HV Substation Interface Activities: Safety/Operational Requirements Produced By: C Doyle

Transcript of HV Interface Presentation (1)

Page 1: HV Interface Presentation (1)

HV Substation Interface Activities: Safety/Operational Requirements

Produced By: C Doyle

Page 2: HV Interface Presentation (1)

Contents

• Activity 1: Installation• Activity 2A: Cable termination HV & LV• Activity 2B: Unlicensed Commissioning• Activity 3: Back Energisation• Activity 4: Commissioning• Activity 5: Post COD

Page 3: HV Interface Presentation (1)

HV INTERFACE ACTIVITY 1: INSTALLATION

HV Substation Interface Activities

Page 4: HV Interface Presentation (1)

HV Interface: Activity 1

Installation• Civil works (cable ducts)• Cable Support Install• Scaffolding• HV Cable Pull• LV Cable Pull• Earthing (assume PS Earth is Tested/Complete)• Install APDF Remote I/O Panel• NG Unlicensed Relays Installation in M1/M2

Page 5: HV Interface Presentation (1)

HV Interface Activity 1: Installation Safety/Procedural Boundaries

X190

X196

X194

X193

F19A

Cable bushing

Sub FenceSUBSTATION POWERSTATION

SAFETY:• NG Safety Rules Apply• NG Performs CPS• SAP (P.Monaghan, Brian

Sleigh)• Implementation Safety

Coordinator (P. Monaghan? TBC)

• Following Review of RAMS, LWC may be issued

• Point of isolation issued for work on LV systems/ System Connection Rules

SAFETY:• APDF work is undertaken

under APDF Local Safety Instructions/Safety Rules

• Rules submitted to NG For Review

• RAMS submitted to NG 3 weeks prior to work taking place for review by NG

Operational:• APDF work under a point

of isolation for any LV work utilising their own Safety Instructions

APDF Working Party Requires:NG Persons NG Competent Persons (key Holder also)Approved scaffolders for NG Safety Rules

Operational:• NG Local Instructions • NG Performs CPO

Notes:• Area will be delineated with the EPC Contractor as PC

under the CDM Regs. APDF can access through own gate but will require a key holder under NG rules. This should be agreed at CDM meeting and also discussed through TP153 meeting to finalise.

• Programme of work to be managed through TP106 and specific working groups. APDF must submit detailed activity programme.

• Note: If earths are not terminated insulated working must be carried out under NSI 5,6 &24, RAMS should be based on this (preferably not done until earths are connected for safety)

Circuit equipment on Power station side

Surge Arrestors

Cable Protected Both Ends

Module M1/M2

Cable Pulled Not Terminated

CCT 1 & CCT 2 C&P Module

Esbi Civil Contractor RequiredNG Persons NG Competent Persons (key Holder also)

NG Working Party Requires:• To work under APDF Permit• Trained as person and work under APDF competent

person

Page 6: HV Interface Presentation (1)

Actions• APDF to confirm what qualifications/inductions NG Working Party Requires to

install Protection Relays in M1/M2 and process for submitting RAMS• APDF to confirm list of personnel undergoing Person/Competent Person

training from AP and DF and that a key holder will also be provided• APDF to confirm the qualifications of their contractors who will access the

substation for cable pulling HV/LV/I&C, cable support install and terminations• APDF RAMs to be submitted to NG a minimum of 3 weeks prior to proposed

work, this is to be coordinated through the TP106/153 meetings on site. ESBI remind APDF of site RAMS review period by OE prior to submission to NG.

• A safety inaugural meeting will be required to take place 6 weeks prior to any works commencing, APDF to advise when this should be scheduled

• APDF to review programme submitted under APDF/CPL/1187 and advise on current programme as changes should be coordinated through the TP meetings with NG

Page 7: HV Interface Presentation (1)

HV INTERFACE ACTIVITY 2A: CABLE TERMINATION HV & LV

HV Substation Interface Activities

Page 8: HV Interface Presentation (1)

HV Interface: Activity 2A

Cable Termination: HV & LV• Install GIS Sealing End (ABB Interface)• HV Cable Testing• Install HV Cable Termination• Earth Terminations (cable)• Scaffolding• LV Cable Testing and Terminations

