Healthcare-Infection Control Spaces HVAC Systems...
Transcript of Healthcare-Infection Control Spaces HVAC Systems...
Engsysco
Wei Sun, P.E.
ASHRAE Distinguished Lecturer
Society Technology Transfer Committee Chair (12-13)
“Clean Spaces” Technical Committee (TC9.11) Chair (07-10)
“Healthcare Facilities” Technical Committee (TC9.6) Member
“Laboratory Systems” Technical Committee (TC9.10) Member
IEST (Institute of Environmental Sciences and Technology) Society President
ISO 14644 Cleanroom Standards USA Delegate
Engsysco, Inc. President
Ann Arbor, Michigan, USA
Web: www.engsysco.com Email: [email protected]
HVAC Systems Design for
Airborne Infection Control Spaces
in Health Care Facilities Belgrade, Serbia April 28, 2017
2015 ASHRAE - Handbook Chapter 8
2013 ASHRAE - “Hospital and Clinics
HVAC Design Manual”
2010 FGI/AIA - “Guidelines for Design
and Construction of Hospital and Health
Care Facilities”
ASHRAE/ASHE Standard 170-2013 -
Ventilation of Health Care Facilities (with
addendums)
2006 CDC - “Infection Control
Guidelines”
2003 CDC - “Guidelines for
Environmental Infection Control in
Health-Care Facilities”
US Healthcare Facilities
Design Guidelines and Standards
USP <797> Guidebook to Pharmaceutical Compounding - Sterile Preparations (2008)
Unified Facilities Criteria (UFC) - Design: Medical Military Facilities (2009)
Unified Facilities Criteria (UFC) – Design Build: Technical Requirements (2005)
VA HVAC Design Manual (2008)
NIH Design Requirements Manual for Biomedical Laboratories and Animal Research Facilities (2008)
WHO Interim Guidelines - Infection Prevention and Control of Pandemic - and Epidemic-Prone Respiratory Diseases in Health Care
US Healthcare Facilities
Design Guidelines and Standards
Aerobiological Engineering Handbook - Airborne Disease Control Technologies
2012 NFPA Standard 99 - Standard for Health Care Facilities
2012 NFPA Handbook - Health Care Facilities Code Handbook
2012 IEEE, National Electrical Safety Code (NESC)
US Healthcare Facilities
Design Guidelines and Standards
Architectural Design:
2012 International Building Code
Engineering Design:
2012 International Mechanical Code
2012 International Plumbing Code
2012 International Fire Code
2012 International Energy Conservation Code
US General Building Codes
Source controls
• Patients with Tuberculosis, Chicken pox, Measles, Smallpox, SARS, Monkey pox, antibiotic resistant microbes..
• Cough etiquette and respiratory hygiene
Administrative controls
• Construction of infection control infrastructure
• Early detection, isolation, treatment and report
Personal protective equipment – primary barrier
Engineering controls – secondary barrier
• Patient placement (room layout, configuration)
• Space environmental control
Airborne Infection Risk Management An Critical Portion of Infection Control Risk Assessment (ICRA)
Operating Room (Operation Theatre)
Airborne Infection Isolation Room (AII)
Protective Environment (PE)
Critical and Intensive Care Unit
Health-Care Settings with Special Environmental
Controls for Airborne Infections (US CDC)
Function Space Standard
Basis
Pressure
Relationship
to Adjacent
Areas
Min. OA
ACH
Min.
Total
ACH
All Air
Exhausted
Directly to
Outside
Air
Recirculated
Within Room
Units (Ex. w/
HEPA)
Relative
Humidity
%
Design
Temp.
°F
Operating Room
(Re-circulating air
system)
AIA Positive 5 25 — No 45-55 62-80
ASHRAE(08) Positive 4 20 N/R No 30-60 68-75
CDC Positive 3 15 N/R Yes 30-60 68-75
Airborne infection
Isolation Room
AIA Negative 2 12 Yes No — 75
ASHRAE(08) Negative 2 12 Yes No — 70-75
CDC Negative 2 12 Yes No — 75
Isolation
Anteroom
AIA Positive or Negative
2 10 Yes No — —
ASHRAE(08) Positive or Negative
2 10 Yes No — —
CDC Positive or Negative
2 10 Yes No — —
Protective
Environment
Room
AIA Positive 2 12 — No — 75
ASHRAE(08) Positive 2 12 — No — 70-75
CDC Positive 2 12 — No — 75
Critical and
Intensive Care
AIA N/A 2 6 — No 30-60 70-75
ASHRAE(08) Positive 2 6 N/R No 30-60 70-75
CDC N/A 2 6 — No 30-60 70-75
(06)
(03)
(06)
(03)
(06)
(03)
(06)
(03)
(06)
(03)
20
Ventilation Requirements (USA)
Ventilation Requirements (ASHRAE 170 – 2013 Std)
Constant volume air handling systems are common in operating rooms, variable systems are permitted for use “only if” they continue to provide a positive room pressure (normally 0.01-0.03 in. wg or 2.5-8 Pa differential) with respect to the corridors and adjacent areas and the required ACHs are maintained.
HEPA-filtered (99.97%) laminar airflow and UVGI (Ultraviolet Germicidal Irradiation) as additional measures could reduce SSI (Surgical-Site Infection) risk for certain operations. Laminar airflow is designed to move clean air over the aseptic operating field at a uniform velocity (0.3–0.5 m/s) (60-100 fpm), sweeping away particles in its path, and recirculated air is passed through a HEPA filter.
