HUAWEI Telecom Energy Solutions Catalog.pdf

44
HUAWEI TECHNOLOGIES CO., LTD. HUAWEI Telecom Energy Solutions Migrate Towards Simplicity

Transcript of HUAWEI Telecom Energy Solutions Catalog.pdf

Page 1: HUAWEI Telecom Energy Solutions Catalog.pdf

HUAWEI TECHNOLOGIES CO., LTD.

HUAWEI Telecom Energy SolutionsMigrate Towards Simplicity

Page 2: HUAWEI Telecom Energy Solutions Catalog.pdf

Full connected world cannot build without network, power supply

become a key factor in network reliability. Along rapid development of

telecommunication industry, site number tends to be explosive and the

growth rate of energy cost exceeds increase of income. Low energy efficiency

and weak expansion ability of traditional site hardly meets requirements of

building a green broadband network and reducing operational cost. How to

effectively deploy sites, elevate energy efficiency and reduce carbon emissions

while improving the power supply and environment assurance reliability, has

become common challenges faced by enterprises and operators globally.

H uawei, with extensive experiences in digital technology, network

technology, M2M, software, big data, and power electronics, is

promoting legacy telecom power onto a new level, where energy

can be accessed anytime, anywhere, energy utilization becomes simpler, energy

management becomes smarter and energy facility is always ready to facilitate

network evolution. MTS (Migrate Towards Simplicity) makes everything simple,

ensures more efficient network and operation. Let's build a better connected

world, together.

Page 3: HUAWEI Telecom Energy Solutions Catalog.pdf

• Large Capacity Power System100A-24,000A/6kW-1,440kW

• Indoor Power System100A-600A/6kW-36kW

• Outdoor Power System100A-400A/6kW-24kW

• Wall-mounted Power System30A-60A/1.74kW-3.2kW

• Embedded Power System30A-400A/1.74kW-24kW

• Monitoring ModulesSUM02B/ECC500

• Rectifier Modules15A-100A/870W-6,000W

• Advanced Energy Storage ModulesESM-A2400Wh(D)/ESM-A9600Wh(N)

Contents

Large capacity power(100A-24,000A)

Outdoor power(100A-400A)

Indoor power(100A-600A)

Wall-mounted power(30A-60A)

Embedded power(30A-400A)

Page 4: HUAWEI Telecom Energy Solutions Catalog.pdf

6

• New Generation Outdoor SolutionMTS9000A

• PowerCube 1000 - Solar HybridPowerCube S1/S2/S3

• PowerCube 1000 - Diesel HybridPowerCube D1-Standard/D1-Advanced

• PowerCube 1000 - Grid HybridPowerCube G2/G3/G4/G4-Mini

• PowerCube 500IVS Solution

• Energy OSSNetEco

Diesel HybridMTS9000A

IVS Solution NetEco

Solar Hybrid

Grid Hybrid

Page 5: HUAWEI Telecom Energy Solutions Catalog.pdf

1

• New Generation Outdoor SolutionMTS9000A

• PowerCube 1000 - Solar HybridPowerCube S1/S2/S3

• PowerCube 1000 - Diesel HybridPowerCube D1-Standard/D1-Advanced

• PowerCube 1000 - Grid HybridPowerCube G2/G3/G4/G4-Mini

• PowerCube 500IVS Solution

• Energy OSSNetEco

Large Capacity Power System100A-24,000A/6kW-1,440kW

Huawei new generation all-digital large capacity power systems

include TP483000D, TP482000B and TP481200B. Adopting high

power desity design and 1U 100A or 50A high efficiency rectifiers,

single rectiifer cabinet can output maximum 3000A/180kw. The

systems have tremendous features such as high reliability, high

efficiency, high power density, high capacity, low noise and easy

maintenance.

Introduction

• Carrier class high reliability, system MTBF over 500,000 hours,

passed over 1000 test items

• Green and energy saving, rectifier efficiency over 96%

• Compact design, single rectifier cabinet can output maximum

3000A/180kw,which is the highest in industry

• Huge system capacity, TP483000D can be expanded to 24,000A

by parallel combination matching network evolution, while

TP482000B expanded to 10000A and TP481200B expanded to

6000A

• Flexible remote monitoring mode, saving OPEX

Features

Legacy power system modernization

• Wireless network central office

• Fixed network central office

• Large capacity convergence site

• Enterprise network central office

• Data center

Application Scenarios

Newly-built scenario

TP481200B TP482000B TP483000D

Legacy power

Reuse AC & DC distribution

Reuse AC distribution All swap

Integrated Type Distributed Type

Page 6: HUAWEI Telecom Energy Solutions Catalog.pdf

2

Specifications

Integrated large power system

Product style TP4812000B-N20C3 TP482000B-N20C5 TP482000B-L20B5

System

Dimension(W×D×H)

600mm×600mm×2000mm

Cabling mode Top inlet & outlet

Rated capacity 1200A(12×100A) 2000A(20×100A) 2000A(40×50A)

AC Distribution

Input mode220/380VAC, three phase four/five line (L1, L2, L3, PE or L1, L2, L3, N, PE)

120/208VAC, three phase four/five line

Input voltage 260VAC-530VAC, rated: 380VAC90VAC-290VAC, rated: 208VAC

Input capacity 2×150A/3P (MCCB) 2×150A/3P (terminal) 2×230A/3P (terminal)

DC Distribution

Battery branch 2×(1000A×2) (NT4) 2×(1000A×2) (NT4) 2×(1000A×2) (NT4)

Load branch6×500A(NT3), 6×160A(NT00), 6×100A(NT00)

6×500A(NT3), 6×160A(NT00), 6×100A(NT00)

6×500A(NT3), 6×160A(NT00), 6×100A(NT00)

Rectifier ModuleInput mode Three phase, 260VAC-530VAC 120V or 240V dual live wire

Rated capacity 100A/6000W 50A/3000W

Distributed large power system

Product style TP483000D

AC Distribution Cabinet

Cabinet style TPA38631B-N20B1 TPA38401B-N20B1

Dimension(W×D×H)

600mm×600mm×2000mm

Input mode 220/380VAC, three phase four/five line (L1, L2, L3, PE or L1, L2, L3, N, PE)

Input voltage 260VAC-530VAC, rated: 380VAC

Input capacity 1×630A/4P (two inputs/manual switchover) 1×400A/4P (two inputs/manual switchover)

AC output

6×160A/3P (MCCB)1×63A/3P (MCB)1×32A/3P (MCB)3×32A/1P (MCB)

4×160A/3P (MCCB)1×63A/3P (MCB)1×32A/3P (MCB)3×32A/1P (MCB)

DC Distribution Cabinet

Cabinet style TPD48302B-N20B1

Dimensions 800mm(W)×600mm(D)×2000mm(H)

Output voltage 42-58VDC, default value: 53.5VDC

Maximum capacity 3000A/180kW

Battery branch 2×(1250A×2) (NT4)

Load branch 8×500A(NT3), 4×400A(NT2), 4×200A(NT1), 8×160A(NT00), 6×100A(NT00)

Rectifier Cabinet

Cabinet style TPR48302B-N20C3 TPR48202B-N20C3

Dimensions(W×D×H) 600mm×600mm×2000mm

Rated capacity 3000A/180kW(30×100A/6kW) 2000A/120kW(20×100A/6kW)

Page 7: HUAWEI Telecom Energy Solutions Catalog.pdf

3

Indoor Power System100A-600A/6kW-36kW

The indoor power systems include integrated power(built-in

batteries) and detached power(separated batteries), whose output

range varies from 100A to 600A. The series can accommodate

high efficiency rectifier modules and have outstanding monitoring

functions, and have been applied in multiple indoor scenarios.

