Horizontal Series Fan Coil Technical...
Transcript of Horizontal Series Fan Coil Technical...
Horizontal Series Fan Coils 200-1200 Nominal CFMxpediair (XPA) offers a variety of horizontal models to meet your Fan Coil application needs for installation in motels, condos, hospitals, hotels, offices, and other multi-room buildings. Select from four models for furred-in, recessed or exposed cabinet applications. Coils are available with 1, 2, 3, or 4 row combinations depending on the model and applications. Controls are available for numerous system types: 2-pipe heating and cooling, 2-pipe with auxiliary electric heat, 2-pipe with total electric heat, or 4-pipe heating/cooling application. Basic cabinets are fabricated from heavy gauge, galvanized steel. Exposed cabinet models are painted with a powder coat finish (arctic white).
This catalog provides limited unit selection information. For more detailed selection capability, contact your local XPA distributor.
Horizontal Series Fan Coil Technical Catalog
HCY–Horizontal Hideaway 200 CFM to 1200 CFMThe Horizontal Hideaway (HCY) fan coil unit is designed specifically to meet the many varied requirements for a ceiling hideaway installation. The low-silhouette styling of the HCY makes this unit ideally suited for drop-ceiling and over-closet applications. Standard HCY units are provided with a galvanized finish.
PHB–Horizontal Hideaway with Plenum 200 CFM to 1200 CFMThe Horizontal Hideaway with Plenum (PHB) fan coil unit provides the same basic features of the HCY plus a return air plenum for above-ceiling mounting in closets, hallways or bathroom areas. The PHB design enables the unit to be adapted to installations requiring return air ducts or to be used as a return-air plenum with a unit-mounted filter and filter-rack assembly. PHB units are shipped from the factory ready for installation with the plenum section in place. No field fabrication is required. PHB units are designed with interchangeable panels so that the unit may be modified on site to accommodate a rear or bottom return. Standard PHB units are provided with a galvanized finish.
THB–Horizontal Telescoping Hideaway 200 CFM to 1200 CFMThe Horizontal Telescoping Hideaway (THB) fan coil unit is mounted fully-recessed for ceiling-recessed applications. The THB’s telescoping frame with hinged panel adapts to any ceiling type and ensures exact alignment of the panel with the ceiling. The hinged-bottom panel provides easy access to all internal components. Standard THB units are provided with a galvanized finish on the cabinet and powder-coat paint finish on the bottom-access panel.
XHB–Horizontal Cabinet 200 CFM to 1200 CFMThe Horizontal Cabinet (XHB) fan coil unit is designed specifically for exposed mounting in hotels, motels, hospitals, nursing homes, offices or other commercial establishments. With the XHB, valuable floor space is not required, and its slim, attractively-styled cabinet blends with all types of decor. Since there is no requirement for duct work or structure modifications, the XHB is ideal for retrofit applications. Standard XHB units are provided with a powder-coat paint finish.
2 www.xpediair.com xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB
Cover Basic Unit Descriptions
2 Table of Contents
3 Unit Options and Features
4-5 Ratings and Listings
6 Motor Data
7 Electric Resistance Heating
8-9 Physical Data–Horizontal Hideaway
10-11 Physical Data–Horizontal Hideaway with Plenum
12-15 Physical Data–Horizontal Telescoping Hideaway
16-17 Physical Data–Horizontal Cabinet
18-21 Standard Features and Options
22 Nominal Filter Sizes
23 Piping Packages (Typical)
XPA works continually to improve its products.
As a result, the design and specifications of each
product may be changed without notice and may
not be as described herein. Please contact XPA for
information regarding current design and product
specifications. Statements and other information
contained herein are not express warranties and
do not form the basis of any bargain between
the parties but are merely XPA’s opinion or
commendation of its products. Manufacturer’s
standard limited warranty applies.
3xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB www.xpediair.com
Unit Options and Features
Nominal Sizes
Horizontal Series
02 - 200 CFM 03 - 300 CFM 04 - 400 CFM 06 - 600 CFM 08 - 800 CFM 10 - 1000 CFM 12 - 1200 CFM
Coil Options
Two-pipe Cooling and/or Heating:
• 3-row • 4-row • 2-row
Four-pipe Cooling and Heating:
• 3/1 Row • 3/2 Row • 4/1 Row
Coil Connections:
• Left or Right Hand 1
• Same End • Opposite End (4-pipe)
Motors
Voltage:
• 115-1-60 • 208-1-60 • 230-1-60 • 277-1-60
Type:
• Permanent Split Capacitor (PSC) • ECM: - 3 Sp Pot Adj - Proportional 0-10 V DC - 4 Sp Solid State • 3-Speed w/off
Electric Heat
Voltage:
• 120 V • 208 V • 240 V • 277 V
Sizes (kW):3
• 0.5 • 1.0 • 1.5 • 2.0 • 3.0 • 4.0 • 5.0 • 6.0 • 7.0 • 8.0 • 10.0
Stages:
• Single-Stage Only
Air Flow Arrangement • Bottom or Rear Return - Front
Supply
Controls
Voltage:
• 120 V • 208 V • 230 V • 277 V • 24 V
System/Application:
Manual Fan Operation:
• Standard Wall-Mount (Switch Only)
Controls … Cont’d.
Valve-Cycle Control:
• 2-Pipe Heat Only • 2-Pipe Cool Only • 2-Pipe Heat and Cool, MCO • 2-Pipe Heat and Cool, ACO • 2-Pipe Heat and Cool w/Auxiliary
Electric Heat, MCO • 2-Pipe Heat and Cool w/Auxiliary
Electric Heat, ACO • 2-Pipe Cool w/Total Electric Heat,
MCO • 2-Pipe Cool w/Total Electric Heat,
ACO • 4-Pipe Heat and Cool, MCO • 4-Pipe Heat and Cool, ACO
Thermostat: 4
• Wall-Mounted 155, Vertical • Wall-Mounted 155, Horizontal • Wall-Mounted 24 V
Programmable • Wall-Mounted 24 V
Non-Programmable
Service Switch:
• 115 V, 277 V, 208 V, 230 V Single-Pole.
NOTES: 1. Standing in front of the unit, hand is determined by looking into the air supply and assigning the hand to match the location of the cooling coil connections.
2. Consult factory for 50 Hz applications.
3. KW’s are unit size and voltage dependent.
4. Furnish only.
4 www.xpediair.com xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB
Ratings and Listings
C-ETL-US Listing
XPA’s Horizontal Series units are listed by ETL. The C-ETL-US listing signifies that XPA’s fan coil units have been examined by ETL and are in compliance with both the U.S. and Canadian applicable standards.
Nominal Cooling Capacity
Unit Type Unit Size/Coil NOMINAL CFM
Cooling Capacity Power Input Watts PSCTotal MBH Sensible MBH
HCYPHBXHBTHB
02
3-Row
200 6.0 4.4 87
03 300 9.0 6.3 85
04 400 12.1 8.8 165
06 600 17.3 13.0 225
08 800 22.6 16.2 235
10 1000 27.5 21.0 305
12 1200 32.8 25.0 435
02
4-Row
200 6.9 4.3 87
03 300 9.8 6.5 85
04 400 13.8 9.8 145
06 600 19.6 14.3 220
08 800 25.5 18.8 235
10 1000 31.0 22.0 300
12 1200 37.2 27.7 425
NOTES: 1. Ratings are based on 80°F DB and 67°F WB EAT, 45°F EWT, 10°F water temperature rise, high fan speed, motor voltage 115/1/60, and air flow under dry coil conditions.
