Heat Pumps Flow Center and Loop Install Guide (1)

download Heat Pumps Flow Center and Loop Install Guide (1)

of 26

Transcript of Heat Pumps Flow Center and Loop Install Guide (1)

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    1/26

    P.O. Box 245

    Syracuse, NY 13211www.roth-america.com

    888-266-7684

    Flow Center and Loop

    Application/InstallationGuide

    Table of Contents:

    Section 1: Model NomenclatureNomenclature description ................................... 2

    Section 2: Installation - Pressurized

    Flow CentersGeneral Installation ............................................... 2

    Optional Adapter Sets .......................................... 3Mounting Flow Center .......................................... 3Interior Piping ......................................................... 4

    Electrical Requirements ........................................ 4Multiple Units .......................................................... 5

    Section 3: Flushing & ChargingOverview ................................................................ 5Flush Cart Design ................................................... 6

    Step by Step Flushing & Charging ....................... 6

    Section 4: Installation -

    Non-Pressurized Flow CentersGeneral Installation ............................................... 9Interior Piping/Flushing .......................................... 9

    Section 5: Closed Loop DesignBasics .................................................................... 11Parallel vs. Series .................................................. 11Header Design..................................................... 12Closed Loop Heat Exchanger Design Rules..... 13

    Soil Moisture Properties ....................................... 16

    Section 6: Antifreeze SelectionOverview .............................................................. 17

    Antifreeze Charging ........................................... 18

    Section 7: HDPE PipePipe Specications .............................................. 20

    Fusion Methods .................................................... 20

    Section 8: Flow Center SelectionPressure Drop Calculations ................................ 21

    Pump Curves ....................................................... 21Pressure Drop Tables ........................................... 22

    Guide Revision Table:

    August, 2010 KT All First Published

    P/N: 2300100909

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    2/26

    2Roth Flow Center & Loop Application ManualAugust, 2010

    Section 1: Model Nomenclature

    Safety Considerations

    WARNING: Before performing service ormaintenance operations on the ow center

    pumps, turn off all power sources. Electricalshock could cause personal injury or death.Before applying power, make sure that all

    covers and screws are in place. Failure todo so could cause risk of electrical shock.

    Flow Center Initial Inspection

    Please read the complete instructionsbefore starting installation. Carefullyfollow instructions to ensure optimum andsafe operation. Leave the instructionswith the owner after installation. The owcenter and Grundfos UP series circulating

    pumps should be installed according to allapplicable codes. Unpack the ow centerand any other component kits required and

    inspect them for shipping damage beforeinstallation. Shipping damage claims mustbe led promptly by the purchaser with thefreight company.

    Note: The ow centers are injected withfoam for condensation preventionduring low temperature operation and for

    noise attenuation. Pump heads can beeld replaced.

    Typical Pressurized Flow Center Installation

    The ow centers are insulated and contain

    all ushing and circulation connectionsfor residential and light commercial earth

    loops that require a ow rate of no morethan 20 gpm. 1-1/4 fusion x 1 doubleo-ring ttings (AGA6PES) are furnished withthe double o-ring ow centers for HDPEloop constructions. Various ttings areavailable for the double o-ring ow centersfor different connections. See table 1 forconnection options. A typical installationwill require the use of a hose kit. Matching

    hose kits come with double o-ring adaptersto transition to 1 hose connection.

    Note: Threaded ow centers all have 1 FPTconnections. Matching hose kits come withthe AGBA55 adapter needed to transitionfrom 1 FPT to 1 hose.

    Model Number: A G FC 1 A

    Part TypeA = Unit Accessory

    OperationG = Pressurized

    B = Non-Pressurized

    Accessory TypeFC = Flow Center

    FM = Flow Module

    Number of Pumps

    Model Number Digit: 1 2 3 4 5 6

    MODEL NUMBER NOMENCLATURE:

    Flow Center TypePressurized Flow Centers:

    A = Composite/Brass valve, double O-Ring fittings, UP26-116 Pumps

    D = Composite/Brass valve, double O-Ring fittings, UP26-99 Pumps

    B = Brass valve, 1 FPT, UP26-99 Pumps

    C = Brass valve, 1 FPT, UP26-116 Pumps

    E = Brass valve, 1 FPT, UP26-99 Pumps

    F = Double O-ring XL fittings, UPS60-150 Pumps

    Non-Pressurized Flow Centers:

    A = UP26-99 Pumps, 1 FPT swivel

    B = UP26-116 Pumps, 1 FPT swivel

    [Consult the price book for more detailed Nomenclature Flow Center Hose Kit Adapter combinations.]

    Section 2: Flow Center Installation -Pressurized

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    3/26

    3Flow Center & Loop Application ManualAugust, 2010

    Roth

    Section 2: Flow Center Installation -Pressurized

    Flow Center Mounting

    The ow center must be located betweenthe heat pump and the earth loop andshould be located as close to the unit aspossible to limit the length of rubber hoseand associated pressure drop (hose kits

    come with 10 of rubber hose - limit one unitper hose kit connection). Other factors forow center location is the ease of futureservice. The ow center must be mountedwith the pump shaft(s) in the horizontal

    position. The only adjustment is that thecirculator pump electrical boxes be on thehorizontal side of the power head in the

    mounted position to help prevent moisturefrom being held inside the junction box(See gures 2a and 2b).

    The ow center can be mounted to thewall or the side of the unit opposite the aircoil. If you are mounting the ow center to

    the stud wall make sure you have isolatedthe ow center from the studs and/or lagbolts to prevent noise and/or vibration. Ifyou are mounting the ow center to theside of the heat pump, be careful not topuncture any internal parts of the unit wheninserting the screws into the cabinet. Keep

    in mind that heat pump access will belimited in this mounting position. Be surewhen mounting the ow center that thereis adequate access to both the ush portsand 3-way valves for any service required.

    Figure 1: Typical Flow Center Installation

    Table 1: Adapter Sets

    Figure 2a: Pump Mounting

    Figure 2b: Control box location

    Part No. Description Connection Use FC Type

    AGA5INS Double O-ring x 1 Brass Barb (Pair) Unit Side O-Ring

    AGA6INS Double O-ring x 1.25 Brass Barb (Pair) Loop or Unit Side O-Ring

    AGA5MPT Double O-ring x 1 Brass MPT (Pair) Loop or Unit Side O-Ring

    AGA6PES Double O-ring x 1.25 PE Socket (Pair) Loop or Unit Side O-Ring

    AGAFP Double O-ring x Cam Lever elbow (male)(pair) Flush Port O-Ring

    AGBA55 1 Brass MPT x 1 Brass Barb (ea) Unit Side FPT

    AGBA56 1 Brass MPT x 1.25 Brass Barb (ea) Loop or Unit Side FPT

    GFMA65 1 Brass MPT x 1.25 PE Socket (ea) Loop or Unit Side FPT

    AGA5FPT Double O-ring x 1 Brass FPT (pair) Loop or Unit Side O-Ring

    AGS5INS Double O-ring x 1 Brass Barb w/PT tap (pair) Unit Side O-Ring

    AGS5MPT Double O-ring x 1 Brass MPT w/PT tap (pair) Units Side O-Ring

    Note:Hose clamps included with hose kits.

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    4/26

    4Roth Flow Center & Loop Application ManualAugust, 2010

    Section 2: Flow Center Installation -Pressurized

    Interior Piping

    All interior piping must be sized for properow rates and pressure loss. Insulationshould be used on all inside piping whenminimum loop temperatures are expectedto be less than 50F. Use the table below

    for insulation sizes with different pipe sizes.All pipe insulation should be a closed celland have a minimum wall thickness of

    3/8. All piping insulation should be gluedand sealed to prevent condensation anddripping. Interior piping may consist of thefollowing materials: HDPE, copper, brass,or rubber hose (hose kit only). PVC is notallowed on pressurized systems.

    Flow Center Electrical Wiring

    Power wiring to the ow center mustconform to all applicable codes. Figure3 illustrates the wiring required at theunit control box. Flow centers are onlyavailable in 230V single phase voltage.Pumps are fused through a pair of circuitbreakers in the unit control box.