Introduction

• High rectifier efficiency (>98%) and non-derating below 55ºC

help save energy

• Footprint saving, 50% footprint saved by integrated power, ‘0’

footprint for rack stack / wall-mounted of mini power

• Large housing ability, up to 8 BBUs accommodation

• Intelligent battery management prolongs battery lifespan

• Support in-band transmission networking, ‘0’ extra data

collector and transmission link cost

• All-in-one controller, MIMO* energy scheduling mgmt., 5 AI, 9

DI, 8 DO

• Support solar access, saving grid expenditure

• High-temp. battery saves 70%-80% site A/C consumption

Features

• Indoor site of access network

• Indoor site of convergence network

• Medium and small capacity central office

• Enterprise communication network

Application Scenarios

Combined Type

Integrated Type

TP48200B/400B/600B

TP48300B/TP48600B Mini TP48300B

Mini Power Detached PowerIntegrated Power

supporting solar evolution

supporting solar evolution

High temp. battery

Unified NetEco

*MIMO: Multiple energy input, multiple mode output

Page 8: HUAWEI Telecom Energy Solutions Catalog.pdf

4

Integrated power system

Specifications

Product type TP48200B TP48400B TP48600B

Dimension(W×D×H)

600mm×600mm×2000mm 600mm×600mm×2000mm 600mm×600mm×2000mm

Rated capacity 200A 400A 600A

Battery space 16-32U(2-4×190Ah) 32U(4×190Ah) 24U(3×190Ah)

User space 0-16U N/A N/A

Input mode220V single phase380V three phase110V dual-wire

220V three phase380V three phase

220V three phase380V three phase

Load branchesLLVD: (MCB)5 branchesBLVD: (MCB)6 branches

LLVD: (MCB)10 branchesBLVD: (MCB)8 branches

LLVD: (fuse)4 branches+(MCB)10 branchesBLVD: (MCB)6 branches

Combined power system

Product type TP48300B TP48600B Mini TP48300B

Dimension(W×D×H)

600mm×400mm×1600mm 600mm×400mm×1600mm 442mm×360mm×480mm

Rated capacity 300A 600A 300A

Installation mode Antistatic floor/ ground installation Antistatic floor/ ground installationOn the battery rack, 19/21/23 inches open rack, ground, DFMU cabinet, wall-mounted

Input mode220V single phase380V three phase

220V three phase380V three phase

220V single phase380V three phase110V dual-wire

Load branchesLLVD: (fuse)7 branches+ (MCB)3 branchesBLVD: (MCB)4 branches

LLVD: (fuse)5 branches+ (MCB)7 branchesBLVD: (MCB)9 branches

LLVD: (MCB)8 branchesBLVD: (MCB)6 branches

Page 9: HUAWEI Telecom Energy Solutions Catalog.pdf

5

Outdoor Power System100A-400A/6kW-24kW

TP48200A(TP48400A) is an AC/DC outdoor power system

that configures 48V/50A rectifier modules to supply rated of

200A(400A) output current, with various cooling system: heat

exchanger(HEX), direct ventilation(DV) and TEC cooling. The power

system has excellent performance such as wide range of AC input

voltage, high power efficiency, intelligent battery management and

remote monitoring.

Introduction

• Cooling capacity up to 1500W, operation temperature can be

-40ºC-45ºC, IP55 protect level, protect main equipment to be

safe and reliable

• High power efficiency of rectifier >98%, intelligent rectifier

dormancy, saving energy

• Support electronic labels, can be co-managed by HUAWEI main

equipment OSS, saving management and maintenance cost

• Intelligent battery management and online test, prolonging

battery lifespan

• Cooling system equipped in door, easy maintance

Features

TP48200A/TP48400A

Integrated Type

TP48200A

Separated Type

TBC300A

Separated Type

• Outdoor carrier’s wireless site power scenarios

• Outdoor enterprise communication network power scenarios

Application Scenarios

Typical outdoor DBS

Typical outdoor BTS

Typical outdoor DBS+BTS

BBU(2U)

POWER (6U)

WIRE(2U)

SPARE

BATTERY

BBU(2U)

RRU

RRU

…… POWER

(6U)

WIRE(2U)

SPARE

BATTERY

BBU(2U)

BBU(2U)

TMC

RFC

POWER (6U)

WIRE(2U)

SPARE

BATTERY

BBU(2U)

BBU(2U)

TMC

RFC

RRU

RRU

……

Page 10: HUAWEI Telecom Energy Solutions Catalog.pdf

6

Separated power cabinet seriesProduct Type TP48200A-HX09A5 TP48200A-HX09A6 TP48200A-HX09A7

System capacity 200A

Dimension(W×D×H)

650mm×650mm×900mm

Cooling HEX(850W)

Input mode 220V single phase/380V three phase 110V dual-live wire N/A

User space 11U 15U

Separated battery cabinet series

Product Type TBC300A-DCA7 TBC300A-DCA6 TBC300A-TCA3

Dimension(W×D×H)

650mm×650mm×900mm

Cooling DV DV TEC

Battery space 16U(2×190Ah)

Heater With heater (500W) Without heater Heat by TEC

Integrated cabinet steel series(1.5m Height)

Product TypeTP48200A-

HD15A6TP48200A-

HD15A7TP48200A-

HD15A8TP48200A-

HD15A9TP48200A-

HT15A5TP48200A-

HT15A6TP48200A-

HX15A1

System capacity 200A

Dimension(W×D×H)

650mm×650mm×1500mm

Cooling HEX(850W)+DV HEX(850W)+TEC HEX(850W)

Input mode 220V/380V 110V 220V/380V 110V 220V/380V 110V 220V/380V

User space 9U 25U

Battery space 16U(2×190Ah) N/A

Heater N/A 500W N/A 500W Heat by TEC N/A

Integrated cabinet steel series(0.9m Height)Product Type TP48120A-HD09A1 TP48120A-HD09A2 TP48120A-HD09A3 TP48120A-HD09A4

System capacity 120A

Dimension(W×D×H)

650mm×650mm×1500mm

Cooling HEX(1500W) +DV HEX(850W) +DV

Input mode 220V/380V 110V 220V/380V 110V

User space 8U

Battery space 8U(1×100Ah)

Heater 500W(Optional)

Specifications

Page 11: HUAWEI Telecom Energy Solutions Catalog.pdf

7

Wall-mounted Power System30A-60A/1.74kW-3.2kW

TP4860C and TP4860H are 2 types of wall-mounted power system,

which can convert from 220VAC single-phase or 110VAC dual-live

wire input to stabilized -48V DC output. Its largest capacity is 60A.

