High-Voltage Centre Break Disconnectors72.5 kV up to 420 kV
Answers for energy.
-
T e s t C o n f i r m a t i o nNo .
L 06078
Reference:Apparatus:
Manufacturer:
Customer:
Place and Date of Tests:Test Specification:Tests Performed:
Tests Results:
113-06/12409-16584Centre break disconnRated voltage: 145 kRated normal frequenSiemens AG, PTD HNonnendammallee 1Germany
Siemens AG, PTD HNonnendammallee 1GermanyFGH-LPF Mannheim
IEC 62271-102: 2001Extended mechanical 2000 operating cycle Verifikation of operat Fa=500N and Fb=During all operating characteristics and t devices are proofedNo significant change
test program can
be
After the tests all part wear. The disconnec The resistance of theThe above mention with the applied test
Detailed results wil
Thomas Schaefer Test Engineer
Mannheim, 21 NoveThis document may o
Independent test laborat (DATech) e.V. in
the field
magnetic compatibility
(EMember Laboratory of the
FGH Engineering
& Test GmbH
.
Hallenweg 40
.
68219 Mannheim
.
Germany
Telefon +49
(0)621/8047-0
.
Telefax +49
(0)621/8047-259
.
www.fgh
-ma.com
.
Combining Forces
Siemens is investing in research and development in order to manufacture the products you need now and will want in years to come. Decades of experience in high-voltage equipment go into the design and production of our products and set international trends. No matter what your application is, our high-voltage products provide the best solution for your requirements every time.
With our high-voltage centre break disconnectors and earthing switches forrated voltages from 72.5 up to 420 kV, we fulfill customers demands for reliabili-ty, safety and cost-effectiveness. By combining the strengths of our well provenproduct portfolio, we can provide this type of centre break disconnector.
By using the well-known maintenance-free contact system from Ruhrtal, we took the best of what disconnector technology has to offer and designed a family of disconnectors especially for your specifications. We meet the high standard of quality that Siemens is known for combined with our customers requirements for cost-effective disconnector products. With this centre break family, you have a reliable competitive solution with complete safety and peace of mind.
2
Well-known Design meets Best Price-Performance Ratio
TGA-ZM-02-90
C E R T I F I C A T E DQS GmbH Deutsche Gesellschaft zur Zertifizierung von Managementsystemen hereby certifies that the company
Siemens AG Power Transmission and Distribution
High Voltage Division Nonnendammallee 104 13629 Berlin
Freyeslebenstrae 1 91058 Erlangen
for the scope
Development, production and sales of products, systems and plants
of the high voltage switchgear, high voltage reactive power compensation and
high voltage direct current transmission including the necessary services
has implemented and maintains a
Quality and Environmental Management System.
Audits, documented in a report, have verified that this
management system fulfills the requirements of the following standards:
DIN EN ISO 9001 : 2000
EN ISO 14001 : 2004
December 2000 edition
November 2004 edition
This certificate is valid until 2009-09-30
Certificate Registration No. 009003 QM UM
Frankfurt am Main
2006-10-01
Ass. iur. M. Drechsel
Dipl.-Ing. S. Heinloth
MANAGING DIRECTORS D-60433 Frankfurt am Main, August-Schanz-Strae 21
Highlights:
Maintenance-free contact system without spring elements
Approved technology applied in more than 40,000 units
Type-tested according to IEC 62271-102
Rated current up to 3150 A, up to 50 kA 3 sec
Best price-performance ratio
-
3Our centre break disconnector family is available for rated voltages from 72.5 kV up to 420 kV. The centre break disconnector is the most frequently used discon-nector type worldwide. The base frame (4) carries the compact operating mecha-nism (5) and two rotating base mounted supporting insulators (2). In the closed position, the current flows via the current path arms (1), which are fixed to the insulators. The disconnector opens in the centre, thus providing an insulating distance.
Each rotating unit (3) comprises two high quality sealed ball-bearings and is de-signed for high mechanical loads, therefore providing a maintenance free service life. These qualities result in low service and investment costs which provide our customers with competitive advantages worldwide.
