1 This document explains the installation procedures for EMC ® CX4 series devices in a Telco rail self-supporting rack, and describes the kits available for mounting these devices. These kits are for Telco rail self-supporting racks only. Introduction .................................................................................................... 2 CX4 series devices .................................................................................... 2 Telco rail self-supporting rack ................................................................ 3 Device placement guidelines ........................................................................ 3 Position in rack ......................................................................................... 4 Device dimensions ................................................................................... 4 Power considerations ............................................................................... 5 Installing a 2U SPS in a Telco rack ............................................................... 7 2U SPS mounting kit (SPS-TELCO-2U) .................................................. 7 Installing 2U SPS mounting trays ........................................................... 8 Installing the 2U SPS in the mounting trays........................................ 10 Installing a 4U SPE (CX4-960) in a Telco rack .......................................... 13 SPE mounting kit (SP-TELCO 4U) ........................................................ 13 Installing SPE mounting trays ............................................................... 14 Installing the SPE in the mounting trays ............................................. 15 Installing a 1U SPS in a Telco rack ............................................................. 19 1U SPS mounting kit ............................................................................... 19 Installing 1U SPS mounting trays ......................................................... 20 Installing the 1U SPS in the mounting trays........................................ 21 Installing a 2U SPE in a Telco rack............................................................. 25 2U SPE (SP-TELCO-2U) mounting kit ................................................ 25 Installing 2U SPE mounting trays ........................................................ 26 Installing the 2U SPE in the mounting trays ...................................... 28 Installing a DAE in a Telco rack ................................................................. 31 DAE mounting kit .................................................................................. 31 Installing 3U DAE mounting trays ...................................................... 32 Installing the DAE enclosure ................................................................ 35 EMC ® CLARiiON ® CX4 Series Enclosures Hardware Installation Guide for Telco Racks P/N 300-007-546 REV A01 February 9, 2009

Transcript of Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays...

Page 1: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

1

This document explains the installation procedures for EMC® CX4 series devices in a Telco rail self-supporting rack, and describes the kits available for mounting these devices. These kits are for Telco rail self-supporting racks only.

Introduction .................................................................................................... 2• CX4 series devices .................................................................................... 2• Telco rail self-supporting rack ................................................................ 3Device placement guidelines........................................................................ 3• Position in rack ......................................................................................... 4• Device dimensions ................................................................................... 4• Power considerations............................................................................... 5Installing a 2U SPS in a Telco rack ............................................................... 7• 2U SPS mounting kit (SPS-TELCO-2U).................................................. 7• Installing 2U SPS mounting trays ........................................................... 8• Installing the 2U SPS in the mounting trays........................................ 10Installing a 4U SPE (CX4-960) in a Telco rack .......................................... 13• SPE mounting kit (SP-TELCO 4U)........................................................ 13• Installing SPE mounting trays ............................................................... 14• Installing the SPE in the mounting trays ............................................. 15Installing a 1U SPS in a Telco rack ............................................................. 19• 1U SPS mounting kit ............................................................................... 19• Installing 1U SPS mounting trays ......................................................... 20• Installing the 1U SPS in the mounting trays........................................ 21Installing a 2U SPE in a Telco rack............................................................. 25• 2U SPE (SP-TELCO-2U) mounting kit ................................................ 25• Installing 2U SPE mounting trays........................................................ 26• Installing the 2U SPE in the mounting trays ...................................... 28Installing a DAE in a Telco rack ................................................................. 31• DAE mounting kit .................................................................................. 31• Installing 3U DAE mounting trays ...................................................... 32• Installing the DAE enclosure ................................................................ 35

EMC® CLARiiON®

CX4 Series Enclosures

Hardware Installation Guide forTelco Racks

P/N 300-007-546REV A01

February 9, 2009

Page 2: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

2 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Introduction

IntroductionThis section lists the EMC CX4 series devices currently supported in Telco rail self-supporting racks (Telco racks) and provides an illustration of a typical rack.

CX4 series devicesEMC offers Telco rack mounting kits for the following CX4 series devices.