    Multiple Units on One Flow Center

    When two units are connected to one looppumping system, pump control is achieved

    by using APSMA loop pump sharingmodule. Using this module allows eitherunit to energize the ow center. Connectthe units and ow center as shown in

    Figures 4 and 5. The APSMA module mustbe located in a NEMA enclosure or insidethe unit control box. Figure 6 shows unitconnections to a common loop with oneow center per unit.

    Piping Material Insul Description

    1" IPS Hose 1-3/8" ID - 3/8" Wall

    1" IPS PE 1-1/4" ID - 3/8" Wall

    1-1/4" IPS PE 1-5/8" ID - 3/8" Wall

    2" IPS PD 2-1/8" ID - 3/8" Wall

    Table 2: Pipe Insulation

    Transformer

    Contactor

    Lockout Board

    (all units)

    Combo Board

    (Optional -- Combo units only)

    PumpConnection

    Pump Circuit Breaker

    (added late 2008)

    Grounding block

    T-StatConnections

    C,R,Y

    1,Y

    2,O,G,W,L

    AccessoryConnections

    ODD,H

    W,A,Y

    T,Y

    U,H

    UM,R

    ElectricHeaterConnections

    C,W

    1,W

    2,W

    3

    COM

    NO

    NC

    COM

    NO

    NC

    ECM Board

    (Optional -- ECM only)

    Blower Relay

    (Optional --

    PSC only)

    Hot Water Pump Relay(Optional -- Combo only)

    or Fan Interlock

    (Optional -- PSC only)

    Wire external loop pump(s)

    to the pump terminalblock in the control box.

    Figure 3: External Pump Wiring

    Figure 4: Pump Sharing Module

    24VAC 24VAC

    240V IN 240V OUT

    Relay Relay

    240VAC

    Power Source

    240VAC

    to Pump(s)

    24VACconnection

    to unit #2(compressor contactor coil)

    24VAC

    connectionto unit #1

    (compressor contactor coil)

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    5/26

    5Flow Center & Loop Application ManualAugust, 2010

    Roth

    Section 2: Flow Center Installation -Pressurized

    Overview

    Once piping is completed between theunit, ow center, and the earth loop, nalpurging and charging of the system isneeded. A ush cart (at least a minimum of1.5 hp pump motor or larger) is needed toachieve adequate ow velocity (2 fps in allpiping) in the loop to purge air and debrisfrom the loop piping (unless the header

    manifold is located inside and has isolationvalves). All air and debris must be removedfrom the system before operation or pump

    failure could result. The ush ports located

    on the ow center are access to the pipingsystem for the ush cart. See gure 7 forconnection details.

    The 3-way valves on the ow center includedirection indicators on the valves whichdetermine the ow path (see gure 8). A3/8 socket drive is required to operate

    the 3-way valves. The valves will turn ineither direction, 360 degrees. Make sureduring this process that the valves are in thesame position so that air does not becometrapped in the system.

    Section 3: Flushing & Charging

    LWT

    EWT

    Heat PumpHeat Pump

    Field-suppliedfull-port ball valve

    for balancing

    Field-suppliedcheck valve to

    prevent short-cycling

    Each heat pumpmust include P/T

    ports to verify flow rates

    EWT

    LWT

    FlowCenter

    FlowCenter

    FlowCenter

    Heat Pump

    EWT

    LWT

    EWT

    LWT

    To Ground Loop

    Figure 5: Two Units Connected to One Flow Center

    Figure 6: Common Loop with One Flow Center per Unit

    HeatPumpHeatPump

    Flow

    Controller

    Field-suppliedfull-port ball valve

    Each heat pumpmust include P/T

    orts to verif flow rates

    LWT

    EWT

    LWT

    EWT

    Heat Pump Heat Pump

    FlowCenter

    EWT

    LWT

    EWT

    LWT

    To Ground Loop

    for balancing

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    6/26

    6Roth Flow Center & Loop Application ManualAugust, 2010

    Section 3: Flushing & Charging

    Flush Cart DesignThe Roth ush cart has been designed toeffectively and efciently ush the earthloop and to facilitate injecting and mixingof the antifreeze. The single most importantelement in ow center reliability is the ability

    to remove all the air and debris from theloop and to provide the proper working

    pressure.

    Features of the ush cart:Cylinder: HDPE, SDR15.5, 10 dia. (10 Gallons)Pump: Myers High Head QP15, 1.5hp, 115VHose connections:

    Cam Lock quick connects - 1-1/2 hosesHand Truck: 600lb rating with pneumatic tiresWiring: Liquid Tight metal on/off switchTubing: SDR11 HDPE

    Connections:

    2 - 3/4 connections for antifreezeand discharge

    Drain: one on the pump and the tank

    Step 1: Flushing the Earth Loop

    1. Connect ush cart hoses to ow

    center ush ports using properadapters #AGAFP.

    2. Connect water supply to hoseconnection on return line of ush cart.

    3. Turn both 3-way valves on ow center toush ports and loop position.

    4. Turn on water supply (make sure water isof proper quality).

    5. As the reservoir lls up, turn the pump on

    and off, sucking the water level down.Do not allow the water level to drop

    below intake tting to the pump.6. Once the water level remains above the

    water outlet in the reservoir leave thepump running continuously.

    7. Once the water level stays above the Tin the reservoir, turn off the water supply(this also allows observation of

    air bubbles).8. Run the pump for a minimum of 2 hours for

    proper ushing and purging (dependingon system size it may take longer).

    9. Dead head the pump every so oftenand watch the water level in the reservoir.Once all the air is removed there shouldnot be more than a 1 to 2 drop in waterlevel in the reservoir. If there is more thana 2 drop, air is still trapped in the system.This is the only way to tell if air is still

    trapped in the system.

    Figure 7: Flush Cart Connections Figure 8: Flow Center 3-Way Valves

    F

    lush

    Port

    F

    lush

    Port

    Flush

    Port

    Flush

    Port

    Loop Loop

    Loop Loop

    Unit Unit

    Unit Unit

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    7/26

    7Flow Center & Loop Application ManualAugust, 2010

    Roth

    Section 3: Flushing & Charging

    10. To dead head the pump, shut off thereturn side ball valve on the ush cart.This will provide a surge in pressure tothe system piping, helping to get the air

    bubbles moving. Do not reverse owduring ushing.

    Water Quality: Even on a closed loopsystem water quality is an issue. The systemneeds to be lled with clean water. If thewater on site has high iron content, highhardness, or the PH is out of balance,premature pump failure may result.Depending upon water quality, it may

    need to be brought in from off site.

    Step 2: Flushing the Unit

    1. Turn off the pump on the ush cart.2. Turn both 3-way valves to the unit and

    ush port position.3. Turn the pump back on. It may be

    necessary to turn the water supply back

    on to keep the water level in the reservoirabove the return tee.

    4. This should only take 5 to 10 minutes to

    purge the unit.5. Once this is done, the entire system

    is now full of water, and the ush cart

    pump may be turned off.

    Step 3: Adding Antifreeze by Displacement

    1. If the antifreeze was not added when theloop was being lled, it will be necessaryto follow the next few steps.

    2. Turn both 3-way Ts back to the originalposition for ushing the loop only.

    3. Close the return side ball valve on theush cart.

    4. Connect hose to the return sidedischarge line and run it to a drain.Open the ball valve on discharge line onush cart.

    5. Turn pump on until water level is suckeddown just above the water outlet in the

    reservoir, and turn pump off. Be sure not

    to suck air back into the system.6. Fill the reservoir back up with

    the antifreeze.7. Repeat steps 5 and 6 until all the

    antifreeze is in the system and reservoir.8. Turn the discharge line ball valve off at

    the ush cart. Turn the return line ballvalve back to the on position.

    Figure 9: Roth Flush Cart Figure 10: Flush Cart Pump Curve

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    8/26

    8Roth Flow Center & Loop Application ManualAugust, 2010

    Section 3: Flushing & Charging

    9. It may be necessary to add some water

    into the reservoir to keep the water levelabove the return tee so that the solutiondoes not foam.

    10. The system must be run for 3 to 4 hoursto mix the antifreeze and water in thereservoir. The uid will not mix insidethe loop.

    11. Check the antifreeze level everyso often to insure that the proper

    amount was added to the system (seeantifreeze charging section).