Page 9: HV Interface Presentation (1)

HV Interface Activity 2A: HV & LV Cable Terminations

X190

X196

X194

X193

F19A

Cable bushing

Sub FenceSUBSTATION POWERSTATION

SAFETY:• NG Safety Rules Apply• NG Performs CPS• SAP (P.Monaghan, Brian

Sleigh)• Implementation Safety

Coordinator (P. Monaghan? TBC)

• Following Review of RAMS, LWC may be issued

• Point of isolation issued for work on LV systems/ System Connection Rules

SAFETY:• APDF work is undertaken

under APDF Local Safety Instructions/Safety Rules

• Rules submitted to NG For Review

• Trafo Compound locked and under NG Safety Rules

Operational:• APDF work under a point

of isolation for any LV work utilising their own Safety Instructions

APDF Working Party Requires:NG Persons NG Competent Persons (key Holder also)Approved scaffolders for NG Safety Rules

Operational:• NG Local Instructions

Apply for Isolations• HVSCC Required to bring

cable and sealing ends in remote compound (Trafo) under NG CPO

• NG Performs CPO

Notes:• Area will be delineated with the EPC Contractor as PC

under the CDM Regs. APDF can access through own gate but will require a key holder under NG rules. This should be agreed at CDM meeting and also discussed through TP153 meeting to finalise.

• Programme of work to be managed through TP106 and specific working groups. APDF must submit detailed activity programme.

• Note: If earths are not terminated insulated working must be carried out under NSI rules, RAMS should be based on this (preferably not done until earths are connected for safety)

Circuit equipment on Power station side

Module M1/M2CCT 1 & CCT 2 C&P Module

No System Connection 3.5m Safety Distance

Page 10: HV Interface Presentation (1)

HV INTERFACE ACTIVITY 2B: UNLICENSED COMMISSIONING PHASE 1

HV Substation Interface Activities

Page 11: HV Interface Presentation (1)

HV Interface: Activity 2B

Unlicensed Commissioning: (LV Cable terminations Complete, Prior to HV Cable)• Commissioning of signals between PP & SS

(Phase 1)

Page 12: HV Interface Presentation (1)

HV Interface Activity 2B: Unlicensed Relay Commissioning Phase 1

X190

X196

X194

X193

F19A

Cable bushing

Sub FenceSUBSTATION POWERSTATION

SAFETY:• NG Safety Rules Apply• NG Performs CPS• SAP (P.Monaghan, Brian

Sleigh)• Implementation Safety

Coordinator (P. Monaghan? TBC)

• Following Review of RAMS, LWC may be issued

SAFETY:• NG work in M1/M2

under APDF rules• Further coordination

required in working group meetings

Operational:• Discuss with APDF. How

will this interface be managed (Phase 1)

NG Working Party Requires:• To work under APDF Permit• Trained as person and work under APDF competent

person

Operational:• NG Local Instructions

Apply for Isolations• NG Performs CPO• SRS requires discussion

at TP153 (LV equipment)

Notes:• SRS requires discussion at TP153 (LV equipment)• Programme of work to be managed through TP106 and

specific working groups. APDF must submit detailed activity programme.

• NG will work under APDF rules in Module M1/M2Circuit equipment on Power station side

Module M1/M2CCT 1 & CCT 2 C&P Module

No System Connection 3.5m Safety Distance

Page 13: HV Interface Presentation (1)

Actions

• NG Unlicensed to confirm power requirements for relays and APDF to ensure these are available for programmed dates

• NG unlicensed to provide commissioning plan for Phase 1 & Phase 2 commissioning

Page 14: HV Interface Presentation (1)

HV INTERFACE ACTIVITY 3A: BACK ENERGISATION CABLE SOAK

HV Substation Interface Activities

Page 15: HV Interface Presentation (1)

HV Interface: Activity 3

Back Energisation: Cable Soak

• Switch in cable for 24hr soak test• HVSCC issued and Revert Back to busbar

disconnects for further back energisation under NG CPS and APDF CPO

Page 16: HV Interface Presentation (1)

