GU320A Controller Manual 1 CONTENT 1. Introduction…………………………………………………………………….…….2 2. Shape and connection of the controller………………………………………..2 3. Operation panel……………………………………………………………………...5 4. Installation guide.…………………………………………………………….……6 5. Instruction of control and operation………………………………………..7 6. Measuring data……………………………………………………………………..9 7. Warning, Pre-alarm and Stop Fault……………………………………………..10 8. Parameters setting…………….…………………………………………….…….11 9. LCD display and menu system…………………………………………………..13 10.Communication function……………………………………………………….……15 11.Preparation before use………………………………………………………...19 12.Troubleshooting…………………………………………………………………..22 PDF created with pdfFactory Pro trial version www.pdffactory.com

Transcript of GU320Acontrol Panel Operation Manual_EN_A4

Page 1: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

1

CONTENT

1. Introduction…………………………………………………………………….…….2 2. Shape and connection of the controller………………………………………..2 3. Operation panel……………………………………………………………………...5 4. Installation guide.…………………………………………………………….……6 5. Instruction of control and operation……………………………………….….7 6. Measuring data…………………………………………………………………….….9 7. Warning, Pre-alarm and Stop Fault……………………………………………..10

8. Parameters setting…………….…………………………………………….…….11 9. LCD display and menu system………………………………………………….….13

10. Communication function……………………………………………………….……15

11. Preparation before use……………………………………………………….…..19 12. Troubleshooting………………………………………………………………….….22

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 2: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

2

1. Introduction: GU320a is a kind of intelligent controller of generator which adopt high grade CMOS chip. It can configure the control procedure and protection parameters of the generator, including lots of function such as measuring, controlling, protection, three remote and so on, which completely satisfied the automatic controlling requirement of different generator sets for the generator user or factory. The controller measure and display all parameters the generator output, and the rotating speed, oil pressure, temperature, DC source voltage, running time of the engine and so on. All of the voltage measured in real virtual value to ensure the accuracy of the data. Including big LCD display and menu selection for Chinese and English. The keys on the control panel are used to select the control mode, start the running procedure, display data, and modify the running protection parameters. The LED indicates the operating mode of the controller and the running state of the generator sets. LCD display each measured parameter and state. The controller is integrated closely by aluminum alloy panel and steel shell which has been spurt powder. All connection of the controller are connected by pin-like terminal with lock, such device can be connected、moved 、maintained and replaced easily and conveniently. This manual is available for the generator intelligent controller GU320a only, which you should carefully read before use 2 Shape and wiring of the controller: 2.1 Detail size:

Control panel W205mm×H156mm Hatch for installation W186m ×H137m Thickness D68mm(unconnected)

131211109 161514C 2624 25D 17 222120 23 282718 19

A 1 B43 5 76 82

RS-CONNECTOR

NOTE:The shell of the controller should be grounded to earth, surge of the electricity system and transient shock to the

meter can be reduced by the perfect low ground impedance. Running temperature of the controller -20~50℃ Storage temperature of the controller -40~80℃

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 3: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

3

2.2 Connection port: Pin NO. Function Signal Line

A1 phase A V input 0-300VAC 1mm² line A2 Phase B V input 0-300VAC 1mm² line A3 Phase C V input 0-300VAC 1mm² line A4 N zero line 1mm² line

B5 A phase A input {S1} 0-5A(AC) 1mm² line B6 B phase A input {S1} 0-5A(AC) 1mm² line B7 C phase A input {S1} 0-5A(AC) 1mm² line B8 Current input common {S2} 0-5A(AC) 1mm² line

C9 Relay output common 1.5mm² line C10 Fuel electromagnetic valve relay output N.O dry contact, 10A/30VDC 1.5mm² line C11 Start relay output N.O dry contact, 10A/30VDC 1.5mm² line C12 Exciter source of charger output Forbid to cathode when no use 1mm² line C13 Gen. Set running output N.O dry contact,3A/30VDC 1mm² line C14 Fault alarm output N.O dry contact,3A/30VDC 1mm² line C15 Pre-alarm output N.O dry contact,3A/30VDC 1mm² line C16 Idle output N.O dry contact,3A/30VDC 1mm² line

D17 Pressure detection P-sensor 1mm² line D18 Temperature detection T-sensor 1mm² line D19 standby Measure 0~5Vdc 1mm² line D20 Pressure signal Low potential valid 1mm² line D21 Temperature signal Low potential valid 1mm² line D22 E.stop signal Low potential valid 1mm² line D23 Start (external control) signal Low potential valid D24 Standby signal measure Low potential valid 1mm²line D25 Magnetic sensor signal{+} D26 Magnetic sensor signal{-}

1-35Vac connected to cathode of the DC source inside

Two-core shield

D27 Operating source {+} 1mm² line D28 Operating source {-}

12V/24V (8-35VDC) 1mm² line

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 4: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

4

2.3 Typical wiring diagram:

Loading output

(3P&N)

G

AUX

SUP

PLY

9 F5

(10

A)

DCV

(8-3

5VD

C)

27

28

+-

(2A)

F4

(Cr

ank)

油门

(Fue

l)起动

10

充电机

12

14

13

11

T-sensor

Pressure

Temperature

E.stop

Remote start

P-sensor

16

15

20

17

23

21

22

Spe

ed s

enso

r(PI

CK-U

P)

26

25

19

18

86 732 54

F2

F3

IDLE

RUNNING

1

Generator

F1

FAULT

PRE.ALARM

RS CONNECTOR

Standby(0~5Vdc)

24

(standby)

Note:

cathode of

the bat

tery an

d sh

ell of

the

con

toll

er must

be

gro

unde

d to

earth

prope

rly

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 5: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

5

3 Operation panel The whole Operation panel is divided into three parts: LED display for measuring parameters、operating keys and running-status LED indicate。 3.1 LCD and its controlling keys LCD with 128×64mm lattice can display multiple lines of data information simultaneously and additive background-light function which make operators read information whenever day or night. To turnoff the background-light, just keep pressing any key for a while.