    Step 4: Final Pressurization of System

    1. Once all of the air and debris has beenremoved, and the antifreeze has been

    added and mixed, the system is ready fornal pressurization.

    2. Turn one of the 3-way valves so that it isopen to all 3 ports, the unit, loop, and

    fush port. Turn the other valve so it isonly open to the loop and fush port(pressure is also applied to the hose kit inthis arrangement).

    3. Turn the ush cart pump on and allow the

    system to start circulating.4. With the pump running, turn the return

    line ball valve to the off position on theush cart, dead heading the pump.

    5. There should be a maximum of 1 to 2inches of drop in the water level in thereservoir. This only takes about3-5 seconds.

    6. Next, turn the supply line ball valve to the

    off position on the ush cart (isolates theow center from the ush cart).

    7. Now that the system is isolated from the

    reservoir the pump can be turned off.Do not open the main ush cart ballvalves yet.

    8. Connect the water supply back to the

    discharge line hose connection, andopen the ball valve. Turn on the watersupply and leave it on for 20 to 30minutes. This will stretch the pipe properlyto insure that the system will not have aat loop during cooling operation.

    9. Once the loop is pressured(recommended pressure on initial start

    up is 50 to 70 psi), turn the water supplyoff. Turn off the discharge line ballvalve, and disconnect the water supply.Maximum pressure should never exceed100 psi under any circumstance!

    10. Turn the 3-way valves on the ow centerback to the normal operation mode,which closes the ush port connections.

    11. Open the ball valves on the ush cart torelieve pressure on the hoses. Disconnectthe hoses from the ow center.

    Note: Pressurized ow centers and GrundfosUP series pumps need a minimum of 3psi onthe suction side of the pump to operate.Maximum operating pressure is 100 psi.

    Loop static pressure will uctuate with theseasons. Pressures will be higher in the

    winter months than during the summermonths. In the cooling mode the heatpump is rejecting heat, which relaxesthe pipe. This uctuation is normal andneeds to be considered when chargingand pressuring the system initially. Typicaloperating pressures of an earth loop are 15

    to 50 psi.

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    9/26

    9Flow Center & Loop Application ManualAugust, 2010

    Roth

    Section 4: Flow Center Installation - Non-Pressurized

    Note - Burping pump(s): On ow center

    initial start up, the pumps must be bled ofair. Start the system and remove the bleedscrew from the back side of the pump(s).This allows any trapped air to bleed out. Italso oods the pump shaft, and keeps thepump(s) cool. Failure to do this could resultin premature pump failure.

    General installation guidelinesStanding column ow centers are designedto operate with no static pressure onthe earth loop. The design is such thatthe column of water in the ow centeris enough pressure to prime the pumpsfor proper system operation and pump

    reliability. The ow center does have acap/seal, so it is still a closed system, wherethe uid will not evaporate. If the earthloop header is external, the loop system willstill need to be ushed with a purge cart asdescribed above (Step 1 and 3). The non-pressurized ow center needs to be isolatedfrom the ush cart during ushing becausethe ow center is not designed to handlepressure. Since this is a non-pressurizedsystem, the interior piping can incorporate

    all the above-mentioned pipe material

    Figure 11: Typical Non-Pressurized Installation

    options (see interior piping), including PVC.The ow center can be mounted to the wallwith the included bracket or mounted onthe oor as long as it is properly supported.

    Flushing the Interior Piping (Non-Pressurized)

    Do not use the ush cart to purge theinterior piping and ow center in a non-

    pressurized system. Once the loop hasbeen ushed the ball valves may beopened above the ush ports. Take agarden hose from the ush port connectedto the water out to the loop pipe, andrun the other end of the hose into thetop of the canister (see gure 12). Fill thecanister with water and turn the pumps on.

    Continue to ll the canister until the waterlevel stays above the dip tube. Once llingis complete, remove the hose and closethe ush port. Turn the system on. Any airthat may still be in the system will burp itselfout of the top of the canister. Leave thetop open for the rst 1/2 hour of run time toensure that all of the air is bled out. Tightenthe cap on the ow center to complete the

    ushing and lling procedure (hand tightenonly -- do not use a wrench). See gures 12

    and 13 for interior and exterior ushing.

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    10/26

    10Roth Flow Center & Loop Application ManualAugust, 2010

    Section 4: Flow Center Installation -Non-Pressurized

    Figure 12: Flushing Inside Piping

    Figure 13: Flushing Outside Piping

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    11/26

    11Flow Center & Loop Application ManualAugust, 2010

    Roth

    Closed Loop Basics

    Closed loop earth coupled systems arecommonly installed in one of three differentcongurations: horizontal, vertical, andpond/lake loop. Each congurationprovides the benet of using the earthsmoderate temperatures as a heat source/sink. All closed loop systems must be

    designed to maintain entering watertemperatures above 25F in heating, andbelow 110F in cooling. Temperaturesoutside this range will cause the heat pumpto function improperly and lockout.

    Select the installation congurationwhich provides the most cost effective

    method of installation after consideringall application constraints. Determiningthe style of loop primarily depends on lotsize and soil conditions. Loop design takesinto account two basic factors. The rst isaccurately engineering a system to functionproperly with low pumping requirementsand adequate heat transfer to handle theload of the structure/system. The secondis to design a loop with the lowest installedcost while still maintaining a high level of

    quality. In the end, the consumer will havepaid approximately the same amount ofmoney for heating, cooling, and hot waterno matter which loop conguration wasinstalled. This leaves the installed cost of theloop as the main factor for determining thesystem payback. Therefore, proper designincludes the most economical systempossible given the installation requirements.

    Parallel vs. Series CongurationsInitially, loops were designed using seriesstyle ow paths due to the lack of fusionttings and procedures to insure there

    there were no leaks. This resulted in largepipe diameters being used (1-1/4 to 2)to reduce pumping requirements due tothe increase of pressure drop because of

    Section 5: Geothermal Closed Loop Design

    the pipe lengths. Since the fusion process

    has become available, parallel ow usingsmaller pipe diameters for loops 2 tonsand larger have become standard for anumber of reasons:

    Cost of the pipe: The larger diameter thepipe, the higher the cost. The benet oflarger pipe only increases performance

    by 10-20%.

    Pumping power: Parallel systems generallyhave much lower pressure drop, whichresults in smaller pumping stations forreduced pump energy.

    Installation ease: Larger diameter pipesare harder to work with, especially during

    cold weather conditions.

    Antifreeze: Because parallel systems utilizesmaller size pipe, the volume of the systemsare smaller, requiring less antifreeze

    Unlimited capacity: Series systems arelimited due to pressure drop reasons,whereas parallel systems are unlimitedin capacity.

    Parallel System Requirements

    Design: Special care in the design isrequired to ensure that all of the air anddebris can be removed from the system.

    Reducing reverse-return header: Requiredfor all parallel systems.

    Pressure drop: Loop lengths must remainwithin +/- 5% of one another for equalpressure drop and balanced ow.

    Fusion: Special training and equipment isrequired to provide fusion ttings.

    Purging: Large pump ush cart is neededto get all of the air and debris out of

    the system.

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    12/26

    12Roth Flow Center & Loop Application ManualAugust, 2010

    Loop Circuiting

    Loops should be designed with acompromise between pressure drop andgood turbulence in the heat exchangepipe for heat transfer. Therefore thefollowing rules should be observed whendesigning a loop:

    1. Use 3 gpm per 3/4 loop ow rate to

    reach turbulent ow.2. Use 3 gpm per ton of nominal

    equipment installed.3.Maintain one loop/circuit per ton of

    nominal capacity with 3/4 pipe and one-half loop/circuit per ton with 1-1/4 pipe.This rule can be deviated by one circuit or

    so for different loop congurations.4. Maximum loop length for 3/4 PE is 800 ft.

    due to pressure drop.

