HPAC Combining DOAS & VRF

download HPAC Combining DOAS & VRF

of 12

Transcript of HPAC Combining DOAS & VRF

  • 8/10/2019 HPAC Combining DOAS & VRF

    1/12

  • 8/10/2019 HPAC Combining DOAS & VRF

    2/12

  • 8/10/2019 HPAC Combining DOAS & VRF

    3/12

  • 8/10/2019 HPAC Combining DOAS & VRF

    4/12

  • 8/10/2019 HPAC Combining DOAS & VRF

    5/12

  • 8/10/2019 HPAC Combining DOAS & VRF

    6/12

  • 8/10/2019 HPAC Combining DOAS & VRF

    7/12

  • 8/10/2019 HPAC Combining DOAS & VRF

    8/12

    performed by different parts of the systems, which

    simplifies calculations.

    With DOAS ventilators, heat recovery can be provided

    internally, qualifying for exceptions from requirements

    for outside-air economizers and further simplifying

    units and controls. DOAS heat-recovery damper control

    including bypass and defrost is a well-established routine

    in packaged ventilator controls and much simpler than

    the custom sequences of VAV control.

    Energy recovery can be incorporated at the system

    level with commercially available products, such as a

    heat wheel or stacked-plate heat exchanger. In addition

    to using local packaged controls, these commonly

    incur maintenance costs lower than those of a larger,

    centralized VAV air-handling unit (AHU). Another

    advantage of heat recovery through DOAS is a

    potential reduction in building cooling tonnage. If

    this approach is conceived during design, savingsfrom the smaller chiller or VRF condensing unit can be

    used to offset the cost of the heat-recovery equipment.

    Also, because buildings with energy recovery are slower

    to warm, during a load-shedding event as part of a

    demand-response action, a chiller can remain off for a

    longer period of time.

    As in a VAV system, bypass dampers may be needed

    at energy-recovery heat exchangers, but the dampers

    will be smaller, and their design with regard to pressure

    losses can be more flexible.

    DOAS need fan power only for ventilation air, which

    reduces fan horsepower and helps to meet energy

    codes.System pressure losses (and resultant fan horsepower)

    can be lower than with a VAV system because power is

    not needed to move cooling air through terminal heating

    coils. Also, less pressure generally is needed to operate

    and control terminal units, which reduces parasitic losses

    and helps to meet energy codes.

    18 HPAC ENGINEERING APRIL 2014

    Grant Bowers, PE, LEED AP, is a mechanical engineer with SSOE Group (www.ssoe.com), provider of architecture, engineer-

    ing, construction-management, and specialized services worldwide. Over the last 20-plus years, he has developed expertise in the

    design of mechanical systems and management of mechanical design and construction projects for manufacturing, cleanroom,

    laboratory, office, government, medical, and education facilities. He can be contacted at 503-439-8777 or [email protected] .

    DOAS and VRF,Separating cooling/heating, ventilation airflows simplifies system design, control

    Combining

    PART 2 OF 2

    VBy GRANT BOWERS, PE, LEED AP

    SSOE Group

    Hillsboro, Ore.

    Variable-air-volume (VAV) systems with air terminal

    units have been used extensively in commercial and

    institutional buildings in the United States for decades.

    Unfortunately, optimized design of a VAV system with

    terminal heat is difficult at best because of limitations

    inherent in VAV and complications posed by design

    standards and regulations. One new approach involves

    the pairing of a dedicated outdoor-air system (DOAS)

    with a variable-refrigerant-flow (VRF) system. By

    separating the goal of achieving ventilation rates from

    the goal of maximizing thermal comfort, we can avoid

    situations in which the two goals are in conflict and

    efforts suffer from the resulting compromises. Whats

    more, we can simplify the design process and find systemefficiencies that go far beyond those commonly achieved

    with VAV systems with terminal heating.

    Part 1 of this two-part article (March 2014,http://bit.ly/

    Bowers_0314) discussed the limitations of VAV design and

    VAV systems. Part 2 will discuss the merits and challenges

    of combining DOAS and VRF systems as an alternative to

    VAV systems.

    Advantages of DOAS

    DOAS provide ventilation air directly to occupiable

    spaces, usually separately from heating and cooling

    functions. Thus, the central air-handling fan, ductwork,

    and diffusers of a DOAS are smaller and use lesspower than those of a VAV system that provides

    cooling. At the same time, separation of ventilation from

    heating and cooling functions enables designers to

    separate ventilation reset from heating turndown,

    allowing supply-air-temperature reset, supply-air-

    pressure reset, and dynamic-ventilation reset to be

  • 8/10/2019 HPAC Combining DOAS & VRF

    9/12

  • 8/10/2019 HPAC Combining DOAS & VRF

    10/12

    22 HPAC ENGINEERING APRIL 2014

    COMBINING DOAS AND VRF, PART 2 OF 2

    for which diffusers are selected for

    more of the time. Similarly, VRF sys-

    tems are closer to being constant

    volume, helping to maintain diffuser

    throw, particularly during heating

    operation, increasing ventilation

    effectiveness.

