Hv Solutions Catalog

48
SOUTHWIRE HV SOLUTIONS High Voltage Product Catalog 69kV – 230kV Cables & Accessories

Transcript of Hv Solutions Catalog

Page 1: Hv Solutions Catalog

SOUTHWIRE

HV SOLUTIONS™

High Voltage Product Catalog69kV – 230kV Cables & Accessories

Page 2: Hv Solutions Catalog

ABOUT SOUTHWIREA technology leader for over 60 years, Southwire Company is the leading wire and cable producer in North America. Southwire manufactures utility cable products including overhead and underground transmission and distribution cable. For more information about Southwire products, services, and technical resources please visit www.southwire.com.

SOUTHWIRE COMPANYONE SOUTHWIRE DRIVECARROLLTON, GA30119

1.800.444.1700www.southwire.com

TABLE OF CONTENTSSection 4: 138 kV Cables Copper Conductor, Traditional Wall 850 mil XLPE Copper Corrugated Sheath

Copper Conductor, SW Standard Wall XLPE Copper Corrugated Sheath

Aluminum Conductor, Traditional Wall 850 mil XLPE Aluminum Corrugated Sheath

Aluminum Conductor, SW Standard Wall XLPE Aluminum Corrugated Sheath

Copper Conductor, Traditional Wall 850 mil XLPE Copper Neutrals, Copper Composite Laminate Sheath

Copper Conductor, SW Standard Wall XLPE Copper Neutrals, Copper Composite Laminate Sheath

Aluminum Conductor, Traditional Wall 850 mil XLPE Copper Neutrals, Aluminum Composite Laminate Sheath

Aluminum Conductor, SW Standard Wall XLPE Copper Neutral, Aluminum Composite Laminate Sheath

Section 5: 161 kV Cables Copper Conductor, SW Standard Wall XLPE Copper Corrugated Sheath

Aluminum Conductor, SW Standard Wall XLPE Aluminum Corrugated Sheath

Copper Conductor, SW Standard Wall XLPE Copper Neutrals, Copper Composite Laminate Sheath

Aluminum Conductor, SW Standard Wall XLPE Copper Neutral, Aluminum Composite Laminate Sheath

Section 6: 230 kV Cables Copper Conductor, SW Standard Wall XLPE Copper Corrugated Sheath

Aluminum Conductor, SW Standard Wall XLPE Aluminum Corrugated Sheath

Copper Conductor, SW Standard Wall XLPE Copper Neutrals, Copper Composite Laminate Sheath

Aluminum Conductor, SW Standard Wall XLPE Copper Neutral, Aluminum Composite Laminate Sheath

Section 7: AccessoriesComponents

Design Criteria

Outdoor Termination

Switchgear & Transformer Termination

Joint

Aluminum Cable Clamps

DISCLAIMERWhile great care has been employed to ensure that the applications, tables, standards and references and other information contained herein are free of errors, absolutely no warranties, either expressed or implied, are made as to the accuracy or completeness of any such tables and formulas contained herein.

Neither Southwire nor anyone else who has been involved in the creation, production or delivery of this publication shall be liable for any direct, indirect, consequential, or incidental damages arising out of the use, the results of the use, or inability to use such publication, even if Southwire has been advised of the possibility of such damages or claim. Some states do not allow the exclusion or limitation for consequential incidental damages, so the above limitation may not apply to you.

SOUTHWIRE SOLUTIONS FOR HigH Voltage UndergroUndCABLES

• XLPE Cables 69 through 230kV with Copper and Aluminum conductors through 4,000 kcmil

• Concentric neutrals, welded and corrugated sheathes in Copper or Aluminum and composite laminate sheathes in Copper or Aluminum cover all applications

• XLPE cables through 345 kV with cross sections up to 5,000 kcmil on special request

• Southwire has supplied over four million feet of HV cable to customers in North America

• We offer many options such as integrated or external optical fiber for distributed temperature sensing, fire retardant cable jackets and cables with the highest fault current ratings

• Special executions include long lengths and pipe retrofit cables

ACCESSORIES

• Our accessories for HV cable use premolded LSR stress cone technology throughout, made by nkt cables in Germany

• Outdoor terminations with porcelain or silicone rubber composite insulators

• GIS and Transformer terminations to IEC 60859• Dry “Plug and Socket” compact switchgear and

transformer terminations through 145 kV • Premolded cable splices• Splice options include shield breaks, metal

casing, DTS fiber integration, capacitive PD detection ports, bolted or compression connectors and cable size transition

• Transitions between different cable insulation types are available

SERVICES

• Feasibility studies and conceptual engineering

• Ampacity Studies• Detailed underground system design• Pulling calculations• Cable pulling• Splicing and terminating services • Sheath bonding and grounding• Commissioning, testing• AC Resonant and PD testing• Construction Management• Full turnkey projects including

civil works• Maintenance• Fault location• Emergency and repair services

Section 1: HTS Triax® Superconducting Cable

Section 2: 69 kV Cables Copper Conductor, Traditional Wall 650 mil XLPE Copper Corrugated Sheath

Copper Conductor, SW Standard Wall XLPE Copper Corrugated Sheath

Aluminum Conductor, Traditional Wall 650 mil XLPE Aluminum Corrugated Sheath

Aluminum Conductor, SW Standard Wall XLPE Aluminum Corrugated Sheath

Copper Conductor, Traditional Wall 650 mil XLPE Copper Concentric Neutral

Aluminum Conductor, Traditional Wall 650 mil XLPE Copper Concentric Neutral

Copper Conductor, Traditional Wall 650 mil XLPE Copper Neutral, Copper Composite Laminate Sheath

Copper Conductor, SW Standard Wall XLPE Copper Neutral, Copper Composite Laminate Sheath

Aluminum Conductor, Traditional Wall 650 mil XLPE Copper Neutral, Aluminum Composite Laminate Sheath

Aluminum Conductor, SW Standard Wall XLPE Copper Neutral, Aluminum Composite Laminate Sheath

Section 3: 115 kV CablesCopper Conductor, Traditional Wall 800 mil XLPE Copper Corrugated Sheath

Copper Conductor, SW Standard Wall XLPE Copper Corrugated Sheath

Aluminum Conductor, Traditional Wall 800 mil XLPE Aluminum Corrugated Sheath

Aluminum Conductor, SW Standard Wall XLPE Aluminum Corrugated Sheath

Copper Conductor, Traditional Wall 800 mil XLPE Copper Neutrals, Copper Composite Laminate Sheath

Copper Conductor, SW Standard Wall XLPE Copper Neutrals, Copper Composite Laminate Sheath

Aluminum Conductor, Traditional Wall 800 mil XLPE Copper Neutrals, Aluminum Composite Laminate Sheath

Aluminum Conductor, SW Standard Wall XLPE Copper Neutral, Aluminum Composite Laminate Sheath

1

5

7

9

11

13

15

17

19

21

23

27

29

31

33

35

37

39

41

45

47

49

51

53

55

57

59

63

65

67

69

73

75

77

79

83

84

85

87

89

90

Page 3: Hv Solutions Catalog

HTS Triax® Superconducting Cable

1 2

Section 1HtS triax®

HtS triax®

MORE POWER TO MORE PEOPLE

compact deSignSHTS Triax allows for a retrofit of existing underground pipe and duct systems to increase power delivery, as well as reduced substation footprint in dense urban areas.

eliminate emFHTS Triax cable is fully shielded.

tHermal independence From SUrroUnding enVironmentHTS cables utilize high performance thermal insulation to maintain operating temperatures of -200oC. This isolates the cable from the surrounding environment and eliminates the need to special back-fill.

5x cUrrent carrying capacity oF copper cableSHTS Triax operates at extremely high currents in normal, steady state conditions.

enVironmentally Friendly cooling mediUmLiquid nitrogen cooling fluid is non-toxic and environmentally friendly.

diStribUtion SUbStationS togetHer on lV Side oF tranSFormer HTS cables at MV can easily carry full station load (80-150 MW) at steady state operation. Benefits include increased asset utilization (share transformer capacity between distribution substations) and increased meshing of distribution grid in dense urban areas.

HTS Triax® Superconducting Cable is Southwire’s unique and proprietary cable design. The Triax cable locates the three electrical phases and neutral conductor concentrically on a single core. This design drastically reduces material usage and cooling requirements of the system, and therefore cost. Applications for this advanced technology address right of way and substation congestion constraints in many of today’s urban environments.

SUperc

on

dU

ctin

g ca

ble

Page 4: Hv Solutions Catalog

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

CONDUCTOR MATERIAL AND SIzEConductor material is a matter of both customer preference and required current carrying capacity

• Copper conductor common for larger loads

• When both copper and aluminum conductors can meet your requirements, the more economical solution will be a function of the metal and the cable component costs

INSULATION THICKNESS• For cables with a radial moisture barrier, “Southwire Standard

Wall” reduced insulation thicknesses within the stress limits in AEIC specification CS9 are recommended

• Cables referred to by “Traditional Wall” insulation (650 mils) follow the traditional insulation wall practice referenced in ICEA standard S-108-720 appendix F as still specified by a number of customers and utilities

• For applications requiring smaller cable diameters, specific designs are available upon request

SHEATH MATERIAL• Copper and aluminum corrugated sheaths offer the best

mechanical and moisture protection for your HV cable, and copper will provide better short circuit performance and improved connectability

• Full wall cables with concentric neutrals are an economical option for mostly dry environments

• Composite laminate sheaths in both copper and aluminum that offer excellent protection against moisture ingress

JACKET• Standard outer jacket: extruded LLDPE with a co-extruded outer

semi-conductive polyethylene layer for jacket integrity testing

• Halogen Free Fire Retardant (HFFR) compounds are available upon request for installations in cable trays and ventilated troughs

3 4

Section 269 kV

power c

ables

Page 5: Hv Solutions Catalog

conductor Size in kcmil1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Diameter over Insulation in 2.21 2.39 2.53 2.67 2.79 2.90 3.00 3.26 3.42 3.58 3.71

mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2 82.8 86.9 90.8 94.2

Diameter over Sheath in 2.68 2.88 3.04 3.19 3.32 3.44 3.56 3.85 4.03 4.20 4.34

mm 68.1 73.2 77.2 81.0 84.3 87.4 90.4 97.8 102.3 106.6 110.3

Overall Jacket Diameter in 2.96 3.16 3.33 3.47 3.60 3.72 3.84 4.13 4.31 4.48 4.62

mm 75.2 80.3 84.6 88.1 91.4 94.5 97.5 104.9 109.4 113.7 117.4

Total Weight lbs/ft 4.8 5.9 6.9 7.9 8.8 9.8 10.7 12.9 14.8 16.7 18.5

Min. Bending Radius (install/perm.) in in 59/44 63/47 67/50 69/52 72/54 74/56 77/58 83/62 86/65 90/67 92/69

Maximum Pulling Tension lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Width in 126x95 126x95 126x95 126x95 126x95 126x95 150x95 158x95 150x95 150x95 150x95

Shipping Reel Capacity* ft 3,000 3,000 3,000 3,000 3,000 2,950 3,000 2,800 2,500 2,200 1,975

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 3.2 3.1 3.1 3.1

Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9

Short circuit for 0.5s3

Conductor kA 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410

Sheath kA 33.6 36.1 38.2 40 41.6 43.2 44.6 48.3 50.5 52.6 54.4

conductor resistance

DC @ 20o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003

DC @ 90o C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 43.8 49.5 54.2 58.4 62.1 65.5 68.7 76.5 81.5 86.2 90.3

Charging Current Amps/kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 1.15 1.22 1.29 1.36

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 600 740 820 960 1040 1110 1180 1390 1506 1595 1673

Power Rating MVA 72 89 98 115 125 133 142 167 180 191 200

Typical Double Ductbank4 Amps 510 630 710 810 880 940 990 1181 1276 1432 1517

Power Rating MVA 61 76 85 97 106 113 119 142 153 172 182

69 kV XLPE – Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 72.5

BIL Rating 350

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 120 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

tra

ditio

na

l Wa

ll 650 mil xlpe c

opper c

orrU

gated

SHeatH

5 6

Section 269 kV power cables

69 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or Milliken• Super Smooth Conductor Shield• Super Clean XLPE Insulation• Traditional Wall - 650 mil XLPE

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Copper Corrugated Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.3 Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current.4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 650 MIL XLPE COPPER CORRUgATED SHEATH

Page 6: Hv Solutions Catalog

69 kV XLPE – Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 72.5

BIL Rating 350

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 120 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

7 8

Section 269 kV power cables

69 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or Milliken• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 430 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Copper Corrugated Sheath• Polyethylene Jacket with Extruded Semi-

Conductive Outer Layer

SW STANDARD WALL XLPE COPPER CORRUgATED SHEATH

conductor Size in kcmil1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Insulation Thickness mils 520 490 470 450 450 440 430 430 440 450 450

mm 20.5 19.3 18.5 17.7 17.7 17.3 16.9 16.9 17.3 17.7 17.7

Diameter over Insulation in 1.95 2.07 2.18 2.27 2.39 2.48 2.56 2.82 2.92 3.1 3.23

mm 49.5 52.5 55.4 57.7 60.7 63.0 65.0 71.6 74.2 78.7 82.0

Diameter over Sheath in 2.39 2.51 2.63 2.73 2.87 2.96 3.05 3.35 3.44 3.64 3.78

mm 60.7 63.8 66.8 69.3 72.9 75.2 77.5 85.0 87.4 92.5 96.0

Overall Jacket Diameter in 2.67 2.80 2.91 3.01 3.15 3.24 3.33 3.63 3.72 3.92 4.06

mm 67.8 71.0 73.9 76.5 80.0 82.3 84.6 92.1 94.5 99.6 103.1

Total Weight lbs/ft 4.2 5.2 6.1 6.9 7.9 8.8 9.6 11.7 13.3 15.3 17

Min. Bending Radius (install/

perm.)in 53/40 56/42 58/44 60/45 63/47 65/49 67/50 73/54 74/56 78/59 81/61

Maximum Pulling Tension lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 126x95 150x95 150x95 158x95

Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,750 2,400 2,100

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3 4.2 4.1

Insulation Shield kV/mm 2.1 2.4 2.6 2.7 2.8 2.9 3.0 3.0 3.0 3.0 3.0

Short circuit for 0.5s3

Conductor kA 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410

Sheath kA 29.9 31.5 33 34.2 35.9 37.1 38.2 41.9 43.1 45.5 47.4

conductor resistance

DC @ 20o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003

DC @ 90o C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 51.1 60.6 68.9 77.1 82.4 88.9 95.3 107.1 108.6 113.3 119.2

Charging Current Amps/kft 0.74 0.91 1.04 1.16 1.24 1.34 1.43 1.31 1.63 1.7 1.79

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 600 750 870 970 1060 1130 1200 1422 1544 1632 1714

Power Rating MVA 72 90 104 116 127 136 144 170 185 196 205

Typical Double Ductbank4 Amps 520 640 740 820 890 950 1000 1202 1303 1377 1445

Power Rating MVA 63 77 89 98 107 114 120 144 156 165 173

SW Sta

nd

ard

Wa

ll xlpe co

pper co

rrUg

ated SH

eatH

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.