When configured with inverter, it can output -48VDC and 220VAC

simultaneously . It can be built in 20Ah/40Ah VRLA battery. It

provides great performance such as compact design, high efficiency

and flexible power backup.

Introduction

• High rectifier efficiency over 96% helps to save energy, output

without derated below 55ºC

• Support built-in inverter to output AC&DC simultaneously

• Support flexible installation mode, such as wall mounted, pole

mounted and grounding installation

• High protection level of IP55

• Low noise and high environment adaptability

Features

TP4860H

TP4860C

• Wireless coverage sites power supply

• WLAN power supply

Application Scenarios

Remote power supply Small site power supply

Page 12: HUAWEI Telecom Energy Solutions Catalog.pdf

8

Wall-mounted power system

Type TP4860H TP4860C

System

Dimension(W×D×H)

450mm×300mm×580mm450mm (excluding 50mm protuberant part on the vent port)×300mm×630mm

Rated capacity DC: 1740W / 2000W / 3200W, AC: 700W (1000VAC)

Cooling mode Natural cooling DV

Installation mode Wall-mounted / floor-mounted Wall-mounted / pole-mounted / floor-mounted

Protection level IP21 IP55

AC Distribution

AC input 220VAC single phase or 110VAC dual-live wire

Inverter output (optional) 3 branches

AC SPD 20kA/40kA, 8/20µs

Signal port SPD 3kA/5kA, 8/20µs

DC Distribution

Maximum output 3200W

Battery branch 1 branch

BLVD 3 branches

DC SPD N/A 10kA / 20kA, 8/20µs

Rectifier Rated power 870W, 1000W or 1600W (optional)

Controller

Sensors interface Battery temperature, door, battery mid-point voltage check

Signal input 7 Digital input

Alarm output 4 Dry contact output

Communication port RS485 / RS232

Inverter (optional)Rated output 1000VA/700W

Working mode Default by DC input priority

Battery (optional)Rated capacity 20Ah/40Ah VRLA battery or 40Ah lithium battery

Normal voltage 12V

Specifications

Page 13: HUAWEI Telecom Energy Solutions Catalog.pdf

9

Embedded Power System30A-400A/1.74kW-24kW

This series of embedded power products includes 5 types of

products: ETP4830, ETP4890, ETP48150, ETP48200 and ETP48400.

They can provide wide range of DC output from 30A to 400A,

and are very broad application in DC power system scenarios. The

functional unit using a standardized installation structure design,

power height ranging from 1U to 11U, compact design, support

19-inch rack or cabinet installation. The system can be adapted

to a wide range of AC input voltage, with intelligent battery

management, remote monitoring, etc.

Introduction

• High rectifier efficiency over 98% helps to save energy, derated

output above 55ºC

• Rectifier with MTBF > 500,000h helps to save OPEX

• E-label function, can achieve assets management of the whole

site, easy for assets management and location of problem quality

• Capacity covers 30A - 400A

• Smooth expansion of capacity from 200A to 400A and ACDB &

DCDB

• Only 5U for 200A system, 12kW/U high power density

• Support 19/21 inch standard rack

• Standard FE, RS485/232 port , supporting 5 AI, 9 DI, 8 DO

• Support MIMO (solar access, 24V output, etc.) evolution

Features

ETP4830

ETP4890

ETP48150

ETP48200

ETP48400

• Access network

• Transmission network

• Wireless base station

• Communication network of enterprise

Application Scenarios

Newly-built site Legacy site modernization

*MIMO: Multiple energy input, multiple mode output

Page 14: HUAWEI Telecom Energy Solutions Catalog.pdf

10

Type ETP4830 ETP4890 ETP48150

System

Dimension(W×D×H)

442mm×255mm×43.6mm (1U)

442mm×255mm×86.1mm (2U)

442mm×255mm×130.5mm (3U)

Installation mode Installed on 19-inch rack or cabinet

Protection level IP20

AC DistributionInput mode

220VAC single phase or 110VAC dual-live wire

220/380VAC 3-phase or 220VAC single phase or 110VAC dual-live wire

SPD 5kA/10kA, 8/20us

DC Distribution

Maximum capacity 2kW 4.8kW 8kW

Battery breakers 1 branch 1 branch 1 branch

Load breakers 2 branches 4 branches 8 branches

Controller

Type SMU01A SMU01B SMU01C

Signal input 7 digital input, 2 analog input 2 digital input

Alarm output 8 dry contact output 4 dry contact output

Communication port RS232/485, FE RS232/485

Type ETP48200 ETP48400

System

Dimension(W×D×H)

482.6mm×330mm×222.5mm(5U) 442mm×330mm×489.5mm(11U)

Installation mode Installed on 19-inch rack or cabinet

Protection level IP20

AC Distribution

Input mode 220/380VAC 3-phase, 220VACsingle phase, or 110VAC dual-live wire

Input breakers 1 branch

Output breakers 1 branch 2 branches

SPD 30kA/60kA, 8/20us 5kA/10kA, 8/20us

DC Distribution

Maximum capacity 12kW 24kW

Battery breakers 2 branches

Load breakers Maximum 10 branches 16 branches

SPD 10kA/20kA, 8/20us

Controller

Signal input6 digital input, 1 door magnetism, 1 water logging, 1 smoke, 2 temperature, 1 battery temperature, 1 environment temperature and humidity

Alarm output 8 dry contact output

Communication port RS232/485, FE

Small and medium capacity embedded power system

Large capacity embedded power system

Specifications

Page 15: HUAWEI Telecom Energy Solutions Catalog.pdf

11

SMU02B is a type of high-end monitoring unit for site and power.

It can monitor and manage telecom power system, and provides

site monitoring function. LCD screen and keyboard are equipped

in the unit to realize man-machine interaction. It has a serial

communication port and an Ethernet port to realize local and

remote monitoring. SMU02B supports the monitoring management

of HUAWEI’s power system series, including embedded power,

indoor power and outdoor power system.