    Circuit 4

    Circuit 1

    1-1/4x 3/4x 3/4 T

    Circuit 3

    3/4x 3/4x 3/4 T

    Circuit 2

    3/4x 3/4x 3/4 T

    2x 1-1/4x 3/4 T2x 2x 3/4 T

    Circuit 8

    Circuits 5 - 7

    (1-1/4 x 1-1/4 x 3/4 Ts)

    Circuits 9 - 12

    Figure 15: Typical Reducing Header up to 12 Tons

    2 foot wide trench

    Circuit 3 Circuit 2 Circuit 1

    Supply Line

    1-1/4elbow

    1-1/4x 3/4x 3/4 T3/4x 3/4x 3/4 T 3/4elbow

    Circuit 3 Circuit 2 Circuit 1

    Return Line

    1-1/4elbow

    1-1/4x 3/4x 3/4 T

    3/4elbow 3/4x 3/4x 3/4 T

    Figure 16: Reverse-Return Header

    Header Design

    Headers for parallel loops should bedesigned with two factors in mind. Therst is pressure drop, and the second is theability to ush the loop. Figure 15 shows thetypical layout for a close header (no morethan 5 between tees) for up to 12 tons and2 header main line. Notice the reduction

    in pipe size as circuits drop off. This designis used to keep the pressure drop down,yet maintain 2 fps for ushing. The othercritical design in the header is the reversereturn connections. This ensures that thereis equal pressure drop through each 3/4circuit, which eliminates the need forbalancing valves. This system will be auto-

    balancing (if all circuits are within +/- 5% inlength from one another). Figure 16 showsthe reverse return layout of the supply/return header manifold.

    Section 5: Geothermal Closed Loop Design

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    13/26

    13Flow Center & Loop Application ManualAugust, 2010

    Roth

    Closed Loop Heat Exchanger Design Rules

    Loop design is based upon variousconditions specic to each job site.Design software based on IGSHPAstandards such as GeoAnalyst isthe best way to size loops.Factorsinclude building load heat gain/losscalculations, equipment capacity,

    equipment efciency, soil conditions,required loop temperature operatingdesign, pipe size, antifreeze selection,weather conditions and lifestyle.

    Know your soil type.Check the sitebefore you decide. Many sourcescan be found locally for informationregarding the site location conditions.

    Example: builders, water well drillers, soilconservation district ofces, geologicalmaps on the internet.

    One ow path (circuit) per ton (12,000BTUS) of equipment(round up or down1 circuit for ton sized unitse.g. 3.5ton unit uses either 3 or 4 circuits). GPM

    ow rates should be 2.25 GPM minimumto 3 GPM per circuit for good turbulenceand heat exchange to the earth.

    Parallel vs. series congurations?Jobs2 ton or larger should use parallel waterow circuits to keep GPM ow rateshigh and pumping HP requirements low.

    Series loops are limited to small tonnageunit sizes (2 total tons or less).

    Divide total trench or bore length asshown in GeoAnalyst software by totaltons of equipment being applied to theloop. Example: 4 ton packaged unit

    trench length = 616 feet or 4 trenches,154 feet long each.

    Trench/bore hole area should belocated 15 feet minimum from thebuilding. If the trench is longer than300 feet, be sure to calculate the totalpiping pressure drop for proper pump/pipe sizing.

    Trench/bore spacing should be kept toa 10 foot minimum distance betweeneach trench/bore hole area.

    Horizontal trenches need not be deeperthan 4-5 feet for most locations, but

    should be approximately 1-2 feet

    deeper than the lowest expected frostline conditions. This will place the pipe ina stable temperature zone.

    Horizontal loop circuits installed intrenches should have enough spaceat the end of the trench to safely

    turn around and return towards thebeginning of the trench without kinksin the tubing or using elbows to reducethe number of fusion joints in the circuit.Good designers try to purchase coil pipethat can go down and back withoutthe use of ttings in the trench, exceptfor the nal connections to the manifoldheader.

    Horizontal trenches/vertical bore holesshould be tapered together at one endof loop eld or the center of a bore eldto utilize a small header pit for parallelcircuits.

    Supply/return manifolds should utilizereverse return design for equal waterow rates on each ow path or circuit.Try to achieve 10 foot trench spacingas soon as practical as you leave theheader pit area and begin the circuittrenches or bore holes.

    Good manifold header design shouldkeep header tee spacing closetogether, less than 2 feet between eachtee outlet, for easy air removal from

    piping system.

    Typical header pitexcavated area isapproximately 4.5 feet long x 4 feetwide x 4.5 5 feet deep.

    Section 5: Geothermal Closed Loop Design

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    14/26

    14Roth Flow Center & Loop Application ManualAugust, 2010

    Never place supply and return piping

    next to the building foundation; alwaysmaintain 15 feet minimum spacing awayfrom any foundation to prevent frostdamage to the building.

    Supply/return line trenching from header

    pit to building should taper uphill towardbuilding, but maintain approximately

    4 feet below nish grade at wallpenetration.Typical trench width is 18-24 wide. Lay supply and return pipingin each corner at bottom of trench. Thiswill reduce the chance of ground waterfollowing piping into the building.

    All piping should be uid pressure tested

    hydrostatically with approximately 100psi for 10 minutes to assure leak freefusion joints and connections beforeback-lling the trench.

    All vertical bore holes should bepressure groutedwith an approvedbentonite grout material utilizing 20%

    solids minimum for proper sealing andheat transfer. This must be done from thebottom up, not just a cap at the top.

    Do not use sand or gravel to backllloop pipe trenches/bores, as it will dryout and impede good heat transferbetween the uid in the pipe and the

    earth. Normally the same soil should beplaced back into the trench. Commonsense should be used regarding largerocks or sharp stones that could crush orcut the piping. Do not place rocks nearthe piping. Cover the loop piping with2-3 feet of good soil rst.

    Its a good idea to include a foil tracer

    tape or copper wire in supply/returntrenching, placing tracer approximately2 feet above piping between header pitand building wall penetration area foreasy locating of the supply/return andmanifold area.

    Supply/return piping will typically be 1.25

    diameter PE from the header manifold(outdoors) to the ow center (loop pump)located in the building near the unit. Allpiping penetrating the building foundationshould be protected in conduit.

    All piping inside the building should beproperly insulatedwith pipe insulation to

    prevent condensation damage to thebuilding.

    Loop uid should be antifreezeprotected to 15F with an approved uidtype, typically Methanol, Ethanol orPropylene Glycol. Test with the properhydrometer.

    All piping and connections should be

    composed of an approved geothermalpolyethylene PE3408 type pipe,utilizingsocket fusion or butt fusion and installedby a qualied fusion technician.

    Notes:

    Safety First!

    We strongly suggest that contractors

    attend either a factory training school orIGSHPA training school for Loop Design andInstallation before attempting loop designand installations.

    Always check BEFORE YOU DIG! Contactyour local underground utility locatorservice and verify any utility that might belocated nearby.

    Stay away from electrical power, septicsystems and well water lines.

    Check with your local building/healthdepartment regarding permits, codes andlaws that may apply to your location orstate/province regarding geothermal loopsystems.

    Section 5: Geothermal Closed Loop Design

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    15/26

    15Flow Center & Loop Application ManualAugust, 2010

    Roth

    Contact your distributor for additional

    information on training locations and dates.

    Good loop design and proper installationare necessary for any system to operateproperly.

    We offer and support several designschools and tools to take the guesswork

    out of residential loop system design. Askyour local distributor about our GeoAnalystsoftware tool that will provide you withthe science behind the design and thecondence you need to actively design,install and service geothermal equipmentand loop systems.

    Like anything else Its not that hardwhen you have the proper training and thetools.

    Section 5: Geothermal Closed Loop Design

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    16/26

    16Roth Flow Center & Loop Application ManualAugust, 2010

    Soil Moisture Properties

    An important factor affecting heat transferbetween the earth and the loop is moisturemigration. When heat is extracted fromthe earth, soil moisture migrates towardthe earth loop, improving heat transferbetween the loop and the surrounding soil.In the cooling mode, heat rejection to thesoil can drive away moisture, degrading

    heat transfer. In heating dominatedclimates, this later negative effect has notbeen observed in practice. However, incooling dominated climates, this specialcondition must be considered in regard toloop lengths due to longer run times in thecooling mode.

    Another important factor affecting heattransfer between the earth and the loopis soil moisture freezing. Freezing allows theextraction of energy from the soil withoutthe normal drop in soil temperature in thevicinity of the pipe. The net effect is thatthe antifreeze solution returning to theheat pump from the earth loop returns at ahigher temperature than if freezing had not

    occurred.

