HEATED AIR CURTAIN www.noirot.com.au Installation and Instruction Manual This manual is for Noirot Heated Air Curtains fitted with electronic control boards. For air curtains without electronic control boards please refer to the manual “Noirot Air Curtain Installation - Manual Control.pdf” Model Power (kW) Air Volume (m 3 /hr) Sound dB(A) High Low High Low High Low 3404-2 9.0 4.5 1270 980 57 49 3404-3 9.0 4.5 1600 1100 57 50

Transcript of HEATED AIR CURTAIN - Climate Master Australia Pty · PDF fileHEATED AIR CURTAIN ... Overheat...

HEATED AIR CURTAIN

www.noirot.com.au

Installation and Instruction Manual

This manual is for Noirot Heated Air Curtains fitted with electronic control boards. For air curtains withoutelectronic control boards please refer to the manual “Noirot Air Curtain Installation - Manual Control.pdf”

Model Power (kW) Air Volume (m3/hr) Sound dB(A)

High Low High Low High Low

3404-2 9.0 4.5 1270 980 57 49

3404-3 9.0 4.5 1600 1100 57 50

www.noirot.com.au P a g e | 2

ContentsTechnical features ................................................................................................................................................3

Installation............................................................................................................................................................3

Electric connection ...............................................................................................................................................4

Wiring Connections ..........................................................................................................................................5

Wiring Diagram.................................................................................................................................................6

Operation..............................................................................................................................................................7

Overheat cut-out ..................................................................................................................................................8

Maintenance.........................................................................................................................................................8

Servicing: ..........................................................................................................................................................8

Warranty...............................................................................................................................................................8

www.noirot.com.au P a g e | 3

Technical features

Power Length Height Depth Weight Speed (m3/Hour) Delta T (°C)

(w) (mm) (mm) (mm) (kg) low high lowspeed

highspeed

2250 / 4500 1100 270 205 20 980 1270 7 11

4500 / 9000 1100 " " " " " 13.5 21

4500 / 9000 1550 270 205 30 1100 1600 12 17

Installation

Appliance should be fitted as close as possible tothe entrance and the top of the door.

It is supplied with 2 supports.

Appliance is supplied with a template printed onthe carton box.

Drill the holes taking care to select the

correct length:

- 1035 mm for 1100 mm long model

- 1485 mm for 1550 mm long model

Fix the supports: screws with 6 mmdiameter are recommended

Engage the appliance into the grooveof the support.

Orientate the appliance according tothe needs. Tighten the 2 screws (6 mmdiameter).

Template locatedon the carton box

Bulkhead

Interior

Fixi

ngs

www.noirot.com.au P a g e | 4

screws

screws

Electric connection

Appliance must be connected by a qualified electrician according to the local regulations and standards.

Diameter of the wires and cutting power of the circuit breakers must match the following voltages:

Power Speed Input Current Per Phase Input Current

230 V 400 Vmotor +

contactor

2250W/4500Wlow 9.78 A 3.25 A

less than 1 A

high 19.57 A 6.5 A

4500W/9000Wlow 19.57 A 6.5 A

high 39.13 A 12.99 A

6000W/12000Wlow 26.08 A 8.66 A

high 52.17 A 17.32 A

Remove the front panel (the one with the air inlet grille) by unscrewing the 6 screws

Fitting Cable Clamp:

Appliance is fitted with a cable clamp for an easy and safe connection. Slide thesupport in order to remove it and put is back when cables are correctly tightened.

www.noirot.com.au P a g e | 5

Wiring Connections

This air curtain is supplied setup for 400V 3-phase + neutral and earth

Other possible voltage connections are:

- 230 V single phase- 400 V tri without neutral (a separate 230V power supply is required for the controls)

NB: Motor operates with 230 V single phase

3-Phase with Neutral

Do not alter bridges

Single Phase

Use long bride connector

3-Phase without Neutral

Remove bridge connectors

www.noirot.com.au P a g e | 6

Wiring Diagram

Terminals: Condensateur = capacitor

Rep. A: Motor Moteur = motorRep. B: Control box Carte electronique = printed circuit boardRep. C: Contactors Limiteur thermique = overheat cut-out with manual resetRep. D: Overheat cut-out Sécurité thermique = overheat cut-outRep. E: Electric supply and communication Résistance = heating element

Voyant d’activation = cut-out indicator light

www.noirot.com.au P a g e | 7

Operation

We recommend the use of the optional electronic control box that enables to operate up to 20 air curtains.

Please see the manual of this accessory.

Connection: a 2 wire low voltage (no polarity) cord from the control box to the “master” appliance. Then, asingle wire between the appliances

NB: when not using the electronic control box, appliance operates at full power + full speed.

Connection to a mechanical room thermostat Thermostat can drive up to 20 appliances (1 wire)

Without any control system:

Add a shunt (see yellow arrow) from the AUX terminal of theprinted circuit board to the L (phase) of the electric supplyterminal

www.noirot.com.au

Overheat cut-out

This appliance is fitted with a thermal overheat cut-out with manualreset.

In case of abnormal operation, the appliance stops and the red lightilluminates.

Turn off air curtain and inspect unit

To reset switch:

Check grilles and ensure they are clean. Make surobstructions blocking the air flow.

Wait for 5 minutes then press the red button of thtop of the unit.

Restart the air curtain.

If thermal overheat cut-out is re-activated, call a

Maintenance

This appliance requires no special maintenance.

To remove dust, use a soft cloth. To remove marks, use a damp cloth. Never use abracould damage the polyester coating. Periodically remove dust which could collect in tusing a vacuum cleaner

Servicing:

In the event of a fault, disconnect from the power supply (switch off or unscrew fuse)done by a qualified electrician.

Identity plate useful data: Product code, power, date of manufacturing (week/year)

NOTE: This guide should be kept by all successive users for future reference

Warranty

Noirot heated air curtains come with a 12 month parts only warranty. For all sales anplease contact: