Group: Applied Systems Part Number: IM ... - Daikin...
Transcript of Group: Applied Systems Part Number: IM ... - Daikin...
Installation and Maintenance IM 696-3
Group: Applied Systems
Part Number: IM 696
Date: December 2004
© 2004 Daikin Applied
MicroTech® IIApplied Rooftop Unit Controller
• Used with Daikin models: RPS, RFS, RCS, RDT, RPR, RFR, RPE,RDE, RCE, RDS, RAR & RAH
Discharge CoolingDisch Air= 55.0°FClg Capacity= 50%Eff Clg Spt= 55°F
Contents
Daikin and MicroTech II are registered trademarks of Daikin Applied . Microsoft is a registered trademark of Microsoft Corporation.
Windows is a trademark of Microsoft Corporation.Copyright © 2004 Daikin Applied . All rights reserved throughout the world.
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Component Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Main Control Board (MCB) . . . . . . . . . . . . . . . . . . . . . . . 4Analog Inputs Terminal Blocks . . . . . . . . . . . . . . . . . . . . 5Binary Inputs Terminal Blocks . . . . . . . . . . . . . . . . . . . . . 5Binary Outputs Terminal Blocks . . . . . . . . . . . . . . . . . . . 5RS-485 Communications Terminal Block . . . . . . . . . . . . 5Power Supply Terminals . . . . . . . . . . . . . . . . . . . . . . . . . 5Keypad/LCD Display Connection . . . . . . . . . . . . . . . . . . 5Communication Modules . . . . . . . . . . . . . . . . . . . . . . . . . 5BACnet/IP Communication Module . . . . . . . . . . . . . . . . . 5BACnet MS/TP Communications Module . . . . . . . . . . . . 6LonWorks® Communication Modules . . . . . . . . . . . . . . . 6RS-232 Connection Port . . . . . . . . . . . . . . . . . . . . . . . . . 715 VDC Supply Connection . . . . . . . . . . . . . . . . . . . . . . . 7Main Control Board LEDs . . . . . . . . . . . . . . . . . . . . . . . . 7Auxiliary Control Boards (CCB1, CCB2, EHB1, and ERB1) . . . . . . . . . . . . . . . . . . 8Analog Inputs Terminal Block (J8) . . . . . . . . . . . . . . . . . 9Binary Inputs Terminal Blocks (J9 and J10) . . . . . . . . . . 9Binary Outputs Terminal Blocks . . . . . . . . . . . . . . . . . . . 9RS-485 Communications Module . . . . . . . . . . . . . . . . . . 9Power Supply Terminals (J1) . . . . . . . . . . . . . . . . . . . . . 9J7 Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9J2 Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Main Control Board (MCB)
Output Relays and Triacs . . . . . . . . . . . . . . . . . . . . . . 9Auxiliary Control Boards (CCB1, CCB2,
GCB1, EHB1, and ERB1) Output Relays . . . . . . . . 10Keypad/Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Remote Keypad Display Option . . . . . . . . . . . . . . . . . . 10Temperature Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . 11Pressure Transducers . . . . . . . . . . . . . . . . . . . . . . . . . . 11Humidity Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Variable Frequency Drives (VFDs) . . . . . . . . . . . . . . . . 11
Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Field Output Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Remote Alarm Output . . . . . . . . . . . . . . . . . . . . . . . . . . 12Fan Operation Output . . . . . . . . . . . . . . . . . . . . . . . . . . 12VAV Box Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Cooling Only Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Cooling Only Units with Field Supplied Heat . . . . . . . . . 13Units with One-Stage Heat . . . . . . . . . . . . . . . . . . . . . . 13Units with Modulating Heat . . . . . . . . . . . . . . . . . . . . . . 14Staged Cooling Outputs . . . . . . . . . . . . . . . . . . . . . . . . 14
Field Analog Input Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Zone Temperature Sensor Packages . . . . . . . . . . . . . . 14Zone Sensor without Remote Set Point Adjustment . . . 14Zone Sensor with Remote Set Point Adjustment . . . . . 15Tenant Override (Timed) . . . . . . . . . . . . . . . . . . . . . . . . 15External Discharge Air Reset Signal . . . . . . . . . . . . . . . 16External Outdoor Air Damper Reset Signal . . . . . . . . . . 16Field Valve Actuator Feedback . . . . . . . . . . . . . . . . . . . 17Humidity Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Humidity Sensor—Discharge Air Control (DAC) Unit . . 19
Field Binary Input Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Manual Cooling and Heating Enable . . . . . . . . . . . . . . . 19
Cooling Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Heating Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Manual Unit Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19External Time Clock or Tenant Override . . . . . . . . . . . . 19Miscellaneous Output Signals . . . . . . . . . . . . . . . . . . . . 20External Exhaust Fan Status . . . . . . . . . . . . . . . . . . . . . 20
Service Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21Controller Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Analog Inputs-Main Control Board (MCB) . . . . . . . . . . . 21Analog Inputs—Auxiliary Control Boards
(CCB1, CCB2, GCB1, EHB1 & ERB1) . . . . . . . . . . . 23Binary Inputs—Main Control Board (MCB) . . . . . . . . . . 23Binary Inputs—Auxiliary Control Boards
(CCB1, CCB2, GCB1, EHB1 & ERB1) . . . . . . . . . . . 23CCB1 & CCB2 (7RPS, RFS/RCS, RDT,
RPR & RFR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23GCB1 (RDS & RAH) . . . . . . . . . . . . . . . . . . . . . . . . . . . 23EHB1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23ERB1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Controller Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Binary Outputs—Main Control Board (MCB) . . . . . . . . . 24Binary Outputs—Auxiliary Control Boards
(CCB1, CCB2, GCB1, EHB1 & ERB1) . . . . . . . . . . . 26CCB1 and CCB2 (RPS, RFS/RCS, RDT,
RPE, RDE, RCE, RPR, and RFR) . . . . . . . . . . . . . . 26GCB1 (RDS & RAH) . . . . . . . . . . . . . . . . . . . . . . . . . . . 31EHB1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31EERB1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Software Identification and Configuration . . . . . . . . . . . . . . . 32Main Control Board (MCB) Configuration . . . . . . . . . . . . . . . 32
Main Control Board (MCB) Data Archiving . . . . . . . . . . 33
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . 34Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Test Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59Troubleshooting Main Control Board (MCB) . . . . . . . . . 59MCB Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59MCB Data Archiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59MCB “Cold” Reboot . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59MCB LED Power-Up Sequence . . . . . . . . . . . . . . . . . . . 59MCB LED Startup Error Codes . . . . . . . . . . . . . . . . . . . 61Battery Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Flash CRC Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62SRAM Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Communication Port Tests . . . . . . . . . . . . . . . . . . . . . . . 62IP Register Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62Troubleshooting Auxiliary Control Boards
(CCB1, CCB2, GCB1, EHB1 and ERB1) . . . . . . . . . 63Hardware Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63RS-485 Communication Card Status LEDs . . . . . . . . . . 63Troubleshooting Keypad/Display . . . . . . . . . . . . . . . . . . 63Keypad/Display Power Up Initialization . . . . . . . . . . . . . 63Troubleshooting Temperature Sensors . . . . . . . . . . . . . 64Troubleshooting Communications Modules . . . . . . . . . . 65BACnet/IP Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65BACnet MS/TP Module . . . . . . . . . . . . . . . . . . . . . . . . . 65LonMark Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65Troubleshooting Pressure Transducers . . . . . . . . . . . . . 66
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Introduction
Introduction
Rooftop unit control configuration
Operation manual bulletin number
Discharge Air Control (VAV or CAV)Space Comfort Control (CAV-zone temperature control)
Rooftop unit model Installation and maintenance data bulletin number
RPS/RDT/RFS/RCS 015-135CRPE/RDE/RCE (evaporative condensing units)RDS and RAH
NOTICE
WARNING
WARNING
CAUTION
CAUTION
CAUTION
This manual contains information regarding the MicroTech II® control system used in the Daikin® RoofPak® applied rooftop product line. It describes the MicroTech II components, input/output configurations, field wiring options and requirements, and service procedures.
For a description of operation and information on using the keypad to view data and set control parameters, refer to the appropriate program-specific operation manual, see Table 1. For installation and commissioning instructions and general information on a particular rooftop unit model, refer to its model-specific installation manual, refer to Table 2.
Table 1: Program-specific unit operation literature
OM-137-2
OM-138-2
Table 2: Model-specific rooftop unit installation literature
IM 738-1
IM 791-1
IM 487-4
This equipment generates, uses, and can radiate radio frequency energy. If not installed and used in accordance with this instruction manual, it can interfere with radio communications. It has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. Operation of this equipment in a residential area is likely to cause harmful interference; in which case users will be required to correct the interference at their own expense. Daikin Applied disclaims any liability resulting from any interference or for the correction thereof.
Electric shock hazard. Can cause personal injury or equipment damage.This equipment must be properly grounded. Connections and service to the MicroTech II control panel must be performed only by personnel knowledgeable in the operation of the equipment being controlled.
Excessive moisture in the control panel can cause hazardous working conditions and improper equipment operation.Protect the electrical components in the main control panel from precipitation.
Extreme temperature can damage system components.This MicroTech II controller is designed to operate in ambient temperatures from –40°F to 158°F. It can be stored in ambient temperatures from –65°F to 176°F. The controller is designed to operate in a 10% to 90% RH (noncondensing) and be stored in a 5% to 95% RH (noncondensing) environment.
Static sensitive components. A static discharge while handling electronic circuit boards can damage components.Discharge any static electrical charge by touching the bare metal inside the main control panel before performing any service work. Never unplug any cables, circuit board terminal blocks, relay modules, or power plugs while power is applied to the panel.
To prevent possible unit damage, before removing power to the controller, pump down compressor.
Daikin IM 696-4 1
General Description
General Description
The MicroTech II Applied Rooftop Unit Controller is a microprocessor-based controller designed to provide sophisticated control of Daikin RoofPak® applied rooftop units. In addition to providing normal temperature, static pressure, and ventilation control, the controller can provide alarm monitoring and alarm-specific component shutdown if critical system conditions occur.
The operator can access temperatures, pressures, operating states, alarm messages, control parameters, and schedules with an 8-key keypad and a 4-line by 20-character display. The controller includes password protection against unauthorized or accidental control parameter changes.
This MicroTech II controller is capable of complete, stand-alone rooftop unit control, or it can be incorporated into a building-wide network using an optional plug-in communication module. Available communication modules include BACnet®/IP, BACnet MS/TP, LONMARK® Space
Comfort Controller (SCC) and LONMARK Discharge Air Controller (DAC).
Component DataThe main components of the MicroTech II control system include the main control board (MCB), one or two optional auxiliary cooling control boards (CCB1, CCB2, or GCB1), an optional auxiliary electric heating control board (EHB1), an optional auxiliary energy recovery wheel control board (ERB1), and a keypad/display. These control components are located in the main control panel as shown in Figure 1 (smaller units), Figure 2 (larger units), and Figure 3. These components are interconnected by shielded multiconductor communication cables, or in the case of the keypad/display by a six conductor cable with an RJ-11 style modular connector. Transformers T2, T3 and T9 supply power to the system. The following pages contain descriptions of these components and their input and output devices.
Figure 1: Main control panel, RPS/RFS/RPR/RFR 15 to 40C and RDS/RAR 800 to 802C
2 Daikin IM 696-4
General Description
Figure 2: Main control panel, RPS/RFS/RPR/RDT 45 to 75C and RAH/RAR 47C
Figure 3: Main control panel, RPS/RFS/RPR/RDT 80 to 135C and RAH/RAR 77C
Daikin IM 696-4 3
General Description
Main Control Board (MCB)Figure 4 shows the main control board (MCB). It contains a microprocessor that is programmed with the main application code to control the unit. The MCB receives up to 16 analog and 16 binary inputs directly and up to 6 analog and 12 binary inputs from each optional auxiliary control board (CCB1,
CCB2, GCB1, EHB1, and ERB1). Auxiliary control boards communicate this data with the MCB via an RS-485 communication bus interface. The MCB controls its own 16 binary outputs and up to 9 binary outputs on each auxiliary board based on the inputs.
Figure 4: Main control board
(RS485)communications
terminal block
RJ-48 jack
Analog inputs terminal block
Binary outputsterminal block
Power supplyterminal
Binary inputsterminal blocks
BACnet/IPcommunication
moduleBACnet MS/TP
or L ON W ORKScommunication
module
4 Daikin IM 696-4
General Description
Analog Inputs Terminal BlocksThe MCB receives up to 16 analog input signals on four terminal blocks located on the left side of the board. From top to bottom, analog inputs AI1 through AI4 are terminated on the first terminal block, AI5 through AI8 on the second, AI9 through AI12 on the third, and AI13 through AI16 on the fourth. Each analog input has two terminals. The terminals for AI1 are 1 and 1C, the terminals for AI2 are 2 and 2C, and so forth. Refer to “Analog Inputs-Main Control Board (MCB)” on page 21 for details regarding analog inputs.
Binary Inputs Terminal Blocks
The MCB receives up to 16 binary input signals on three terminal blocks located on the top of the board. From right to left, binary inputs BI1 through BI6 are terminated on the first terminal block, BI7 through BI10 on the second and BI11 through BI16 on the third. Refer to “Binary Inputs—Main Control Board (MCB)” on page 23 for details regarding binary inputs.
Binary Outputs Terminal Blocks
The MCB controls up to 16 binary outputs when controlling the unit. The binary outputs either energize on-board electromechanical relays (BO1 through BO4, BO11 and BO12) or triacs (BO5 through BO10 and BO13 through BO16).
The unit control devices are wired to these relays or triacs through six output terminal blocks on the right side of the MCB. From top to bottom binary outputs BO1 and BO2 are terminated on the first terminal block, BO3 and BO4 on the second, BO5 through BO7 on the third, BO8 through BO10 on the fourth, BO11 through BO13 on the fifth, and BO14 through BO16 on the sixth.
Each binary output has three terminals. The terminals for BO1 are NO, 1, and NC, the terminals for BO2 are NO, 2, and NC, and so forth. Each binary output lights an LED when the output is active. Refer to “Binary Outputs—Main Control Board (MCB)” on page 24 for details regarding binary outputs.
RS-485 Communications Terminal Block
The MCB exchanges information with up to four optional auxiliary control boards via the RS-485 communication bus terminal block in the lower left corner of the MCB. This terminal block has four terminals, three of which are labeled REF, Minus, and Plus. These terminals connect the auxiliary boards to the RS-485 communication bus to interface them with the MCB.
If unit is equipped with and evaporative condenser and a VFD controlling the first condenser fan on each circuit (condenser fan #11 and #21), this VFD is also controlled via this RS-485 communication bus terminal block.
Power Supply Terminals
Transform T2 supplies 24 VAC power to the MCB on the 24V and COM terminals located at the upper right corner of the MCB.
Some of the binary outputs on the MCB drive 24 VAC pilot relays in the unit control circuit. 24 VAC to power these pilot relays is provide from transformer T3, through the SRC 1–8 and SRC 9–16 terminals located at the upper right corner of the MCB, and through the particular binary output contacts. Place the output jumper associated with these outputs in the SRC position. For detailed information regarding binary output jumpers, refer to “Binary Outputs—Main Control Board (MCB)” on page 24.
Keypad/LCD Display Connection
The keypad is connected to the main control board via a six-conductor cable connected to a modular jack located at the bottom of the MCB. This connects the keypad to the RS-485 communication bus interface with the MCB.
Communication ModulesIn systems that require networking, one of the following communications modules can be installed.
BACnet/IP Communication Module
A BACnet/IP Communication Module can be plugged into the MCB as shown in Figure 4 on page 4.
The BACnet/IP Communication Module is designed to be an add-on module to the MCB for networking to Building Automation and Control Network (BACnet) systems. It is a plug-in module that can be attached to the MCB via a 36-pin header, and includes four locking stand-offs to securely attach it to the board. The MicroTech II Applied Rooftop Unit Controller meets the requirements of ANSI/AHRAE 135-2001 standard for BACnet/IP per Annex J of the standard with a conformance level of 3.
For a detailed description and troubleshooting information regarding this communications module, refer to installation and maintenance bulletin IM 703, MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module—BACnet / IP. For details regarding BACnet protocol data, refer to engineering data document, ED 15060, MicroTech II Applied Rooftop Unit Controller Protocol Information.
A unit equipped with the optional BACnet/IP Communication Module is connected to an BACnet network through an eight-position RJ-48 style modular jack located on the bottom edge of the MCB. This connection is shown schematically in Figure 5 on page 7.
Daikin IM 696-4 5
General Description
BACnet MS/TP Communications Module
A BACnet MS/TP Communication Module can be plugged into the MCB as shown in Figure 4 on page 4.
The BACnet MS/TP Communication Module is designed to be an add-on module to the MCB for networking to Building Automation and Control Network (BACnet) systems. It is a plug-in module that can be attached to the MCB via a 12-pin header, and includes four locking stand-offs to securely attach it to the board. It allows the MCB to interoperate with systems that use the BACnet Master Slave/Token Passing (MS/TP) protocol with a conformance level of 3. The MicroTech II Applied Rooftop Unit Controller meets the requirements of ANSI/AHSRAE 135-2001 standard for BACnet systems.
For a detailed description and troubleshooting information regarding this communications module, refer to installation and maintenance bulletin IM 704, MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communication Module—BACnet / MS/TP. For details regarding BACnet protocol data, refer to engineering data document, ED 15060, MicroTech II Applied Rooftop Unit Controller Protocol Information.
A unit equipped with the optional BACnet MS/TP Communication Module is connected to a BACnet network through terminals 128 (+) and 129 (-) on terminal block TB2 in the main control panel. These terminals are factory wired to the BACnet MS/TP module when the module is factory installed. When the module is field installed, the add on communication module kit includes a wiring harness to be installed between terminals 128 and 129 and the BACnet MS/TP module. This connection is shown schematically in Figure 5 on page 7.
LONWORKS® Communication Modules
A LONWORKS Communication Module can be plugged into the MCB as shown in Figure 4 on page 4. This module provides LONWORKS network communication capability to the MCB. It is a plug-in module that can be attached to the MCB via a 12-pin header, and includes 4 locking stand-offs to securely attach it to the board.
For a detailed description and troubleshooting information regarding this communications module, refer to installation and maintenance bulletin IM 702, MicroTech II Applied Rooftop Controller and Self-Contained Unit Controller LONWORKS Communication Modules. For details regarding LONMARK® protocol data for these modules, refer to engineering data document, ED 15060, MicroTech II Applied Rooftop Unit Controller Protocol Information.
There are two versions of this module available. One is the LONMARK Space Comfort Controller (SCC) module and the other is the LONMARK Discharge Air Control (DAC) module.
Space Comfort Control (SCC) Module. The Space Comfort Controller (SCC) module supports the LonMark Space Comfort Controller (SCC) functional number 8500.
Discharge Air Control (DAC) Module. The Discharge Air Controller (DAC) Communication module supports the LONMARK Discharge Air Controller (DAC) functional number 8610.
A unit equipped with an optional LONWORKS Communication module can be connected to a LONWORKS network through terminals 128 (A), 129 (B) on terminal block TB2 in the main control panel. These terminals are factory wired to the module when the module is factory installed. When the module is field installed, the add-on communication module kit includes a wiring harness to be installed between terminals 128 and 129 and the module. This connection is shown schematically in Figure 5 on page 7.
6 Daikin IM 696-4
General Description
Figure 5: MCB communication interface
U n i t T e r m i n a l B l o c k T B 2
B A C
n e t- M
S T P C O
M M
. M
O D
U L E
5 2 2 ( C L R )
5 2 3 ( B L K )
5 2 2
5 2 3
B A C
n e t- IP
C O
M M
. M O
D U
L E
R J 4 5 M O D U L A R
J A C K
R S 2 3 2 P O R T ( D B - 9 M A L E )
S E R IA L C O M M . L O C A T E D O N D E A D F R O N T ( D B - 9 M A L E )
B A C n e t M S T P
L o n W o r k s
B A C n e t IP
M A IN C O N T R O L B O A R D ( M C B )
S E R V IC E T O O L
1 0 B A S E - T S T Y L E C O N N E C T IO N
1 2 8
1 2 9
1 2 8
1 2 9
RS-232 Connection Port
A PC loaded with MicroTech II Service Tool software can be connected directly or via a telephone modem to the RS-232 communications port located on the bottom edge of the MCB. This connection is shown schematically in Figure 5.
15 VDC Supply Connection
The two 15V terminals located above the analog input terminals blocks provide 15 VDC power. This power supply is not used in the rooftop controller application. This power supply is limited to 30 mA.
CAUTION
Main Control Board LEDs
There are a number of LEDs in various locations on the MCB. These LEDs consist of three groupings. There are 16 Binary Input (BI) LEDs located in the upper left corner of the MCB. These LEDs are lit when the corresponding Binary Input is turned ON. For information regarding the functions of the Binary Inputs refer to “Binary Inputs—Main Control Board (MCB)” on page 23. There are 16 Binary Output (BO) LEDs, one located next to each Binary Output on the right side of the MCB. These LEDs are lit when the corresponding Binary Output is turned ON. For information regarding the functions of the Binary Outputs refer to “Binary Outputs—Main Control Board (MCB)” on page 24. There are four miscellaneous LEDs located along the bottom of the MCB. These LEDs provide error code information and indication of activity on the various communication channels. Table 3 lists these LEDs with their functions.
LED function Location on MCB LED color
MCB error indication*RedOff Blinking
*Refer to “Troubleshooting Main Control Board (MCB)” on page 58.
This is an unregulated power supply and should not be used to feed three-wire potentiometer inputs.
Table 3: Main control board miscellaneous LEDs
RS-485 bus activity indication (LED is ON when activity present on the bus) Left of RS-485 port connector GreenRS-232 port activity indication (LED is ON when activity present at the port) Left of RS-232 port connector GreenBACnet/IP port activity Indication (LED is ON when activity present at the port) Left of BACnet/IP port connector Green
Right of BACnet/IP port connector
Normal Battery low or defective
Daikin IM 696-4 7
General Description
Auxiliary Control Boards (CCB1, CCB2, EHB1, and ERB1)There are up to four optional auxiliary control boards. These are the cooling control boards (CCB1 and CCB2 or GCB1), the electric heat control board (EHB1) and the energy recovery wheel control board (ERB1). Although the input and output functions on the four boards are defined differently in software, the boards are physically identical.
The CCB1 and CCB2 are used whenever a unit is equipped with a factory DX condensing unit (models RPS, RFS/RCS, RDT, RPR, RPE, RDE, RCE, and RFR). The GCB1 board, loaded with special generic cooling staging software, can also be used to control a field supplied condensing unit interfaced with an air handling unit (RDS or RAH) equipped with a DX
cooling coil. The CCB1 and CCB2 or GCB1 are not used on units equipped with chilled water or no cooling.
The EHB1 is used whenever a unit is equipped with more than one stage of electric heat. It is not used on units with single stage or modulating heat.
The ERB1 is used whenever a unit is equipped with an optional energy recovery wheel system.
A typical auxiliary control board is shown in Figure 6. This board receives up to 6 analog and 12 binary inputs and exchanges information with the MCB via an RS-485 communication bus.
Figure 6: Auxiliary control board (CCB1 board shown)
Binary inputs terminal block
Binary outputsterminal block (RS485)
communicationsterminal block
Analog inputs terminal block
8 Daikin IM 696-4
General Description
Analog Inputs Terminal Block (J8)
The auxiliary control board receives up to six analog input signals via the AI (J8) terminal block on the right side of the board.
Note – These analog inputs are only used on the ERB1 application. Refer to “Analog Inputs—Auxiliary Control Boards (CCB1, CCB2, GCB1, EHB1 & ERB1)” on page 23 for details regarding analog inputs.
Binary Inputs Terminal Blocks (J9 and J10)
The auxiliary control board receives up to 12 binary input signals via the BI (J9 and J10) terminal blocks on the right side of the board. BI1 through BI6 are located on terminal block J9 and BI7 through BI12 are located on terminal block J10. Refer to “Binary Inputs—Auxiliary Control Boards (CCB1, CCB2, GCB1, EHB1 & ERB1)” on page 23 for details regarding binary inputs.
Binary Outputs Terminal Blocks
The auxiliary control board includes nine binary output relays (BO1 through BO9) that are energized based on commands received from the MCB. These relays provide the appropriate switching actions for the control devices that are wired to them through the BO terminals on the left side of the board. Refer to “Binary Outputs—Auxiliary Control Boards (CCB1, CCB2, GCB1, EHB1 & ERB1)” on page 26 for details regarding binary outputs.
RS-485 Communications Module
Each auxiliary control board is equipped with a plug-in RS-485 Communication module. This module includes a three-position terminal block with terminals labeled N2+, N2- and REF. These terminals are wired to the +, - and REF terminals on the RS-485 communication terminal block on the MCB. The auxiliary control board exchanges information with the MCB via this interface.
Each auxiliary board RS-485 Communication module includes an 8-position dip switch assembly (SW1) for addressing the board. Refer to Figure 6 on page 8. The CCB1 must always be set to address 2, the CCB2 to address 3, the GCB1 to address 5, the EHB1 to address 4 and the ERB1 to address 6. This is done by setting the switches on each of the auxiliary control boards as indicated in Table 4. If the switches are not set as indicated, the MCB will not communicate correctly with the board and it will not function properly.
Auxiliary control board
(address)
Dip switch #
1 2 3 4 5 6 7 8
Power Supply Terminals (J1)
Either transformer T9 (CCB1 and CCB2) or T3 (GCB1, EHB1, and ERB1) supplies 24 VAC power to terminal block J1, terminals 1 (24VAC) and 2 (COM) on the auxiliary control board.
J7 Terminal Block
The J7 terminal block located at the top of the auxiliary control board is not used in this product application.
J2 Terminal Block
The J2 terminal block located between the J10 and J8 terminal block on the right side of the auxiliary control board is not used in this product application.
Main Control Board (MCB) Output Relays and TriacsBinary outputs BO1 through BO4, BO11, and BO12 control pilot duty Form C electromechanical relays mounted on the MCB. The output terminals of these relays are connected to a set of binary output terminal blocks located right side of the MCB. These relays are designed for Class 2 operation and to switch loads with either of the following characteristics:• 5VDC @ 10 mA minimum, 1 A maximum• 30 VAC @ 2 A nominal, 10 A inrush
Binary outputs BO5 through BO10 and BO13 through BO16 control triacs mounted on the MCB. The output terminals of these triacs are connected to a binary output terminal block located on the right side of MCB. These triacs are designed to switch loads with either of the following characteristics:• 20 mA minimum, 24 VAC @ 1 A maximum (with a total
load current from all triacs not to exceed 2.8 A, TBV).
Table 4: Auxiliary control board address switches
CCB1 (2) Up Down Up Up Up Up Up UpCCB2 (3) Down Down Up Up Up Up Up UpEHB1 (4) Up Up Down Up Up Up Up UpGCB1 (5) Down Up Down Up Up Up Up UpERB1 (6) Up Down Down Up Up Up Up Up
Daikin IM 696-4 9
General Description
Auxiliary Control Boards (CCB1, CCB2, GCB1, EHB1, and ERB1) Output RelaysBinary outputs BO1 and BO2 control high power Form A electromechanical relays mounted on the auxiliary control board. The output terminals of these relays are connected to the binary output terminals located on the left side of the auxiliary control board. These relays are designed to switch loads with either of the following characteristics:• 1 hp 120 VAC• 25 A resistive @ 120 VAC
Note – For this product application, place both jumpers on theboards just below the upper right corner of the RS-485 Communication Card on the right most pins. If these are not positioned correctly, the devices controlled by binary outputs BO1 and BO2 will not function properly.
Binary outputs BO3 through BO5 and BO7 through BO9 control low power Form A electromechanical relays mounted on the auxiliary control board. The output terminals of these relays are connected to the binary output terminals located on the left side of the auxiliary control board. These relays are designed to switch loads with either of the following characteristics:• 1/10 hp 120 VAC• 5 A resistive @ 120 VAC
Binary output BO6 controls one low power Form C electromechanical relay mounted on the auxiliary control board. The output terminals of this relay are connected to the binary output terminals located on the left side of the auxiliary control board. This relay is designed to switch loads with either of the following characteristics:• 1/10 hp 120 VAC• 5 A resistive @ 120 VAC
Keypad/DisplayThe keypad/display, shown in Figure 7 on page 10, has eight keys and a 4-line by 20-character LCD display. The keypad/display is the operator interface to the MCB. All operating conditions, system alarms, control parameters, and schedules can be monitored from the keypad/display. If the correct password is entered, adjustable parameters or schedules can be modified. For information on using the, keypad/display refer to the “Getting Started” section of the applicable operation manual (Refer to Table 1 on page 1).
Figure 7. Keypad/display
Remote Keypad Display OptionA unit may be equipped with a remote keypad/display option. When this is the case, either the local unit keypad/display or the remote keypad/display is active. When the selector switch on the remote keypad/display control board in the unit is switched to the “local” setting, the local keypad/display is active and the remote keypad/display is disabled (the “local” LED on the board is ON and the “remote” LED on the board is OFF). When the selector switch is switched to the “remote” setting, the remote keypad/display is active and the local keypad/display is disabled (the “local” LED on the board is OFF and the “remote” LED on the board is ON).
Note – When the selector switch position is changed, the selected keypad/display goes through the “normal” power up sequence before becoming active. Generally this takes about 60 seconds.
The operation of the remote keypad is identical to that of the local keypad/display as described in the appropriate operation manual for the unit. Refer to Table 1 on page 1.
WARNINGUnit can be started from a remote location. Severe personal injury or death can occur.When the remote keypad is enabled, the unit can be started from a remote location. Before servicing unit, make sure the keypad/display selector switch is in the “local” position (“local” LED on the remote keypad/display control board is ON and the “remote” LED is OFF) or that remote keypad is physically disconnected. If the local unit keypad/display is blank, assume that the remote keypad display is enabled.
10 Daikin IM 696-4
General Description
Temperature SensorsThe MicroTech II controller uses passive positive temperature coefficient (PTC) sensors. These sensors vary their input resistance to the MCB as the temperature changes. Resistance versus temperature information is included in “Troubleshooting Temperature Sensors” on page 63.
Pressure TransducersThe MicroTech II controller uses 0 to 5" w.c., 1 to 6 VDC static pressure transducers for measuring duct static pressure. If building static pressure control is provided, a –0.25" w.c. to 0.25" w.c., 1 to 5 VDC static pressure transducer is used. Voltage-to-pressure conversion data is included in “Troubleshooting Pressure Transducers” on page 65.
Humidity SensorsThe MicroTech II controller uses 0–100% RH, 0–5 VDC humidity sensors. Refer to “Humidity Sensors” on page 18 for details regarding these sensors.
ActuatorsThe MicroTech II controller uses floating-point (tri-state) control actuators for valve and damper modulation.
Spring-return actuators are used for the cooling and heating valves and mixing dampers (outside air and return air). All cooling and heating valves are normally open and the mixing dampers are normally closed to the outside air. On units equipped with face and bypass (F&BP) dampers, a spring-return, two-position end-of-cycle (EOC) valve is used to prevent overheating or overcooling when the dampers are in the full bypass position. All EOC valves are normally open.
The controller senses position feedback in the form of 0–5 VDC signals through 0–500 ohms potentiometers on the heating and cooling valve and mixing damper actuators. The MCB uses these feedback signals to display cooling or heating capacity, mixing damper position and discharge and return fan capacity.
Note – Face and bypass damper actuators are not equipped with feedback to the controller. When a unit is equipped with chilled water cooling with face and bypass or hot water or steam heating with face and bypass, the cooling or heating capacity is calculated by the MCB based on drive open versus drive close time of the actuator.
Variable Frequency Drives (VFDs)When controlling discharge, return, or exhaust fan variable frequency drives, the MicroTech II controller uses floating-point (tri-state) output signals to modulate the drive speed.
Speed feedback is supplied to the controller via a 0–10 VDC signal from the VFD. The MCB uses these feedback signals to display discharge and return fan capacity.
Daikin IM 696-4 11
Field Wiring
Field Wiring
Below are descriptions of the various options and features that may require field wiring to the MicroTech II controller. Refer to the job plans and specifications and the as-built wiring schematics. For a typical set of wiring schematics, refer to “Typical Wiring Diagrams” on page 34.
For more information on the electrical installation, refer to “Field Control Wiring” in the “Electrical Installation” section of the applicable unit installation manual (see Table 2 on page 1).
Field Output SignalsThe following output signals may be available for field connections to a suitable device:• Remote Alarm Output (MCB-BO4)• Fan Operation Output (MCB-BO3)• VAV Box Output (MCB-BO12)• Generic condensing unit staged cooling outputs
(GCB1–BO1 through GCB1–BO9)
The Remote Alarm Output and Fan Operation Output are available on all units. The VAV Box Output is available only on VAV units. The optional staged cooling outputs are available only on RDS and RAH units interfaced to a field-supplied condensing unit.
Remote Alarm OutputThe Remote Alarm Output (MCB-B04) supplies 24 VAC to terminal 115 on the field terminal block (TB2) when the output is on. To use this signal, wire the coil of a field supplied and installed 24 VAC pilot relay across terminals 115 and 117 on TB2. When this output is on, 24 VAC is supplied from the T3 control transformer through output relay MCB-B04 to energize the field relay. Refer to the as-built wiring diagrams.
CAUTION
The action of this output depends on the setup of each of the possible alarms. The output is on continuously (field relay energized) when there are no active alarms within the unit controller. Each alarm is then configured to cause the output to turn off, blink on and off rapidly, blink on and off slowly, or remain on (no alarm indication). For details regarding how to use the keypad to configure these alarms, refer to the “Alarm Monitoring” section of the applicable operation manual (see Table 1 on page 1).
Fan Operation OutputThe Fan Operation Output (MCB-B03) supplies 24 VAC to terminal 116 on the field terminal block (TB2) when the output is on. To use this signal, the coil of a field supplied and installed 24 VAC pilot relay must be wired across terminals 116 and 117 on TB2. When the output is energized, 24 VAC is supplied from the T3 control transformer through output relay MCB-B03 to energize the field relay. Refer to the as-built wiring diagrams.
CAUTION
The Fan Operation Output (MCB-BO3) can be used to control field equipment that depends on fan operation (field installed isolation dampers, VAV boxes, etc.) This output is turned on at the beginning of the Startup operating state and remains on during fan operation. The fans remain off during the Startup operating state allowing time for equipment such as isolation dampers to open prior to the starting of the fan. The duration of the Startup operating state is adjustable by setting the Start Init= parameter in the Timer Settings menu on the keypad. When the unit is shut off this output remains on for 30 seconds after the airflow switch stops sensing airflow. This output is on whenever the airflow switch senses airflow.
Note – If the DF CapCtrl= parameter in the Unit Configuration menu of the keypad is set to “Position,” the output turns off three minutes after the unit shuts off and remains off until the unit is restarted. For more details regarding the sequence of this output, refer to the applicable operation manual (see Table 1 on page 1).
The total VA of all field-mounted relays cannot exceed 15 VA, and they must have a 24 VAC Class 2 coil. Other power can cause unit malfunction.
The total VA of all field-mounted relays cannot exceed 15 VA, and they must have a 24 VAC Class 2 coil. Other power can cause unit malfunction.
12 Daikin IM 696-4
Field Wiring
VAV Box OutputThe VAV Box Output (MCB-B012) supplies 24 VAC to terminal 118 on the field terminal block (TB2) when the output is on. To use this signal, the coil of a field supplied and installed 24 VAC pilot relay must be wired across terminals 118 and 117 (units with inlet guide vanes) or 119 and 117 (units with VFDs) on TB2. When the output is energized, 24 VAC is supplied from the T3 control transformer through output relay MCB-B012 to energize the field relay. Refer to the as-built wiring diagrams or to “Auxiliary VFD control” on page 48.
CAUTION
The VAV Box Output (MCB-BO12) is designed to coordinate unit operation with VAV box control. Field use of this output is optional; however, it is highly recommended, especially for VAV systems that have heating capability (unit or duct mounted).
