High-Performance Online UPS
-
Upload
widepermit -
Category
Documents
-
view
215 -
download
0
Transcript of High-Performance Online UPS
-
8/3/2019 High-Performance Online UPS
1/9
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 52, NO. 3, JUNE 2005 889
High-Performance Online UPS UsingThree-Leg-Type Converter
Jin-Ha Choi, Jung-Min Kwon, Jee-Hoon Jung, and Bong-Hwan Kwon, Member, IEEE
AbstractA high-performance single-phase online uninterrupt-ible power supply (UPS) is proposed. The UPS is composed ofa three-leg-type converter which operates as a battery chargerand an inverter. The first leg is controlled to charge the battery,and the third leg is controlled to make the output voltage. Thecommon leg is controlled in line frequency. The charger andthe inverter are controlled independently. The charger has thecapability of power-factor correction while charging a battery.The inverter regulates output voltage and limits output currentunder an impulsive load. The three-leg-type converter reducesthe number of switching devices. As a result, the system has lesspower loss and a low-cost structure. In the determination of thecharger voltage, the nominal voltage is derived using the feedback
linearization concept and then a perturbed voltage is determinedfor the reactive power control. The disturbance of input voltage isdetected using a fast sensing technique of the input voltage. Ex-perimental results obtained with a 3-VA prototype show a normalefficiency of over 87% and an input power factor of over 99%.
Index TermsBattery charger, power-factor correction (PFC),uninterruptible power supply (UPS).
I. INTRODUCTION
UNINTERRUPTIBLE power supplies (UPSs) are used to
supply clean and uninterrupted power to critical loads,
such as computers, comunication systems, and medical support
systems, etc. As such sensitive equipment is used worldwide,their interruption due to a power failure may lead to critical ac-
cidents. The UPS system is indispensible for this reason.
The recent increase in the use of nonlinear loads caused se-
rious concern for power quality and, consequently, on the dis-
turbances tolerated by sensitive electronic loads. IEEE Standard
4461987 [1] describes the voltage tolerance limits for sensi-
tive loads, such as computer power supplies. In IEEE Standard
4461987, shown in Table I, a voltage drop of more than 15%
cannot be tolerated for more than 30 cycles (or 500 ms). Simi-
larly, a 35% voltage drop can be tolerated for only one cycle (or
16.7 ms). In addition, power factor can be tolerated for over 0.8.
In an effort to meet these requirements, voltage regulation andpower-factor correction (PFC) have become very important.
A typical single-phase converter shown in Fig. 1(a) has four
legs; two of them are used for a rectifier/battery charger, and the
Manuscript receivedJune 11, 2003; revised September 1, 2004. Abstract pub-lished on the Internet March 14, 2005.
J.-H. Choi was with the Department of Electronic and Electrical Engineering,Pohang University of Science and Technology, Pohang 790-784, Korea . Heis now with LG Electronics Company Ltd., Seoul 150-721, Korea (e-mail:[email protected]).
J.-M. Kwon, J.-H. Jung, and B.-H. Kwon are with the Department ofElectronic and Electrical Engineering, Pohang University of Science andTechnology, Pohang 790-784, Korea (e-mail: [email protected]).
Digital Object Identifier 10.1109/TIE.2005.847575
others for an inverter. To improve this, a three-leg-type converter
shown in Fig. 1(b) is proposed. According to the recent literature
[2][9], a three-leg-type converter is developed in many ways.
The most surpassing feature is that power losses can be de-
creased by using a common leg for both the pulsewidth-modula-
tion (PWM) rectifier and PWM inverter. In addition, the system
can have excellent input and output characteristics.
The proposed system has such characteristics as high ef-
ficiency, high power factor, and fast response to input and
output disturbances. The disturbance of the input voltage, such
as overvoltage and undervoltage, can cause a system trip and
hardware equipment failure. To overcome these, fast detec-tion of input voltage disturbances and a fast output voltage
compensation technique are necessary to achieve good output
voltage regulation. Here, we propose a fast output voltage
controller by utilizing a fast input voltage detection method and
a feedforward controller. This paper also proposes a new output
voltage recovery technique under an impulsive load [10]. By
using leakage transformers, universal filtering is implemented
without any additional passive filters [11].