Device Mounting kit Kit part number

CX4- 960 SPE (storage processor enclosure) SP-TELCO-4U 100-561-374

CX4-120/CX4-240/CX4-480 SPE SPE-TELCO-2U 100-562-702

DAE (2/4-gigabit Ultrapoint™ disk-array enclosure) FRAME-T-PDAE 100-561-511

SPS (standby power supply -- AC-powered CX4-960) SPS-TELCO-2U 100-561-370

SPS (AC-powered CX4-120/CX4-240/CX4-480) SPST-2GB 100-561-284

Page 3: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

3

Device placement guidelines

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Telco rail self-supporting rackFigure 1 shows a typical Telco rack built to NEMA specifications for 19" devices.

Figure 1 Telco rail self-supporting rack

Device placement guidelinesBefore attaching the mounting trays to the Telco rack, you must decide where to put them. Where you install the devices depends on the kinds of devices you will install.

Flange edge toflange edge:450.85 mm(17.75 inches)

Mounting holeto mounting hole:465.074 mm(18.31 inches)

76.2 mm to203.2 mm(3 inchesto 8 inches)

CL3658

Page 4: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

4 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Device placement guidelines

Position in rack Devices with internal cooling fans that move air from front to back (or vice versa) and not from beneath or above have no special cooling requirements that direct placement in the rack. All of the storage systems and enclosures mentioned in this document have fans that move air from front to back.

Requirements are as follows:

◆ DAE enclosures should be installed above the SPE to facilitate cable routing in the rear of the Telco rack.

◆ SPS trays (AC systems) should be installed below the storage processor enclosure.

For example, arrange a typical SPE and DAE configuration as shown in Figure 2.

Figure 2 CX4 series enclosure placement in a Telco rack (generic SPE)

Device dimensionsDimensions and weights for CX4 series system components are listed in the Technical Specifications and Operating Limits document for each system, available in the Technical Documentation and Advisories section of the EMC Powerlink website: http://Powerlink.EMC.com.

CL4272

SPESPS

DAE

Page 5: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

5

Device placement guidelines

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Power considerations

Power distribution must support the number of outlets required for the device (2 per enclosure) and the device power rating. Power specifications for CX4 series system components are listed in the Technical Specifications and Operating Limits document for each system, available in the Technical Documentation and Advisories section of the EMC Powerlink website: http://Powerlink.EMC.com.

Note: System specifications and guidelines specific to CX4 series systems with DC-48 V DC power are listed in the EMC CLARiiON DC Powered CX4 Series Enclosures Installation and Operation Guide (300-007-920), also available on the Powerlink website.

For high availability, a CX4 series system requires at least two discrete site power circuits. Each SPS unit (AC systems) should connect to a separate power distribution unit and power source; power supplies in any component should not share a power source.

◆ AC power cords for the SPE and first DAE connect to SPS output AC receptacles.

◆ DC systems do not use an SPS.

Figure 3 shows a typical AC power connection configuration.

Page 6: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

6 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Device placement guidelines

Figure 3 Typical high-availability wiring configuration (AC)

4 PDUs, 2 per circuit

SPE

SPS SPS

DAE

DAE

DAE

DAE

DAE

DAE

DAE

CL4273

Page 7: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

7

Installing a 2U SPS in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 2U SPS in a Telco rackThis section describes the components of the 2U, 2.2 KW SPS mounting kit (SPS-TELCO-2U) used in AC-powered CX4-960 systems. It also describes how to install the mounting kit on the Telco rack and how to install the SPSs in the mounting kit. Note that an SPS is not required for DC-powered systems.

2U SPS mounting kit (SPS-TELCO-2U)The following table lists and describes the components in a 2U SPS mounting kit. Illustrations of these components can be found in Figure 4 on page 8. The quantity listed below is per configuration (includes two SPSs).

Component Quantity Use

Front tray 1 Attaches to the front of the Telco rack

Rear tray 1 Attaches to the rear of the Telco rack

Rear cover 1 Attaches to the rear tray and the SPSs

Left and right latch brackets 1 each Attach to front tray and SPS hold 2U bezel

M4 x 12mm screws 8 Secure the SPS units to the rear cover

M5 x 12mm screws 8 Secure the front and rear trays to the rack rails

M4 x 8mm screws 8 Secure the front plate/tray to the SPS

10-32 x .750” screws 4 Secure the rear cover to the rear tray

Page 8: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

8 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 2U SPS in a Telco rack

.