The following are application guidelines for four basic heating configurations. For all of these configurations, the VAV Box Output (MCB-BO12) is off for an adjustable time period after unit start-up (default is 3 minutes). During this period (the Recirc operating state), heating and cooling is disabled, and the outside air damper is held closed. The fans circulate building air and equalize space, duct, and unit temperatures.
Cooling Only Units
For cooling only VAV systems, the VAV Box Output can override zone thermostat control and drive the VAV boxes fully open to facilitate air circulation during the Recirc operating state. During this time, the VAV Box Output is in the OFF (or heat) position (field-installed pilot relay de-energized).
VAV units have a “post heat” control feature that forces the discharge air volume to a minimum before turning on the VAV Box Output when the Recirc operating state is complete. Post heat operation prevents excessive duct static pressure that could otherwise occur when the zone thermostats regain VAV box control.1
When the unit is not in the Startup or Recirc operating state and “post heat” is not active, the VAV Box Output is in the ON
(or cool) position (field relay energized) so that the zone thermostats control the VAV boxes.
The field-supplied fan operation and VAV box relay contacts can be wired in series so that the boxes open when the unit is not operational.
Cooling Only Units with Field Supplied Heat
For VAV systems with cooling only rooftop units and duct mounted reheat coils, the VAV Box Output can override zone thermostat control and drive the VAV boxes fully open when heating is required. If necessary, the MicroTech II controller energizes the fans for night setback and morning warm-up heating operation. When this occurs, the unit enters and remains in the UnocFanO or MWU operating state until heat is no longer required. The temperature control sequences are the same as those for units with factory-supplied heating equipment. While the unit is in these states, the VAV Box Output is in the OFF (or heat) position (field-supplied pilot relay de-energized).
VAV units have a “post heat” control feature that forces the discharge air volume to a minimum before closing the VAV box output when the heating period is complete. “Post heat” operation prevents excessive duct static pressure that could otherwise occur when the zone thermostats regain VAV box control.1
When the unit is not in the Startup, Recirc, or any heating operating state and “post heat” is not active, the VAV Box Output is in the ON (or cool) position (field-supplied pilot relay energized) so that the zone thermostats control the boxes.
The field supplied fan operation and VAV box relay contacts can be wired in series so that the boxes open when the unit is not operational.
Units with One-Stage Heat
The VAV Box Output should be used to override zone thermostat control and drive the VAV boxes fully open when heating is required. While the unit is in Startup, Recirc, or any heating operating state (UnocHtg, MWU, or Heating), the VAV Box Output is in the OFF (or heat) position (field-installed pilot relay de-energized).
VAV units have a “post heat” control feature that forces the discharge air volume to a minimum before closing the VAV Box Output when the unit leaves the Recirc or any other heating operating state. “Post heat” operation prevents excessive duct static pressure conditions that could otherwise occur when the zone thermostats regain VAV box control.1
When the unit is not in Startup, Recirc, or any other heating state and post heat operation is not active, the VAV Box Output is in the ON (or cool) position (field-supplied pilot relay energized) so that the zone thermostats control the boxes.
The field-supplied fan operation and VAV box relay contacts can be wired in series so that the boxes open when the unit is not operational.
The total VA of all field-mounted relays cannot exceed 15 VA, and they must have a 24 VAC Class 2 coil. Other power can cause unit malfunction.
1. The setting of a “post heat” timer determines theduration of post heat operation. This timer is set tozero at the factory and must be set to a non-zerovalue to enable the “post heat” function. For moreinformation on post heat operation, refer to “PostHeat Operation” in the “Discharge Fan AirflowControl” section of the applicable VAV operationmanual (see Table 1 on page 1).
Daikin IM 696-4 13
Field Wiring
Units with Modulating Heat
The VAV Box Output should be used to switch the VAV boxes between heating and cooling control. While the unit is in Startup, Recirc, or any heating operating state (UnocHtg, MWU, or Heating), the VAV Box Output is in the OFF (or heat) position (field-installed pilot relay de-energized) switching the VAV boxes into heating operation.
VAV units have a “post heat” control feature that forces the discharge air volume to a minimum before closing the VAV Box Output when the unit leaves Recirc or any other heating operating state. “Post heat” operation prevents excessive duct static pressure that could otherwise occur when the zone thermostats regain VAV box control.1
When the unit is not in Startup, Recirc, or any other heating operating state, the VAV Box Output is in the ON (or cool) position (field-supplied pilot relay energized) switching the boxes to cooling control.
Staged Cooling OutputsModel RDS and RAH rooftop air handlers can be ordered with factory-installed evaporator coils and the capability to control up to eight stages of field-supplied cooling equipment. The MicroTech II outputs designated for these applications are GCB1-BO1 through GCB1-BO8. These outputs are wired to terminal block TB4 in the main control panel for connection to the field supplied condensing unit. Refer to the as-built wiring schematics for the unit or to Figure 25 on page 56.
As the controller increases cooling capacity, it sequentially energizes the relays in ascending order. As the controller decreases cooling capacity, it sequentially de-energizes the relays in descending order. Refer also to Table 19 on page 31.
Field Analog Input Signals
Zone Temperature Sensor PackagesTable 5 lists the two zone (space) temperature sensor packages that are available for use with applied rooftop units equipped with a MicroTech II controller. A zone temperature sensor (ZNT1) is optional for all rooftop units except for the 100% outdoor air CAV-ZTC (SCC) unit in which case one is required. In all unit configurations, however, a zone temperature sensor is required to take advantage of any of the following standard controller features:• Unoccupied heating or cooling• Pre-occupancy purge• Discharge air reset based on space temperature (DAC units
only)• Timed tenant override• Remote set point adjustment (CAV-ZTC units only)
Daikin part no.
Tenant override switch
Remote set point
adjustment
For use with
DAC CAV-ZTC (SCC)
111048101 Yes No X X111048102 Yes Yes X
Zone Sensor without Remote Set Point Adjustment
The standard MicroTech II room temperature sensor package that does not include set point adjustment can be used with any applied rooftop MicroTech II control configuration. It includes a tenant override button.
This zone sensor must be field installed and field-wired to the unit using twisted pair, shielded cable (Belden 8761 or equivalent). Figure 8 shows the required wiring termination points.
Table 5: MicroTech II zone temperature sensors
14 Daikin IM 696-4
Field Wiring
Zone Sensor with Remote Set Point Adjustment
The standard MicroTech II room temperature sensor package equipped with a set point adjustment potentiometer is available to use with CAV-ZTC (SCC) units. This sensor package also includes a tenant override button. The set point adjustment potentiometer is wired across analog input MCB-AI2. The set point varies from 52°F to 83.2°F as the resistance changes from 0–1660 ohms.
This zone sensor package must be field installed and field wired to the unit using twisted, shielded cable. Four conductors with a shield wire are required. Cable with 22 AWG conductors (Belden 8761 or equivalent) is sufficient. Figure 9 shows the required wiring termination points.
CAUTION
Figure 8. Zone sensor with tenant override
WALLSTAT
3
4
120
ZNT1 ZONE SENSOR
Shield Wire
OVERRIDE121
INPUT
GND.
Unit TerminalBlock TB2
Figure 9. Zone sensor with tenant override and remote set point adjustment
WALLSTAT
3
4
120
ZNT1 ZONE SENSOR
Shield Wire
1326 COOLING & HEATING
SETPOINT
OVERRIDE121
INPUT
GND.
INPUT
Unit TerminalBlock TB2
Tenant Override (Timed)The tenant override button provided with the two optional zone temperature sensor packages can be used to override unoccupied operation for a programmed time period. This time period is adjustable between 0 and 5 hours using the TntOvrd= parameter in the Timer Settings menu of the keypad/display (default is 2 hours). Except for the fact that it is temporary, tenant override operation is identical to occupied operation.
Pressing and releasing the push button switch on the sensor momentarily shorts zone temperature sensor ZNT1, resetting and starting the override timer. The unit then starts up and runs until the override timer times out.
Note – Hold the button in for at least 1 second but not more than 30 seconds.
For detailed information on setting the override timer, refer to the “Auto/Manual Operation” section of the applicable operation manual (see Table 1 on page 1).
Note – If this tenant override feature is used on a VAV unit, it may be necessary to signal the VAV boxes that the unit is operating. Use the VAV Box Output for this purpose.
Do not install this cable in the same conduit as power wiring. Such installation can cause unit malfunction.
Daikin IM 696-4 15
Field Wiring
External Discharge Air Reset SignalThe discharge air temperature set point on DAC units can be reset by an external voltage or current signal applied to analog input MCB-AI2. The external reset method can be selected at the controller keypad. External reset requires a field supplied reset signal in the range of 0–10 VDC or 0–20 mA wired to terminals 132 and 133 on the field terminal block (TB2). Refer to the unit wiring diagrams or Figure 16 on page 38 for wiring termination details.
CAUTION
If the external reset option is selected, the controller linearly resets the cooling and heating discharge air temperature set points between user-programmed minimum and maximum values as the field supplied reset signal varies from a minimum to maximum (or maximum to minimum) value.
Field wire the external reset signal to the unit using a twisted pair, shielded cable (Belden 8761 or equivalent). Cable with 22 AWG conductors is sufficient.
CAUTION
Note – If the field signal is in the 0–10 VDC range, configure the analog input jumper associated with analog input MCB-AI2 in the no-jumper (NJ-VDC) position. The analog input DIP switch for this input then must be in the ON (V) position. If the field signal is in the 0–20 mA range, configure the jumper in the current (2-MA) position. The analog input DIP switch for this input then must be in the OFF (T) position.
Detailed information regarding discharge air temperature reset is located in the “Discharge Set Point Reset” section of the applicable operation manual (see Table 1 on page 1).
External Outdoor Air Damper Reset Signal
CAUTION
On units equipped with a 0–100% modulating economizer but not equipped with the optional Design Flow outdoor air measuring option, the minimum outside air damper position set point can be reset by an external voltage or current signal applied to analog input MCB-AI7. The external reset method can be selected at the controller keypad. External reset requires a field supplied reset signal in the range of 0–10 VDC or 0–20 mA wired to terminals 124 and 125 on the field terminal block (TB2). Refer to the unit wiring diagrams or Figure 18 on page 42 (SCC units) for wiring termination details.
If the external reset option is selected, the controller linearly resets the outside air damper position set point between user-programmed minimum and maximum values as the field supplied reset signal varies between a minimum and maximum (or maximum to minimum) value.
The external reset signal must be field-wired to the unit using a twisted pair, shielded cable (Belden 8761 or equivalent). Cable with 22 AWG conductors is sufficient.
CAUTION
Note – If the field signal is in the 0–10 VDC range, configure the analog input jumper associated with analog input MCB-AI7 in the no-jumper (NJ-VDC) position. The analog input dip-switch for this input then must be in the ON (V) position. If the field signal is in the 0–20 mA range, configure the jumper in the current (2-MA) position. The analog input dip-switch for this input then must be in the OFF (T) position.
Detailed information regarding outside air damper position reset can be found in the “Economizer” section of the applicable operation manual (see Table 1 on page 1).
Ground loop current hazard. Can cause equipment damage.Isolate the external reset signal from any ground other than MicroTech II controller chassis ground. If not isolated, ground loop currents can occur, causing damage or erratic unit operation. The device or system providing external reset signal must be connected to the MicroTech II controller chassis, or it must be providing an isolated output. If not, condition the signal with a signal isolator.
Do not install this cable in the same conduit as power wiring. Such installation can cause unit malfunction.
Ground loop current hazard. Can cause equipment damage.Isolate the external reset signal from any ground other than MicroTech II controller chassis ground. If not isolated, ground loop currents can occur, causing damage or erratic unit operation. The device or system providing external reset signal must be connected to the MicroTech II controller chassis, or it must be providing an isolated output. If not, condition the signal with a signal isolator.
Do not install this cable in the same conduit as power wiring. Such installation can cause unit malfunction.
16 Daikin IM 696-4
Field Wiring
Field Valve Actuator FeedbackWhen the MicroTech II controller is interfaced with a field supplied hot water, steam, or chilled water valve actuator, a position feedback signal can be field-wired from the actuator and input to the MCB. This signal is not required for control purposes but is required for 0–100% capacity indication on the keypad or via a network interface. If the signal is not supplied, the valve is controlled properly, but associated capacity parameter will always indicate 0%.
Field wire the external feedback signal to the unit using a twisted pair, shielded cable (Belden 8761 or equivalent). Cable with 22 AWG conductors is sufficient.
CAUTION
Field Hot Water or Steam Valve Actuator. When interfaced with a field-supplied hot water or steam valve actuator, a valve feedback signal in the form of a resistance that varies from 0 to 500 ohms or 0–5 VDC as the actuator strokes from 0 to 100% open can be wired to terminals 91 and 92 on the field terminal block (TB2). These terminals are factory-wired to analog input MCB-AI10. Refer to the unit wiring diagrams or Figure 16 on page 38 (DAC units) or Figure 18 on page 42 (SCC units) for wiring termination details.
If the field-supplied feedback signal is 0–500 ohms, the following procedures are required:1 Set the analog input jumper associated with MCB-AI10 to
the resistance (1-RTD) position.2 Set the analog input DIP switch associated with MCB-AI10
to the OFF (or T) position.3 Set the Feedback= parameter in the Heating Setup menu on
the unit keypad/display to “2 Wire.”4 After the three items above are set, run the unit through the
Calibrate Mode.
If the field supplied feedback signal is 0–5 VDC, the following procedures are required:1 Set the analog input jumper associated with MCB-AI10 to
the no jumper (NJ-VDC) position.2 Set the analog input DIP switch associated with MCB-AI10
to the ON (or V) position.3 Set the Feedback= parameter in the Heating Setup menu on
the unit keypad/display to “3 Wire.”4 After the three items above are set, run the unit through the
Calibrate Mode.
Field Chilled Water Valve Actuator. When interfaced with a field-supplied chilled water valve actuator, a valve feedback signal in the form of a resistance that varies from 0 to 500 ohms or 0–5 VDC as the actuator strokes from 0 to 100% open can be wired to terminals 8 and 9 on the terminal block (TB5). These terminals are factory-wired to analog input
MCB-AI11. Refer to the unit wiring diagrams for wiring termination details.
If the field-supplied feedback signal is 0–500 ohms, the following procedures are required:1 Set the analog input jumper associated with MCB-AI1 to
the resistance (1-RTD) position.2 Set the analog input dip-switch associated with MCB-AI11
to the OFF (or T) position.3 Set the Feedback= parameter in the Chilled Water Setup
menu on the unit keypad/display to “2 Wire.”4 After the three items above are set, run the unit through the
Calibrate Mode.
If the field supplied feedback signal is 0–5 VDC, the following procedures are required:1 Set the analog input jumper associated with MCB-AI11 to
the no jumper (NJ-VDC) position.2 Set the analog input dip-switch associated with MCB-AI11
to the ON (or V) position.3 Set the Feedback= parameter in the Chilled Water Setup
menu on the unit keypad/display to “3 Wire.”4 After the three items above are set, run the unit through the
Calibrate Mode.
Do not install this cable in the same conduit as power wiring. Such installation can cause unit malfunction.
Daikin IM 696-4 17
Field Wiring
Humidity SensorsWhen the MicroTech II controller is configured for constant volume zone temperature control (SCC), a dehumidification sequence is available and can be activated through the keypad. In order to use this function, an optional factory-supplied, field-mounted humidity sensor is required.
Either a wall mount or duct mount sensor is available. The sensor must be wired to terminals 126, 127 and 131 on the unit field terminal block (TB2). Terminal 126 is wired to OUT (0–5 VDC), terminal 127 to GND and terminal 131 to PWR on the humidity sensor. These terminals are factory wired to the MCB analog input MCB-AI12. The input must be 0–5 VDC as the relative humidity varies from 0–100%. Refer to the unit wiring diagrams or Figure 18 on page 42 for wiring termination details.
Note – The output select jumper (J1) on the sensor must be in the 0–5 VDC position. The TEMP terminals on the sensor are not used (see Figure 10 or Figure 11 on page 18).
Field wire the humidity sensor wiring to terminals 126 and 127 to the unit using a twisted pair, shielded cable (Belden 8761 or equivalent). Cable with 22 AWG conductors is sufficient.
CAUTION
Note – Set the analog input jumper associated with MCB-AI12 to the no jumper (NJ-VDC) position. Set the analog input dip switch associated with this input to the ON (V) position.
Figure 10: Humidity sensors (wall mount)
Output adjustmentjumper
0 to 5V0 to 10V
Terminal block TB1
Output adjustmentpotentiometer
Output Adjust
Up
Terminal blo
Wiring open
Mountingdirectionarrows
Figure 11: Humidity sensor (duct mounted)
0–5 V Output jumper Wiring block
(screw terminals are accessed through the cutoutin the housing.)
Of fset adjustment potentiometer
Screw hole
Screw hole Probe
0–10 V Output jumper (factory set)
OUTPUT SELECTION
INPUT18-30V AC,12-30VDC OUTPUT0-10,OR0-5VDC
TERMINAL DESIGNA TION
OFFSET ADJUST
DA TE
0-5V
0-10
V
PWR
OU
T TE
MP
TEM
P
CO
M
Do not install this cable in the same conduit as power wiring. Such installation can cause unit malfunction.
18 Daikin IM 696-4
Field Wiring
Humidity Sensor—Discharge Air Control (DAC) Unit
A humidity sensor can be wired to terminals 126, 127 and 131 on TB2 on a discharge air control (DAC) unit as shown on the unit wiring diagram or Figure 16 on page 39. However, this input is not used for control purposes and the current relative humidity value from the sensor cannot be read via the keypad/display. The current value from the sensor can be read via a network interface only.
Field Binary Input SignalsThe following sections describe options that, if used, require field wiring to binary input terminals. Twisted pair, shielded cable is not required for binary input wiring.
Manual Cooling and Heating EnableCooling Enable
24 VAC must be applied to binary input MCB-BI3 to enable cooling operation. If not, the unit Clg Status= parameter in the System menu of the keypad/display indicates “Off Sw” and cooling operation is unavailable. 24 VAC is applied to MCB-BI3 when terminals 101 and 105 on the unit field terminal block (TB2) are made; either with a factory installed jumper wire or a field supplied switch. Refer to the unit wiring diagrams or Figure 16 on page 39 (DAC units) or Figure 17 on page 40 (SCC units) for wiring termination details.
