GROUPD-ASSEMBLYBUILDINGS

6
LSGD ENGINEERS ASSOCIATION LSGD ENGINEERS ASSOCIATION, KERALA *211* DIARY - 2013 GROUP D- Assembly Buildings (RULE 30 (2.3e) , 55] Buildings for the purposes of amusement, recreation, religious, travel - Floor area exceeding Theatres, Cinemas, auditoriums Transport terminals, stadiums - * 150m2/300m2 Art galleries, Museums, skating rinks and libraries etc. (* Required clarification) APPROV ALS REQUIRED: RULE NO. APPROVAL FROM CONDITIONS REMARKS 4 (1.2) Local Self Government All building /Structures 26A Disposal of waste There shall be provisions for safe disposal of waste 55 (1) DTP Building area upto 6000m 2 1 hectres=247.105 55(1) CTP Building area above 500m 2 upto1000m 2 55(8a) Fire Force ,N.O.C required for all bldgs. Air (control and N.O.C For high rise building prevention of If discharge of effects is high pollution) act 1981 If generator provided Water (control and Pollution control board prevention of pollution)act 1974 55(10) Cinema Theatres Kerala Cinema Regulations Act 1988 Ref: details IS 4878-1968 bylaws for construction of Cinema Building 32(2) Airport authority Within 22 km radius of Airport N.O.C reference point 23(4) coastal zone If near water body and notified Environmental management authority by govt. (protection) act (29 of 1986) Railways If within 30m of railway boundary 7(5.6)(15) Defence establishment If within 100m 100(2),23(5) Electrical inspectorate If constructing near/below electric line Indian Electricity act and rules 1956 11A Earth work exceeding + 1.50m Approval required 110-120A High rise building See page No. 248 No.

description

assembly buildings field details

Transcript of GROUPD-ASSEMBLYBUILDINGS

  • LSGD E

    NGINE

    ERS A

    SSOCIA

    TION

    LSGD ENGINEERS ASSOCIATION, KERALA *211* DIARY - 2013

    GROUP D- Assembly Buildings (RULE 30 (2.3e) , 55]Buildings for the purposes of amusement, recreation, religious, travel - Floor area exceeding

    Theatres, Cinemas, auditoriums

    Transport terminals, stadiums - * 150m2/300m2

    Art galleries, Museums, skating rinks and libraries etc. (* Required clarification)

    APPROVALS REQUIRED:RULE NO. APPROVAL FROM CONDITIONS REMARKS

    4 (1.2) Local Self Government All building /Structures

    26A Disposal of waste There shall be provisionsfor safe disposal of waste

    55 (1) DTP Building area upto 6000m2 1 hectres=247.105

    55(1) CTP Building area above 500m2upto1000m2

    55(8a) Fire Force ,N.O.C required for all bldgs.Air (control and N.O.C For high rise building

    prevention of If discharge of effects is highpollution) act 1981 If generator providedWater (control and Pollution control board

    prevention ofpollution)act 1974

    55(10) Cinema Theatres Kerala Cinema Regulations Act 1988 Ref: detailsIS 4878-1968 bylaws for constructionof Cinema Building

    32(2) Airport authority Within 22 km radius of AirportN.O.C reference point

    23(4) coastal zone If near water body and notified Environmental management authority by govt. (protection) act

    (29 of 1986)

    Railways If within 30m of railway boundary

    7(5.6)(15) Defence establishment If within 100m

    100(2),23(5) Electrical inspectorate If constructing near/below electric line Indian Electricityact and rules 1956

    11A Earth work exceeding +1.50m Approval required

    110-120A High rise building See page No. 248No.

  • LSGD E

    NGINE

    ERS A

    SSOCIA

    TION

    LSGD ENGINEERS ASSOCIATION, KERALA *212* DIARY - 2013

    Rule Item Conditions Required RemarksNo.Open space (set backs) for buildings upto 10m ht.

    Places of Other buildings likeworship auditorium etc.upto 300 500300m2 500m2 800m2 +800m2

    Front 3m 6m av. 7.5m av. 10.5m av. Addl. set [email protected] min. 5m. min 6m. min 50cm for every 3m

    Rear 1.5m 2m. min 3m. min 3m. av. over 10m ht.1.5m.min 1.5m.min 1.5m.min

    55(2) Sides 1.5m 2m.av 4m.av 5m.av1.5m.min 1.5m.min 1.5m.min

    24(8) Addl. set back @0.50m/.30m24(12) Set back for same as set back required for 10 m high

    underground bldg.of same occupancy groupfloorOpen spacefor fire fighting Min.

