H.J. Heinz Distribution Center - Penn State Engineering · Michael J. Carroll Mechanical OptionH.J....

35
River Avenue Pittsburgh, Pennsylvania Michael J. Carroll Mechanical Option Primary Advisor: Dr. Bahnfleth H.J. Heinz Distribution Center

Transcript of H.J. Heinz Distribution Center - Penn State Engineering · Michael J. Carroll Mechanical OptionH.J....

River Avenue

Pittsburgh, Pennsylvania

Michael J. CarrollMechanical OptionPrimary Advisor: Dr. Bahnfleth

H.J. Heinz Distribution Center

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Presentation OutlineBuilding Synopsis

Client Concerns

Goals of Project

Mechanical Systems

Mechanical System Selection

Daylight Addition

Roof Framing Redesign

Conclusions

Questions

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Building Synopsis

Total 150,000 ft2

140,000 ft2 Warehouse

3 Offices, 2 Break Rooms, 2 Sets of Rest Rooms

Built 8/2000 11/2001

$14 million cost

Addition to Prior Warehouse

Adjacent to Allegheny River

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

H.J. Heinz Distribution Center

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

H.J. Heinz Distribution Center

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

H.J. Heinz Distribution Center

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Client Concerns

Open Floor Space

Storage for Canned Food

Temperate Climate

Freezing of Cans Near Intake Louvers

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Client Concerns

Freezing Cans

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Goals of Project

Provide Economical and Efficient Working Environment

Supply Zonal Air Conditioning

Impart Daylight into Warehouse

Design Roof Framing for Daylighting Clerestories

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Mechanical Systems

Existing Mechanical:

3 Duct Heaters

12 Intake Air Louvers

13 Exhaust Fans

Air-to-Air Packaged Heat Pumps

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Mechanical Systems

Existing Cooling:

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Mechanical Systems

Existing Heating:

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Mechanical Systems

Proposed Mechanical:Geothermal Heat ExchangerGround Water Heat Pump SystemSurface Water Heat Pump SystemZonal Heating and Cooling Control

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

1425 Tons336 TonsWarehouseZone 4

210 Tons20 TonsConveyor HallwayZone 3

12 Tons2 TonsWest Office AreaZone 2

11 Ton1 TonEast Office AreaZone 1

Quantity of UnitsUnit SizeDesign Load RoomsZone

Zonal Heat Pump Sizes and Quantities

Mechanical Systems

Proposed Heat Pump Locations:

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Mechanical Systems

Geothermal Exchanger Heat Pump:

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

$443,775.66

$5,587.50$2.98$1.94$1.041,8751-1/2" Fiberglass with Jacket Insulation (LF)

$12,000.00$6.40$4.03$2.371,8751" Copper H2O Pipe (in Linear Feet)

$103,538.16$2.64$2.03$0.6139,2191-1/4" Polyethylene HX Pipe (in Linear Feet)

$24,000.00$12,000.00$2,800.00$9,200.00210 Ton Heat Pump

$3,275.00$3,275.00$1,350.00$1,925.0012 Ton Heat Pump

$2,425.00$2,425.00$1,100.00$1,325.0011 Ton Heat Pump

$292,950.00$20,925.00$6,425.00$14,500.001425 Ton Heat Pump

TotalUnit TotalInstallationMaterialQuantityUnit

Geothermal Heat Pump Equipment Pricing

Mechanical Systems

Geothermal Exchanger Heat Pump:

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Mechanical Systems

Ground Water Heat Pump

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

$366,816.34

$5,587.50$2.98$1.94$1.041,8751-1/2" Fiberglass with Jacket Insulation (LF)

$12,000.00$6.40$4.03$2.371,8751" Copper H2O Pipe (in Linear Feet)

$5,274.00$14.65$9.60$5.053602-1/2" Sch. 40 Steel Pipe (LF)

$13,354.84$6,677.42$2,336.88$4,340.5423 HP - 150 GPM End-Suction Pump (each)

