Power and productivityfor a better worldTM
Medium voltage products
HD4/REMedium voltage SF6 gas-insulated circuit-breaker for secondary distribution
2
• Lightandcompactmechanicallyandelectricallyoptimizedcircuit-breaker
• Upto24kVratedvoltage,upto 630Aratedthermalcurrentupto 16kAratedbreakingcapacity
• Electricarcextinctionwithoutcurrentchopping
•Norestrikingafterinterruptionthankstorapidre-establishmentofthedielectricpropertiesoftheextinctionmedium
HD4/REMedium voltage SF6 gas-insulated circuit-breaker for secondary distribution
•Permanentlysealedpoles•Stored-energyoperatingmechanismabletoperformacompleteO-C-Ocyclewithoutreloadingthesprings
•Maintenance-free•ApplicationofaREF601solid-stateprotectionrelay(IECversion)withcurrentsensors(onrequest)
•SF6gaspressuremonitoringdevice(availableonrequest)
3
H
LP
1
11
2
3
7
6
8
9
10
8
5
4
12
13
Technical specifications
Circuit-breaker HD4/RE 12 HD4/RE 17 HD4/RE 24
Rated and insulation voltage [kV] 12 17 24
Withstandvoltageat50Hz [kV] 28 38 50
Impulsewithstandvoltage [kV] 75 95 125
Ratedfrequency [Hz] 50-60 50-60 50-60
Ratedthermalcurrent(40°C) [A] 630 630 630
Ratedbreakingcapacity/Admissible short-timewithstandcurrent(1s)
[kA] 12.5 12.5 12.5
16 16 16
Makingcapacity [kA] 31.5 31.5 31.5
40 40 40
Sequenceofoperations [O-3m-CO-3m-CO]
Openingtime [ms] 77 77 77
Arcing time [ms] 10-15 10-15 10-15
Total break-time [ms] 87-92 87-92 87-92
Closingtime [ms] 50 50 50
Overalldimensions(fixedversionwithout currentsensors)
H[mm] 670 670 670
L[mm] 282 282 282
D[mm] 1029 1029 1029
PhasedistanceI[mm] 230 230 230
Weightoffixedversion(1) [kg] 74 74 74
Absol.pressureofSF6(nomin.dutyvalue) [kPa] 380 380 380
(1) Increasetheindicatedweightby20kgforcircuit-breakerswithREF601deviceand3currentsensors(15kgonlywith2currentsensors)
1 REF601protectionrelay(onrequest)2 Manualloadingoftheclosingsprings3 Closingpushbutton4 Openingpushbutton5 Indicatorforclosingspringsloaded(yellow)anddischarged(white)6 Operationcounter7 Circuit-breakeropen/closedindicator8 Medium voltage terminals9 Currentsensor(forREF601release-ifapplicable)10 Circuit-breakerpole11 Key lock12 SF6gaspressurestatuslockingandsignallingdevice(appliedonrequest
onlytocircuit-breakerswithpressureswitch)13 Setofwheels(onrequest)
4
AccessoriesincludedinthestandardequipmentforHD4/REKIT 1 Open/closed signalling contacts (-BGB1)
Thestandardequipmentincludesasetoffiveauxiliarycontacts.Otheradditionalsetsofauxiliarycontactsareavailableonrequest,withasurcharge.Theirnumberdependsontheversionofthedevice.Seesummaryofthetotalquantitiesthatcanbesupplied.