3 Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current.

4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

Page 7: Hv Solutions Catalog

conductor Size in kcmil 500 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61

mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9

Diameter over Insulation in 2.21 2.39 2.53 2.67 2.79 2.90 3.00

mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2

Diameter over Sheath in 2.78 2.98 3.15 3.30 3.43 3.55 3.67

mm 70.6 75.7 80.0 83.7 87.1 90.2 93.2

Overall Jacket Diameter in 3.06 3.26 3.43 3.58 3.71 3.83 3.95

mm 77.7 82.8 87.1 90.8 94.2 97.3 100.3

Total Weight lbs/ft 3.2 3.6 4.1 4.5 4.9 5.3 5.7

Min. Bending Radius (install/perm.) in 61/46 65/49 69/51 72/54 74/56 77/57 79/59

Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 150x95 150x95

Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 2,950 3,000 3,000

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3

Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8

Short circuit for 0.5s2

Conductor kA 33.8 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 38 40.7 43 45 46.9 48.6 50.1

conductor resistance

DC @ 20o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.044 0.030 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 43.8 49.5 54.2 58.4 62.1 65.5 68.7

Charging Current Amps/kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 470 580 680 770 840 910 970

Power Rating MVA 57 70 82 93 101 109 116

Typical Double Ductbank3 Amps 400 500 580 650 710 770 820

Power Rating MVA 48 60 70 78 85 93 98

69 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 72.5

BIL Rating 350

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 120 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

tra

ditio

na

l Wa

ll 650 mil xlpe a

lUm

inU

m c

orrU

gated

SHeatH

9 10

Section 269 kV power cables

69 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield• Super Clean XLPE Insulation• Traditional Wall - 650 mil XLPE

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Aluminum Corrugated Sheath• Polyethylene Jacket with Extruded Semi-

Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current.3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 650 MIL XLPE ALUMINUM CORRUgATED SHEATH

Page 8: Hv Solutions Catalog

conductor Size in kcmil 500 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61

mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9

Insulation Thickness mils 520 490 470 450 450 440 430

mm 20.5 19.3 18.5 17.7 17.7 17.3 16.9

Diameter over Insulation in 1.95 2.07 2.18 2.27 2.39 2.48 2.56

mm 49.5 52.6 55.4 57.7 60.7 63.0 65.0

Diameter over Sheath in 2.47 2.61 2.73 2.83 2.96 3.06 3.15

mm 62.7 66.3 69.3 71.9 75.2 77.7 80.0

Overall Jacket Diameter in 2.75 2.89 3.01 3.11 3.24 3.34 3.43

mm 69.9 73.4 76.5 79.0 82.3 84.8 87.1

Total Weight lbs/ft 2.7 3.0 3.4 3.7 4.1 4.4 4.7

Min. Bending Radius (install/perm.) in 55/41 58/43 60/45 62/47 65/49 67/50 69/51

Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95

Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 4.5 4.5 4.5 3.4 4.5 4.5 4.5

Insulation Shield kV/mm 2.1 2.4 2.6 1.8 2.8 2.9 3.0

Short circuit for 0.5s2

Conductor kA 33.8 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 33.8 35.6 37.3 38.7 40.5 41.8 43.1

conductor resistance

DC @ 20o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.044 0.030 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 51.1 60.6 68.9 77.1 82.4 88.9 95.3

Charging Current Amps/kft 0.77 0.91 1.04 1.16 1.24 1.34 1.43

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 470 590 690 780 860 920 990

Power Rating MVA 57 71 83 94 103 110 119

Typical Double Ductbank3 Amps 410 510 590 660 720 780 820

Power Rating MVA 49 61 71 79 87 94 98

69 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 72.5

BIL Rating 350

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 120 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll xlpe alU

min

Um

co

rrUg

ated SH

eatH

11 12

Section 269 kV power cables

69 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 430 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Aluminum Corrugated Sheath• Polyethylene Jacket with Extruded Semi-

Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current.3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE ALUMINUM CORRUgATED SHEATH

Page 9: Hv Solutions Catalog

conductor Size in kcmil1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Diameter over Insulation in 2.21 2.39 2.53 2.67 2.79 2.90 3.00 3.18 3.34 3.5 3.63

mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2 80.8 84.9 88.9 92.2

Diameter over Neutrals in 2.56 2.74 2.88 3.02 3.14 3.25 3.35 3.53 3.69 3.84 3.98

mm 65.0 69.6 73.2 76.7 79.8 82.6 85.1 89.6 93.7 97.6 101.1

Overall Jacket Diameter in 2.86 3.04 3.18 3.32 3.44 3.55 3.66 3.83 3.99 4.15 4.28

(mm) 72.6 77.2 80.8 84.3 87.4 90.2 93.0 97.4 101.4 105.4 108.7

Total Weight lbs/ft 4.2 5.2 6.1 7.1 8.0 8.9 9.8 11.6 13.4 15.2 17

Min. Bending Radius (install/

perm.)in 57/43 61/46 64/48 66/50 69/52 71/53 73/55 77/57 80/60 83/62 86/64

Maximum Pulling Tension lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 150x95 150x95 150x95 150x95

Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 3,000 3,000 2,950 3,000 2,700 2,400 2,150

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 3.2 3.1 3.1 3.0

Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9

Short circuit for 0.5s3

Conductor kA 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410

Nuetrals kA 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6 35.6

conductor resistance

DC @ 20o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003

DC @ 90o C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 43.8 49.5 54.2 58.4 62.1 65.5 68.7 74.4 81.4 83.7 90.3

Charging Current Amps/kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 1.12 1.22 1.26 1.36

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 610 760 880 980 1070 1150 1210 1456 1600 1709 1814

Power Rating MVA 73 91 106 118 128 138 145 175 192 205 217

Typical Double Ductbank4 Amps 520 640 740 830 900 960 1020 1226 1341 1432 1517

Power Rating MVA 63 77 89 100 108 115 122 147 161 172 182

69 kV XLPE - Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 72.5

BIL Rating 350

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 120 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

tra

ditio

na

l Wa

ll 650 mil xlpe c

opper c

on

cen

tric n

eUtr

alS

13 14

Section 269 kV power cables

69 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or Milliken• Super Smooth Conductor Shield• Super Clean XLPE Insulation• Traditional Wall - 650 mil XLPE

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Concentric Neutrals• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.3 Declared Values are for 80 x 14 AWG copper wire. Larger wires can accommodate more current.4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 650 MIL XLPE COPPER CONCENTRIC NEUTRALS

Page 10: Hv Solutions Catalog

conductor Size in kcmil 500 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61

mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9

Diameter over Insulation in 2.21 2.39 2.53 2.67 2.79 2.90 3.00

mm 56.1 60.7 64.3 67.8 70.9 73.7 76.2

Diameter over Neutral in 2.56 2.74 2.88 3.02 3.14 3.25 3.35

mm 65.0 69.6 73.2 76.7 79.8 82.6 85.1

Overall Jacket Diameter in 2.86 3.04 3.18 3.32 3.44 3.55 3.66

mm 72.6 77.2 80.8 84.3 87.4 90.2 93.0

Total Weight lbs/ft 3.1 4.1 4.5 4.9 5.2 5.6 6.0

Min. Bending Radius (install/perm.) in in 57/43 61/46 64/48 66/50 69/52 71/53 73/55

Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95

Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3

Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8

Short circuit for 0.5s2

Conductor kA 33.8 50.8 67.7 84.6 101.5 118.5 135.4

Nuetrals kA 35.6 35.6 35.6 35.6 35.6 35.6 35.6

conductor resistance

DC @ 20o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.044 0.030 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 43.9 49.5 54.2 58.4 62.1 65.5 68.7

Charging Current Amps/kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 480 600 700 780 860 930 1000

Power Rating MVA 58 72 84 94 103 112 120

Typical Double Ductbank3 Amps 410 510 590 660 730 780 830

Power Rating MVA 49 61 71 79 88 94 100

69 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 72.5

BIL Rating 350

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 120 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

tra

ditio

na

l Wa

ll 650 mil xlpe c

opper c

on

cen

tric n

eUtr

alS

15 16

Section 269 kV power cables

69 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield• Super Clean XLPE Insulation• Traditional Wall - 650 mil XLPE

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Concentric Neutrals• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared Values are for 80 x 14 AWG copper wire. Larger wires can accommodate more current.3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 650 MIL XLPE COPPER CONCENTRIC NEUTRALS

Page 11: Hv Solutions Catalog

conductor Size in kcmil1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.78 1.98 2.08 2.21

mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 45.2 50.2 52.8 56.1

Diameter over Insulation in 2.21 2.39 2.54 2.67 2.79 2.90 3.00 3.18 3.34 3.5 3.63

mm 56.1 60.7 64.5 67.8 70.9 73.7 76.2 80.8 84.8 88.9 92.2

Diameter over Sheath in 2.59 2.77 2.92 3.06 3.18 3.29 3.39 3.59 3.75 3.91 4.04

mm 65.8 70.4 74.2 77.7 80.8 83.6 86.1 91.2 95.3 99.3 102.6

Overall Jacket Diameter in 2.91 3.09 3.24 3.38 3.50 3.61 3.71 3.91 4.07 4.23 4.36

mm 73.9 78.5 82.3 85.9 88.9 91.7 94.2 99.3 103.4 107.4 110.7

Total Weight lbs/ft 4.5 5.5 6.5 7.4 8.4 9.3 10.2 12.1 13.8 15.7 17.5

Min. Bending Radius (install/

perm.)in 58/44 62/46 65/49 68/51 70/53 72/54 74/56 78/59 81/61 85/63 87/65

Maximum Pulling Tension lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Width in 126x95 126x95 126x95 138x95 138x95 138x95 150x95 150x95 150x95 150x95 150x95

Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,650 2350 2100

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3 3.2 3.1 3.1 3.0

Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8 1.9 1.9 1.9 1.9

Short circuit for 0.5s3

Conductor kA 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410

Sheath kA 42.3 42.8 43.2 43.5 43.9 44.1 44.4 44.9 45.4 45.8 46.1

conductor resistance

DC @ 20o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003

DC @ 90o C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 43.8 49.5 54.2 58.4 62.1 65.5 68.7 74.4 81.4 83.7 90.3

Charging Current Amps/kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03 1.12 1.22 1.26 1.36

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 610 760 880 980 1070 1150 1210 1456 1600 1709 1814

Power Rating MVA 73 91 106 118 128 138 145 175 192 205 217

Typical Double Ductbank4 Amps 520 640 740 830 900 960 1020 1226 1341 1432 1517

Power Rating MVA 63 77 89 100 108 115 122 147 161 172 182

69 kV XLPE - Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 72.5

BIL Rating 350

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 120 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

tra

ditio

na

l Wa

ll 650 mil xlpe c

opper n

eUtr

alS W

itH

co

pper co

mpo

Site lam

inate SH

eatH

17 18

Section 269 kV power cables

69 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or Milliken• Super Smooth Conductor Shield• Super Clean XLPE Insulation• Traditional Wall - 650 mil XLPE

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Concentric Neutrals with Copper

Composite Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current.4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 650 MIL XLPE COPPER NEUTRALS WITH COPPER COMPOSITE LAMINATE SHEATH

Page 12: Hv Solutions Catalog

69 kV XLPE - Copper Conductor

conductor Size in kcmil1 500 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61 1.78 1.98 2.08 2.21

mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9 45.2 50.2 52.8 56.1

Insulation Thickness mils 520 490 470 450 450 440 430 430 440 450 450

mm 20.5 19.3 18.5 17.7 17.7 17.3 16.9 16.9 17.3 17.7 17.7

Diameter over Insulation in 1.95 2.07 2.18 2.27 2.39 2.48 2.56 2.74 2.92 3.1 3.23

mm 49.5 52.5 55.4 57.7 60.7 63.0 65.0 69.6 74.2 78.7 82.0

Diameter over Sheath in 2.33 2.45 2.56 2.66 2.78 2.87 2.95 3.16 3.41 3.51 3.64

mm 59.3 62.2 65.0 67.4 70.5 72.8 74.9 80.3 86.6 89.1 92.5

Overall Jacket Diameter in 2.65 2.77 2.88 2.98 3.10 3.19 3.27 3.48 3.73 3.83 3.96

mm 67.3 70.4 73.2 75.7 78.6 80.9 83.0 88.4 94.7 97.2 100.6

Total Weight lbs/ft 4.9 6.0 6.3 7.1 8.0 8.9 9.7 11.7 13.5 15.4 17.1

Min. Bending Radius (install/

perm.) in 53/40 55/42 58/43 60/45 62/46 64/48 65/49 70/52 75/56 77/57 79/59

Maximum Pulling Tension lbs 4,000 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 138x95 150x95 150x95 150x95

Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,800 2,500 2,200

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5 4.4 4.3 4.2 4.1

Insulation Shield kV/mm 2.1 2.4 2.6 2.7 2.8 2.9 3.0 3.0 3.0 3.0 3.0

Short circuit for 0.5s3

Conductor kA 51.3 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410.0

Sheath kA 41.7 42 42.3 42.5 42.8 43.1 43.3 43.8 44.5 44.7 45.1

conductor resistance

DC @ 20o C Ω/kft 0.021 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003

DC @ 90o C Ω/kft 0.027 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 51.1 60.6 68.9 77.1 82.4 88.9 95.3 103.8 112.1 113.3 119.24

Charging Current Amps/kft 0.77 0.91 1.04 1.16 1.24 1.34 1.43 1.56 1.68 1.702 1.791

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 620 770 900 1010 1100 1180 1250 1471 1609 1730 1836

Power Rating MVA 75 93 108 121 132 142 150 176 193 207 220

Typical Double Ductbank4 Amps 520 640 740 830 900 960 1010 1235 1346 1444 1530

Power Rating MVA 63 77 89 100 108 115 121 148 161 173 183

cable data

Voltage Characteristics (kV)

Max Voltage Rating 72.5

BIL Rating 350

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 120 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

Stan

da

rd W

all xlpe c

opper n

eUtr

alS W

itH

co

pper co

mpo

Site lam

inate SH

eatH

19 20

Section 269 kV power cables

69 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or Milliken• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 430 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Copper Composite

Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.