    117 (if ht.of bldg All around building 5mmore than 15mor 4 floors)

    24(2) Min.Space Upto 10m. ht. 1.50mbetween bldgs.in same plot. Above 10m ht. 3m

    104(1,2) Set back of well From road-same as for the bldg.Other sides 3.0m

    104(3) Well & bldg. inthe same plot Can abut/ inside bldg. Nil

    104(4) Dist. of well from septic tank etc. 7.5mDist. of septic tanketc from boundary 1.2m

    86 Setbacks accessory Main bldg. Can abutbldg. Plot boundaries 1 m

    Road boundary -same as in residentail bldg.55(3) Min.ht.of room Non a/c 4 m

    A/c 3 m55(4)(5) Min.headroom For non A/C 3m

    below & abovemezzanine For A/C 2.4m

    55(6) Min.ht. of storeroom/toilet/cellar 2.4 m

    55(7) Mezanine area 25% of Carpet area,max.350max.slope

    55(B) Satndard of In assembly halls 28m3 fresh air per To satisfyVentilation seat NBC 1983

    55(11) Wedding hall Provision for collection and disposal ofwith cooking & solid and liquid wastedining facility

  • LSGD E

    NGINE

    ERS A

    SSOCIA

    TION

    LSGD ENGINEERS ASSOCIATION, KERALA *213* DIARY - 2013

    Rule Item Conditions Required RemarksNo.Sanitary facilities

    No. of person 1 person per 1m2 carpet area *Carpet area 80% ofMale 2/3 floor area ORFemale 1/3 *Actual usable carpetAudito Bus area (Ref.Definition)rium Terminal Railway Airport *No.of men =

    55(12) WC-male 1 per 200 4 per 1000+1 5 per 1000+1 per 5 per 1000+ 2/3 No.of persons54(6) per additional 1000 additional 1000 1 per addl.1000 *No.of women =Table-9 1/3 No.of persons

    WC Female 1 per 100 Sanitation facilityUrinal 1 per 50 6 per 1000+ 1 per 6 per 1000+ 1per 6 per 1000+ 1 for 1 person per

    additional 1000 addl. 1000 per addl. 1000 1 sq.mWash basinMale 1 per 200 4 Nos. min 4 Nos. min 4 Nos. minFemale 1 per 200 4 Nos.min. 4 Nos. min 4 Nos. min

    38(1) Sizes Width Area WC/Bath - 1 wall49(6) bathroom Min.1.1m 1.50m2 to abut open space/

    Latrine (WC) Min.1 .0m 1.1m2 varandah air shaftBathroom+WC Min.1.10m 2.2m2

    24(6) Interior openspace Bldgs. with 7m. ht 1.5mMin.width *For habitable room

    Others 2.4m24(7) Unpaved yard (For percolation of rain water) Can drain rain water to

    If permeable soil Required public drain ifIf impermeable soil Not req. impermeable

    24(11) Roof/Shade Min.open space req. Roofprojection allowedprojection Less than 0.60m Not allowed

    0.60 m 0.30 m0.75 m1.00 m 0.60 m1.50 m 0.75 m

    26 Use of open Roof projection to open space of 3 m 75 cmspace abutingroad Ramp. star, bridge etc can constructMin.dist. between Road widening/ bldg. linecentral line of 5m should be consideredroad & bldg *Applicable to all sides

    25(1) Min.dist.between Upto 10 m ht. 3m 5m distance betweenplot boundary & For bldg upto 7m height centerline and bldg.bldg. cul-de-sac not exceeding 250m (all road width) not applicable

    Road width upto 3m 2m *Rule 25(1-2)Internal road of residential colony *Applicable to all sidescul-de-sac upto 75m 1m

    25(2) DTP Scheme/ Master plan to satisfy

  • LSGD E

    NGINE

    ERS A

    SSOCIA

    TION

    LSGD ENGINEERS ASSOCIATION, KERALA *214* DIARY - 2013

    Rule Item Conditions Required RemarksNo.

    ASSEMBLY BUILDING55(ia) Coverage Places of worship other buildings. 50%

    Assembly building 40% 1.Addl. fee @ Rs.500/m2

    31(2) F.A.R 0.70 without addl. fee 2. @ Rs.1000/m2

    F.A.R with addl. 0.70 -1.00 1. Addl. fee @ Rs.500/m2fee 1.00-1.50 2. @ Rs.1000/m2

    31(2aii) coverage&F.A.R Can give for A1, A2, D,E & F groups if plot area uptoNoteiii for more than on the basis of weighted average of floor 0.5 hectre. F.AR.

    one occupancy area under respective occupancies if and coverage shallin a bldg. the plot has an area more than 0.50ht. be the most restrictive

    occupancy32(1) Maximum Building line above 12m No restrictiona,b ht.of bldg. Building line below 12m 1.5 x (road width

    + front setback)Note: If abutting more than 1 road greater road width to consider

