Page 1: HANDRAIL & STAIR COMPLIANCE GUIDELINES

1300 751 701 | FTIGROUP.COM.AU

HANDRAIL & STAIR COMPLIANCE GUIDELINES

Page 2: HANDRAIL & STAIR COMPLIANCE GUIDELINES

The following Fast Tread® Handrail & Stair Compliance Guideline has been created to provide a basic outline of FTI Group’s interpretation of the Building Code of Australia/National Construction Code (BCA/NCC) & Australian Standard AS1428 and to professionally fulfil our obligation to our clients to flag any compliance issues prior to construction stage.

In the following Handrail & Stair Compliance Guideline, with reference to BCA 2016 V1 & V2, BCA 2019 V1 & V2 and AS1428.1-2009, we cover the following:

FAST TREAD® PREFORMED STAIRS

HANDRAIL & STAIR COMPLIANCE GUIDELINES

1. RISERSa. Heights

i. Minimum & Maximum ii. Variation

b. Layback

c. Quantities

2. GOINGS a. Minimum & Maximum Length

b. Variation

3. HEAD CLEARANCE

4. LANDINGS

5. HANDRAIL a. Clearance

i. Door encroachment ii. Knuckle Clearance iii. Clear Width

b. Height

i. Stairs ii. Landings

c. Terminations

d. Openings

e. Returns

PO Box 1103, Goulburn NSW

ftigroup.com.au

+61 2 9052 [email protected]

ABN: 68 609 425 452© FTI Group Pty Ltd 2020

Page 2 of 14

Page 3: HANDRAIL & STAIR COMPLIANCE GUIDELINES

a. Heights

i. Minimum & Maximum

• The minimum height any riser can be is 115mm

• The maximum height any riser can be is 190mm

Excerpts below for reference:

ii Variation

• Adjacent risers, or between adjacent goings, is no greater than 5mm; and

• The largest and smallest riser within a flight, or the largest and smallest going within a flight, does not exceed 10mm

BCA – refer D2.13(a)(iii), (A) &(B)

Excerpts below for reference:

1. RISERS

PO Box 1103, Goulburn NSW

ftigroup.com.au

+61 2 9052 [email protected]

ABN: 68 609 425 452© FTI Group Pty Ltd 2020

Page 3 of 14

Page 4: HANDRAIL & STAIR COMPLIANCE GUIDELINES

b. Layback

• The stair riser may be vertical or have a splay backwards up to a maximum 25mm

AS1428 – refer clause 11.1(d) Figure 27(A) & Figure 27(B)

Excerpts below for reference:

c. Quantities

• No more than 18 nor less than 2 risers

BCA – D2.13(a)(i)

Excerpts below for reference:

1. RISERS (cont.)

PO Box 1103, Goulburn NSW

ftigroup.com.au

+61 2 9052 [email protected]

ABN: 68 609 425 452© FTI Group Pty Ltd 2020

Page 4 of 14

Page 5: HANDRAIL & STAIR COMPLIANCE GUIDELINES

2. GOINGSa. Minimum & Maximum Length

• The minimum length of any going is 250mm

• The maximum length of any going is 355mm

BCA – refer to Table D2.13 RISER & GOING DIMENSION (mm)

Excerpts below for reference:

b. Variation

• Adjacent goings, is no greater than 5mm; and

• The largest and smallest going within a flight, does not exceed 10mm

BCA – refer to clause D2.13 Goings and risers (b) (ii)

Excerpts below for reference:

PO Box 1103, Goulburn NSW

ftigroup.com.au

+61 2 9052 [email protected]

ABN: 68 609 425 452© FTI Group Pty Ltd 2020

Page 5 of 14

Page 6: HANDRAIL & STAIR COMPLIANCE GUIDELINES

3. HEAD CLEARANCE

4. LANDINGS

• The minimum unobstructed height from line or stair nosing to ceiling is 2000mm or 1980mm at doorways

BCA – refer to clause D1.6 Dimensions of exits and paths of travel to exits.

AS1428 – refer to clause 6.2

Excerpts below for reference:

• Maximum gradient of 1:50

• Not less than 750mm long

BCA – refer to clause D2.14 Landings

Excerpts below for reference:

PO Box 1103, Goulburn NSW

ftigroup.com.au

+61 2 9052 [email protected]

ABN: 68 609 425 452© FTI Group Pty Ltd 2020

Page 6 of 14

Page 7: HANDRAIL & STAIR COMPLIANCE GUIDELINES

5. HAND RAILa. Clearance

i. Door Encroachment

• Maximum encroachment into required width of exit = 500mm

BCA – refer to clause D2.20

Excerpts below for reference:

ii. Knuckle Clearance

• Minimum clearance between a handrail and an adjacent wall or other obstruction shall not be less than 50mm.