Heating Enable
24 VAC must be applied to binary input MCB-BI4 to enable heating operation. If not, the Htg Status= parameter in the System menu of the keypad/display indicates “Off Sw” and heating operation is unavailable. 24 VAC is applied to MCB-BI4 when terminals 101 and 106 on the field terminal block (TB2) are made; either with a factory installed jumper wire or field supplied switch. Refer to the unit wiring diagrams or Figure 16 on page 38 (DAC units) or Figure 17 on page 41 (SCC units) for wiring termination details.
Manual Unit EnableUnit operation is manually disabled when 24 VAC is applied to binary input MCB-BI2. The UnitStatus= parameter in the System menu of the keypad/display indicates “Off Sw” and the unit will not operate. This occurs when a field supplied and installed switch across terminals 101 and 104 on the field terminal block (TB2) is in the on or closed position. Refer to the unit wiring diagrams or Figure 16 on page 39 (DAC units) or Figure 17 on page 40 (SCC units) for wiring termination details.
If not disabled by this method, the unit is enabled to run when placed in the occupied mode. For details regarding occupied/unoccupied operation refer to the “Auto/Manual Operation” section of the appropriate program-specific operation manual (refer to Table 1 on page 1).
External Time Clock or Tenant OverrideThere are several methods of switching the rooftop unit between occupied and unoccupied operation. It can be done by the controller internal schedule, a network schedule, an external time clock, or a tenant override switch.
If the internal schedule or a network schedule is used, field wiring is not required.
An external time clock or a tenant override switch can be used by installing a set of dry contacts across terminals 101 and 102 on the field terminal block (TB2). When these contacts close, 24 VAC is applied to binary input MCB-BI1, overriding any internal or network schedule and placing the unit into occupied operation (provided the unit is not manually disabled). When the contacts open (24 VAC is removed from MCB-BI1) the unit acts according to the controller internal time schedule or a network schedule. Refer to the unit wiring diagrams or Figure 16 on page 39 (DAC units) or Figure 17 on page 40 (SCC units) for wiring termination details.
For information on setting internal and network controller schedules, refer to the “Scheduling” section in the applicable operation manual (refer to Table 1 on page 1).
Daikin IM 696-4 19
Field Wiring
Miscellaneous Output SignalsThe five optional output signals listed below can be provided by installing field supplied 24 VAC relays wired between terminal 107 on the field terminal block (TB2) and the terminals listed in Table 6. Refer to the unit wiring diagrams or Figure 16 on page 39 (DAC units) or Figure 17 on page 40 (SCC units) for wiring termination details.
CAUTION
• Airflow status• Dirty filter (including optional final filter)• Gas furnace fail alarm (Heat Fail)• Freeze alarm (steam or water coils, optional)• Smoke alarm (optional)
Terminal block TB2 Description Energized field
relay indication
External Exhaust Fan StatusWhen a large exhaust fan or group of exhaust fans is started or stopped during normal rooftop unit operation, the building static pressure may become too positive or negative. If a field binary input signal is delivered to the unit when an external exhaust fan is started, a VAV unit controller that uses “fan tracking” control can modify its return fan control algorithm to compensate for the change in exhaust fan airflow. The fan tracking control feature can reduce or eliminate objectionable building pressure fluctuations that might otherwise occur.
To take advantage of this exhaust fan airflow compensation feature, field wire a set of dry contacts across terminals 101 and 103 on the field terminal block (TB2). When these contacts close, 24 VAC is applied to binary input MCB-BI13, indicating that the external exhaust fan is on. When the contacts open, 24 VAC is removed from MCB-BI13, indicating that the exhaust fan is off. Refer to the unit wiring diagrams or Figure 16 on page 39 for wiring termination details.
For detailed information on the fan tracking feature, refer to the “Return Fan Capacity Control” section of the DAC operation manual (refer to Table 1 on page 1).
The total VA of all field-mounted relays cannot exceed 15 VA and they must have a 24 VAC Class 2 coil. Other power can cause unit malfunction.
Table 6: Miscellaneous field signal termination points
107 Ground NA
108 Fan operation (airflow indication) Airflow present
109 Dirty filter indication Filters dirty
111 Heat alarm detected (gas heat flame failure)
Alarm
112 Freezestat (freeze condition detected)
Normal
113 Smoke (smoke detected) Normal
20 Daikin IM 696-4
Service Information
Service Information
Controller Inputs
Analog Inputs-Main Control Board (MCB)The 16 analog inputs to the MCB are configurable for four different input types by positioning a jumper associated with each input position (refer to Figure 12). The four jumper positions are 1-RTD (temperature sensor or potentiometer), 2-MA (current), 3-NTC (10K ohms thermistor) or no jumperNJ-VDC (voltage).
Figure 12. Analog input jumpers (MCB)
1-RTD 2-MA 3-NTC NJ-VDC
Topof
MCB
The 1-RTD jumper position is used for all the temperature sensor inputs and 0-500 ohm actuator potentiometer position feedback inputs. The NJ-VDC (no jumper) position is used for 0–5 VDC actuator position feedback inputs and the remainder of the standard input devices which are configured for either 0–5 VDC or 0–10 VDC. The 2-MA and the 3-NTC (10K ohm thermistor) jumper positions are not used in this product application for any of the standard input devices. Refer to Table 7 on page 22 (DAC units) and Table 8 on page 22 (SCC units) for a description of all the analog inputs including the correct jumper positions.
In addition to the analog input jumpers, there are two sets of dip switches (SW1 and SW4) associated with the MCB analog inputs. Each set contains eight switches numbered 1 through 8. Refer to Figure 13. The switches on SW1 correspond to inputs MCB-AI1 through MCB-AI8 and the switches on SW4 correspond to inputs MCB-AI9 through MCB-AI16. One switch corresponds to each analog input. If the input is a temperature sensor or potentiometer input (input jumper in the 1-RTD position) then the corresponding switch must be in theT (OFF) position. If the input is a voltage input (no inputjumper NJ-VDC position) then the corresponding switch mustbe in the V (ON) position. Table 7 on page 22 (DAC units) andTable 8 on page 22 (SCC units) include the correct switchsettings for all the analog inputs.
Note – If a special application requires a current input with the input jumper set to the 2-MA position, then the corresponding input switch must be set to the T (OFF) position.
Figure 13. Analog input switches (MCB)
Daikin IM 696-4 21
Service Information
.
Analog input Input description Input jumper Input switch
Analog input Input Description AI jumper AI switch
Table 7: Analog inputs for main control board (MCB)—discharge air controller (DAC)
MCB-AI1 Zone (space) air temperature (optional) 1-RTD T (OFF)MCB-AI2 External discharge air temperature reset NJ-VDC (no jumper) V (ON)MCB-AI3 Discharge air temperature 1-RTD T (OFF)MCB-AI4 Return air temperature 1-RTD T (OFF)MCB-AI5 Outdoor air temperature 1-RTD T (OFF)MCB-AI6 Entering fan air temperaturea 1-RTD T (OFF)MCB-AI7 External OA damper reset NJ-VDC (no jumper) V (ON)
DesignFlow OA airflow #1 (right-hand station)b NJ-VDC (no jumper) V (ON)MCB-AI8 DesignFlow OA airflow #2 (left-hand station)c NJ-VDC (no jumper) V (ON)MCB-AI9 Outdoor air damper positionh NJ-VDC (no jumper) V (ON)MCB-AI10 Heating valve positionh NJ-VDC (no jumper) V (ON)MCB-AI11 Cooling valve positionh NJ-VDC (no jumper) V (ON)
Evaporative Condenser Sump Temperature 1-RTD T (OFF)MCB-AI12 Relative humidityd NJ-VDC (no jumper) V (ON)MCB-AI13 Duct static pressure #1e NJ-VDC (no jumper) V (ON)MCB-AI14 Duct static pressure #2/building static pressure (optional)f NJ-VDC (no jumper) V (ON)MCB-AI15e Discharge fan VFD speed /inlet vane position NJ-VDC (no jumper) V (ON)MCB-AI16g Return fan VFD speed NJ-VDC (No Jumper) V (ON)
a. EFT sensor supplied only on units equipped with gas or electric heat.b. If unit equipped with DesignFlow OA airflow measuring stations, input is an airflow signal from the right-hand DesignFlow station. Otherwise, is an optional
external OA damper position reset signal supplied by field.c. If unit equipped with DesignFlow OA airflow measuring stations, input is an airflow signal from the left-hand DesignFlow station. Otherwise it is a spare input.d. A humidity sensor can be wired to this input to provide a space humidity reading via a BACnet network interface to the unit.e. This input applicable to VAV units only (discharge fan VFD or inlet vanes).f. This input defined as a second duct static pressure input on VAV units if the unit is configured for “fan tracking” return fan control. It is defined as a building
static pressure input if unit is configured for “direct building pressure” return fan control.g. This input applicable on units equipped with a return VFD or inlet vanes.h. Some older units are equipped with a 0–500Ω (2-wire) resistance feedback signal. In this case, the analog input jumper must be in the 1-RTD position, the
corresponding input switch must be in the T (OFF) position and the Feedback= parameter in the Economizer Setup, Heating Setup or Chilled Water Setupmenu (as applicable) must be set to “2 Wire.”
Table 8: Analog inputs for main control board (MCB)—CAV-ZTC (SCC)
MCB-AI1 Zone (space) air temperaturea 1-RTD T (OFF)MCB-AI2 Remote space temperature set point (optional) 1-RTD T (OFF)MCB-AI3 Discharge air temperature 1-RTD T (OFF)MCB-AI4 Return air temperature 1-RTD T (OFF)MCB-AI5 Outdoor air temperature 1-RTD T (OFF)MCB-AI6 Entering fan air temperatureb 1-RTD T (OFF)MCB-AI7 External OA damper reset NJ-VDC (no jumper) V (ON)
Designflow OA airflow #1 (right-hand station)c NJ-VDC (no jumper) V (ON)MCB-AI8 designflow OA airflow #2 (left-hand station)d NJ-VDC (no jumper) V (ON)MCB-AI9 Outdoor air damper positionf NJ-VDC (no jumper) V (ON)
MCB-AI10 Heating valve positionf NJ-VDC (no jumper) V (ON)MCB-AI11 Cooling valve positionf NJ-VDC (no jumper) V (ON)
Evaporative condenser sump temperature 1-RTD T (OFF)MCB-AI12 Relative humidity NJ-VDC (no jumper) V (ON)MCB-AI13 Not used NA NAMCB-AI14 Building static pressure (optional) NJ-VDC (no jumper) V (ON)MCB-AI15 Not used NA NAMCB-AI16e Return fan VFD speed NJ-VDC (no jumper) V (ON)
a. Sensor required if unit is 100% OA. Otherwise, it is optional.b. Sensor supplied only on units equipped with gas or electric heat.c. If unit equipped with DesignFlow OA airflow measuring stations, this input is an airflow signal from the right-hand DesignFlow station. Otherwise, it is an
external OA damper position reset signal supplied by the field.d. If unit equipped with DesignFlow OA airflow measuring stations, this input is an airflow signal from the left-hand DesignFlow station. Otherwise, it is a spare
input.e. This input applicable on units equipped with a return VFD or inlet vanes.f. Some older units are equipped with a 0-500W (2-wire) resistance feedback signal. In this case the analog input jumper must be in the 1-RTD position, the
corresponding input switch must be in the T (OFF) position and the Feedback= parameter in the Economizer Setup, Heating Setup or Chilled Water Setupmenu (as applicable) must be set to “2 Wire.”
22 Daikin IM 696-4
Service Information
Analog Inputs—Auxiliary Control Boards (CCB1, CCB2, GCB1, EHB1 & ERB1)The optional auxiliary control boards (CCB1, CCB2, GCB1, EHB1 and ERB1) have up to six analog inputs available. However, in this product application, these are used only on the ERB1. Analog inputs ERB1-A1 and ERB1-A2 are configured for temperature sensor inputs. The remainder are spare inputs.
Refer to Table 9 for a description of each analog input on the ERB1 board.
Analog input Input description
ERB1-AI5 Not usedERB1-AI6 Not used
Binary Inputs—Main Control Board (MCB)The 16 binary inputs to the MCB are in the form of 0 VAC (off) or 24 VAC (on) applied to the binary input terminals. Transformer T2 is the source of this the 24 VAC for these inputs.
Each binary input has an LED associated with it that lights when 24 VAC is present at the corresponding input terminal. These binary input LEDs are grouped together and are located in the upper left had corner of the board. Table 10 summarizes the binary input functions and LED indications for the binary inputs to the MCB.
Binary Inputs—Auxiliary Control Boards (CCB1, CCB2, GCB1, EHB1 & ERB1)The optional auxiliary control boards include 12 binary inputs. Inputs BI1 through BI6 are designed for a set of dry contacts between the COM terminal and the individual binary input terminals on J9. BI7 through BI12 are designed for 24 VAC inputs (input is ON when 24 VAC is present at the corresponding input terminal on J10 and OFF when 0 VAC is not present). The following sections described how these inputs are defined for each of the auxiliary control boards.
Note – The set of two jumpers in the upper right corner of the board (below the RS-485 Communications module) must both be placed on the right most pins. Placing the jumper on the left most pins interlocks binary inputs BO1 with BI1 and BO2 with BI2 respectively. This interlock is not used on this product application
CCB1 & CCB2 (7RPS, RFS/RCS, RDT, RPR & RFR)
When a unit is equipped with a factory condensing unit, each of the two cooling circuits is controlled with an auxiliary control board. Circuit #1 is controlled by the CCB1 and circuit #2 is controlled by the CCB2. Table 10 and Table 11 on page 24 summarize the binary inputs for the CCB1 and CCB2 respectively.
GCB1 (RDS & RAH)
When a rooftop air handling unit is interfaced with a field supplied condensing unit, the cooling stages in the condensing unit are controlled by a generic condenser auxiliary control board. This board is designated GCB1. In this case only GCB1-BI12 is defined in the GCB1 control software. It is a “cool enable” input. Cooling is enabled when 24 VAC is present and disabled when 24 VAC is not present at this input. This input is supplied to the GCB1 through a “cooling enable” output from the MCB.
EHB1
When a unit is equipped with multistage electric heat, the heating stages are controlled by an electric heat auxiliary control board. This board is designated EHB1. In this case only EHB1-BI12 is defined for the EHB1. It is a “heat enable” input. Heating is enabled when 24 VAC is present and disabled when 24 VAC is not present at this input. This input is supplied to the EHB1 through a “heating enable” output from the MCB.
ERB1
When a unit is equipped with an optional energy recovery wheel system, the system is controlled by an energy recovery auxiliary control board. This board is designated ERB1. None of the binary inputs are used on the ERB1.
Table 9: Analog inputs for energy recovery wheel control board (ERB1)
ERB1-AI1 Leaving energy recovery wheel temperature (exhaust), optional
ERB1-AI2 Leaving energy recovery wheel temperature (discharge)ERB1-AI3 Not usedERB1-AI4 Not used
Table 10: Binary inputs for main control board (MCB) Binary input Input description Lit LED
indicationMCB-BI1 External Time clock or tenant override OccupiedMCB-BI2 Manual system disable DisabledMCB-BI3 Remote cool enable EnabledMCB-BI4 Remote heat enable EnabledMCB-BI5 Gas furnace flame failure alarm AlarmMCB-BI6 Airflow status Airflow detectedMCB-BI7 Freeze alarm for steam or hot water coils NormalMCB-BI8 Smoke alarm: supply air, return air or both NormalMCB-BI9 First filter switch NormalMCB-BI10 Final filter switch (optional) NormalMCB-BI11 Outdoor enthalpy statusa
a. Not used on 100% outdoor air units.
Low OA enthalpyMCB-BI12 Not used —MCB-BI13 External exhaust fan status (optional)b
b. Applicable only on VAV units configured for “fan tracking” return fancontrol.
OnMCB-BI14 Duct hi limitc
c. Applicable on VAV units only.
NormalMCB-BI15 Not used —MCB-BI16 Not used —
Daikin IM 696-4 23
Service Information
Binary Input Input Description 24 VAC Present Indication
CCB1-BI1 Compressor #5 Contactor Auxiliary Switch Status M5 Contactor EnergizedCCB1BI2 Not Used -CCB1-BI3 Not Used -CCB1-BI4 Not Used -CCB1-BI5 Not Used -CCB1-BI6 Circuit #1 Low Pressure Switch Status (LP1) Switch ClosedCCB1-BI7 Circuit #1 High Pressure Switch Status (HP1 or HP3) NormalCCB1-BI8 Circuit #1 Frost Protection Switch Status (FP1) NormalCCB1-BI9 Compressor #1 Contactor Auxiliary Switch Status M1 Contactor Energized
CCB1-BI10 Compressor #3 Contactor Auxiliary Switch Status M3 Contactor EnergizedCCB1-BI11 Circuit #1 Pumpdown Switch Status Switch ClosedCCB1-BI12 Circuit #1 Cool Enable Input Enabled
Binary Input Input Description 24 VAC Present Indication
CCB2-BI1 Compressor #6 Contactor Auxiliary Switch Status M6 Contactor EnergizedCCB2-BI2 Not Used -CCB2-BI3 Not Used -CCB2-BI4 Not Used -CCB2-BI5 Not Used -CCB2-BI6 Circuit #2 Low Pressure Switch Status (LP2) Switch ClosedCCB2-BI7 Circuit #2 High Pressure Switch Status (HP2 or HP4) NormalCCB2-BI8 Circuit #2 Frost Protection Switch Status (FP2) NormalCCB2-BI9 Compressor #2 Contactor Auxiliary Switch Status M2 Contactor Energized
CCB2-BI10 Compressor #4 Contactor Auxiliary Switch Status M4 Contactor EnergizedCCB2-BI11 Circuit #2 Pumpdown Switch Status Switch ClosedCCB2-BI12 Circuit #2 Cool Enable Input Enabled
Controller Outputs
Binary Outputs—Main Control Board (MCB)The main control board has 16 binary outputs that provide unit control in response to input conditions. Binary outputs energize on-board electromechanical relays (BO1 through BO4, BO11 and BO12) or triacs (BO5 through BO10 and BO13 through BO16). Unit control devices are wired to the relays and triacs through six output terminal blocks located on the right side of the MCB.
