Hazardous Area Classification Innoil & Gas Industry

34
Hazardous Area Classification in Oil & Gas Industry A Fire Prevention Tool SFPE ENGINEERING TECHNOLOGY CONFERENCE Oct 4, 2010 New Orleans, LA 1

Transcript of Hazardous Area Classification Innoil & Gas Industry

Page 1: Hazardous Area Classification Innoil & Gas Industry

Hazardous Area Classification in Oil & Gas Industry

A Fire Prevention Tool

SFPE ENGINEERING TECHNOLOGY CONFERENCE

Oct 4, 2010

New Orleans, LA

1

Page 2: Hazardous Area Classification Innoil & Gas Industry

Overview

2

Oil and gas plants handle flammable materials

Page 3: Hazardous Area Classification Innoil & Gas Industry

Flammable Range

Air

Flammable

Too lean to burnToo rich to burn

100%

0%LFL UFL

LFL Lower Flammable Limit

UFL Upper Flammable Limit

3

Page 4: Hazardous Area Classification Innoil & Gas Industry

Flammable Range of Few Materials

Material LFL (Vol %) UFL (Vol %)

Methane 5 15

Ethane 3 15.5

Propane 2 9.5

Butane 1.5 8.5

Hydrogen 4 75.6

4

Page 5: Hazardous Area Classification Innoil & Gas Industry

Flammable Range - Methane

0%Lean – will not burn

Flammable

Too rich – will not burn

UFL – 15%

LFL – 5%

100%

5

Page 6: Hazardous Area Classification Innoil & Gas Industry

Source of Release

• A point from which a flammable gas, vapor or liquid may be released into atmosphere.

ex. flanges, instrument connections, pump seals, etc

6

Page 7: Hazardous Area Classification Innoil & Gas Industry

Sources of Release

Instrument Connection

Flange

7

Page 8: Hazardous Area Classification Innoil & Gas Industry

Fire Triangle

Simultaneous occurrence of all three sources causes fire.

Cutting off any one, extinguishes fire. 8

Page 9: Hazardous Area Classification Innoil & Gas Industry

Ignition Source

Electrical Apparatus

9

Page 10: Hazardous Area Classification Innoil & Gas Industry

Aim of Area Classification

• To avoid ignition of releases that may occur from time to time

• The approach is to reduce to an acceptable level the probability of coincidence of a flammable atmosphere and an electrical or other source of ignition.

10

Page 11: Hazardous Area Classification Innoil & Gas Industry

Hazardous Area

• A three dimensional space in which a flammable atmosphere may be expected to be present at such frequencies as to require special precaution for the design and construction of equipment, and the control of potential ignition sources.

Leak Source

11

Page 12: Hazardous Area Classification Innoil & Gas Industry

Hazardous Area

12

Hazardous Area

Page 13: Hazardous Area Classification Innoil & Gas Industry

Extent of Hazardous Area

• Direct Example Approachlimited to common facilities

• Point Source Approachrelease rates are dependent on process conditions

• Risk-based Approachan option methodology which may reduce the hazardous area determined by the point source approach

13

Page 14: Hazardous Area Classification Innoil & Gas Industry

Grade of Release

• Continuous: A release that is continuous or nearly so.

• Primary: A release that is likely to occur periodically or occasionally in normal operation. (Vents, Sample points, etc)

• Secondary: A release that is unlikely to occur in normal operation and, in any event, will do so only infrequently and for short periods. (Flanges, Instrument connections, etc)

14

Page 15: Hazardous Area Classification Innoil & Gas Industry

Subdivision of Hazardous Area

• Zone 0: flammable atmosphere is continuously present or present for long periods.

• Zone 1: flammable atmosphere is likely to occur in normal operation.

• Zone 2: flammable atmosphere is not likely to occur in normal operation and, if it occurs, will exist only for short period.

15

Page 16: Hazardous Area Classification Innoil & Gas Industry

Zone and Division

Continuous Release

Primary Release

Secondary Release

Codes and Standards

Zone 0 Zone 1 Zone 2IEC 60079, IP 15, API 505, NFPA 497

Division 1 Division 2API 500, NEC Article 500, NFPA 497

16

Page 17: Hazardous Area Classification Innoil & Gas Industry

Grade of Release and Zone (Division)

Under unrestricted ‘open air’ conditions:

• Continuous grade normally leads to Zone 0 (Division 1)

• Primary grade normally leads to Zone 1 (Division 1)

• Secondary grade normally leads to Zone 2 (Division 2)

17

Page 18: Hazardous Area Classification Innoil & Gas Industry

Effect of Ventilation

• The term ‘grade of release’ and ‘zone’ are not synonymous.