Introduction

• Performs comprehensive power management and intelligent

battery management

• Grid quality detection

• Support time, voltage, capacity disconnecting protection and

LLVD1, LLVD2, BLVD

• Supports north CAN and FE ports accessing and support SNMP

protocol through FE interface

• Support local display and configuration by LCD screen or HTTPS

browsing

• Supports electronic label function

• Support remote management and remote software upgrade from

NetEco

• Supports downloading historical logs and statistics data

• Provides 5 analog inputs(AI), 12 dry contact outputs(DO) and 9

Boolean value inputs(DI)

• Provides multiple ports accessing, such as smoke sensor, door

status sensor, water sensor, battery temperature sensor, ambient

temperature and humidity sensor

• Supports multiple languages, such as English, Chinese, Turkish,

Spanish, Portuguese and German

• Supports hot plug

Features

Full Series of Monitoring Modules SMU02B

SMU02B

Page 16: HUAWEI Telecom Energy Solutions Catalog.pdf

12

ECC500(Energy Control Center) is a central control unit of

PowerCube system, which adopts advanced power conversion

technology and intelligent management to maximize efficiency

of energy utilization. It consists of main control module, basic I/

O module, expansion I/O module, GPRS module(optional), D.G.

control module(optional) and one reserved slot.

Introduction

• Unified controller with comprehensive data acquisition function

• Supports multiple energy input and adopts advanced energy

scheduling strategic to matching different hybrid power

application scenario.

• Supports comprehensive management of power, energy storage

system, environment and intelligent equipments.

• Support remote management and remote software upgrade from

NetEco.

• Support local display and configuration by LCD screen or HTTPS

browsing

• Support time, voltage, capacity disconnecting protection and

LLVD1, LLVD2, BLVD

• Supports electronic label function

• Supports downloading historical logs and statistics data

• Provides multiple ports accessing, such as smoke sensor, door

status sensor, water sensor, battery temperature sensor, ambient

temperature and humidity sensor

• Supports multiple languages, such as English, Chinese, Turkish,

Spanish, Portuguese and German

• Supports hot plug

• Support extended IO port

• Support GPRS communications with NetEco server

Features

Full Series of Monitoring ModulesECC500

ECC500

Page 17: HUAWEI Telecom Energy Solutions Catalog.pdf

13

Specifications

HUAWEI 1U height rectifier module with high efficiency and high

power density can cover the output capacity from 15A to 100A

or from 870W to 6000W. Rectifier efficiency is over 96%, and has

tremendous features such as high reliability, high power density, soft

start, excellent input and output protection, low noise and multi-

module paralle.etc. HUAWEI rectifier modules are widely applied in

HUAWEI -48VDC power system such as embedded power, outdoor

power, indoor power and large power system.

Introduction

• Full series of high efficiency modules, applied in multiple

scenarios

• Efficiency over 96%, energy saving

• 1U height, high power density

• MTBF over 500,000hours, high reliability

• Excellent grid and environment adaptability

Features

Full Series of Rectifier Modules15A-100A/870W-6,000W

Module style Dimensions (H×W×D) Efficiency Input voltage Output power

R4850S 40.8mm×105mm×281mm 98%85-300VAC, 220V single phase or 110V dual live lines

3000W

R4815G140.8mm×95.5mm×208mm

>96%

85-300VAC, 220V single phase or 110V dual live lines

870W

R4830G1 1600W

R4830G240.8mm×105mm×281mm

2000W

R4850G2 3000W

R48100G1 43mm×238mm×378mm 260-530VAC, three phase three line 6000W

R4815G

R4830G1

R4830G2

R4850G

R48100G

R4850S

Page 18: HUAWEI Telecom Energy Solutions Catalog.pdf

14

HUAWEI advanced Energy Storage Modules(ESM) are a type of

lithium iron phosphate battery integrated with management

system. As an important module of PowerCube diesel hybrid

solution and grid hybrid solution, ESM can be used in off grid

and unstable grid areas. With fast charging adaptability and long

lifespan, ESM can sharply reduce the D.G. running time and O&M

cost comparing with traditional solutions.

Introduction

• High charge acceptance to ensure rapid and complete recharge

• Long shelf life up to 2 years at 35ºC due to low self-discharge

• Good performance at high temperature up to 55ºC

• Support parallel use and maximum capacity of 28.8kWh in

parallel

Features

Full Series of Advanced Energy Storage ModulesESM-A2400Wh(D), ESM-A9600Wh(N)

Specifications

ESM-A2400Wh(D) ESM-A9600Wh(N)

Nominal Voltage 48V

Operating Voltage 47V-58V DC

Charging Voltage@ 25ºC 56.4V

Recommended Operating Temperature 25ºC-35ºC

Self Discharge @ 25ºC Less than 5% after 90 days storage

Nominal Capacity 2400Wh@ 5hr, 25ºC 9600Wh @ 5hr, 25ºC

Total Weight Approx. 42.5kg Approx. 125kg

Maximum Charging Current Limited 50 A 100 A

ESM-A Dimension(WxDxH) 435mmx420mmx125 mm 440mmx500mmx500mm

ESMU Dimension(WxDxH) 444mmx310mmx44.5mm

ESM-A2400Wh(D)

ESM-A9600Wh(N)

Page 19: HUAWEI Telecom Energy Solutions Catalog.pdf

15

Huawei new generation telecom power solution (MTS9000A) ensures carriers realize network easy deployment, site level

saving, efficient O&M and smooth evolution for its easy, intelligent and high efficiency performance. Huawei MTS system

highly integrates power system, cooling system, site monitor system and housing system to provide safe and reliable

environment for main equipment.

MTS9000A solution could be widely used in outdoor sites.

• wireless coverage site

• Transmission node site

Introduction

Huawei new generation telecom power solution MTS9000A

provides plentiful intelligent management functions to make

telecom power system easy and high efficiency.

Solution

New Generation Telecom Power SolutionMTS9000A

MTS9000A

SOH SOCSOH management

MTS9000A provides SOH management based on monitoring

battery cell SOH & SOC (Status of health, status of charge) in real

time, to prolong battery serving life and avoid site power failure.

Access control management

MTS9000A Intelligent access control management system makes

the O&M easier and safer. The electrical lock on the cabinet is

designed to be opened by:

• authorized card within valid period

• mobile APP with authorized username and password

• NetEco remotely

Smart capture

To reduce carrier investment loss due to illegal invasion, MTS9000A

provide intelligent photograph capture function against illegal

activities. The camera mounted on the top of inner cabinet will take

a series of pictures automatically while invasion, and the pictures

will be sent to OSS center(NetEco) immediately

Page 20: HUAWEI Telecom Energy Solutions Catalog.pdf

16

Site energy efficiency management

Huawei MTS9000A solution provide energy information collecting

sensors on site to measure energy input and output, the data will

upload to NetEco server for SEE analysis. NetEco could show SEE

status on multiple customized views.

Mobile APP management

Mobile APP management is a new innovative OSS auxiliary function

supported by MTS9000A, customer can not only maintain telecom

site in mobile APP through OSS server, but also log on though WIFI

module integrated in MTS9000A while arrived site. With the help

of mobile APP, customer could realize network management at

anywhere and anytime.