There are three terminals associated with each binary output. The terminals associated with BO1 are labeled NO, 1, and NC, the terminals associated with BO2 are labeled NO, 2, and NC, and so forth. Each binary output has an LED associated with it that lights when the corresponding output relay or the triac is turned on.
Each binary output has an output jumper associated with it. The three jumper positions are: 1-SRC V (jumper on the bottom two pins), 2-BRD24V (jumper on the top two pins) and 3-OFFBRD (no jumper). Refer to Figure 14.
Figure 14. Binary output jumper (MCB)
2 - BRD24V(Not Used)
1 - SRC V. 3-OFFBRDTopof
MCB
When the jumper is in position 1-SRC V, 24 VAC from the SRC 1-8 terminal (BO1 through BO8) or the SRC 9-16 terminal (BO9 through BO16) is applied to the numbered terminal of the associated outputs. In the case of BO1 through BO4, BO11 and BO12, this signal is then delivered to either the NC terminal when the corresponding output is off (output relay de-energized) or the NO terminal when the corresponding output is on (output relay energized). In the case of BO5 through BO10 and BO13 through BO16, this signal is then delivered to the NO terminal when the corresponding output is on (triac energized). Transformer T3 furnishes 24 VAC to the SRC 1-8 terminal and the SRC 9-16 terminal. This jumper configuration is used when a specific binary output is used to energize a 24 VAC pilot relay in the unit. Refer to Table 13 on page 25 for the correct jumper position for all the standard binary outputs.
Table 11: Binary inputs for circuit #1 auxiliary cooling control board (CCB1)
Table 12: Binary inputs for circuit #2 auxiliary cooling control board (CCB2)
24 Daikin IM 696-4
Service Information
When the jumper is in position 3-OFFBRD (no jumper installed) there is no on-board voltage applied to the numbered terminal of the corresponding binary output. In the case of BO1 through BO4, BO11 and BO12, the numbered terminal is simply “made” to the NO terminal when the corresponding output is on (output relay energized) or to the NC terminal when the corresponding output is off (output relay de-energized). In the case of BO5 through BO10 and BO13 through BO16, the numbered terminal is simply “made” to the
NO terminal when the corresponding triac output is on. This jumper configuration is used most often in this product application. Refer to Table 13 on page 25 for the correct jumper position for all the standard binary outputs.
The 2-BRD24V jumper configuration is not used in this product application.
Binary output Output description Lit LED indication Jumper position
BO13
BO14
BO15BO16
Table 13: Binary outputs for main control board (MCB)
BO1 Discharge air fan, On/Off Fan ON 3-OFFBRD (no jumper)BO2 Return air fan, ON/OFF Fan ON 3-OFFBRD (no jumper)BO3 Fan Operation Output Signal Fans ON 1-SRC VBO4 Alarm Output Signal Normal 1-SRC VBO5 Close outdoor air dampers Closing 3-OFFBRD (no jumper)BO6 Open outdoor air dampers Opening 3-OFFBRD (no jumper)BO7a Close chilled water valve Closing 3-OFFBRD (no jumper)
Close chilled water F&BP dampers Closing 3-OFFBRD (no jumper)Cool enable Enabled 3-OFFBRD (no jumper)Evaporative condenser sump pump, ON/OFF Pump ON 3-OFFBRD (no jumper)
BO8b Open chilled water valve Opening 3-OFFBRD (no jumper)Open chilled water F&BP dampers Opening 3-OFFBRD (no jumper)
BO9c Close heating valve Closing 3-OFFBRD (no jumper)Close heating F&BP dampers Opening 3-OFFBRD (no jumper)
BO10d Open heating valve Opening 3-OFFBRD (no jumper)Open heating F&BP dampers Opening 3-OFFBRD (no jumper)
BO11e Gas furnace enable/disable Enabled 1-SRC VSingle stage heat ON/OFF Heat On 1-SRC VF&BP damper/valve changeover Dampers open / valve modulating 1-SRC VHeat enable Enabled 1-SRC V
BO12 VAV box output signal Cooling mode 3-OFFBRD (no jumper)Decrease discharge fan VFD speed Decreasing 1-SRC VDehumidification reheat circuit # 2 Reheat ON 3-OFFBRD (no jumper)Increase discharge fan VFD speed Increasing 1-SRCDehumidification reheat circuit # 1 Reheat ON 3-OFFBRD (no jumper)Decrease return fan VFD speed Decreasing 1-SRC VIncrease return fan VFD speed Increasing 1-SRC V
a. If the unit is equipped with chilled water cooling, output BO7 closes the chilled water valve. If the unit is equipped with chilled water cooling with face andbypass dampers, output BO7 closes the face dampers. If the unit is equipped with DX cooling, BO7 provides a signal to the auxiliary cooling control boards(CCB1 and CCB2) to enable cooling operation. If unit is equipped with an evaporative condenser, BO7 turns the sump pump on.
b. If the unit is equipped with chilled water cooling, output BO8 opens the chilled water valve. If the unit is equipped with chilled water cooling with face andbypass dampers, output BO8 opens the face dampers.
c. If the unit is equipped with modulating heat, output BO9 closes the heating valve. If the unit is equipped with modulating heat with face and bypass dampers,output BO9 closes the face dampers.
d. If the unit is equipped with modulating heat, output BO10 opens the heating valve. If the unit is equipped with modulating heat with face and bypass dampers,output BO10 opens the face dampers.
e. If the unit is equipped with modulating gas heat, output BO11 enables the gas furnace. If the unit is equipped with single stage heat for morning warm uppurposes, BO11 turns on the single stage of heat. If the unit is equipped with modulating heat with face and bypass dampers, BO11 changes the heat controlsuch that BO9 and BO10 either modulate the heating value or the face and bypass dampers. If the unit is equipped with multiple stage electric heat, outputBO11 provides a signal to the auxiliary electric heat control board (EHB1) to enable heating operation.
Daikin IM 696-4 25
Service Information
Binary Outputs—Auxiliary Control Boards (CCB1, CCB2, GCB1, EHB1 & ERB1)The optional auxiliary control boards include nine binary outputs that control nine on-board electromechanical relays. Unit control devices are wired to these outputs through output terminals on the left side of the board. The functions of these outputs vary for the different auxiliary board applications. The following sections describe the output functions for the auxiliary control board applications.
CCB1 and CCB2 (RPS, RFS/RCS, RDT, RPE, RDE, RCE, RPR, and RFR)
When a unit is equipped with a factory condensing unit, each of the two cooling circuits is controlled with an auxiliary control board. Circuit #1 is controlled by the CCB1 and Circuit #2 is controlled by the CCB2. There are nine binary output relays on each cooling control board. These relays are energized based on commands received from the MCB to provide the appropriate switching actions in the DX cooling control circuits.
The output relays on the CCB1 and CCB2 board control compressor contactors, compressor unloaders, circuit liquid line solenoid valves, or condenser fan outputs. Tables 14 through 21 list the CCB1 and CCB2 output functions for the available unit compressor staging configurations.
The liquid line solenoid valve on each circuit opens (BO4 turned on) before the first compressor in the circuit is turned on. Normally the compressor outputs in the circuit begin turning on according to the controller staging logic as soon as the circuit low pressure switch closes. The exception to this rule is when a unit is equipped and configured for low ambient operation. In this case the first stage compressor in a circuit is turned on at the same time the liquid line solenoid valve is opened.
The condenser fan outputs are turned on and off based on ambient temperature set points adjustable through the unit keypad.
The compressor staging sequences for the available compressor staging configurations are described in the following sections.
2-Compressors/3-Stage. In this configuration there aretwo unequally sized scroll compressors and two coolingcircuits. All cooling outputs are always controlled in the sameway. There is no compressor or circuit lead/lag operation withthis configuration.
The normal staging sequence is as follows:
When a capacity increase is required and the cooling capacity is 0%, the small compressor in Circuit #1 is turned on. When a further capacity increase is required, the large compressor in Circuit #2 is turned on while the small compressor in Circuit #1 is turned off. When a further capacity increase is required, the small compressor in Circuit #1 is turned on while the large
compressor in Circuit #2 remains on. When capacity decrease is required, the compressors stage off in the reverse order.
If the small compressor (Circuit #1) is disabled, the large compressor (Circuit #2) operates when cooling is required and the cooling capacity is set to 66%. If the large compressor is disabled, the small compressor operates when cooling is required and the cooling capacity is set to 33%.
Table 14 summarizes the normal binary output functions and staging sequencing for the CCB1 and CCB2 for the 2-Compressor/3-Stage cooling configuration. The “X”characters in Table 14 indicate that the output is energized fora particular cooling capacity.
Cooling circuit
number
Output number Description
Action with
output on
Cooling capacity (%)
0 33 66 100
Table 14: Binary outputs for cooling control boards (CCB1 and CCB2): 2-compressors/3-stage
1 (CCB1)
BO1 Compressor #1 (small compressor) ON/OFf
ON X X
BO2 Not used -BO3 Not used -BO4 Circuit # 1 liquid line
solenoid valve open/closea
a. Circuit Lead/Lag and Cross Circuit Loading versus Lead Circuit loading donot apply to this staging configuration.
Open X X
BO5 Condenser fan #11 ON/OFF
ON b
b. Condenser fan outputs turn on and off based on ambient or evaporativecondensing sump temperature set points adjustable through the unitkeypad.
c. This output is not used on unit equipped with an evaporative condenserand a VFD controlling the first condenser fan on each circuit (CondenserFan # 11 and # 21). The VFD controlling these fans is started and stoppedand modulated via RS-485 communications with the main control board.
d. This output is used to open a sump dump valve on units equipped with anevaporative condenser. Output is energized to open valve.
b
BO6 Condenser fan #12 ON/OFF
ON b b
BO7 Not used -BO8d Not used -BO9 Not used -
2 (CCB2)
BO1 Compressor #2 ON/OFF (large compressor)
ON X X
BO2 Not used -BO3 Not used -BO4 Circuit #2 liquid line
solenoid valve open/closea
Open X X
BO5 Condenser fan # 11 ON/OFFc
ON b b
BO6 Condenser fan # 12 ON/OFF
ON b b
BO7 Not used -BO8d Not used -BO9 Not used -
26 Daikin IM 696-4
Service Information
4-Compressors/4-Stage or 6-Compressor/6-Stage. In thisconfiguration there are four compressors and two coolingcircuits. The unit cooling capacity is increased and decreasedby turning on and off compressors. One of the circuits isdesignate the “Lead” and the other the “Lag” circuit. Fordetailed information regarding circuit lead/lag operation, referto the “Compressor Staging” section of the applicableoperation manual (refer to Table 1 on page 1). Disabledcompressors are not turned on.
There are two methods for controlling the two circuits when both are enabled. These are referred to as Cross Circuit Loading and Lead Circuit Loading and are described in the following sections. For detailed information regarding selecting Cross Circuit Loading versus Lead Circuit Loading, refer to the “Compressor Staging” section of the applicable operation manual (refer to Table 1 on page 1).
Cross Circuit Loading. With this method, the two circuits are alternately loaded and unloaded as evenly as possible.
The normal staging sequence is as follows:
When a capacity increase is required and the number of operating compressors in both circuits is the same, the compressor in the “Lead” circuit with the fewest run hours that is not operating is turned on. When a capacity increase is required and the number of compressors in the two circuits is not the same, the compressor in the “Lag” circuit with the fewest run hours that is not operating is turned on.
When a capacity decrease is required and the number of operating compressors in both circuits is the same, the operating compressor in the “Lag” circuit with the most run hours is turned off. When a capacity decrease is required and the number of operating compressors in the two circuits is not the same, the operating compressor in the “Lead” circuit with the most run hours is turned off.
Lead Circuit Loading. With this method, one circuit is loaded completely before the first compressor in the second circuit is turned on, and one circuit is unloaded completely before the other circuit begins to be unloaded.
The normal staging sequence is as follows:
When a capacity increase is required and the number of operating compressors is 0, the compressor in the “Lead” circuit with the fewest run hours is turned on. When a further capacity increase is required, the second compressor in the “Lead” circuit is turned on, fully loading that circuit. When a further capacity increase is required, the compressor in the “Lag” circuit with the fewest run hours is turned on. When a further capacity increase is required, the remaining compressor on the “Lag” circuit is turned on, fully loading that circuit.
When a capacity decrease is required, the compressor in the “Lag” circuit with the most run hours is turned off. When a further capacity decrease is required, the remaining compressor in the “Lag” circuit is turned off. When a further capacity decrease is required, the compressor in the “Lead” circuit with the most run hours is turned off. When a further capacity decrease is required, the remaining compressor in the “Lead” circuit is turned off.
Table 15 on page 28 summarizes the normal binary output functions and staging sequencing for the CCB1 and CCB2 for the 4-compressor/4-stage cooling configuration. Table on page 28 summarizes the normal binary output functions and staging sequences for the CCB1 and CCB2 for the 6-compressor/ 6-stage cooling configuration. The Xs in thetable indicate that the output is energized for a particularcooling capacity.
With either the Cross Circuit Loading or Lead Circuit Loading methods, a disabled circuit remains at zero capacity. If the other circuit is enabled, it acts as the “Lead” and the circuit capacity is controlled using the Lead Circuit Loading.
Daikin IM 696-4 27
Service Information
Cooling circuit
number
Output number Description
Action with
output on
Cooling capacity (%)Cross circuit loading Lead circuit loading
0 25 50 75 100 0 25 50 75 100
a. If Circuit #2 is the “lead” circuit, interchange the data in the table between CCB1 and CCB2 for the correct output staging data.b. If Compressor #3 has fewer run hours it operates instead of Compressor #1 at this cooling capacity.c. If Compressor #4 has fewer run hours it operates instead of Compressor #2 at this cooling capacity.d. Condenser fan outputs turn on and off based on ambient or evaporative condenser sump temperature set points adjustable through the unit keypad.e. This output is applicable on 060C size units only.f. This output is not used on unit equipped with an evaporative condenser and a VFD controlling the first condenser fan on each circuit (Condenser Fan # 11 and
# 21). The VFD controlling these fans is started and stopped and modulated via RS-485 communications with the main control board.g. This output is used to open a sump dump valve on units equipped with an evaporative condenser. Output is energized to open valve.
a. If Circuit #2 is the “lead” circuit, interchange the data in the table between CCB1 and CCB2 for the correct output staging data.b. If Compressor #5 has fewer run hours it operates instead of Compressor #1 or Compressor # 3 at this cooling capacity.c. If Compressor #6 has fewer run hours it operates instead of Compressor #2 or Compressor #4 at this cooling capacity.d. Condenser fan outputs turn on and off based on ambient or evaporative condenser sump temperature set points adjustable through the unit keypad.e. This output is applicable on 075C size units only, or on units equipped with an evaporative condenser in which case the output is used to open a sump dump
valve when energized.f. This output is not used on unit equipped with an evaporative condenser and a VFD controlling the first condenser fan on each circuit (Condenser Fan # 11 and
# 21). The VFD controlling these fans is started and stopped and modulated via RS-485 communications with the main control board.
Table 15: Binary outputs for cooling control boards (CCB1 and CCB2): 4-compressors/4-stage (circuit #1 lead)a
1 (CCB1) BO1 Compressor #1 ON/OFF ON X X X X X X X XBO2 Compressor #3 ON/OFF ON b b X X b X X XBO3 Not used —BO4 Circuit #1 liquid line solenoid
valve open/closeOpen X X X X X X X X
BO5 Condenser fan #11 ON/OFFf ON d d d d d d d dBO6 Condenser fan #12 ON/OFF ON d d d d d d d dBO7 Condenser fan #13 ON/OFFe ON d d d d d d d dBO8g Not usedg —BO9 Not used —
2 (CCB2) BO1 Compressor #2 ON/OFF ON X X X X XBO2 Compressor #4 ON/OFF ON c c X c XBO3 Not used —BO4 Circuit #1 liquid line solenoid
valve open/closeOpen X X X X X
BO5 Condenser fan #21 ON/OFFf ON d d d d dBO6 Condenser fan #22 ON/OFF ON d d d d dBO7 Condenser fan #23 ON/OFFe ON d d d d dBO8g Not used —BO9 Not used —
Table 16: Binary outputs for cooling control boards (CCB1 and CCB2): 6-compressors/6-stage (circuit #1 lead)a
Cooling circuit # Output # Description
Action with
output ON
Cooling capacity (%)Cross circuit loading Lead circuit loading
0 16 33 50 66 83 100 0 16 33 50 66 83 100
1 (CCB1)
BO1 Compressor #1 ON/OFF ON X X X X X X X X X X X XBO2 Compressor #3 ON/OFF ON b b X X X X b X X X X XBO3 Not used —BO4 Circuit #1 liquid line solenoid valve open/close Open X X X X X X X X X X X XBO5 Condenser fan #11 ON/OFFf ON d d d d d d d d d d d dBO6 Condenser fan #12 ON/OFF ON d d d d d d d d d d d dBO7 Condenser fan #13 ON/OFF ON d d d d d d d d d d d dBO8 Condenser fan # 14 ON/OFFe ON d d d d d d d d d d d dBO9 Compressor #5 ON/OFF ON b b b b X X b b X X X X
2 (CCB2)
BO1 Compressor #2 ON/OFF ON X X X X X X X XBO2 Compressor #4 ON/OFF ON c c X X X c X XBO3 Not used —BO4 Circuit #2 liquid line solenoid valve open/close Open X X X X X X X XBO5 Condenser fan #21 ON/OFFf ON d d d d d d d dBO6 Condenser fan #22 ON/OFFf ON d d d d d d d dBO7 Condenser fan #23 ON/OFF ON d d d d d d d dBO8 Condenser fan #24 ON/OFFe ON d d d d d d d dBO9 Compressor #6 ON/OFF ON c c c c X c c X
28 Daikin IM 696-4
Service Information
4-Compressors/8-Stage. In this configuration there are fourequally sized compressors and two cooling circuits.Compressor #1 and Compressor #3 are in Cooling Circuit #1and Compressor #2 and Compressor #4 are in Cooling Circuit#2. Compressor #1 and Compressor #2 each have oneunloader. Compressor #3 and Compressor #4 have nounloading. Each cooling circuit is controlled in the same way.One circuit is designated the “Lead” and the other the “Lag”circuit. For detailed information regarding circuit lead/lagoperation, refer to the applicable operation manual (refer toTable 1 on page 1).