Experimental results of a 3-kVA prototype show the perfor-
mance of the proposed UPS. From the experimental results,
it can be seen that a maximum overall efficiency of 87% and
a power factor of 99% can be obtained. Moreover, the inputand output characteristics have good steady-state and dynamic
performance. The main advantages of the proposed approach
are: 1) the rectifier works as an active filter and thus eliminate
harmonics created by nonlinear loads; 2) the inverter regulates
output voltage under any disturbance; 3) it possesses high ef-
ficiency and high power factor; and 4) there is current-limiting
capability for impulsive loads.
II. SYSTEM DESCRIPTION
Fig. 2(a) shows the configuration of the single-phase UPS
using a three-leg-type converter. The proposed UPS uses
leakage transformers to reduce cost. The leakage inductance ofthe leakage transformer is utilized as an inductor of the LCfilter
without using additional inductors. The leakage inductance of
the leakage transformer should be designed to have reasonable
value; otherwise, an additional inductance must be added in
series with the transformer. The leakage inductance can be
handled by controlling the separation degree of the primary
winding and secondary winding of the transformer. Tight
coupling of the primary winding and the secondary winding
reduces the leakage inductance of the transformer. The input
and output capacitors are simultaneously utilized as a capacitor
of the LCfilters for the charger and inverter. Thus, the UPS has
universal filtering capabilities to act as a line-voltage filter, an
0278-0046/$20.00 2005 IEEE
-
8/3/2019 High-Performance Online UPS
2/9
890 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 52, NO. 3, JUNE 2005
TABLE ITYPICAL RANGE OF INPUT POWER QUALITY AND LOAD PARAMETERS OF MAJOR COMPUTER MANUFACTURERS
Fig. 1. Single-phase converters. (a) Conventional converter with four legs. (b) Three-leg-type converter.
output-voltage stabilizer, a backup voltage filter, and an active
filter compensating for the reactive current.
Fig. 2(b) shows the three-leg-type converter using leakage
transformers. In the three-leg circuit of Fig. 2(b), the rectifier
leg and the common leg operate as a PWM recti fier (boost con-verter) and, at the same time, the common leg and the inverter
leg operate as a PWM inverter (buck converter). By using the
common leg, the system can reduce one switching leg compared
with the conventional four-leg variety. Due to reduced devices
and a simpler structure, it can provide low cost and small size.
The operation of the proposed UPS can be divided into eightmodes. When the input voltage is normal, the operation is di-
-
8/3/2019 High-Performance Online UPS
3/9
CHOI et al.: HIGH-PERFORMANCE ONLINE UPS USING THREE-LEG-TYPE CONVERTER 891
Fig. 2. Configurations of the proposed UPS. (a) Proposed UPS. (b) Three-leg-type converter using leakage transformers.
vided into four modes, as shown in Fig. 3. The others are in-
verter/backup modes. Mode 1 and Mode 2 show the current
flows and switching states during the positive half cycle of the
input voltage, and Mode 3 and Mode 4 vice versa. Since the
common leg is switched by the polarity of the input voltage, the
switch is consistently turned on during the positive cycle,
while the switch is turned on during the negative cycle. In
Mode 1, the lower switches and are turned on. Then, the
inductor current increases in a positive direction and the mag-
netic energy is stored in . Mode 1a and Mode 1b are deter-
mined by the switching state of the unipolar PWM strategy in
the inverterleg. If isturned oninMode 1a, the dc-link voltage
is applied to the load and flows toward the load. Since the
switch is turned on in Mode 1b, a zero voltage is applied to
the load, and the output current is freewheeling through and
. InMode 2, the switch isoff and ison. Next, the energy
stored in is transferred to the dc-link stage. Since the posi-
tive voltage is applied to the load in Mode 2a, the dc link is
discharged by the amount of the output current . Therefore, it
can be seen that the current charges the dc link during the
Mode 2a. In Mode 2b, zero voltage is applied to the load and the
output current is freewheeling, as in Mode 1b. Similarly, Mode
3 andMode 4 show the operation modes during the negative half
cycle of the input voltage. Obviously, Fig. 2 shows that only theamount of current flows through the common legin
each mode, where is battery charging current. The on-loss
of the common leg switches is further reduced. The other modes
are inverter modes. If the input voltage is lost, only the inverter
is operating without charging the battery. The modes also use a
unipolar PWM strategy. The operation is straightforward.