• Easy land acquisition for its compact figure, knockdown type cabinet and Multiple energy input & output

• Intelligent O&M, Overall energy system and environment monitoring and convenient mobile app supported

• Easy Evolution, All modular design, easy expansion and upgrading

• High efficiency, High efficiency rectifier and site & network level efficiency management

Benefits

Page 21: HUAWEI Telecom Energy Solutions Catalog.pdf

17

Accessories

Battery SOC & SOH management

Item iBox

Parameters

Dimension 110mm×142mm×10mm(L×W×H)

Installation Cabinet interior side wall

Working Voltage 12V ± 2V

Working Current Less than 100mA

CommunicationNorthbound interface: ModbusSouthbound interface: Zigbee

Camera

Item Camera

Parameters

Pixels 0.3 Million

Lens 6mm infrared

Output Format JPEG

Night Vision Monochrome image, 6m distance

Communication RS485, Modbus,

Working Voltage DC 9-15V

Working Current Less than 100mA( night vision, less than 300mA)

Working temperature -20˚C to 70˚C

Intelligent Electronic Door Lock

Item eLock

Parameters

Working Voltage 12V ± 20%

Working Current Less than 60mA

Unlock Magnetic card, Live APP, OSS, LUI on site

Record Unlock time and authorization number

IP level Closed status: IP55

AC Meter

Item AC Meter

Parameters

Working Voltage 36 to 72 VDC

Working Current Less than 100mA

Detecting Voltage Range 90 to 300VAC

Detecting Current Range 0 to 75A

AC PUE Measurement Precession

±1%

EFUSE

Item EFUSE

Parameters

Dimension 442mm×42mm×300mm(W×H×D)

Distribution 10 Routes, up to 20A/route (5,10,15,20A configurable)

SPD Differ mode: 10kA, ComVmon mode: 20kA; 8/20µs

Working Voltage 40 to 60VDC

Maximum Current 100A

Page 22: HUAWEI Telecom Energy Solutions Catalog.pdf

18

Product ModelMTS9510A

(Mini-shelter)MTS9512A MTS9513A

Cabinet

Base Dimension (W x D)

815mmx735mm

Height 1.4m, 2.0m, 2.3m 2.0m 2.0m

Application modeEquipment cabinetBattery cabinetIntegrated cabinet

Integrated telecom energy solution

Cooling modeHEX (Only for equipment cabinet and integrated cabinet)DV/TEC (Only for battery cabinet)DC/AC Aircon

Maintenance Front operation & maintenance

Panel material Sandwich panel

Battery shelf 2/3/4 Layers

Protection level IP55 for Aircon and HEX, IP45 for DV

EmbeddedPower

Power Model N/AETP48200-C5B4/C4

ETP48200-C5B5/C3

ETP48200-C5C5 ETP48300-C6A1

Capacity N/A 200A 200A 200A 300A

Input voltage N/A 220/380V 110V dual live 220/380V 220/380V

Input frequency N/A 45Hz to 66Hz

AC input N/A MCB:1×63A/3P MCB:1×100A/2P N/A

AC input SPD N/A 30kA/60kA (8/20µs) N/A

Dimension N/A 5U 6U

Rectifier capacity N/A 3000W

Rectifier efficiency N/A >96%

DC distribution N/A

LLVD: 2×80A/1P, 3×32A/1PBLVD: 1×63A/1P, 3×32A/1P, 1×16A/1P Battery breaker: 2×125A/1P

LLVD: 2×80A/1P, 3×32A/1PBLVD:1×63A/1P, 2×32A/1P, 1×16A/1P Battery breaker:2×125A/1P

LLVD: 2×80A/1P, 9×32A/1PBLVD:1×63A/1P, 3×32A/1P, 4×16A/1P Battery breaker: 2×125A/1P

LLVD: 2×80A/1P, 9×32A/1PBLVD: 1×63A/1P, 3×32A/1P, 1×16A/1P Battery breaker:4×125A/1P

Advanced Features

Optional Features N/A

• Battery SOH management• Access control management• Smart capture• Mobile APP management• Site energy efficiency management (unavailable for ETP48300-C6A1)(Above features are unavailable for ETP48200-C5B4/B5)

Environment

Operation temperature

-40˚C to +50˚C -40˚C to +55˚C -40˚C to +45˚C

Storage & transportation temperature

-40˚C to +70˚C

Humidity 5% to 95%

Battery(optional)

Specification 12V/2V 12V 12V 12V 12V

Capacity Max. 4x190Ah Max. 3x190Ah Max. 2x190Ah Max. 2x190Ah Max. 2x190Ah

Specifications

Page 23: HUAWEI Telecom Energy Solutions Catalog.pdf

19

Hybrid Power-Solar HybridPowerCube S1: Pure Solar Solution

Pure solar hybrid solution is currently the most favored choice for green power solutions in many regions for low and medium

load sites.

Introduction

• ‘Zero’ OPEX, ‘Zero’ CO2 emission

• More PV panels saving with advanced SolarMax MPPT(Maximum Power Point Tracking) tech.

• Multi-anti-theft design to protect assets

Benefits

• Mountainous areas and isolated islands where the topography is complicated and transportation is inconvenient

• Scenic spots which require environment protection.

Scenarios

High Efficiency PV Module: 15%

High-temperature Tolerant Solar Cycle Battery

High Precision MPPT: Upto 99.8%

United Controller with Advanced SolarMax Technology

Page 24: HUAWEI Telecom Energy Solutions Catalog.pdf

20

Configuration

Solution 1 (Outdoor) Solution 2 (Outdoor) Solution 3 (Outdoor) Solution 4 (Indoor)

Typical Power Load <0.8kW < 3kW

ControllerMPPT(Maximum Power Point Tracking) box

ECC500(Energy Control Center) with MPPT(Maximum Power Point Tracking) module

Installation Type Pole-mounted Ground-mounted

Capacity of SSU N/A Max. 8x50A SSU

Capacity of PV Module Max. 3,000Wp Max. 24,000Wp

BLVD 1x32A, 2x10A 2x80A, 2x63A

LLVD N/A 4x32A, 2x16A, 1x10A

Cooling for Equipment Natural cooling HEX

EcoCool / Split DC Aircon

Cooling for Battery Natural cooling Natural cooling

Cabinet ICC100 ICC350 ICC310 ICC200

Remaining Space N/A 7U 26U 31U

Battery Model and Capacity

TCB-A (Temperature Cycle Battery): 300/400/500/650/800Ah (Max. 4 groups)SCB-A (Solar Cycle Battery): 200/300/500/600/800Ah (Max. 4 groups)

Key TechnologySolarMax technology includes features such as high precision MPPT(Maximum Power Point Tracking) of upto 99.8%, high conversion efficiency of 98.50%, high temperature adaptability and high sensation of light.

Page 25: HUAWEI Telecom Energy Solutions Catalog.pdf

21

Hybrid Power-Solar HybridPowerCube S2: Solar & Diesel Solution

Solar & D.G. hybrid solution is applicable for modernization of legacy diesel powered sites with medium and high

load in outlying areas.