Figure 4 2U SPS mounting kit components

Installing 2U SPS mounting traysThis section describes how to install the front and rear 2.2 KW SPS trays on the Telco rack.

Note: Be sure to allow enough room to install the SPE and all the DAEs above the 2.2 KW SPS. Remember that although the SPS units are 2U high, the Telco rack mounting kit requires 3U vertical space.

For ease of installation, use a screwdriver with at least a 10" long shaft. Hand-tighten screws until all components are in place to allow for adjustment to satisfy the precise tolerances of the holes.

Installing the2.2 KW SPS front tray

1. Align the screw holes on the outer edges of the SPS front tray with the holes on the rack.

2. Secure the tray to the rack with four M5 x 12mm screws, two per side. Select the most widely spread holes on the front tray that line up with holes on the rack. See Figure 5.

CL4274

Page 9: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

9

Installing a 2U SPS in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Note: To gain access to lower holes on the mounting tray, insert the screwdriver through the access holes in the tray front.

Figure 5 Securing the 2.2 KW SPS front tray

Installing the2.2 KW SPS rear tray

1. Align the screw holes on the outer edges of the 2.2 KW SPS rear tray with the holes on the rack. Ensure that the floors of the front and rear trays are level with each other as shown in Figure 6.

2. Secure the tray to the rack with four M5 x 12mm screws, two per side. See Figure 6.

Figure 6 Positioning and securing the 2.2 KW SPS rear tray

CL4275

Page 10: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

10 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 2U SPS in a Telco rack

Installing the 2U SPS in the mounting traysFollow the steps below to install the 2U SPSs in the mounting trays.

WARNING!The enclosure is heavy and should be installed into a rack by two people. To avoid personal injury and/or damage to the equipment, do not attempt to lift and install the enclosure into a rack without a mechanical lift and/or help from another person.

L’armoire étant lourde, sa mise en place sur une rampe nécessite deux personnes. Afin de ne pas vous blesser et/ou endommager le matériel, n’essayez pas de soulever et d’installer l’armoire sur une rampe sans avoir recours à un relevage mécanique et/ou à l’aide d’une autre personne.

Das Gehäuse ist schwer und sollte nur von zwei Personen in einem Rack installiert werden. Zur Vermeidung von körperlichen Verletzungen und/oder der Beschädigung des Gerätes, bitte das Gehäuse nicht ohne die Hilfe einer zweiten Person anheben und einbauen.

Il contenitore è pesante e dev'essere installato nel rack da due persone. Per evitare danni personali e/o all’apparecchiatura, non tentare di sollevare ed installare in un rack il contenitore senza un sollevatore meccanico e/o l’aiuto di un’altra persona.

Debido a su considerable peso, la instalación del compartimento en el bastidor deben realizarla siempre dos personas. Para evitar daños personales o en el equipo, el compartimento no debe levantarse ni instalarse en el bastidor sin la ayuda de un elevador mecánico o de otra persona.

1. With two people, lift one SPS up and place it on the edge of one side of the rear tray.

Page 11: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

11

Installing a 2U SPS in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Note: Be sure to put the front of the SPS into the tray first, as you are installing it from the rear of the mounting trays.

2. Push the SPS in until it is flush with the front tray.

3. Attach the front of the SPS to the front tray using four M5 x 8mm screws, as shown in Figure 7.

Figure 7 Securing the front of the SPS

4. Repeat steps 2 through 4 for the second SPS.

5. Attach the rear cover to the back of the SPSs using eight M4 x 12mm screws, as shown in Figure 8.

Figure 8 Attaching the rear cover to the SPSs

CL4277

Page 12: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

12 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 2U SPS in a Telco rack

6. Attach each side of the rear cover to the rear tray using two 10-32 x .750” screws as shown in Figure 9.

Figure 9 Attaching the rear cover to the rear tray

7. Attach the two bezel mounting latches to the front of the SPS with M5 x 8mm screws as shown in Figure 10.

Figure 10 Attaching thefour bezel mounting latches

8. Press the front bezel over the mounting latches.

Page 13: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

13

Installing a 4U SPE (CX4-960) in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 4U SPE (CX4-960) in a Telco rackThis section describes the components of the CX4-960 4U SPE mounting kit. It also describes how to install the mounting kit on a Telco rack and how to install the SPE enclosure in the mounting kit.

