastings mi 49058

telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: [email protected]

Sprinkler 51e

design criteria - fm (Also refer to Approval Chart 2 above.)

fm approval requirements:

The sprinklers indicated in Approval Chart 2 are FM Approved as quick response non-storage upright sprinklers as indicated in the FM Approval Guide.

For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM

Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope

and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.

note: the fm installation guidelines may differ from culus and/or nfPa criteria.

imPortant: always refer to Bulletin form no. f_091699 - care and Handling of sprinklers. also refer to page

qr1-3 for general care, installation, and maintenance information. viking sprinklers are to be installed in ac-

cordance with the latest edition of viking technical data, the appropriate standards of nfPa, fm global, lPcB,

aPsad, vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and

standards, whenever applicable.

approval chart 2 (fm)microfast® quick response upright sprinklers

maximum 175 Psi (12 bar) WWP

Base Part

number1sin

thread size nominal k-factor overall length fm approvals3

(refer also to design criteria below.)nPt BsP u.s. metric2 inches mm

standard orifice

12978 VK300 1/2” 15 mm 5.6 80.6 2-3/16 56 A2, B3

07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 A2

large orifice

06665B VK350 3/4” -- 8.0 115.2 2-5/16 59 A2, B3

14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 A2, B3

06764B VK350 1/2” 15 mm 8.0 115.2 2-5/16 59 A2, B3

small orifice4

06717B6 VK325 1/2” 15 mm 2.8 40.3 2-3/16 56 A1

approved temperature ratings

A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C)

B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C)

approved finishes

1 - Brass and Chrome-Enloy®

2 - Brass, Chrome-Enloy®, White Polyester5, and

Black Polyester5

3 - ENT

footnotes

1 Base part number is shown. For complete part number, refer to Viking’s current price schedule.

2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

3 This table shows the FM Approvals available at the time of printing. Check with the manufacturer for any additional approvals.

4 FM Approved as quick response non-storage pendent sprinklers. For specific application and installation requirements, reference the latest appli-

cable FM Loss Prevention Data Sheets (including Data Sheet 2-0).5 Other colors are available on request with the same Approvals as the standard colors.6 The sprinkler orifice is bushed.

Page 26: HYDRAULIC CALCULATIONS Alberta Street Public House

Form No. F_080488

tHis Page

intentionallY

left Blank

Replaces page 51a-e, dated July 12, 2012. (Added Electroless Nickel PTFE

Coating)