Introduction

• High reliability

• Maximum usage of solar energy with leading algorithm design

• Excellent TCO performance with optimized PV & IDG combination

Benefits

• Areas where sunshine duration fluctuates greatly in each month

• Modernization of legacy D.G. powered sites with limited footprint

• Systems requiring high reliability requirements

Scenarios

High Pillar Structure & Anti-theft Bolts

IDG: Integrated Diesel Generator High Efficiency Rectifier: Upto 96%

United Controller with Advanced SolarMax Technology

Page 26: HUAWEI Telecom Energy Solutions Catalog.pdf

22

Configuration

Solution 1 (Outdoor) Solution 2(Indoor)

Typical Power Load <3.5kW

Controller ECC500(Energy Control Center)

Installation Type Ground-mounted

Distribution Capacity Max. 8x50A (SSU+PSU)

Capacity of PV Module Max. 24,000Wp

BLVD 2x80A, 2x63A

LLVD 4x32A, 2x16A, 1x10A

Integrated Diesel Generator Capacity

10/14kW with 3W+N; 11.5/16kW with dual-live wire or reuse

Cooling for Equipment HEX

EcoCool / Split DC aircon

Cooling for Battery Natural cooling

Cabinet ICC350 ICC310 ICC200

Remaining Space 7U 26U 31U

Battery Model and Capacity

TCB-A (Temperature Cycle Battery): 300/400/500/650/800Ah (Max. 4 groups)DCB-A (Deep Cycle Battery): 300/420/490/600/800Ah (Max. 4 groups)DCB-B (Deep Cycle Battery): 200/300/500/650/800Ah (Max. 4 groups)

Key TechnologySolarMax technology includes features such as high precision MPPT(Maximum Power Point Tracking) of upto 99.8%, high conversion efficiency of 98.50%, high temperature adaptability & high sensation of light.

Page 27: HUAWEI Telecom Energy Solutions Catalog.pdf

23

Hybrid Power-Solar HybridPowerCube S3: Solar & Grid (Diesel)

Solar & Grid hybrid solution is applicable for medium and high load sites with grid connection.

Introduction

• High reliability

• Solar energy is priority

• Low TCO, less maintenance costs

Benefits

• Areas having unstable grid, Solar energy acts a complement to the unstable grid

• Scenarios where Mains supply needs to blend with sustainable energy solution to cut down emission

Scenarios

United Controller with Advanced SolarMax Technology

Carrier Class Reliability, Complete SPD Design

Page 28: HUAWEI Telecom Energy Solutions Catalog.pdf

24

Configuration

Solution 1 (Outdoor) Solution 2 (Indoor)

Typical Power Load <3.5kW

Controller ECC500(Energy Control Center)

Distribution Capacity Max. 8x50A (SSU+PSU)

Capacity of PV Module Max. 12,000Wp

BLVD 2x80A, 2x63A

LLVD 4x32A, 2x16A, 1x10A

AC Input 220VAC (85-300VAC) , 50/60Hz (45-66Hz) , 3-phase & 4-wire

Integrated Diesel Generator Capacity

10/14kW with 3W+N; 11.5/16kW with dual-live wire

Cooling for Equipment HEX

EcoCool / Split DC Aircon

Cooling for Battery Natural cooling

Cabinet ICC310 ICC200

Remaining Space 26U 31U

Battery Model and Capacity

TCB-A (Temperature Cycle Battery): 300/400/500/650/800Ah (Max. 4 groups)DCB-A (Deep Cycle Battery): 300/420/490/600/800Ah (Max. 4 groups)DCB-B (Deep Cycle Battery): 200/300/500/650/800Ah (Max. 4 groups)

Key TechnologySolarMax technology includes features such as high precision MPPT(Maximum Power Point Tracking) of upto 99.8%, high conversion efficiency of 98.50%, high temperature adaptability & high sensation of light.

Page 29: HUAWEI Telecom Energy Solutions Catalog.pdf

25

Hybrid Power-Diesel HybridPowerCube D1-Standard & D1-Advanced

Diesel hybrid solution is suitable for medium and high load sites with high reliability requirement.

Introduction

• Up to 75% fuel saving and 90% D.G. running time saving

• Up to 97.5% D.G. maintenance cost saving

• Smooth evolution to Solar Hybrid Solution

Benefits

• Modernization of legacy D.G. powered sites with low load rate

• Areas where Diesel-powered site OPEX is comparatively less than that of the Solar site

• Areas lacking professional D.G. maintenance engineers

Scenarios

United Controller with Advanced DieselMax

Technology

Integrated Diesel Generator

Fuel Level Sensor 5 Levels of Anti-theft Structure Design

Deep Cycle Battery

Page 30: HUAWEI Telecom Energy Solutions Catalog.pdf

26

Configuration

D1-Standard(Outdoor)

D1-Standard(Indoor)

D1-Advanced(Outdoor)

D1-Advanced(Indoor)

Typical Power Load <5kW

Controller ECC500(Energy Control Center)

System Capacity Max. 6x50A PSU(Standard)Max. 8x50A PSU(Co-site)

Max. 8x50A PSU Max. 6x50A PSU Max. 8x50A PSU

Integrated Diesel Generator Capacity

10/14kW with 3W+N; 11.5/16kW with dual-live wire(standard/advanced), 10/14kW with 3W+N;(Co-site)

Integrated Fuel Tank Capacity

800L

BLVD 2x80A, 2x63A(standard/advanced), 1x63A/tenant, total for 4 tenants(Co-site)

LLVD 4x32A, 2x16A, 1x10A(standard/advanced), 1x63A,2x80A/tenant, total for 4 tenants(Co-site)

AC Input 220VAC (85-300VAC), 50/60Hz (45-66Hz), 3-phase & 4-wire

Cooling for Equipment HEX

EcoCool / Split DC Aircon

HEX

EcoCool / Split DC Aircon

Cooling for Battery DC Aircon / Free cooling DC Aircon / Free cooling

Cabinet ICC500 ICC 900 ICC200 ICC500 ICC900 ICC200

Remaining Space 12-14U 19-29U 31U 14U 31U

Battery Model and Capacity

TCB-A (Temperature Cycle Battery): 300/400/500/650/800Ah (Max. 2 groups)DCB-A (Deep Cycle Battery): 300/420/490/600Ah (Max. 2 groups)DCB-B (Deep Cycle Battery): 200/300/500/650Ah (Max. 2 groups)

For ICC500,ESU-A (Advanced Energy Storage Unit),Max. 2x200AhFor ICC900,ESU-A (Advanced Energy Storage Unit),Max. 3x200Ah + 2x150Ah backup batteries(optional)

Key TechnologyDieselMax Technology includes features such as dynamic load algorithm, high AC to DC conversion efficiency of 96% and high charging/discharging efficiency of 96%

Page 31: HUAWEI Telecom Energy Solutions Catalog.pdf

27

Hybrid Power-Grid HybridPowerCube G2: Advanced Fast Charging Solution

Advanced fast charging system is feasible when electricity grid is unreliable and outage time is short but frequent.

Introduction

• Fast charging: Full charging < 2hrs

• Energy storage: 4-5 years lifespan

• ‘Zero’ D.G. running time or removing D.G.