SPE mounting kit (SP-TELCO 4U)The following table lists and describes the components in the 4U SPE mounting kit. Illustrations of these components can be found in Figure 11. The quantity listed below is per enclosure.

Figure 11 4U SPE mounting kit components

Component Quantity Use

Front 4U tray 1 Attaches to the front of the Telco rack

Rear 4U tray 1 Attaches to the rear of the Telco rack

Rear fastening bracket (left and right) 2 Attaches to the rear corner of the SPE enclosure and SPE rear tray

Front bezel latch bracket assemblies 2 Attach to front 4U tray; support 4U bezel

#10-32 x.5" screws 26 8 to secure the front tray to the Telco rack8 to secure the rear tray to the Telco rack6 to secure the SPE enclosure to the front tray4 to secure the rear fastening brackets to the rear corners of the SPE

Page 14: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

14 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 4U SPE (CX4-960) in a Telco rack

Installing SPE mounting traysThis section describes how to install the front and rear SPE trays on the Telco rack.

Note: Be sure to allow enough room to install the SPE and all the DAEs above the 2.2 KW SPS.

For ease of installation, use a screwdriver with at least a 10" long shaft. Hand-tighten screws until all components are in place to allow for adjustment to satisfy the precise tolerances of the holes.

Installing the SPE fronttray

1. Align the screw holes on the outer edges of the SPE front tray with the holes on the rack.

2. Secure the tray to the rack with eight #10-32 X .5" screws, four per side. Select the four most widely spread holes on the front tray that line up with holes on the rack. See Figure 12.

Figure 12 Securing the SPE front tray

Installing the SPE reartray

1. Align the screw holes on the outer edges of the SPE rear tray with the holes on the rack. Ensure that the floors of the front and rear trays are level with each other as shown in Figure 13.

Page 15: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

15

Installing a 4U SPE (CX4-960) in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

2. Secure the tray to the rack with eight #10-32 x .5" screws, four per side, the first two of which are shown in Figure 13.

Figure 13 Securing the SPE rear tray

Installing the SPE in the mounting traysFollow the steps below to install the SPE enclosure on the Telco rack.

WARNING!The enclosure is heavy and should be installed into a rack by two people. To avoid personal injury and/or damage to the equipment, do not attempt to lift and install the enclosure into a rack without a mechanical lift and/or help from another person.

L’armoire étant lourde, sa mise en place sur une rampe nécessite deux personnes. Afin de ne pas vous blesser et/ou endommager le matériel, n’essayez pas de soulever et d’installer l’armoire sur une rampe sans avoir recours à un relevage mécanique et/ou à l’aide d’une autre personne.

Das Gehäuse ist schwer und sollte nur von zwei Personen in einem Rack installiert werden. Zur Vermeidung von körperlichen

Page 16: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

16 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 4U SPE (CX4-960) in a Telco rack

Verletzungen und/oder der Beschädigung des Gerätes, bitte das Gehäuse nicht ohne die Hilfe einer zweiten Person anheben und einbauen.

Il contenitore è pesante e dev'essere installato nel rack da due persone. Per evitare danni personali e/o all’apparecchiatura, non tentare di sollevare ed installare in un rack il contenitore senza un sollevatore meccanico e/o l’aiuto di un’altra persona.

Debido a su considerable peso, la instalación del compartimento en el bastidor deben realizarla siempre dos personas. Para evitar daños personales o en el equipo, el compartimento no debe levantarse ni instalarse en el bastidor sin la ayuda de un elevador mecánico o de otra persona.

1. With two people, lift the enclosure up and place it on the edge of the front tray.

2. Push the enclosure in until the front edges of the enclosure are even with the rack.

3. Attach the front of the unit to the front tray using six screws, three per side, as shown in Figure 14.

Figure 14 Securing the front of the SPE enclosure

!