2. For all application ratings, contact your local XPA distributor.
3061627HEATING AND COOLING EQUIPMENT
5xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB www.xpediair.com
Ratings and Listings … Cont’d.
Air Delivery (60 Hz)
Model CoilUnit
Size
CFM@ 0.0 ESP - For Fan Speed High Speed CFM @ ESP Indicated
Low Med High 0.05 0.10 0.15 0.20 0.25 0.30 0.35
HCY
3 Row
2 221 271 357 338 318 298 277 256 234 2123 238 291 384 359 333 308 282 258 233 2094 296 410 656 610 565 522 479 438 398 3606 275 402 733 698 663 626 587 547 506 4648 367 700 928 893 856 818 779 738 696 652
10 622 845 1291 1215 1140 1068 997 929 862 79812 726 1300 1560 1478 1394 1305 1213 1117 1017 913
4 Row
2 218 260 327 312 296 279 262 244 224 2053 218 264 337 313 291 271 252 234 219 2044 279 382 567 526 488 452 418 387 358 3316 266 388 683 652 619 585 550 514 476 4378 350 670 902 857 815 775 737 700 666 633
10 612 824 1208 1146 1084 1022 959 897 834 77112 696 1245 1480 1407 1330 1249 1164 1075 982 885
PHB
3 Row
2 198 232 285 270 254 237 221 204 186 1683 221 270 346 325 304 283 260 237 212 1874 265 358 523 491 459 428 397 368 338 3096 267 384 650 619 586 549 509 466 420 3718 356 642 789 752 713 672 630 586 540 492
10 552 738 1063 1008 953 899 846 794 742 69112 668 1122 1307 1241 1173 1103 1031 958 884 807
4 Row
2 194 230 276 261 245 228 211 193 175 1553 213 258 325 305 284 262 239 216 192 1664 259 346 490 462 434 406 377 349 320 2916 275 390 628 597 563 525 483 438 390 3378 349 622 755 726 692 655 612 566 515 459
10 541 723 1023 971 918 865 813 761 709 65712 635 1079 1271 1204 1136 1066 995 922 847 771
THB
3 Row
2 211 259 333 310 287 265 244 224 204 1843 216 270 353 335 317 297 277 256 234 2114 303 398 572 544 515 486 456 427 396 3656 294 422 712 676 637 597 554 509 462 4138 375 678 821 786 748 707 664 617 568 516
10 536 719 1098 1038 978 916 853 790 726 66012 634 1115 1313 1248 1180 1111 1041 969 896 821
4 Row
2 196 240 302 277 253 232 212 194 178 1643 210 262 340 322 303 284 264 243 221 1994 286 375 523 495 466 437 407 377 347 3166 277 400 666 628 588 547 505 461 417 3718 364 652 776 737 696 653 608 560 511 459
10 508 680 1019 964 907 850 791 732 672 61112 598 1032 1188 1131 1072 1012 949 885 818 750
XHB
3 Row
2 203 241 306 290 271 249 225 199 170 1393 220 273 335 325 310 289 263 232 195 1534 279 371 519 493 466 439 410 380 350 3186 308 418 640 602 564 526 487 447 408 3688 314 625 776 746 710 669 622 570 513 450
10 474 648 1027 965 900 833 764 693 620 54412 684 1179 1226 1154 1082 1009 935 861 785 710
4 Row
2 191 233 291 271 250 229 207 184 161 1373 195 256 320 296 272 247 220 192 163 1334 263 348 481 458 434 407 378 347 315 2806 293 402 606 565 525 486 446 408 369 3328 296 595 728 701 665 621 568 507 439 361
10 447 607 981 920 855 786 713 635 553 46612 578 972 1108 1040 971 901 830 759 686 613
NOTES: 1. Tabled values are standard CFM at sea level, 70°F with dry coil. 2. Ratings include factory-installed filter and/or grille, where applicable. 3. Consult factory for 50 Hz applications.
6 www.xpediair.com xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB
Motor Data
Thermal Overload Protection
All permanently lubricated split-capacitor motors furnished by XPA contain internal thermal-overload protection. The overload automatically resets when the temperature returns to a safe limit.
Electronic Testing Laboratories, Inc. approves the motor and thermal overload combination at locked rotor conditions only.
Motor Performance Data - HCY, PHB, XHB, THB
Voltage Fan SpeedUnit Size 02 03 04 06 08 10 12
Nominal HP 1/30 1/30 1/12 1/12 1/6 (2) 1/12 (2) 1/6
115 V
60 Hz
1 Phase
HighAmps 0.53 0.83 1.40 1.40 2.50 2.80 5.00
Watts 87 85 165 165 235 305 435
MediumAmps 0.31 0.50 0.70 0.72 1.50 1.40 2.80
Watts 55 55 80 80 160 150 305
LowAmps 0.27 0.34 0.45 0.45 1.20 0.90 1.20
Watts 35 35 50 50 120 100 130
208 V
60 Hz
1 Phase
HighAmps 0.48 0.48 0.69 0.69 1.30 1.38 2.60
Watts 86 89 115 130 195 260 340
MediumAmps 0.29 0.29 0.43 0.47 0.69 0.94 1.33
Watts 60 60 89 100 135 190 255
LowAmps 0.15 0.15 0.22 0.24 0.47 0.46 0.94
Watts 28 28 45 48 90 90 180
230 V
60 Hz
1 Phase
HighAmps 0.48 0.48 0.69 0.69 1.30 1.38 2.60
Watts 103 106 135 155 210 290 380
MediumAmps 0.31 0.32 0.45 0.52 0.70 1.00 1.34
Watts 70 73 105 115 150 220 285
LowAmps 0.15 0.15 0.24 0.28 0.50 0.50 1.00
Watts 33 33 53 60 105 110 210
277 V
60 Hz
1 Phase
HighAmps 0.35 0.35 0.69 0.69 0.91 1.38 1.82
Watts 80 80 150 155 240 270 440
MediumAmps 0.26 0.26 0.43 0.43 0.62 0.80 1.20
Watts 64 66 110 110 160 200 300
LowAmps 0.16 0.16 0.25 0.35 0.35 0.25 0.66
Watts 40 43 60 90 90 75 175
NOTES: 1. Total unit motor Amps and Watts are shown.
7xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB www.xpediair.com
Electric Resistance Heating
Electric heaters are available on XPA Horizontal Series fan coil units for the following applications.
Total Electric Heat
Total electric heat eliminates the requirement for a boiler. Heating and/or cooling may be available on an individual basis throughout the year. Two-pipe chilled water is used for cooling; and the electric heater is used for heating. Individual room controls can be supplied for either manual or automatic changeover.
Auxiliary Electric Heat
Auxiliary electric heat is ideal for tempering room air between seasons and during the cooling season when chilled water is being circulated. Individual room controls are supplied to provide electric heat only when chilled water is being circulated. During regular heating season, heating is provided by hot water being circulated in the system.
Construction
The heater coils of high-grade resistance wire are supported by ceramic insulators on plated steel brackets. These heat elements are suspended directly in front of the fan outlet between the blower and the coil. High limit thermal cutouts protect the heater in the event of air failure.