    From an in tegrated-des ign

    perspective, DOAS/VRF can aid

    implementation of advanced air-

    distribution strategies, including

    displacement ventilation and under-

    floor air distribution (UFAD). Dis-

    placement ventilation and UFAD

    require less energy and offer greater

    ventilation effectiveness and highercontaminant-removal rates than

    traditional full-room air mixing.

    Displacement ventilation and UFAD

    improve not only how ventilation

    air gets to an occupied space, but

    how it moves to and through the

    breathing zone. Displacement-

    ventilation and UFAD approaches

    offer options in the areas of natu-

    ral ventilation for entire buildings

    or hybrid ventilation to move more

    air when building delta-T is l ow.

    Displacement-ventilation and UFADstrategies have higher contaminant-

    removal rates, as well as better air-

    distribution effectiveness. Further-

    more, displacement ventilation and

    UFAD increase energy effectiveness

    by reducing fan-power use and

    lowering heat-removal costs by

    reducing the treatment of air above

    the occupied zone of a room.

    The capital cost of a DOAS with

    separate heating/cooling system is

    comparable to that of a VAV system.

    The life-cycle cost of a DOAS with

    separate heating/cooling system,

    however, can be lower because of

    greater system energy effectiveness,

    venti lation effectiveness, reliability,

    and maintainability.

    Advantages of VRF

    VAV systems often use heated

    and chilled water to transfer heat

    to and from air supplied for space

    heating and cooling and ventilation

    pre-treatment. With smaller systems,

    terminal heating/cooling units often

    employ traditional direct-expansion(DX) heat transfer using piped refrig-

    erant. Traditional DX systems have

    one evaporator coil per fan unit piped

    to a single condensing unit located

    outdoors. Sometimes, the DX can

    be reversible, providing heat, rather

    than cooling, to supply air.

    A VRF system, on the other hand,

    can have several evaporator coils

    piped to a condensing unit (Figure

    1), which allows the con-

    densing unit to oper-

    ate only at thecurrent

    net total heating or cooling capac-

    ity (whichever is greater) and en-

    ables heat transfer from zones with

    excess heat to zones with heat de-mand (Figure 2). The larger number

    of evaporator coils leads to greater

    individual space temperature con-

    trol. Each conditioned zone has heat-

    ing- or cooling-capacity modulation

    via a refrigerant valve at the fan coil,

    while the central system typically has

    capacity modulation via a staged or

    variable-speed compressor.

    The heat-recovery function of a

    VRF system can lower energy cost

    directly by transferring excess heat

    from spaces being cooled to spaces

    needing heat. Power input to modern

    VRF systems is considerably lower

    than that to traditional DX systems,

    with coefficients of performance

    (COP) as high as 3.8, compared

    with the COP of less than 3.0 of DX

    systems.

    VRF systems general ly have

    smaller components to maintain and

    better system redundancy. Thus,

    maintenance is less expensive and

    less impactful on building opera-

    tions. VRF fan-coil units often are

    designed to be maintained within anoccupied space, not requiring access

    doors or ceiling-tile removal.

    In VRF systems, piping from

    evaporator coils to condensers

    often is smaller because heat is

    carried in specialized refrigerants,

    instead of heating water or chilled

    water. While VRF piping systems

    may have a greater number of

    individual lines, pairs of smaller

    lines can be run next

    to each other

    Outdoor Unit 1 Outdoor Unit 2

    Defrost

    Liquid pipe

    High/low-pressure gas pipe

    Suction gas pipe

    Branch-selector

    unit

    Heatinglow low

    Heatinglow low

    Heatinglow low

    Heatinglow low

    FIGURE 1. Variable-refrigerant-flow-system architecture.

    FIGURE 2.

    Variable-refrigerant-

    flow simultaneous

    heating and cooling.

  • 8/10/2019 HPAC Combining DOAS & VRF

    11/12

    24 HPAC ENGINEERING APRIL 2014

    COMBINING DOAS AND VRF, PART 2 OF 2

    in piping racks, taking up less vertical

    space than larger-diameter heating-

    water/chilled-water piping.

    VRF systems sometimes sufferfrom the stigma of cold DX cooling

    air (maybe 45F to 50F, as compared

    with 55F VAV air), but spaces can

    be quite comfortable when cool-

    ing air is distributed properly and

    supply-air temperature is reset.