    Earth loops are sized after the housedesign heating and cooling loads havebeen calculated, and the heat pump sizehas been selected. All heat pumps aredesigned with high and low limits on theenergy source liquid which are acceptable.

    CLAY

    H2O

    H2O

    H2O

    H2 2O

    SAND

    SILT

    Cross View (DRY) Microscopic View

    Cross View (WET)

    Consistency: Hershey Bar

    Visible to Eye Microscopic View

    Microscopic View

    O H

    Denition of Sizes:

    SAND = Visible to Eye - 1/4 GRAVEL = 1/4 - 3

    COBBLE = 3 - 12 BOULDER = 12 and up

    Moisture Content for All Soils:

    DRY = No Water MOIST = Damp Feel WET = Visible Water

    Section 5: Geothermal Closed Loop Design

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    17/26

    17Flow Center & Loop Application ManualAugust, 2010

    Roth

    Section 6: Antifreeze Selection & Charging

    Antifreeze Overview

    In areas where minimum entering looptemperatures drop below 40F, or wherepiping will be routed through areassubject to freezing, antifreeze is required.Alcohols and glycols are commonly usedas antifreeze. However, local and state/provincial codes supercede any instructions

    in this document. The system needsantifreeze to protect the coaxial heatexchanger from freezing and rupturing.Freeze protection should be maintained to15F below the lowest expected enteringloop temperature. For example, if 30Fis the minimum expected entering looptemperature, the leaving loop temperature

    could be 22 to 25F. Freeze protectionshould be set at 15F (30-15 = 15F). Todetermine antifreeze requirements,calculate how much volume the systemholds. Then, calculate how muchantifreeze will be needed by determiningthe percentage of antifreeze required forproper freeze protection. See tables 3 and4 for volumes and percentages. The freeze

    protection should be checked duringinstallation using the proper hydrometer

    to measure the specic gravity and freezeprotection level of the solution.

    Antifreeze Characteristics

    Selection of the antifreeze solution

    for closed loop systems require theconsideration of many important factors,which have long-term implications on theperformance and life of the equipment.

    Each area of concern leads to a differentbest choice of antifreeze. There is noperfect antifreeze. Some of the factorsto consider are as follows (Brine = antifreezesolution including water):

    Safety: The toxicity and ammability of thebrine (especially in a pure form).

    Cost: Prices vary widely.

    Thermal Performance: The heat transferand viscosity effect of the brine.

    Corrosiveness: The brine must becompatible with the system materials.

    Stability: Will the brine require periodicchange out or maintenance?

    Convenience: Is the antifreeze available

    and easy to transport and install?

    Codes: Will the brine meet local and state/provincial codes?

    The following are some generalobservations about the types of brinespresently being used:

    Methanol: Wood grain alcohol that isconsidered toxic in pure form. It has goodheat transfer, low viscosity, is non-corrosive,and is mid to low price. The biggest downside is that it is ammable in concentrationsgreater than 25%.

    Ethanol: Grain alcohol, which by the ATF(Alcohol, Tobaco, Firearms) department

    of the U.S. government, is required to bedenatured and rendered unt to drink.

    It has good heat transfer, mid to highprice, is non-corrosive, non-toxic even inits pure form, and has medium viscosity.It also is ammable with concentrationsgreater than 25%. Note that the brandof ethanol is very important. Make sure ithas been formulated for the geothermal

    industry. Some of the denaturants are notcompatible with HDPE pipe (for example,solutions denatured with gasoline).

    Propylene Glycol: Non-toxic, non-corrosivemid to high price, poor heat transfer, highviscosity when cold, and can introducemicro air bubbles when adding to thesystem. It has also been known to form a

    slime-type coating inside the pipe. Foodgrade glycol is recommended becausesome of the other types have certaininhibitors that react poorly with geothermal

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    18/26

    18Roth Flow Center & Loop Application ManualAugust, 2010

    Section 6: Antifreeze Selection & Charging

    systems. A 25% brine solution is a minimumrequired by glycol manufacturers, so thatbacteria does not start to form.

    Ethylene Glycol: Considered toxic and isnot recommended for use in earthloop applications.

    GS4 (Potassium acetate): Consideredhighly corrosive (especially if air is present

    in the system) and has a very low surfacetension, which causes leaks throughmost mechanical ttings. This brine isnot recommended for use in earth loopapplications.

    Notes:1. Consult with your representative or

    distributor if you have any questionsregarding antifreeze selection or use.

    2. All antifreeze suppliers and manufacturersrecommend the use of either de-ionizedor distilled water with their products.

    10F (-12.2C) 15F (-9.4C) 20F (-6.7C) 25F (-3.9C)

    Procool (Ethanol) 25% 22% 17% 12%

    Methanol 25% 21% 16% 10%

    Propylene Glycol 38% 30% 22% 15%

    All antifreeze solutions are shown in pure form not premixed.

    Minimum Temperature for Freeze Protection

    Type of Antifreeze

    Table 3: Antifreeze Percentages by Volume

    Caution: Use extreme care when opening,pouring, and mixing ammable antifreezesolutions. Remote ames or electrical sparkscan ignite undiluted antifreezes and vapors.Use only in a well ventilated area. Do notsmoke when handling ammable solutions.

    Failure to observe safety precautions mayresult in re, injury, or death. Never workwith 100% alcohol solutions.

    Antifreeze Charging

    Calculate the total amount of pipe inthe system and use table 3 to calculate

    the amount of volume for each specicsection of the system. Add the entirevolume together, and multiply that volume

    by the proper antifreeze percentageneeded (table 4) for the freeze protectionrequired in your area. Then, double checkcalculations during installation with theproper hydrometer and specic gravitychart (gure 14) to determine if the correct

    amount of antifreeze was added.

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    19/26

    19Flow Center & Loop Application ManualAugust, 2010

    Roth

    Volume/100 ft.U.S. Gal.

    Copper 1" CTS 4.1

    Copper 1.25" CTS 6.4Copper 1.5" CTS 9.2

    HDPE .75 SDR11 3.0

    HDPE 1" SDR11 4.7

    HDPE 1.25" SDR11 7.5

    HDPE 1.5" SDR11 9.8

    HDPE 2" SDR11 15.4

    Additional component volumes:

    Unit coaxial heat exchanger = 1 Gallon

    Flush Cart = 8-10 Gallons

    10 of 1 Rubber Hose = 0.4 Gallons

    Type Size

    Table 4: Pipe Fluid Volume

    Section 6: Antifreeze Selection & Charging

    0.9600

    0.9700

    0.9800

    0.9900

    1.0000

    1.0100

    1.0200

    1.0300

    1.0400

    1.0500

    -5 0 5 10 15 20 25 30 32

    SpecificGravity

    Freeze Protection (deg F)

    Procool Methanol Propylene Glycol

    Figure 14: Antifreeze Specic Gravity

    NOTE: Most manufacturers ofantifreeze solutions recommendthe use of de-ionized water. Tapwater may include chemicalsthat could react with the anti-freeze solution.

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    20/26

    20Roth Flow Center & Loop Application ManualAugust, 2010

    Section 7: HDPE Pipe

    High Density Polyethylene Pipe (HDPE)All earth loop piping materials shouldbe limited to only polyethylene pipeunderground. Copper, brass, galvanized,or steel pipe or ttings should not be used.For fusion applications, the HDPE pipe mustmeet IGSHPA (International Ground SourceHeat Pump Association) cell classicationrequirements (see below). The water wellindustry uses similar black HDPE 160 psi ratedpipe. However, this pipe does not allow forfusion joints. Below are the specications forthe proper geothermal HDPE pipe:

    1. All pipe and heat fused materials shallbe made from high density, extra-high

    molecular weight PE 3408 resin.2. The cell classication shall be 345444C as

    specied in ASTM D-3350.3. Extruded pipe shall conform to the

    requirements of ASTM D-3035.4. Socket ttings shall conform to the

    requirements of ASTM D-2683 and ratedfor pressure equivalent to SDR-11 pipe.

    5. Wall thickness of pipe shall be in

    tolerance of the specications of 160 psiand SDR-11 for heat fused pipe & ttings.