LCD and its control keys provide a friendly operating interface for operators, operators can read information and setting running parameters conveniently.

3.2 LCD display of menu system and running state

Function Name

Entering submenu/modify/confirming modification

Scroll up menu/ value ascend

Scroll down menu/ value descend

3.3 Operating keys and LED Function Name

AUTO key/LED The key is used for “auto-operate mode”. Running in this mode, the LED above the button will illuminate. According to the “remote control startup input signal”, the controller determines whether the generator startup or not.

MAN Key / Indicator Light The key is used for “manual-operation mode”. Running in this mode, the LED above the button will illuminate. By pressing “START” and “STOP” key, the controller will start or stop the generator.

TEST Key/ Indicator Light The key is used for testing operation mode settings. Running in this mode, the indicator light on the key on. Here, when the “remote control startup input signal” simulated by the controller is valid, the generator startup. When it switch other mode, the generator stops.

START Key/LED The key is used for generators manually startup. And when the controller is in “manual-operation mode”, press this key to start the generator. Till the controller performing the start procedure to the Gen set run in normal, the LED above the key on. After the Gen set running normally, the LED above the key on.

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 6: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

6

STOP/RESET key/LED Used to stop the generator by hand, when the controller set in “MAN” mode, this key could stop the generator. Press this key more than 2 seconds can release the fault stop lock if there is fault output. (When the controller performing the stop procedure, the indicator light above the key illuminate. If failed to stop, the light flash.)

LAMP TEST /MUTE key Alarm mute and lamp test key. Press the key more than 2 seconds, all LEDs on the panel will light. It used to test all LEDs on the panel. When Pre-alarm or fault alarm occur, press this key can mute the buzzer. At the same time the light above the key illuminate. Press it again will cancel mute. If the controller still in fault, the buzzer will keep alarm.

4 Installation guide 4.1 Hatch size for panel installation as the figure attached.

Four special screws fix the controller. If the shell of the controller is installed on the body of a generator directly or other violent vibratory device, preventing device must be installed.

4.2 Connection for control line please refer to the diagram attached and the typical wiring diagram 2.3 above.

4.3 Oil pressure and temperature sensor installation of the engine:

( )

D18GU320a CONTROLLER

D17 D18D17

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 7: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

7

5 Control and Operation Instruction There are three control modes: “AUTO”、 “MANUAL” and “TEST”。 5.1 Configuration for operating mode:

Operation Description

Press “AUTO” (for 2 seconds), the LED above illuminate, the controller then operating in “AUTO”

Press“MAN”key(for 2 seconds), the LED on the button will illuminate, then the controller runs in this mode.

Press “TEST” (for 2 seconds), the LED above illuminate, the controller then operating in “TEST”

NOTE: you can choose only one of the three modes.

When the controller is ready

Operation Description U=0V I=0A P=0kW F=0Hz SP=0rpm OP=0kPa TEMP=0℃ Bat=24V

When the controller can’t detect the running speed, pressure, temperature of the engine, the related data will be 0, and the LCD display:

RUN

5.2 Start and control process: Operation Description

When the controller run in TEST, or the remote control start signal able in Auto, or press “START” in MAN, the controller begin to delay the start procedure, the light above the key will bicker.

The LCD display the count for start delay (not in “MAN” ) START

00:09 Fuel relay action, the fuel electromagnetic valve of the engine open. After delay for 200 milliseconds, the start relay active and crank begin.

CRANK 1

When the running speed of the engine reach the crank cutout speed, the controller will stop the start output and begin the safety-on delay.

SAFETY-ON DELAY 00:08

U=380V I=0A P=0kW F=50Hz SP=1500rpm OP=465kPa TEMP=70℃ Bat=24V

After the controller has detected the normal running speed, output voltage, pressure, temperature has been setup, and no other fault the same time, then display the parameters as right. (Scroll page for detail)

RUN

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 8: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

8

When the remote control start signal valid, the start delay will active and begin to time. During the delay, if the remote start signal invalid, start delay will instantaneously stop, the controller will stop the start procedure, and return to original state“READY” after the time for fail to start out.

During cranking or idle, if the remote control start input signal is invalid, the controller stop the followed start procedure and close all output for relay control, then stop the start process and return to original state“READY” after the time for fail to start out.

Note: when cranking, the engine ignited, while the alternator output frequency reach the preset frequency, the start motor de-energized:

Or de-energized the motor through the following way a、 The magnetism speed pickup device mounted on the flywheel of the engine has detected the frequency reached preset. b、 The output voltage of the alternator reach 80% of the rated voltage. c、 The low oil pressure switch of the engine open.

5.3 Fail to Start and Restart Condition: Operation Description

During the cranking time, engine igniting is forbidden, and the controller remains crank intermission, it will not output starting signal. FAIL TO START indicator light flash.

CRK-RST 00:04

Once the crank intermission reach, the controller will attempt to start the engine again. CRANK 2

The phenomena above repeat again and again, until the engine reach the normal running parameters. While starting, if any stop fault occurs, the controller will stop controlling output instantly until the fault eliminated and reset, then it can be operated again. 5.4 Fail to start condition:

Operation Description When the phenomena above repeat again and again, the starting attempts exceed preset , the controller will stop controlling output. Then the LCD display:

ALARM: START FAILURE

NOTE:

If it occurs FAIL TO START fault, the operator must check the whole “Genset” system. and confirm the fault and eliminate them, then press “ STOP/RESET” key to unlock the fault-locking state, and reset the controller again.