Electric Heater Selection
Voltage kWUnit Size
02 03 04 06 08 10 12
120 V
0.5 • • - - - - -
1.0 • • • • • - -
1.5 • • • • • - -
2.0 • • • • • • •3.0 - • • • • • •
208 V
0.5 • • - - - - -
1.0 • • • • • - -
1.5 • • • • • - -
2.0 • • • • • • •3.0 - • • • • • •4.0 - - - • • • •5.0 - - - •
Note 6 • • •6.0 - - - •
Note 6•
Note 6 • •8.0 - - - - - •
Note 6•
Note 6
240 V277 V
0.5 • • - - - - -
1.0 • • • • • - -
1.5 • • • • • - -
2.0 • • • • • • •3.0 - • • • • • •4.0 - - - • • • •5.0 - - - •
Note 6 • • •6.0 - - - •
Note 6•
Note 6 • •8.0 - - - - - •
Note 6•
Note 6
10.0 - - - - - - • Note 6
NOTES: 1. All heaters are single stage and single phase. 2. Heaters over 48 Amps are subdivided and fused. 3. Electric Heating Capacities (BTUH) = Heater kW x 3413. 4. Electric Heater Amperage = (Heater kW x 1000)/Applied
Voltage) 5. Consult factory for 50 Hz applications. 6. High and medium speed only.
8 www.xpediair.com xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB
Physical Data
HCY – Horizontal Hideaway
AIR VENT
1"(25) SUPPLY DUCTCOLLAR
SUPPLYAIR
MTG. HOLES
RESILIENT MOUNTING GROMMET W/ 3/8"(10) DIA. HOLES (TYP. OF 4)
CHILLED/HOT WATERSUPPLY & RETURNCONNECTIONS
A'
OPTIONAL EXTENDEDDRAIN PAN(SEE NOTE 2)
OPTIONAL DRIP LIPSHIPPED LOOSE
OPTIONAL 5/8"(16) O.D. TELL-TALEDRAIN CONNECTION, AVAILABLE ON
STANDARD AND EXTENDED DRAIN PANS
7/8"(22) O.D. CONDENSATE DRAIN
FLEXIBLE METALCONDUIT
RIGHT SIDE VIEWFRONT VIEW
TOP VIEW
6(152)
1-1/2(38)
B
A
3(76)
2-1/4(64)
1-1/8(29)
1(25)
H
E 3/4(19)
3/4(19)
16(406)
G F
17-1/2*(445)
8-3/8*(213)
1(25)
D'
7/8(22)
JUNCTION BOX
(REMOTE MOUNT)
(SEE NOTE 4)
(NOTE 5)
4(102)
4(102)
Unit Model
Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A' B D' E F G H J Blower Motor
HCY02 21-1/4 (540) 31-1/4 (794) 16 (406) 13 (330) 18-1/4 (464) 6-1/4 (159) 8-3/4 (222) 19-3/4 (502) 38 (965) 1 1 36HCY03 25-1/4 (641) 36-1/4 (921) 20 (508) 14 (356) 22-1/4 (565) 6-1/4 (159) 8-3/4 (222) 23-3/4 (603) 38 (965) 1 1 39HCY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 15 (381) 28-1/4 (718) 6-1/4 (159) 8-3/4 (222) 29-3/4 (756) 38 (965) 2 1 49HCY06 36-1/4 (921) 43-1/4 (1099) 31 (787) 10 (254) 33-1/4 (845) 7-1/2 (191) 10 (254) 34-3/4 (883) 38 (965) 2 1 59HCY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 17 (432) 40-1/4 (1022) 7-1/2 (191) 10 (254) 41-3/4 (1060) 38 (965) 2 1 64HCY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 11 (279) 54-1/4 (1378) 7-1/2 (191) 10 (254) 55-3/4 (1416) 60 (1524) 4 2 95HCY12 65-1/4 (1657) 75-1/4 (1911) 60 (1524) 13 (330) 62-1/4 (1581) 7-1/2 (191) 10 (254) 63-3/4 (1619) 65 (1651) 4 2 107
NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4” (6). 4. Drip lip recommended. 5. Product specifications are subject to change without notice. 6. Control box size and position may vary (consult factory). 7. Dimension “G” represents maximum on lowest end of sloped drain pan. 8. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with
options ordered. Consult XPA web site for up to date drawings.
9xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB www.xpediair.com
Physical Data … Cont’d.
HCY - Horizontal Hideaway with Electric Heat
RIGHT SIDE VIEWFRONT VIEW
TOP VIEW
CONTROL BOX
(REMOTE MOUNT)
HEATER ELEMENTELECTRIC STRIPHIGH LIMITSTRIP HEATER
CONDUIT - SEEFLEXIBLE METAL
7/8 (22) O.D. CONDENSATE DRAIN
OPTIONAL 5/8 (16) O.D. TELL-TALE
DRAIN CONNECTION, AVAILABLE ON
STANDARD AND EXTENDED
DRAIN PANS
SHIPPED LOOSEOPTIONAL DRIP LIP
A'
CONNECTIONSSUPPLY & RETURNCHILLED/HOT WATER
MTG. HOLES
AIRSUPPLY
DUCT COLLAR1"(25) SUPPLY
VENTAIR
6(152)
1-1/2(38)
1-1/8(29)
2-1/4(64)
A
B
E
1(25)
D'
21-1/2(546)
12-3/8(314)
G F
7/8(22)
16(406)
H3/4(19)TYP
3(76)
(NOTE 4)
6(152)STD.
5-3/8(137)STD.
DIMENSION "J"
UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 6)
RESILIENT MOUNTING GROMMETW/ 3/8 (10)
DIA. HOLES(TYP. OF 4)
OPTIONAL EXTENDEDDRAIN PAN
7-1/3(187)
2(51)
(SEE SUPPLEMENTALDRAWING FOR COILSTUBOUT LOCATIONS)
Unit Model
Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B D’ E F G H J Blower Motor
HCY02 21-1/4 (540) 31-1/4 (794) 16 (406) 13 (330) 18-1/4 (464) 6-1/4 (159) 8-3/4 (222) 19-3/4 (502) 38 (965) 1 1 38HCY03 25-1/4 (641) 36-1/4 (921) 20 (508) 14 (356) 22-1/4 (565) 6-1/4 (159) 8-3/4 (222) 23-3/4 (603) 38 (965) 1 1 41HCY04 31-1/4 (794) 43-1/4 (1099) 26 (660) 15 (381) 28-1/4 (718) 6-1/4 (159) 8-3/4 (222) 29-3/4 (756) 38 (965) 2 1 51HCY06 36-1/4 (921) 43-1/4 (1099) 31 (787) 10 (254) 33-1/4 (845) 7-1/2 (191) 10 (254) 34-3/4 (883) 38 (965) 2 1 61HCY08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 17 (432) 40-1/4 (1022) 7-1/2 (191) 10 (254) 41-3/4 (1060) 38 (965) 2 1 66HCY10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 11 (279) 54-1/4 (1378) 7-1/2 (191) 10 (254) 55-3/4 (1416) 60 (1524) 4 2 97HCY12 65-1/4 (1657) 75-1/4 (1911) 60 (1524) 13 (330) 62-1/4 (1581) 7-1/2 (191) 10 (254) 63-3/4 (1619) 65 (1651) 4 2 109
NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4” (6). 4. Drip lip recommended. 5. Product specifications are subject to change without notice. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with
options ordered. Consult XPA web site for up to date drawings.