3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current.

4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE COPPER NEUTRALS WITH COPPER COMPOSITE LAMINATE SHEATH

Page 13: Hv Solutions Catalog

conductor Size in kcmil 500 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61

mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9

Diameter over Insulation in 2.21 2.39 2.54 2.67 2.79 2.90 3.00

mm 56.1 60.7 64.4 67.8 70.9 73.7 76.2

Diameter over Sheath in 2.60 2.78 2.93 3.06 3.18 3.29 3.39

mm 66.0 70.5 74.3 77.7 80.7 83.5 86.1

Overall Jacket Diameter in 2.92 3.10 3.25 3.38 3.50 3.61 3.71

mm 74.1 78.7 82.4 85.8 88.9 91.7 94.2

Total Weight lbs/ft 3.7 4.2 4.7 5.1 5.5 5.8 6.2

Min. Bending Radius (install/perm.) in 58/44 62/46 65/49 68/51 70/52 72/54 74/56

Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Width in 126x95 126x95 126x95 138x95 138x95 138x95 150x95

Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 3.9 3.7 3.5 3.4 3.4 3.3 3.3

Insulation Shield kV/mm 1.6 1.7 1.7 1.8 1.8 1.8 1.8

Short circuit for 0.5s2

Conductor kA 33.8 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 41.6 42 42.3 42.6 42.9 43.1 43.4

conductor resistance

DC @ 20o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.043 0.028 0.021 0.017 0.014 0.012 0.011

Capacitance pF/ft 43.9 49.5 54.2 58.4 62.1 65.5 68.7

Charging Current Amps/kft 0.66 0.74 0.81 0.88 0.93 0.98 1.03

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 480 600 700 780 860 930 1000

Power Rating MVA 58 72 84 94 103 112 120

Typical Double Ductbank3 Amps 410 510 590 660 730 780 830

Power Rating MVA 49 61 71 79 88 94 100

69 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 72.5

BIL Rating 350

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 120 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

tra

ditio

na

l Wa

ll 650 mil xlpe c

opper n

eUtr

alS W

itH

alU

min

Um

co

mpo

Site lam

inate SH

eatH

21 22

Section 269 kV power cables

69 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor • Super Smooth Conductor Shield• Super Clean XLPE Insulation• Traditional Wall - 650 mil XLPE

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Aluminum

Composite Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current.34ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 650 MIL XLPE COPPER NEUTRALS WITH ALUMINUM COMPOSITE LAMINATE SHEATH

Page 14: Hv Solutions Catalog

conductor Size in kcmil 500 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.79 0.97 1.12 1.25 1.37 1.48 1.61

mm 20.1 24.7 28.5 31.8 34.8 37.6 40.9

Insulation Thickness mils 520 490 470 450 450 440 430

mm 20.5 19.3 18.5 17.7 17.7 17.3 16.9

Diameter over Insulation in 1.95 2.07 2.18 2.27 2.39 2.48 2.56

mm 49.5 52.5 55.3 57.7 60.7 63.0 65.1

Diameter over Sheath in 2.34 2.46 2.57 2.66 2.78 2.87 2.95

mm 59.4 62.4 65.2 67.5 70.6 72.9 75.0

Overall Jacket Diameter in 2.66 2.78 2.89 2.98 3.10 3.19 3.27

mm 67.5 70.5 73.3 75.7 78.7 81.0 83.1

Total Weight lbs/ft 3.3 3.7 4.0 4.3 4.7 5.0 5.3

Min. Bending Radius (install/perm.) in 53/40 56/42 58/43 60/45 62/46 64/48 65/49

Maximum Pulling Tension lbs 3,000 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 138x95 138x95

Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 3,000 3,000

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 4.5 4.5 4.5 4.5 4.5 4.5 4.5

Insulation Shield kV/mm 2.1 2.4 2.6 2.7 2.8 2.9 3.0

Short circuit for 0.5s2

Conductor kA 33.8 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 41 41.2 41.5 41.7 42 42.2 42.4

conductor resistance

DC @ 20o C Ω/kft 0.035 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.043 0.028 0.021 0.017 0.014 0.012 0.011

Capacitance pF/ft 51.1 60.6 68.9 77.1 82.4 88.9 95.3

Charging Current Amps/kft 0.77 0.91 1.04 1.16 1.24 1.34 1.43

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 485 608 712 803 884 957 1023

Power Rating MVA 58 73 86 96 106 115 123

Typical Double Ductbank3 Amps 408 507 590 661 724 780 829

Power Rating MVA 49 61 71 79 87 94 100

69 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 72.5

BIL Rating 350

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 120 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

Stan

da

rd W

all xlpe c

opper n

eUtr

alS W

itH

alU

min

Um

co

mpo

Site lam

inate SH

eatH

23 24

Section 269 kV power cables

69 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield • Super Clean XLPE Insulation• 430 mil XLPE minimum

• True Triple Extrusion and Dry Cured • Firmly Bonded Insulation Shield• Copper Neutrals with Aluminum

Composite Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current.34ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE COPPER NEUTRALS WITH ALUMINUM LAMINATE SHEATH

Page 15: Hv Solutions Catalog

KNOW YOUR OPTIONS: 115 KV POWER CABLE

CONDUCTOR MATERIAL AND SIzEConductor material is a matter of both customer preference and required current carrying capacity

• Copper conductor common for larger loads

• When both copper and aluminum conductors can meet your requirements, the more economical solution will be a function of the metal and the cable component costs

INSULATION THICKNESS• For cables with a radial moisture barrier, “Southwire Standard

Wall” reduced insulation thicknesses within the stress limits in AEIC specification CS9 are recommended

• Cables referred to by “Traditional Wall” insulation (800 mils) follow the traditional insulation wall practice referenced in ICEA standard S-108-720 appendix F as still specified by a number of customers and utilities

• For applications requiring smaller cable diameters, specific designs are available upon request within the stress limits in AEIC specification CS9

SHEATH MATERIAL• Copper and aluminum corrugated sheaths offer the best

mechanical and moisture protection for your HV cable, and copper will provide better short circuit performance and improved connectability

• Composite laminate sheaths in both copper and aluminum that offer excellent protection against moisture ingress

JACKET• Standard outer jacket: extruded LLDPE with a co-extruded outer

semi-conductive polyethylene layer for jacket integrity testing

• Halogen Free Fire Retardant (HFFR) compounds are available upon request for installations in cable trays and ventilated troughs

25 26

Section 3115 kV

power c

ables

Page 16: Hv Solutions Catalog

conductor Size in kcmil1 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Diameter over Insulation in 2.69 2.84 2.97 3.09 3.20 3.30 3.48 3.64 3.80 3.93

mm 68.3 72.1 75.4 78.5 81.3 83.9 88.4 92.5 96.4 99.8

Diameter over Sheath in 3.23 3.39 3.54 3.67 3.79 3.90 4.10 4.27 4.44 4.59

mm 81.9 86.1 89.8 93.2 96.3 99.1 104.1 108.6 112.9 116.6

Overall Jacket Diameter in 3.51 3.67 3.82 3.95 4.07 4.18 4.38 4.55 4.72 4.87

mm 89.0 93.2 96.9 100.3 103.4 106.2 111.2 115.7 120.0 123.7

Total Weight lbs/ft 6.6 7.6 8.6 9.6 10.6 11.6 13.5 15.4 17.3 19.2

Min. Bending Radius (install/perm.) in 70/53 73/55 76/57 79/59 81/61 84/63 88/66 91/68 94/71 97/73

Maximum Pulling Tension lbs 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Width in 126x95 126x95 150x95 150x95 150x95 150x95 158x95 150x95 150x95 158x95

Shipping Reel Capacity2 ft 3,000 2,950 3,000 3,000 2,725 2,750 2,675 2,400 2,075 1,875

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 5.3 5.1 4.9 4.8 4.7 4.6 4.5 4.4 4.4 4.3

Insulation Shield kV/mm 2.2 2.2 2.3 2.3 2.4 2.4 2.4 2.5 2.5 2.5

Short circuit for 0.5s3

Conductor kA 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410.0

Sheath kA 40.4 42.5 44.3 46 47.5 48.9 51.3 53.5 55.7 57.5

conductor resistance

DC @ 20o C Ω/kft 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003

DC @ 90o C Ω/kft 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 43.1 46.9 50.3 53.4 56.2 58.8 63.3 67.3 71.1 74.5

Charging Current Amps/kft 1.08 1.17 1.26 1.34 1.41 1.47 1.58 1.68 1.78 1.87

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 740 860 960 1040 1110 1170 1404 1523 1625 1708

Power Rating MVA 148 172 192 208 222 234 280 304 324 341

Typical Double Ductbank4 Amps 630 730 810 870 930 980 1159 1250 1326 1388

Power Rating MVA 126 146 162 174 186 196 231 249 265 277

115 kV XLPE - Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 120

BIL Rating 550

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 200 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

tra

ditio

na

l Wa

ll 800 mil xlpe c

opper c

orrU

gated

SHeatH

27 28

Section 3115 kV power cables

115 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or Milliken• Super Smooth Conductor Shield• Super Clean XLPE Insulation• Traditional Wall - 800 mil XLPE

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Copper Corrugated Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.3 Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current.4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 800 MIL XLPE COPPER CORRUgATED SHEATH

Page 17: Hv Solutions Catalog

conductor Size in kcmil1 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Insulation Thickness mils 660 630 610 590 580 570 550 540 540 550

mm 26.0 24.8 24.0 23.2 22.8 22.4 21.7 21.3 21.3 21.7

Diameter over Insulation in 2.41 2.50 2.59 2.67 2.76 2.84 2.99 3.12 3.28 3.43

mm 61.2 63.4 65.8 67.8 70.1 72.2 75.9 79.3 83.2 87.1

Diameter over Sheath in 2.90 3.00 3.10 3.18 3.29 3.37 3.53 3.68 3.84 4.01

mm 73.7 76.1 78.7 80.9 83.4 85.6 89.6 93.3 97.6 101.9

Overall Jacket Diameter in 3.18 3.28 3.38 3.46 3.57 3.65 3.81 3.96 4.12 4.29

mm 80.8 83.3 85.8 88.0 90.6 92.7 96.7 100.5 104.7 109.0

Total Weight lbs/ft 5.9 6.8 7.7 8.5 9.4 10.3 12.1 13.9 15.8 17.6

Min. Bending Radius (install/perm.) in 64/48 66/49 68/51 69/52 71/53 73/55 76/57 79/59 82/62 86/64

Maximum Pulling Tension lbs 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95 126x95 126x95 138x95 138x95

Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 3,000 2,950 2,975 2,750 2,375 2,125

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 6.1 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8

Insulation Shield kV/mm 2.9 3.0 3.2 3.4 3.5 3.6 3.8 3.9 4.0 3.9

Short circuit for 0.5s3

Conductor kA 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410.0

Sheath kA 36.3 37.6 38.8 39.9 41.2 42.2 44.2 46.0 48.1 50.2

conductor resistance

DC @ 20o C Ω/kft 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003

DC @ 90o C Ω/kft 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 49.0 55.4 61.2 66.8 71.4 76.0 84.9 91.7 97.3 100.7

Charging Current Amps/kft 1.23 1.39 1.53 1.67 1.79 1.90 2.12 2.30 2.44 2.52

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 750 870 970 1060 1130 1200 1435 1561 1667 1757

Power Rating MVA 150 174 194 212 226 240 286 311 333 350

Typical Double Ductbank4 Amps 640 740 820 890 940 990 1182 1279 1359 1425

Power Rating MVA 128 148 164 178 188 198 236 255 271 284

115 kV XLPE - CopperConductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 120

BIL Rating 550

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 200 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll xlpe co

pper co

rrUg

ated SH

eatH

29 30

Section 3115 kV power cables

115 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 540 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Copper Corrugated Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