    Additionally, supply air is necessary

    in VRF systems only when a space

    needs heating or cooling. Supply-air-

    temperature reset can be granular to

    the zone, rather than selected based

    on system-level parameters, such as

    outside-air temperature.

    Unlike traditional DX systems,

    VRF systems general ly do not

    require a full periodic reversal for

    defrost of outdoor coils during

    heating season. DX-system defrost

    cycles on traditional heat pumps can

    inject cold air into occupied spaces

    periodically when heat is needed,

    which, of course, can lead to discom-

    fort or added cost for reheat. Where

    there is no ducted outside air (as in

    an overlaid DOAS/VRF system),

    some or all fan coils can be stopped

    during defrost. Alternatively, sup-plemental heat can be provided at

    individual fan coils, as opposed to

    all coils, and some VRF systems use

    split coils to avoid full defrost.1Even

    better, with modular outdoor units,

    a single unit can be taken offline and

    reversed for defrost, while all fan

    coils remain in heating mode (Figure

    3). These VRF techniques for reduc-

    ing (or eliminating) electric heat for

    defrost can have a substantial impact

    on energy-cost reduction and some-

    times even reduce building electrical-service size.

    Building heating/cooling loads

    and fan-power requirements vary

    simultaneously. These independent

    variables contribute to the difficulty

    of estimating real-time total build-

    ing loads. Thus, VAV central equip-

    ment can be oversized considerably,

    resulting in equipment-efficiency

    losses and extra facility costs, such

    as additional support structure.

    Sizing of a VRF system can be based

    on building-envelope block (net)

    loads plus peak internal loads, while

    sizing of a DOAS can be based on

    peak population. These are more

    easily estimable.

    With the combination of a DOAS

    and a VRF system, venti lat ion

    airflow, ventilation pre-cooling, and

    ventilation pre-heating are handled

    by the DOAS, while space heating

    and cooling are handled by the VRF

    system. This simplifies design, as

    simultaneous pressure effects of

    various overlapped control schemes

    are avoided.

    VRF systems are much less prone

    to inefficient modes of operation,

    such as reheat and recooling, than

    are VAV systems. For example, witha VAV system in typical winter or

    shoulder-season operation, air will

    be cooled mechanically at the central

    system, delivered to interior zones

    with heavy lighting and people loads,

    and then reheated by exterior termi-

    nal units for spaces requiring heat.

    With VRF systems, there often

    is little or no ductwork at occupied

    spaces. Larger areas may require

    ductwork for local air distribution

    from fan-coil units, but most spaces

    can be served with ductless fan coils

    mounted either on walls or within

    suspended ceilings. Various types of

    fan-coil units are available (Figure 4).

    VRF heat transfer is accomplished

    with copper tubing, installation of

    which is relatively simple compared

    with custom ductwork. The tubing

    is relatively small, although circuits

    can be numerous.

    VRF systems offer greater flexibil-

    ity for retrofits, including interior-

    space remodels, because refrigerant

    piping often just needs to be changed

    back to a zone-level distribution

    assembly. This can be much lessintrusive than modifying ductwork

    all of the way back to distribution

    mains or back to an AHU. Addition-

    ally, VRF-system redundancy can

    allow individual refrigerant circuits

    to operate while one is undergoing

    maintenance, repair, or replacement.

    Because VRF outdoor units often

    Outdoor unit Outdoor unit Outdoor unit

    Heating

    (not available in heat pump)

    Defrosting Ex1 Defrosting Ex2

    Heat

    Heat

    Ex1 Ex2 Ex1 Ex2 Ex1 Ex2

    FIGURE 3. Variable-refrigerant-flow defrost cycle.

    FIGURE 4. Variable-refrigerant-flow fan-coil types.

  • 8/10/2019 HPAC Combining DOAS & VRF

    12/12

    APRIL 2014 HPAC ENGINEERING 25

    COMBINING DOAS AND VRF, PART 2 OF 2

    are modular, expansion of a system

    to accommodate the expansion of a

    building can be relatively painless.

    Air-cooled condensing units forVRF systems can be located almost

    anywhere outside (e.g., rooftops,

    storage facilities, dedicated exterior

    rooms), as long as refrigerant piping

    is sized and routed as usual for DX

    systems. In high-rise buildings, these

    units can be located on each floor,

    as opposed to a VAV system serving

    the floor with limited load diversity

    or piping and ductwork routed to

    central mechanical rooms, to the

    roof, or to grade.

    Air-cooled condensing units

    with inverter compressors (variable

    speed) also are available for VRF

    systems. These adjust central-equip-

    ment capacity to system need more

    efficiently than increasing/reducing

    fan speed does.

    VRF is mature technology, with

    several major manufacturers world-

    wide. VRF systems are in opera-

    tion throughout Asia and Europe

    and making significant inroads

    into U.S. markets, often in green

    buildings.2VRF controls with new-

    generation user interfaces thatinclude Internet-browser screens

    and even smartphone applications

    to facilitate remote adjustments

    and troubleshooting now are being

    manufactured.

    VRF systems can represent one-

    stop shopping for designers and

    contractors, as compared with built-

    up VAV systems, which typically

    require coordination of equipment

    from several manufacturers.

    Lastly, DOAS/VRF systems pay for

    themselves. Conceptually, approxi-mately 20 percent higher capital cost

    (mechanical only, ignoring structural

    savings) can be expected. But con-

    sidering energy savings of approxi-

    mately 10 percent per year, payback

    periods often are five years or less.

    VRF Drawbacks (Real and

    Perceived)

    Though attractive from many

    perspectives, DOAS/VRF systems

    do have drawbacks. First, with

    increased use of refrigerants, safety

    is a consideration. Calculations are

    required to verify occupants are notexposed to more than the allowable

    concentration of refrigerant (see

    Applying Refrigerant Codes by

    Greg Cunniff, PE, December 2013,

    ht tp ://b it .ly/Cunnif f_1213 ). Safety

    measures, such as refrigerant moni-

    tors, air-transfer ducts, and dampers,

    may be required.

    VRF systems generally are avail-

    able for relatively small zones. For

    relatively large spaces, such as

    cafeterias, gymnasiums, theaters,

    and conference rooms, separate

    HVAC units may be required.

    Copper refrigerant piping can

    be expensive, particularly when

    metals prices jump. However, some

    VRF manufacturers are introducing

    steel tubing, which has been used

    in automotive air-conditioning

    applications for many decades.

    Condensate drains often are

    needed for individual VRF cooling

    coils. However, fan-coil units typi-

    cally are available with low-cost ac-

    cessory pumps. These pumps often

    use flexible tubing for condensatedischarge, rather than expensive

    gravity condensate piping.

    A separate ventilation system

    usually is required with VRF, but for

    smaller commercial and residential

    systems, outside air can be ducted

    directly from the outdoors to fan-coil

    units. Direct-ducted outside air often

    is limited to a relatively low outside-

    air/supply-air fraction, and using

    MERV13 filters per the U.S. Green

    Building Councils LEED (Leadership

    in Energy & Environmental Design)rating system may require careful

    analysis of the pressure capability of

    fan-coil units.

    Some designers have avoided VRF

    systems because certified perfor-

    mance dataoften required by build-

    ing codeswere not available. ANSI/

    AHRI Standard 1230-2010,Perfor-

    mance Rating of Variable Refriger-

    ant Flow (VRF) Multi-Split Air-Condi-

    tioning and Heat Pump Equipment,1

    standardizes energy-efficiency

    ratings of VRF systems. As a result,

    documentation is now available for

    VRF systems. In addition to simpli-fying the permit process, this docu-

    mentation helps to validate that VRF

    systems provide energy-efficiency

    ratios not available with built-up

    VAV systems.

    Summary/Conclusion

    VAV reheat systems once were

    convenient and made good economic

    sense for use with high air-change

    rates. Today, stretching VAV designs

    to address the competing motives of

    good ventilation and energy savings

    can be complex and expensive.

    By combining a DOAS with an

    inherently efficient heating and

    cooling system, such as VRF, a

    system designer can find system

    efficiencies that go far beyond those

    commonly achieved with VAV with

    terminal heat.

    Designers would be well-served to

    break through to the new DOAS par-

    adigm and consider supplementing

    their DOAS with VRF. Such systems

    take advantage of VRFs inherent en-

    ergy recovery, better controllability,ease of design coordination, and re-

    duced space requirements. In addi-

    tion to simplifying system design and

    operation, the use of DOAS/VRF, in

    lieu of old-style VAV reheat, provides

    greener systems by reducing both

    energy use and overall life-cycle cost.

    References

    1) AHRI. (2010). Pe rf or ma nc e

    rating of variable refrigerant flow

    (vrf) multi-split air-conditioning and

    heat pump equipment. ANSI/AHRIStandard 1230-2010. Arlington, VA:

    Air-Conditioning, Heating, and

    Refrigeration Institute.

    2) ASHRAE. (2012). AS HR AE

    handbookHVAC systems and

    equipment. Atlanta: ASHRAE.

    Did you find this art icle useful? Send

    comments and suggestions to Executive

    Editor Scott Arnold at scott.arnold@

    penton.com.