H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog

Transcript of H3 V3 Engineering Catalog - Olympic...

  • H3/V3 Series Horizontal and Vertical

    Indoor Air Handling Units

    Engineering Catalog

  • www.aaon.com

    3

    Table of Contents AAON H3/V3 Series Features and Options Introduction............................................................. 6 H3/V3 Base Model Description ...................................................................................................... 7 Unit Size........................................................................................................................................ 12 Unit Orientation ............................................................................................................................ 12 Revision ........................................................................................................................................ 14 Voltage .......................................................................................................................................... 14 Interior Corrosion Protection ........................................................................................................ 14 Model Option A1 - Cooling Type ................................................................................................. 15 Model Option A2 - Cooling Rows ................................................................................................ 15 Model Option A3 - Cooling Stages .............................................................................................. 16 Model Option A4 - Cooling FPI ................................................................................................... 16 Model Option B1 - Heating Type ................................................................................................. 17 Model Option B2 - Heating Designation ...................................................................................... 18 Model Option B3 - Heating Stages ............................................................................................... 19 Supply Blower Configuration ....................................................................................................... 20 Supply Blower Model ................................................................................................................... 20 Supply Blower Motor ................................................................................................................... 21 Supply Blower Control/Control Vendors ..................................................................................... 22 Refrigeration Options .................................................................................................................... 23 Special Controls ............................................................................................................................ 26 Additional Controls ....................................................................................................................... 29 Return Air Damper Position ......................................................................................................... 30 Outside Air Damper Position ........................................................................................................ 30 Mixing Box Damper Control ........................................................................................................ 31 Pre Filter Box ................................................................................................................................ 31 Unit Filter Type............................................................................................................................. 32 Final Filter Box ............................................................................................................................. 33 Filter Options ................................................................................................................................ 33 Coil Coating .................................................................................................................................. 34 Expansion Valve ........................................................................................................................... 35 Expansion Valve Controls ............................................................................................................ 35 Exterior Corrosion Protection ....................................................................................................... 35 Tonnage......................................................................................................................................... 36 Added or Modified Systems ......................................................................................................... 36 GPM Cooling Coil ........................................................................................................................ 37 GPM Heating Coil ........................................................................................................................ 37 Control Panel ................................................................................................................................ 38 Warranty ....................................................................................................................................... 40 Type .............................................................................................................................................. 40 General Data ................................................................................................................................. 41 Unit Information ........................................................................................................................... 41 Filter Information .......................................................................................................................... 47 Controls ......................................................................................................................................... 59 Control Vendors ............................................................................................................................ 64

  • www.aaon.com

    4

    Electrical Service Sizing Data ...................................................................................................... 67

    R94190 Rev. A 120726 (ACP 30585)

    Index of Tables and Figures Tables: Table 1 - Unit Sizes ....................................................................................................................... 12Table 2 - Electric Heating Capacities ........................................................................................... 18Table 3 - A Cabinet (up to 1,200 cfm) Information ...................................................................... 41Table 4 - B Cabinet (up to 2,000 cfm) Information ...................................................................... 42Table 5 - C Cabinet (up to 4,000 cfm) Information ...................................................................... 43Table 6 - D Cabinet (up to 6,000 cfm) Information ...................................................................... 44Table 7 - E Cabinet (up to 10,000 cfm) Information .................................................................... 45Table 8 - E Cabinet (up to 10,000 cfm) Information Continued .................................................. 46Table 9 - Chilled Water and Hot Water Coil Connection Sizes ................................................... 46Table 10 - H3 Series A Cabinet Pre Filters ................................................................................... 47Table 11 - V3 Series A Cabinet Pre Filters ................................................................................... 47Table 12 - H3 Series B Cabinet Pre Filters ................................................................................... 48Table 13 - V3 Series B Cabinet Pre Filters ................................................................................... 48Table 14 - H3 Series C Cabinet Pre Filters ................................................................................... 49Table 15 - V3 Series C Cabinet Pre Filters ................................................................................... 49Table 16 - H3 Series D Cabinet Pre Filters ................................................................................... 50Table 17 - V3 Series D Cabinet Pre Filters ................................................................................... 50Table 18 - H3 Series E Cabinet Pre Filters ................................................................................... 51Table 19 - V3 Series E Cabinet Pre Filters ................................................................................... 51Table 20 - H3 Series A Cabinet Unit Filters ................................................................................. 52Table 21 - V3 Series A Cabinet Unit Filters ................................................................................. 52Table 22 - H3 Series B Cabinet Unit Filters ................................................................................. 53Table 23 - V3 Series B Cabinet Unit Filters ................................................................................. 53Table 24 - H3 Series A Cabinet Final Filters ................................................................................ 54Table 25 - V3 Series A Cabinet Final Filters ................................................................................ 54Table 26 - H3 Series B Cabinet Final Filters ................................................................................ 55Table 27 - V3 Series B Cabinet Final Filters ................................................................................ 55Table 28 - H3 Series C Cabinet Final Filters ................................................................................ 56Table 29 - V3 Series C Cabinet Final Filters ................................................................................ 56Table 30 - H3 Series D Cabinet Final Filters ................................................................................ 57Table 31 - V3 Series D Cabinet Final Filters ................................................................................ 57Table 32 - H3 Series E Cabinet Final Filters ................................................................................ 58Table 33 - V3 Series E Cabinet Final Filters ................................................................................ 58

  • www.aaon.com

    5

    Figures: Figure 1- H3 Series Unit Orientation ............................................................................................ 13Figure 2 - V3 Series Unit Orientation ........................................................................................... 13Figure 3 - Magnehelic Gauge ....................................................................................................... 34Figure 4 - Example Low Voltage Terminal Block ....................................................................... 59Figure 5 - WattMaster VCM-X Controller ................................................................................... 64Figure 6 - VCM-X Controller Operator Interfaces ....................................................................... 64Figure 7 - JENEsys Controller ...................................................................................................... 65Figure 8 - Remote Mounted AAON Mini Controller ................................................................... 66

  • www.aaon.com

    6

    AAON H3/V3 Series Features and Options Introduction

    Energy Efficiency Direct Drive Backward Curved Plenum

    Supply Fans Mixing Box/Airside Economizer Double Wall Rigid Polyurethane Foam

    Panel Construction, R-6.25 Insulation Modulating/SCR Electric Heat Premium Efficiency Motors VFD Controlled Supply Fans ECM Driven Supply Fans Heat Pump Configuration Matching Energy Efficient Condensing

    Units Indoor Air Quality 100% Outside Air High Efficiency Filtration Double Wall Construction Interior Corrosion Protection Polymer E-Coated Coils Stainless Steel Drain Pans Humidity Control High Capacity Cooling Coils Modulating Hot Gas Reheat Safety Phase and Brown Out Protection Return Air Smoke Detector Supply and Return Air Firestats

    Installation and Maintenance Left or Right Hand Connections Clogged Filter Switch Color-Coded Wiring Diagram Labeled Components Direct Drive Supply Fans Hinged Access Doors with Lockable

    Handles Access to Fans, Coils, Drain Pans,

    Heating, Filters and Controls Factory Installed TXV Factory Installed Electric Heating Factory Installed Mixing Box Magnehelic Gauge Single Point Power Connection Supply and Return Duct Flange System Integration 800-10,000 cfm in Five Cabinet Sizes Horizontal and Vertical Airflow Chilled Water Cooling Coils Customer Provided Controls Electric Heating Hot Water/Steam Heating Coils Non-Compressorized R-410A DX Coils Controls Flexibility Environmentally Friendly Mixing Box/Airside Economizer R-410A DX Coils Extended Life Exterior Corrosion Protection Interior Corrosion Protection Polymer E-Coated Coils Stainless Steel Drain Pans

  • www.aaon.com

    7

    H3/V3 Base Model Description

    - H3 A R A

    - 3

    - 0

    - 1 4 1 C

    - Series and Generation

    Unit Size

    Unit Orientation Revision Voltage

    Corrosion Protection A1 A2 A3 A4

    BASE MODEL

    H3 = Horizontal - Back Intake, Front Discharge SERIES AND GENERATION

    V3 = Vertical - Back Intake, Top Discharge

    A = Up to 1,200 cfm UNIT SIZE

    B = Up to 2,000 cfm C = Up to 4,000 cfm D = Up to 6,000 cfm E = Up to 10,000 cfm

    R = Right Hand Connections UNIT ORIENTATION

    L = Left Hand Connections

    A = First Revision REVISION

    1 = 230V/1/60Hz VOLTAGE

    2 = 230V/3/60Hz 3 = 460V/3/60Hz 4 = 575V/3/60Hz 8 = 208V/3/60Hz 9 = 208V/1/60Hz

    0 = None CORROSION PROTECTION

    A = Interior Corrosion Protection

    Model Option A: COOLING

    0 = No Cooling A1: COOLING TYPE

    1 = R-410A DX Cooling 2 = Chilled Water Cooling

    0 = No Cooling A2: COOILNG ROWS

    4 = 4 Row Coil 6 = 6 Row Coil 8 = 8 Row Coil

    0 = No Cooling A3: COOLING STAGES

    1 = Single Circuit 2 = Two Circuits - Interlaced Coil D = Double Serpentine F = Single Serpentine H = Half Serpentine Q = Quarter Serpentine