    Pipe Fusion MethodsThe three basic types of pipe joiningmethods that are used for earth coupledapplications are socket, butt, and sidesaddle fusion. In all processes the pipe

    is melted together with the tting toform a joint that is even stronger thanthe original pipe. Although when any of

    the procedures are performed properlythe joint is stronger than the pipe wall,the preferred method for 2 and smallerdiameter pipe is socket fusion because ofthe following:

    1. Allowable tolerance of mating the pipe

    is much greater. According to generalfusion guidelines, a 3/4 SDR11 butt fusionjoint alignment can be off by no morethan 10% of the wall thickness (0.01 in.).A hundredth of an inch accuracy whilefusing in a difcult position can be almostimpossible to attain in the eld.

    2. The socket fusion joint is 3 to 4 times the

    cross sectional area of a butt fusion jointin sizes under 2, and therefore tends tobe more forgiving of operator skill level.

    3. Joints are frequently required in difculttrench conditions. The smaller the socketfusion iron is, the more mobile the operator

    will be, which will provide less incentive tocut corners during the fusion procedure.

    Once the pipe diameter gets over 2,socket fusion loses its advantages, andbutt fusion is typically the method ofchoice. Butt fusion requires a differentfusion machine, which is larger and lessmaneuverable. All technicians doingfusion joints should be certied by the pipemanufacturer as well as IGSHPA. Please seethe pipe manufacturers and IGSHPA tablesand specications for all fusion procedures.

    Note: Earth loop systems require ahydrostatic test of 40-50 psi beforebacklling to test for leaks. Do not use anair test for leaks on an earth loop system.

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    21/26

    21Flow Center & Loop Application ManualAugust, 2010

    Roth

    Pressure drop calculations

    When designing the earth loop andselecting the proper ow center, a pressuredrop calculation must be done to calculatehow much pumping power is needed forproper ow through the heat pump andloops. In general, if basic loop designrules are followed, systems of 3 tons or less

    would require a one pump ow center, andsystem from 3.5 to 6 tons would require atwo pump ow center. As a precautionarymeasure a loop pressure drop calculationshould be performed for accurate owestimation. The pressure drop must includethe following components:

    1. Heat pump at design ow rate2. Hose kit (maximum 10)3. Supply and Return header piping4. Circuit piping (only one if piped in parallel)5. Antifreeze

    Once the pressure drop of the system has

    been calculated at design ow rate, reviewthe ow center pump curve to select aow center that matches design criteria.There are many options with ow centersfrom one pump, two pump, three pump,four pump, and size pumps from UP26-99Fto UP26-116F. The following pages includepressure drop tables for the pipe and the

    ow center pump curves.

    Note: Roth has software available to assistin calculating the pressure drop of anearth coupled system along with ushing

    requirements.

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

    Flow Rate (U.S. GPM)

    Ft.ofHead

    1 - UP26-991 - UP26-116

    2 - UP26-992 - UP26-1163 - UP26-99

    Legend

    Figure 17: Grundfos Pump Curves

    Section 8: Flow Center Selection

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    22/26

    22Roth Flow Center & Loop Application ManualAugust, 2010

    Antifreeze (30F EWT): 22% by Volume Solution of Procool - freeze protected to 15F

    Flow Rate

    US GPM PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE

    1 0.37 0.55 1029 0.13 0.35 820 0.04 0.21 630 0.02 0.16 560 0.01 0.10 450

    2 1.25 1.10 2058 0.43 0.70 1640 0.13 0.43 1291 0.06 0.32 1121 0.02 0.19 854

    3 2.54 1.66 3105 0.87 1.06 2483 0.27 0.64 1921 0.13 0.47 1646 0.04 0.29 1304

    4 4.20 2.21 4134 1.44 1.41 3303 0.44 0.86 2581 0.21 0.63 2206 0.07 0.38 1708

    5 6.21 2.76 5163 2.13 1.76 4123 0.66 1.07 3212 0.32 0.79 2766 0.10 0.48 2158

    6 8.55 3.31 6191 2.94 2.11 4943 0.90 1.29 3872 0.43 0.95 3327 0.13 0.57 2563

    7 11.19 3.87 7239 3.84 2.47 5786 1.18 1.50 4502 0.57 1.10 3852 0.17 0.67 3012

    8 14.13 4.42 8268 4.85 2.82 6606 1.49 1.72 5163 0.72 1.26 4412 0.22 0.76 34179 17.37 4.97 9296 5.97 3.17 7426 1.84 1.93 5793 0.88 1.42 4972 0.27 0.86 3866

    10 20.89 5.52 10325 7.17 3.52 8245 2.21 2.15 6453 1.06 1.58 5533 0.32 0.96 4316

    11 24.67 6.08 11373 8.48 3.87 9065 2.61 2.36 7084 1.26 1.73 6058 0.38 1.05 4720

    12 28.74 6.63 12401 9.87 4.23 9909 3.04 2.57 7714 1.46 1.89 6618 0.45 1.15 5170

    13 11.35 4.58 10728 3.50 2.79 8374 1.68 2.05 7179 0.51 1.24 5575

    14 12.93 4.93 11548 3.98 3.00 9004 1.91 2.21 7739 0.58 1.34 6024

    15 14.59 5.28 12368 4.49 3.22 9665 2.16 2.36 8264 0.66 1.43 6429

    16 16.32 5.64 13211 5.03 3.43 10295 2.42 2.52 8824 0.74 1.53 6878

    17 18.15 5.99 14031 5.59 3.65 10955 2.69 2.68 9385 0.82 1.63 7328

    18 20.07 6.34 14851 6.18 3.86 11586 2.97 2.84 9945 0.91 1.72 7733

    19 22.06 6.69 15671 6.79 4.08 12246 3.27 2.99 10470 1.00 1.82 8182

    20 24.13 7.04 16491 7.43 4.29 12876 3.57 3.15 11030 1.09 1.91 8587

    21 26.28 7.40 17334 8.10 4.50 13507 3.89 3.31 11591 1.19 2.01 9036

    22 28.51 7.75 18154 8.78 4.72 14167 4.22 3.47 12151 1.29 2.10 9441

    23 30.81 8.10 18974 9.49 4.93 14797 4.57 3.62 12676 1.39 2.20 9891

    24 10.22 5.15 15458 4.92 3.78 13237 1.50 2.29 10295

    25 10.98 5.36 16088 5.28 3.94 13797 1.61 2.39 10745

    26 11.76 5.58 16748 5.66 4.10 14357 1.73 2.49 11194

    28 13.39 6.01 18039 6.44 4.41 15443 1.96 2.68 12048

    30 15.11 6.44 19330 7.27 4.73 16563 2.22 2.87 12903

    32 16.92 6.86 20590 8.14 5.04 17649 2.48 3.06 13757

    34 18.81 7.29 21881 9.04 5.36 18769 2.76 3.25 14611

    36 20.79 7.72 23171 10.00 5.67 19855 3.05 3.44 15465

    38 22.85 8.15 24462 10.99 5.99 20975 3.35 3.63 16319

    40 25.00 8.58 25753 12.02 6.30 22061 3.67 3.82 17174

    42 27.23 9.01 27043 13.09 6.62 23181 3.99 4.02 18073

    44 29.54 9.44 28334 14.20 6.93 24267 4.33 4.21 18927

    46 15.35 7.25 25388 4.68 4.40 19781

    48 16.54 7.57 26508 5.05 4.59 20635

    50 17.76 7.88 27594 5.42 4.78 21489

    2" SCH403/4" SDR11 1-1/4" SCH401" SDR11 1-1/2" SCH40

    Antifreeze (30F EWT): 21% by Volume Solution of Methanol - freeze protected to 15F

    Flow Rate

    US GPM PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE1 0.36 0.55 1121 0.13 0.35 893 0.04 0.21 687 0.02 0.16 610 0.01 0.10 490