10 www.xpediair.com xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB
Physical Data … Cont’d.
PHB – Horizontal Hideaway with Plenum
15-1/4(387)
11-3/8(289)
FILTER REMOVAL
FILTER REMOVAL
10-1/2(267)
20(508)
19(483)
7/8(22)
FG
1"(25) SUPPLYDUCT COLLAR
SUPPLYAIR
E
A 16(406)
1-1/2(38)
1-1/8(29) C
2-1/4(57) B 3(76)
MTG. HOLES
CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS(SEE SUPPLEMENTALDRAWING FOR COILSTUBOUT LOCATIONS)
D'
A'
OPTIONALEXTENDED DRAIN PAN
OPTIONAL DRIP LIPSHIPPED LOOSE(NOTE 4)
AIR VENT
REAR ACCESSPANEL
1"(25) FILTER
1"(25) RETURNDUCTCOLLAR
1"(25) FILTER
FILTERRETAINER CLIP
BOTTOM ACCESS
PANEL
7/8 (22) O.D.CONDENSATEDRAIN
RETURNAIR
AIRRETURN
RIGHT SIDE VIEWFRONT VIEW
TOP VIEW
OPTIONAL5/8 (16) O.D.
TELL-TALE DRAINCONNECTION,
AVAILABLE ON STANDARD
AND EXTENDED DRAIN PANS3-1/4
(83)
HREAR MTG. HOLES
JUNCTION
INSULATED PLENUM
1-1/2(38)
1(25)
3/4(19)TYP
OPTIONAL REAR RETURN
4(102)
3(76) BOX
UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 6)
RESILIENT MOUNTING GROMMET
W/ 3/8 (10) DIA. HOLES
(TYP. OF 4)
2(51)
7-1/3(187)
Unit Model
Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B C D’ E F G H Blower Motor
PHB02 21-1/4 (540) 31-1/4 (794) 16 (406) 18-1/4 (464) 13 (330) 19-3/4 (502) 6-1/4 (159) 8-3/4 (222) 15-3/8 (391) 1 1 55PHB03 25-1/4 (641) 36-1/4 (921) 20 (508) 22-1/4 (565) 14 (356) 23-3/4 (603) 6-1/4 (159) 8-3/4 (222) 19-3/8 (883) 1 1 60PHB04 31-1/4 (794) 43-1/4 (1099) 26 (660) 28-1/4 (718) 15 (381) 29-3/4 (756) 6-1/4 (159) 8-3/4 (222) 25-3/8 (645) 2 1 70PHB06 36-1/4 (921) 43-1/4 (1099) 31 (787) 33-1/4 (845) 10 (254) 34-3/4 (883) 7-1/2 (190) 10 (254) 30-3/8 (772) 2 1 82PHB08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 40-1/4 (1022) 17 (432) 41-3/4 (1060) 7-1/2 (190) 10 (254) 37-3/8 (949) 2 1 95PHB10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 54-1/4 (1378) 11 (279) 55-3/4 (1416) 7-1/2 (190) 10 (254) 51-3/8 (1305) 4 2 135PHB12 65-1/4 (1657) 75-1/4 (1911) 60 (1524) 62-1/4 (1581) 13 (330) 63-3/4 (1619) 7-1/2 (190) 10 (254) 59-3/8 (1508) 4 2 154
NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4” (6). 4. Drip lip recommended. 5. Product specifications are subject to change without notice. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with
options ordered. Consult XPA web site for up to date drawings.
11xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB www.xpediair.com
Physical Data … Cont’d.
PHB - Horizontal Hideaway with Plenum with Electric Heat
FRONT VIEW RIGHT SIDE VIEWCONTROL BOXIN TOP & BOTTOM OFELECTRICAL KNOCKOUTS
CONTROL BOX
STRIP HEATER HIGH LIMIT
ELECTRIC STRIP HEATER ELEMENT
3-1/4(83)
3/4(19)
AIRRETURN
INSULATED PLENUM
REAR MTG. HOLESH 1-1/2
(38)
7/8 (22) O.D. CONDENSATION DRAIN
1"(25) FILTER
REARACCESSPANEL
VENT
OPTIONAL DRIP LIP SHIPPED LOOSE (NOTE 5)
CHILLED/HOT WATER SUPPLY & RETURN CONNECTIONS (SEE SUPPLEMENTAL DRAWING FOR COIL STUBOUT LOCATIONS)
W/ 3/8 (10) DIA. HOLES (TYP. OF 4)RESILIENT MOUNTING GROMMET
1 (25)
16(406)
3/4(19)TYP
AIRSUPPLY
1"(25)SUPPLY
DUCTCOLLAR
7/8(22)
23(584)
24(610)
10-1/2(267)
FILTERREMOVAL
11-3/8(289)
19-1/4(489)
FILTER REMOVAL
D'
A'
OPTIONAL EXTENDED DRAIN PAN
1"(25) RETURNDUCT COLLAR
1"(25) FILTER
FILTER RETAINER CLIP
BOTTOM ACCESS
PANEL
AIRRETURN
OPTIONAL 5/8 (16) O.D.
TELL-TALE DRAIN CONNECTION,
AVAILABLE ON STANDARD
AND EXTENDED DRAIN PANS
1-1/2(38)
1-1/8(29) C
2-1/4(57) B 3
(76)A
FRONT MTG. HOLES
TOP VIEW OPTIONAL REAR RETURN
FG
6(152)STD.
5-3/8(137)STD.
UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 7)
AIR
7-1/3(187)
2(51)
Unit Model
Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A A’ B C D’ E F G H Blower Motor
PHB02 21-1/4 (540) 31-1/4 (794) 16 (406) 18-1/4 (464) 13 (330) 19-3/4 (502) 6-1/4 (159) 8-3/4 (222) 15-3/8 (391) 1 1 57PHB03 25-1/4 (641) 36-1/4 (921) 20 (508) 22-1/4 (565) 14 (356) 23-3/4 (603) 6-1/4 (159) 8-3/4 (222) 19-3/8 (883) 1 1 62PHB04 31-1/4 (794) 43-1/4 (1099) 26 (660) 28-1/4 (718) 15 (381) 29-3/4 (756) 6-1/4 (159) 8-3/4 (222) 25-3/8 (645) 2 1 72PHB06 36-1/4 (921) 43-1/4 (1099) 31 (787) 33-1/4 (845) 13 (330) 34-3/4 (883) 7-1/2 (190) 10 (254) 30-3/8 (772) 2 1 84PHB08 43-1/4 (1099) 57-1/4 (1454) 38 (965) 40-1/4 (1022) 17 (432) 41-3/4 (1060) 7-1/2 (190) 10 (254) 37-3/8 (949) 2 1 97PHB10 57-1/4 (1454) 65-1/4 (1657) 52 (1321) 54-1/4 (1378) 11 (279) 55-3/4 (1416) 7-1/2 (190) 10 (254) 51-3/8 (1305) 4 2 137PHB12 65-1/4 (1657) 75-1/4 (1911) 60 (1524) 62-1/4 (1581) 13 (330) 63-3/4 (1619) 7-1/2 (190) 10 (254) 59-3/8 (1508) 4 2 156
NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4” (6). 4. Product specifications are subject to change without notice. 5. Drip lip recommended. 6. Threaded fittings must be field tightened and leak tested. 7. Control box size and position may vary (consult factory).