    0 = No Cooling A4: COOLING FPI

    A = 10 fpi B = 8 fpi C = 12 fpi

    Model Number

  • www.aaon.com

    8

    H3/V3 Base Model and Features Description

    1 2 F

    : A A B B

    - B1 B2 B3 1A 1B 1C 1D

    Model Option B: HEATING

    0 = No Heating B1: HEATING TYPE

    1 = Hot Water 3 = Electric Heating 4 = Steam Distributing

    0 = No Heating B2: HEATING DESIGNATION

    1 = 1 Row Coil 2 = 2 Row Coil A = 7 kW (5.3 kW @ 208V) B = 14 kW (10.5 kW @ 208V) C = 21 kW (15.8 kW @ 208V) D = 28 kW (21.0 kW @ 208V) E = 35 kW (26.3 kW @ 208V) F = 42 kW (31.5 kW @ 208V) G = 49 kW (37.0 kW @ 208V) H = 56 kW (42.0 kW @ 208V) J = 63 kW (47.3 kW @ 208V) K = 70 kW (52.5 kW @ 208V) L = 77 kW (57.8 kW @ 208V) M = 84 kW (63.0 kW @ 208V)

    0 = No Heating B3: HEATING STAGES

    1 = 1 Stage 2 = 2 Stage 3 = 3 Stage 4 = 4 Stage S = Modulating/SCR Electric F = Single Serpentine 10 fpi H = Half Serpentine 10 fpi Q = Quarter Serpentine 10 fpi

    Feature 1: SUPPLY FAN

    0 = 1 Blower + Premium Eff. Motor 1A: SUPPLY AIR BLOWER CONFIGURATION

    1 = 1 Blower + Premium Eff. Motor + 1 VFD A = 1 Blower + 1 High Efficiency EC Motor B = 2 Blowers + 2 High Efficiency EC Motors

    1 = 15 Backward Curved Plenum Fan 1B: SUPPLY AIR BLOWER

    2 = 15 BC Plenum, 50% Width with Banding 3 = 18.5 Backward Curved Plenum Fan 4 = 18.5 BC Plenum Fan, 70% Width with Banding 5 = 22 Backward Curved Plenum Fan 6 = 24 Backward Curved Plenum Fan 7 = 27 Backward Curved Plenum Fan 8 = 27 BC Plenum Fan, 70% Width with Banding A = 310 mm Direct Drive BC Plenum Fan B = 355 mm Direct Drive BC Plenum Fan C = 450 mm Direct Drive BC Plenum Fan

    1 = 1 hp - 1760 rpm 1C: SUPPLY AIR BLOWER MOTOR

    2 = 2 hp - 1760 rpm 3 = 3 hp - 1760 rpm 4 = 5 hp - 1760 rpm 5 = 7.5 hp - 1760 rpm 6 = 10 hp - 1760 rpm A = 500 W (0.67 hp) B = 1.0 kW (1.34 hp) C = 1.7 kW (2.28 hp) D = 3.0 kW (2.90 hp or 4.02 hp)

    0 = Standard - Terminal Block

    1D: SUPPLY BLOWER CONTROL/CONTROL VENDORS

    A = Potentiometer Supply Fan Control B = WattMaster Orion Controls System C = Field Installed Controls by Others

    Model/Feature Number

  • www.aaon.com

    9

    H3/V3 Features Description

    0 C 0

    - F T B

    - 2 3 4 5A 5B 5C

    0 = Standard - None Feature 2: REFRIGERATION OPTIONS

    A = Single Circuit External Hot Gas Bypass B = Dual Circuit External Hot Gas Bypass C = Heat Pump D = Option B + H E = Options B + J F = Options C + H G = Options C + J H = Modulating Hot Gas Reheat J = Factory Installed Modulating Hot Gas Reheat K = Dual Circuit Modulating Hot Gas Reheat + Option B L =Factory Installed Dual Circuit Modulating Hot Gas Reheat + Option B M = Dual Circuit Modulating Hot Gas Reheat + Option C N = Factory Installed Dual Circuit Modulating Hot Gas Reheat + Option C P = Option H (Circuit 1) + Option A (Circuit 2) Q = Option J (Circuit 1) + Option A (Circuit 2)

    0 = Standard - None Feature 3: SPECIAL CONTROLS

    A = Constant Volume Controller - CV Cool + CV Heat B = Constant Volume Controller with Modulating Hot Gas Reheat - CV Cool + CV Heat C = VAV Controller - VAV Cool + CV Heat D = VAV Controller with MHGR - VAV Cool + CV Heat E = Make Up Air Controller - CV Cool + CV Heat F = Make Up Air Controller with Modulating Hot Gas Reheat - CV Cool + CV Heat G = WattMaster Modulating Hot Gas Reheat Controller

    0 = Standard - None Feature 4: ADDITIONAL CONTROLS

    A = Phase and Brownout Protection B = Return and Supply Air Firestat C = Return Air Smoke Detector D = Options A + B E = Options A + C F = Options B + C G = Options A + B + C Feature 5: MIXING BOX

    0 = Standard - None 5A: RETURN AIR DAMPER POSITION

    F = Front L = Left Hand (Front OA Damper Required) R = Right Hand (Front OA Damper Required) T = Top (Front OA Damper Required)

    0 = Standard - None 5B: OUTSIDE AIR DAMPER POSITION

    F = Front L = Left Hand (Front RA Damper Required) R = Right Hand (Front RA Damper Required) T = Top (Front RA Damper Required)

    0 = Standard - None 5C: MIXING BOX DAMPER CONTROL

    A = 2 Position Actuators B = Fully Modulating Actuators C = Fixed Position Dampers

    Feature Number

  • www.aaon.com

    10

    H3/V3 Features Description

    0 G 0

    - 0 0 A A A

    6A 6B 6C 7 8 9 10 11

    Feature 6: FILTER BOX

    0 = Standard - None 6A: PRE FILTER BOX

    A = 2 Pleated - 30% Eff. - MERV 8 B = 4 Pleated - 30% Eff. - MERV 8 C = 4 Pleated - 65% Eff. - MERV 11 D = 4 Pleated - 85% Eff. - MERV 13 E = 4 Pleated - 95% Eff. - MERV 14 F = 2 Pleated - 30% Eff. - MERV 8 + 4 Pleated - 30% Eff. - MERV 8 G = 2 Pleated - 30% Eff. - MERV 8 + 4 Pleated - 65% Eff. - MERV 11 H = 2 Pleated - 30% Eff. - MERV 8 + 4 Pleated - 85% Eff. - MERV 13 J = 2 Pleated - 30% Eff. - MERV 8 + 4 Pleated - 95% Eff. - MERV 14

    0 = Standard - None 6B: UNIT FILTER

    A = 2 Pleated - 30% Eff. - MERV 8 B = 4 Pleated - 30% Eff. - MERV 8 C = 4 Pleated - 65% Eff. - MERV 11 D = 4 Pleated - 85% Eff. - MERV 13 E = 4 Pleated - 95% Eff. - MERV 14 F = 2 Pleated - 30% Eff. - MERV 8 + 4 Pleated - 30% Eff. - MERV 8 G = 2 Pleated - 30% Eff. - MERV 8 + 4 Pleated - 65% Eff. - MERV 11 H = 2 Pleated - 30% Eff. - MERV 8 + 4 Pleated - 85% Eff. - MERV 13 J = 2 Pleated - 30% Eff. - MERV 8 + 4 Pleated - 95% Eff. - MERV 14

    0 = Standard - None 6C: FINAL FILTER BOX

    A = 2 Pleated - 30% Eff. - MERV 8 B = 12 Cartridge - 65% Eff. - MERV 11 C = 12 Cartridge - 85% Eff. - MERV 13 D = 12 Cartridge - 95% Eff. - MERV 14 E = 2 Pleated - 30% Eff. - MERV 8 + 12 Cartridge - 65% Eff. - MERV 11 F = 2 Pleated - 30% Eff. - MERV 8 + 12 Cartridge - 85% Eff. - MERV 13 G = 2 Pleated - 30% Eff. - MERV 8 + 12 Cartridge - 95% Eff. - MERV 14

    0 = Standard - None Feature 7: FILTER OPTIONS

    A = Magnehelic Gauge B = Clogged Filter Switch C = Options A + B

    0 = Standard - None Feature 8: COIL COATING

    A = E-coated Cooling and Heating Coils

    0 = None Feature 9: EXPANSION VALVE

    A = Thermal Expansion Valves

    0 = None

    Feature 10: EXPANSION VALVE CONTROLS

    A = Standard Control

    0 = Standard - None Feature 11: EXTERNAL PAINT

    A = AAON Gray Paint B = Special Paint

    Feature Number

  • www.aaon.com

    11

    H3/V3 Features Description

    C 0

    - 0 0

    - A 0 0 0 0 0 0 0 0

    12 13 14A 14B 15 16 17 18 19 20 21 22 23

    0 = Standard - None Feature 12: TONNAGE

    A = 2 ton Capacity B = 3 ton Capacity C = 4 ton Capacity D = 5 ton Capacity E = 6 ton Capacity F = 7 ton Capacity G = 8 ton Capacity H = 10 ton Capacity J = 14 ton Capacity K = 17 ton Capacity L = 22 ton Capacity M = 25 ton Capacity N = 30 ton Capacity P = 31 ton Capacity Q = 34 ton Capacity R = 45 ton Capacity S = 55 ton Capacity T = 63 ton Capacity