5.5 Auto stop process Operation Description

When the remote start input signal is invalid, the cooling delay begin to count down, the running signal cut and the LCD then display:

COOL

02:34 While the cooling delay timeout, the controller disconnect the fuel valve, and count down for Fail To Stop, then the LCD display:

STOP 00:24

While the Fail To Start timeout, if the engine still run, the controller will sent an alarm, and the LCD display:

ALARM: STOP FAILURE

If the engine stop during the fail to stop permission delay, the LCD will display: READY

When the remote control start input signal is invalid, the cool delay begin, if the remote control start input signal is valid during the delay, the cooling delay time stop instantaneously, the controller monitor each parameter again, and reset Auto running state if normal. 5.6 Stop by “MAN”

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 9: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

9

Operation Description

The generator running normally, when press “STOP/RESET” key for a while in “MAN” mode, the controller begin cooling delay to stop as the Auto stop. Press the “STOP/RESET” key again for a while will disconnect the fuel valve, and the generator sets stop.

The Fail To Stop time begin, the LCD display: STOP 00:24

When the stop failed time beyond, the engine still run, the controller will send an alarm, the LCD will display:

ALARM: STOP FAILURE

The engine stop slowly during the Fail To Start permission time, and the LCD display: READY

5.7 The oil electromagnetic valve is the start running and stop process of the generator of normal open

type.( Different from normal closed type). Start control process:

When start running, oil relay of the controller take no action, no power in the oil electromagnetic valve, namely the oil electromagnetic magnet take no action. Stop control process:

The control at the begging of the stop control process output oil electromagnetic valve source, oil electromagnetic valve action, the engine begin to stop. Then powered down after for the delay according to the fail to start delay setting.

Other control process is the same to the engine of normal closed oil electromagnetic valve.

5.8 Idle Function While READY, the idle relay open, controller runs the start procedure, start delay begin to count down, the idle relay

active the same time. When startup and the start motor open, idle delay begin to countdown (if IDLE DELAY is set 0, the idle relay will open, then begin to safety-on delay, namely the controller has no idle function). When delay time out, the idle relay will open, the safety-on time begin and after each parameter run in normal, the generator sets run.

6 Measuring display data 6.1 Electricity measuring data

Gen. Phase V L1-N L2-N L3-N Gen. Line V L1-L2 L2-L3 L3-L1 Gen. A L1 L2 L3 Gen. HZ HZ Gen. KVA Sum of phase L1 L2 L3 Gen. KW Sum of phaseL1 L2 L3 Gen. PF Average of L1 L2 L3 Gen. KVAr Sum of phase L1 L2 L3 Gen. KWh Gen. KVArh

As the frequency measuring is from L1 phase of the generator, ensure no fault with this part before use.

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 10: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

10

6.2 Other measuring data Oil pressure(KPa) Obtain the data from an external sensor Coolant temperature(℃) Obtain the data from an external sensor Rotating speed (RPM) Obtain the data from speed sensor Total running time of the oil engine(h) Battery voltage (V)

7 Warning and Fault Stop 7.1 Warning

(NOTE: warning is a very serious alarm state, it won’t affect the generator system operation, only remind the operator of the improper condition. When warning occurs, the state indicator light illuminate, but the buzzer won’t alarm and the fault won’t lock. Once the fault has been eliminated, the warning light off automatically. Charge failure The controller detect the voltage lower than the “LOW battery pre-alarm setting” from the aux AC charger, “CHARGE FAILURE” indicator light illuminate, and the buzzer alarm. Baterry low The controller detect the battery voltage lower than the “Low battery pre-alarm value”, the state LCD will display “WARNING: BATTERY LOW”, and the buzzer warn. Low pressure After the safety-on delay timeout, and the controller detect the output pressure of the engine lower than the low pressure alarm value preset, the buzzer warn. The state LCD will display “WARNING:LOW OILPRESS” H temperature The controller detect the coolant temperature of the engine higher than the high temperature preset alarm value, and then the buzzer warn, the state screen display“WARNING:COOLANT TEMP” ,the buzzer warn. Overspeed If the running speed of the engine over the preset alarm value, the LCD will display “WARNING:OVER SPEED”,and the buzzer warn. Underspeed If the running speed of the engine descend to alarm level preset, then the state LCD display “WARNING:UNDER SPEED”,and the buzzer warn. High voltage If the controller detects the output voltage of the generator over the alarm value preset, the state LCD will display “WARNING: V HIGH”,and the buzzer warn. Low voltage If the controller detects output voltage lower than the alarm value preset, then the state LCD will display “WARNING:V LOW”,and the buzzer warn. Overcurrent If the controller detects the output current over the alarm value preset, then the state LCD display “WARNING: I HIGH”,and the buzzer warn. Standby input If set the aux input to a warning input, then if the signal at the input is valid, the LCD will display “WARNING:EXT. ALARM”,and the buzzer warn. 7.2 Stop Fault

(Note: “Stop fault” can lock the control system and stop the generator running. After the fault is eliminated, by pressing the “reset” key unlocking the fault lock, then you can operate the controller again.) Fail to Start If the engine starting times over the preset value, the engine still does not run, namely it occurs “Fail to Start.” The LCD will display“ALARM:START FAILURE”, The indicator light Fail to Start illuminate, and the buzzer warns. Fail to Stop If the generator fail to stop after the stop delay timeout, then the buzzer warn and the LCD display “ALARM: STOP FAILURE”。 Emergency stop When the emergency stop input signal is valid, the controller stop all output of the relay except the alarm, the LCD display “ALARM:E.STOP”,“EMERGENCY STOP” indicator light illuminate, and the buzzer warn. Low Oil Pressure After the safety-on time-delay timeout, the controller detects the oil pressure switch closed, the engine stop instantaneously, and the LCD display “ALARM: LOW OILPRESS”, the fault indicator light “LOW OIL PRESSURE”, the buzzer warn.