Electrical characteristics
InsulationvoltagetostandardVDE0110,GroupC
660VAC
800VDC
Rated voltage 24V…660V
TestVoltage 2kVfor1min
Maximumratedcurrent 10A-50/60Hz
Breakingcapacity Class1(IEC62271-1)
Numberofcontacts 6/12
Contacttravel 90°
Actuating force 0.6Nm
Resistor <6.5mΩ
Storagetemperature -30°C...+120°C
Operatingtemperature -20°C...+70°C
(-30°acc.toUL37.09)
Contacttemperaturerise 10 K
Mechanicallife 30,000mechanicaloperations
Protectionclass IP20
Cablesection 1 mm2
Additional requirements (IEC 60947)
Rated voltage Un Breaking capacity (10,000 breaks)
220VAC cosϕ = 0.70 20 A
220VAC cosϕ=0.45 10 A
24VDC 1 ms 12 A
15ms 9 A
50ms 6 A
60VDC 1 ms 10 A
15ms 6 A
50ms 4.6 A
110VDC 1 ms 7 A
15ms 4.5A
50ms 3.5A
220VDC 1 ms 2 A
15ms 1.7 A
50ms 1.5A
250VDC 1 ms 2 A
15ms 1.4 A
50ms 1.2 A
Summary of the total quantity of auxiliary contacts available(*)
Standard equipment On request
HD4/RE 6 10
HD4/RE-SEC 5 9
(*) eachshuntopeningreleaserequiresanormallyopencontact(withcircuit-breakeropen)inordertoself-de-energize.Thusthequantitiesgivenabovemustbereducedbyoneunitpershuntopeningreleaseordered
HD4/REMedium voltage SF6 gas-insulated circuit-breaker for secondary distribution
5
KIT 2Shunt opening release (-MBO1)
Allowsthedevicetobeopenedbyremotecontrol.Thereleaseoperateswithbothdirectandalternatingcurrent.Thisreleaseissuitableforbothinstantaneousandpermanentduty.However,anauxiliarycontactshutsoffthepowersuppliedtotheshuntopeningreleaseafterthecircuit-breakerhasbeenopened.Toguaranteethereleaseaction,thecurrentimpulsemustlastat least 100 ms.FunctionalityandcontinuitycanbemonitoredwiththeSTUdevice(accessory9,availableonrequest),orwithdevicesthatintegrateCCCorTCS.Thepowersupplyvoltageoftheshuntopeningreleasemustmatchthatoftheshuntclosingrelease(andofthelamps,ifsupplied)whenthecircuit-breakerlockingdeviceforinsufficientpressureisrequired.
KIT 3 Open position key lock
Thislockpreventstheclosingoperation(localandremote)whenthekeyhasbeenremoved.Toactivatethelock,openthecircuit-breaker,keeptheopeningpushbuttondepressed,turnandremovethekey.Specifythetypeoflockrequired:3A Lockwithdifferentkeys3B Lockwiththesamekeys.
Characteristics
Un LV:24...30VDC;48...60VDC/AC50-60Hz
Un HV:110...132-220...250VDC/AC50-60Hz
Operatinglimits 65…120%Un
Inrushpower(Ps) 70...100 W
Inrushtime 150ms
Continuouspowerconsumption(Pc)
1.5W
Openingtime 77 ms
Insulationvoltage 2000V50Hz(for1min)
6
HD4/REMedium voltage SF6 gas-insulated circuit-breaker for secondary distribution
OptionalaccessoriesfortheHD4/REseries
Automaticallyloadstheclosingspringofthecircuit-breaker’soperatingmechanism.Thegearmotorimmediatelyreloadstheclosingspringafterthecircuit-breakerhasclosed.Theclosingspringcanstillbeloadedinthemanualmode(usingtherelativeleverbuiltintotheoperatingmechanism)inapowerfailureorduringmaintenancework.
NOTE. The24VD.C.gearmotorisalwayssuppliedwiththeprotectingthermalmagneticcircuit-breaker(accessory15).
2. Shunt closing release (-MBC)
Theshuntclosingrelease(-MBC)allowsthedevicetobeclosedbyremotecontrol.Thereleasecanfunctionwithbothdirectandalternatingcurrentandisfitforbothinstantaneousandcontinuousservice.Whenpermanentlyenergized,thereleaseprovidestheelectricanti-pumpingfunction.Inthecaseofinstantaneousservice,thecurrentimpulsemustlastat least 100 ms.