Drawing is not to scale and is provided for reference only. Dimensions may vary with
options ordered. Consult XPA web site for up to date drawings.
12 www.xpediair.com xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB
Physical Data … Cont’d.
THB – Horizontal Telescoping Hideaway
TOP VIEW
FRONT VIEW RIGHT SIDE VIEW
(TYPICAL BOTH SIDES)PARTIAL REAR VIEW
1-1/2 (38) KNOCKOUT (TYPICAL)
7/8 (22) KNOCKOUT
DRAIN CONNECTION7/8 (22) O.D. CONDENSATE
AIRRETURN STAMPED
RETURN AIR GRILLE & 1"(25) FILTER
DUCT COLLAR1"(25) SUPPLY
F
1-1/4(32)
24(610)
1-1/2(38)
20-3/4(527)
1-1/2(38)
D
12 (305) MIN.
14 (356)MAX.
11-1/4(286)
A6-1/8(156) B C
1-1/2(38)TYP
CHILLED/HOT WATER SUPPLY & RETURN CONNECTION (SEE SUPPLEMENTAL DRAWING FOR COIL STUBOUT LOCATIONS)RESILIENT MOUNTING GROMMETS WITH 3/8 (10) DIA. HOLE (TYP. OF 4)
OPTIONAL "L" SHAPED DRIP
JUNCTIONBOX
26(660)
1(25)
1(25)
1-1/2(38)
20-3/4(527)
1-1/2(38) 1
(25)1
(25)
E
6-1/8(156)
AIR
SUPPLY
HINGED BOTTOM RETURN AIR PANEL
OPTIONAL DUCTED REAR RETURN
AIRVENT
UNIT LABEL AND WIRING DIAGRAM (SEE NOTE 6)
1(25)
6(152)
Unit Model
Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A B C D E F Blower Motor
THB02 35 (889) 16 (406) 12-3/4 (324) 37 (940) 32 (813) 6 (152) 1 1 115THB03 35 (889) 20 (508) 8-3/4 (222) 37 (940) 32 (813) 6 (152) 1 1 120THB04 41 (1041) 26 (660) 8-3/4 (222) 43 (1092) 38 (965) 6 (152) 2 1 135THB06 53 (1346) 31 (787) 15-3/4 (400) 55 (1397) 50 (1270) 7 (178) 2 1 150THB08 53 (1346) 38 (965) 8-3/4 (222) 55 (1397) 50 (1270) 7 (178) 2 1 155THB10 75 (1905) 52 (1321) 16-3/4 (425) 77 (1956) 72 (1829) 7 (178) 4 2 227THB12 75 (1905) 60 (1524) 8-3/4 (222) 77 (1956) 72 (1829) 7 (178) 4 2 241
NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4” (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with
options ordered. Consult XPA web site for up to date drawings.
13xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB www.xpediair.com
Physical Data … Cont’d.
THB – Horizontal Telescoping Hideaway with Electric Heat
TOP VIEW
FRONT VIEW
ELECTRIC STRIPHEATER ELEMENT
STRIPA HEATER
HIGH LIMIT
F
D
12(305)MIN.
14(356)MAX.
11-1/4(286)
A6-1/8(156) B C1-1/2
(38)TYP
OPTIONAL "L" SHAPED DRIPLIP, SHIPPED LOOSE (NOTE 5)
CONTROL
26(660)
1(25) 1-1/2
(38)
20-3/4(527)
1-1/2(38)
1(25)
1(25)
E
6-1/8(156)
1(25)
BOX
UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 6)
1(25)
RIGHT SIDE VIEW
(TYPICAL BOTH SIDES)PARTIAL REAR VIEW
1-1/2 (38)KNOCKOUT
(TYPICAL)
7/8 (22) KNOCKOUT
DRAIN CONNECTION7/8 (22) O.D. CONDENSATE
AIRRETURN STAMPED
RETURN AIR GRILLE & 1"(25) FILTER
DUCT COLLAR1"(25) SUPPLY
1-1/4(32)
24(610)
1-1/2(38)
20-3/4(527)
1-1/2(38)
CHILLED/HOT WATER SUPPLY & RETURN CONNECTION (SEE SUPPLEMENTAL DRAWING FOR COIL STUBOUT LOCATIONS)
RESILIENT MOUNTING GROMMETS WITH 3/8 (10) DIA. HOLE (TYP. OF 4)
AIR
SUPPLY
HINGED BOTTOM RETURN AIR PANEL
OPTIONAL DUCTED REAR RETURN
AIRVENT
6(152)
Unit Model
Dimensions - Inches (Millimeters) Quantity/Unit Unit Weight*A B C D E F Blower Motor
THB02 35 (889) 16 (406) 12-3/4 (324) 37 (940) 32 (813) 6 (152) 1 1 117THB03 35 (889) 20 (508) 8-3/4 (222) 37 (940) 32 (813) 6 (152) 1 1 122THB04 41 (1041) 26 (660) 8-3/4 (222) 43 (1092) 38 (965) 6 (152) 2 1 137THB06 53 (1346) 31 (787) 15-3/4 (400) 55 (1397) 50 (1270) 7 (178) 2 1 152THB08 53 (1346) 38 (965) 8-3/4 (222) 55 (1397) 50 (1270) 7 (178) 2 1 157THB10 75 (1905) 52 (1321) 16-3/4 (425) 77 (1956) 72 (1829) 7 (178) 4 2 229THB12 75 (1905) 60 (1524) 8-3/4 (222) 77 (1956) 72 (1829) 7 (178) 4 2 243
NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Optional drip lip not required with optional extended drain pan. 3. All dimensions are +/- 1/4” (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with
options ordered. Consult XPA web site for up to date drawings.
14 www.xpediair.com xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB
Physical Data … Cont’d.
THB – Horizontal Telescoping Hideaway with Bottom Supply
FRONT VIEW
(TYPICAL BOTH SIDES)PARTIAL REAR VIEW
1-1/2 (38) KNOCKOUT
(TYPICAL)
7/8 (22) KNOCKOUT
D
12"(305)MIN.
14"(356)MAX.