    0 = Standard - None

    Feature 13: ADDED OR MODIFIED SYSTEMS

    Feature 14: GPM

    0 = Standard - None 14A: GPM COOLING COIL

    A = 1.5-2.5 gpm B = 2.6-7.0 gpm C = 7.1 -14.0 gpm D = 14.1-24.0 gpm E = 24.1-40.0 gpm F = 40.1-80.0 gpm G = 80.1-150.0 gpm H = 150.1-250.0 gpm

    0 = Standard - None 14B: GPM HEATING COIL

    A = 1.5-2.5 gpm B = 2.6-7.0 gpm C = 7.1 -14.0 gpm D = 14.1-24.0 gpm E = 24.1-40.0 gpm F = 40.1-80.0 gpm G = 80.1-150.0 gpm H = 150.1-250.0 gpm

    0 = None Feature 15: CONTROL PANEL

    A = Small Control Panel - 12 x 12 B = Medium Control Panel - 25 x 22 C = Large Control Panel - 48 x 22

    0 = Standard - None Feature 16: BLANK

    0 = Standard - None Feature 17: BLANK

    0 = Standard - None Feature 18: BLANK

    Feature 19: BLANK

    0 = Standard - None Digit 41:

    0 = Standard - None Feature 20: BLANK

    0 = Standard - None Feature 21: BLANK

    0 = Standard - 1 Year Parts Feature 22: WARRANTY

    0 = Standard Feature 23: TYPE

    X = Special Pricing Authorization

    Feature Number

  • www.aaon.com

    12

    Model Number Unit Size

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    The first letter of the model string designates the airflow configuration, the second number designates the generation and the third letter designates the unit size. Refer to AAONEcat32 for unit dimensions.

    Table 1 - Unit Sizes

    Model Cabinet Size Configuration Intake

    Location Discharge Location

    H3-A Up to 1,200 cfm

    Horizontal Back Front H3-B Up to 2,000 cfm H3-C Up to 4,000 cfm H3-D Up to 6,000 cfm H3-E Up to 10,000 cfm V3-A Up to 1,200 cfm

    Vertical Back Top V3-B Up to 2,000 cfm V3-C Up to 4,000 cfm V3-D Up to 6,000 cfm V3-E Up to 10,000 cfm

    Model Number Unit Orientation

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    R = Right Hand Connections - Refrigerant piping stub outs, hydronic coil stub outs and unit access panels are located on the right hand side of the air handling unit. Condensate drain pan connections are available on either the right or left hand side of the unit. L = Left Hand Connections - Refrigerant piping stub outs, hydronic coil stub outs and unit access panels are located on the left hand side of the air handling unit. Condensate drain pan connections are available on either the right or left hand side of the unit.

  • www.aaon.com

    13

    Figure 1- H3 Series Unit Orientation

    Figure 2 - V3 Series Unit Orientation

    H3 Series

    Return Air Supply Air

    Right Hand Side

    Left Hand Side

    Connections and service access on right side for right hand orientation

    Top View

    Air Flow

    Connections and service access on right side for right hand orientation

    Right Hand Side Left Hand Side

    Supply Air

    Return Air

    Top View V3 Series

    Air Flow Consider the air flow to be

    hitting the back of your head.

    Consider the air flow to be hitting the back of your head.

  • www.aaon.com

    14

    Model Number Revision

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    A = First Revision - This digit is used for future product updates and improvements.

    Model Number Voltage

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    1 = 208-230V/1/60Hz 2 = 208-230V/3/60Hz 3 = 460V/3/60Hz

    Model Number Interior Corrosion Protection

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None A = Interior Corrosion Protection - All exposed metal surfaces in the air tunnel except the coils, coil casings and condensate drain pans are spray coated with a two-part polyurethane, heat baked coating. Selection covers coating of the fans, dampers, filter rack and service door interiors. Option is intended for use in coastal saltwater conditions under the stress of heat, salt, sand and wind and is applicable to all corrosive environments where a polyurethane coating is acceptable. Coating exceeds 2,500 hours when tested under ASTM B 117-95 requirements. Condensate drain pans are fabricated of 18 gauge 304 stainless steel. See Feature 8 for coil corrosion protection options.

  • www.aaon.com

    15

    Model Number Model Option A1 - Cooling Type

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = No Cooling - Heating only air handling unit. 1 = R-410A DX Cooling - Draw-through R-410A DX evaporator coil air handling unit. 2 = Chilled Water Cooling - Draw-through chilled water coil air handling unit. No valves or valve controls are included with this option. Chilled water coil air handling unit includes supply and return water connection stub outs.

    Model Number Model Option A2 - Cooling Rows

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = No Cooling - Heating only air handling unit. 4 = 4 Row Coil - Four row coil. 6 = 6 Row Coil - Six row coil. 8 = 8 Row Coil - Eight row coil.

  • www.aaon.com

    16

    Model Number Model Option A3 - Cooling Stages

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = No Cooling - Heating only air handling unit. 1 = Single Circuit - Single circuited evaporator coil. 2 = Two Circuits - Interlaced Coil - Dual circuited evaporator coil with interlaced circuitry. D = Double Serpentine - Chilled water coil with double serpentine circuitry. No valves or valve controls are included with this option. Chilled water coil air handling unit includes supply and return water connection stub outs. F = Single Serpentine - Chilled water coil with single serpentine circuitry. No valves or valve controls are included with this option. Chilled water coil air handling unit includes supply and return water connection stub outs. H = Half Serpentine - Chilled water coil with half serpentine circuitry. No valves or valve controls are included with this option. Chilled water coil air handling unit includes supply and return water connection stub outs.

    Standard chilled water coil circuitry option.

    Q = Quarter Serpentine - Chilled water coil with quarter serpentine circuitry. No valves or valve controls are included with this option. Chilled water coil air handling unit includes supply and return water connection stub outs.

    Model Number Model Option A4 - Cooling FPI

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = No Cooling - Heating only air handling unit. A = 10 fpi - Cooling coil with 10 fins per inch. B = 8 fpi - Cooling coil with 8 fins per inch.

    Standard cooling coil fpi option.

    C = 12 fpi - Cooling coil with 12 fins per inch.

  • www.aaon.com

    17

    Model Number Model Option B1 - Heating Type

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = No Heating - Cooling only air handling unit. 1 = Hot Water Coil - Hot water heating coil located in the preheat position upstream of the cooling coil. No valves or valve controls are included with this option. 3 = Electric Heat - Electric heater with multiple elements located downstream of the cooling coil and supply fan. 4 = Steam Distributing Coil - Steam heating coil located in the preheat position upstream of the cooling coil. No valves or valve controls are included with this option.

  • www.aaon.com

    18

    Model Number Model Option B2 - Heating Designation

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = No Heating - Cooling only air handling unit. 1 = 1 Row Coil - Single row hot water or steam heating coil. No valves or valve controls are included with this option. 2 = 2 Row Coil - Two row hot water or steam heating coil. No valves or valve controls are included with this option.

    Table 2 - Electric Heating Capacities

    Electric Heat Capacity kW (230V, 460V) kW (208V)

    A = Heat A 7.0 5.3 B = Heat B 14.0 10.5 C = Heat C 21.0 15.8 D = Heat D 28.0 21.0 E = Heat E 35.0 26.3 F = Heat F 42.0 31.5 G = Heat G 49.0 37.0 H = Heat H 56.0 42.0 J = Heat J 63.0 47.3 K = Heat K 70.0 52.5 L = Heat L 77.0 57.8

    M = Heat M 84.0 63.0 Note: AAONEcat32 will select the correct heating designation option for electric heat based on the desired leaving air and entering air temperature conditions. For heat pump units this is the emergency or backup heat capacity, which is the capacity of the secondary heater available when heat pump heating is not in use. See General Data section for model specific heating information.

  • www.aaon.com

    19

    Model Number Model Option B3 - Heating Stages

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = No Heating 1 = 1 stage - Single stage heat control. 2 = 2 stage - Two stage heat control. 3 = 3 stage - Three stage heat control. 4 = 4 stage - Four stage heat control. S = Modulating/SCR Electric Modulating/SCR Electric - Potentiometer Control - Fully modulating electric heating, controlled by a Silicon Controlled Rectifier (SCR) and DDC controller. Includes a factory wired supply air temperature sensor, which is field installed in the supply ductwork, and a factory wired supply air temperature setpoint adjustment potentiometer, which is field mounted. Potentiometer dial uses variable resistance to provide simple setpoint control. Modulating/SCR Electric - 0-10VDC Control Signal - Fully modulating electric heating, controlled by an SCR and DDC controller. A terminal strip to connect a 0-10 VDC control signal by others is included. Heating elements line voltage is modulated linearly with respect to the control signal. F = Single Serpentine 10 fpi - Hot water or steam heating coil with single serpentine circuitry and 10 fins per inch. No valves or valve controls are included with this option.

    H = Half Serpentine 10 fpi - Hot water heating coil with half serpentine circuitry and 10 fins per inch. No valves or valve controls are included with this option.

    Standard hot water and steam heating coil options.

    Q = Quarter Serpentine 10 fpi - Hot water heating coil with quarter serpentine circuitry and 10 fins per inch. No valves or valve controls are included with this option.

    Note: For heat pump units this is the number of emergency or backup heat stages, which is the number of stages of the secondary heater available when heat pump heating is not in use. See General Data section for tonnage specific heating information.