SW STANDARD WALL XLPE COPPER CORRUgATED SHEATH

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.3 Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current.4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

Page 18: Hv Solutions Catalog

conductor Size in kcmil 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.25 1.38 1.49 1.61

mm 24.7 28.5 31.8 35.0 37.8 40.9

Diameter over Insulation in 2.69 2.84 2.97 3.09 3.20 3.30

mm 68.3 72.1 75.4 78.5 81.3 83.9

Diameter over Sheath in 3.50 3.45 3.65 3.78 3.90 4.02

mm 88.8 87.7 92.6 96.0 99.2 102.1

Overall Jacket Diameter in 3.78 3.73 3.93 4.06 4.18 4.30

mm 95.9 94.8 99.7 103.1 106.3 109.2

Total Weight lbs/ft 4.3 4.8 5.2 5.7 6.1 6.5

Min. Bending Radius (install/perm.) in 76/57 75/56 79/59 81/61 84/63 86/64

Maximum Pulling Tension lbs 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 150x95 150x95 150x95 150x95

Shipping Reel Capacity1 ft 3,000 2,975 3,000 2,725 2,750 2,600

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 5.3 5.1 4.9 4.8 4.7 4.6

Insulation Shield kV/mm 2.2 2.2 2.3 2.3 2.4 2.4

Short circuit for 0.5s2

Conductor kA 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 45.5 47.8 49.8 51.7 53.4 54.9

conductor resistance

DC @ 20o C Ω/kft 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.030 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 43.1 46.9 50.3 53.4 56.2 58.8

Charging Current Amps/kft 1.08 1.17 1.26 1.34 1.41 1.47

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 580 680 770 840 910 970

Power Rating MVA 116 136 154 168 182 194

Typical Double Ductbank3 Amps 500 580 650 710 760 810

Power Rating MVA 100 116 130 142 152 162

115 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 120

BIL Rating 550

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 200 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

tra

ditio

na

l Wa

ll 800 mil xlpe a

lUm

inU

m c

orrU

gated

SHeatH

31 32

Section 3115 kV power cables

115 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield• Super Clean XLPE Insulation• Traditional Wall – 800 mil XLPE

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Aluminum Corrugated Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current.3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 800 MIL XLPE ALUMINUM CORRUgATED SHEATH

Page 19: Hv Solutions Catalog

conductor Size in kcmil 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.26 1.38 1.49 1.61

mm 24.7 28.5 31.9 35.0 37.8 40.9

Insulation Thickness mils 660 630 610 590 580 570

mm 26.0 24.8 24.0 23.2 22.8 22.4

Diameter over Insulation in 2.41 2.50 2.59 2.67 2.76 2.84

mm 61.2 63.4 65.8 67.8 70.1 72.2

Diameter over Sheath in 3.00 3.10 3.20 3.29 3.39 3.48

mm 76.1 78.7 81.3 83.5 86.1 88.3

Overall Jacket Diameter in 3.28 3.38 3.48 3.57 3.67 3.76

mm 83.2 85.8 88.4 90.6 93.2 95.4

Total Weight lbs/ft 3.7 4.0 4.3 4.7 5.0 5.3

Min. Bending Radius (install/perm.) in 66/49 68/51 70/52 71/54 73/55 75/56

Maximum Pulling Tension lbs 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 126x95

Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 2,950 2,975

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 6.1 6.0 6.0 6.0 6.0 6.0

Insulation Shield kV/mm 2.7 3.0 3.2 3.4 3.5 3.6

Short circuit for 0.5s2

Conductor kA 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 41 42.4 43.7 44.9 46.3 47.5

conductor resistance

DC @ 20o C Ω/kft 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.030 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 49.0 55.4 61.2 66.8 71.4 76.0

Charging Current Amps/kft 1.23 1.39 1.53 1.67 1.79 1.90

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 590 690 780 860 920 980

Power Rating MVA 118 138 156 172 184 196

Typical Double Ductbank3 Amps 500 580 650 720 770 820

Power Rating MVA 100 116 130 144 154 164

115 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 120

BIL Rating 550

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 200 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll xlpe alU

min

Um

co

rrUg

ated SH

eatH

33 34

Section 3115 kV power cables

115 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 590 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Aluminum Corrugated Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current.3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE ALUMINUM CORRUgATED SHEATH

Page 20: Hv Solutions Catalog

conductor Size in kcmil1 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Diameter over Insulation in 2.69 2.84 2.97 3.09 3.20 3.30 3.48 3.64 3.80 3.93

mm 68.3 72.1 75.4 78.5 81.3 83.9 88.4 92.5 96.4 99.8

Diameter over Sheath in 3.07 3.22 3.36 3.48 3.59 3.69 3.89 4.05 4.21 4.34

mm 78.1 81.8 85.2 88.3 91.1 93.7 98.8 102.9 106.8 110.3

Overall Jacket Diameter in 3.39 3.54 3.68 3.80 3.91 4.01 4.21 4.37 4.53 4.66

mm 86.2 90.0 93.3 96.4 99.2 101.8 107.0 111.0 115.0 118.4

Total Weight lbs/ft 6.6 7.6 8.5 9.5 10.4 11.4 13.5 15.3 17.2 19.0

Min. Bending Radius (install/

perm.)in 68/51 71/53 74/55 76/57 78/59 80/60 84/63 87/66 91/68 93/70

Maximum Pulling Tension lbs 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Width in 138x95 138x95 138x95 150x95 150x95 150x95 158x95 158x95 158x95 158x95

Shipping Reel Capacity2 ft 3,000 3,000 2,775 3,000 3,000 2,725 2,775 2,450 2,175 1,975

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 5.3 5.1 4.9 4.8 4.7 4.6 4.5 4.4 4.4 4.3

Insulation Shield kV/mm 2.2 2.2 2.3 2.3 2.4 2.4 2.4 2.5 2.5 2.5

Short circuit for 0.5s3

Conductor kA 76.9 102.5 128.1 153.8 179.4 205.0 256.3 307.5 358.8 410.0

Sheath kA 43.6 44.0 44.3 44.6 44.9 45.2 45.9 46.4 46.8 47.1

conductor resistance

DC @ 20o C Ω/kft 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003

DC @ 90o C Ω/kft 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 43.1 46.9 50.3 53.4 56.2 58.8 63.3 67.3 71.1 74.5

Charging Current Amps/kft 1.08 1.17 1.26 1.34 1.41 1.47 1.58 1.68 1.78 1.87

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 750 870 980 1070 1140 1210 1432 1574 1722 1830

Power Rating MVA 150 174 196 214 228 242 286 314 343 365

Typical Double Ductbank4 Amps 640 740 820 890 950 1010 1210 1320 1416 1500

Power Rating MVA 128 148 164 178 190 202 242 263 283 299

115 kV XLPE - Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 120

BIL Rating 550

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 200 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

tra

ditio

na

l Wa

ll 800 mil xlpe c

opper n

eUtr

alS, c

opper

co

mpo

Site lam

inate SH

eatH

35 36

Section 3115 kV power cables

115 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or MIlliken• Super Smooth Conductor Shield• Super Clean XLPE Insulation• Traditional Wall 800 mil

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Copper Composite

Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current.4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 800 MIL XLPE COPPER NEUTRALS, COPPER COMPOSITE LAMINATE SHEATH

Page 21: Hv Solutions Catalog

conductor Size in kcmil1 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Insulation Thickness mils 660 630 610 590 580 570 550 540 540 550

mm 26.0 24.8 24.0 23.2 22.8 22.4 21.7 21.3 21.3 21.7

Diameter over Insulation in 2.41 2.50 2.59 2.67 2.76 2.84 2.99 3.12 3.28 3.43

mm 61.2 63.4 65.8 67.8 70.1 72.2 75.9 79.3 83.2 87.1

Diameter over Sheath in 2.79 2.88 2.98 3.06 3.15 3.23 3.39 3.53 3.69 3.84

mm 70.9 73.2 75.6 77.6 79.9 82.0 86.1 89.7 93.6 97.6

Overall Jacket Diameter in 3.11 3.20 3.30 3.38 3.47 3.55 3.71 3.85 4.01 4.16

mm 79.1 81.3 83.7 85.7 88.0 90.1 94.3 97.8 101.8 105.7

Total Weight lbs/ft 6.0 6.9 7.7 8.6 9.4 10.3 12.3 14.0 15.6 17.6

Min. Bending Radius (install/

perm.)in 62/47 64/48 66/49 68/51 69/52 71/53 74/56 77/58 80/60 83/62

Maximum Pulling Tension lbs 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 126x95 138x95 138x95 138x95 138x95 150x95 150x95 150x95

Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 3,000 3,000 2,775 2,775 2,400 2,175

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 6.1 6.0 6.0 6.0 6.0 6.0 6.0 6.0 6.0 5.8

Insulation Shield kV/mm 2.9 3.0 3.2 3.4 3.5 3.6 3.8 3.9 4.0 3.9

Short circuit for 0.5s3

Conductor kA 76.9 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410.0

Sheath kA 42.9 43.1 43.3 43.5 43.8 44.0 44.6 45.0 45.4 45.8

conductor resistance

DC @ 20o C Ω/kft 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003

DC @ 90o C Ω/kft 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 49.0 55.4 61.2 66.8 71.4 76.0 84.9 91.7 97.3 100.7

Charging Current Amps/kft 1.23 1.39 1.53 1.67 1.79 1.90 2.12 2.30 2.44 2.52

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 761 885 990 1080 1158 1226 1481 1622 1747 1854

Power Rating MVA 152 177 198 216 231 245 295 324 348 370

Typical Double Ductbank4 Amps 643 744 828 899 961 1015 1221 1331 1428 1512

Power Rating MVA 129 149 165 180 192 203 244 266 285 302

115 kV XLPE - Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 120

BIL Rating 550

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 200 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll xlpe co

pper neU

tra

lS, co

pper co

mpo

Site la

min

ate SHeatH

37 38

Section 3115 kV power cables

115 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or MIlliken• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 540 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Copper Composite

Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.

3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current.

4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE COPPER NEUTRALS, COPPER COMPOSITE LAMINATE SHEATH

Page 22: Hv Solutions Catalog

conductor Size in kcmil 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.26 1.38 1.49 1.61

mm 24.7 28.5 31.9 35.0 37.8 40.9

Diameter over Insulation in 2.69 2.84 2.97 3.09 3.20 3.30

mm 68.3 72.1 75.4 78.5 81.3 83.9

Diameter over Sheath in 3.08 3.23 3.36 3.48 3.59 3.69

mm 78.2 81.9 85.3 88.4 91.2 93.8

Overall Jacket Diameter in 3.40 3.55 3.68 3.80 3.91 4.01

mm 86.3 90.1 93.4 96.5 99.3 101.9

Total Weight lbs/ft 4.8 5.3 5.7 6.1 6.5 6.9

Min. Bending Radius (install/perm.) in 68/51 71/53 74/55 76/57 78/59 80/60

Maximum Pulling Tension lbs 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Width in 138x95 138x95 138x95 150x95 150x95 150x95

Shipping Reel Capacity1 ft 3,000 3,000 2,775 3,000 3,000 2,725

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 5.3 5.1 4.9 4.8 4.7 4.6

Insulation Shield kV/mm 2.2 2.2 2.3 2.3 2.4 2.4

Short circuit for 0.5s2

Conductor kA 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 42.7 43.0 43.3 43.6 43.8 44.1

conductor resistance

DC @ 20o C Ω/kft 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.030 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 43.1 46.9 50.3 53.4 56.2 58.8

Charging Current Amps/kft 1.08 1.17 1.26 1.34 1.41 1.47

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 595 696 785 864 934 999

Power Rating MVA 119 139 157 173 187 199

Typical Double Ductbank3 Amps 504 586 658 722 778 829

Power Rating MVA 101 117 132 144 155 166

115 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 120

BIL Rating 550

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 200 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

tra

ditio

na

l Wa

ll 800 mil xlpe c

opper n

eUtr

alS, a

lUm

inU

m

co

mpo

Site lam

inate SH

eatH

39 40

Section 3115 kV power cables

115 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield• Super Clean XLPE Insulation• Traditional Wall – 800 mil XLPE

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Aluminum

Composite Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current.34ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 800 MIL XLPE COPPER NEUTRALS, ALUMINUM COMPOSITE LAMINATE SHEATH

Page 23: Hv Solutions Catalog

conductor Size in kcmil 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.26 1.38 1.49 1.61

mm 24.7 28.5 31.9 35.0 37.8 40.9

Insulation Thickness mils 660 630 610 590 580 570

mm 26.0 24.8 24.0 23.2 22.8 22.4

Diameter over Insulation in 2.41 2.50 2.59 2.67 2.76 2.84

mm 61.2 63.4 65.8 67.8 70.1 72.2

Diameter over Sheath in 2.80 2.89 2.98 3.06 3.15 3.23

mm 71.0 73.3 75.7 77.7 80.0 82.1

Overall Jacket Diameter in 3.12 3.21 3.30 3.38 3.47 3.55

mm 79.2 81.4 83.8 85.8 88.1 90.2

Total Weight lbs/ft 4.3 4.6 4.9 5.2 5.5 5.8

Min. Bending Radius (install/perm.) in 62/47 64/48 66/49 68/51 69/52 71/53

Maximum Pulling Tension lbs 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 126x95 138x95 138x95 138x95

Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 3,000

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 6.1 6.0 6.0 6.0 6.0 6.0

Insulation Shield kV/mm 2.7 3.0 3.2 3.4 3.5 3.6

Short circuit for 0.5s2

Conductor kA 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 42.0 42.2 42.4 42.6 42.8 43.0

conductor resistance

DC @ 20o C Ω/kft 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.030 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 49.0 55.4 61.2 66.8 71.4 76.0