There are two methods for controlling the two circuits when both are enabled: Cross Circuit Loading and Lead Circuit Loading. For details regarding selecting Cross Circuit Loading versus Lead Circuit Loading, refer to the “Compressor Staging” section of the applicable operation manual (refer to Table 1 on page 1).
Cross Circuit Loading. With this method, the two circuits are alternately loaded and unloaded as evenly as possible.
The normal staging sequence is as follows:
When a capacity increase is required and both circuits are operating at the same capacity, the “Lead” circuit is staged up if not already at its maximum. When a capacity increase is required and both circuits are not operating at the same capacity, the “Lag” circuit is staged up if not already at its maximum capacity. When a capacity decrease is required and both circuits are operating at the same capacity, the “Lag”
circuit is staged down. When a capacity decrease is required and both circuits are not operating at the same capacity, the “Lead” circuit is staged down.
Lead Circuit Loading. With this method, one circuit is loaded completely before the first compressor in the other circuit is turned on, and one circuit is unloaded completely before the other circuit is unloaded.
The normal staging sequence is as follows:
When a capacity increase is required and the “Lead” circuit is not at maximum, the “Lead” circuit is staged up. When a capacity increase is required and the “Lead” circuit is already at its maximum stage, the “Lag” circuit is staged up. When a capacity decrease is required and the “Lag” circuit is not at zero capacity, the “Lag” circuit is staged down. When a capacity decrease is required and the “Lag” circuit is at zero capacity, the “Lead” circuit is staged down.
Table 17 on page 29 summarizes the normal binary output functions and staging sequencing for CCB1 and CCB2 for the 4 Compressors/8 Stage Lead Circuit Loading cooling configuration. The Xs in the table indicate that the output is energized for a particular circuit cooling capacity.
With either the Cross Circuit Loading or Lead Circuit Loading methods, a disabled circuit remains at zero capacity. If the other circuit is enabled, it acts as the “Lead” and the circuit capacity is controlled using the Lead Circuit Loading method as shown in Table 17.
Cooling circuit #
Output # Description
Action with
output ON
Cooling capacity (%)Cross circuit loading Lead circuit loading
0 12 25 37 50 62 75 87 100 0 12 25 37 50 62 75 87 100
a. If Circuit #2 is the “lead” circuit, interchange the data in the table between CCB1 and CCB2 for the correct output staging data.b. Condenser fan outputs turn on and off based on ambient or evaporative condenser sump temperature set points adjustable through the unit keypad.c. This output is not used on unit equipped with an evaporative condenser and a VFD controlling the first condenser fan on each circuit (Condenser Fan # 11 and
# 21).The VFD controlling these fans is started and stopped and modulated via RS-485 communications with the main control board.
Table 17: Binary outputs for cooling control boards (CCB1 and CCB2): 4-compressors/8-stage
1 (CCB1) BO1 Compressor #1 ON/OFF ON X X X X X X X X X X X X X X X XBO2 Compressor # 3 ON/OFF ON X X X X X X X X X XBO3 Unloader #1, Compressor #1 Unloaded X X X X X X XBO4 Circuit # 1 liquid line solenoid
valve open/closeOpen X X X X X X X X X X X X X X X X
BO5 Condenser fan #11 ON/OFFc ON b b b b b b b b b b b b b b b bBO6 Condenser fan #12 ON/OFF ON b b b b b b b b b b b b b b b bBO7 Condenser fan #13 ON/OFF ON b b b b b b b b b b b b b b b bBO8 Condenser fan #14 ON/OFF ON b b b b b b b b b b b b b b b bBO9 Not used —
2 (CCB2) BO1 Compressor #2 ON/OFF ON X X X X X X X X X X XBO2 Compressor #4ON/OFF ON X X X X XBO3 Unloader #1, compressor #2 Unloaded X X X X X XBO4 Circuit # 1 liquid line solenoid
valve open/closeOpen X X X X X X X X X X X
BO5 Condenser fan #21 ON/OFFc ON b b b b b b b b b b bBO6 Condenser fan #22 ON/OFF ON b b b b b b b b b b bBO7 Condenser fan #23 ON/OFF ON b b b b b b b b b b bBO8 Condenser fan #24 ON/OFF ON b b b b b b b b b b bBO9 Not used —
Daikin IM 696-4 29
Service Information
3-Compressors/4-Stage. In this configuration there aretwo equally sized small compressors in Cooling Circuit #1 andone large compressor in Cooling Circuit #2. The coolingoutputs are always controlled in the same way. There is nocircuit lead/lag operation with this configuration.
Starting with 0% cooling capacity, when a capacity increase is required, the small compressor on circuit #1 with the fewest run hours is turned on (25%). When a further capacity increase is required, the remaining compressor on circuit #1 is turned on (50%). When a further capacity increase is required, the large compressor on circuit #2 is turned on and the small compressor on circuit #1 with the most run hours is turned off (75%). When a further capacity increase is required, the small compressor on circuit #1 that is not operating is turned on (100%).
Starting with 100% capacity, when a capacity decrease is required, the small compressor on circuit #1 with the most run hours is turned off (75%). When a further capacity decrease is required, the large compressor on circuit #2 is turned off and
the small compressor on circuit #1 that is not operating is turned on (50%). When a further capacity decrease is required, the small compressor on circuit #1 with the most run hours is turned off (25%). When a further capacity decrease is required, the operating small compressor on circuit #1 is turned off (0%)
Note – If one of the small compressors on circuit #1 is disabled, the unit stages between 25% (using the enabled small compressor on circuit #1) and 75% (small compressor on circuit #1 and large compressor on circuit #2) skipping the 50% capacity step. If both of the small compressors on circuit #1 are disabled, the large compressor on circuit #2 (50% capacity) cycles on and off to maintain the load. If the large compressor on circuit #2 is disabled, the two small compressors on circuit #1 cycles on and off (based on run hours) to maintain the load.
Table 20 on page 31 summarizes the normal binary output functions and staging sequencing for CCB1 and CCB2 for the 3 Compressors/4 Stage cooling configuration. The Xs in the table indicate that the output is energized for a particular cooling capacity.
Cooling circuit #output Description Action with output ON
Cooling capacity (%)0 25 50 75 100
1 (CCB1)
BO1 Compressor # 1 ON/OFF (small compressor) On X X X XBO2 Compressor # 3 ON/OFF (small compressor) On b X b XBO3 Not used —BO4 Circuit # 1 liquid line solenoid valve open/close Open X X X XBO5 Condenser fan # 11 ON/OFFd On c c c cBO6 Condenser fan # 12 ON/OFF On c c c cBO7 Condenser fan # 13 ON/OFF On c c c cBO8 Not usede —BO9 Not used —
2 (CCB2)
BO1 Compressor # 2 ON/OFF On X XBO2 Not used OnBO3 Not used —BO4 Circuit # 2 liquid line solenoid valve open/close Open X XBO5 Condenser fan # 21 ON/OFFd On c cBO6 Condenser fan # 22 ON/OFF On c cBO7 Condenser fan # 23 ON/OFF On c cBO8 Not usede —BO9 Not used —
a. Circuit Lead/Lag does not apply to this staging configuration.b. If Compressor #3 has fewer run hours it operates instead of Compressor #1 at this cooling capacity.c. Condenser fan outputs turn on and off based on ambient or evaporative condenser sump temperature set points adjustable through the unit keypad.d. This output is not used on unit equipped with an evaporative condenser and a VFD controlling the first condenser fan on each circuit (Condenser Fan # 11 and
# 21).The VFD controlling these fans is started and stopped and modulated via RS-485 communications with the main control board.
e. This output is used to open a sump dump valve on units equipped with an evaporative condenser. Output is energized to open valve.
Table 18: Binary outputs for cooling control boards (CCB1 & CCB2): 3-compressors/4-stage (circuit #1 lead)a
30 Daikin IM 696-4
Service Information
GCB1 (RDS & RAH)
For RDS and RAH model air handling units interfaced with generic condensing units, the cooling stages are controlled by an auxiliary control board loaded with special generic condensing unit control software. This board is designated GCB1. There are nine binary output relays on the GCB1. These relays are energized based on commands received from the MCB to provide the appropriate switching action in the condensing unit control circuitry. The condensing unit control circuit terminals are wired to these output relays through the binary output terminals on the left side of the board.
These cooling outputs are energized and de-energized sequentially to maintain the cooling load. The outputs are sequentially turned on whenever the cooling capacity is increased. The outputs are sequentially turned off whenever the cooling capacity is decreased.
This sequence of one output per stage is shown in Table 19 on page 31. With this arrangement, protection of the compressors and control of condenser fans are not provided by the
MicroTech II controller but rather by the condensing unit control system.
EHB1
When a unit is equipped with a multiple stage electric heater the heat is controlled by an auxiliary electric heat control board. The board is designated EHB1. There are nine binary output relays on the EHB1 board. These relays are energized based on commands from the MCB to provide the appropriate switching action in the electric heat control circuitry. The electric heat control terminals are wired to these output relays through the binary output terminals on the left side of the board.
These heating outputs are energized and de-energized sequentially to maintain the heating load. These outputs are sequentially turned on whenever the heating capacity is increased. These outputs are sequentially turned off whenever the heating capacity is decreased. The sequence of one output per stage is shown in Table 20.
Output # Output description Action with output ON
Cooling stage
0 1 2 3 4 5 6 7 8
GCB1-BO1 Cooling stage #1 ON/OFF On X X X X X X X XGCB1-BO2 Cooling stage #2 ON/OFF On X X X X X X XGCB1-BO3 Cooling stage #3 ON/OFF On X X X X X XGCB1-BO4 Cooling stage #4 ON/OFF On X X X X XGCB1-BO5 Cooling stage #5 ON/OFF On X X X XGCB1-BO6 Cooling stage #6 ON/OFF On X X XGCB1-BO7 Cooling stage #7 ON/OFF On X XGCB1-BO8 Cooling stage #8 ON/OFF On XGCB1-BO9 Not used —
Output # Output description Action with output on
Heating stage
0 1 2 3 4 5 6 7 8
EHB1-BO1 Heating stage #1 ON/OFF ON X X X X X X X XEHB1-BO2 Heating stage #2 ON/OFF ON X X X X X X XEHB1-BO3 Heating stage #3 ON/OFF ON X X X X X XEHB1-BO4 Heating stage #4 ON/OFF ON X X X X XEHB1-BO5 Heating stage #5 ON/OFF ON X X X XEHB1-BO6 Heating stage #6 ON/OFF ON X X XEHB1-BO7 Heating stage #7 ON/OFF ON X XEHB1-BO8 Heating stage #8 ON/OFF ON XEHB1-BO9 Not used —
Table 19: Binary outputs for cooling control board (CCB21): RDS or RAH with up to 8 DX cooling stages
Table 20: Binary outputs for electric heat control board (EHB1): up to 8 heat stages
Daikin IM 696-4 31
Service Information
EERB1
When a unit is equipped with an optional energy recovery wheel, the system is controlled by an auxiliary energy recovery control board. The board is designated ERB1. There are nine binary output relays on the ERB1. These relays are energized based on commands from the MCB to provide the appropriate switching action in the energy recovery wheel control circuitry. The energy recovery wheel control terminals are wired to these output relays through the binary output terminals on the left side of the board. Table 21 summarizes the binary output connections for the ERB1 board.
Binary output Output description Action with
output ON
ERB1-BO1 Enthalpy wheel ON/OFF OnERB1-BO2 Not used —ERB1-BO3 Not used —ERB1-BO4 Close enthalpy wheel bypass dampers ClosingERB1-BO5 Open enthalpy wheel bypass dampers OpeningERB1-BO6 Not used —ERB1-BO7 Decrease enthalpy wheel speed DecreasingERB1-BO8 Increase enthalpy wheel speed IncreasingERB1-BO9 Not used —
Software Identification and ConfigurationThe MicroTech II control system code is made up of up to four different software components. All unit applications include a main control board application code component that resides in the main control board (MCB). Then, depending on the unit configuration, there may be one or two cooling auxiliary control boards, an electric heat auxiliary control board, or an energy recovery auxiliary control board each loaded with an application code component.
The application code in the main control board and any auxiliary control boards are each assigned a ten-digit software identification number. This includes a seven-digit base number followed by a three-digit version number.
The software identification numbers the unit was loaded with at the factory appears on the software identification label located near the keypad/display. Figure 16 shows a typical label. The box labeled “UNIT SOFTWARE NUMBER” contains the software identification number for the code in the main controller (MCB). The box labeled “COMPRESSOR SOFTWARE” contains the software identification number for the code in the auxiliary cooling control board(s) (CCB1, CCB2 and GCB1) when applicable. The box labeled “STAGE ELEC HEAT SOFTWARE” contains the software identification number for the code in the auxiliary electric heat control board (EHB1), when applicable. The box labeled “ENERGY RECOVERY SOFTWARE” contains the software identification number for the code in the auxiliary energy recovery control board (ERB1), when applicable.
Note – The “UNIT SOFTWARE NUMBER” loaded into the main controller (MCB) also appears in the AHUID= parameter in the Unit Configuration menu on the unit keypad/display.
Figure 15.
UNIT SOFTWARE NUMBER
SOFTWARE CONFIGURTION CODE
COMPRESSOR SOFTWARE
STAGE ELEC HEAT SOFTWARE
ENERGY RECOVERY SOFTWARE
UNIT G.O.-SEQ NUMBER
2506010146
11780830411002210100211YYY
2506011310
2506012210
2506013210
728121-050
Software identification label
Main Control Board (MCB) ConfigurationAfter the main control board software component is loaded into the MCB, it must be “configured” for the specific control application. This consists of setting the value of 20 configuration variables within the MCB. These variables define things such as the type of cooling, number of compressors and cooling stages and the type of heat. If all of these items are not set appropriately for the specific unit, the unit will not function properly. The correct settings for these parameters are defined for a given unit by the unit Software Configuration Code. The Software Configuration Code consists of a 26-character string of numbers and letters. The code id located on the unit Software Identification Label on the back of the door where the unit keypad is mounted. See also Figure 22 on page 33.
Only the first 22 characters of this code are used for software configuration purposes. The first 22 characters of the Software Configuration Code currently loaded into a unit controller can be determined via the unit keypad/display by viewing the six menu items under the Configuration Code menu. The six menu items are Pos #1–4=, Pos #5–8=, Pos #9–12=, Pos #13–16=, Pos #17–20= and Pos #21–22=. The Software Configuration Code in the unit is determined by combining the values of these six parameters.
For example, if the six parameters read as Pos #1–4=1.178, Pos #5–8=0.830, Pos #9 12=4.104, Pos #13–16=0.221, Pos #17–20=0.100 and Pos #21–22=2.0, then the Software Configuration Code in the unit is 1178083041040221010020. Note that the decimal points in the values are ignored when constructing the code. Table 22 on page 33 lists the configuration code variables including the position within the code, a description of the parameter, the variable object and
Table 21: Binary outputs for energy recovery wheel control board (ERB1)
32 Daikin IM 696-4
Service Information
attribute name and the applicable settings for each. The factory default values are shown in bold font.
Configuration string position Description Values (default in bold)
Main Control Board (MCB) Data ArchivingAll MCB control parameters and the real time clock settings are backed up by the MCB battery when power is removed from the MCB. In the event of a battery failure, the MCB includes a data archiving function. Once a day, just after midnight, all the MCB control parameter settings are archived to a file stored in the MCB FLASH memory. If the MCB is powered up with a low or defective battery (or with the battery removed), the most recently archived data is restored to the controller.
Note – When this archived data restoration process occurs, it increases the controller start up and initialization time period by approximately 75 seconds.
Table 22: Software configuration string
1 Unit Type0 RA zone control1 RA DAT control2 100 OA zone control3 100 OA DAT control
2 Cooling Type0 None1 Compressorized clg2 Chilled water (2-wire FB)A Chilled water (3-wire FB)
3Compressoriz
ed cooling configuration
0 2 comp/2 stage1 2 comp/3 stage2 2 comp/4 stage3 2 comp/6 stage4 3 comp/4 stage5 4 comp/4 stage6 6 comp/6 stage7 4 comp/8 stage8 Generic condenser
4Generic
condenser stages
1 – 8 Stages (Default = 8)
5 Low ambient 0 No1 Yes
6* Condenser fan type
0 No evap cond control1 2 cond fans/cir– ABB VFD2 2 cond fans/cir– Graham VFD 3 2 cond fans/cir– Reliance VFD4 2 cond fans/cir– no VFD5 3 cond fans/cir– ABB VFD6 3 cond fans/cir– Graham VFD7 3 cond fans/cir– Reliance VFD8 3 cond fans/cir– no VFD
7 Damper type
0 None1 Single position 30% (2-wire FB)2 Single position 100% (2-wire FB)3 Economizer (2-wire FB)A Single position 30% (3-wire FB)B Single position 100% (3-wire FB)C Economizer (3-wire FB)
8 DesignFlo
0 No DesignFlo1 018–030 (800) (non-precision PS)2 036–040 (802) (non-precision PS)3 045–075 (047) (non-precision PS)4 080–135 (077) (non-precision PS)A 018–030 (800) (precision PS)B 036–040 (802) (precision PS)C 045–075 (047) (precision PS)D 080–135 (077) (precision PS)
9 Heating type 0None1F BP ctrl2Multi staged3Modulated gas, 3–1 (2-wire FB)4Modulated gas, 20–1 (2-wire FB)5Steam or hot water (2-wire FB)6Single stage gas7Single stage electricAModulated gas, 3–1 (3-wire FB)BModulated gas, 20–1 (3-wire FB)CSteam or hot water (3-wire FB)
10 Max heating stages
1 – 8 stages (default = 1)
11,12, and 13 Max heat rise Three digits (default = 100)
14 Discharge fan type
0 Constant volume1 Variable inlet vanes2 Variable freq drive
15 Return fan type
0 Constant volume1 Variable inlet vanes2 Variable freq drive3 No Return fan4 Propeller exhaust
16
Return/exhaust fan
capacity control method
0 None1 Tracking2 Bldg press3 Position
17Second pressure
sensor type
0 None1 Duct2 Bldg
18 Entering fan temp sensor
0 No1 Yes
19 Energy recovery
0 None1 Constant speed wheel2 Variable speed wheel
20 Final filter0 No1 Yes
21 Heating configuration
0 Draw through preheat1 Draw through reheat2 Blow through
22 Cooling configuration
0 Draw through1 Blow through
Table 22: Software configuration string (continued)Configuration string position Description Values (default in bold)
Daikin IM 696-4 33
Typical Wiring Diagrams
Typical Wiring Diagrams
The applied rooftop unit wiring diagrams on the following pages are typical. They are included to show common factory and field wiring schemes. For exact wiring information pertaining to a particular unit, refer to the wiring diagrams supplied with the unit.