• Smooth evolution to Solar Hybrid Solution

Benefits

• Modernization of Grid plus backup D.G. powered sites

• Areas lacking professional D.G. maintenance engineers

Scenarios

United Controller with Advanced GridMax Technology

Advanced Energy Storage Unit

Page 32: HUAWEI Telecom Energy Solutions Catalog.pdf

28

Configuration

G2 (Outdoor) G2 (Indoor)

Typical Power Load <5kW

Controller ECC500(Energy Control Center)

AC Input 220VAC (85-300VAC) , 50/60Hz (45-66Hz) , 3-phase & 4-wire

System Capacity Max. 6x50A PSU Max. 8x50A PSU

Cooling for Equipment HEX

EcoCool / Split DC Aircon

Cooling for Battery DC Aircon

BLVD 2x80A, 2x63A

LLVD 4x32A, 2x16A, 1x10A

Cabinet ICC500 ICC900 ICC200

Remaining Space 14U 14U 31U

Battery Model and Capacity

ESU-A (Advanced Storage Energy Unit): 200Ah (Max. 2 groups)

ESU-A (Advanced Storage Energy Unit): 200Ah (Max. 3 groups)

ESU-A (Advanced Storage Energy Unit): 200Ah (Max. 4 groups)

Key Technology GridMax Technology includes features such as fast charging, step charging and high adaptability

Page 33: HUAWEI Telecom Energy Solutions Catalog.pdf

29

Hybrid Power-Grid HybridPowerCube G3: Enhanced Fast Charging Solution

Enhanced fast charging system is used for areas where electricity grid not only faces often short outages but also

seldom abnormal long outages.

Introduction

• Fast charging: Full charging < 3hrs

• Energy storage: 4-5 years lifespan

• ‘Zero’ D.G. running time or removing D.G.

• Smooth evolution to Solar Hybrid Solution

Benefits

• Modernization of Grid plus backup D.G. powered sites

• Areas lacking professional D.G. maintenance engineers

Scenarios

United Controller with Advanced GridMax technology, Unique Control Algorithm of Hybrid Energy Storage

Hybrid Energy Storage

Page 34: HUAWEI Telecom Energy Solutions Catalog.pdf

30

Configuration

G3 (Outdoor) G3 (Indoor)

Typical Power Load <5kW

Controller ECC500(Energy Control Center)

System Capacity Max. 6x50A PSU Max. 8x50A PSU

AC Input 220VAC (85-300VAC) , 50/60Hz (45-66Hz) , 3-phase & 4-wire

Cooling for Equipment HEXEcoCool / Split DC Aircon

Cooling for Battery DC Aircon

BLVD 2x80A, 2x63A

LLVD 4x32A, 2x16A, 1x10A

Cabinet ICC500 ICC900 ICC200

Remaining Space 14U 9U 28U

Battery Model and Capacity

ESU-A (Advanced Storage Energy Unit): 50Ah.FCB-A (Fast Charging Battery): 200/300/400/500/650Ah

Max. 2x50Ah ESU-A + 1x400Ah FCB-A

Max. 3x50Ah ESU-A + 1x650Ah FCB-A

Max. 3x50Ah ESU-A + 1x650Ah FCB-A

Key TechnologyGridMax Technology includes features such as fast charging,step charging and high adaptability.

Page 35: HUAWEI Telecom Energy Solutions Catalog.pdf

31

Hybrid Power-Grid HybridPowerCube G4: Standard Fast Charging Solution

Standard fast charging system is suitable for areas where electricity grid has seldom daily outages.

Introduction

• Fast charging: Full charging < 4hrs

• Energy storage: 3-4 years lifespan

• ‘Zero’ D.G. running time or removing D.G.

• Smooth evolution to Solar Hybrid Solution

Benefits

• Modernization of Grid plus backup batteries powered sites

• New-building sites in unstable grid areas

Scenarios

Fast Charging Battery

Split DC Aircon

United Controller with Advanced

GridMax Technology

Page 36: HUAWEI Telecom Energy Solutions Catalog.pdf

32

Configuration

G4 (Outdoor) G4 (Indoor)

Typical Power Load <5kW

Controller ECC500(Energy Control Center)

System Capacity Max. 6x50A PSU Max. 8x50A PSU

AC Input 220VAC (85-300VAC) , 50/60Hz (45-66Hz) , 3-phase & 4-wire

Cooling for Equipment HEX

EcoCool / Split DC Aircon

Cooling for Battery DC Aircon / Free cooling

BLVD 2x80A, 2x63A

LLVD 4x32A, 2x16A, 1x10A

Cabinet ICC500 ICC900 ICC200

Remaining Space 12U 27U 31U

Battery Model and Capacity

FCB-A (Fast Charging Battery): 200/300/400/500/650Ah

Max. 1x650Ah FCB-A Max. 2x650Ah FCB-A Max. 1x650Ah FCB-A

Key Technology GridMax Technology includes features such as fast charging, step charging and high adaptability.

Page 37: HUAWEI Telecom Energy Solutions Catalog.pdf

33

Hybrid Power-Grid HybridPowerCube G4 Mini: Mini Standard Fast Charging Solution

Mini-Standard fast charging system is suitable for areas where the electricity grid suffers from weekly multiple

longtime outages.

Introduction

• Fast charging: Full charging < 4hrs

• Energy storage: 2-3 years lifespan

• ‘Zero’ D.G. running time or removing D.G.

• Smooth evolution to Solar Hybrid Solution

Benefits

• Modernization of Grid plus backup batteries powered sites

• New-building sites in unstable grid areas

Scenarios

United Controller with Advanced GridMax technology

Fast ChargingBattery (12V per cell)

Page 38: HUAWEI Telecom Energy Solutions Catalog.pdf

34

Configuration

G4 Mini (Outdoor) G4 Mini (Indoor)

Typical Power Load <3kW

Controller ECC500(Energy Control Center)

System Capacity Max. 6x50A PSU Max. 8x50A PSU

AC Input 220VAC (85-300VAC), 50/60Hz (45-66Hz), 3-phase & 4-wire

Cooling for Equipment HEX

EcoCool / Split DC Aircon

Cooling for Battery Free Cooling

BLVD 2x80A, 2x63A

LLVD 4x32A, 2x16A, 1x10A

Cabinet ICC330 ICC200

Remaining Space 8U 31U

Battery Model and Capacity

FCB-B (Fast Charging Battery): Max. 2x150Ah FCB-B (Fast Charging Battery): Max. 4x150Ah

Key Technology GridMax Technology includes features such as fast charging, step charging and high adaptability

Page 39: HUAWEI Telecom Energy Solutions Catalog.pdf

35

Intelligent Video Surveillance Power SolutionPowerCube500: IVS Solution

Intelligent video surveillance demands grow rapidly. HUAWEI IVS solution can be applied in various scenarios from good

grid, poor grid to off grid.