11-1/4(286)
A1-1/2(38)
1-1/2(38)
30-3/4(781)
34(864)
RIGHT SIDE VIEW
AIR PANELBOTTOM RETURNHINGED
1-1/2(38)
AIR GRILLE &
AIR
1"(25) FILTER
STAMPED RETURN
7/8 (22) O.D.CONDENSATE
DRAIN CONNECTION
RETURN
1-1/2(38)
SUPPLYAIR
STAMPED SUPPLY
AIR GRILLE
E
36(914) 30-3/4
(781)
1(25)
1-1/2(38)
1(25) TOP VIEW
1(25) 1-1/2
(38)JUNCTION BOX
1(25)
1-1/2 (38)
RESILIENT MOUNTING GROMMETS WITH 3/8 (10) DIA. HOLE (TYP. OF 4)
OPTIONAL "L" SHAPED DRIP LIP, SHIPPED LOOSE (NOTE 5)
CHILLED/HOT WATER SUPPLY & RETURN CONNECTION (SEE SUPPLEMENTAL DRAWING FOR COIL STUBOUT LOCATIONS)
6(152)
OPTIONALDUCTEDREAR RETURN
1(25)
6(152)
AIR VENT
1-1/2 (38)
UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 6)
Unit ModelDimensions - Inches (Millimeters) Quantity/Unit
Unit Weight*A D E F Blower Motor
THB02 35 (889) 37 (940) 32 (813) 6 (152) 1 1 131THB03 35 (889) 37 (940) 32 (813) 6 (152) 1 1 136THB04 41 (1041) 43 (1092) 38 (965) 6 (152) 2 1 153THB06 53 (1346) 55 (1397) 50 (1270) 7 (178) 2 1 172THB08 53 (1346) 55 (1397) 50 (1270) 7 (178) 2 1 177THB10 75 (1905) 77 (1956) 72 (1829) 7 (178) 4 2 256THB12 75 (1905) 77 (1956) 72 (1829) 7 (178) 4 2 270
NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4” (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with
options ordered. Consult XPA web site for up to date drawings.
15xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB www.xpediair.com
Physical Data … Cont’d.
THB – Horizontal Telescoping Hideaway with Bottom Supply with Electric Heat
FRONT VIEW
(TYPICAL BOTH SIDES)PARTIAL REAR VIEW
1-1/2 (38) KNOCKOUT
(TYPICAL)
7/8 (22)KNOCKOUT
D
12"(305)MIN.
14"(356)MAX.
11-1/4(286)
A1-1/2
(38) TYP
30-3/4(781)
34(864)
RIGHT SIDE VIEW
1-1/2(38)
AIRRETURN
1-1/2(38)
SUPPLYAIR
E
36(914)
30-3/4(781)
1(25)
1-1/2(38)
1(25)
1-1/2(38)
TOP VIEW
1(25)
1-1/2(38)
1(25)
1-1/2(38)
RESILIENT MOUNTING GROMMETS WITH 3/8 (10) DIA. HOLE (TYP. OF 4)
OPTIONAL "L" SHAPED DRIP LIP, SHIPPED LOOSE (NOTE 5)
CHILLED/HOT WATER SUPPLY & RETURN CONNECTION (SEE SUPPLEMENTAL DRAWING FOR COIL STUBOUT LOCATIONS)
6(152)
STRIP HEATERHIGH LIMIT
ELECTRIC STRIPHEATER ELEMENT
CONTROLBOX
UNIT LABEL AND WIRING DIAGRAM (SEE NOTE 6)
AIR PANELBOTTOM RETURNHINGED
STAMPED RETURN AIR GRILLE & 1"(25) FILTER
STAMPED SUPPLY
AIR GRILLE
7/8 (22) O.D.CONDENSATE
DRAIN CONNECTION
AIRVENT OPTIONAL
DUCTED REAR RETURN
1(25)
6(152)
Unit ModelDimensions - Inches (Millimeters) Quantity/Unit
Unit Weight*A D E Blower Motor
THB02 35 (889) 37 (940) 32 (813) 1 1 133THB03 35 (889) 37 (940) 32 (813) 1 1 138THB04 41 (1041) 43 (1092) 38 (965) 2 1 155THB06 53 (1346) 55 (1397) 50 (1270) 2 1 174THB08 53 (1346) 55 (1397) 50 (1270) 2 1 179THB10 75 (1905) 77 (1956) 72 (1829) 4 2 258THB12 75 (1905) 77 (1956) 72 (1829) 4 2 272
NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4” (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with
options ordered. Consult XPA web site for up to date drawings.
16 www.xpediair.com xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB
Physical Data … Cont’d.
XHB – Horizontal Telescoping Hideaway
SUPPLYAIR
APPROX.REF.
1-1/2(38)
RETURNAIR
7/8" (22) O.D.
DRAIN CONNECTIONAIR VENT
RESILIENT MOUNTINGGROMMETS WITH 3/8" (10)DIA. HOLE (TYP. OF 4)
2(51)
2(51)
2(51)
SUPPLY AIR GRILLESTANDARD STAMPED
OPTIONAL "L" SHAPEDDRIP LIP, SHIPPEDLOOSE (NOTE 5)
CHILLED/HOT WATERSUPPLY & RETURN
CONNECTIONS
STAMPED RETURNAIR GRILLE &1" (25) FILTER
RIGHT SIDE VIEWFRONT VIEW
TOP VIEW
REMOVABLE HINGEDR.A./ACCESS
PANEL
7/8 (22) KNOCKOUT
(TYP. OF 2)1-1/2 (38) KNOCKOUT(TYP. OF 5)
PARTIAL REAR VIEW(TYPICAL BOTH SIDES)
2(51)
5-3/4(146)AIR
RETURN
1" (25) FILTERAIR GRILLE &STAMPED RETURNOPTIONAL
OPTIONAL
LOCATION
STANDARD
C B C
E
A
FG
3 1/2(89)
23-1/2(597)
CONDENSATE
JUNCTION BOX
18(457)
UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 6)
(SEE SUPPLEMENTALDRAWING FOR COIL
STUBOUT LOCATIONS)
Unit ModelDimensions - Inches (Millimeters) Quantity/Unit Unit
Weight*A B C E F G Blower MotorXHB02 38 (965) 17-1/8 (435) 10-7/16 (265) 34 (864) 5-3/4 (146) 11 (279) 1 1 98XHB03 42 (1067) 21-1/2 (546) 10-1/4 (260) 38 (965) 5-3/4 (146) 11 (279) 1 1 118XHB04 48 (1219) 25-7/8 (657) 11-1/16 (281) 44 (1118) 5-3/4 (146) 11 (279) 2 1 126XHB06 53 (1346) 34-5/8 (879) 9-3/16 (233) 49 (1245) 6-3/4 (171) 12 (305) 2 1 168XHB08 60 (1524) 39 (991) 10-1/2 (267) 56 (1422) 6-3/4 (171) 12 (305) 2 1 176XHB10 74 (1880) 52-1/8 (1324) 10-15/16 (262) 70 (1778) 6-3/4 (171) 12 (305) 4 2 215XHB12 82 (2083) 60-7/8 (1546) 10-9/16 (268) 78 (1981) 6-3/4 (171) 12 (305) 4 2 245
NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4” (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with
options ordered. Consult XPA web site for up to date drawings.
17xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB www.xpediair.com
Physical Data … Cont’d.
XHB – Horizontal Cabinet with optional Electric HeatHi-Static Hideaway
SUPPLYAIR
APPROX.REF.
1-1/2(38)
RETURNAIR
7/8 (22) O.D.