    2 1.22 1.10 2242 0.42 0.70 1786 0.13 0.43 1406 0.06 0.32 1221 0.02 0.19 931

    3 2.49 1.66 3383 0.85 1.06 2705 0.26 0.64 2093 0.13 0.47 1793 0.04 0.29 1420

    4 4.11 2.21 4503 1.41 1.41 3598 0.43 0.86 2812 0.21 0.63 2403 0.06 0.38 1861

    5 6.08 2.76 5624 2.09 1.76 4491 0.64 1.07 3499 0.31 0.79 3014 0.09 0.48 2351

    6 8.37 3.31 6745 2.87 2.11 5385 0.88 1.29 4218 0.42 0.95 3624 0.13 0.57 2792

    7 10.95 3.87 7886 3.76 2.47 6303 1.16 1.50 4905 0.56 1.10 4196 0.17 0.67 3281

    8 13.83 4.42 9007 4.75 2.82 7197 1.46 1.72 5624 0.70 1.26 4807 0.22 0.76 3722

    9 17.00 4.97 10128 5.84 3.17 8090 1.80 1.93 6311 0.86 1.42 5417 0.26 0.86 4212

    10 20.45 5.52 11248 7.02 3.52 8983 2.16 2.15 7030 1.04 1.58 6028 0.32 0.96 4702

    11 24.15 6.08 12390 8.30 3.87 9876 2.56 2.36 7717 1.23 1.73 6600 0.38 1.05 5143

    12 28.13 6.63 13510 9.66 4.23 10795 2.98 2.57 8404 1.43 1.89 7210 0.44 1.15 5632

    13 11.11 4.58 11688 3.42 2.79 9123 1.65 2.05 7821 0.50 1.24 6073

    14 12.65 4.93 12581 3.90 3.00 9810 1.87 2.21 8431 0.57 1.34 6563

    15 14.28 5.28 13474 4.40 3.22 10529 2.12 2.36 9003 0.65 1.43 7004

    16 15.98 5.64 14393 4.92 3.43 11216 2.37 2.52 9614 0.72 1.53 7494

    17 17.77 5.99 15286 5.47 3.65 11935 2.63 2.68 10224 0.80 1.63 7983

    18 19.64 6.34 16179 6.05 3.86 12622 2.91 2.84 10834 0.89 1.72 8424

    19 21.59 6.69 17073 6.65 4.08 13341 3.20 2.99 11407 0.98 1.82 8914

    20 23.62 7.04 17966 7.27 4.29 14028 3.50 3.15 12017 1.07 1.91 9355

    21 25.72 7.40 18884 7.93 4.50 14715 3.81 3.31 12627 1.16 2.01 9844

    22 27.90 7.75 19778 8.60 4.72 15434 4.13 3.47 13238 1.26 2.10 1028523 30.16 8.10 20671 9.29 4.93 16121 4.47 3.62 13810 1.36 2.20 10775

    24 10.01 5.15 16840 4.81 3.78 14420 1.47 2.29 11216

    25 10.75 5.36 17527 5.17 3.94 15031 1.58 2.39 11706

    26 11.51 5.58 18246 5.54 4.10 15641 1.69 2.49 12195

    28 13.11 6.01 19652 6.30 4.41 16824 1.92 2.68 13126

    30 14.79 6.44 21058 7.11 4.73 18044 2.17 2.87 14057

    32 16.56 6.86 22432 7.96 5.04 19227 2.43 3.06 14987

    34 18.41 7.29 23838 8.85 5.36 20448 2.70 3.25 15918

    36 20.35 7.72 25244 9.79 5.67 21630 2.99 3.44 16848

    38 22.37 8.15 26650 10.76 5.99 22851 3.28 3.63 17779

    40 24.47 8.58 28056 11.77 6.30 24034 3.59 3.82 18709

    42 26.65 9.01 29462 12.81 6.62 25255 3.91 4.02 19689

    44 28.91 9.44 30868 13.90 6.93 26437 4.24 4.21 20620

    46 15.03 7.25 27658 4.59 4.40 21550

    48 16.19 7.57 28879 4.94 4.59 22481

    50 17.39 7.88 30061 5.31 4.78 23411

    2" SCH403/4" SDR11 1" SDR11 1-1/4" SCH40 1-1/2" SCH40

    Table 5: Procool (Ethanol)

    Table 6: Methanol

    Section 8: Flow Center Selection

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    23/26

    23Flow Center & Loop Application ManualAugust, 2010

    Roth

    Table 7: Propylene Glycol

    Table 8: Water

    Antifreeze (30F EWT): 30% by Volume Solution of Propylene Glycol - freeze protected to 15F

    Flow Rate

    US GPM PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE

    1 0.43 0.55 584 0.15 0.35 466 0.05 0.21 358 0.02 0.16 318 0.01 0.10 255

    2 1.44 1.10 1169 0.49 0.70 932 0.15 0.43 733 0.07 0.32 637 0.02 0.19 485

    3 2.92 1.66 1764 1.00 1.06 1411 0.31 0.64 1091 0.15 0.47 935 0.05 0.29 741

    4 4.84 2.21 2348 1.66 1.41 1876 0.51 0.86 1466 0.25 0.63 1253 0.08 0.38 970

    5 7.15 2.76 2933 2.46 1.76 2342 0.76 1.07 1824 0.36 0.79 1572 0.11 0.48 1226

    6 9.84 3.31 3517 3.38 2.11 2808 1.04 1.29 2200 0.50 0.95 1890 0.15 0.57 1456

    7 12.89 3.87 4112 4.42 2.47 3287 1.36 1.50 2558 0.66 1.10 2188 0.20 0.67 1711

    8 16.28 4.42 4697 5.59 2.82 3753 1.72 1.72 2933 0.83 1.26 2506 0.25 0.76 19419 20.01 4.97 5281 6.87 3.17 4218 2.12 1.93 3291 1.02 1.42 2825 0.31 0.86 2196

    10 24.06 5.52 5866 8.26 3.52 4684 2.54 2.15 3666 1.22 1.58 3143 0.37 0.96 2452

    11 28.42 6.08 6461 9.76 3.87 5150 3.01 2.36 4024 1.45 1.73 3441 0.44 1.05 2682

    12 11.37 4.23 5629 3.50 2.57 4382 1.68 1.89 3760 0.51 1.15 2937

    13 13.08 4.58 6095 4.03 2.79 4757 1.94 2.05 4078 0.59 1.24 3167

    14 14.89 4.93 6560 4.59 3.00 5115 2.20 2.21 4396 0.67 1.34 3422

    15 16.80 5.28 7026 5.17 3.22 5490 2.49 2.36 4695 0.76 1.43 3652

    16 18.80 5.64 7505 5.79 3.43 5848 2.79 2.52 5013 0.85 1.53 3908

    17 20.91 5.99 7971 6.44 3.65 6224 3.10 2.68 5331 0.94 1.63 4163

    18 23.11 6.34 8437 7.12 3.86 6582 3.42 2.84 5650 1.04 1.72 4393

    19 25.41 6.69 8903 7.82 4.08 6957 3.76 2.99 5948 1.15 1.82 4648

    20 27.80 7.04 9368 8.56 4.29 7315 4.12 3.15 6266 1.26 1.91 4878

    21 30.27 7.40 9847 9.33 4.50 7673 4.48 3.31 6585 1.37 2.01 5133

    22 10.11 4.72 8048 4.86 3.47 6903 1.48 2.10 5363

    23 10.94 4.93 8406 5.26 3.62 7201 1.60 2.20 5619

    24 11.78 5.15 8781 5.66 3.78 7519 1.73 2.29 5849

    25 12.65 5.36 9139 6.08 3.94 7838 1.86 2.39 6104

    26 13.55 5.58 9514 6.51 4.10 8156 1.99 2.49 6359

    28 15.42 6.01 10248 7.42 4.41 8773 2.26 2.68 6845

    30 17.40 6.44 10981 8.37 4.73 9409 2.55 2.87 7330

    32 19.49 6.86 11697 9.37 5.04 10026 2.86 3.06 7815

    34 21.67 7.29 12430 10.42 5.36 10663 3.18 3.25 8300

    36 23.95 7.72 13163 11.52 5.67 11279 3.51 3.44 8786

    38 26.32 8.15 13897 12.66 5.99 11916 3.86 3.63 9271

    40 28.80 8.58 14630 13.85 6.30 12532 4.23 3.82 9756

    42 15.08 6.62 13169 4.60 4.02 10267

    44 16.36 6.93 13786 4.99 4.21 10752

    46 17.68 7.25 14422 5.40 4.40 11237

    48 19.05 7.57 15059 5.81 4.59 11723

    50 20.46 7.88 15676 6.24 4.78 12208

    2" SCH403/4" SDR11 1" SDR11 1-1/4" SCH40 1-1/2" SCH40

    Water -- No Antifreeze (50F EWT)