    132 Telecommunication towers exemptedParking

    34(1)(2) Carparking 15 seats of accommodationtable 5 (5.5x2.7m -15m2) Carpet area of auditorium or dining hall

    which ever is higher only to consider*1.5m2 of carpet area per person

    34(3) Two wheeler 25% of car parking areaparking area

    34 Parking in 50% of mandatory open spaceopen area

    110- High rise building See page No. 248120A

    Clearance from overhead Electric LinesRule Voltage Vertical clearane from Horizontal clearance Exemption : Single storied bldgs.canNo the highest building from the nearest pointbe allowed if no objection certificate100(2) Law& medium 2.4 1.2 issued by Chief electrical inspector23(5) upto 11 KV 3.7 1.2 is produced.Table- 11-33 KV 3.7 1.8 * For EHV lines, the clearance above the

    1 66 KV* 4.3 2.4 ground shall not be less than 5,182 mtr. plus 110KV* 4.9 3.0 0.305mtrs. for every 33KV or part there of by 220KV* 5.5 3.7 which the voltage of the line exceeds 33KV. 400KV* 7.3 5.5 The minimum clearance along or across any

    street shall not be less than 6.096 mtrs.

  • LSGD E

    NGINE

    ERS A

    SSOCIA

    TION

    LSGD ENGINEERS ASSOCIATION, KERALA *215* DIARY - 2013

    39 Stair case39(1) Min.no.of stairs For above 4 floors 2 nos. 1stair may be external39(2) Width Min. 120 cm Including sunken floor39(3) Tread Min.30cm39(4) Rise 15 cm39(5) Ht. of handrail Not less than 90 cm39(6) Width of access Not less than width of stair min.1.20

    (passage) to stair40 Slope of ramp Pedestrian 1 in 1056(3) Vehicular Suitable41 Width of coridor Min.100 cm 100 cm

    Varandah.42(1) Fire escape Upto 2 floor Nil

    stair nos. Above 2 floor required42(2) Width Min .75cm

    Tread Min.15cmRise Max.19cmNo.of riser Max.16 nos.

    42(3) Ht. of handrail Min.100 cm42(4) Position Exterior of building42(5) Flight Straight42(6) Entrance Separated from internal stair43(2) Travel distance

    to fire escape Max.30m114(6) Spiral stair Max. ht. of bldg 10m *Only for low occupancy47(1) 9m group114(7) Min.diametre 150cm *Should have enough47(2) head room44 For protection55(9) requirement As per NBC45 *Gross area of the in m2

    (3,4,5) Exit width stair No.of unit stair width of 50cm = Gross area per person 1.5m2 Table 6 of the floor (25x12.5) *No. of occupantsper

    Door (No.of unit door width of 50cm = Gross area unit exit width of 50cmof the floor (75x12.5) for stair 60 Door-90

    *A half unit width of 25cm can also consider

    46(2) Min. exit door width 1.2m40A Facilities For persons with disabilities (+1000m2) 40A

    1-8(c)

    Rule Item Conditions Required RemarksNo.

  • LSGD E

    NGINE

    ERS A

    SSOCIA

    TION

    LSGD ENGINEERS ASSOCIATION, KERALA *216* DIARY - 2013

    Rule Item Conditions Required RemarksNo.48(1) Lift needed? 4 floor excluding sunken floor & plinth area required *If decimal table

    exceeding 2500m2 next valueNo. of addl.lifts (Total plinth area -2500) / 2500(over 4000m2)

    48(2) NBC Part VIII, Building services,section5-Elevatorsand Escalators

    48(2)(b) More than (One of the lift should be able to carry stretcher.1 lift

    49(2) Max.dist. of lighted portion from window 7.5m If artificial lightrequired

    49(3) Lighting & Lighting through window abuting varandahventilation less than 3 m 3m

    Min. width of open space for above Varandah 3m49(5) For bath / WC Sufficient49(6) WC/bath - 1 wall to abut open space/varandah/ If not

    air shaft airconditioned49(4) Ventilation in kitchen49(1) ventilated as in habitable room Refer NBC

    Suitable flue to be provided49(6) Air shaft for No.of floors Width & area Not required if

    ventilation Up to 3 0.90 1.08m2 centrally4 to 6 1.2 2.40m2 Air conditioned7 to 10 1.5 3.0m2

    Above 10 2.0 5.0m2

    109A RAIN WATER HARVESTING109B(3) Storage tank 50 ltres per m2 of total floor area

    capacity109C Solar assisted Solar assisted water heating/lighting system Group A1, A2

    water heating & be provided for bldgs. exceeding 500 sq.m Group C and D lightning of built up area. system in bldgs

    Accessfor other occupancy GroupsTABLE 4. 2

    Rule Occupancy Total floor area of bldgs. in sq.m Number of storeys Minimum widthNo of access rqd. in m33(1) Occupancies Upto 300 Single storey 1.2 a other than Above 300 upto 1000 Two storey 3.6

    Group A1 Above 1000 upto 4000 Three storey 5(see Note(e) Above 4000 upto 8000 Four storey 6

    Above 8000 upto 12000 Above four storey 8Above 12000 10.