Page 17: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

17

Installing a 4U SPE (CX4-960) in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

4. At the back of the enclosure, use #10-32 X .5" screws to attach the two rear fastening brackets to the rear corners of the enclosure tray, as illustrated in Figure 15. Leave the brackets loose; you will need to adjust their position to the chassis rear.

Figure 15 Rear fastening brackets

5. Slide the rear fastening brackets into the corresponding notches in the chassis rear, then secure the brackets to the mounting tray.

6. Assemble the latch brackets. See Figure 16.

Figure 16 Assembling the latch brackets

7. Attach the latch bracket assemblies to the front trays. See Figure 17.

CL4070

Page 18: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

18 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 4U SPE (CX4-960) in a Telco rack

Figure 17 Attaching the latch bracket assemblies

8. Press the front bezel onto the latch brackets at the front of the cabinet until it snaps into place, then lock the bezel with the key.

Page 19: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

19

Installing a 1U SPS in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 1U SPS in a Telco rackThis section describes the components of the mounting kit for the 1U SPS used in AC-powered CX4-120, CX4-240, and CX4-480 series systems. It also describes how to install the mounting kit in a Telco rack and how to install the SPS enclosures in the mounting kit. Note that an SPS is not required for DC-powered systems.

1U SPS mounting kitThe following table lists and describes the components in a 1U SPS mounting kit. Illustrations of these components can be found in Figure 18. The quantity listed below is per configuration (includes two SPSs).

Figure 18 1U SPS mounting kit components

Component Quantity Use

Front tray 1 Attaches to the front of the Telco rack

Rear tray 1 Attaches to the rear of the Telco rack

Rear cover 1 Attaches to the rear tray and the SPSs

10-32 x .500 Phillips pan-head screws 12 Attach tray to rack; rear assembly to tray

4mm x 7mm Phillips pan-head screws 12 Attach SPS to front and rear of tray

Page 20: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

20 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 1U SPS in a Telco rack

Installing 1U SPS mounting traysThis section describes how to install the front and rear 1U SPS trays on the Telco rack.

Note: Be sure to allow enough room to install the SPE and all the DAEs above the 1U SPS.

For ease of installation, use a screwdriver with at least a 10" long shaft. Hand-tighten screws until all components are in place to allow for adjustment to satisfy the precise tolerances of the holes.

Installing the1U SPS front tray

1. Align the screw holes on the outer edges of the SPS front tray with the holes on the rack.

2. Secure the tray to the rack with two 10-32 x .500 screws per side. Select the most widely spread holes on the front tray that line up with the holes on the rack. See Figure 19.

.

Figure 19 Securing the 1U SPS front tray

Installing the1U SPS rear tray

1. Align the screw holes on the outer edges of the 1U SPS rear tray with the holes on the rack. Ensure that the floors of the front and rear trays are level with each other as shown in Figure 20.

Page 21: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

21

Installing a 1U SPS in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

2. Secure the tray to the rack with two 10-32 x .500 screws per side. See Figure 20.

Figure 20 Positioning and securing the 1U SPS rear tray

Installing the 1U SPS in the mounting traysFollow the steps below to install the 1U SPSs in the mounting trays.

WARNING!The enclosure is heavy and should be installed into a rack by two people. To avoid personal injury and/or damage to the equipment, do not attempt to lift and install the enclosure into a rack without a mechanical lift and/or help from another person.

L’armoire étant lourde, sa mise en place sur une rampe nécessite deux personnes. Afin de ne pas vous blesser et/ou endommager le matériel, n’essayez pas de soulever et d’installer l’armoire sur une rampe sans avoir recours à un relevage mécanique et/ou à l’aide d’une autre personne.

Das Gehäuse ist schwer und sollte nur von zwei Personen in einem Rack installiert werden. Zur Vermeidung von körperlichen Verletzungen und/oder der Beschädigung des Gerätes, bitte das Gehäuse nicht ohne die Hilfe einer zweiten Person anheben und einbauen.