The Centre Break Disconnectors from Siemens
1 Current path arms2 Supporting insulators3 Rotating unit4 Base frame 5 Compact operating mechanism
5
1
2
3
4
-
The Contact System
The main contact system has been adopted from the well established range of Ruhrtal high-voltage dis-connector products. This system consists of block contacts and spread contact fingers and assures a steady contact force even after decades of operation. The current flows in the contact head from the terminal (7) to the current path tube (6) through highly-flexible copper leads (8).
6 7
8
4
The most significant features are:
Self-resilient contact fingers, no further spring elements necessary to generate the contact force
Factory-set contact forces, no re-adjustments required during service life
Ice layers up to 20 mm can be broken without difficulties
Silver-plated contact surface providing highest conductivity without regular grease lubrication
Maintenance-free contact system up to 25 years
By using the well-established blockfinger contact system, we provide our customers with very practical advantages: smooth operation, exemplary availability and optimum security.
-
The Earthing Switch
5
Three-pole centre break disconnector with earthing switch in inboard design
The use of earthing switches ensures absolute safety by grounding and discharging all high-voltage com-ponents in a circuit or switchgear. Suitable built-on earthing switches are available for the complete range of our centre break disconnector types from 72.5 up to 420 kV.
-
6Motor Operating Mechanism
The motor operating mechanism includes all components required for operating the disconnector and consists of three main subassemblies:
1 Corrosion-resistant housing (protection degree IP 55)
2 Gear unit with motor
3 Electrical equipment with auxiliary switch
The motor operating mechanism can also be operated manually by a hand crank which can be inserted inside the cubicle. The insertion of the hand crank automatically isolates the motor circuit for safety pur-poses. Heaters are provided to prevent condensation.
1
2
3
-
7Technical Data
High-Voltage Centre Break Disconnectors Type 3DN1
Rated normal current 1250/1600/2000/2500/3150 A
Values in accordance with IEC, other values on request
Rated lightning impulse withstand voltage
Rated short-time withstand current (1 s - 3 s) up to 50 kA
Temperature range -50 ... +50 C
Rated frequency 50/60 Hz
Control voltage 110/125/220/250 VDC
Motor voltage 110/125/220/250 VDC or
230 VAC, 50 Hz/ 60 Hz
Rated power frequency withstand voltage
Rated voltage 72.5 123 145 245 362 420300
common value 140 230 275 460 450 520395
across isolating distance 160 265 315 530 520 610435
across isolating distance 375 630 750 1200 1175 + 205 1425 + 2401050 + 170
common value 325 550 650 1050 1175 14251050
[kV]
[kV]
[kV]
[kV]
[kV]
-
For further Information
Name/Company
Street
Postal code/City/Country
Phone/Fax
E-mail
Please send me more information on the following topics:
Ruhrtal - Disconnectors and Earthing Switches
High-voltage circuit-breakers: Type 3AP1/2, 72.5 kV to 550 kV
High-voltage circuit-breakers for outdoor installation
Live-tank and dead-tank high-voltage circuit-breakers technology
High-voltage compact switchgear 3AP1 DTC for 145 kV and 245 kV
Eliminate stress: Controlled switching of high-voltage circuit-breakers
SF6 in power engineering - acting responsibly
Further copies of this brochure
Please fax this page to the following number: Fax +49 30/386-25867
or send us an e-mail: [email protected]
Power Transmission Division Order No. E50001-G630-A146-X-4A00 Printed in Germany Dispo-Stelle 30000 Mu. PA 11092.0
Siemens AG
Energy Sector
Power Transmission Division
High Voltage Products
Nonnendammallee 104
13629 Berlin, Germany
For more Information please contact our
Customer Support Center.
Phone: +49 180 524 7000
Fax: +49 180 524 2471
(Charges depending on provider)
Email: [email protected]
Printed on elementary chlorine-free bleached paper.
All rights reserved. Trademarks mentioned in this document are the property of Siemens AG, its affiliates, or their respective owners.
Subject to change without prior notice.
The information in this document contains general descrip-tions of the technical options available, which may not apply cases. The required technical options should therefore be specified in the contract.
Published by and copyright 2009
Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany
www.siemens.com/energy
www.hv-circuit-breaker.com