  • www.aaon.com

    20

    Feature 1A Supply Blower Configuration

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = 1 Blower with Premium Efficiency Motor 1 = 1 Blower with Premium Efficiency Motor with 1 VFD A = 1 Blower with High Efficiency Electronically Commutated Motor (ECM) B = 2 Blowers with 2 High Efficiency Electronically Commutated Motors (ECM) AAONEcat32 will select the correct available options for Feature 1A based on unit conditions and the input from the fan selection program. When all of the other features have been selected, you will be prompted to select supply fans, motors and VFDs under the Fan Selection window. In the Fan Selection window you will be able to choose the number of fans, VFDs and motor efficiency. General fan information, fan sound information and fan curves will be available for viewing in the Fan Selection window.

    Feature 1B Supply Blower Model

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    1 = 15 Backward Curved Plenum Fan 2 = 15 Backward Curved Plenum Fan, 50% Width with Banding 3 = 18.5 Backward Curved Plenum Fan 4 = 18.5 Backward Curved Plenum Fan, 70% Width with Banding 5 = 22 Backward Curved Plenum Fan 6 = 24 Backward Curved Plenum Fan 7 = 27 Backward Curved Plenum Fan 8 = 27 Backward Curved Plenum Fan, 70% Width with Banding A = 310 mm Direct Drive Backward Curved Plenum Fan B = 355 mm Direct Drive Backward Curved Plenum Fan C = 450 mm Direct Drive Backward Curved Plenum Fan AAONEcat32 will select the correct available options for Feature 1B based on unit conditions and the input from the fan selection program. When all of the other features have been selected, you will be prompted to select supply fans, motors and VFDs under the Fan Selection window. In the Fan Selection window you will be able to choose the number of fans, VFDs, and motor efficiency. General fan information, fan sound information, and fan curves will be available for viewing in the Fan Selection window.

  • www.aaon.com

    21

    Feature 1C Supply Blower Motor

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    1 = 1 hp - 1760 rpm 2 = 2 hp - 1760 rpm 3 = 3 hp - 1760 rpm 4 = 5 hp - 1760 rpm 5 = 7.5 hp - 1760 rpm 6 = 10.0 hp - 1760 rpm

    A = 500 W (0.67 hp) B = 1.0 kW (1.34 hp) C = 1.7 kW (2.28 hp) D = 3.0 kW (2.90 hp or 4.02 hp)

    AAONEcat32 will select the correct available options for Feature 1C based on unit conditions and the input from the fan selection program. When all of the other features have been selected, you will be prompted to select supply fans, return or exhaust fans, motors and VFDs under the Fan Selection window. In the Fan Selection window you will be able to choose the number of fans, VFDs and motor efficiency. General fan information, fan sound information and fan curves will be available for viewing in the Fan Selection window. Note: High efficiency Electronically Commutated Motors (ECM) are kW rated.

  • www.aaon.com

    22

    Feature 1D Supply Blower Control/Control Vendors

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - Terminal Block - No factory provided unit controller. Terminal block is provided for unit and supply fan control. Field supplied control signal is required with a VFD driven fan. A = Potentiometer Supply Fan Control - No factory provided unit controller. Supply air cfm setpoint potentiometer is factory provided and installed. Potentiometer dial uses variable resistance to provide simple setpoint control. B = WattMaster Orion Controls System - AAON provided and factory installed WattMaster VCM-X controller (Feature 3). Option requires the selection of an operator interface in AAONEcat32 to set up controller. Supply fan speed is controlled by WattMaster VCM-X unit controller. See Controls section for more information. C = Field Installed Controls By Others - No factory provided unit controller. Terminal block is provided for unit and supply fan control. Field supplied 0-10 VDC control signal is required with an ECM driven fan.

  • www.aaon.com

    23

    Feature 2 Refrigeration Options

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None - DX air handling unit includes factory installed expansion valve and liquid and suction line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. Chilled water coil air handling unit includes supply and return water connection stub outs. A = Single Circuit External Hot Gas Bypass - Factory installed and field adjustable pressure activated bypass valve on the lead refrigeration circuit factory setup to divert hot compressor discharge gas to the evaporator coil if pressure on the evaporator side of the valve drops below 105 psi for R-410A (34F at sea level). The bypass valve is at full capacity after six degrees of differential (28F at sea level). This option is used to prevent coil freeze-up during periods of low airflow or cold entering coil conditions without cycling of the compressors on and off. Option is required on all Variable Air Volume (VAV) and Make Up Air (MUA) units without variable capacity scroll compressors. This option is used for refrigeration system protection only and cannot be used for cooling capacity modulation. When lead circuit includes a variable capacity scroll compressor, this option includes hot gas bypass on the lag circuits. DX air handling unit includes factory installed expansion valve, factory installed hot gas bypass valve, and liquid, suction and hot gas line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. B = Dual Circuit External Hot Gas Bypass - Factory installed and field adjustable pressure activated bypass valves on all refrigeration circuits factory setup to divert hot compressor discharge gas to the evaporator coil if pressure on the evaporator side of the valve drops below 105 psi for R-410A (34F at sea level). The bypass valve is at full capacity after six degrees of differential (28F at sea level). This option is used to prevent coil freeze-up during periods of low airflow or cold entering coil conditions without cycling of the compressors on and off. Option is required on all Variable Air Volume (VAV) and Make Up Air (MUA) units without variable capacity scroll compressors. This option is used for refrigeration system protection only and cannot be used for cooling capacity modulation. DX air handling unit includes factory installed expansion valves, factory installed hot gas bypass valves, and liquid, suction and hot gas line stub outs for connection to a matching condensing unit. Expansion valve sensing bulbs must be field installed on the suction lines. C = Heat Pump - Heat pump air handling unit which can provide energy efficient heating and cooling. DX air handling unit includes factory installed expansion valves with check valve, and liquid and suction line stub outs for connection to a matching heat pump condensing unit. Heat pump filter dryer is factory provided for field installation at the indoor coil. Expansion valve sensing bulbs must be field installed on the suction lines. Reversing valves, accumulators and outdoor coil filter dryers, check valves and thermal expansion valves should be provided with the matching condensing unit. See Model Options B1, B2 and B3 for emergency (backup) heat options and Feature 3.

  • www.aaon.com

    24

    Feature 2 - Refrigeration Options Continued D = Modulating Hot Gas Reheat with Dual Circuit External Hot Gas Bypass - Option B + refrigerant reheat coil mounted downstream of the evaporator coil. Coil must be field piped to the lead cooling circuit, with factory provided reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON modulating hot gas reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. E = Factory Installed Modulating Hot Gas Reheat with Dual Circuit External Hot Gas Bypass - Option B + refrigerant reheat coil mounted downstream of the evaporator coil. Coil is factory piped to the lead cooling circuit, with reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. F = Heat Pump with Modulating Hot Gas Reheat - Option C + refrigerant reheat coil mounted downstream of the evaporator coil. Coil must be field piped to the lead cooling circuit, with factory provided reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON modulating hot gas reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. G = Heat Pump with Factory Installed Modulating Hot Gas Reheat - Option C + refrigerant reheat coil mounted downstream of the evaporator coil. Coil is factory piped to the lead cooling circuit, with reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. H = Modulating Hot Gas Reheat - Refrigerant reheat coil mounted downstream of the evaporator coil. Coil must be field piped to the lead cooling circuit, with factory provided reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON modulating hot gas reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line.

  • www.aaon.com

    25

    Feature 2 - Refrigeration Options Continued J = Factory Installed Modulating Hot Gas Reheat - Refrigerant reheat coil mounted downstream of the evaporator coil. Coil is factory piped to the lead cooling circuit, with reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. K = Dual Circuit External Hot Gas Bypass with Dual Circuit Modulating Hot Gas Reheat - Option B + Interlaced refrigerant reheat coil mounted downstream of the evaporator coil. Coil must be field piped to the cooling circuits, with factory provided reheat valves and check valves, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON dual circuit reheat condensing unit includes receiver tanks and condensing unit reheat valves. DX air handling unit includes factory installed expansion valves and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulbs must be field installed on the suction lines. L = Dual Circuit External Hot Gas Bypass with Factory Installed Dual Circuit Modulating Hot Gas Reheat - Option B + Interlaced refrigerant reheat coil mounted downstream of the evaporator coil. Coil is factory piped to the cooling circuits, with reheat valves and check valves, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON reheat condensing unit includes receiver tanks and condensing unit reheat valves. DX air handling unit includes factory installed expansion valves and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulbs must be field installed on the suction lines. M = Heat Pump with Dual Circuit Modulating Hot Gas Reheat - Option C + Interlaced refrigerant reheat coil mounted downstream of the evaporator coil. Coil must be field piped to the cooling circuits, with factory provided reheat valves and check valves, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON dual circuit reheat condensing unit includes receiver tanks and condensing unit reheat valves. DX air handling unit includes factory installed expansion valves and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulbs must be field installed on the suction lines. N = Heat Pump with Factory Installed Dual Circuit Modulating Hot Gas Reheat - Option C + Interlaced refrigerant reheat coil mounted downstream of the evaporator coil. Coil is factory piped to the cooling circuits, with reheat valves and check valves, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON reheat condensing unit includes receiver tanks and condensing unit reheat valves. DX air handling unit includes factory installed expansion valves and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulbs must be field installed on the suction lines.