• National security infrastructure demands in terms of border monitoring, fortress spot protecting and website facility

management will adopt the IVS system, which sites grid are unavailable.

• As energy saving and environment friendly demands, in densely populated areas will adopt the IVS system, especially

in city, road, square, scenic spot etc.

Introduction

• Higher efficiency, energy saving, green & environment friendly

• Simplified configuration

• Easy deployment and footprint saving, pole-mounted or ground installation supported

• Anti-theft design and assets protected

Benefits

• Modernization of Grid plus backup batteries powered sites

• New-building sites in unstable grid areas

Scenarios

Integrated cabinet,

including battery,

power converter, etc.

Camera

Grid hybrid IVS solution

Integrated cabinet,

including battery,

power converter, etc.

Camera

Solar Panel

Solar hybrid IVS solution

Page 40: HUAWEI Telecom Energy Solutions Catalog.pdf

36

None Backup Time Short Backup Time Long Backup Time Off Grid

Typical Power Load <300 W <150 W <150 W <80 W

Power Supply Source Grid Grid + Battery Grid + Battery Solar + Battery

Autonomy Time 0 Hours 2 Hours 12 Hours 72 Hours

Installation Mode (Cabinet)

Pole Mounted Pole MountedPole Mounted/Ground Installation

Pole Mounted/Ground Installation

Height of Pole Typical 6m

Maximum PV Capacity N/A 800Wp

Input AC Voltage 110/220 V N/A

SPDAC port: 5kA/10kA, FE port: nominal 2kA/6kV

Output VoltageDC12VOptional (DC48V PoE, AC 24V, AC 220V)

Protection Level IP55

Configuration

Solution 1 Solution 2 Solution 3 Solution 4

Page 41: HUAWEI Telecom Energy Solutions Catalog.pdf

37

Site Energy Management SpecialistiManager NetEco (Site)

Network Availability = Communication Availability * Transmission Availability * Energy Availability

Site will be out-of-service during energy interruption. Well managed perfect communication equipment and well

managed perfect transmission equipment together with perfect energy system are not necessarily bring high network

availability and satisfied revenue, unless energy system is simultaneously well managed.

Conventional inefficient manpower-based O&M mode can not meet in depth needs of increasing network scale and

diversified types of energy supply and consumption.

Facing cutthroat competition, we never must be considered as they are now of meticulous management for electricity,

fuel, efficiency and asset, to improve profitability by cutting OPEX.

Introduction

• Better back high efficient O&M, makes O&M visible, controllable and manageable; realize automation and information,

reduce manpower site visit; assists preventative maintenance, provides prediction and expert suggestion.

• Improves power availability, ensures smooth communication, improves QoS and QoE; drives revenue and subscribers

increasing.

• Makes site energy saving manageable, controllable and measureable; supports PUE analysis and optimization.

Benefits

NetEco is innovated to adapt to these strategies, it is a centralized remote OSS solution for site energy equipment. The

following diagram indicates the unique features and customer values of NetEco solution.

Scenarios

Flexible Server Options: NetEco

Hybrid Power Systems Site Power SystemsAdaptable to diversified scenarios

Saving Site data acquisition devices-free

Transmission-SavingIn-band networking solution

Flexible and Stable Out-of-band networking solution

Small-scale (<=1000 Sites)

Medium-scale (<=2000 Sites)

Large-scale(<=5000 Sites)

Northbound

Out-of-bandGPRS/IP/E1

In-bandGreen Channel OR

Networking

Mobile APP

Grid HybridDiesel Hybrid

Indoor Power Outdoor PowerEmbedded

PowerSolar Hybrid

3rd Party System

Page 42: HUAWEI Telecom Energy Solutions Catalog.pdf

38

Items Specifications and/or Features

System Capacity Small scale Medium scale Large scale

1,000 sites per server 2,000 sites per server 5,000 sites per server

Networking modeIn-band transmission Out-of-band transmission

For some Huawei 3900 G/U/L serials macro sites IP, GPRS, E1, etc.

Integration with 3rd party

Alarm SNMP northbound interface: supports SNMP v1, SNMP v2c, and SNMP v3; Performance SNMP northbound interface, based on SNMPv3

Platform function Supports management of multiple time zones, data backup and restore, online help

Real-time monitoring GIS site Map (based on Google Map), real-time monitoring, GUI, power supply logics, customized real-time counter subscription and my workspace

Alarm management Alarm collection and storage, alarm browse, alarm notification, alarm processing, alarm setting, dry contact alarm management, alarm masking and alarm thresholds setting

Configuration Mgmt. Site controller discovery, graphical drag and drop site configuration, batch sites copy and batch parameters modification, site parameter setting by SMS; configuration data export to EXCEL

Performance and Report

Historical data collection, query, statistical analysis, report management; customized report, automatic periodic report

Security management Network security management, role and operation authority management, user and password management, operation authentication, log management, ECC500-based video capture

Asset management Inventory data management, asset anti-theft

Value-added featuresOverall network battery management, overall network diesel generator and fuel management, site DC power sharing, Diesel Max II efficiency optimization

Preventative maintenance

Early-warning: reduces the probability of power failure Maintenance reminder: D.G. refueling, defected battery changing, etc.

Prospective PredictionOperating time prediction: D.G. fuel capacity, battery backup time, etc. Lifespan prediction: Battery remain capacity, discharge times, etc.

Configuration

Remarks: Features are constrained to the configuration of site hardware and controller software, as well as NetEco versions.

Page 43: HUAWEI Telecom Energy Solutions Catalog.pdf

Migrate Towards Simplicity

Page 44: HUAWEI Telecom Energy Solutions Catalog.pdf

Copyright © Huawei Technologies Co., Ltd. 2015. All rights reserved.

No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.

General Disclaimer

The information in this document may contain predictive statements including,

without limitation, statements regarding the future financial and operating results,

future product portfolio, new technology, etc. There are a number of factors

that could cause actual results and developments to differ materially from those

expressed or implied in the predictive statements. Therefore, such information

is provided for reference purpose only and constitutes neither an offer nor an

acceptance. Huawei may change the information at any time without notice.

Trademark Notice

, HUAWEI, and are trademarks or registered trademarks of Huawei Technologies Co., Ltd.

Other trademarks, product, service and company names mentioned are the property of their respective owners.

HUAWEI TECHNOLOGIES CO., LTD.

Huawei Industrial Base

Bantian Longgang

Shenzhen 518129, P.R. China

Tel: +86-755-28780808

Version No.: M3-022333-20141109-C-1.0

www.huawei.com

Global Recognition, Market Share No.124.7% Market Share of Global Telecom Power in 2013, NO.1 in Industry.

1,600,000+ power system, 170+ countries, 310+ operators

130+ service branches, 1,100+ professional partners, 7×24 hours service

Data Resource: Frost & Sullivan

DC Power

Global Product Leadership

Award for DC Power Market

Frost & Sullivan

98% Efficiency Rectifier

Recommended Excellent

Solution Award

CIC