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 11: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

11

H Temperature The controller has detected the T-sensor switch of the engine closed, the engine stop instantaneously, the LCD display “ALARM:COOLANT TEMP”,and the indicator light“HIGH TEMPERATURE” illuminate, the buzzer warn. Overspeed The controller has detected the running speed of the engine beyond the overspeed fault setting value, the engine stop instantaneously, the LCD display “ALARM:OVER SPEED””,and the indicator light “OVERSPEED” illuminate, the buzzer warn. Under Speed The controller detects the running speed of the engine lower than the low speed fault value, the engine stop instantaneoussly, and the LCD display “ALARM:UNDER SPEED”,the buzzer warn. High Voltage The controller detect the output voltage of the generator higher than the high voltage fault value, the engine will stop after confirming the delay, and LCD display “ALARM:V HIGH”,the buzzer warn. Low Voltage After the safety-on delay timeout, the controller detect the output voltage of the generator lower than the low voltage fault value, the LCD will display “ALARM:V LOW””after confirming the delay,and the buzzer warn. Overcurrent The controller detect the output current of the controller higher than the over current fault value, the engine will stop after confirming the delay, and the LCD display “ALARM:I HIGH”,the buzzer warn. Standby Output If set the aux input to fault stop, then when the signal at the input is valid, the engine will stop instantaneously, and the LCD display “ALARM:EXT. ALARM”,the buzzer warn. NOTE:

u The data of low oil pressure pre-alarm is from the measuring of the oil pressure sensor, and the data of low pressure stop fault is from the measuring of the oil pressure sensor (set for no use at factory) or the oil pressure switch state.

u The data of high temperature pre-alarm is the water position from the measuring of the temperature sensor, and the data of high temperature stop fault is the water position from the measuring of the temperature sensor (set for no use at factory) or the temperature switch state.

u The rotating speed of the engine typically from the measuring frequency of the speed sensor mounted on the flywheel of the engine, if no speed sensor equipped in the system, the controller will take the voltage frequency of the generator output as the controlling and fault protection parameter. To be convenient for the user, part of the data is rotating speed, RPM=HZ*30.

u Generator fault during the running of the generator: stop instantaneously after the high temperature , or low pressure, or overspeed, or under speed occur. But the low speed and low pressure required the idle delay set to 0 (without idle function) to active protection, or it won't be active.

8 Parameter Setting 8.1 SYSTEM

NO. Item Preset Range 1.0 QUIT) 1.1 ( CT) 60 1~5000 1.2 VT) 1 1~100 1.3 Comm Address) 1 1~255 1.4 (Default settings) 1.5 Language> English/中文 English 中文/English 1.6 Firmware update

8.2 GENERATOR

NO. Item Preset Range 2.0 QUIT 2.1 V Low Alarm 0V AC45~20000V 0 (no setting) 2.2 V Low preALM 198V AC45~20000V 0 (no setting)

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 12: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

12

2.3 V High preALM 253V AC45~20000V 29999 (no setting) 2.4 V High Alarm 29999

3+V AC45~20000V 29999 (no setting)

2.5 I High preALM 9999A 0~9999A 9999 (no setting) 2.6 I High Alarm 9999A 0~9999A 9999 (no setting) 2.7 Alarm delay 10s 0~600s

8.3 ENGINE

NO. Item Preset Range 3.0 QUIT 3.1 Nominal speed 1500 99-9999 RPM 3.2 Pickup frequency 3000 1-9999 Hz 3.3 Set pickup now 3.4 Pair of Poles 2 1~4 3.5 Fuel mode 0 0~1 0(NC) 1 (NO) 3.6 T-sensor mode 0 0~8 0 (no use) 3.7 P-sensor mode 0 0~9 0 (no use) 3.8 H-sensor mode 0 0~1 0 (no use) 1 (use) 3.9 Start delay 10s 0~300 s 3.10 Crank attempt 3 1~10s 3.11 Crank time 8s 0~30 s 3.12 Crank reset 15s 0~300 s 3.13 Crank disconnect 300RPM 1-9999 RPM 3.14 Idle delay 0秒 0~9999s 3.15 Safety-on delay 60s 0~600s 3.16 Cooling delay 300s 0~600 s 3.17 Stop delay 20s 0~60s 3.18 Under SP Alarm 0 RPM 0-9999 RPM 0 (no setting) 3.19 Under SP preALM 1440 RPM 0-9999 RPM 0 (no setting) 3.20 Over SP preALM 1600 RPM 0-9999 RPM 9999 (no setting) 3.21 Over SP Alarm 1710 RPM 0-9999 RPM 9999 (no setting) 3.22 Oil-P low Alarm 140KPa 50~300Kpa 0 (no setting) 3.23 Oil-P low preALM 220KPa 50~300Kpa 0 (no setting) 3.24 Coolant preALM 95℃ 70~160℃ 9999 (no setting) 3.25 Coolant Alarm 105℃ 70~160℃ 9999 (no setting) 3.26 Batt low preALM 8.0V 1~25V 0 (no setting) 3.27 External. Alarm 0

3.28 External analog 2

0 unit V, 1 unit %, measuring 0-5v signal. 2 unit %, self determine the input according to the resistance type and sensor data.