Operating Room (1) (Example - CDC Based)
Operating Room (2)
Operating Room (3)
(ASHRAE 170-2013)
Additional diffusers may be located outside of the Primary Supply Diffuser Array (Zone) if needed to achieve required environmental conditions or air change rates, but no more than 30% of the Primary Supply Diffuser Array.
New definition of Procedure Room is equivalent to Class A ORs previously.
New definition of Operating Room is equivalent to Class B and C ORs previously.
Enlarged Clean Zone Area (3.2m x 3.2m)
Higher ACH
Foldable Air Curtain
Floor Mounted System
Airflow Effectiveness Improvement in OR
Use of negative pressure rooms with control of air flow direction (normally - 0.01 to -0.03 in. wg or -2.5 to -8 Pa differential), airflow volume differential at a minimum of 125 CFM (60 L/s) exhaust versus supply.
Seal room below 0.5 ft2 (465 cm2) of air leakage (called Effective Leakage Area under 4 Pa pressure differential test)
Filtered (90%) supply air to the room. Air from negative pressure rooms and treatment rooms is to be HEPA-filtered (99.97%) and exhausted directly to the outside. Recirculation is not allowed. Isolation rooms can be constructed ideally with an anteroom. UVGI fixtures can be placed in upper room or inside the ducts as an additional measure.
Personal protective equipment such as respirators (NIOSH type N95 or powered purifier) for healthcare workers prior to entering isolation rooms.
Airborne Infection Isolation Room (1) (Example - CDC Based)
Cascading
Sink
Bubble
Airborne Infection Isolation Room (2) (Example - CDC Based)
These rooms are to be designed for high-risk, immuno-compromised patients (BMT, organ transplant, leukemia, burn, late-stage HIV…) to minimize fungal spore counts (measured in CFU) in air.
Ideally, incoming air by HEPA filters, supply air on one side of the room across the patient, and exhaust out through the opposite side of the room.
Positive room air pressure of 2.5 Pa (0.01" w.g.) relative to the corridor, airflow volume differential at a minimum of 125 CFM (60L/s) supply versus exhaust.
Seal room below 0.5 ft2 (465 cm2) of air leakage.
Protective Environments (1) (Example - CDC Based)
Protective Environments (2)
Based on the patient type and critical-care suite configuration, positive, negative or neutral room pressure (normally from -0.01 to 0.01 in. wg or -2.5 to 2.5 Pa differential) with respect to the corridors and adjacent areas.
Filtered (90%) supply airflow, and recirculated air is allowed.
Critical and Intensive Care Room (1) (Example - CDC Based)
Critical and Intensive Care Room (2)
Hospital Room Airflow, Pressure, Flow Direction, Temperature and Humidity Requirements
(For Hospitals and Outpatient Facilities, FGI) (1)
Hospital Room Airflow, Pressure, Flow Direction, Temperature and Humidity Requirements
(For Hospitals and Outpatient Facilities, FGI) (2)
Example Design Criteria – Operating Room
Complex (multi-functional) AHU System (Discharge at 55°F year-around)
• Exhaust only
• Exhaust w./ heat pipe
• Exhaust w./ enthalpy wheel
• Dual Return paths
• 100% OA for purge
Use only with
psychrometric
analysis!!!
AHU Flow Diagram (With Possible Options)
Renewable Energy
Geothermal
Solar Panels
Wind Turbine
Energy Recovery
Cogeneration - Not only for Backup Power, but as Main Power.
Use Water-cooled Compressors (Large) to Recover Waste Heat
Energy Recovery - Heat Pipe, Thermal Wheel, Run-around Coils
Building
Building Envelope - Increase Air Tightness, Reduce Leakage through Windows and Walls, Add Vestibules
Use Vertical Fenestration and Overhang in West, East & South Windows
Reduce or Eliminate of West-side Windows
Commissioning and Retro-commissioning – User friendly Software
ASHRAE Developing Cost Effective Solutions
Toward Low Energy Healthcare Buildings
Lighting & Power
Sensor Controlled Natural Day Lighting
Building and Space (Section/zone) Metering through BMS
Reduce Plug Load: Use BMS Clock Control to Deactivate Non-Critical Office Equipment during Night/Weekends, Can Be Overridden with Light Switch.
Reduce Lighting Waste by Occupancy Sensor
LED Lights
Water
Collect Rain Water with Filtration for Irrigation and Underground Sprinkler System
Cooling Condensate Collection (AHU over 5 Ton) for Cooling Tower Make-Up Water
ASHRAE Developing Cost Effective Solutions
Toward Low Energy Healthcare Buildings
HVAC
Logic Controlled Ventilation – Use Combination of Natural and Hybrid
Ventilation Automatically
CO2 Demand Controlled Ventilation, Air-side Economizers (Varies with
Climate Zones)
Enhanced Particle and Microbial Filtration Technology to Lower OA
Intake Quantify
OA Intake Shut down – Chemical and Multi-gas Sensing to Close OA
Damper when Chemical Concentrations in OA Above Allowable Limits
Decoupled Ventilation (DOAS), Improved Dehumidification for Latent
Removal
AHU Discharge Temperature - Dynamic Reset of VAV System
ASHRAE Developing Cost Effective Solutions
Toward Low Energy Healthcare Buildings
Sample View of US Hospitals 1
Sample View of US Hospitals 2
Rooftop Chillers
Direct versus Indirect Lighting
Exterior Lighting
Public Waiting Areas with Window Glazing
Sample of Energy Saving Approaches
Solar Panels on Roof
Logic Controlled Sun Shade
Use Exterior Lighting
Sample of Energy Saving Approaches