Page 22: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

22 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 1U SPS in a Telco rack

Il contenitore è pesante e dev'essere installato nel rack da due persone. Per evitare danni personali e/o all’apparecchiatura, non tentare di sollevare ed installare in un rack il contenitore senza un sollevatore meccanico e/o l’aiuto di un’altra persona.

Debido a su considerable peso, la instalación del compartimento en el bastidor deben realizarla siempre dos personas. Para evitar daños personales o en el equipo, el compartimento no debe levantarse ni instalarse en el bastidor sin la ayuda de un elevador mecánico o de otra persona.

1. With two people, lift one SPS up and place it on the edge of one side of the rear tray.

Note: Be sure to put the front of the SPS into the tray first, as you are installing it from the rear of the mounting trays.

2. Push the SPS in until it is flush with the front tray.

3. Attach the front of the SPS to the front tray using two 4x7mm screws, as shown in Figure 7.

Figure 21 Securing the front of the SPS

4. Repeat steps 2 through 4 for the second SPS.

Page 23: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

23

Installing a 1U SPS in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

5. Attach the rear cover to the back of the SPSs using eight 4x7mm screws as shown in Figure 22.

Figure 22 Attaching the rear cover to the SPSs

6. Attach each side of the rear cover to the rear tray using two 10-32 x .500 sems screws as shown in Figure 23.

Figure 23 Attaching the rear cover to the rear tray

Page 24: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

24 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 1U SPS in a Telco rack

7. Attach 1U latch brackets to the front of the sps tray, and push the bezel into place.

Page 25: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

25

Installing a 2U SPE in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 2U SPE in a Telco rackThis section describes the components of the CX4-120, CX4-240, and CX4-480 series 2U SPE mounting kit. It also describes how to install the mounting kit in a Telco rack and how to install the SPE enclosure in the mounting kit.

2U SPE (SP-TELCO-2U) mounting kitThe following table lists and describes the components in the SPE mounting kit listed in the table on page 2. Illustrations of the components of the kit can be found in Figure 24. The quantity listed below is per enclosure.

Component Quantity Use

Front support tray 1 Attaches to the front of the Telco rack

Rear support tray 1 Attaches to the rear of the Telco rack

Rear fastening bracket (left and right) 2 Attaches to the rear corner of the SPE enclosure and SPE rear tray

#10-32 x .5" screw 16 4 to attach the front tray to the Telco rack4 to attach the rear tray to the Telco rack4 to attach the front tray to the SPE4 to attach the rear brackets to the rear corners of the SPE

Page 26: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

26 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 2U SPE in a Telco rack

Figure 24 2U SPE mounting kit components

Installing 2U SPE mounting traysThis section describes how to install the front and rear SPE mounting trays on the Telco rack.

Note: Be sure to allow enough room to install all the DAEs above the SPE.

For ease of installation, use a screwdriver with at least a 10" long shaft. To satisfy the precise tolerances of the holes, hand-tighten screws until all components are in place to allow for adjustment.

Installing the 2U SPEfront tray

1. Align the screw holes on the outer edges of the SPE front tray with the holes on the rack.

Rear fasteningbracket

Front tray

Rear tray

CL3672

Page 27: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

27

Installing a 2U SPE in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

2. Secure the tray to the rack with six #10-32 x .5" long screws, three per side. Select the most widely spread holes on the front tray that line up with holes on the rack. See Figure 25.

Figure 25 Securing the 2U SPE front tray

Installing the 2U SPErear tray

1. Align the screw holes on the outer edges of the rear tray with the holes on the rack. Ensure that the floors of the front and rear trays are level with each other.

2. Secure the tray to the rack with six #10-32 x .5" long screws, three per side, as shown in Figure 26.

Figure 26 Securing the 2U SPE rear tray

CL3673

Mountingscrew

(3 per side)

CL3674

Mountingscrew

(3 per side)

Page 28: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

28 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 2U SPE in a Telco rack

Installing the 2U SPE in the mounting traysFollow the steps below to install the SPE enclosure on the Telco rack.

WARNING!The enclosure is heavy and should be installed into a rack by two people. To avoid personal injury and/or damage to the equipment, do not attempt to lift and install the enclosure into a rack without a mechanical lift and/or help from another person.