1. Spring-loading gearmotor (-MAS)
Characteristics
Un 24...30-48...60-110...130-220...250V–
Un 100...130-220...250V~50/60Hz
Operatinglimits 85…110%Un
Inrushpower(Ps) DC=600W;AC=600VA
Ratedpower(Pn) DC=200W;AC=200VA
Inrushtime 0.2 s
Loadingtime 6-7 s
Insulationvoltage 2000V50Hz(for1min)
7
3. Additional shunt opening release (-MBO2)
SimilarlytoshuntopeningreleaseMBO1,thisallowstheopeningcommandoftheapparatustobetransmittedintheremotemodeandcanbeenergizedbyacircuitthatiscompletelyseparatefromreleaseMBO1.Thereleaseoperateswithbothdirectandalternatingcurrent.Thisreleaseissuitableforbothinstantaneousandpermanentduty.However,anauxiliarycontactshutsoffthepowersuppliedtotheshuntopeningreleaseafterthecircuit-breakerhasbeenopened.Toguaranteethereleaseaction,thecurrentimpulsemustlastatleast100ms.FunctionalityandcontinuitycanbemonitoredwiththeSTUdevice(accessory9,availableonrequest),orwithdevicesthatintegrateCCCorTCS.
4. Under-voltage release (-MBU)
Theundervoltagereleaseopensthecircuit-breakerwhenthereisasensitivereductionorlackofthevoltagethatpowersit.Itcanbeusedforremoterelease(bymeansofapushbuttonofthenormallyclosedtype),forlockingonclosingorformonitoringthevoltageinauxiliarycircuits.Thecircuit-breakercanonlyclosewhenthereleaseisenergized(theclosinglockisobtainedmechanically).Thereleaseoperateswithbothdirectandalternatecurrent.ThisaccessoryissuppliedaspartofthestandardequipmentwhentheCEI0-16versionofprotectiondeviceREF601isordered(withthesamepowersupplyvoltageastheonerequestedforREF601).
Characteristics
Un LV:24...30VDC;48...60VDC/AC50-60Hz
Un HV:110...132-220...250VDC/AC50-60Hz
Operatinglimits 65…120%Un
Inrushpower(Ps) 70...100 W
Inrushtime 150ms
Continuouspowerconsumption(Pc)
1.5W
Openingtime 77 ms
Insulationvoltage 2000V50Hz(for1min)
Characteristics
Un LV:24...30VDC;48...60VDC/AC50-60Hz
Un HV:110...132-220...250VDC/AC50-60Hz
Operatinglimits –circuit-breakeropening:35-70%Un
–circuit-breakerclosing:85-110%Un
Inrushpower(Ps) 150W
Inrushtime 150ms
Continuouspowerconsumption(Pc)
3 W
Openingtime 60...80 ms
Insulationvoltage 2000V50Hz(for1min)
8
HD4/REMedium voltage SF6 gas-insulated circuit-breaker for secondary distribution
5. Electrical signalling of undervoltage voltage trip (-BGB5)
Theundervoltagereleasecanbeequippedwithacontact(normallyclosedoropen,asrequired)thatsignalswhentheundervoltagereleaseisenergizedorde-energized,soastosignalthestatusofthereleaseintheremotemode.Specifythetypeofsignallingrequired:5A Undervoltagereleaseenergizedsignal5B Undervoltagereleasede-energizedsignal.
6. Opening solenoid (-MO3)
Openingsolenoid-MO3isademagnetizingreleasethatissuppliedaspartofthestandardequipmentwhenthePR521seriesovercurrentprotectiondeviceisrequired.Thedemagnetizingreleaseisanaccessoryandisnotanalternativetoreleases-MO1and-MO2.UseofthisreleasewithundercurrentprotectiondevicesdifferingfromthePR521seriesmustbecheckedoutbeforehand.ThisopeningsolenoidcannotbeusedwiththeREF601seriesprotectiondevice.