Note – Some of the component designations depend on unit sizes. The following legend applies to Figure 16 through Figure 25. For complete, exact component designations and locations, refer to the legend supplied with the unit.
Legend
ID Description Standard locationACT3, 4 Actuator motor, economizer Economizer sectionACT5 Actuator motor, discharge
isolation damperDischarge section
ACT6 Actuator motor, return air isolation damper
Return section
ACT7 Actuator motor, heat face/bypass
Coil section, heat
ACT8 Actuator motor, cool face/Bypass
Coil section, cool
ACT10, 11
Actuator motor, exhaust dampers
Return section
ACT12 Actuator motor, enthalpy wheel bypass damper
Energy recovery section
AFD10 Adjustable frequency drive, supply fan
AFD/supply fan section
AFD11 Adjustable frequency drive, evap cond. fans
Main/RCE control box
AFD20 Adjustable frequency drive, return/exhaust fan
AFD/ret. ex. fan section
AFD60 Adjust. freq. drive, energy recovery wheel(s)
Energy recovery section
AS Airflow switch, burner blower Gas heat boxBM Burner blower motor Heat section, gasC1–8 Power factor capacitors,
compressorsCondenser section
C10 Power factor capacitors, supply fan
Supply Fan section
C11 Capacitors, Speedtrol, circuit #1
Condenser bulkhead
C20 Power factor capacitors, return fan
Return section
C21 Capacitors, Speedtrol, circuit #2
Condenser bulkhead
CB10 Circuit breaker, supply fan Main control boxCB11 Circuit breaker, evaporative
condenser fan(s)Main/cond. control box
CB20 Circuit breaker, return/ exhaust fan
Main control box
CB60 Circuit breaker, energy recovery wheel
Main control box
CCB1, 2 Compressor control boards, refrig. circuits
Main control box
CPC Circuit board, main, micro controller
Main control box
CPR Circuit board, expansion, micro controller
Main control box
CS1, 2 Control switches, refrig. circuits Main/cond. control boxDAT Discharge air temperature
sensorDischarge section
DFLH Design flow lefthand sensor Return sectionDFRH Design flow righthand sensor Return sectionDHL Duct hi-limit Main control boxDS1 Disconnect, total unit or cond/
heatMain control box
DS2 Disconnect, SAF/RAF/controls Main control boxDS3 Disconnect, electric heat Electric heat boxDS4 Disconnect, condenser (RCS
Only)RCS control box
EAT Exhaust air temperature sensor
Energy recovery section
EFT Entering fan air temperature sensor
Supply fan section
EHB1 Staged electric heat board Main control boxERB1 Energy recovery board Main control boxERM1 Energy recovery wheel motor
#1Energy recovery section
ERM2 Energy recovery wheel motor #2
Energy recovery section
F1A, B Fuse, control circuit transformer (T1), primary
Main control box
F1C Fuse, control circuit transformer (T1), secondary
Main control box
F2 Fuse, control circuit transformer (T2), primary
Main control box
F3 Fuse, burner blower motor Main control box F4 Fuse, ctrl. circuit transformer
(T4), primaryMain control box
FB11, 12 Fuseblock, Speedtrol Main/cond. control boxFB31–40 Fuseblock, electric heat (top
bank)Electric heat box
FB41–50 Fuseblock, electric heat (bot. bank)
Electric heat box
FB65 Fuseblock, evap. cond. sump heater
Main/cond. control box
FD Flame detector Heat section, gasFLC Fan limit control Heat section, gasFP1, 2 Frost protection, refrig. circuits Coil section, coolFS1, 2 Freezestat control Coil section, heat/coolFSG Flame safeguard Gas heat boxGCB1 Generic condenser board,
refrig. circ.Main control box
GFR1, 2 Ground fault relay Main control boxGFS1, 2 Ground fault sensor Main control boxGFR4 Ground fault relay, condenser Condenser control boxGFS4 Ground fault sensor,
condenserCondenser control box
ID Description Standard location
34 Daikin IM 696-4
Typical Wiring Diagrams
GRD Ground All control boxesGV1 Gas valve, pilot Heat section, gasGV2 Gas valve, main/safety Heat section, gasGV3 Gas valve, redundant/safety Heat section, gasGV4–8 Gas valve, main, hi turn down Heat section, gasHL1–10 Hi-limits, pwr, elec heaters (top
bank)Heat section, electric
HL11–20 Hi-limits, pwr, elec heaters (bot. bank)
Heat section, electric
HL22 Hi-limits, gas heat (pre-filters) Supply fan sectionHL23 Hi-limits, gas heat (final filters) Final filter sectionHL31–40 Hi-limits, ctl. elec heaters (top
bank)Heat section, electric
HL41–50 Hi-limits, ctl. elec heaters (bot. bank)
Heat section, electric
HP1–4 Hi-pressure controls, refrig On compressorsHP5 Hi-pressure controls, gas Heat section, gasHS1 Heat switch, electric heat
shutdownMain control box
HS3 Heat switch, electric heat deadfront interlock
Electric heat box
HTR1–6 Crankcase heaters On compressorsHTR65 Heater, sump Evap. condenser sectionHTR66 Heater, vestibule Evap. condenser vestibuleHUM1 Humidstat sensor Energy recovery sectionIT Ignition transformer Gas heat boxLAT Leaving air temperature sensor Energy recovery sectionLP1, 2 Low-pressure controls,
refrigerationOn compressors
LP5 Low-pressure control, gas Heat section, gasLR10 Line Reactor, supply fan Inverter bypass boxLR20 Line reactor, return/exhaust fan Inv. bypass/main cont. boxLS1, 2 Limit switch, low fire, high fire Gas heat boxLT10–23 Light, cabinet sections Supply fan sectionM1–8 Contactor, compressor Main/cond. control boxM10 Contactor, supply fan Main control boxM11–18 Contactor, condenser fans,
circuit #1Main/cond. control box
M20 Contactor, return fan Main control boxM21–28 Contactor, Condenser fans,
circuit #2Main/cond. control box
M29 Contactor, burner motor Gas heat boxM30 Contactor, reversing, invertor
bypass, supply fanInverter bypass box
M31–39 Contactor, electric heat (top bank)
Electric heat box
M40 Contactor, reversing, Invertor Bypass, Return Fan
Inverter bypass box
M41–50 Contactor, electric heat (bot. bank)
Electric heat box
ID Description Standard locationM60 Contactor, energy recovery
wheelMain control box
M64 Contactor, sump pump Main/cond. control boxM65 Contactor, sump heater Main/cond. control boxMCB Microprocessor circuit board Main control boxMJ Mechanical Jumper All control boxesMMP1–8 Manual motor protector,
compressorsMain/cond. control box
MMP10 Manual motor protector, supply fan
Main control box
MMP11–18
Manual motor protector, cond. fans, ckt#1
Main/cond. control box
MMP20 Manual motor protector, return fan
Main control box
MMP21–28
Manual motor protector, cond. fans, ckt#2
Main/cond. control box
MMP30 Manual motor protector, invrtr. bypass, sup. fan
Inverter bypass box
MMP40 Manual motor protector, invrtr. bypass, ret. fan
Inverter bypass box
MMP51, 52, 53
Manual motor protector, exhaust fan(s)
Prop exhaust box
MMP60 Manual motor protector, energy recovery wheel
Main control box
MMP64 Manual motor protector, sump pump
Main/RCE control box
MP1–6 Motor protector, compr.#1-6 On compressorsOAE Outside air enthalpy sensor Economizer sectionOAT Outside air temperature sensor Economizer sectionOP1–4 Oil pressure controls,
compr.#1-4Condenser section
PB1, 2 Power block, power distribution Main control boxPB3 Power block, power
distribution, electric heatElectric heat box
PB4 Power block, power distribution, condenser
Condenser control box
PB9, 10 Power block, supply fan Junction box, split unitPB11, 12 Power block, power distribution Main control boxPB19, 20 Power block, return/exhaust
fanJunction box, split unit
PC5 Pressure control, clogged filter Pre filter sectionPC6 Pressure control, clogged final
filterFinal filter section
PC7 Pressure control, proof airflow Supply fan sectionPC8 Pressure control, minimum
airflowCoil section, cool
PC12, 22 Pressure control, Fantrol Condenser sectionPM1 Phone modem Main control boxPS1, 2 Pumpdown switches, refrig
circuitsMain/cond. control box
PS3 Pumpdown switch, RFS only Main control boxPVM1, 2 Phase voltage monitor Main control box
ID Description Standard location
Daikin IM 696-4 35
Typical Wiring Diagrams
PVM4 Phase voltage monitor, condenser
Condenser control box
R1, 2 Relay, hi pressure reset Main/cond. control boxR3, 4 Relay, hi pressure delay Main/cond. control boxR5–8 Relay, safety, cool fail Main/cond. control boxR9, 10 Relay, compressor lockout Main/cond. control boxR11, 12 Relay, Speedtrol fan cycling Main/cond. control boxR20 Relay, Heat, gas/ steam/ hot
water Gas heat/main cont. box
R21, 22 Relay, heat, gas (hi-turn down) Gas heat boxR23 Relay, heat, gas & electric Gas/electric heat boxR24 Relay, heat alarm, gas Main control boxR25 Relay, heat, gas, start supply
fan inverterMain control box
R26 Relay, isol/exh. dampers, open/close
Main control box
R28 Relay, isolation damper, safety Main control boxR29 Relay, remote fire alarm Main control boxR30 Relay, cool valve with face
bypassMain control box
R45 Relay, UV lights Main control boxR46, 47 Relay, supply fan inverter, incr/
decrMain control box
R48, 49 Relay, return fan inverter, incr/decr
Main control box
R56 Relay, heater, water pipe Main/RCE control boxR58,59 Relay, heat wheel inverter, incr/
decrMain control box
R60 Relay, energy recovery wheel, enable
Main control box
R61 Relay, smoke detector, discharge air
Main control box
R62, 63, 65
Relay, use on specials Main control box
R64 Relay, sump pump Main/RCE control boxR66 Relay, smoke detector, return
airMain control box
R67 Relay, supply fan, enable Main control boxR68 Relay, return fan, enable Main control boxR69 Relay, Inv. bypass VAV box
interlockMain control box
R70–79 Relay, use on specials Main control boxRAE Return air enthalpy sensor Return sectionRAT Return air temperature sensor Return sectionREC1 Receptacle, main box Main control boxREC2 Receptacle, condenser box Condenser control boxREC3 Receptacle, field power, 115V Discharge bulkheadREC10–23
Receptacle, cabinet sections Cabinet sections
ID Description Standard locationS1 Switch, system on/off Main control boxS2 Switch, system on/off,
condenser unitCondenser control box
S3 Switch, furnace on/off Gas heat boxS4 Switch, inverter bypass, on/ off Main control boxS7 Switch, local on/auto/off to
controllerMain control box
S10–23 Switches, cabinet section lights Cabinet sectionsS40–45 Switches, door interlock, UV
lightsCabinet sections
SC11 Speed control, circuit #1 Condenser bulkheadSC21 Speed control, circuit #2 Condenser bulkheadSD1 Smoke detector, supply Discharge sectionSD2 Smoke detector, return Return sectionSPS1, 2 Static pressure sensors, duct/
buildingMain control box
SR1-3 Sequencing relays, electric heat
Electric heat box
SV1, 2 Solenoid valves, liquid Condenser sectionSV5, 6 Solenoid valves, hot gas Condenser sectionSV61, 62 Solenoid valves, sump, fill Main/RCE control boxSV63 Solenoid valves, sump, drain Main/RCE control boxSWT Sump water temperature
sensorEvap. condenser section
T1 Transformer, main control (line/115VAC)
Main control box
T2 Transformer, control input (115/24VAC)
Main control box
T3 Transformer, control output (115/24VAC)
Main control box
T4 Transformer, exh. damper actuator (115/12VDC)
Main control box
T5 Transformer, electric heat Electric heat boxT6 Transformer, dew point
controller (115/24VAC)Main control box
T9 Transformer, refrig. circuit 24V Main control boxT11 Transformer, speedtrol (line/
240VAC)Condenser section
TB1 Terminal block, internal Main control boxTB2 Terminal block, field Main control boxTB3 Terminal blocks, factory Main control boxTB4 Terminal block, RFS, field Main control boxTB5 Terminal block, RCS, field Condenser control boxTB6 Terminal block, RCS, factory Condenser control boxTB7 Terminal block, 115V
convenience outlet, fieldMain control box
TB8 Terminal block, 115V conv. outlet, RCS, field
Condenser control box
TB11 Terminal block, heat Heat control box
ID Description Standard location
36 Daikin IM 696-4
Typical Wiring Diagrams
200/ H200
1. Field wiring
3. Shielded wire/cable
4. Main control box terminals
5. Auxilliary box terminals
6. Field terminals
7. Plug connector
8. Wire/harness number
General Notes
2. Factory wiring
9. Wire nut/IDWN7
TB23 Terminal block, oil pressure box, RPE/RCE only
Evap. condenser vestibule
TB25, 26, 27, 28
Terminal block, split unit junction box
Junction box, split unit
TC12, 13, 14
Temperature controls, Fantrol Condenser section
TC56 Temperature control, water pipe heater
Evap. condenser vestibule
TC66 Temperature control, vestibule exhaust fan
Evap. condenser vestibule
TD1, 2 Time delay, compressor lockout
Main/cond. control box
TD3, 4 Time delay, hi-pressure Main/cond. control boxTD5–8 Time delay, part winding,
compr #1 - 4Main control box
TD10 Time delay, hi turn down burner Gas heat boxTD11, 12 Time delay, low ambient Main/cond. control boxTR1, 2 Transducer, pressure Main control boxU1, 2 Unloaders, compressors On compressorsUV Ultra-violet light(s) Coil/discharge sectionVM1 Valve motor #1, heating Gas heat box/ heat sectionVM5 Valve motor #5, cooling Coil section, coolVV1 Vent valve, gas heat Heat Section, GasWL63 Water level, sump, fill Evap. condenser sectionWL64 Water level, sump, low water Evap. condenser sectionZNT1 Zone temp. sensor, setback Field installed
ID Description Standard location
Daikin IM 696-4 37
Typical Wiring Diagrams
Figure 16: VAV control inputs (DAC)/1
.68
/1.6
8
H22
8-1
H22
9-2
DRN
-4
CO
NTA
CT
MU
ST B
E O
PEN
DU
RIN
G N
ORM
AL
OPE
RATI
ON
TO C
CB
1
H23
1-1
H23
2-2
DRN
-4
H23
0-3
H22
3-1
H22
4-2
DRN
-4
BU
ILD
ING
BA
CK
NET
MST
P
H22
1-2
H22
7-2
DRN
-4
H22
6-1
H22
0-1
DRN
-4
NO
TES
TO F
IELD
:
1.RE
FER
TO I.
M. F
OR
MIC
ROTE
CH
II A
LARM
CO
NFI
GU
RATI
ON
.
2.TO
EN
AB
LE S
OFT
WA
REIN
TERN
AL
TIM
E C
LOC
K,
TERM
INA
LS 1
01 &
102
MU
ST N
OT
BE
JUM
PERE
D
THE
FIEL
D T
O R
EMO
VE
JUM
PERS
WH
ENIN
STA
LLIN
G C
OO
L/H
EAT
ENA
BLE
SW
ITC
HES
3.
SHO
WN
IN N
IGH
TO
R U
NO
CC
UPI
EDM
OD
E
DIS
CH
ARG
E A
IRTE
MPE
RATU
REEX
TERN
AL
RESE
T
H22
8-4
H22
8-1
H23
1-1
H23
1-3
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
156
203
200
610
115V
24V
CLA
SS 2
RS23
2 PO
RT
AI7
AI6
AI5
BI7
BI6
BI5
AI4
AI3
AI2AI1
BI4
BI3
BI2BI1
MIC
ROPR
OC
ESSO
R C
ON
TRO
L B
OA
RD AN
ALO
GIN
PUT
BIN
ARY
INPU
T
SW1
#6(E
NTE
RIN
G F
AN
TEM
PERA
TURE
)
GA
S H
EAT
ALA
RM
SW1
#7
(DRI
VE
SID
E)
5VD
CPW
R SU
P
DIS
PLA
Y
IS L
OC
ATE
D O
N D
EAD
FRO
NT
A (D
B9-
MA
LE) C
ON
NEC
TIO
N
CO
NN
.
SW1
#4(R
ETU
RN A
IRSE
NSO
R)
OFF
ON A
UTO
SW1
#2
SW1
#5
SW1
#3
SW1
#1
(DIS
CH
ARG
E A
IRSE
NSO
R)
(OU
TDO
OR
AIR
SEN
SOR)
CO
OL_
ENA
BLE
HEA
T_EN
AB
LE
MA
NU
AL_
ENA
BLE
OV
ERRI
DE
REQ'
D FO
R NI
GHT S
ETBA
CK O
R SP
ACE R
ESET
ZO
NE
OR
SPA
CE
SEN
SOR
AIR
FLO
W
54
32
41
76R54R32R1
7C
7
6C
6
5C
5
4C
4
3C
3
2C
2
1C
1
P1
REF
N2-
N2+
J1
CO
M
24V
AC
14 15 GRD
1610 11 12 13
21
21
43
23 24
1 2
4
WH
T
BLK
DRN
35
111
WH
T
BLK
DRN
123
3 4
1 2
G
5V+
H 5V-
RED
WH
T
BLK
DRN
RS-2
32
1 2
4
WH
T
BLK
DRN
REF
N2-
N2+
128
129
WH
T
BLK
DRN
GRD
3
2
1
104
102
105
106
101
101
1 2
4
AC
1 2
4
AC
WH
T
BLK
DRN
WH
T
BLK
DRN
WH
T
BLK
DRN
WH
T
BLK
DRN
4
3
132
133
120
121
GRD
GRD
108
41
12
112
3/Y
1/R
101
PVM
1
T2
MC
B
TB1B
T1_1
15V
AC
T1_N
TB1B
F3
S1/6
.00
115T
1/1.