    Flow Rate

    US GPM PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE1 0.23 0.55 6760 0.08 0.35 5387 0.02 0.21 4142 0.01 0.16 3681 0.00 0.10 2954

    2 0.78 1.10 13520 0.27 0.70 10774 0.08 0.43 8481 0.04 0.32 7363 0.01 0.19 5613

    3 1.59 1.66 20402 0.54 1.06 16315 0.17 0.64 12622 0.08 0.47 10814 0.02 0.29 8567

    4 2.62 2.21 27162 0.90 1.41 21703 0.28 0.86 16961 0.13 0.63 14496 0.04 0.38 11225

    5 3.88 2.76 33922 1.33 1.76 27090 0.41 1.07 21103 0.20 0.79 18177 0.06 0.48 14179

    6 5.34 3.31 40682 1.83 2.11 32477 0.56 1.29 25442 0.27 0.95 21859 0.08 0.57 16838

    7 6.99 3.87 47565 2.40 2.47 38018 0.74 1.50 29583 0.36 1.10 25310 0.11 0.67 19792

    8 8.83 4.42 54325 3.03 2.82 43405 0.93 1.72 33922 0.45 1.26 28992 0.14 0.76 22451

    9 10.85 4.97 61085 3.73 3.17 48792 1.15 1.93 38064 0.55 1.42 32673 0.17 0.86 25405

    10 13.05 5.52 67844 4.48 3.52 54179 1.38 2.15 42403 0.66 1.58 36355 0.20 0.96 28359

    11 15.41 6.08 74727 5.30 3.87 59567 1.63 2.36 46544 0.78 1.73 39806 0.24 1.05 31017

    12 17.95 6.63 81487 6.16 4.23 65108 1.90 2.57 50686 0.91 1.89 43487 0.28 1.15 33971

    13 7.09 4.58 70495 2.18 2.79 55025 1.05 2.05 47169 0.32 1.24 36630

    14 8.07 4.93 75882 2.49 3.00 59167 1.20 2.21 50850 0.36 1.34 39584

    15 9.11 5.28 81269 2.81 3.22 63505 1.35 2.36 54302 0.41 1.43 42243

    16 10.20 5.64 86810 3.14 3.43 67647 1.51 2.52 57983 0.46 1.53 45197

    17 11.34 5.99 92197 3.49 3.65 71986 1.68 2.68 61665 0.51 1.63 48151

    18 12.53 6.34 97585 3.86 3.86 76128 1.86 2.84 65346 0.57 1.72 50810

    19 13.78 6.69 102972 4.24 4.08 80467 2.04 2.99 68798 0.62 1.82 53764

    20 15.07 7.04 108359 4.64 4.29 84608 2.23 3.15 72479 0.68 1.91 56422

    21 16.41 7.40 113900 5.06 4.50 88750 2.43 3.31 76161 0.74 2.01 59376

    22 17.80 7.75 119287 5.48 4.72 93089 2.64 3.47 79842 0.81 2.10 6203523 19.25 8.10 124674 5.93 4.93 97230 2.85 3.62 83293 0.87 2.20 64989

    24 6.39 5.15 101569 3.07 3.78 86975 0.94 2.29 67648

    25 6.86 5.36 105711 3.30 3.94 90656 1.01 2.39 70602

    26 7.35 5.58 110050 3.53 4.10 94338 1.08 2.49 73556

    28 8.36 6.01 118530 4.02 4.41 101471 1.23 2.68 79168

    30 9.44 6.44 127011 4.54 4.73 108834 1.38 2.87 84781

    32 10.57 6.86 135294 5.08 5.04 115967 1.55 3.06 90394

    34 11.75 7.29 143775 5.65 5.36 123330 1.72 3.25 96006

    36 12.99 7.72 152255 6.24 5.67 130462 1.91 3.44 101619

    38 14.27 8.15 160736 6.86 5.99 137825 2.10 3.63 107232

    40 15.61 8.58 169216 7.51 6.30 144958 2.29 3.82 112844

    42 17.01 9.01 177697 8.18 6.62 152321 2.49 4.02 118753

    44 18.45 9.44 186178 8.87 6.93 159454 2.71 4.21 124365

    46 19.94 9.87 194658 9.59 7.25 166817 2.93 4.40 129978

    48 10.33 7.57 174180 3.15 4.59 135591

    50 11.09 7.88 181313 3.39 4.78 141203

    2" SCH403/4" SDR11 1" SDR11 1-1/4" SCH40 1-1/2" SCH40

    Section 8: Flow Center Selection

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    24/26

    24Roth Flow Center & Loop Application ManualAugust, 2010

    Table 9: Hose Kit Pressure Drop

    1" Rubber Hose Pressure Drop per 100ft of Pipe Table

    Flow Rate

    US GPM PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE PD (ft) Vel (ft/s) RE

    1 0.13 0.35 820 0.13 0.35 893 0.15 0.35 466 0.12 0.35 923

    2 0.43 0.70 1640 0.42 0.70 1786 0.49 0.70 932 0.42 0.70 1847

    3 0.87 1.06 2483 0.85 1.06 2705 1.00 1.06 1411 0.85 1.06 2796

    4 1.44 1.41 3303 1.41 1.41 3598 1.66 1.41 1876 1.40 1.41 3720

    5 2.13 1.76 4123 2.09 1.76 4491 2.46 1.76 2342 2.07 1.76 4643

    6 2.94 2.11 4943 2.87 2.11 5385 3.38 2.11 2808 2.85 2.11 55677 3.84 2.47 5786 3.76 2.47 6303 4.42 2.47 3287 3.73 2.47 6516

    8 4.85 2.82 6606 4.75 2.82 7197 5.59 2.82 3753 4.71 2.82 7440

    9 5.97 3.17 7426 5.84 3.17 8090 6.87 3.17 4218 5.79 3.17 8363

    10 7.17 3.52 8245 7.02 3.52 8983 8.26 3.52 4684 6.96 3.52 9286

    11 8.48 3.87 9065 8.30 3.87 9876 9.76 3.87 5150 8.23 3.87 10210

    12 9.87 4.23 9909 9.66 4.23 10795 11.37 4.23 5629 9.58 4.23 11160

    13 11.35 4.58 10728 11.11 4.58 11688 13.08 4.58 6095 11.02 4.58 12083

    14 12.93 4.93 11548 12.65 4.93 12581 14.89 4.93 6560 12.55 4.93 13006

    15 14.59 5.28 12368 14.28 5.28 13474 16.80 5.28 7026 14.16 5.28 13930

    16 16.32 5.64 13211 15.98 5.64 14393 18.80 5.64 7505 15.85 5.64 14879

    17 18.15 5.99 14031 17.77 5.99 15286 20.91 5.99 7971 17.62 5.99 15803

    18 20.07 6.34 14851 19.64 6.34 16179 23.11 6.34 8437 19.48 6.34 16726

    19 22.06 6.69 15671 21.59 6.69 17073 25.41 6.69 8903 21.41 6.69 17650

    20 24.13 7.04 16491 23.62 7.04 17966 27.80 7.04 9368 23.42 7.04 18573

    *NOTES:

    1. Procool is at 22% by volume; Methanol is at 21% by volume; Propylene Glycol is at 30% by volume.

    2. Percentage by volume, shown above is 15F freeze protection.

    3. All fluids with antifreeze are shown at 30F; water is at 50F.

    Methanol* Propylene Glycol*Procool (Ethanol)* Water*

    Section 8: Flow Center Selection

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    25/26

  • 8/12/2019 Heat Pumps Flow Center and Loop Install Guide (1)

    26/26

    P.O. Box 245

    Syracuse, NY 13211

    888-266-7684 US

    800-969-7684 CAN

    866-462-2914 FAX

    www.roth-america.com

    [email protected]

    *AHRI certication is shown as the Roth brand under the Enertech Manufacturing certication reference number**Roth Industries geothermal heat pumps are shown as a multiple listing of Enertech Manufacturings ETL certication

    *** Roth geothermal heat p mps are listed as a brand nder Enertech Man fact rings Energ Star ratings

    *

    *****