9
Thisisamechanicaldevicethatallowstheoperationoftheundervoltage release to be de-activated.Thisallowsthecircuit-breakertobeclosedevenwhentheundervoltagereleaseisnotenergized.Theundervoltagereleaseisactivated/de-activatedbymeansofadedicatedtwo-positionselectorswitchinstalledonthefrontofthecircuit-breakeroperatingmechanism.Theunder-voltageoverrideisalwaysequippedwithanelectricaldeviceforsignallingwhentheunder-voltagereleaseisde-activated(-BGB6).ThemechanicalundervoltageoverridecannotbesuppliedwhentheCEI0-16versionREF601protectiondeviceisrequired.The“Temporarymechanicaloverride”versionisavailableonrequest.Thisallowstheactionofthede-energizedunder-voltagereleasetoremainde-activatedforaslongasthecontrolknobonthefrontofthecircuit-breaker’soperatingmechanismremainsdepressedinthemanualmode.ThetemporarymechanicaloverridecannotbesuppliedwhentheCEI0-16versionREF601protectiondeviceisrequired.
7. Mechanical override of the undervoltage release 8. Closing spring loaded and discharged signalling contacts (-BGS2)
Twopairsofcontacts(oneopenandtheotherclosed)allowthestatusofthecircuit-breaker’sclosingspringtobesignalledintheremotemode.Onlyonecontactcanbewired,thusspringloadedorspringdischargedcanbesignalledintheremotemode.
10
10. Device for monitoring the functionality and continuity of the shunt opening/closing releases (STU Shunt Test Unit)
The STU device can be used in conjunction with the shunt opening release (-MBO1; -MBO2) or shunt closing release (-MBC) for functionality and continuity tests (one device for each release to be tested). The testing/monitoring Shunt Test Unit can be used to test the continuity of releases with rated operating voltage between 24 V and 250 V (AC and DC), as well as the functionality of the release’s electronic circuit. The continuity test is performed in cycles with a 20-second interval between one test and the next. The unit has optical LED indicators on the front. The following information is given:– POWER ON: power is being supplied– -MO/-MC TESTING: the test is being performed– TEST FAILED: this signal is given after a test has failed or
when there is no auxiliary power being supplied– ALARM: this signal is given after three consecutive tests
have failed.
HD4/REMedium voltage SF6 gas-insulated circuit-breaker for secondary distribution
9A
9B
9C
9. Padlock device for the opening and closing pushbuttons
Allows the opening and closing pushbuttons to be locked with up to three 4-mm diameter padlocks (not supplied). This locking system is available in three versions:9A Locking of both pushbuttons without distinction9B Separate locking of the opening and/or closing
pushbuttons9C Locking for HD4/RE-Sec circuit-breakers without
distinction
NOTE. Lock 9A prevents closing by remote control; lock 9B does not prevent closing by remote control.
11
Circuit-breakerintheHD4/REfamilycanalsobesuppliedwiththefollowingaccessories,alreadyavailablefortheHD4/Rfamily:– Gearmotorthermalmagneticprotectioncircuit-breaker– Electronictime-lagdevice– Externaltoroidaltransformer– REF601protectiondevice(IECversion)– CurrentsensorsforprotectiondeviceREF601– KECAcurrentsensorsforrelayREF601– Setofwheels– Socketandplug– Two-levelpressureswitch– Circuit-breakerlockingdevice(with/withoutlamps)for
insufficient SF6gaspressure– Connectionterminals
Power and productivityfor a better worldTM
Contacts
1VCP000575–Rev.-,en–HD4/REBrochure–2015.06(mt)ABB S.p.A.
Power Products DivisionUnità Operativa Sace-MVViaFriuli,4I-24044DalmineTel:+390356952111Fax:+390356952874E-mail:[email protected]
www.abb.it
The data and illustrations are not binding.We reservetherighttomakechangeswithoutnotice inthecourseoftechnicaldevelopmentoftheproduct.