III. SYSTEM ANALYSIS
A. Active Power Filter Mode of the Charger
The charger in Fig. 2(b) acts to compensate for the reac-
tive current required by the load connected on the output side,
thereby reflecting a linear load to the input, while charging thebattery. The common leg is switched at low switching frequency
depending on the sign of the input voltage. It is assumed that the
inductor current is continuous. In the case of positive half cycle
of the input voltage, if the switches and are turned on
(Mode 1), the inductor current increases and magnetic energy
is stored in the inductor. Similarly, in the negative cycle, the
switches and are turned on (Mode 2) to increase the in-
ductor current in opposite direction. Thus, the following voltage
equation is satisfied:
(1)
where and are the source voltage and current, respectively,and is the inductance of the leakage transformer.
-
8/3/2019 High-Performance Online UPS
4/9
892 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 52, NO. 3, JUNE 2005
Fig. 3. Operation modes of the proposed UPS.
In the positive cycle, if the switches and are turned on
(Mode 3), the energy stored in the inductor is transferred to the
dc link. In the same manner, in the negative cycle, the switches
and are turned on (Mode 4) to release the energy to the
dc-link capacitor. Then,
(2)
where is the dc-link voltage, is the turns ratio
of the transformer , and denotes the sign of . It isnoted that under unity-power-factor control.
Depending on the duty ratio of the switch and of
the switch , the average inductor voltage over one switching
period gives the following source current variation :
(3)
(4)
The duty ratios and can be considered to be in each
half cycle. Let the duty ratio be represented by(5)
-
8/3/2019 High-Performance Online UPS
5/9
CHOI et al.: HIGH-PERFORMANCE ONLINE UPS USING THREE-LEG-TYPE CONVERTER 893
Fig. 4. Proposed power-factor controller of the active power filter mode.
which is composed of a nominal duty ratio and a perturbed
duty ratio . Then, the nominal duty ratio and the per-
turbed duty ratio can be represented as
(6)
(7)
where and are the peak source voltage and angular
frequency, respectively. The nominal duty ratio generates
voltage for a feedback linearization of the original nonlinear
system. By contrast, the perturbed duty ratio is used to
control the current required by the inverter. To force the current
of the charger to track its current command , the current
controller is utilized as follows:
(8)
where is the current control gain.
Let be the average charging current over the line period
. Then, total real power of the system is composed of the power
for charging the battery and the output average power
given by
(9)
Therefore, the average input current becomes
where is the peak value of the input voltage. Then
the reference current for the input current of the charger in
Fig. 2(a) is computed as
(10)
The current component is required for charging the
battery and the component for compensating reactive current
is . Fig. 4 shows the proposed control algorithms
of the active power filter mode. The output of the current
controller only generates the inductor voltage drop required to
maintain the sinusoidal source current. With the addition of the
nominal duty to the rectifier which is originally a nonlinear
dynamic system, the relation between the input and output
of the rectifier becomes a first-order linear dynamic system
(7) with easy controllability. Thus, the addition of the nominal
duty relaxes the burden of the current controller and im-proves the input current waveform.
Fig. 5. Peak voltage detectors. (a) Conventionalpeak voltage detector. (b) Fastpeak voltage detector.
With loss of the input power, the static bypass switch is
opened and the charger is disabled. The inverter operates in
backup mode (or inverter mode) and supplies power to the load
using the battery. The unipolar PWM switching scheme is used
for the inverter. It results in a better output voltage waveform
and in a better frequency response than the bipolar PWM
switching scheme, since the effective switching frequency
of the output voltage waveform is doubled and the ripple is
reduced. The common leg is switched at the line frequency
synchronized to the input voltage, as previously stated.