Charging Current Amps/kft 1.23 1.39 1.53 1.67 1.79 1.90

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 603 706 796 876 948 1013

Power Rating MVA 121 141 159 175 189 202

Typical Double Ductbank3 Amps 509 592 665 729 786 837

Power Rating MVA 102 118 133 146 157 167

115 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 120

BIL Rating 550

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 200 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll xlpe co

pper neU

tra

l, alU

min

Um

co

mpo

Site la

min

ate SHeatH

41 42

Section 3115 kV power cables

115 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 570 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Aluminum

Composite Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current.34ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE COPPER NEUTRAL, ALUMINUM COMPOSITE LAMINATE SHEATH

Page 24: Hv Solutions Catalog

KNOW YOUR OPTIONS: 138 KV POWER CABLES

CONDUCTOR MATERIAL AND SIzEConductor material is a matter of both customer preference and required current carrying capacity

• Copper conductor common for larger loads

• When both copper and aluminum conductors can meet your requirements, the more economical solution will be a function of the metal and the cable component costs

INSULATION THICKNESS• For cables with a radial moisture barrier, “Southwire Standard

Wall” reduced insulation thicknesses within the stress limits in AEIC specification CS9 are recommended

• Cables referred to by “Traditional Wall” insulation (850 mils) follow the traditional insulation wall practice referenced in ICEA standard S-108-720 appendix F as still specified by a number of customers and utilities

• For applications requiring smaller cable diameters, specific designs are available upon request within the stress limits in AEIC specification CS9

SHEATH MATERIAL• Copper and aluminum corrugated sheaths offer the best

mechanical and moisture protection for your HV cable, and copper will provide better short circuit performance and improved connectability

• Composite laminate sheaths in both copper and aluminum that offer excellent protection against moisture ingress

JACKET• Standard outer jacket: extruded LLDPE with a co-extruded outer

semi-conductive polyethylene layer for jacket integrity testing

• Halogen Free Fire Retardant (HFFR) compounds are available upon request for installations in cable trays and ventilated troughs

43 44

Section 4138 kV

power c

ables

Page 25: Hv Solutions Catalog

conductor Size in kcmil1 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Diameter over Insulation in 2.79 2.94 3.07 3.19 3.30 3.40 3.66 3.82 3.98 4.11

mm 70.8 74.6 78.0 81.0 83.8 86.4 93.0 97.1 101.0 104.4

Diameter over Sheath in 3.34 3.50 3.65 3.78 3.90 4.02 4.31 4.49 4.66 4.80

mm 84.8 89.0 92.7 96.0 99.1 102.0 109.4 113.9 118.3 122.0

Overall Jacket Diameter in 3.62 3.78 3.93 4.06 4.18 4.30 4.59 4.77 4.94 5.08

mm 91.9 96.1 99.8 103.1 106.2 109.1 116.6 121.1 125.4 129.1

Total Weight lbs/ft 6.8 7.9 8.9 9.9 10.9 11.9 14.1 16.0 18.0 19.8

Min. Bending Radius (install/

perm.)in 72/54 76/57 79/59 81/61 84/63 86/64 92/69 95/71 99/74 102/76

Maximum Pulling Tension lbs 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Width in 138x95 150x95 150x95 150x95 150x95 158x95 158x95 158x95 158x95 158x95

Shipping Reel Capacity2 ft 3,000 3,000 3,000 2,725 2,750 2,775 2,550 2,250 1,925 1,825

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 6.1 5.9 5.7 5.5 5.4 5.3 5.1 5.0 4.9 4.9

Insulation Shield kV/mm 2.4 2.5 2.5 2.6 2.6 2.7 2.7 2.8 2.8 2.9

Short circuit for 0.5s3

Conductor kA 76.9 102.5 128.1 153.8 179.4 205.0 256.3 307.5 358.8 410.0

Sheath kA 41.8 43.9 45.7 47.4 48.9 50.3 54 56.2 58.3 60.2

conductor resistance

DC @ 20o C Ω/kft 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.003 0.003 0.003

DC @ 90o C Ω/kft 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 41.4 45.0 48.3 51.2 53.8 56.3 62.4 66.2 69.8 73.0

Charging Current Amps/kft 1.24 1.35 1.45 1.54 1.62 1.69 1.87 1.99 2.10 2.19

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 740 850 950 1030 1100 1170 1379 1515 1613 1698

Power Rating MVA 177 204 228 247 263 280 330 363 386 406

Typical Double Ductbank4 Amps 630 720 800 870 930 970 1153 1243 1316 1378

Power Rating MVA 151 173 192 208 223 232 276 298 315 330

138 kV XLPE - Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 145

BIL Rating 650

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 240 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

tra

ditio

na

l Wa

ll 850 mil xlpe c

opper c

orrU

gated

SHeatH

45 46

Section 4138 kV power cables

138 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or Milliken• Super Smooth Conductor Shield • Super Clean XLPE Insulation• Traditional Wall - 850 mil XLPE

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Copper Corrugated Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.3 Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current.4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 850 MIL XLPE COPPER CORRUgATED SHEATH

Page 26: Hv Solutions Catalog

conductor Size in kcmil1 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Insulation Thickness mils 770 730 700 680 660 650 630 630 630 640

mm 30.3 28.7 27.6 26.8 26.0 25.6 24.8 24.8 24.8 25.2

Diameter over Insulation in 2.63 2.70 2.77 2.85 2.92 3.00 3.22 3.38 3.54 3.69

mm 66.8 68.5 70.4 72.4 74.2 76.3 81.8 85.9 89.8 93.7

Diameter over Sheath in 3.16 3.23 3.30 3.39 3.46 3.56 3.81 3.98 4.15 4.32

mm 80.2 82.1 83.9 86.1 88.0 90.3 96.6 101.1 105.4 109.7

Overall Jacket Diameter in 3.44 3.51 3.58 3.67 3.74 3.84 4.09 4.26 4.43 4.60

mm 87.4 89.2 91.0 93.2 95.1 97.5 103.8 108.2 112.5 116.8

Total Weight lbs/ft 6.4 7.3 8.1 9.0 9.9 10.7 12.8 14.6 16.6 18.4

Min. Bending Radius (install/

perm.)in 69/52 70/53 72/54 73/55 75/56 77/58 82/61 85/64 89/66 92/69

Maximum Pulling Tension lbs 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 126x95 126x95 126x95 150x95 150x95 150x95 150x95 150x95

Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 2,950 3,000 2,725 2,500 2,225 2,000

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.3 6.3 6.1

Insulation Shield kV/mm 2.7 3.0 3.2 3.4 3.6 3.7 3.9 4.0 4.0 4.0

Short circuit for 0.5s3

Conductor kA 76.9 102.5 128.1 153.8 179.4 205.0 256.3 307.5 358.8 410.0

Sheath kA 39.6 40.5 41.4 42.5 43.4 44.6 47.7 49.9 52.0 54.1

conductor resistance

DC @ 20o C Ω/kft 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.003 0.003 0.003

DC @ 90o C Ω/kft 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 44.2 50.0 55.3 60.1 64.7 68.7 78.5 83.5 88.4 91.4

Charging Current Amps/kft 1.33 1.50 1.66 1.80 1.95 2.06 2.36 2.51 2.65 2.75

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 750 860 960 1050 1110 1180 1423 1546 1651 1746

Power Rating MVA 180 206 230 251 266 283 341 370 395 418

Typical Double Ductbank4 Amps 630 730 810 880 930 990 1172 1267 1345 1421

Power Rating MVA 151 175 194 211 223 237 281 303 322 340

138 kV XLPE - Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 145

BIL Rating 650

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 240 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll xlpe co

pper co

rrUg

ated SH

eatH

47 48

Section 4138 kV power cables

138 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or Milliken• Super Smooth Conductor Shield • Super Clean XLPE Insulation• 630 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Copper Corrugated Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.

3 Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current.

4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE COPPER CORRUgATED SHEATH

Page 27: Hv Solutions Catalog

conductor Size in kcmil 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.25 1.38 1.49 1.61

mm 24.7 28.5 31.8 35.0 37.8 40.9

Diameter over Insulation in 2.79 2.94 3.07 3.19 3.30 3.40

mm 70.8 74.6 78.0 81.0 83.8 86.4

Diameter over Sheath in 3.44 3.61 3.76 3.90 4.02 4.13

mm 87.4 91.7 95.5 98.9 102.1 105.0

Overall Jacket Diameter in 3.72 3.89 4.04 4.18 4.30 4.41

mm 94.5 98.8 102.6 106.0 109.2 112.1

Total Weight lbs/ft 4.5 5.0 5.5 5.9 6.3 6.7

Min. Bending Radius (install/perm.) in 74/56 78/58 81/61 84/63 86/64 88/66

Maximum Pulling Tension lbs 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 150x95 150x95 158x95 158x95 158x95 158x95

Shipping Reel Capacity1 ft 3,000 3,000 2,925 2,925 2,775 2,800

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 6.1 5.9 5.7 5.5 5.4 5.3

Insulation Shield kV/mm 2.4 2.5 2.5 2.6 2.6 2.7

Short circuit for 0.5s2

Conductor kA 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 47.1 49.4 51.4 53.2 54.9 56.5

conductor resistance

DC @ 20o C Ω/kft 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.030 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 41.4 45.0 48.3 51.2 53.8 56.3

Charging Current Amps/kft 1.24 1.35 1.45 1.54 1.62 1.69

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 580 680 760 840 900 960

Power Rating MVA 139 163 182 201 216 230

Typical Double Ductbank*** Amps 500 580 640 700 760 800

Power Rating MVA 120 139 153 168 182 192

138 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 145

BIL Rating 650

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 240 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

tra

ditio

na

l Wa

ll 850 mil xlpe a

lUm

inU

m c

orrU

gated

SHeatH

49 50

Section 4138 kV power cables

138 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield • Super Clean XLPE Insulation• Traditional Wall – 850 mil XLPE

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Aluminum Corrugated Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current.3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 850 MIL XLPE ALUMINUM CORRUgATED SHEATH

Page 28: Hv Solutions Catalog

conductor Size in kcmil 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.26 1.38 1.49 1.61

mm 24.7 28.5 31.9 35.0 37.8 40.9

Insulation Thickness mils 770 730 700 680 660 650

mm 30.3 28.7 27.6 26.8 26.0 25.6

Diameter over Insulation in 2.63 2.70 2.77 2.85 2.92 3.00

mm 66.8 68.5 70.4 72.4 74.2 76.3

Diameter over Sheath in 3.26 3.34 3.41 3.50 3.57 3.67

mm 82.8 84.7 86.6 88.8 90.7 93.1

Overall Jacket Diameter in 3.54 3.62 3.69 3.78 3.85 3.95

mm 89.9 91.8 93.7 95.9 97.8 100.3

Total Weight lbs/ft 4.2 4.5 4.7 5.1 5.4 5.7

Min. Bending Radius (install/perm.) in 71/53 72/54 74/55 76/57 77/58 79/59

Maximum Pulling Tension lbs 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 126x95 126x95 126x95 126x95 150x95 150x95

Shipping Reel Capacity1 ft 3,000 3,000 2,950 2,950 3,000 3,000

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 6.5 6.5 6.5 6.5 6.5 6.5

Insulation Shield kV/mm 2.7 3.0 3.2 3.4 3.6 3.7

Short circuit for 0.5s2

Conductor kA 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 44.6 45.6 46.6 47.8 48.8 50.1

conductor resistance

DC @ 20o C Ω/kft 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.030 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 44.2 50.0 55.3 60.1 64.7 68.7

Charging Current Amps/kft 1.33 1.50 1.66 1.80 1.95 2.06

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 590 690 770 850 920 980

Power Rating MVA 142 165 185 204 220 235

Typical Double Ductbank3 Amps 500 580 650 710 770 810

Power Rating MVA 120 139 156 170 185 194

138 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 145

BIL Rating 650

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 240 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll xlpe alU

min

Um

co

rrUg

ated SH

eatH

51 52

Section 4138 kV power cables

138 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield • Super Clean XLPE Insulation• 650 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Aluminum Corrugated Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current.3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE ALUMINUM CORRUgATED SHEATH

Page 29: Hv Solutions Catalog

conductor Size in kcmil1 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Diameter over Insulation in 2.79 2.94 3.07 3.19 3.30 3.40 3.66 3.82 3.98 4.11

mm 70.8 74.6 78.0 81.0 83.8 86.4 93.0 97.1 101.0 104.4

Diameter over Sheath in 3.17 3.32 3.46 3.58 3.69 3.79 4.07 4.23 4.39 4.52

mm 80.6 84.4 87.8 90.8 93.6 96.2 103.4 107.5 111.4 114.8

Overall Jacket Diameter in 3.49 3.64 3.78 3.90 4.01 4.11 4.39 4.55 4.71 4.84

mm 88.7 92.5 95.9 98.9 101.7 104.3 111.5 115.6 119.5 123.0

Total Weight lbs/ft 6.8 7.8 8.8 9.7 10.7 11.6 13.8 15.6 17.5 19.3

Min. Bending Radius (install/

perm.)in 70/52 73/55 76/57 78/58 80/60 82/62 88/66 91/68 94/71 97/73

Maximum Pulling Tension lbs 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Width in 138x95 138x95 150x95 150x95 150x95 150x95 158x95 158x95 158x95 158x95

Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 2,733 2,725 2,700 2,375 2,125 1,900

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 6.1 5.9 5.7 5.5 5.4 5.3 5.1 5.0 4.9 4.9