  • www.aaon.com

    26

    Feature 2 - Refrigeration Options Continued P = Modulating Hot Gas Reheat with Single Circuit External Hot Gas Bypass - Refrigerant reheat coil mounted downstream of the evaporator coil on refrigeration circuit 1 and hot gas bypass (Option A) on refrigeration circuit 2. Reheat coil must be field piped to the lead cooling circuit, with factory provided reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON modulating hot gas reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line. Q = Factory Installed Modulating Hot Gas Reheat with Single Circuit External Hot Gas Bypass - Refrigerant reheat coil mounted downstream of the evaporator coil on refrigeration circuit 1 and hot gas bypass (Option A) on refrigeration circuit 2. Reheat coil is factory piped to the lead cooling circuit, with reheat valve and check valve, to provide the unit with a dehumidification mode of operation for when the cooling load has been satisfied. Matching AAON reheat condensing unit includes receiver tank and condensing unit reheat valve. DX air handling unit includes factory installed expansion valve and liquid, suction and hot gas reheat line stub outs for connection to a matching condensing unit. Expansion valve sensing bulb must be field installed on the suction line.

    Feature 3 Special Controls

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None - Terminal strip for use with a thermostat. See Controls section for more information. A = Constant Volume Unit Controller - Constant Volume Cooling and Constant Volume Heating - Standard Constant Volume controls for non-heat pump systems. During the cooling mode of operation the supply fan provides constant airflow and mechanical cooling modulates based on the controlling temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Outside air temperature sensor, supply air temperature sensor and space temperature sensor with setpoint reset and unoccupied override are factory supplied for field installation. See Controls section for more information.

  • www.aaon.com

    27

    Feature 3 - Special Controls Continued B = Constant Volume Unit Controller with Modulating Hot Gas Reheat - Constant Volume Cooling and Constant Volume Heating - Standard Constant Volume controls for non-heat pump systems. During the cooling mode of operation the supply fan provides constant airflow and mechanical cooling modulates based on the controlling temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Outside air temperature sensor, supply air temperature sensor and space temperature sensor with setpoint reset and unoccupied override are factory supplied for field installation. Modulating hot gas reheat provides the unit with a dehumidification mode of operation for when the cooling load has been satisfied. This option provides constant supply air temperature control during dehumidification, which prevents space temperature swings. Complete system, with AAON air handling unit and AAON condensing unit, includes modulating condenser control valve, modulating reheat control valve, supply air temperature sensor and controller to maintain the supply air temperature during the dehumidification mode of operation. A terminal contact (RH1) is included for connecting a humidistat. A wall mounted humidistat is available as an accessory. With this option, receiver tanks are provided with the condensing unit. See Feature 2 and Controls section for more information. C = Variable Volume Unit Controller - Variable Volume Cooling and Constant Volume Heating - Standard VAV controls for non-heat pump systems and heat pump systems. During the cooling mode of operation the supply fan modulates based on the supply static pressure and mechanical cooling modulates based on the supply air temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Outside air temperature sensor, return air temperature, supply air temperature sensor and supply air static pressure probe are factory supplied for field installation. Space temperature sensor with setpoint reset and unoccupied override is factory supplied with WattMaster VCM-X controller for field installation. See Controls section for more information. D = Variable Volume Unit Controller with Modulating Hot Gas Reheat - Variable Volume Cooling and Constant Volume Heating - Standard VAV controls for non-heat pump systems and heat pump systems. During the cooling mode of operation the supply fan modulates based on the supply static pressure and mechanical cooling modulates based on the supply air temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Outside air temperature sensor, return air temperature, supply air temperature sensor and supply air static pressure probe are factory supplied for field installation. Space temperature sensor with setpoint reset and unoccupied override is factory supplied with WattMaster VCM-X controller for field installation. Modulating hot gas reheat provides the unit with a dehumidification mode of operation for when the cooling load has been satisfied. This option provides constant supply air temperature control during dehumidification, which prevents space temperature swings. Complete system, with AAON air handling unit and AAON condensing unit, includes modulating condenser control valve, modulating reheat control valve, supply air temperature sensor and controller to maintain the supply air temperature during the dehumidification mode of operation. A terminal contact (RH1) is included for connecting a humidistat. A wall mounted humidistat is available as an accessory. With this option, receiver tanks are provided with the condensing unit. See Feature 2 and Controls section for more information.

  • www.aaon.com

    28

    Feature 3 - Special Controls Continued E = Make Up Air Unit Controller - Constant Volume Cooling and Constant Volume Heating - Standard Make Up Air controls for non-heat pump systems. During the cooling mode of operation the supply fan provides constant airflow and mechanical cooling modulates based on the controlling temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Outside air temperature sensor and supply air temperature sensor are factory supplied for field installation. See Controls section for more information. F = Make Up Air Unit Controller with Modulating Hot Gas Reheat - Constant Volume Cooling and Constant Volume Heating - Standard Make Up Air controls for non-heat pump systems. During the cooling mode of operation the supply fan provides constant airflow and mechanical cooling modulates based on the controlling temperature. During the heating mode of operation the supply fan provides constant airflow and heating modulates based on the controlling temperature. Outside air temperature sensor and supply air temperature sensor are factory supplied for field installation. Modulating hot gas reheat provides the unit with a dehumidification mode of operation for when the cooling load has been satisfied. This option provides constant supply air temperature control during dehumidification, which prevents space temperature swings. Complete system, with AAON air handling unit and AAON condensing unit, includes modulating condenser control valve, modulating reheat control valve, supply air temperature sensor and controller to maintain the supply air temperature during the dehumidification mode of operation. A terminal contact (RH1) is included for connecting a humidistat. With this option, receiver tanks are provided with the condensing unit. See Feature 2 and Controls section for more information. G = WattMaster Modulating Hot Gas Reheat - Modulating hot gas reheat provides the unit with a dehumidification mode of operation for when the cooling load has been satisfied. This option provides constant supply air temperature control during dehumidification, which prevents space temperature swings. Complete system, with AAON air handling unit and AAON condensing unit, includes modulating condenser control valve, modulating reheat control valve, supply air temperature sensor and controller to maintain the supply air temperature during the dehumidification mode of operation. A terminal contact (RH1) is included for connecting a humidistat. A wall mounted humidistat is available as an accessory. With this option, receiver tanks are provided with the condensing unit. See Feature 2 for more information.

  • www.aaon.com

    29

    Feature 4 Additional Controls

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None A = Phase and Brown Out Protection - Voltage monitor that is used to protect motors and compressors from voltage imbalance, over/under voltage and phase loss. Reset is automatic. B = Return and Supply Air Firestats - Bimetallic snap-action safety switches sensing temperature only, mounted in both the supply and return air streams. The supply air switch is rated to 200F and the return air switch is rated to 125F. Both switches manually reset and are wired to shut down the 24 VAC control circuit. Firestats are non-addressable. C = Return Air Smoke Detector - Photoelectric type smoke detector factory mounted in the return air section of the unit. Detector is wired to shut down the 24 VAC control circuit upon detector activation, thereby shutting off the unit. Relay contacts are provided for interfacing the detector with alarm panels. A test magnet is supplied in the unit controls cabinet. Smoke detectors are non-addressable. D = Phase and Brown Out Protection + Return and Supply Air Firestats - Options A + B E = Phase and Brown Out Protection + Return Air Smoke Detector - Options A + C F = Return and Supply Air Firestats + Return Air Smoke Detector - Options B + C G = Phase and Brown Out Protection + Return and Supply Air Firestats + Return Air Smoke Detector - Options A + B + C

  • www.aaon.com

    30

    Feature 5A Return Air Damper Position

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None F = Front - Mixing box with return air damper located on the front of the mixing box. Damper includes its own independent actuator. L = Left Hand - Front Outside Air Damper Required - Mixing box with return air damper located on the left hand side of the mixing box. Damper is manually adjustable fixed position or will include its own independent actuator. Outside air damper must be located on the front of the mixing box (Feature 5B). R = Right Hand - Front Outside Air Damper Required - Mixing box with return air damper located on the right hand side of the mixing box. Damper is manually adjustable fixed position or will include its own independent actuator. Outside air damper must be located on the front of the mixing box (Feature 5B). T = Top - Front Outside Air Damper Required - Mixing box with return air damper located on the top of the mixing box. Damper is manually adjustable fixed position or will include its own independent actuator. Outside air damper must be located on the front of the mixing box (Feature 5B).

    Feature 5B Outside Air Damper Position

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None F = Front - Mixing box with outside air damper located on the front of the mixing box. Damper includes its own independent actuator. L = Left Hand - Front Return Air Damper Required - Mixing box with outside air damper located on the left hand side of the mixing box. Damper is manually adjustable fixed position or will include its own independent actuator. Return air damper must be located on the front of the mixing box (Feature 5A). R = Right Hand - Front Return Air Damper Required - Mixing box with outside air damper located on the right hand side of the mixing box. Damper is manually adjustable fixed position or will include its own independent actuator. Return air damper must be located on the front of the mixing box (Feature 5A). T = Top - Front Return Air Damper Required - Mixing box with outside air damper located on the top of the mixing box. Damper is manually adjustable fixed position or will include its own independent actuator. Return air damper must be located on the front of the mixing box (Feature 5A).

  • www.aaon.com

    31

    Feature 5C Mixing Box Damper Control

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None A = 2 Position Actuator - Two position actuators on the return air and outside air mixing box dampers. Position one is the closed position. Position two is the fully open position, which is activated when there is a call for supply fan operation. The actuators are spring return closed. B = Fully Modulating Actuator - Fully modulating actuators on the return air and outside air mixing box dampers. Position one is the closed position. Position two is the minimum outside air position, which is activated when there is a call for supply fan operation. During the economizer mode the outside air actuator modulates between minimum position and having the outside air dampers fully open to maintain a discharge temperature of 55F. The minimum outside air position can be field adjusted for the desired amount of outside air. The actuators are spring return closed. C = Fixed Position Dampers - Manually adjustable fixed position return air and outside air mixing box dampers.