DRAIN CONNECTION
AIR VENT
RESILIENT MOUNTINGGROMMETS WITH 3/8 (10)DIA. HOLE (TYP. OF 4)
2(51)
2(51)
2(51)
SUPPLY AIR GRILLESTANDARD STAMPED
OPTIONAL "L" SHAPEDDRIP LIP, SHIPPEDLOOSE (NOTE 5)
CHILLED/HOT WATERSUPPLY & RETURN
CONNECTIONS
STAMPED RETURNAIR GRILLE &1"(25) FILTER
ELECTRIC STRIPHEATER ELEMENT
RIGHT SIDE VIEWFRONT VIEW
TOP VIEW
REMOVABLE HINGEDR.A./ACCESS
PANEL
7/8 (22)KNOCKOUT(TYP. OF 2)
1-1/2 (38) KNOCKOUT
(TYP. OF 5)
PARTIAL REAR VIEW(TYPICAL BOTH SIDES)
2(51)
CONTROL BOX
5-3/4(146)AIR
RETURN
OPTIONAL
OPTIONAL
LOCATION
STANDARD
C B C
E
A
FG
3-1/2(89)
23-1/2(597)
CONDENSATE
UNIT LABEL ANDWIRING DIAGRAM(SEE NOTE 6)
18(457)
1" (25) FILTERAIR GRILLE &STAMPED RETURNOPTIONAL
(SEE SUPPLEMENTALDRAWING FOR COIL
STUBOUT LOCATIONS)
Unit ModelDimensions - Inches (Millimeters) Quantity/Unit Unit
Weight*A B C E F G Blower MotorXHB02 38 (965) 17-1/8 (435) 10-7/16 (265) 34 (864) 5-3/4 (146) 11 (279) 1 1 100XHB03 42 (1067) 21-1/2 (546) 10-1/4 (260) 38 (965) 5-3/4 (146) 11 (279) 1 1 120XHB04 48 (1219) 25-7/8 (657) 11-1/16 (281) 44 (1118) 5-3/4 (146) 11 (279) 2 1 128XHB06 53 (1346) 34-5/8 (879) 9-3/16 (233) 49 (1245) 6-3/4 (171) 12 (305) 2 1 170XHB08 60 (1524) 39 (991) 10-1/2 (267) 56 (1422) 6-3/4 (171) 12 (305) 2 1 178XHB10 74 (1880) 52-1/8 (1324) 10-15/16 (262) 70 (1778) 6-3/4 (171) 12 (305) 4 2 217XHB12 82 (2083) 60-7/8 (1546) 10-9/16 (268) 78 (1981) 6-3/4 (171) 12 (305) 4 2 247
NOTES: * Unit weights (shown in pounds) are based on dry coils, minimum rows and exclude packaging, valves or other components. 1. RH shown, LH opposite. 2. Internal factory valve packages and drains may not align w/cabinet knockouts. 3. All dimensions are +/- 1/4” (6). 4. Product specifications are subject to change without notice. 5. Drip lip required for units with valves. 6. Control box size and position may vary (consult factory). 7. Threaded fittings must be field tightened and leak tested.
Drawing is not to scale and is provided for reference only. Dimensions may vary with
options ordered. Consult XPA web site for up to date drawings.
18 www.xpediair.com xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB
Standard Features and Options
Features And Options StandardFactory
Installed Option
Field Installed Option
Fac-tory Special
QuoteAir Flow ArrangementFront Supply/Rear Return (HCY) X – – –Front Supply/Rear or Bottom Return (PHB, THB, XHB) X (Bottom) X (Rear) – –Coils2 Rows 2-Pipe (HCY, PHB, THB, XHB) – X – –3 Rows 2-Pipe (HCY, PHB, THB, XHB) X – – –4 Rows 2-Pipe (HCY, PHB, THB, XHB) – X – –3/1, 3/2, 4/1 Rows 4-Pipe (HCY, PHB, THB, XHB) – X – –Manual Air Vent X – – –Automatic Air Vent – X – –DX Coils – X – –Steam Coils – X – XConnectionRight or Left (Same End) X – – –Right or Left (Opposite End) – X – –Drain PanGalvanized Internally Coated with 2-part closed Cell Foam X – – –Stainless Steel Externally Coated – X – –Drip Lip (recommended with motorized valves) – – X –Extended Drain Pans (HCY, PHB) – X – –Secondary Drain Connection – X – vFin MaterialAluminum with Galvanized End Sheets X – – –Copper with Stainless End Sheets and Bottom Coil Baffle – X – XNichrome Wire Strip Electric Heater (Total and Auxiliary) – X – –Filters1" Throwaway non-woven synthetic filter X – – –1" Permanent – X – –1" Pleated MERV 8 – X – –Insulation1/2" Standard Fiberglass X – – –1/2" Premium IAQ Fiberglass – X – X1/2" Foil Face – X – –1/4" Closed Cell – X – –Motor TypePSC Motors with Quick Connect Plug X – – –Motor Voltage120/1/60 3-Speed X – – –208/230/277/1/60 3-Speed (Optional Voltage) – X – –Supply/Return Air GrillesLouvered Stamped Supply Grille (XHB) X – – –
Double Deflection, Aluminum Finish Supply Grille – X (XHB X (HCY, PHB, THB)
X (HCY, PHB, THB)
Double Deflection, Integral Supply Grille - painted – X (XHB) – –Stamped Return Grille (THB, XHB) X – – –
Hinged Bar-Type, Aluminum-finish Return Grille with Throwaway Filter - F.O. – – X (HCY, PHB, THB)
X (HCY, PHB, THB)
ControlsService Switch with Lockout Tabs – X – –Single Point Power Connection – X – –Incoming Power Fusing – X – –24 V Controls – X – –Condensate Overflow Switch – X – –3-Speed Switch X – X –Thermostats – – X –Custom Control (DDC) – X – X
19xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB www.xpediair.com
As detailed in the table on page 20, we offer a control
for most of the customer needs. Additional controls and
devices are available to meet even the most demanding
operating logic.
Three-speed Fan Control
All of our basic control schemes utilize a 2- or 3-speed
switch to modulate the cooling output, to maximize the
percentage of latent heat removal, and to further minimize
the sound level when maximum cooling or heating perfor-
mance is not required.
Low Voltage Control (24 V)
A low voltage control is available with all of our control
schemes.
Condensate High Level Switch
This switch shuts down the unit when the water level in the
drain pan reaches an unsafe level. Building code changes in
much of the country now require this type of device.
Service Switches
We offer concealed service switches for use by maintenance
and service personnel to shut off the power while working
on the unit.
Fusing
We offer incoming power fusing for all units as well as blow-
er motor and control sub-fusing for units that use electric
heat. The blower motor and control sub-fusing (single power
source wiring) is required when single source power with
electric heat is specified.
Control Packages
Vertical Wall Series 155
24 V Programmable and Non-Programmable Digital Series
Standard Features and Options, Cont’d.
20 www.xpediair.com xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB
Control Package Applications
Unit Type Control Option System Type Changeover Type Vertical and Horizontal
Wall Series155
24 V Programmable and Non-Programmable
Digital Series– Manual Fan Manual1 None – –
2-PipeValve Cycle*
Heat Only None
Cool Only None
Heat/CoolManual –
Automatic
Heat/Cool with Auxiliary Electric Heat
Manual –Automatic
Cool with Total Electric Heat
Manual –Automatic
4-Pipe Heat/CoolManual –
Automatic
NOTE: 1. Fan switch only; no thermostat.
Thermostat Features
All listed controls include fan switching.Control Type1
Vertical and Horizontal Wall Series 155 24 V Digital Series
24 V, 115 V, 208 V, 240 V, 277 V 24 V onlyRemote Wall Mounted
Manual Fan Switch Operation
Auto Fan Speed Control N/A
Continuous 3-Speed Fan
Cycling Fan N/A
O.A. Damper Signal
Remote Temperature Sensor Opt OptAdjustable Operating Range Kit
Touch Pad/Digital Display N/A
Local Temperature Set-Back N/A
Water Temperature Purge Cycle N/A
Pipe Sensor N/A
NOTES: 1. Control packages with valve cycle control are continuous fan operation only. 2. All wall-mount control packages are shipped loose for field installation. (Boxes, tile rings, plaster rings, etc. are not provided.) 3. Aquastats are included in control packages, as required.