B. Fast Detection of the Input Voltage
With loss of input power, the UPS must transfer instantly to
the backup mode to minimize a transient effect on the output
voltage. To accomplish this, a fast detection technique of the
input voltage is required. In general, the conventional peak
voltage detector with diodes, capacitor, and resistor is used as
a voltage sensing circuit, as shown in Fig. 5(a). When the input
signal is decreased, the capacitor is discharged through the
resistor and when increased, the capacitor is charged directly.
Therefore, the charging speed is faster than the discharging
one. Reducing the resistance increases the discharge speed.
However, the ripple current of the detected signal is increased.
A fast detection technique of the input voltage is shown in
Fig. 5(b) which is composed of a phase shifter, two multipliers,and an adder. The detection technique utilizes the simple
trigonometric theorem as follows:
(11)
The phase shifter delays its input waveform by 90 , i.e., the co-
sine waveform of the input voltage is converted to the sine wave-
form, and each waveform is multiplied and added. The sensed
signal voltage of the input voltage then becomes
(12)
where is the detection gain of the input voltage. Thus, the
detector output can represent the magnitude of the inputvoltage.
-
8/3/2019 High-Performance Online UPS
6/9
894 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 52, NO. 3, JUNE 2005
Fig. 6. Control block diagram of the inverter.
Consider a digitized implementation of the detection algo-
rithm of the input voltage. The 90 phase shifter of the input
voltage with the angular frequency has the transfer character-
istic of the first-order all-pass filter as follows:
(13)
Using the following bilinear transformation:
(14)
where is the sample period, the transfer function of the phase
shifter in the discrete domain is given by
(15)
Therefore, the output of the phase shifter in the discrete-
time domain can be obtained as follows:
(16)
where
(17)
Thus, the algorithm (12) for detecting the input-voltage mag-
nitude can be calculated using the input voltage and the
output signal of the 90 phase shifter.
C. Current-Limiting Technique Under the Impulsive Load
Fig. 6 shows the inverter control block diagram. The output
voltage is regulated through the proportionalintegral (PI)-type
voltage controller. The proposed current limiter consists of two
operation modes: a normal mode and an overcurrent mode. The
two modes are decided by the value of the output current. When
the absolutevalueof the output current islowerthan the lim-
ited current value , the inverter operates in normal mode.
In this mode, the duty of the inverter is determined as
(18)
where is the output of the voltage controller and is
obtained from the sine lookup table. Due to the sinusoidal refer-
ence , the inverter generates sinusoidal output voltage in
normal mode. When the impulsive load such as a capacitive rec-tifier load is attached, the inverter supplies excessive current to
Fig. 7. Control algorithm of output current limiter.
charge the load capacitor. This excessive current may damage
the switching devices in the inverter. If a large current is de-
tected, the current limiter reduces the output voltage reference.
A fast p-type controller reduces the reference value and holds
the reference value during a half cycle, then the capacitor ischarged to some degree without increasing the current. As the
-
8/3/2019 High-Performance Online UPS
7/9
CHOI et al.: HIGH-PERFORMANCE ONLINE UPS USING THREE-LEG-TYPE CONVERTER 895
Fig. 8. Overall block diagram of proposed UPS.
capacitor is fully charged in some cycles, no further impulsive
current flows through the inverter. Then, the inverter operates in
normal mode. The output voltage is recovered to its rated value.
The detailed algorithm of the current limiter is shown in Fig. 7.
As the p-type controller is used, various impulsive loads can be
attached to the system. The system will recover its rated output
value immediately thereafter.
IV. EXPERIMENTAL RESULTS
In a microprocessor-based control system, software flexi-
bility facilitates the development and updating of the control
technique and uses control theory to obtain high performance.
Moreover, a single-chip microcontroller can implement the
controller with a lower cost and smaller size than the gen-
eral-purpose microprocessor with accompanying externalcircuits such as an A/D converter, D/A converter, and PWM
generator. The overall control block diagram of the single-phase
online UPS is implemented using a single-chip microcontroller
Intel 80196 MH, as shown in Fig. 8. The switching times of
each device are implemented in software and PWM pulses are
generated through the pulse generator of the microcontroller.