L’armoire étant lourde, sa mise en place sur une rampe nécessite deux personnes. Afin de ne pas vous blesser et/ou endommager le matériel, n’essayez pas de soulever et d’installer l’armoire sur une rampe sans avoir recours à un relevage mécanique et/ou à l’aide d’une autre personne.

Das Gehäuse ist schwer und sollte nur von zwei Personen in einem Rack installiert werden. Zur Vermeidung von körperlichen Verletzungen und/oder der Beschädigung des Gerätes, bitte das Gehäuse nicht ohne die Hilfe einer zweiten Person anheben und einbauen.

Il contenitore è pesante e dev'essere installato nel rack da due persone. Per evitare danni personali e/o all’apparecchiatura, non tentare di sollevare ed installare in un rack il contenitore senza un sollevatore meccanico e/o l’aiuto di un’altra persona.

Debido a su considerable peso, la instalación del compartimento en el bastidor deben realizarla siempre dos personas. Para evitar daños personales o en el equipo, el compartimento no debe levantarse ni instalarse en el bastidor sin la ayuda de un elevador mecánico o de otra persona.

1. With two people, lift the enclosure up and place it on the edge of the front tray.

2. Push the enclosure in until the front flanges of the enclosure are flush against the tray.

Page 29: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

29

Installing a 2U SPE in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

3. Attach the front of the unit to the front tray using four #10-32 x .5" long screws, two per side, as shown in Figure 27.

Figure 27 Securing the front of the 2U SPE enclosure

4. At the back of the enclosure, attach the two rear fastening brackets to the rear corners of the enclosure tray, as illustrated in Figure 28.

Insert one #10-32 x .5" long screw through each screw hole of the rear fastening bracket and through the rear tray enclosure, but leave the screws loose enough for the bracket to slide along the tray rail. Repeat this step for the other side.

5. Slide the brackets into the aligned notches in the SPE chassis and secure them (see Figure 28)

CL3662

SPE

Mountingscrew

(2 per side)

Front

Page 30: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

30 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a 2U SPE in a Telco rack

.

Figure 28 Securing the back of the 2U SPE enclosure

CL3666

Rearfasteningbracket(1 per side)

SPE enclosure

SPE

Page 31: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

31

Installing a DAE in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a DAE in a Telco rackThis section describes the components of the DAE mounting kit. It also describes how to install the mounting kit in a Telco rack and how to install the DAE enclosure in the mounting kit.

DAE mounting kitThe following table lists and describes the components in the DAE mounting kit listed in the table on page 2. Illustrations of the components can be found in Figure 29. The quantity listed below is per enclosure.

Component Quantity Use

Front 3U support tray 1 Attaches to the front of the Telco rack

Rear 3U support tray 1 Attaches to the rear of the Telco rack

Rear fastening bracket (left and right) 2 Attaches to the rear corner of the DAE enclosure and rear tray

#10-32 x .5" screw 20 6 to secure front tray to the Telco rack6 to secure rear tray to the Telco rack4 to secure the DAE enclosure to the front tray4 to secure the rear fastening brackets to the rear corners of the DAE

Page 32: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

32 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a DAE in a Telco rack

Figure 29 DAE mounting kit components

Installing 3U DAE mounting traysThis section describes how to install the front and rear DAE trays on the Telco rack.

Install the DAE trays:

◆ directly above the SPE or

◆ directly above another DAE.

Note: For ease of installation, use a screwdriver with at least a 10" long shaft. To satisfy the precise tolerances of the holes, hand-tighten screws until all components are in place to allow for adjustment.

Installing the DAE fronttray

1. Align the screw holes on the outer edges of the DAE front tray with the holes on the rack.

2. Secure the tray to the rack with six #10-32 x .5" screws, three per side. Select the three most widely spread holes on the front tray that line up with holes on the rack. The first two screws are shown in a typical configuration in Figure 30.

Rear fastening bracket(one per side)

DAEfront tray

DAErear tray

CL3694

Page 33: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

33

Installing a DAE in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Figure 30 Securing the DAE front tray

Installing the DAE reartray

1. Align the screw holes on the outer edges of the DAE rear tray with the holes on the rack. Ensure that the floors of the front and rear trays are level with each other.