Control Options
• 24 V control packages• Unit-mounted fan switches (Special Quote)• Single power source wiring (motor/control fusing)• Incoming power fusing• Service switches
• Minimum room temperature thermostats (Special Quote)• Low voltage remote shutdown relays (Special Quote)• Fan and valve cycle applications (Special Quote)• Thermostats available with large letter print for handicap
applications (Special Quote)• DX coil applications
Standard Features and Options, Cont’d.
21xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB www.xpediair.com
Supply Air Grilles
Unit Size Nominal CFMRecommended
Grille Size - Inches (Millimeters)
02 200 16" x 6" (406 x 152)
03 300 20" x 6" (508 x 152)
04 400 26" x 6" (660 x 152)
06 600 30" x 6" (762 x 152)
08 800 38" x 6" (965 x 152)
10 1000 52" x 6" (1320 x 152)
12 1200 60" x 6" (1524 x 152)
NOTES: 1. Refer to Physical Data, pages 8 through 17 for actual unit supply air opening dimensions.
2. Field-furnished duct transitions may be required.
Return Air Filter Grilles
Unit Size Nominal CFMRecommended
Grille Size - Inches (Millimeters)
02 200 24" x 10" (610 x 254)
03 300 28" x 10" (711 x 254)
04 400 32" x 10" (813 x 254)
06 600 42" x 10" (1067 x 254)
08 800 42" x 10" (1067 x 254)
10 1000 54" x 10" (1372 x 254)
12 1200 64" x 10" (1626 x 254)
NOTES: 1. Refer to Physical Data, pages 8 through 17 for actual unit return air opening dimensions.
2. Field-furnished duct transitions may be required.
Optional Double-deflection, Integral Supply Grille Painted to Match Color of Unit
(XHB)
Optional Double Deflection, Aluminum-finish Supply Grille (Optional special ship separate for models HCY, PHB, and THB.
Consult factory for details.)Optional Hinged, Bar-type, Aluminum-finish Return Grille
with Throwaway Filter (Optional special ship separate for models HCY, PHB, and THB.
Consult factory for details.)
Standard Features and Options, Cont’d.
22 www.xpediair.com xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB
Nominal Filter Sizes
All cabinet model units (except HCY) have non-woven synthetic throwaway filters furnished as standard equipment. Clean-
able and pleated filters are optional.
Unit Size
Nominal One-Inch Filter Size - Inches (Millimeters)
HCY (Note 1) PHB
THB Bottom Return
Stamped
THB Rear Return
Stamped
XHB Bottom Return
Stamped
XHB Rear Return
Stamped
XHB Rear Return
Ducted
02 10" x 24"(254 x 610)
10" x 18" (254 x 457)
10" x 28"(254 x 711)
7" x 21"(178 x 533)
10" x 23-1/2"(254 x 597)
8" x 23-1/2"(203 x 597)
8" x 23-1/2"(203 x 597)
03 10" x 28"(254 x 711)
10" x 22" (254 x 559)
10" x 28"(254 x 711)
7" x 21"(178 x 533)
10" x 28"(254 x 711)
8" x 28"(203 x 711)
8" x 28"(203 x 711)
04 10" x 32"(254 x 813)
10" x 28" (254 x 711)
10" x 33"(254 x 838)
7" x 27"(178 x 533)
10" x 32-1/2"(254 x 826)
8" x 32-1/2"(203 x 826)
8" x 32-1/2" (203 x 826)
06 10" x 42"(254 x 1067)
10" x 33" (254 x 838)
10" x 45"(254 x 1143)
7" x 38"(178 x 965)
10" x 37"(254 x 940)
8" x 37"(203 x 940)
8" x 37"(203 x 940)
08 10" x 42"(254 x 1067)
10" x 40" (254 x 1016)
10" x 45"(254 x 1626)
7" x 38"(178 x 965)
10" x 41"(254 x 1041)
8" x 41"(203 x 1041)
8" x 41"(203 x 1041)
10 10" x 54"(254 x 1372)
10" x 54" (254 x 1372)
10" x 62"(254 x 1575)
7" x 52"(178 x 1321)
10" x 54-1/2"(254 x 1384)
8" x 54-1/2"(203 x 1384)
8" x 54-1/2"(203 x 1384)
12 10" x 64" (254 x 1626)
10" x 62" (254 x 1575)
10" x 62"(254 x 1575)
7" x 52"(178 x 1321)
10" x 63"(254 x 1600)
8" x 63" (203 x 1600)
8" x 63"(203 x 1600)
NOTES: 1. Filter sizes for the HCY models are recommended filter sizes only. No filter is factory provided with these models. 2. Sizes shown are nominal ordering sizes.
23xpediair® Horizontal Series Fan Coils - HCY, PHB, XHB, THB www.xpediair.com
Piping Packages (Typical)
Two-way Motorized Control Valve
In a two-way motorized control valve package, the motor
drives the valve open, and a spring returns the valve to a
normally closed position. No water flows with the unit off.
The standard supply connection from the coil will accept
a swaged copper fitting for field brazing. As an option, this
connection may be factory furnished with a union. When a
swage is necessary, it becomes part of the valve package.
The isolation, or ball, valve in the return piping is shipped
loose for field installation.
(Ships Separate)
2-way ValveCoil
Air Vent
SwageS
R
S
R BallValve
BallValve
Two-way Motorized Control Valve with Changeover
In a two-way motorized changeover control valve package,
the motor drives the valve open, and a spring returns the
valve to a normally closed position. No water flows through
the coil with the unit off. The aquastat bypass line allows a
small amount of water to flow from the supply to the return
piping when the control valve is closed. The strap-on aqua-
stat senses whether the flowing water is cold or hot and
switches a contact closed to provide automatic summer/
winter changeover (ACO) for the system.
S
R
S
Swage
2-way ValveAquastat BleedBypass Line
A
Aquastat
R
Coil
Air Vent
Swage
BallValve
BallValve
Three-way Motorized Control Valve
In a three-way motorized control valve package, a divert-
ing valve controls water flow to the coil. When the unit is
off, water bypasses the coil and flows directly to the system
return. A balancing valve may be specified in the bypass line
to permit equal flow balancing.
OptionalBalance Valve
S
Swage
3-way Valve
R
Coil
Air Vent
SwageA
Aquastat
S
R BallValve
BallValve
NOTES: 1. Please note that project specifications for system pressure, pressure drop limitations and flow rate should be checked prior to selecting specific components or the valve pack-age size.
2. The supply and return piping connections of the factory-provided valve package are either swaged for field brazing (standard) or union fitted (optional) for connection to the coil.
3. Consult XPA’s Valve Packages and Piping Components manual or your local representative for detailed piping and valve application information. Factory-provided valve packages are assembled, brazed, wired electrically and dry-fit to the coil connections before shipping. Field braz-ing to the coil completes the installation. Some applica-tions dictate shipping isolation valves loose.