Voltage or current signals are measured by using the 10-bit
analog-to-digital converter in the microcontroller. The imple-
mentation of the voltage or current controllers and PWM pulse
generation is performed every sample period s.
The overall system is divided into two parts: the controller
and power circuit. The controller part includes the micro-
controller running the control algorithms and driver circuits.The power circuit is implemented as in Fig. 8. The rating of
TABLE IISYSTEM PARAMETERS OF THE PROPOSED UPS USED FOR EXPERIMENT
the proposed UPS is designed for up to 3 kVA with 60-Hz
220-V nominal input/output voltages. To handle this power
rating, 50-A/600-V insulated gate bipolar transistors (IGBTs)
are selected as power semiconductor switches. These power
semiconductor switches are operated with a carrier frequencyof 15 kHz and a dead time of 2 s. The system parameters
used for the experiment are given in Table II. The experimental
waveforms of input and output signals of the input voltage
detector for 20% line voltage disturbance are shown in Fig. 9.
This voltage detector gives a fast response to the voltage sag
due to line voltage disturbance.
As the inverter operates independently of the line status, the
UPS transfers seamless power to the load from the battery in line
fault state. Upon the return of the input power, the UPS trans-
fers back to the active filter mode while charging the battery. In
this transition, a fast transfer time is not required. The output
voltage is slowly adjusted to be in phase with the line voltage
using a phase-locked loop. Once synchronism is achieved andthe magnitude of the input voltage is in the working range, the
-
8/3/2019 High-Performance Online UPS
8/9
896 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 52, NO. 3, JUNE 2005
Fig. 9. Input and output signals of the input voltage detector for 20% linevoltage disturbance.
Fig. 10. Input current and voltage waveforms of proposed UPS.
UPS starts to operate in the active filter mode while the mag-
netic contactor (MC) connects the line to the charger. Fig. 10
shows the input voltage and the input current of the UPS under
a linear load. In this case, the input current of the UPS is the
sum of the charging current for the battery and the load current.
The line current is exactly in phase with the input line voltage
and nearly sinusoidal. Thus, the input power factor approaches
unity. The result measured by the power meter shows that thetotal efficiency of the UPS is 87% and the power factor is 99%.
Fig. 11 shows the output voltage and the output current, respec-
tively, when the UPS is impacted by a capacitive rectifier load
( F). From the experimental waveforms, it is ob-
served that if a current-limiting technique is employed, the UPS
fulfills the impulsive loading quickly. In addition, it can be seen
that its rated output voltage is recovered within 2 cycles of the
fundamental line period.
V. CONCLUDING REMARKS
We have proposed an improved single-phase online UPS
which uses a three-leg-type converter. The proposed UPScombines low cost with excellent performance. The inverter
Fig. 11. Compensated output voltage and current under impulsive load.
generates output independently on line voltage from the battery,
and the UPS transfers uninterrupted power to the load. Theexperimental results validate that the proposed current-limiting
algorithm has quick voltage recovery characteristics under an
impulsive load. The fast input voltage detector also improves
the dynamic response of the output voltage. As the detector
gives a fast output response to the voltage sag, it is adequate
for the UPS demanding fast input disturbance detection. The
experimental results also show that the proposed UPS gives
good dynamic and steady-state performance.
REFERENCES
[1] IEEE Recommended Practice for Emergency and Standby Power Sys-
tems for Industrial and Commercial Applications, IEEE Standard 446-1987, 1987.[2] N. Hirao, T. Satonaga, T. Uematsu, T. Kohama, T. Ninomiya, and M.
Shoyama, Analytical considerations on power loss in a three-arm-typeuninterruptible power supply, in Proc. IEEE PESC98, 1998, pp.18861891.
[3] S. J. Chiang, T. S. Lee, and J. M. Chang, Design and implementationof a single phase three-arms rectifier inverter, Proc. IEEElect. Power
Appl., vol. 147, no. 5, pp. 379384, Sep. 2000.[4] T. Uematsu, T. Ikeda, N. Hirao, S. Totsuka, T. Ninomiya, and H.