Insulation Shield kV/mm 2.4 2.5 2.5 2.6 2.6 2.7 2.7 2.8 2.8 2.9

Short circuit for 0.5s3

Conductor kA 76.9 102.5 128.1 153.8 179.4 205.0 256.3 307.5 358.8 410.0

Sheath kA 43.9 44.2 44.6 44.9 45.2 45.5 46.2 46.6 47.0 47.4

conductor resistance

DC @ 20o C Ω/kft 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.003 0.003 0.003

DC @ 90o C Ω/kft 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 41.4 45.0 48.3 51.2 53.8 56.3 62.4 66.2 69.8 73.0

Charging Current Amps/kft 1.24 1.35 1.45 1.54 1.62 1.69 1.87 1.99 2.10 2.19

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 750 870 970 1060 1140 1210 1455 1592 1714 1821

Power Rating MVA 180 208 232 254 273 290 348 381 410 436

Typical Double Ductbank4 Amps 640 740 820 890 950 1000 1206 1314 1410 1493

Power Rating MVA 153 177 196 213 228 240 289 315 338 357

138 kV XLPE - Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 145

BIL Rating 650

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 240 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

53 54

Section 4138 kV power cables

138 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or Milliken• Super Smooth Conductor Shield • Super Clean XLPE Insulation• Traditional Wall – 850 mil XLPE

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Copper Composite

Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current.4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 850 MIL XLPE COPPER NEUTRALS, COPPER COMPOSITE LAMINATE SHEATH

tra

ditio

na

l Wa

ll 850 mil xlpe c

opper n

eUtr

alS, c

opper

co

mpo

Site lam

inate SH

eatH

Page 30: Hv Solutions Catalog

conductor Size in kcmil1 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Insulation Thickness mils 770 730 700 680 660 650 630 630 630 640

mm 30.3 28.7 27.6 26.8 26.0 25.6 24.8 24.8 24.8 25.2

Diameter over Insulation in 2.63 2.70 2.77 2.85 2.92 3.00 3.22 3.38 3.54 3.69

mm 66.8 68.5 70.4 72.4 74.2 76.3 81.8 85.9 89.8 93.7

Diameter over Sheath in 3.01 3.08 3.16 3.24 3.31 3.39 3.63 3.79 3.95 4.10

mm 76.5 78.3 80.1 82.2 83.9 86.1 92.2 96.3 100.2 104.2

Overall Jacket Diameter in 3.33 3.40 3.48 3.56 3.63 3.71 3.95 4.11 4.27 4.42

mm 84.6 86.4 88.3 90.3 92.1 94.2 100.4 104.4 108.4 112.3

Total Weight lbs/ft 6.4 7.3 8.1 8.9 9.8 10.6 12.7 14.4 16.3 18.1

Min. Bending Radius (install/

perm.)in 67/50 68/51 70/52 71/53 73/54 74/56 79/59 82/62 85/64 88/66

Maximum Pulling Tension lbs 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Traverse in 126x95 138x95 138x95 138x95 138x95 138x95 150x95 150x95 150x95 158x95

Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 3,000 2,775 3,000 2,625 2,325 2,050

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.3 6.3 6.1

Insulation Shield kV/mm 2.7 3.0 3.2 3.4 3.6 3.7 3.9 4.0 4.0 4.0

Short circuit for 0.5s3

Conductor kA 76.9 102.5 128.1 153.8 179.4 205.0 256.3 307.5 358.8 410.0

Sheath kA 45.4 43.6 43.8 44.0 44.2 44.4 45.0 45.5 45.9 46.3

conductor resistance

DC @ 20o C Ω/kft 0.014 0.011 0.008 0.007 0.006 0.005 0.004 0.003 0.003 0.003

DC @ 90o C Ω/kft 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 44.2 50.0 55.3 60.1 64.7 68.7 78.5 83.5 88.4 91.4

Charging Current Amps/kft 1.33 1.50 1.66 1.80 1.95 2.06 2.36 2.51 2.65 2.75

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 760 880 980 1070 1150 1220 1472 1610 1733 1840

Power Rating MVA 182 211 235 256 275 292 352 385 415 440

Typical Double Ductbank4 Amps 640 740 820 890 960 1010 1214 1323 1419 1502

Power Rating MVA 153 177 196 213 230 242 291 317 340 360

138 kV XLPE - Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 145

BIL Rating 650

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 240 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

55

Section 4138 kV power cables

138 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or Milliken• Super Smooth Conductor Shield • Super Clean XLPE Insulation• 630 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Copper Composite

Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.

3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current.

4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE COPPER NEUTRALS, COPPER COMPOSITE LAMINATE SHEATH

SW Sta

nd

ard

Wa

ll xlpe co

pper neU

tra

lS, co

pper co

mpo

Site la

min

ate SHeatH

56

Page 31: Hv Solutions Catalog

conductor Size in kcmil 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.26 1.38 1.49 1.61

mm 24.7 28.5 31.9 35.0 37.8 40.9

Diameter over Insulation in 2.79 2.94 3.07 3.19 3.30 3.40

mm 70.8 74.6 78.0 81.0 83.8 86.4

Diameter over Sheath in 3.18 3.33 3.46 3.58 3.69 3.79

mm 80.7 84.5 87.8 90.9 93.7 96.3

Overall Jacket Diameter in 3.50 3.65 3.78 3.90 4.01 4.11

mm 88.8 92.6 96.0 99.0 101.8 104.4

Total Weight lbs/ft 5.0 5.5 5.9 6.3 6.7 7.1

Min. Bending Radius (install/perm.) in 70/52 73/55 76/57 78/58 80/60 82/62

Maximum Pulling Tension lbs 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Width in 138x95 138x95 150x95 150x95 150x95 150x95

Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 2,725 2,725

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 6.1 5.9 5.7 5.5 5.4 5.3

Insulation Shield kV/mm 2.4 2.5 2.5 2.6 2.6 2.7

Short circuit for 0.5s2

Conductor kA 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 42.9 43.2 43.5 43.8 44.1 44.3

conductor resistance

DC @ 20o C Ω/kft 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.030 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 41.4 45.0 48.3 51.2 53.8 56.3

Charging Current Amps/kft 1.24 1.35 1.45 1.54 1.62 1.69

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 590 690 780 860 930 990

Power Rating MVA 142 165 187 206 223 237

Typical Double Ductbank3 Amps 500 580 650 720 770 830

Power Rating MVA 120 139 156 173 185 199

138 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 145

BIL Rating 650

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 240 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

57 58

Section 4138 kV power cables

138 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield • Super Clean XLPE Insulation• Traditional Wall – 850 mil XLPE

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Aluminum

Composite Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current.34ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

TRADITIONAL WALL 850 MIL XLPE COPPER NEUTRALS, ALUMINUM COMPOSITE LAMINATE SHEATH

tra

ditio

na

l Wa

ll 850 mil xlpe c

opper n

eUtr

alS, a

lUm

inU

m

co

mpo

Site lam

inate SH

eatH

Page 32: Hv Solutions Catalog

conductor Size in kcmil 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.26 1.38 1.49 1.61

mm 24.7 28.5 31.9 35.0 37.8 40.9

Insulation Thickness mils 770 730 700 680 660 650

mm 30.3 28.7 27.6 26.8 26.0 25.6

Diameter over Insulation in 2.63 2.70 2.77 2.85 2.92 3.00

mm 66.8 68.5 70.4 72.4 74.2 76.3

Diameter over Sheath in 3.02 3.09 3.16 3.24 3.31 3.39

mm 76.6 78.4 80.2 82.2 84.0 86.2

Overall Jacket Diameter in 3.34 3.41 3.48 3.56 3.63 3.71

mm 84.8 86.5 88.4 90.3 92.2 94.3

Total Weight lbs/ft 4.7 5.0 5.3 5.6 5.9 6.2

Min. Bending Radius (install/perm.) in 67/50 68/51 70/52 71/53 73/54 74/56

Maximum Pulling Tension lbs 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 126x95 138x95 138x95 138x95 138x95 138x95

Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 2,775

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 6.5 6.5 6.5 6.5 6.5 6.5

Insulation Shield kV/mm 2.7 3.0 3.2 3.4 3.6 3.7

Short circuit for 0.5s2

Conductor kA 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 42.5 42.7 42.8 43.0 43.2 43.4

conductor resistance

DC @ 20o C Ω/kft 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.028 0.021 0.017 0.014 0.012 0.011

Capacitance pF/ft 44.2 50.0 55.3 60.1 64.7 68.7

Charging Current Amps/kft 1.33 1.50 1.66 1.80 1.95 2.06

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 600 700 790 870 940 1000

Power Rating MVA 144 168 189 208 225 240

Typical Double Ductbank3 Amps 500 590 660 720 780 830

Power Rating MVA 120 142 158 173 187 199

138 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 145

BIL Rating 650

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 240 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

59 60

Section 4138 kV power cables

138 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield • Super Clean XLPE Insulation• 650 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Aluminum

Composite Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current.34ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE COPPER NEUTRAL, ALUMINUM COMPOSITE LAMINATE SHEATH

SW Sta

nd

ard

Wa

ll xlpe co

pper neU

tra

l, alU

min

Um

c

om

poSite la

min

ate SHeatH

Page 33: Hv Solutions Catalog

KNOW YOUR OPTIONS: 161 KV POWER CABLE

CONDUCTOR MATERIAL AND SIzEConductor material is a matter of both customer preference and required current carrying capacity

• Copper conductor common for larger loads

• When both copper and aluminum conductors can meet your requirements, the more economical solution will be a function of the metal and the cable component costs

INSULATION THICKNESS• For cables with a radial moisture barrier, “Southwire Standard

Wall” reduced insulation thicknesses within the stress limits in AEIC specification CS9 are recommended

• For applications requiring smaller cable diameters, specific designs are available upon request within the stress limits in AEIC specification CS9

SHEATH MATERIAL• Copper and aluminum corrugated sheaths offer the best

mechanical and moisture protection for your HV cable, and copper will provide better short circuit performance and improved connectability

• Composite laminate sheaths in both copper and aluminum that offer excellent protection against moisture ingress

JACKET• Standard outer jacket: extruded LLDPE with a co-extruded outer

semi-conductive polyethylene layer for jacket integrity testing

• Halogen Free Fire Retardant (HFFR) compounds are available upon request for installations in cable trays and ventilated troughs

61 62

Section 5161 kV

power c

ables

Page 34: Hv Solutions Catalog

conductor Size in kcmil1 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Insulation Thickness mils 840 790 760 730 710 690 700 710 720 730

mm 33.1 31.1 29.9 28.7 28.0 27.2 27.6 28.0 28.3 28.7

Diameter over Insulation in 2.77 2.82 2.89 2.95 3.02 3.08 3.36 3.52 3.72 3.87

mm 70.3 71.6 73.4 74.9 76.7 78.3 85.3 89.4 94.4 98.3

Diameter over Sheath in 3.32 3.36 3.44 3.51 3.58 3.65 3.96 4.14 4.36 4.52

mm 84.3 85.4 87.5 89.2 91.0 92.7 100.7 105.2 110.6 114.9

Overall Jacket Diameter in 3.60 3.64 3.72 3.79 3.86 3.93 4.24 4.42 4.64 4.80

mm 91.4 92.5 94.6 96.3 98.1 99.8 107.8 112.3 117.8 122.0

Total Weight lbs/ft 6.8 7.6 8.4 9.3 10.1 11.0 13.2 15.1 17.1 19.0

Min. Bending Radius (install/

perm.)in 72/54 73/55 74/56 76/57 77/58 79/59 85/64 88/66 93/70 96/72

Maximum Pulling Tension lbs 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Traverse in 138x95 126x95 126x95 126x95 150x95 150x95 158x95 150x95 150x95 158x95

Shipping Reel Capacity2 ft 3,000 2,950 2,950 2,950 3,000 3,000 2,725 2,450 2,150 1,900

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 7.2 7.2 7.2 7.2 7.2 7.2 6.9 6.8 6.6 6.4

Insulation Shield kV/mm 2.8 3.2 3.4 3.6 3.8 4.0 4.0 4.1 4.0 4.0

Short circuit for 0.5s3

Conductor kA 76.9 102.5 128.1 153.8 179.4 205.0 256.3 307.5 358.8 410.0

Sheath kA 41.6 42.1 43.1 44.0 44.9 45.7 49.7 51.9 54.6 56.7

conductor resistance

DC @ 20o C Ω/kft 0.014 0.011 0.008 0.007 0.007 0.005 0.004 0.004 0.003 0.003

DC @ 90o C Ω/kft 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 41.7 47.3 52.2 57.0 61.3 65.6 72.3 76.8 79.4 82.2

Charging Current Amps/kft 1.46 1.66 1.83 2.00 2.15 2.30 2.53 2.69 2.78 2.88

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 714 842 952 1037 1111 1179 1413 1532 1633 1718

Power Rating MVA 200 235 266 290 310 329 395 428 456 480

Typical Double Ductbank4 Amps 607 711 799 866 924 977 1163 1255 1330 1393

Power Rating MVA 170 199 223 242 258 273 325 350 371 389

161 kV XLPE - Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 169

BIL Rating 750

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 280 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll xlpe co

pper co

rrUg

ated SH

eatH

63 64

Section 5161 kV power cables

161 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or MIlliken• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 690 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Copper Corrugated Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.

3 Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current.