8.4 Note for pressure and temperature sensor

Different type of P-sensor and T-sensor according to the table followed, if the sensor available is not in the table, then write the sensor parameter into the controller through the software, and the sensor setting in the parameter setting should be the last type “user define” Pressure sensor

NO. Type 0 NOT USE 1 VDO 10 bar 2 VDO 5 bar 3 Datcon 10 bar 4 Datcon 7 bar

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 13: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

13

5 Datcon 5 bar 6 Murphy 7 bar 7 CMB 812 8 KP-YV01 9 User define

Temperature sensor

NO. Type 0 NOT USE 1 VDO 120 degrees C 2 Datcon high 3 Datcon low 4 Murphy 5 Commis 6 TS120 7 KP-T01 8 User define

9 LCD and menu system

Display several lines of information at the same time according to the 128×64 lattice. LCD has background light.

Press any key for a while to turn off the background light. Set a different parameter in every page and controlled upon it,

each electricity parameter of load displayed in main page, press “ ”and“ ”scroll to display each electricity

parameter and measuring data. If there is no fault occur, LCD hold the main page, and when fault occur, LCD display the

fault information in the state screen instantaneously. When more than one fault occur, LCD display one fault state of them.

Press “ ”and“ ”refer to the running parameters. Increase and decrease by degrees to set and adjust the parameter. When press the increase or decrease key for a while,

the ones digit changes one by one, and then the tens digit change after ten changes, the rest may be deduced by analogy. Press“ ”in the main page two seconds to enter setting state, then press “ ”and“ ”to look over in the menu of the same level, and press “ ”to enter next submenu to select and adjust the item, press “ ”to adjust. When indicate to enter password, enter “ ” “ ” “ ”“ ”,then press“ ”two seconds to quit setting state.

9.1 Static LCD display:

When the controller is ready

Operation Description U=0V I=0A P=0kW F=0Hz SP=0rpm OP=0kPa TEMP= OPEN Bat=24V

While the controller hasn’t detected the running speed of the engine, if the P-sensor and T-sensor disconnect , the related data will display “OPEN”, and the LCD display:

RUN

Set the controller without T-sensor and P-sensor

Operation Description U=0V I=0A P=0kW F=0Hz SP=0rpm OP=---kPa TEMP= ---℃ Bat=24V

The controller won’t check the data such as pressure and temperature of the engine, the related data will display “— ”in ready or running, and the LCD display:

RUN

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 14: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

14

Controller running normally Operation Description

U=0V I=0A P=0kW F=0Hz SP=1500rpm OP=475kPa TEMP=80℃ Bat=25.4V

The current and voltage in this page is the average of the three phase.

RUN V1=220V U12=380V I1=0A A1=0kVA P1=0kW PF1=1.00 Q1=0kVAr

Press “ ”or“ ” to switch pages

RUN V2=220V U23=380V I2=0A A2=0kVA P2=0kW PF2=1.00 Q2=0kVAr

Press “ ”or“ ” to switch pages

RUN V3=220V U31=380V I3=0A A3=0kVA P3=0kW PF3=1.00 Q3=0kVAr

Press “ ”or“ ” to switch pages

RUN Run Hour=12 KWHr=1000 KVArHr=250 AI=0%

Press “ ”or“ ” to switch pages

RUN 9.2 Adjust the running parameter Example: (Set 1000/5 of the current transformer, the CT should be 200)

Operation Description

Press “ ”for two seconds to enter the configure menu, and then the LCD display:

<<SETTING/参数设定>>

0.QUIT

Press “ ”and“ ”key, then press “ ”, the LCD will display: 1. CT

=1000

Press “ ”, and then press “ ”will indicate to enter the password:

“ ” “ ” “ ” “ ”

1. CT

Password:****

Press“ ”or“ ”to vary the parameters, set to 200 at this time and the LCD then Indicate:

1. CT

=200

After the configuration, press “ ”to confirm, and then press “ ”

and“ ”key, the LCD then display:

<<SETTING/参数设定>>

1. System

Then press “ ”and“ ”to quit, or press “ ”key more than two seconds to exit, the LCD then display:

READY

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 15: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

15

Example: ( Set the start attempts of the controller to be 2) Operation Description

Press “ ”more than two seconds to enter the parameter setting menu, then the LCD display:

<<SETTING/参数设定>> 0.QUIT /退出

Press “ ”three times then press “ ”, then the LCD display: 3.ENGINE 0.QUIT

Press “ ”nine times and then press “ ”, the LCD will display: 9. Crank attempt =3

Press “ ”will indicate to enter password, enter the password: “ ”

“ ” “ ” “ ”

9. Crank attempt Password:****

Press “ ”or“ ”to vary the parameter. Set it to be 2 this time, press

“ ”to confirm, then press“ ”two seconds to exit the parameter setting menu.

9. Crank attempt =2

Example:( Reset all the parameters to be the default value at factory) Operation Description

Press “ ”two seconds to enter setting menu, then the LCD display: <<SETTING/参数设定>> 0.QUIT

Press “ ”and“ ”key, then press “ ”four times, the LCD

then display: 4. Default settings

Press “ ”and then indicate you to enter password, enter and set the

password to be :“ ” “ ” “ ” “ ”

4. Default settings Password:****

Press “ ”to default settings, then press “ ”before press “ ”for two seconds to exit the parameter setting menu.

4. Default settings DONE

Example:( Set the controller to line programming mode) Operation Description

Press “ ”for two seconds to enter parameter setting menu, then the LCD display:

<<SETTING/参数设定>> 0.QUIT

Press “ ”and“ ”key, then press “ ”one time, then the

LCD display: 6. Firmware update

Press “ ”key will indicate you to enter password(3132), enter the

password: “ ” “ ” “ ” “ ”

6. Firmware update Password:****

Then press “ ”to enter program mode. You should make sure the power supply is normal in this mode. The program will reset for use after correctly burn to record according to the program software, or it won’t exit, and you should remove the working source. Then the LCD display:

Firmware Update. Download from PC. Don’t turnoff power, Before finished!