Kawamoto, A study of the high performance single phase UPS, inProc. IEEE PESC98, 1998, pp. 18721878.
[5] I. Ando, I. Takahashi, Y. Tanaka, and M. Ikchara, Development of ahigh efficiency UPS having active filter ability composed of a three armsbridge, in Proc. IEEE IECON97, 1997, pp. 804809.
[6] I. Youichi, I. Satoru, T. Isao, and H. Hitoshi, New power conver-sion technique to obtain high performance and high efficiency for
single-phase UPS, in Conf. Rec. IEEE-IAS Annu. Meeting, 2001, pp.23832388.
[7] H. Pinheiro, R. Blume, and P. Jain, Space vector modulation for singlephase on-line three-leg UPS, in Proc. IEEE Int. Conf. Industrial Elec-tronics, Control and Instrumentation, 2000, pp. 679689.
[8] B. Francois, P. Delarue, A. Bouscayrol, and J. Niiranen, Five-legac-ac power converter: Structure, modeling, and control, in Conf. Rec.
IEEE-IAS Annu. Meeting, Rome, Italy, 2000.[9] B.-R. Lin and D.-J. Chen, Implementation of a single-phase three-leg
AC/AC converter with neutral-point diode-clamped scheme, Proc.IEEElect. Power Appl., vol. 149, no. 6, pp. 423432, Nov. 2002.
[10] Y. Yang, J. Liu, and D. Zhou, Pulse by pulse current limiting techniquefor SPWM inverters, in Proc. IEEE PEDS99, 1999, pp. 10211026.
[11] F. Kamran and T. G. Habetler, A novel on-line UPS with universalfiltering capabilties, IEEE Trans. Power Electron., vol. 13, no. 3, pp.410418, May 1998.
[12] A. V. Zyl, J. H. R. Enslin, W. H. Steyn, and R. Spee, A new unifiedapproach to power quality management, in Proc. IEEE PESC95, 1995,pp. 183188.
-
8/3/2019 High-Performance Online UPS
9/9
CHOI et al.: HIGH-PERFORMANCE ONLINE UPS USING THREE-LEG-TYPE CONVERTER 897
Jin-Ha Choi was born in Seoul, Korea, in 1972. Hereceived the B.S., M.S., and Ph.D. degrees in elec-tronic and electrical engineering from Pohang Uni-versity of Science and Technology, Pohang, Korea,in 1996, 1998, and 2003, respectively.
Since 2004,he has beenwiththe DALaboratory ofLG Electronics Company Ltd., Seoul, Korea, wherehe is currently a Researcher. His research interests
are UPSs, motor drives, power converter/inverter sys-tems, and microprocessor applications.
Jung-Min Kwon was born in Ulsan, Korea, in 1981.He received the B.S. degree in electrical and elec-tronic engineering from Yonsei University, Seoul,Korea, in 2004. He is currently working toward the
M.S. degree in electronic and electrical engineeringat Pohang University of Science and Technology,
Pohang, Korea.His research interests are photovoltaic systems and
power supplies.
Jee-Hoon Jung was born in Suwon, Korea, in 1977.He received the B.S. and M.S. degrees in 2000 and2002, respectively, from the Department of Elec-tronic and Electrical Engineering, Pohang Universityof Science and Technology, Pohang, Korea, wherehe is currently working toward the Ph.D. degree inelectronic and electrical engineering.
His research interests include motor drives and di-
agnosis, controland signalprocessing with micropro-cessors, and switch-mode power supplies.
Bong-Hwan Kwon (M91) was born in Pohang,Korea, in 1958. He received the B.S. degree fromKyungbuk National University, Taegu, Korea, in1982, and the M.S. and Ph.D. degrees in electricalengineering from Korea Advanced Institute ofScience and Technology, Seoul, Korea, in 1984 and1987, respectively.
Since 1987, he has been with the Department ofElectronic and Electrical Engineering, Pohang Uni-versity of Science and Technology, Pohang, Korea,where he is currently a Professor. His research in-
terests are motor drives, high-frequency converters, and switch-mode power
supplies.