• Poor ventilation may result in a more stringent zone while, with high ventilation provision, the converse will be true.

18

Page 19: Hazardous Area Classification Innoil & Gas Industry

• Cone Roof Storage Tank

Zone Classification

Zone 1

Zone 0

Zone 2

Zone 1

19

Page 20: Hazardous Area Classification Innoil & Gas Industry

• Floating Roof Storage Tank

Zone Classification

Zone 1

Zone 2

Zone 1

20

Page 21: Hazardous Area Classification Innoil & Gas Industry

Classification of Zone (Division)

• Zone (Division) classification is based on the frequency of release.

• Each zone (division) is further classified into Groups and Temperature Class based on the properties of flammable material processed in that zone (division).

21

Page 22: Hazardous Area Classification Innoil & Gas Industry

Gas Group

Typical Gas Hazard NEC Article 500 IEC

Acetylene A IIC

Hydrogen B IIC

Ethylene C IIB

Propane D IIA

• Flammable materials are sub-divided into groups based on minimum ignition energy required for igniting them.

22

Page 23: Hazardous Area Classification Innoil & Gas Industry

Auto-ignition Temperature (AIT)

• Minimum temperature required to initiate or cause self-sustained combustion of the fluid independent of the heating.

23

Page 24: Hazardous Area Classification Innoil & Gas Industry

Temperature Class

Temperature Class Auto-ignition Temperature (o C)

T1 >450T2 >300T3 >200T4 >135T5 >100T6 >85

• Temperature Class is assigned to flammable material based on its auto-ignition temperature.

24

Page 25: Hazardous Area Classification Innoil & Gas Industry

Auto-ignition Temperature (AIT)

Material AIT (o C) Temperature Class

Methane 595 T1

Ethane 515 T1

Propane 470 T1

Butane 365 T2

Pentane 285 T3

25

Page 26: Hazardous Area Classification Innoil & Gas Industry

Area Classification

Zone 2 IIA T3

Zone 2 IIC T1

Zone 1 IIA T3

Zone 1 IIC T1

26

Page 27: Hazardous Area Classification Innoil & Gas Industry

Battery Room

• Lead acid batteries emit H2 during charging and create hazardous area

• Battery rooms are classified as Zone 1 Group IIC Temperature Class T1

27

Page 28: Hazardous Area Classification Innoil & Gas Industry

Factors to be considered:• Zone in which the equipment will be

used.• Sensitivity to ignition of the material

likely to be present, expressed as a gas group.

• Sensitivity of the material present to ignition by hot surfaces, expressed as a temperature class.

Selection of Electrical Equipment

28

Page 29: Hazardous Area Classification Innoil & Gas Industry

Selection According to Zone Classification

• Equipment suitable for Zone 0 can be used in Zones 0, 1 or 2.

• Equipment suitable for Zone 1 can be used in Zones 1 or 2.

• Equipment suitable for Zone 2 can be used only in Zone 2.

29

Page 30: Hazardous Area Classification Innoil & Gas Industry

Selection According to Gas Groups

• Grouping becomes more severe in going from IIA to IIB to IIC.

• Group IIB equipment may be used in place of Group IIA equipment.

• Group IIC equipment can be used in place of equipment for both Group IIA and IIB.

30

Page 31: Hazardous Area Classification Innoil & Gas Industry

Selection According to Temperature Class

Temperature Class Maximum Surface Temperature (o C)

T1 450T2 300T3 200T4 135T5 100T6 85

• Equipment having a lower maximum surface temperature class may be used in place of that a higher maximum surface temperature (lower T class), but not conversely.

31

Page 32: Hazardous Area Classification Innoil & Gas Industry

• Oil Immersed ProtectionHeavy current switchgear and transformers

• Pressurization or Continuous DilutionAnalyzers, control boxes, etc

• Powder-filled ProtectionElectronics, chokes, etc

• Flame-proof EnclosureMotors, lighting, junction boxes, etc

Equipment Protection

32

Page 33: Hazardous Area Classification Innoil & Gas Industry

Summary

• Identify the flammable materials.• Identify sources of release and

determine grade of release (and hence Zone 0,1, 2 or Division 1, 2).

• Determine extent of hazardous area.• Assign Gas Groups and Temperature

Class.• Select appropriate Electrical apparatus.

33

Page 34: Hazardous Area Classification Innoil & Gas Industry

Thank you

34