4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE COPPER CORRUgATED SHEATH

Page 35: Hv Solutions Catalog

conductor Size in kcmil 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.26 1.38 1.49 1.61

mm 24.7 28.5 31.9 35.0 37.8 40.9

Insulation Thickness mils 840 790 760 730 710 690

mm 33.1 31.1 29.9 28.7 28.0 27.2

Diameter over Insulation in 2.77 2.82 2.89 2.95 3.02 3.08

mm 70.3 71.6 73.4 74.9 76.7 78.3

Diameter over Sheath in 3.42 3.47 3.55 3.62 3.70 3.76

mm 86.9 88.1 90.2 91.9 93.9 95.6

Overall Jacket Diameter in 3.70 3.76 3.83 3.90 3.98 4.04

mm 94.1 95.5 97.3 99.0 101.0 102.7

Total Weight lbs/ft 4.5 4.7 5.0 5.3 5.6 5.9

Min. Bending Radius (install/perm.) in in 74/56 75/56 77/57 78/58 80/60 81/61

Maximum Pulling Tension lbs 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 150x95 150x95 150x95 150x95 150x95 150x95

Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 2,725

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 7.2 7.2 7.2 7.2 7.2 7.2

Insulation Shield kV/mm 2.8 3.2 3.4 3.6 3.8 4.0

Short circuit for 0.5s2

Conductor kA 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 46.8 47.4 48.5 49.5 50.5 51.4

conductor resistance

DC @ 20o C Ω/kft 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.030 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 41.7 47.3 52.2 57.0 61.3 65.6

Charging Current Amps/kft 1.46 1.66 1.83 2.00 2.15 2.30

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 559 665 758 833 902 969

Power Rating MVA 156 186 212 233 252 271

Typical Double Ductbank3 Amps 475 562 637 697 751 804

Power Rating MVA 133 157 178 195 210 225

161 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 169

BIL Rating 750

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 280 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll xlpe alU

min

Um

co

rrUg

ated SH

eatH

65 66

Section 5161 kV power cables

161 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 690 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Aluminum Corrugated Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 50 mils alluminum sheath. Thicker sheath can accommodate more current.3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE ALUMINUM CORRUgATED SHEATH

Page 36: Hv Solutions Catalog

conductor Size in kcmil1 750 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 24.7 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Insulation Thickness mils 840 790 760 730 710 690 700 710 720 730

mm 33.1 31.1 29.9 28.7 28.0 27.2 27.6 28.0 28.3 28.7

Diameter over Insulation in 2.77 2.82 2.89 2.95 3.02 3.08 3.36 3.52 3.72 3.87

mm 70.3 71.6 73.4 74.9 76.7 78.3 85.3 89.4 94.4 98.3

Diameter over Sheath in 3.15 3.20 3.28 3.34 3.41 3.47 3.69 3.87 4.05 4.20

mm 80.1 81.3 83.2 84.7 86.5 88.1 93.8 98.3 102.8 106.7

Overall Jacket Diameter in 3.47 3.52 3.60 3.66 3.73 3.79 4.01 4.19 4.37 4.52

mm 88.2 89.5 91.3 92.8 94.6 96.2 101.9 106.5 110.9 114.8

Total Weight lbs/ft 6.7 7.5 8.4 9.2 10.0 10.8 12.8 14.6 16.5 18.4

Min. Bending Radius (install/

perm.)in 69/52 70/53 72/54 73/55 75/56 76/57 80/60 84/63 87/65 90/68

Maximum Pulling Tension lbs 6,000 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Traverse in 138x95 138x95 138x95 138x95 150x95 150x95 150x95 150x95 158x95 158x95

Shipping Reel Capacity2 ft 3,000 3,000 3,000 3,000 3,000 3,000 2,725 2,600 2,250 2,025

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 7.2 7.2 7.2 7.2 7.2 7.2 6.9 6.8 6.6 6.4

Insulation Shield kV/mm 2.8 3.2 3.4 3.6 3.8 4.0 4.0 4.1 4.0 4.0

Short circuit for 0.5s3

Conductor kA 76.9 102.5 128.1 153.8 179.4 205.0 256.3 307.5 358.8 410.0

Sheath kA 43.8 43.9 44.1 44.3 44.5 44.6 45.2 45.7 46.1 46.5

conductor resistance

DC @ 20o C Ω/kft 0.014 0.011 0.008 0.007 0.007 0.005 0.004 0.004 0.003 0.003

DC @ 90o C Ω/kft 0.018 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 41.7 47.3 52.2 57.0 61.3 65.6 72.3 76.8 79.4 82.2

Charging Current Amps/kft 1.46 1.66 1.83 2.00 2.15 2.30 2.53 2.69 2.78 2.88

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 724 856 969 1058 1136 1209 1464 1602 1723 1830

Power Rating MVA 202 239 271 296 317 338 409 447 481 511

Typical Double Ductbank4 Amps 614 721 813 883 944 1001 1209 1317 1412 1495

Power Rating MVA 172 202 227 247 264 280 338 368 394 417

161 kV XLPE - Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 169

BIL Rating 750

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 280 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll xlpe co

pper neU

tra

lS WitH

c

opper c

om

poSite la

min

ate SHeatH

67 68

Section 5161 kV power cables

161 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or Milliken• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 690 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Copper Composite

Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.

3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current.

4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE COPPER NEUTRALS WITH COPPER COMPOSITE LAM INATE SHEATH

Page 37: Hv Solutions Catalog

conductor Size in kcmil 750 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 0.97 1.12 1.26 1.38 1.49 1.61

mm 24.7 28.5 31.9 35.0 37.8 40.9

Insulation Thickness mils 840 790 760 730 710 690

mm 33.1 31.1 29.9 28.7 28.0 27.2

Diameter over Insulation in 2.77 2.82 2.89 2.95 3.02 3.08

mm 70.3 71.6 73.4 74.9 76.7 78.3

Diameter over Sheath in 3.16 3.21 3.28 3.34 3.41 3.47

mm 80.2 81.4 83.3 84.8 86.6 88.2

Overall Jacket Diameter in 3.48 3.53 3.60 3.66 3.73 3.79

mm 88.3 89.6 91.4 92.9 94.7 96.3

Total Weight lbs/ft 5.0 5.2 5.5 5.8 6.1 6.4

Min. Bending Radius (install/perm.) in 70/52 71/53 72/54 73/55 75/56 76/57

Maximum Pulling Tension lbs 4,500 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 138x95 138x95 138x95 138x95 150x95 150x95

Shipping Reel Capacity1 ft 3,000 3,000 3,000 3,000 3,000 3,000

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 7.2 7.2 7.2 7.2 7.2 7.2

Insulation Shield kV/mm 2.8 3.2 3.4 3.6 3.8 4.0

Short circuit for 0.5s2

Conductor kA 50.8 67.7 84.6 101.5 118.5 135.4

Sheath kA 42.8 42.9 43.1 43.3 43.4 43.6

conductor resistance

DC @ 20o C Ω/kft 0.023 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.030 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 41.7 47.3 52.2 57.0 61.3 65.6

Charging Current Amps/kft 1.46 1.66 1.83 2.00 2.15 2.30

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 566 675 771 848 920 990

Power Rating MVA 158 189 216 237 257 277

Typical Double Ductbank3 Amps 480 569 646 708 765 821

Power Rating MVA 134 159 181 198 214 229

161 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 169

BIL Rating 750

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 280 kV / 15 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll xlpe co

pper neU

tra

l, a

lUm

inU

m c

om

poSite la

min

ate SHeatH

69 70

Section 5161 kV power cables

161 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 690 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Aluminum

Composite Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current.34ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE COPPER NEUTRALS WITH ALUMINUM COMPOSITE LAMINATE SHEATH

Page 38: Hv Solutions Catalog

KNOW YOUR OPTIONS: 230 KV POWER CABLES

CONDUCTOR MATERIAL AND SIzEConductor material is a matter of both customer preference and required current carrying capacity

• At 230 kV, copper is most common

• When both copper and aluminum conductors can meet your requirements, the more economical solution will be a function of the metal and the cable component costs

INSULATION THICKNESS• For cables with a radial moisture barrier, “Southwire(SW) Standard

Wall” reduced insulation thicknesses within AEIC specification CS9 are recommended

• For applications requiring smaller cable diameters, cables with reduced insulation thickness are available upon request within the stress limits in AEIC specification CS9

SHEATH MATERIAL• Copper and aluminum corrugated sheaths offer the best

mechanical and moisture protection for your HV cable, and copper will provide better short circuit performance and improved connectability

• Composite laminate sheaths in both copper and aluminum that offer excellent protection against moisture ingress

JACKET• Standard outer jacket: extruded LLDPE with a co-extruded outer

semi-conductive polyethylene layer for jacket integrity testing

• Halogen Free Fire Retardant (HFFR) compounds are available upon request for installations in cable trays and ventilated troughs

71 72

Section 6230 kV

power c

ables

Page 39: Hv Solutions Catalog

conductor Size in kcmil1 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Insulation Thickness mils 960 910 890 880 870 850 850 850 850

mm 37.8 35.8 35.0 34.6 34.3 33.5 33.5 33.5 33.5

Diameter over Insulation in 3.16 3.19 3.27 3.36 3.44 3.66 3.82 3.98 4.11

mm 80.2 81.0 83.1 85.3 87.5 93.0 97.1 101.0 104.4

Diameter over Sheath in 3.75 3.79 3.87 3.98 4.06 4.31 4.49 4.66 4.80

mm 95.3 96.2 98.4 101.0 103.1 109.4 113.9 118.3 121.9

Overall Jacket Diameter in 4.03 4.07 4.15 4.26 4.34 4.59 4.77 4.94 5.08

mm 102.4 103.3 105.5 108.1 110.3 116.6 121.1 125.4 129.0

Total Weight lbs/ft 8.5 9.2 10.1 11.1 12.0 14.1 16.0 18.0 19.8

Min. Bending Radius (install/perm.) in 81/60 81/61 83/62 85/64 87/65 92/69 95/71 99/74 102/76

Maximum Pulling Tension lbs 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Traverse in 158x95 158x95 158x95 158x95 158x95 158x95 158x95 158x95 158x95

Shipping Reel Capacity2 ft 2,900 2,925 2,925 2,775 2,775 2,550 2,250 1,925 1,825

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 9.0 9.0 8.9 8.8 8.7 8.6 8.5 8.2 8.1

Insulation Shield kV/mm 3.5 3.9 4.1 4.2 4.3 4.5 4.6 4.7 4.8

Short circuit for 0.5s3

Conductor kA 102.5 128.1 153.8 179.4 205.0 256.3 307.5 358.8 410.0

Sheath kA 47.0 47.5 48.5 49.8 50.9 54.0 56.2 58.3 60.2

conductor resistance

DC @ 20o C Ω/kft 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003

DC @ 90o C Ω/kft 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 41.6 46.1 49.6 52.5 55.3 62.4 66.2 69.8 73.0

Charging Current Amps/kft 2.08 2.31 2.48 2.63 2.77 3.12 3.31 3.49 3.65

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 850 950 1030 1100 1170 1372 1486 1579 1659

Power Rating MVA 339 379 411 439 467 547 592 630 661

Typical Double Ductbank4 Amps 720 800 860 920 960 1137 1225 1296 1357

Power Rating MVA 287 319 343 367 383 453 489 517 541

230 kV XLPE - Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 245

BIL Rating 1050

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 330 kV / 30 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll xlpe co

pper co

rrUg

ated SH

eatH

73 74

Section 6230 kV power cables

230 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or Milliken• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 850 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Welded Copper Corrugated Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.3 Declared values for 30 mils copper sheath. Thicker sheath can accommodate more current.4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE COPPER CORRUgATED SHEATH

Page 40: Hv Solutions Catalog

conductor Size in kcmil 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 1.12 1.26 1.38 1.49 1.61

mm 28.5 31.9 35.0 37.8 40.9

Insulation Thickness mils 960 910 890 880 870

mm 37.8 35.8 35.0 34.6 34.3

Diameter over Insulation in 3.16 3.19 3.27 3.36 3.44

mm 80.2 81.0 83.1 85.3 87.5

Diameter over Sheath in 3.87 3.90 3.99 4.09 4.18

mm 98.2 99.1 101.3 104.0 106.2

Overall Jacket Diameter in 4.15 4.18 4.27 4.37 4.46

mm 105.3 106.2 108.4 111.0 113.3

Total Weight lbs/ft 5.5 5.8 6.1 6.5 6.8

Min. Bending Radius (install/perm.) in in 83/62 84/63 85/64 87/66 89/67

Maximum Pulling Tension lbs 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 158x95 158x95 158x95 158x95 158x95

Shipping Reel Capacity1 ft 2,925 2,925 2,750 2,800 2,625

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 9.0 9.0 8.9 8.8 8.7

Insulation Shield kV/mm 3.5 3.9 4.1 4.2 4.3

Short circuit for 0.5s2

Conductor kA 67.7 84.6 101.5 118.5 135.4

Sheath kA 52.9 53.3 54.5 56 57.2

conductor resistance

DC @ 20o C Ω/kft 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 41.6 46.1 49.6 52.5 55.3

Charging Current Amps/kft 2.08 2.31 2.48 2.63 2.77

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 670 760 830 900 960

Power Rating MVA 267 303 331 359 383

Typical Double Ductbank3 Amps 570 640 700 750 800

Power Rating MVA 228 255 279 299 319

230 kV XLPE - Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 245

BIL Rating 1050

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 330 kV / 30 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll xlpe alU

min

Um

co

rrUg

ated SH

eatH

75 76

Section 6230 kV power cables

230 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 870 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Welded Aluminum Corrugated Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer• Firmly Bonded Insulation Shield

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 50 mils aluminum sheath. Thicker sheath can accommodate more current.3 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL XLPE ALUMINUM CORRUgATED SHEATH