HV Interface Activity 3: Back Energisation Cable Soak

X190

X196

X194

X193

F19A

Cable bushing

Sub FenceSUBSTATION POWERSTATION

SAFETY:• NG Safety Rules Apply• NG Performs CPS• SAP (P.Monaghan, Brian

Sleigh)• Implementation Safety

Coordinator (P. Monaghan? TBC)

• Following Review of RAMS a RISSP may be issued

SAFETY:• APDF work is undertaken

under APDF Local Safety Instructions/Safety Rules

• Rules submitted to NG For Review

• Trafo Compound locked and under NG Safety Rules

Operational:• National Grid are CPO

APDF Working Party Requires:NG Persons NG Competent Persons (key Holder also)

Operational:• NG Local Instructions

Apply for Isolations• HVSCC Required to bring

cable and sealing ends in remote compound (Trafo) under NG CPO

• NG Performs CPO

Notes:• Area will be delineated with the EPC Contractor as PC

under the CDM Regs. APDF can access through own gate but will require a key holder under NG rules. This should be agreed at CDM meeting and also discussed through TP153 meeting to finalise.

• Programme of work to be managed through TP106 and specific working groups. APDF must submit detailed activity programme.

• Immediately after cable soak the control boundary moves to HV disconnects under a HVSCC, NG relinquish CPO role and O&M undertake this role under their local instructions which have been approved by NG

• NG retain the CPS role under contract to Asset Management

• Partial Discharge monitoring/testing to be discussed at TP106

Circuit equipment on Power station side

Module M1/M2CCT 1 & CCT 2 C&P Module

No System Connection 3.5m Safety Distance

Page 17: HV Interface Presentation (1)

HV INTERFACE ACTIVITY 3: BACK ENERGISATION

HV Substation Interface Activities

Page 18: HV Interface Presentation (1)

HV Interface: Activity 3

Back Energisation: GSUT Energisation, LV GCB, 6.6kV (as per back energisation procedure)

• Energise GSUT, IPB’s, HV Side of GCB, UT up to 6.6kV Incoming Breakers

Page 19: HV Interface Presentation (1)

HV Interface Activity 3B: Back Energisation: GSUT Energisation, LV GCB, 6.6kV (as per back energisation procedure)

X190

X196

X194

X193

F19A

Cable bushing

Sub FenceSUBSTATION (O&M Operational CPO)

POWERSTATION

SAFETY:• NG Safety Rules Apply• NG Performs CPS• SAP (P.Monaghan, Brian

Sleigh)• Implementation Safety

Coordinator (P. Monaghan? TBC)

• Following Review of RAMS a RISSP may be issued (type of safety document to be discussed)

SAFETY:• APDF work is undertaken

under APDF Local Safety Instructions/Safety Rules

• RISSP Issued and taken by O&M CPO, RISSP integrated into APDF safety rules

Operational:• O&M are now CPO

under their operational procedures/local instructions

APDF Working Party in Substation Requires:NG Persons NG Competent Persons (key Holder also)APDF liaise with O&M CPO/Requesting Safety officer

Operational:• HVSCC agreed with SRS

defined as O&M CPO• Contact persons agreed

in SRS and through compliance process between O&M CPO and NG Control Centre

Notes:• Area will be delineated with the EPC Contractor as PC

under the CDM Regs. APDF can access through own gate but will require a key holder under NG rules. This should be agreed at CDM meeting and also discussed through TP153 meeting to finalise.

• Programme of work to be managed through TP106 and specific working groups. APDF must submit detailed activity programme.