AS1428 – refer clause 12(h) & Figure 29 (in part)

Excerpts below for reference:

PO Box 1103, Goulburn NSW

ftigroup.com.au

+61 2 9052 [email protected]

ABN: 68 609 425 452© FTI Group Pty Ltd 2020

Page 7 of 14

Page 8: HANDRAIL & STAIR COMPLIANCE GUIDELINES

iii. Clear Width

• The minimum clearance between handrail and any obstruction is 1000mm

AS1428 – refer clause 11.2 Figure 28(in part)

BCA – refer Figure D2.20

Excerpts below for reference:

5. HAND RAIL (a. clearance cont.)

PO Box 1103, Goulburn NSW

ftigroup.com.au

+61 2 9052 [email protected]

ABN: 68 609 425 452© FTI Group Pty Ltd 2020

Page 8 of 14

Page 9: HANDRAIL & STAIR COMPLIANCE GUIDELINES

b. Height

i. Stairs

• Minimum height is 865mm(from nosing line)

• Maximum height is 1000mm(from nosing line)

BCA – refer clause D2.17(a)(iv)

AS1428 – refer clause 12(d) Figure 29(in part)

Excerpts below for reference:

5. HAND RAIL (cont.)

PO Box 1103, Goulburn NSW

ftigroup.com.au

+61 2 9052 [email protected]

ABN: 68 609 425 452© FTI Group Pty Ltd 2020

Page 9 of 14

Page 10: HANDRAIL & STAIR COMPLIANCE GUIDELINES

ii. Landings

• Minimum height is 865mm

• Maximum height is 1000mm

• If length is 500mm or greater, height must be 1000mm.

BCA – refer Table D2.16a BARRIER CONSTRUCTION

Excerpts below for reference:

5. HAND RAIL (b. height cont.)

PO Box 1103, Goulburn NSW

ftigroup.com.au

+61 2 9052 [email protected]

ABN: 68 609 425 452© FTI Group Pty Ltd 2020

Page 10 of 14

Page 11: HANDRAIL & STAIR COMPLIANCE GUIDELINES

c. Terminations

• Continue past the last riser 1 x full going plus a minimum of 300mm horizontally and return 180degrees.

AS1428 – refer clause 11.2(d & e) and Figure 26(A) of clause 11.1

Excerpts below for reference:

Pictures below for reference:

5. HAND RAIL (cont.)

PO Box 1103, Goulburn NSW

ftigroup.com.au

+61 2 9052 [email protected]

ABN: 68 609 425 452© FTI Group Pty Ltd 2020

Page 11 of 14

Page 12: HANDRAIL & STAIR COMPLIANCE GUIDELINES

d. Openings

• Fire-isolated Stair Ways (where horizontal rails are used)

– A 460mm sphere must not be able to pass through any opening

• Non fire-isolated Stair Ways - or where required as an accessible stair

- A 125mm sphere must not be able to pass through any opening (other than the heel of the stair)

BCA – refer to table D2.16a BARRIER CONSTRUCTION

Excerpts below for reference:

5. HAND RAIL (cont.)

PO Box 1103, Goulburn NSW

ftigroup.com.au

+61 2 9052 [email protected]

ABN: 68 609 425 452© FTI Group Pty Ltd 2020

Page 12 of 14

Page 13: HANDRAIL & STAIR COMPLIANCE GUIDELINES

e. Returns

• Handrails must maintain a consistent height as they transition from stair to landing to stair

• No Vertical drops or change in elevation

• Minimum landing length from face of the first riser of the upper flight to the outer wall or any obstruction. = 1 x going + ½ diameter of handrail + 1000mm (excludes handrail to outside of landing or other obstructions such as hydrants etc)

BCA – refer clause D2.17(a)(v) & (vi)

AS1428 – refer to clause 11.2(c), 12(e.). ]

Excerpts below for reference:

Pictures below for reference:

NOTE: Typical Handrail Return drawings available upon request.

5. HAND RAIL (cont.)

PO Box 1103, Goulburn NSW

ftigroup.com.au

+61 2 9052 [email protected]

ABN: 68 609 425 452© FTI Group Pty Ltd 2020

Page 13 of 14

Page 14: HANDRAIL & STAIR COMPLIANCE GUIDELINES

The above guidelines are a guide only and are evidently subject to your project specific requirements/design and your own interpretation of the above-mentioned Codes & Standards. We welcome all comments and feedback plus any performance or alternative solutions in view of moving forward with the production of your stair flights & handrail.

FTI Group Pty Ltd are committed to a 100% client satisfaction guarantee by delivering a quality product to site, on time, every time and exactly as promised.

Thank you for choosing Fast Tread® Preformed Stairs & Handrail, we greatly appreciate your custom and look forward to working with you throughout your project.

Copyright © 2020 by FTI Group Pty Ltd. All rights reserved. No part of this document may be reproduced, distributed, or transmitted in any form or by any means including photocopying, recording or other electronic or mechanical method, without the permission of FTI Group Pty Ltd. No document/drawing/detail produced by FTI Group Pty Ltd may be used by any party other than FTI Group Pty Ltd. For permission requests, write to FTI Group Pty Ltd.

Please feel free to contact us at any time with any questions on 1300 751 701 or [email protected].

5. HAND RAIL (e. returns cont.)

PO Box 1103, Goulburn NSW

ftigroup.com.au

+61 2 9052 [email protected]

ABN: 68 609 425 452© FTI Group Pty Ltd 2020

Page 14 of 14