Page 41: Hv Solutions Catalog

conductor Size in kcmil1 1000 1250 1500 1750 2000 2500 3000 3500 4000

Dimensional Nominal

Conductor Diameter in 1.12 1.25 1.37 1.48 1.61 1.76 1.92 2.08 2.21

mm 28.5 31.8 34.8 37.6 40.9 44.7 48.8 52.8 56.1

Insulation Thickness mils 960 910 890 880 870 850 850 850 850

mm 37.8 35.8 35.0 34.6 34.3 33.5 33.5 33.5 33.5

Diameter over Insulation in 3.16 3.19 3.27 3.36 3.44 3.66 3.82 3.98 4.11

mm 80.2 81.0 83.1 85.3 87.5 93.0 97.1 101.0 104.4

Diameter over Sheath in 3.54 3.58 3.66 3.75 3.83 4.07 4.23 4.39 4.52

mm 90.0 90.8 92.8 95.1 97.2 103.4 107.5 111.4 114.8

Overall Jacket Diameter in 3.86 3.90 3.98 4.07 4.15 4.39 4.55 4.71 4.84

mm 98.1 98.9 101.0 103.3 105.4 111.5 115.6 119.5 123.0

Total Weight lbs/ft 8.3 9.1 9.9 10.8 11.7 13.8 15.6 17.5 19.3

Min. Bending Radius (install/perm.) in 77/58 78/58 80/60 81/61 83/62 88/66 91/68 94/71 97/73

Maximum Pulling Tension lbs 8,000 10,000 12,000 14,000 16,000 20,000 24,000 28,000 32,000

typical Shipping reel Size

Flange x Traverse in 150x95 150x95 150x95 158x95 158x95 158x95 158x95 158x95 158x95

Shipping Reel Capacity2 ft 3,000 3,000 3,000 2,925 2,925 2,700 2,375 2,100 1,900

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 9.0 9.0 8.9 8.8 8.7 8.6 8.5 8.2 8.1

Insulation Shield kV/mm 3.5 3.9 4.1 4.2 4.3 4.5 4.6 4.7 4.8

Short circuit for 0.5s3

Conductor kA 102.5 128.1 153.8 179.4 205 256.3 307.5 358.8 410

Sheath kA 44.8 44.9 45.1 45.3 45.6 46.2 46.6 47.0 47.4

conductor resistance

DC @ 20o C Ω/kft 0.011 0.008 0.007 0.006 0.005 0.004 0.004 0.003 0.003

DC @ 90o C Ω/kft 0.014 0.011 0.009 0.008 0.007 0.005 0.005 0.004 0.003

Capacitance pF/ft 41.6 46.1 49.6 52.5 55.3 62.4 66.2 69.8 73.0

Charging Current Amps/kft 2.08 2.31 2.48 2.63 2.77 3.12 3.31 3.49 3.65

Ampacity @ 90o C per circuit

Typical Single Ductbank4 Amps 860 970 1050 1130 1200 1435 1507 1689 1794

Power Rating MVA 343 387 419 451 479 572 601 673 715

Typical Double Ductbank4 Amps 730 810 880 940 1000 1189 1296 1389 1471

Power Rating MVA 291 323 351 375 399 474 517 554 587

230 kV XLPE – Copper Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 245

BIL Rating 1050

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 330 kV / 30 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

77 78

Section 6230 kV power cables

230 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Copper,

Compressed Conductor or Milliken• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 850 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Copper Composite

Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 2500-4000 kcmil conductors are 5 segment Milliken conductors.2 Increased shipping reel capacity can be accommodated on request.3 Declared values for 80 x 14 AWG copper wire screen with 6 mil copper tape shield. Larger wires can accommodate more current.4 4ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL, COPPER NEUTRALS, COPPER COMPOSITE LAMINATE SHEATH

SW Sta

nd

ard

Wa

ll, co

pper neU

tra

lS, co

pper co

mpo

Site la

min

ate SHeatH

Page 42: Hv Solutions Catalog

conductor Size in kcmil 1000 1250 1500 1750 2000

Dimensional Nominal

Conductor Diameter in 1.12 1.26 1.38 1.49 1.61

mm 28.5 31.9 35.0 37.8 40.9

Insulation Thickness mils 960 910 890 880 870

mm 37.8 35.8 35.0 34.6 34.3

Diameter over Insulation in 3.16 3.19 3.27 3.36 3.44

mm 80.2 81.0 83.1 85.3 87.5

Diameter over Sheath in 3.55 3.58 3.66 3.75 3.83

mm 90.1 90.9 92.9 95.2 97.3

Overall Jacket Diameter in 3.87 3.90 3.98 4.07 4.15

mm 98.2 99.0 101.1 103.4 105.5

Total Weight lbs/ft 6.0 6.2 6.5 6.9 7.2

Min. Bending Radius (install/perm.) in 77/58 78/58 80/60 81/61 83/62

Maximum Pulling Tension lbs 6,000 7,500 9,000 10,500 12,000

typical Shipping reel Size

Flange x Traverse in 150x95 150x95 150x95 158x95 158x95

Shipping Reel Capacity1 ft 3,000 3,000 3,000 2,925 2,925

Electrical

electrical Stress @ Uo

Conductor Shield kV/mm 9.0 9.0 8.9 8.8 8.7

Insulation Shield kV/mm 3.5 3.9 4.1 4.2 4.3

Short circuit for 0.5s2

Conductor kA 67.7 84.6 101.5 118.5 135.4

Sheath kA 43.7 43.8 44.0 44.2 44.4

conductor resistance

DC @ 20o C Ω/kft 0.017 0.014 0.012 0.010 0.009

DC @ 90o C Ω/kft 0.022 0.018 0.015 0.013 0.011

Capacitance pF/ft 41.6 46.1 49.6 52.5 55.3

Charging Current Amps/kft 2.08 2.31 2.48 2.63 2.77

Ampacity @ 90o C per circuit

Typical Single Ductbank3 Amps 690 770 850 920 980

Power Rating MVA 275 307 339 367 391

Typical Double Ductbank3 Amps 580 650 710 770 820

Power Rating MVA 232 259 283 307 327

230 kV XLPE – Aluminum Conductor

cable data

Voltage Characteristics (kV)

Max Voltage Rating 245

BIL Rating 1050

Temperatures (oC)

Nominal Conductor 90

Max. Emergency Conductor 105

Short Circuit Conductor 250

Minimum Installation -10

Design Characteristics

Design Standards AEIC, IEC

Typical Test Voltages 330 kV / 30 min.

XLPE Loss Factor 0.0005

Relative Permittivity 2.3

SW Sta

nd

ard

Wa

ll, co

pper neU

tra

lS, alU

min

Um

co

mpo

Site la

min

ate SHeatH

79 80

Section 6230 kV power cables

230 kV pow

er cables

CABLE CONSTRUCTION• Reverse Concentric Stranded Aluminum,

Compressed Conductor• Super Smooth Conductor Shield• Super Clean XLPE Insulation• 870 mil XLPE minimum

• True Triple Extrusion and Dry Cured• Firmly Bonded Insulation Shield• Copper Neutrals with Aluminum

Composite Laminate Sheath• Polyethylene Jacket with Extruded

Semi-Conductive Outer Layer

1 Increased shipping reel capacity can be accommodated on request.2 Declared values for 80 x 14 AWG copper wire screen with 8 mil aluminum tape shield. Larger wires can accommodate more current.34ft top of duct, 1oC-m/W native, 0.8oC-m/W ductbank backfill, 25oC Ambient, 75% lf, 9” spacing, single-point or cross bonded

SW STANDARD WALL, COPPER NEUTRALS, ALUMINUM COMPOSITE LAMINATE SHEATH

Page 43: Hv Solutions Catalog

KNOW YOUR OPTIONS: HV CABLE ACCESSORIES

81 82

Section 7H

V c

able accessories

Southwire HV Solutions is proud to be North America’s exclusive supplier of NKT Cables’ complete line of high voltage cable accessories

Page 44: Hv Solutions Catalog

Components Design Criteria

83 84

Section 7HV cable accessories

HV

cable a

ccessories

Silicone rubber is a preferred material for cable accessories due to its excellent mechanical and electrical properties. For more than 40 years, silicone has been used successfully as high-quality electrical insulation for voltages up to 400 kV. Silicone rubber features high quality electrical insulation, superior corona and tracking resistance, combined with high elasticity. It facilitates multi range application, where one silicone rubber body can be used for various conductor cross sections. Optimal flexibility ensures easy assembly of the accessories.

outstanding features of the silicone rubber insulation material are:

• UV and ozone resistance

• Durable water rejection

• Weather and aging resistance

• Non-flammable, self-extinguishing, heat resistant

• Applicable for use at temperatures between -50° C and +180° C

• High elasticity

• High tracking resistance

• Unlimited storage life

• Friendly to the environment

The specific electrical problems of the cable termination are found at the point between the high-grade solid electrical insulation of the cable and the gaseous insulation air, which has a significantly lower dielectric strength. In order to achieve sufficient insulating clearance, the outer conductive layer of the cable must be stripped to below the end of the core. This causes unacceptably high field intensities at the end of the outer conductive layer (figure 1) which must be eliminated by means of stress control. Figure 2 shows the field of the cable termination controlled capacitively by a funnel shaped electrode. It is dimensioned in such a way that field intensities do not exceed at any point. This prevents harmful partial discharge.

Page 45: Hv Solutions Catalog

Outdoor Termination

Outdoor Termination

85 86

Section 7HV cable accessories

HV

cable a

ccessories

FeV-V oUtdoor termination WitH compoSite inSUlator

The different versions of this outdoor termination type FEV-V are designed for operation under severe outdoor conditions. Main components of the termination are the composite insulator with upper metal work, metal base plate with supporting insulators and premolded stress cone for electrical field control.

• Integrated premolded stress control system made of silicone rubber

• All metal work made of corrosion resistant aluminum alloy

• Termination is standing on supporting pedestal insulators, so that the cable screen can be isolated from earth

• Silicone fluid filled

• Top bolt available in two versions, screw type or press type

• Different top bolt diameter available suiting to the cable dimensions

• Type tested on Southwire Cable according to IEEE 48 and IEC 60840

FeV-p oUtdoor termination WitH porcelain inSUlator

The different versions of outdoor termination type FEV-P are designed for operation under severe outdoor conditions. Main components of the termination are the porcelain insulator with upper metal work, metal base plate with supporting insulators and premolded stress cone for electrical field control.

• Integrated premolded stress control system made of silicone rubber

• All metal work made of corrosion resistant aluminum alloy

• Termination is standing on supporting pedestal insulators, so that the cable screen can be isolated from earth

• Silicone fluid filled

• Top bolt available in two versions, screw type or press type

• Different top bolt diameter available suiting to the cable dimensions

• Type tested on Southwire Cable according to IEEE 48 and IEC 60840

Page 46: Hv Solutions Catalog

Switchgear and Transformer Termination

Switchgear and Transformer Termination

87 88

Section 7HV cable accessories

HV

cable a

ccessories

KSeV/KteV dry type plUg-in termination Up to 145 kV

All versions of dry-type termination are designed for installation in SF6 gas insulated switchgear (GIS) or for installation in the oil filled cable box of the transformer. The complete termination consists of epoxy resin insulator with embedded electrode, fixing ring which is fitted to the cable, comprising metal cable gland, compression device and premolded plug-in stress cone for electrical field control.

• Plug-in part comprising of four components (stress cone made of silicone rubber, cable gland, connection bolt, spring loaded compression device)

• Insulator according with IEC 60859 for GIS and transformer termination

• Conductor connection bolt designed as mechanical screw type connector

• Combination with different adapter and additional electrodes are available to fulfill the requirements of IEC 60859 Part 1 and 2 and older switchgear housings.

• Type test certificate in accordance with IEC 60840 available

• Dead-end plug available

SeV/teV epoxy inSUlator termination

The termination is designed for direct installation in SF6 gas insulated switchgear (GIS) or in the oil filled cables box of the transformer. Major components of the termination are the pressure tight epoxy resin insulator with embedded electrode, metal fixing ring, metal cable gland and prefabricated stress cone for electrical field control.

• Integrated prefabricated stress control system with silicon rubber

• Pressure tight epoxy resin insulator is cast in one piece with integrated insulation ring at the bottom allowing to separate the cable screen from earth.

• Cable gland made of corrosion resistant aluminum alloy

• Possible installation position vertical up to 45° then up to 90° with oil expansion vessel required

• Type test according to IEC 60840 is available

Page 47: Hv Solutions Catalog

Joint Aluminum Cable Clamps

89 90

Section 7HV cable accessories

HV

cable a

ccessories

Sm premolded Joint

This premolded joint in three piece design with compact dimensions is made of silicone rubber. Main components of the standard joint are conductor connection, cable adapters, main joint sleeve and outer protective covering.

• Integrated premolded stress control system with silicone rubber

• Three piece design with compact dimensions

• Screw type or compression conductor connector

• Minimal tool requirement

• Version with screen separation available

• Type tested on Southwire Cable according to IEEE 404 and IEC 60840

Southwire is proud to introduce its own line of High Voltage Cable Clamps. Made of anodized aluminum, these clamps can accommodate cables diameters ranging from 3 -5 inches. Every set includes the requisite parts (nuts, bolts and washers) for secure mounting and can be equipped with compression springs to accommodate various sheathing options.

Cable Diameter Part Number

3” – 4” (76mm – 101mm) SWHV – 809 Size 1

4” – 5” (101mm – 127mm) SWHV – 809 Size 2

3” – 4” (76mm – 101mm) SWHV – 809S Size 1 (w/ springs)

4” – 5” (101mm – 127mm) SWHV – 809S Size 2 (w/ springs)

Page 48: Hv Solutions Catalog

SOUTHWIRE

HV SOLUTIONS™

SoUtHWire companyOne Southwire DriveCarrollton, Georgia 30119

800-444-1700www.southwire.com

edition 2011.1