• NG retain the CPS role under contract to Asset Management

• O&M are CPO

Circuit equipment on Power station side

Module M1/M2CCT 1 & CCT 2 C&P Module

O&M Personnel:NG Persons (to access substation)Competent PersonsAuthorised PersonsRequesting Safety Officer (can be the CPO) but must be trained to level to receive a RISSP

Page 20: HV Interface Presentation (1)

Control/Safety/Maintenance Ownership Boundaries

X190X196

X194

X193

CCGT Equipment

Sub Fence

NG Safety Rules /Maintenance

NG Ownership

NG Operational

APDF Safety rules

O&M Ownership

O&M Operational

Page 21: HV Interface Presentation (1)

HV Safety/Operational Interface Protocol

Warwick

Substation

Power Station

NG

O&M

APDF

HV Control Person/ CPO

CPOCPS

Implementing Safety

Coordinator/ SAP

APDF HV Interface manager

TP106/TP153/Working Group meetings

Planned Operational Switching/ Outages

Client Review

Planned Outages

Planned Operational Switching

Emergency Switching

Planned Switching Communications

Switching Request/ RISSP Issue

Emergency Switching

Planned Switching

Page 22: HV Interface Presentation (1)

Actions

• O&M Safety Rules/HV Switching/RISSP Process (including third party involvement) to be finalised and submitted to NG for review ASAP

• O&M to confirm timelines for training of Authorised Personnel for HV Control Persons

• Switching should be remote i.e. DCS• APDF to include a HV Switching Interface protocol in

safety rules to include RISSP process• CPL/O&M to confirm that HV Busbar Disconnects are to

be switched by NG and not at DCS.

Page 23: HV Interface Presentation (1)

HV INTERFACE ACTIVITY 4: COMMISSIONING

HV Substation Interface Activities

Page 24: HV Interface Presentation (1)

HV Interface: Activity 4Commissioning

• Commissioning as Per APDF Programme• Phase 2 Commissioning of Unlicensed Protection Relays (load)• Full Control & Protection Commissioning• Plant functional tests• Grid Compliance Tests• Performance Test• Reliability Run• Handover

Page 25: HV Interface Presentation (1)

HV Interface Activity 4: Commissioning

X190

X196

X194

X193

F19A

Cable bushing

Sub FenceSUBSTATION (O&M Operational CPO)

POWERSTATION

SAFETY:• NG Safety Rules Apply• NG Performs CPS• SAP (P.Monaghan, Brian

Sleigh)• Implementation Safety

Coordinator (P. Monaghan? TBC)

• Following Review of RAMS a RISSP may be issued (type of safety document to be discussed)

SAFETY:• APDF work is undertaken

under APDF Local Safety Instructions/Safety Rules

• RISSP Issued and taken by O&M CPO, RISSP integrated into APDF safety rules

Operational:• O&M are now CPO

under their operational procedures/local instructions

APDF Working Party in Substation Requires:NG Persons NG Competent Persons (key Holder also)APDF liaise with O&M CPO/Requesting Safety officer

Operational:• HVSCC agreed with SRS

defined as O&M CPO• Contact persons agreed

in SRS and through compliance process between O&M CPO and NG Control Centre

Notes:• Area will be delineated with the EPC Contractor as PC

under the CDM Regs. APDF can access through own gate but will require a key holder under NG rules. This should be agreed at CDM meeting and also discussed through TP153 meeting to finalise.

• Programme of work to be managed through TP106 and specific working groups. APDF must submit detailed activity programme.

• NG retain the CPS role under contract to Asset Management

• O&M are CPO• O&M are working in APDF working parties for power

station commissioning and are trained under APDF Safety Rules

Circuit equipment on Power station side

Module M1/M2CCT 1 & CCT 2 C&P Module

O&M Personnel:NG Persons (to access substation)Competent PersonsAuthorised PersonsRequesting Safety Officer (can be the CPO) but must be trained to level to receive a RISSP

Page 26: HV Interface Presentation (1)

HV Interface: Activity 5

Post COD• Normal Operation

Page 27: HV Interface Presentation (1)

Control/Safety/Maintenance Ownership Boundaries

X190X196

X194

X193

CCGT Equipment

Sub Fence

NG Safety Rules /Maintenance

NG Ownership

NG Operational

O&M Ownership

O&M Operational

O&M Safety Rules /Maintenance

Page 28: HV Interface Presentation (1)

HV Safety/Operational Interface Protocol

Warwick

Substation

Power Station

NG

O&M

HV Control Person/ CPO

CPOCPS

Implementing Safety

Coordinator/ SAP

Planned Outages

Planned Operational Switching

Emergency Switching

Planned Switching Communications/TOGA

Switching Request/ RISSP Issue