    Feature 6A Pre Filter Box

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None A = 2 Pleated Pre Filter - 30% Efficient - 2 inch pleated, 30% efficient, MERV 8 pre filters mounted in a pre filter box downstream of the return and outside air openings. B = 4 Pleated Pre Filter - 30% Efficient - 4 inch pleated, 30% efficient, MERV 8 pre filters mounted in a pre filter box downstream of the return and outside air openings. C = 4 Pleated Pre Filter - 65% Efficient - MERV 11 - 4 inch pleated, 65% efficient, MERV 11 pre filters mounted in a pre filter box downstream of the return and outside air openings. D = 4 Pleated Pre Filter - 85% Efficient - MERV 13 - 4 inch pleated, 85% efficient, MERV 13 pre filters mounted in a pre filter box downstream of the return and outside air openings. E = 4 Pleated Pre Filter - 95% Efficient - MERV 14 - 4 inch pleated, 95% efficient, MERV 14 pre filters mounted in a pre filter box downstream of the return and outside air openings. F = 2 Pleated Pre Filter - 30% Efficient with 4 Pleated Pre Filter - 30% Efficient - 2 inch pleated, 30% efficient, MERV 8 pre filters mounted upstream of 4 inch pleated, 30% efficient, MERV 8 pre filters mounted in a pre filter box downstream of the return and outside air openings.

  • www.aaon.com

    32

    Feature 6A - Pre Filter Box Continued G = 2 Pleated Pre Filter - 30% Efficient with 4 Pleated Pre Filter - 65% Efficient - MERV 11 - 2 inch pleated, 30% efficient, MERV 8 pre filters mounted upstream of 4 inch pleated, 65% efficient, MERV 11 pre filters mounted in a pre filter box downstream of the return and outside air openings. H = 2 Pleated Pre Filter - 30% Efficient with 4 Pleated Pre Filter - 85% Efficient - MERV 13 - 2 inch pleated, 30% efficient, MERV 8 pre filters mounted upstream of 4 inch pleated, 85% efficient, MERV 13 pre filters mounted in a pre filter box downstream of the return and outside air openings. J = 2 Pleated Pre Filter - 30% Efficient with 4 Pleated Pre Filter - 95% Efficient - MERV 14 - 2 inch pleated, 30% efficient, MERV 8 pre filters mounted upstream of 4 inch pleated, 95% efficient, MERV 14 pre filters mounted in a pre filter box downstream of the return and outside air openings.

    Feature 6B Unit Filter Type

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None A = 2 Pleated Unit Filter - 30% Efficient - 2 inch pleated, 30% efficient, MERV 8 unit filters mounted adjacent and upstream of the evaporator coil . B = 4 Pleated Unit Filter - 30% Efficient - 4 inch pleated, 30% efficient, MERV 8 unit filters mounted adjacent and upstream of the evaporator coil. C = 4 Pleated Unit Filter - 65% Efficient - MERV 11 - 4 inch pleated, 65% efficient, MERV 11 unit filters mounted adjacent and upstream of the evaporator coil. D = 4 Pleated Unit Filter - 85% Efficient - MERV 13 - 4 inch pleated, 85% efficient, MERV 13 unit filters mounted adjacent and upstream of the evaporator coil. E = 4 Pleated Unit Filter - 95% Efficient - MERV 14 - 4 inch pleated, 95% efficient, MERV 14 unit filters mounted adjacent and upstream of the evaporator coil. F = 2 Pleated Unit Filter - 30% Efficient with 4 Pleated Unit Filter - 30% Efficient - 2 inch pleated, 30% efficient, MERV 8 unit filters mounted upstream of 4 inch pleated, 30% efficient, MERV 8 unit filters mounted adjacent and upstream of the evaporator coil. G = 2 Pleated Unit Filter - 30% Efficient with 4 Pleated Unit Filter - 65% Efficient - MERV 11 - 2 inch pleated, 30% efficient, MERV 8 unit filters mounted upstream of 4 inch pleated, 65% efficient, MERV 11 unit filters mounted adjacent and upstream of the evaporator coil. H = 2 Pleated Unit Filter - 30% Efficient with 4 Pleated Unit Filter - 85% Efficient - MERV 13 - 2 inch pleated, 30% efficient, MERV 8 unit filters mounted upstream of 4 inch pleated, 85% efficient, MERV 13 unit filters mounted adjacent and upstream of the evaporator coil. J = 2 Pleated Unit Filter - 30% Efficient with 4 Pleated Unit Filter - 95% Efficient - MERV 14 - 2 inch pleated, 30% efficient, MERV 8 unit filters mounted upstream of 4 inch pleated, 95% efficient, MERV 14 unit filters mounted adjacent and upstream of the evaporator coil.

  • www.aaon.com

    33

    Feature 6C Final Filter Box

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None A = 2 Pleated Final Filter - 30% Efficient - 2 inch pleated, 30% efficient, MERV 8 final filters mounted downstream of the supply fan and heating. B = 4 Pleated Final Filter - 65% Efficient - MERV 11 - 4 inch pleated, 65% efficient, MERV 11 final filters mounted downstream of the supply fan and heating. C = 4 Pleated Final Filter - 85% Efficient - MERV 13 - 4 inch pleated, 85% efficient, MERV 13 final filters mounted downstream of the supply fan and heating. D = 4 Pleated Final Filter - 95% Efficient - MERV 14 - 4 inch pleated, 95% efficient, MERV 14 final filters mounted downstream of the supply fan and heating. E = 2 Pleated Final Filter - 30% Efficient with 4 Pleated Final Filter - 65% Efficient - MERV 11 - 2 inch pleated, 30% efficient, MERV 8 final filters mounted upstream of 4 inch pleated, 65% efficient, MERV final filters mounted downstream of the supply fan and heating. F = 2 Pleated Final Filter - 30% Efficient with 4 Pleated Final Filter - 85% Efficient - MERV 13 - 2 inch pleated, 30% efficient, MERV 8 final filters mounted upstream of 4 inch pleated, 85% efficient, MERV 13 final filters mounted downstream of the supply fan and heating. G = 2 Pleated Final Filter - 30% Efficient with 4 Pleated Final Filter - 95% Efficient - MERV 14 - 2 inch pleated, 30% efficient, MERV 8 final filters mounted upstream of 4 inch pleated, 95% efficient, MERV 14 final filters mounted downstream of the supply fan and heating.

    Feature 7 Filter Options

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None *A = Clogged Filter Switch (CFS) - Adjustable differential pressure switch sensing pressure drop across the unit filter bank and cooling coil. The range of adjustment is 0.17 to 5.0 in. W.C. with contact closure on rise. The switch is mounted in the fan compartment with terminal connections in the low voltage control section. Normally open dry contacts (C1 and C2) are provided for clogged filter indication. *B = Magnehelic Gauge - Magnehelic gauge reading pressure drop across the filter bank and cooling coil. The gauge reads from 0 to 3 in. W.C. in 0.10 in. graduations, and is mounted in the control cabinet. *C = Clogged Filter Switch + Magnehelic Gauge - Options A + B *A Special Pricing Authorization (SPA) is required if the CFS or Magnehelic gauge is to be used to respond to the pressure drop across only the cooling coil.

  • www.aaon.com

    34

    Figure 3 - Magnehelic Gauge

    Feature 8 Coil Coating

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard A = Polymer E-Coated Cooling and Heating Coils - Polymer e-coating applied to both the cooling and heating coils. Complete coil and casing are coated. Coating exceeds a 6,000 hour salt spray test per ASTM B 117-90 requirements, yet is only 0.8-1.2 mils thick and has excellent flexibility. Option is intended for use in coastal saltwater conditions under the stress of heat, salt, sand and wind and is applicable to all corrosive environments where a polymer e-coating is acceptable. Coating includes a 5 year non-prorated warranty.

  • www.aaon.com

    35

    Feature 9 Expansion Valve

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = None - Chilled water cooling or heating only air handling unit. A = Thermal Expansion Valves - Factory installed thermal expansion valve on the evaporator coils. Expansion valve sensing bulb must be field installed on the suction line.

    Feature 10 Expansion Valve Controls

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = None - No DX cooling coil. A = Standard Control - Factory installed standard thermal expansion valve control.

    Feature 11 Exterior Corrosion Protection

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None A = AAON Gray Exterior Paint - Cabinet exterior is primer washed then spray coated with a two-part polyurethane, heat-baked exterior paint. The paint is gray in color and capable of withstanding at least 2,500 hours, with no visible corrosive effects, when tested in a salt spray and fog atmosphere in accordance with the ASTM B 117-95 test procedure. B = Special Price Authorization with Special Paint - If a special paint color is specified, a set-up charge and price add per unit is required. Use this designation if other special paint options are necessary. The Applications Department must issue a Special Pricing Authorization (SPA) to include a non-standard option.