Settings and operating for other parameters refer to above. 10 Function(optional, uses can select according to practice) 10.1 Introduction

The controller with an“RS CONNECTOR”communication port,which use match with the CI485A(CI232A)communication interface module, so as to made the controller possess RS485/RS232 serial communication port. The serial communication adopts the designing of photoelectric insulation, besides, it installed protective circuit to prevent the interference and spoil from the error connection. RS485 adopts 9600-baud communication. The controllers with communication function possess the following benefits.

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 16: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

16

100% Remote signaling including running states and fault ones. 100% remote measure data Include measurement data of all controllers. 100% Remote control function. Covering the whole control function of panel.

10.2 CI485 Communication Link (Controller with RS485 com and CI48A accessory), more details please refer to the following wiring

diagram:

(Controller with RS232 com and CI232A accessory ),more details please refer to the following wiring diagram:

The communication interface provides users a method, to make the users fetch more information that

cannot obtain from the panel. The relative software can display the whole parameters measured and state information; it also can set various parameters.

RS C

ON

NEC

TOR

G U320a C o ntro lle r C I485 A(D

B9)

A

SB (R S4 8 5)

Tra n sfo rm te rm ina l

RS C

ON

NEC

TOR

GU320a Controller CI232A

(DB9

)

MODEM

Computer

CI2

32A

Able to connected respectively

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 17: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

17

The controller with RS485 communication interface, which allows connect at least 255 same serial controllers to the same communication line. And each equipment has sole ID No. To switch PC or MODEM, you need to collocate another RS485/RS232 converter. Typical wiring diagram as below:

Note:Communication cable use high quality twisted pair cable with shielded, and its total length of cable less than 1000m. Each anode and cathode of RS485 interface must be connected properly, and the cable shield only can be connected to the earth at one side.

GU3

20a

Con

trolle

r

(DB9)

RS CONNECTOR

CI4

85A

A B S

Com

pute

r

GU3

20a

Con

trolle

r

RS CONNECTOR

(DB9)

CI4

85A

GU3

20a

Con

trolle

r

RS CONNECTOR

(DB9)

CI4

85A

MO

DEM

A

转换器

RS48

5/23

2

B S

Abl

e to

con

nect

resp

ectiv

ely

A B SBA S

R co

nnec

t to

risist

er

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 18: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

18

10.3 Central Pick-up Control Unit Communication Protocols RS485 mechanism is a kind of network form by character signal between the computer and hardware device. Controller working baud rate is 9600-Baud, communication protocol is MODBUS-RTU. When it is working, the computer will send out a serial orders to the central pick-up controller, and then wait the reflect data block.. NOTE: max byte (word) of write/read, read is 16, write is 14. Only continuous write order 10(hex)

could be used for write . Controller Data Cell Address Address Byte Content Unit

$1000 1 L3-N Voltage Ph-c phase voltage unit:V $1001 1 L2-N Voltage Ph-B phase voltage unit:V

$1002 1 L1-N Voltage Ph-A phase voltage unit:V $1003 1 L3-L1 Voltage AC phase and line voltage unit:V $1004 1 L2-L3 Voltage BC phase and line voltage unit:V $1005 1 L1-L2 Voltage AB phase and line voltage unit:V $1006 1 L3 Current Ph-c phase current unit:A

$1007 1 L2 Current ph-B phase current unit:A $1008 1 L1 Current ph-A phase current unit:A $1009 1 L3 PF ph-c PF $100A 1 L2 PF ph-B PF $100B 1 L1 PF ph-C PF $100C 1 Frequency Generator frequency unit:0.1HZ $100D 1 L3 VA Ph-C real power unit:KVA $100E 1 L2 VA Ph-B real power unit:KVA $100F 1 L1 VA Ph-A real power unit:KVA $1010 1 L3 W Ph-C active power unit:KW $1011 1 L2 W Ph-B active power unit:KW $1012 1 L1 W Ph-A active power unit:KW $1013 1 L3 VAr Ph-C reactive power unit:KVAr $1014 1 L2 Var Ph-B reactive power unit:KVAr $1015 1 L1 VAr Ph-A reactive power unit:KVAr $1016 1 Tacho Rotating speed of Speed sensor unit:RPM $1017 1 OilPress value of oil p-sensor unit:Kpa $1018 1 Coolant value of T-sensor unit:℃ $1019 1 VBAT Battery voltage unit:V $101A 1 VALT Charge excitation voltage unit:V $101B 1 AI input voltage standby unit:mV

bit0—oil pressure bit1—water temperature bit2—emergency stop bit3—remote control start

$101C 1

Bit4—switch signal standby bit0—diesel engine oil bit1—diesel engine start bit2—Gen.set run in normal bit3—Alarm output bit4—Pre-alarm output

$101D 1

bit5—Idle speed output $101E 1 LED $101F 1 Palarm Pre-alarm code

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 19: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

19

$1020 1 Alarm Alarm code 03: diesel engine stop 04: diesel engine start 05: Test state 06: Man mode 07: Auto mode