2. Secure the tray to the rack with six M5 x 12 mm screws, three per side, the first two of which are shown in Figure 31.

CL3665

Mounting screw(3 per side)

DAE3Pfront tray

Page 34: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

34 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a DAE in a Telco rack

.

Figure 31 Securing the DAE rear tray

Mounting screws(3 per side)

Rear fasteningbracket (1 perside)

CL3661

DAErear tray

Page 35: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

35

Installing a DAE in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing the DAE enclosureFollow the steps below to install a DAE enclosure on the Telco rack.

WARNING!The enclosure is heavy and should be installed into a rack by two people. To avoid personal injury and/or damage to the equipment, do not attempt to lift and install the enclosure into a rack without a mechanical lift and/or help from another person.

L’armoire étant lourde, sa mise en place sur une rampe nécessite deux personnes. Afin de ne pas vous blesser et/ou endommager le matériel, n’essayez pas de soulever et d’installer l’armoire sur une rampe sans avoir recours à un relevage mécanique et/ou à l’aide d’une autre personne.

Das Gehäuse ist schwer und sollte nur von zwei Personen in einem Rack installiert werden. Zur Vermeidung von körperlichen Verletzungen und/oder der Beschädigung des Gerätes, bitte das Gehäuse nicht ohne die Hilfe einer zweiten Person anheben und einbauen.

Il contenitore è pesante e dev'essere installato nel rack da due persone. Per evitare danni personali e/o all’apparecchiatura, non tentare di sollevare ed installare in un rack il contenitore senza un sollevatore meccanico e/o l’aiuto di un’altra persona.

Debido a su considerable peso, la instalación del compartimento en el bastidor deben realizarla siempre dos personas. Para evitar daños personales o en el equipo, el compartimento no debe levantarse ni instalarse en el bastidor sin la ayuda de un elevador mecánico o de otra persona.

1. With two people, lift the enclosure up and place it on the edge of the enclosure front tray.

2. Push the enclosure in until the front flanges of the enclosure are flush against the rack.

Page 36: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

36 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a DAE in a Telco rack

3. Attach the front of the unit to the front tray with four #10-32 x .5" screws, two per side. See Figure 32.

Figure 32 Securing the DAE enclosure front

4. At the back of the enclosure, attach the two rear fastening brackets to the rear corners of the enclosure tray, as illustrated in Figure 33.

Insert one #10-32 x .5" screw through each screw hole of the rear fastening bracket and through the rear tray enclosure. Repeat this step for the other side.

CL3664

Mountingscrews

(2 per side)

Front

Page 37: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

37

Installing a DAE in a Telco rack

CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Figure 33 Securing the DAE enclosure back

!

EXP

PRIEXP

PRI

#

!

EXP

PRI EXP

PRI

#

A

B

Mountingscrew (2 perside)

CL3663

Tab(2 perside)

Notch(2 per side)

Rear

Page 38: Hardware Installation Guide - Dell EMC · EMC® CLARiiON® CX4 Series Enclosures ... and rear trays to the rack rails ... Hardware Installation Guide for Telco Racks. CX4 Series Encolsures

38 CX4 Series Encolsures Hardware Installation Guide for Telco Racks

Installing a DAE in a Telco rack

Copyright © 2009 EMC Corporation. All rights reserved.

EMC believes the information in this publication is accurate as of its publication date. The information is subject to change without notice.

THE INFORMATION IN THIS PUBLICATION IS PROVIDED “AS IS.” EMC CORPORATION MAKES NO REPRESENTATIONS OR WARRANTIES OF ANY KIND WITH RESPECT TO THE INFORMATION IN THIS PUBLICATION, AND SPECIFICALLY DISCLAIMS IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.

Use, copying, and distribution of any EMC software described in this publication requires an applicable software license.

For the most up-to-date regulatory document for your product line, go to the Technical Documentation and Advisories section on EMC Powerlink.

For the most up-to-date listing of EMC product names, see EMC Corporation Trademarks on EMC.com.

All other trademarks used herein are the property of their respective owners.