$7,950.00$7,950.00$590.00$7,360.001110 GPM Plate & Frame Heat Exchanger

$24,000.00$12,000.00$2,800.00$9,200.00210 Ton Heat Pump

$3,275.00$3,275.00$1,350.00$1,925.0012 Ton Heat Pump

$2,425.00$2,425.00$1,100.00$1,325.0011 Ton Heat Pump

$292,950.00$20,925.00$6,425.00$14,500.001425 Ton Heat Pump

TotalUnit TotalInstallationMaterialQuantityUnit

Ground Water Heat Pump Equipment Pricing

Mechanical Systems

Ground Water Heat Pump

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Mechanical Systems

Surface Water Heat Pump

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

$1,043,501.50

$5,587.50$2.98$1.94$1.041,8751-1/2" Fiberglass with Jacket Insulation (LF)

$12,000.00$6.40$4.03$2.371,8751" Copper H2O Pipe (in Linear Feet)

$703,264.00$6.40$4.03$2.37109,8851-1/4" Polyethylene HX Pipe (in Linear Feet)

$24,000.00$12,000.0

0$2,800.00$9,200.00210 Ton Heat Pump

$3,275.00$3,275.00$1,350.00$1,925.0012 Ton Heat Pump

$2,425.00$2,425.00$1,100.00$1,325.0011 Ton Heat Pump

$292,950.00$20,925.00$6,425.00$14,500.001425 Ton Heat Pump

TotalUnit TotalInstallationMaterialQuantityUnit

Surface Water Heat Pump Equipment Pricing

Mechanical Systems

Surface Water Heat Pump:

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Mechanical System Selection

Which is the Best Heat Pump Solution???

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Mechanical System Selection

Ground Water Heat PumpAdvantages:

Less Drilling for Wells than Geothermal Piping

Less Piping required than Surface Water or Geothermal

$76,960 savings over Geothermal

$676,685 savings over Water Source

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Daylighting

Existing Warehouse Lighting:

190 - 400 Watt Metal Halide Fixtures

140 - 180 Watt Fluorescent T8’s

= Total 101,750 Watts Installed Warehouse Daylighting:

3 Sets of 3’ high windows length of Warehouse

Visible Transmittance of 0.50

Window-to-wall Ratio = 0.36

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Daylighting

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Daylighting

Summer / Clear Sky Illuminance

275 Fc on Floor130 Fc on

Can Sides

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Daylighting

Winter / Overcast Sky Illuminance

30 Fc on Floor22 Fc on

Can Sides

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Daylighting

8.6621.5930.22Total Illuminance (fc) =

4.0416.983.321.3025.60Illuminance (fc) =

0.600.600.700.700.60LFF =

0.82LDD =

0.900.900.980.980.90BF =

0.850.850.910.910.85LLD =

0.96RSDD =

0.870.870.800.870.87CU =

36,00036,0009,2005,95036,000Lumens =

301269050190Luminaires

F01(metal halide)

F01(metal halide)

F10(fluorescent)

F02(fluorescent)

F01(metal halide)

Luminaire

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Daylighting

Summer Month Peak Savings:

64 kilowatts$186

Winter Month Peak Savings:

25.6 kilowatts$75

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Structural Redesign

Existing Roof Structure:

Pre-fabricated Wide-Flange Steel Beams

Redesigned Structural Members:

New Joist-Girders 3 sets of 3’ high windows required

(= 2 clerestories)10’ opening for clerestory for length of warehouse (737’)

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Structural Redesign

Joist Girder on West/East Exterior with ClerestoriesModified 60G12N6.7K

Joist Girder on Interior with ClerestoriesModified 60G12N13.4K

Joist Girder on West/East Exterior Walls with No Clerestories60G12N6.7K

Joist Girder on Interior with No Clerestories60G12N13.4K

Roof Framing Supporting Clerestories36LH13

Roof Framing Throughout (excluding Clerestories)32LH06

North and South Exterior Walls24K7

LocationJoist Size

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Structural Redesign

Modified Joist Girders

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Conclusions

Ground Water Heat Pumps are Economical for the Pittsburgh EnvironmentHeating and Cooling provided in all spacesDaylight reduces Power Demand, and Provide Natural SunlightJoist Girders supply needed strength and span Warehouse requires

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

AccoladesThe AE Department

Dr. William BahnflethDr. Jim FreihautMoses LingM. Kevin ParfitJonathan Dougherty

LLI TechnologiesJames White, PEMarjorie ConradChuck Boyle

Mosities ConstructionTom Edwards

Star ElectricBob Kalan

AE Colleagues

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center

Questions

Michael J. Carroll Mechanical OptionH.J. Heinz Distribution Center