$1021 1

08: Reset $1022 1 SN Product serial number $2001 1 Comm Address $2002 1 Language $2003 1 CT $2004 1 V Low Alarm unit:V $2005 1 V Low preALM unit:V $2006 1 V High preALM unit:V $2007 1 V High Alarm unit:V $2008 1 I High preALM unit:A $2009 1 I High Alarm unit:A $200A 1 $200B 1 $200C 1 $200D 1 $200E 1 $200F 1 $2010 1 $2011 1 Alarm delay unit:S $2012 2 KWH unit: Kwh $2014 2 KVArH unit: KVArh $2016 1 VT $2018 1 Nominal speed unit:RPM $2019 1 Pickup frequency unit:RPM $201A 1 Fuel mode $201B 1 T-sensor mode $201C 1 P-sensor mode $201D 1 H-sensor mode $201E 1 Start delay unit:S $201F 1 Crank attempt $2020 1 Crank time unit:S $2021 1 Crank reset unit:S $2022 1 Crank disconnect unit:RPM $2023 1 Idle delay unit:S $2024 1 Safety-on delay unit:S $2025 1 Cooling delay unit:S $2026 1 Stop delay unit:S $2027 1 Under SP Alarm unit:RPM $2028 1 Under SP preALM unit:RPM $2029 1 Over SP preALM unit:RPM $202A 1 Over SP Alarm unit:RPM $202B 1 Oil-P Alarm unit:Kpa $202C 1 Oil-P preALM unit:Kpa $202D 1 Coolant preALM unit:℃ $202E 1 Coolant Alarm unit:℃ $202F 1 Batt low preALM unit:V

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 20: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

20

$2030 1 RUNHr unit:HOUR $2031 1 Ext.Alarm mode $2032 1 Ext.Analog unit:0 - V / 1 - % $2040 1 V1 calibration $2041 1 V2 calibration $2042 1 V3 calibration $2043 1 I1 calibration $2044 1 I2 calibration

$2045 1 I3 calibration $2046 1 Oil pressure calibration $2047 1 Temerature calibration $2048 1 Battery voltage calibration $2049 1 Excitation charge voltage calibration $204A 1 Aux input voltage calibration

$204B ――― $205E P-sensor data, ordered according to the resistance(0.1Ω) from big to small and resistance-related value-resistance $205F ――― $2072 T-sensor data, ordered according to the resistance(0.1Ω) from big to small and resistance-related value-resistance $2073F ――― $2086 oil position sensor, ordered according to the resistance(0.1Ω) from big to small and resistance-related value-resistance. Note: fault code table

Code Fault Code Fault 0 NO ERROR 10 BATTERY LOW 1 NO PICKUP 11 CHARGE FAILURE 2 OVER SPEED 12 V LOW

3 UNDER SPEED 13 V HIGH

4 O-SENSOR OPEN 14

5 LOW OILPRESS 15

6 T-SENSOR OPEN 16 I HIGH

7 COOLANT TEMP 17

8 START FAIL 18

9 STOP FAIL 19 11 Preparation before use 11.1 To confirm that the controller has installed and fixed properly, and the installation ambient must accord with installation demand 11.2 To confirm the whole connecting of control lines accord to the electric norm, and confirm to the typical connecting diagram of “1.3”. Especially the DC power supply must add fusing element safety wire to protect, and the polarity must be right. Otherwise, it will destroy the controller 11.3 The controller must be ground to the earth properly. 11.4 We suggest that the operators install the “ E- stop” key outside. Connecting the “E-stop” output terminal to the normal contact of “E-stop” key, and the other point of contact must connect to the anode of working source. 11.5 Putting through the DC working source, confirming the preset parameter accord with actual running requirements. Such as: current ratio, mode of speed sensor, mode of pressure sensor, mode of temperature, etc.

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 21: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

21

11.6 If the speed sensor is magnetic speed sensor, we must adjust speed measuring parameter according to the following steps.

Method 1: After the power supply is available, set the controller to MAN mode, the LED above the MAN key on. Now, calculate

the measuring input frequency of the speed sensor first according to the rated rotating speed and number of tooth of the engine flywheel. F=tooth × running speed÷60.] you can simply input the calculated value to the controller to complete settings. Detail procedure are as below:

Operation Description The controller is in ready state:

READY

Press “ ”for two seconds to enter the configure menu, then the LCD display: <<SETTING/参数设定>> 0.QUIT

Press “ ”three times and then press “ ”, the LCD will

display: 3.ENGINE 0.QUIT

Press “ ”for two times and then press “ ”, the LCD will

display: 2. Pickup frequency

=0

Press “ ” will indicate you to enter password, input the

password is: “ ” “ ” “ ” “ ”

2. Pickup frequency Password:****

Press “ ”or“ ”at the same time to change the parameter.

Input the calculated measuring frequency of the speed sensor,

the LCD will display the settings:

3. Pickup frequency =

Press “ ”to confirm and then press “ ”for two seconds to exit the configure menu, and the LCD will display:

READY

Method 2

Operation Description The controller is in ready state:

READY

Press “ ”for two seconds to enter the configure menu, then the LCD display: <<SETTING/参数设定>> 0.QUIT

Press “ ”three times and then press “ ”, the LCD will

display: 3.ENGINE 0.QUIT

Press “ ”three times again, then the LCD display: 3.ENGINE 3.Set pickup now

With the engine running, press “ ”after it is steady, then the controller compared the rotating speed of the speed sensor with the voltage frequency of the generator, transfer the measuring frequency at the 1500RPM rotating speed. When DONE disappeared, the measuring and calibration of the speed has been done.

3.ENGINE 3.Set pickup now DONE

NOTE: during the calibration of the speed measuring parameter, the protection of the controller is imperfection, the operator should take more attention to the condition of the generator set. When it is out of the way, stop the calibration process immediately. Check out the fault before do it again. If possible, it is suggested that the operator equipped a protection circuit or device externally.

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 22: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

22

12 Troubleshooting: Fault Phenomenon Fault Eliminate

“Genset”does notstartup

In the “ MAN” mode, you press“START”key. In the “AUTO” mode, remote control start input signal is valid. In the “Test” mode, there is no start.