  • www.aaon.com

    36

    Feature 12 Tonnage

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None - Chilled water cooling or heating only air handling unit. A = 2 ton Capacity - Two ton capacity matching condensing unit. B = 3 ton Capacity - Three ton capacity matching condensing unit. C = 4 ton Capacity - Four ton capacity matching condensing unit. D = 5 ton Capacity - Five ton capacity matching condensing unit. E = 6 ton Capacity - Six ton capacity matching condensing unit. F = 7 ton Capacity - Seven ton capacity matching condensing unit. G = 8 ton Capacity - Eight ton capacity matching condensing unit. H = 10 ton Capacity - Ten ton capacity matching condensing unit. J = 14 ton Capacity - Fourteen ton capacity matching condensing unit. K = 17 ton Capacity - Seventeen ton capacity matching condensing unit. L = 22 ton Capacity - Twenty two ton capacity matching condensing unit. M = 25 ton Capacity - Twenty five ton capacity matching condensing unit. N = 30 ton Capacity - Thirty ton capacity matching condensing unit. P = 31 ton Capacity - Thirty one ton capacity matching condensing unit. Q = 34 ton Capacity - Thirty four ton capacity matching condensing unit. R = 45 ton Capacity - Forty five ton capacity matching condensing unit. S = 55 ton Capacity - Fifty five ton capacity matching condensing unit. T = 63 ton Capacity - Sixty three ton capacity matching condensing unit.

    Feature 13 Added or Modified Systems

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None

  • www.aaon.com

    37

    Feature 14A GPM Cooling Coil

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None A = 1.5-2.5 gpm B = 2.6-7.0 gpm C = 7.1-14.0 gpm D = 14.1-24.0 gpm E = 24.1-40.0 gpm F = 40.1-80.0 gpm G = 80.1-150.0 gpm H = 150.1-250.0 gpm

    Feature 14B GPM Heating Coil

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None A = 1.5-2.5 gpm B = 2.6-7.0 gpm C = 7.1-14.0 gpm D = 14.1-24.0 gpm E = 24.1-40.0 gpm F = 40.1-80.0 gpm G = 80.1-150.0 gpm H = 150.1-250.0 gpm

  • www.aaon.com

    38

    Feature 15 Control Panel

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = None A = Small Control Panel - 12 x 12 - Small external control panel which can be attached to the unit or located near the unit. Six feet of separate control wiring with conduit and power wiring with conduit is factory provided between the control panel and unit. B = Medium Control Panel - 25 x 22 - Medium external control panel which can be attached to the unit or located near the unit. Six feet of separate control wiring with conduit and power wiring with conduit is factory provided between the control panel and unit. C = Large Control Panel - 48 x 22 - Large external control panel which can be attached to the unit or located near the unit. Six feet of separate control wiring with conduit and power wiring with conduit is factory provided between the control panel and unit.

    Feature 16 Blank

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None

    Feature 17 Blank

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None

  • www.aaon.com

    39

    Feature 18 Blank

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None

    Feature 19 Blank

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None

    Feature 20 Blank

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None

    Feature 21 Blank

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - None

  • www.aaon.com

    40

    Feature 22 Warranty

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard - 1 Year Parts - Parts only warranty for a period of 12 months from the date of equipment startup or 18 months from the date of shipment, whichever is less.

    Feature 23 Type

    Example: H3-ARA-3-0-141C-12E:AABB-0C0-FTB-0G0-00AAAC0-00-A00000000

    0 = Standard X = Special Price Authorization - The Applications Department must issue a Special Pricing Authorization (SPA) to include a non-standard option.

  • www.aaon.com

    41

    General Data Unit Information

    Table 3 - A Cabinet (up to 1,200 cfm) Information

    Model H3-A V3-A

    Evaporator Coil

    Number of Circuits 1 or 2, Interlaced Quantity/Face Area 1/2.2 ft2

    Rows/fpi 4, 6 or 8/8, 10 or 12

    Chilled Water Cooling Coil

    Quantity/Face Area 1/2.2 ft2

    Rows/fpi 4, 6 or 8/8, 10 or 12 (Double, Single, Half or Quarter Serpentine) Standard Coil Single Serpentine with 10 fpi

    Electric Heat Capacity (kW) 230/460V 3 7, 14

    208V 3 5.3, 10.5

    Stages 7 kW - 1 or Fully Modulating with SCR 14 kW

    - 1, 2 or Fully Modulating with SCR

    Hot Water Heating Coil

    Quantity/Face Area 1/2.19 ft2 Rows/fpi 1 or 2/10 (Single, Half or Quarter Serpentine)

    Standard Coil 1 Row Single Serpentine 10 fpi

    Steam Heating Coil

    Quantity/Face Area 1/2.19 ft2 Rows/fpi 1 or 2/10 (Single Serpentine)

    Standard Coil 1 Row Single Serpentine 10 fpi

    Supply Fans

    Quantity/Type 1/ Direct Drive Backward Curved Plenum

  • www.aaon.com

    42

    Table 4 - B Cabinet (up to 2,000 cfm) Information

    Model H3-B V3-B

    Evaporator Coil

    Number of Circuits 1 or 2, Interlaced Quantity/Face Area 1/3.5 ft2 1/3.7 ft2

    Rows/fpi 4, 6 or 8/8, 10 or 12

    Chilled Water Cooling Coil

    Quantity/Face Area 1/3.54 ft2 1/3.44 ft2

    Rows/fpi 4, 6 or 8/8, 10 or 12 (Double, Single, Half or Quarter Serpentine) Standard Coil Single Serpentine with 10 fpi

    Electric Heat Capacity (kW) 230/460V 3 7, 14, 21, 28

    208V 3 5.3, 10.5, 15.8, 21

    Stages

    7 kW - 1 or Fully Modulating with SCR 14 kW - 1, 2 or Fully Modulating with SCR

    21 kW - 1, 2, 3 or Fully Modulating with SCR 28 kW

    - 2, 3, 4 or Fully Modulating with SCR

    Hot Water Heating Coil

    Quantity/Face Area 1/3.54 ft2 1/3.44 ft2 Rows/fpi 1 or 2/10 (Single, Half or Quarter Serpentine)

    Standard Coil 1 Row Single Serpentine 10 fpi

    Steam Heating Coil

    Quantity/Face Area 1/3.54 ft2 1/3.44 ft2 Rows/fpi 1 or 2/10 (Single Serpentine)

    Standard Coil 1 Row Single Serpentine 10 fpi

    Supply Fans

    Quantity/Type 1/Belt Driven or Direct Drive Backward Curved Plenum

  • www.aaon.com

    43

    Table 5 - C Cabinet (up to 4,000 cfm) Information

    Model H3-C V3-C

    Evaporator Coil

    Number of Circuits 1 or 2, Interlaced Quantity/Face Area 1/7.2 ft2 1/7.1 ft2

    Rows/fpi 4, 6 or 8/8, 10 or 12

    Chilled Water Cooling Coil

    Quantity/Face Area 1/7.22 ft2

    Rows/fpi 4, 6 or 8/8, 10 or 12 (Double, Single, Half or Quarter Serpentine) Standard Coil Single Serpentine with 10 fpi

    Electric Heat Capacity (kW) 230/460V 3 14, 21, 28, 35, 42

    208V 3 10.5, 15.8, 21.0, 26.3, 31.5

    Stages

    14 kW - 1, 2 or Fully Modulating with SCR 21 kW - 1, 2, 3 or Fully Modulating with SCR 28 kW - 2, 3, 4 or Fully Modulating with SCR 35 kW - 2, 3, 4 or Fully Modulating with SCR 42 kW

    - 3, 4 or Fully Modulating with SCR

    Hot Water Heating Coil

    Quantity/Face Area 1/7.22 ft2 Rows/fpi 1 or 2/10 (Single, Half or Quarter Serpentine)

    Standard Coil 1 Row Single Serpentine 10 fpi

    Steam Heating Coil

    Quantity/Face Area 1/7.22 ft2 Rows/fpi 1 or 2/10 (Single Serpentine)

    Standard Coil 1 Row Single Serpentine 10 fpi

    Supply Fans

    Quantity/Type 1 or 2/Belt Driven or Direct Drive Backward Curved Plenum

  • www.aaon.com

    44

    Table 6 - D Cabinet (up to 6,000 cfm) Information

    Model H3-D V3-D

    Evaporator Coil

    Number of Circuits 1 or 2, Interlaced Quantity/Face Area 1/10.3 ft2 1/10.2 ft2

    Rows/fpi 4, 6 or 8/8, 10 or 12

    Chilled Water Cooling Coil

    Quantity/Face Area 1/10.28 ft2 1/10.38 ft2

    Rows/fpi 4, 6 or 8/8, 10 or 12 (Double, Single, Half or Quarter Serpentine) Standard Coil Single Serpentine with 10 fpi

    Connection Sizes

    Electric Heat Capacity (kW) 230/460V 3 14, 21, 28, 35, 42, 49, 56, 63, 70

    208V 3 10.5, 15.8, 21.0, 26.3, 31.5, 37.0, 42.0, 47.3, 52.5

    Stages

    14 kW - 1, 2 or Fully Modulating with SCR 21 kW - 1, 2, 3 or Fully Modulating with SCR 28 kW - 2, 3, 4 or Fully Modulating with SCR 35 kW - 2, 3, 4 or Fully Modulating with SCR 42 kW - 3, 4 or Fully Modulating with SCR 49 kW - 3, 4 or Fully Modulating with SCR 56 kW - 3, 4 or Fully Modulating with SCR 63 kW - 3, 4 or Fully Modulating with SCR 70 kW

    - 4 or Fully Modulating with SCR

    Hot Water Heating Coil

    Quantity/Face Area 1/10.28 ft2 1/10.38 ft2 Rows/fpi 1 or 2/10 (Single, Half or Quarter Serpentine)