1. Checking up the fault indicator light on by using of “L.TEST” key,or

consult LCD display to confirm that whether it has fault display. 2. Checking up the volts d.c. of connecting terminal“B10”of controller. If no

voltage, you need to check up the relative fuse. If the voltage is low, you need to charge the battery additionally. Until the battery capacity full, you may restart again.

3. Checking up the volts d.c. of connecting terminal “B12”of controller. If no voltage, it means that the controller generate fault, you need to change the controller.

4. To startup the magnetic flux on the motor, connecting the magnetic flux junction with the battery cathode by DC voltage meter. If the magnetic flux has voltage, means that it fault, you need to replace. If not, please check up the connecting line of control hold, to know whether it becomes flexible or short circuit.

Diesel Starting Fault

The diesel keeps rotating, but cannot start. Or the diesel stop after starting. For all of this, the controller will display the “ fail to start” signal.

1. Checking up oil fuel. 2. Checking up the volts D.C. of connecting terminal“B11”of controller. If no

voltage, it means that the controller generate fault, you need to change the controller.

3. Checking up the fuel control magnetic flux connecting line and voltage on the magnetic flux.

4. Checking up the fuse at one side of alternator. 5. Checking up the oil fuel pipe and oil filter, to know about whether it is jam. 6. If the white smoke emit from the exhaust system, it means that the fuel has going

into the generator, but the diesel keep stop. For this, please refer to the《Diesel Manual》for further details.

7. If the outside ambient low, suggesting to use hot start. 8. Once the fault eliminate, by press“RESET”key to reset again.

High temperature leads to diesel stop

The LCD display: “HIGH TEMPERATURE” and “HIGH TEMP”fault light on

1. Checking up the temperature sensor mode of controller“T-sensor mode”, to know about whether it is in the wrong setting. If it is, then you need to reset again.

2. Checking up the diesel, to know about whether it is overload. 3. Checking up the radiator, to know about whether it is jam. 4. Checking up the belt of fan, to know about whether it is loosen. 5. Checking up the outside temperature, to confirm that it is in accord with the

designing range of generator. 6. Once the diesel cooling down, you need to check up the cooling water level.

Remember that do not add a great deal of water into the cooling diesel. If you do, the diesel will suffer from serious destruction.

7. Please refer to the《Diesel Manual》for further details。 8. Once the fault eliminate, by press“RESET”key to reset again. 9. In the condition of unload, keep the generator running for 10 minutes. After the “ Genset” cooling down, on load again.

Low oil pressure leads

to stop

The LCD display:“LOW OIL PRESSURE” and“LOW OIL PRESS” fault indicator light on.

1.Checking up the temperature sensor mode of controller“T-sensor mode”, to know about whether it is in the wrong setting. If it is, then you need to reset again. 2.Checking up the oil fuel. If it is not enough, please add some. 3. Please refer to the《Diesel Manual》for further details.。 4.Checking up the oil pressure switch by testing instrument. If it is wrong, you need to change it. 5.Once the fault eliminate, by press “RESET”key to reset again.

Over speed leads to diesel stop

The LCD display:“OVERSPEED” and “OVER SPEED”fault indicator light on.

1. Checking up the temperature sensor mode of controller“H-sensor mode, to know about whether it is in the wrong setting. If it is, then you need to reset again.

2. Checking up the actuator, to know about whether it has throttle lever movement, if do, please readjust.

3. If you installed electro-magnetic actuator, please check up the throttle level, to know about whether it is movement without hindrance. If it is necessary, please adjust.

4. Please refer to the《Diesel Manual》for further details. 5. Once the fault eliminate, by press“RESET”key to reset again.

PDF created with pdfFactory Pro trial version www.pdffactory.com

Page 23: GU320Acontrol Panel Operation Manual_EN_A4

GU320A Controller Manual

23

Not enough speed leads to stop

The LCD will display“Speed L alarm”signal.

1. Checking up the diesel, to know about whether it is overload. 2. Checking up the fuel, to know about whether it is enough. 3. Checking up the actuator, to know about whether it is remove. If do, please

adjust. 4. If the electro-magnetic actuator has throttle lever, you need to check it, to know

about whether it is movement without hindrance. If it is necessary, please adjust it.

5. When the diesel running, you need to adjust the speed of diesel. 6. Please refer to the《Diesel Manual》for further details.

Low voltage leads to stop

The LCD will display“Ph-V low alarm”signal.

1. Breaking the load adding to the AC generator. After the generator stop, you need to eliminate the fault and reset the “Genset” again..

2. Checking up the “low voltage fault setting value” of “Main”, confirming that the data is right.

3. If the voltage low, you need to set the potentiometer via adjusting the output voltage of generator, then return to the normal voltage.

4. Please refer to the《Alternator Manual》for further details.

High voltage leads to stop

The LCD will display“Ph-V high alarm”signal.

1. Breaking the load adding to the AC generator. After the generator stop, you need to eliminate the fault and reset the “Genset” again.

2. Checking up the “high voltage fault setting value” of “Main”, confirming that the data is right.

3. Checking up the measuring voltage of controller, if it is in normal mode, please check up the load, so as to confirm that whether it is non-capacitive.

4. If the voltage high, you need to set the potentiometer via adjusting the output voltage of generator, then return to the normal voltage.

5. Please refer to the《Alternator Manual》for further details.

Generator fail to stop

After the Controller close, the generator still keep running, then the LCD will display“Fail to start” signal.

1. Checking up the fuel magnetic valve(or throttle lever), so as to confirm that the fuel magnetic valve close the oil channel safely in the close condition.

2. Checking up the fuel magnetic valve, if it is necessary, please change it.