    Standard Coil Single Serpentine with 10 fpi

    Steam Heating Coil

    Quantity/Face Area 1/10.28 ft2 1/10.38 ft2 Rows/fpi 1 or 2/10 (Single Serpentine)

    Standard Coil Single Serpentine with 10 fpi

    Supply Fans

    Quantity/Type 1 or 2/Belt Driven or Direct Drive Backward Curved Plenum

  • www.aaon.com

    45

    Table 7 - E Cabinet (up to 10,000 cfm) Information

    Model H3-E V3-E

    Evaporator Coil

    Number of Circuits 1 or 2, Interlaced Quantity/Face Area 1/17.5 ft2 1/17.3 ft2

    Rows/fpi 4, 6 or 8/8, 10 or 12

    Chilled Water Cooling Coil

    Quantity/Face Area 1/17.19 ft2 1/17.57 ft2

    Rows/fpi 4, 6 or 8/8, 10 or 12 (Double, Single, Half or Quarter Serpentine) Standard Coil Single Serpentine with 10 fpi

    Electric Heat Capacity (kW) 230/460V 3 14, 21, 28, 35, 42, 49, 56, 63, 70, 77, 84

    208V 3 10.5, 15.8, 21.0, 26.3, 31.5, 37.0, 42.0, 47.3, 52.5, 57.8, 63.0

    Stages

    14 kW - 1, 2 or Fully Modulating with SCR 21 kW - 1, 2, 3 or Fully Modulating with SCR 28 kW - 2, 3, 4 or Fully Modulating with SCR 35 kW - 2, 3, 4 or Fully Modulating with SCR 42 kW - 3, 4 or Fully Modulating with SCR 49 kW - 3, 4 or Fully Modulating with SCR 56 kW - 3, 4 or Fully Modulating with SCR 63 kW - 3, 4 or Fully Modulating with SCR 70 kW - 4 or Fully Modulating with SCR 77 kW - 4 or Fully Modulating with SCR 84 kW

    - 4 or Fully Modulating with SCR

  • www.aaon.com

    46

    Table 8 - E Cabinet (up to 10,000 cfm) Information Continued

    Model H3-E V3-E

    Hot Water Heating Coil

    Quantity/Face Area 1/17.19 ft2 1/17.57 ft2 Rows/fpi 1 or 2/10 (Single, Half or Quarter Serpentine)

    Standard Coil Single Serpentine with 10 fpi

    Steam Heating Coil

    Quantity/Face Area 1/17.19 ft2 1/17.57 ft2 Rows/fpi 1 or 2/10 (Single Serpentine)

    Standard Coil Single Serpentine with 10 fpi

    Supply Fans

    Quantity/Type 1 or 2/Belt Driven or Direct Drive Backward Curved Plenum

    Table 9 - Chilled Water and Hot Water Coil Connection Sizes Coil gpm Sweat Connection Size (inches) 1.5-2.5 5/8 2.6-7.0 7/8 7.1-14.0 1 1/8 14.1-24.0 1 3/8 24.1-40.0 1 5/8 40.1-80.0 2 1/8 80.1-150.0 2 5/8 150.1-250.0 3 1/8

  • www.aaon.com

    47

    Filter Information

    Table 10 - H3 Series A Cabinet Pre Filters Feature 6A (Quantity) Size Type

    0 No Pre Filters A (1) 16 x 25 x 2 Pleated, 30% Eff, MERV 8 B

    (1) 16 x 25 x 4

    Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14

    F

    (1) 16 x 25 x 2 and (1) 16 x 25 x 4

    Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8

    G Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11

    H Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff, MERV 13

    J Pleated, 30% Eff, MERV 8 and Pleated, 95% Eff, MERV 14

    Table 11 - V3 Series A Cabinet Pre Filters Feature 6A (Quantity) Size Type

    0 No Pre Filters A (1) 16 x 25 x 2 Pleated, 30% Eff, MERV 8 B

    (1) 16 x 25 x 4

    Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14

    F

    (1) 16 x 25 x 2 and (1) 16 x 25 x 4

    Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8

    G Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11

    H Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff, MERV 13

    J Pleated, 30% Eff, MERV 8 and Pleated, 95% Eff, MERV 14

  • www.aaon.com

    48

    Table 12 - H3 Series B Cabinet Pre Filters Feature 6A (Quantity) Size Type

    0 No Pre Filters A (2) 16 x 20 x 2 Pleated, 30% Eff, MERV 8 B

    (2) 16 x 20 x 4

    Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14

    F

    (2) 16 x 20 x 2 and (2) 16 x 20 x 4

    Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8

    G Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11

    H Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff, MERV 13

    J Pleated, 30% Eff, MERV 8 and Pleated, 95% Eff, MERV 14

    Table 13 - V3 Series B Cabinet Pre Filters Feature 6A (Quantity) Size Type

    0 No Pre Filters A (1) 24 x 24 x 2 Pleated, 30% Eff, MERV 8 B

    (1) 24 x 24 x 4

    Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14

    F

    (1) 24 x 24 x 2 and (1) 24 x 24 x 4

    Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8

    G Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11

    H Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff, MERV 13

    J Pleated, 30% Eff, MERV 8 and Pleated, 95% Eff, MERV 14

  • www.aaon.com

    49

    Table 14 - H3 Series C Cabinet Pre Filters Feature 6A (Quantity) Size Type

    0 No Pre Filters

    A (2) 20 x 20 x 2" and (1) 16 x 20 x 2" Pleated, 30% Eff, MERV 8

    B (2) 20 x 20 x 4" and

    (1) 16 x 20 x 4"

    Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14

    F (2) 20 x 20 x 2" and

    (1) 16 x 20 x 2" and

    (2) 20 x 20 x 4" and (1) 16 x 20 x 4"

    Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8

    G Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11

    H Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff, MERV 13

    J Pleated, 30% Eff, MERV 8 and Pleated, 95% Eff, MERV 14

    Table 15 - V3 Series C Cabinet Pre Filters Feature 6A (Quantity) Size Type

    0 No Pre Filters A (4) 16 x 20 x 2 Pleated, 30% Eff, MERV 8 B

    (4) 16 x 20 x 4

    Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14

    F

    (4) 16 x 20 x 2 and (4) 16 x 20 x 4

    Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8

    G Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11

    H Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff, MERV 13

    J Pleated, 30% Eff, MERV 8 and Pleated, 95% Eff, MERV 14

  • www.aaon.com

    50

    Table 16 - H3 Series D Cabinet Pre Filters Feature 6A (Quantity) Size Type

    0 No Pre Filters

    A (1) 20 x 20 x 2 and (4) 16 x 20 x 2" Pleated, 30% Eff, MERV 8

    B (1) 20 x 20 x 4 and

    (4) 16 x 20 x 4"

    Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14

    F (1) 20 x 20 x 2 and

    (4) 16 x 20 x 2" and

    (1) 20 x 20 x 4 and (4) 16 x 20 x 4"

    Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8

    G Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11

    H Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff, MERV 13

    J Pleated, 30% Eff, MERV 8 and Pleated, 95% Eff, MERV 14

    Table 17 - V3 Series D Cabinet Pre Filters Feature 6A (Quantity) Size Type

    0 No Pre Filters

    A (2) 20 x 20 x 2 and (4) 16 x 20 x 2" Pleated, 30% Eff, MERV 8

    B (2) 20 x 20 x 4 and

    (4) 16 x 20 x 4"

    Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14

    F (2) 20 x 20 x 2 and

    (4) 16 x 20 x 2" and

    (2) 20 x 20 x 4 and (4) 16 x 20 x 4"

    Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8

    G Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11

    H Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff, MERV 13

    J Pleated, 30% Eff, MERV 8 and Pleated, 95% Eff, MERV 14

  • www.aaon.com

    51

    Table 18 - H3 Series E Cabinet Pre Filters Feature 6A (Quantity) Size Type

    0 No Pre Filters A (10) 16 x 20 x 2 Pleated, 30% Eff, MERV 8 B

    (10) 16 x 20 x 4

    Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14

    F

    (10) 16 x 20 x 2 and (10) 16 x 20 x 4

    Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8

    G Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11

    H Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff, MERV 13

    J Pleated, 30% Eff, MERV 8 and Pleated, 95% Eff, MERV 14

    Table 19 - V3 Series E Cabinet Pre Filters Feature 6A (Quantity) Size Type

    0 No Pre Filters

    A (3) 20 x 20 x 2 and (6) 16 x 20 x 2" Pleated, 30% Eff, MERV 8

    B (3) 20 x 20 x 4 and

    (6) 16 x 20 x 4"

    Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 14

    F (3) 20 x 20 x 2 and (6) 16 x 20 x 2"

    and (3) 20 x 20 x 4 and

    (6) 16 x 20 x 4"

    Pleated, 30% Eff, MERV 8 and Pleated, 30% Eff, MERV 8

    G Pleated, 30% Eff, MERV 8 and Pleated, 65% Eff, MERV 11

    H Pleated, 30% Eff, MERV 8 and Pleated, 85% Eff, MERV 13

    J Pleated, 30% Eff, MERV 8 and Pleated, 95% Eff, MERV 14

  • www.aaon.com

    52

    Table 20 - H3 Series A Cabinet Unit Filters Feature 6B (Quantity) Size Type

    0 No Unit Filters A (1) 16 x 25 x 2 Pleated, 30% Eff, MERV 8 B

    (1) 16 x 25 x 4

    Pleated, 30% Eff, MERV 8 C Pleated, 65% Eff, MERV 11 D Pleated, 85% Eff, MERV 13 E Pleated, 95% Eff, MERV 1