68
S1S1
TB1D
PL5
+PP
EFT
+N
B
R24
TB2
N2+
/8.0
6
N2-
/8.0
6
REF/
8.07
DFR
H_D
S+
NB
PL22
+PP
PWR
KEY
PAD
SERI
AL
PL1
+PP
RAT
+N
B
BC
NT
TB2
S7
TB2
TB2
TB2
TB2
TB2
TB2
PL2
+PP
DA
T+
NB
PL3
+PP
OA
T+
NB
TIM
E_C
LOC
K+
NB
ZN
T1+
NB
TB2
TB2
PL15
+PP
PL15
+PP
PC7
+N
B
TB_1
01
TB2
FS1
+N
BTB
2TB_1
01
3
NJ=
VD
C
tv
3=
NT
C2
=M
A1
=R
TD
21 3
=N
TC
1=
RT
DN
J=V
DC
2=
MA
2
tv
133
NJ=
VD
C
tv
3=
NT
C2
=M
A1
=R
TD
21
COM
M. C
ARD
BACN
ET-M
STP
3=
NT
C
1=
RT
DN
J=V
DC
2=
MA
2
tv
13 3
NJ=
VD
C
tv
3=
NT
C2
=M
A1
=R
TD
21
3
NJ=
VD
C
tv
3=
NT
C2
=M
A1
=R
TD
21
3
NJ=
VD
C
tv
3=
NT
C2
=M
A1
=R
TD
21
203A
168A
168B
204A
168C
204B
201A
200A
230C
229C
228C
225A
210D
210C
209C
214B
233C
232C
231C
214A
208C
225C
224C
223C
211A
210A
209A
227D
227C
226C
221D
221C
220C
219C
218C
217C
217A
215A
215C
228A
231A
220
223
(Sc
he
ma
tic
co
nti
nu
es
on
ne
xt
pa
ge
.)
38 Daikin IM 696-4
Typical Wiring Diagrams
Figure 16: VAV control inputs (DAC), continued
/8.01
/4.00
/3.00
/1.6
8
H25
2-2
H25
O-S
R
H25
0-4
H25
O-+
H25
2-1
H26
2-8
H26
1-10
DRN
-13
H26
4-6
H26
5-8
DRN
-3
OPE
N A
NA
LOG
INPU
T(S
HO
WN
WIT
H F
AN
IN O
FF P
OSI
TIO
N)
H24
3-4
H24
4-2
H24
5-3
DRN
-1
H23
4-2
H23
5-1
DRN
-4
H23
6-3
FILT
ERIN
DIC
ATI
ON
FOR
FIEL
DH
242-
4
H24
3-1
H24
2-3
H23
9-3
H24
0-4
H24
1-5
DRN
-9
OPE
N A
NA
LOG
INPU
T
H23
7JM
P
H23
5-6
H23
5-5
H23
7-4
H23
7-3
H23
7-5
H23
7-3
H26
7-1
H26
7-2
H26
5-1
H26
5-2
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
440
440
313
265
267
445
445
BI8
BI9
BI1
0
AI9
AI1
0
AI8
AI1
1
AI1
2
15V
DC
AI1
3
BI1
5
AI1
5
AI1
4
BI1
6
BI1
2
BI1
4
BI1
3
AI1
6
BI1
1
DU
CT
HI-
LIM
IT
HUM
#15SW
4
#16SW
4
#15SW
4
#16SW
4
500H
OM
500H
OM
SW4
#13
(DU
CT
STA
TIC
PRES
SEN
SOR)
SW4
#14
EXTE
RNA
L EX
HA
UST
SW
ITC
H
SW4
#10
CC
W(C
L)
CW
(OP)
SW1
#8
(OPP
DRI
VE
SID
E)
SW4
#12
PRE
FILT
ER
(0-5
V)
SPA
CE
HU
MID
ITY
SEN
SOR
SW4
#9
CC
W(O
P)
CW
(CL)
SW4
#11
RA S
MO
KE
DET
ECTO
R
SA S
MO
KE
DET
ECTO
R
16R1514R1312R1110R98R
16C1615C1514C
1413C1312C1211C1110C109C
9
8C
8
31
14 2
SR+
TR1
TR
3
1
2
S+
10
8
13
WH
T
BLK
DRN
WH
T
BLK
DRN
6 8 3
8-7+ 8-7+
WH
T
BLK
DRN
-
+S
103
GTY
14 32
RED
WH
T
BLK
DRN
321
4 1
2 3
DRN
RED
WH
T
BLK
4
1
109
32 3
1
131
WH
T
BLK
DRN
PWR
CO
M
OU
T12
6
127
GRD
107
748
9 43 5
DRN
WH
T
RED
BLK
34
17 166
517 16
6
6
35
113
21
115
H
111
5H
2
87
87
T2_1
15V
AC
DH
L
24V
CO
M/2
.47
24V
CO
M/2
.51
PL13
+PP
PL13
+PP
PL13
+PP
OA
E+
NB
RAE
+N
B
PL7
+PP PL
8+
PP
AFD
10+
NB
AFD
20+
NB
SPS1
TB2
EXS
+N
B
VM
1+
NB
PL18
+PP
DFL
H_O
DS
+N
BPL
23+
PP
PL14
+PP
TB2
PL14
+PP
PC5
+N
B
TB2
SHS1
+N
B
TB2
TB2
AC
T3+
NB
PL11
+PP
PL21
+PP
PL20
+PP
SD1
+N
BPL
20+
PP
SD2
+N
B
PL21
+PP
PL20
+PP
PL21
+PP
TB2
PL21
+PP
PL21
+PP
SD2
+N
B
T1_N
PL20
+PP
SD1
+N
BPL
20+
PP
R61
R66
SIG
_SD
/2.3
8
SIG
_SD
/2.4
1
3=
NT
C
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NT
C
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NT
C
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NT
C
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NT
C
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NT
C
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NT
C
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NT
C
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NT
C
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NT
C
1=
RT
DN
J=V
DC
2=
MA
2
tv
13 3
NJ=
VD
C
tv
3=
NT
C2
=M
A1
=R
TD
21
260A
252A
JPR
266C
265C
264C
263C
262C
261C
257C
257A
246C
245C
244C
214B
214B
236C
235C
234C
254C
253C
252C
243A
242A
241C
240C
214B
238C
203B
204B
237A
235A
204B
204B
168C
(Sch
emat
ic c
on
tin
ues
on
pre
vio
us
pag
e.)
Daikin IM 696-4 39
Typical Wiring Diagrams
Figure 17: Constant volume control inputs (SCC)/1
.68
/1.6
8
H22
0-1
H22
1-2
DRN
-4
H22
5-1
H22
6-4
H22
6-2
NO
TES
TO F
IELD
:
1.RE
FER
TO I.
M. F
OR
MIC
ROTE
CH
II A
LARM
CO
NFI
GU
RATI
ON
.
2.TO
EN
AB
LE S
OFT
WA
REIN
TERN
AL
TIM
E C
LOC
K,
TERM
INA
LS 1
01 &
102
MU
ST N
OT
BE
JUM
PERE
D
THE
FIEL
D T
O R
EMO
VE
JUM
PERS
WH
ENIN
STA
LLIN
G C
OO
L/H
EAT
ENA
BLE
SW
ITC
HES
3.
SHO
WN
IN N
IGH
TO
R U
NO
CC
UPI
EDM
OD
E
TO C
CB
1
H23
7JM
P
H23
5-6
H23
5-5
H23
7-4
H23
7-3
H23
7-5
H23
7-3
H23
7JM
P
H23
5-6
H23
5-5
H23
7-4
H23
7-3
H23
7-5
H23
7-3
H23
1-1
H23
1-3
H22
8-4
H22
8-1
H23
1-1
H23
2-2
H23
4-2
H23
5-1
DRN
-4
DRN
-4
H23
6-3
H23
0-3
H22
3-1
H22
4-2
DRN
-4
BU
ILD
ING
BA
CK
NET
MST
P
OPE
N A
NA
LOG
INPU
T
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
265
267
SW1
#2
SW1
#5
SW1
#3
SW1
#1
OFF
ON A
UTO
(DIS
CH
ARG
E A
IRSE
NSO
R)
(OU
TDO
OR
AIR
SEN
SOR)
6
WA
LLST
AT
OV
ERRI
DE
CO
OLI
NG
&
HEA
TIN
G
SETP
OIN
T
ZON
E SE
NSO
R
MA
NU
AL_
ENA
BLE
CO
OL_
ENA
BLE
HEA
T_EN
AB
LE
AIR
FLO
W
SW1
#8
SW1
#7
(DRI
VE
SID
E)
(OPP
DRI
VE
SID
E)
5VD
CPW
R SU
P
SW1
#4(R
ETU
RN A
IRSE
NSO
R)
IS L
OC
ATED
ON
DEA
DFR
ON
T
A (D
B9-
MA
LE) C
ON
NEC
TIO
N
CO
NN
.
DIS
PLAY
SW1
#6
115V
24V
CLA
SS 2
RS23
2 PO
RT
BI8
AI8
AI7
AI6
AI5
BI7
BI6
BI5
AI4
AI3
AI2AI1
BI4
BI3
BI2BI1
MIC
ROPR
OC
ESSO
R C
ON
TRO
L B
OA
RD AN
ALO
GIN
PUT
BIN
ARY
INPU
T
3
2
1
104
102
105
106
101
101
1 2
4
AC
1 2
4
AC
120
121
132
3
4
WH
T
BLK
DRN
WH
T
BLK
DRN
BLK
RED
WH
T
DRN
GRD
WH
T
BLK
DRN
34
17 166
517 16
6
6
35
113
3
113
112
3/Y
1/R
101
108
41
12
123 321
3 4
41 2 1
2 3
G
5V+
H 5V-
RED
WH
T
BLK
DRN
DRN
RED
WH
T
BLK
1 2
4
WH
T
BLK
DRN
RS-2
32
REF
N2-
N2+
128
129
WH
T
BLK
DRN
GRD
54
32
41
8R76R54R32R1
8C
8
7C
7
6C
6
5C
5
4C
4
3C
3
2C
2
1C
1
P1
REF
N2-
N2+
J1
CO
M
24VA
C
14 15 GRD
1610 11 12 13
21
23 24
S7
TB2
TB2
TB2
TB2
TB2
TB2
PL2
+PP
DAT
+N
B
PL3
+PP
OAT
+N
B
TB2
ZN
T1+
NB
TIM
E_C
LOC
K+
NB
N2+
/8.0
6
N2-
/8.0
6
REF/
8.07
PL21
+PP
PL20
+PP
SD1
+N
BPL
20+
PP
SD2
+N
B
PL21
+PP
PL20
+PP
PL21
+PP
TB2
+PP
TB2
TB_1
01
TB2
FS1
+N
BTB
2TB_1
01
TB2
PL15
+PP
PL15
+PP
PC7
+N
B
DFR
H_D
S+
NB
DFL
H_O
DS
+N
B
PL22
+PP
PL23
+PP
PWR
PL1
+PP
RAT
+N
B
SERI
AL
KEY
PAD
BC
NT
TB2
PVM
1
T2
MC
B
TB1B
T1_1
15VA
CT1
_N
TB1B
S1TB
1D
3=
NTC
1=
RT
DN
J=V
DC
2=
MA
2
tv
13 3
NJ=
VD
C
tv
3=
NTC
2=
MA
1=
RT
D
21
3
NJ=
VD
C
tv
3=
NTC
2=
MA
1=
RT
D
21
3
NJ=
VD
C
tv
3=
NTC
2=
MA
1=
RT
D
21 3
=N
TC
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NTC
1=
RT
DN
J=V
DC
2=
MA
2
tv
133
NJ=
VD
C
tv
3=
NTC
2=
MA
1=
RT
D
21
COM
M. C
ARD
BACN
ET-M
STP
3
NJ=
VD
C
tv
3=
NTC
2=
MA
1=
RT
D
21
227D
227C
226C
222C
221C
220C
217C
217A
215A
215C
210D
210C
209C
235A
231A
228A
214B
214B
236C
235C
234C
233C
232C
231C
214A
225C
224C
223C
208C
211C
203A
203B
204A
204B
204A
168A
168C
237A
220
223
(Sch
emat
ic c
on
tin
ues
on
nex
t p
age.
)
40 Daikin IM 696-4
Typical Wiring Diagrams
Figure 17: Constant volume control inputs (SCC), continued
/1.6
8
/8.01
/3.00
OPE
N B
INA
RYIN
PUT
OPE
N B
INA
RYIN
PUT
H24
3-4
H24
4-2
H24
5-3
DRN
-1
H25
2-2
H25
O-S
R
H25
0-4
H25
O-+
H25
2-1
OPE
N A
NA
LOG
INPU
T
H23
9-3
H24
0-4
H24
1-5
DRN
-9
H23
7JM
P
H23
5-6
H23
5-5
H23
7-4
H23
7-3
H23
7-5
H23
7-3
H26
7-1
H26
7-2
H26
5-1
H26
5-2
OPE
N A
NA
LOG
INPU
T
FILT
ERIN
DIC
ATIO
NFO
R FI
ELD
H24
2-4
H24
3-1
H24
2-3
OPE
N A
NA
LOG
INPU
T
OPE
N A
NA
LOG
INPU
T
H23
7JM
P
H23
5-6
H23
5-5
H23
7-4
H23
7-3
H23
7-5
H23
7-3
H26
7-1
H26
7-2
H26
5-1
H26
5-2
FILT
ERIN
DIC
ATIO
NFO
R FI
ELD
H24
2-4
H24
3-1
H24
2-3
H23
1-1
H23
1-3
H23
1-1
H23
2-2
H23
4-2
H23
5-1
DRN
-4
DRN
-4
H23
6-3
H23
0-3
H24
7-1
H24
7-4
H24
8-2
OPE
N A
NA
LOG
INPU
T
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
343
313
265
267
253
253
252
253
253
SW4
#10
CC
W(C
L)
CW
(OP)
HUM
SW4
#11SW
4
#9
CC
W(O
P)
CW
(CL)
RA S
MO
KE
DET
ECTO
R
SA S
MO
KE
DET
ECTO
R
SW4
#14SW
4
#12
(0-5
V)
SPA
CE
HU
MID
ITY
SEN
SOR
SW4
#15 SW
4
#16SW
4
#12
PRE
FILT
ER
(0-5
V)
SPA
CE
HU
MID
ITY
SEN
SOR
SW1
#8
SW1
#7
(DRI
VE
SID
E)
(OPP
DRI
VE
SID
E)
FIN
AL
FILT
ER
BI8
BI9
BI1
0
AI9
AI1
0
AI8
AI7
AI1
1
AI1
2
15V
DC
AI1
3
BI1
5
AI1
5
AI1
4
BI1
6
BI1
2
BI1
4
BI1
3
AI1
6
BI1
1
BI7
SW4
#13
107
847
14 32
DRN
RED
WH
T
BLK
14 2
SR+
TR1
TR
3
1
2
S+
748
9 43 5
DRN
WH
T
RED
BLK
34
17 166
517 16
6
6
35
113
21
115
H
111
5H
2
4
1
109
3
131
WH
T
BLK
DRN
PWR
CO
M
OU
T12
6
127
GRD
3
113
1
109
2 3
1
131
WH
T
BLK
DRN
PWR
CO
M
OU
T12
6
127
GRD
112
3/Y
1/R
101
123 321
3 4
41 2 1
2 3
RED
WH
T
BLK
DRN
DRN
RED
WH
T
BLK
12 3
1
4 2
16R1514R1312R1110R98R7
16C1615C1514C
1413C1312C1211C1110C109C
9
8C
8
7C
7
TB2
VM
1+
NB
PL18
+PP
24V
CO
M/2
.47
24V
CO
M/2
.51
PL13
+PP
PL13
+PP
PL13
+PP
OA
E+
NB
RA
E+
NB
AC
T3+
NB
PL11
+PP
PL21
+PP
PL20
+PP
SD1
+N
BPL
20+
PP
SD2
+N
B
PL21
+PP
PL20
+PP
PL21
+PP
TB2
PL21
+PP
PL21
+PP
SD2
+N
B
T1_N
PL20
+PP
SD1
+N
BPL
20+
PP
PL14
+PP
TB2
PL14
+PP
TB2
SHS1
+N
B
TB2
+PP
TB2
TB2
PC5
+N
B
TB2
SHS1
+N
B
TB2
TB2
FS1
+N
BTB
2TB_1
01D
FRH
_DS
+N
B
DFL
H_O
DS
+N
B
PL22
+PP
PL23
+PP
PL6
+PP
PC6
+N
BPL
6+
PP
T2_1
15VA
C
3=
NTC
1=
RT
DN
J=V
DC
2=
MA
2
tv
13 3
NJ=
VD
C
tv
3=
NTC
2=
MA
1=
RT
D
213
=N
TC
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NTC
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NTC
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NTC
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NTC
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NTC
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NTC
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NTC
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
3=
NTC
1=
RT
DN
J=V
DC
2=
MA
2
tv
13
246C
245C
244C
214B
252A
JPR
241C
240C
214B
238C
235A
254C
253C
252C
243A
231A
214B
236C
235C
234C
233C
232C
231C
248A
203B
204B
168C
204A
237A
242A(S
chem
atic
co
nti
nu
es o
n p
revi
ou
s p
age.
)
Daikin IM 696-4 41
Typical Wiring Diagrams
Figure 18: Control actuator outputs (constant volume RPS with hot water or steam heat with economizer) /1
.68
/2.6
8
/4.00
/4.00
NO
TES
TO F
IELD
:
1.A
LL F
IELD
MO
UN
TED
REL
AYS
MU
ST H
AV
E 24
VAC
CLA
SS2
CO
ILS
THE
TOTA
L VA
OF
THE
FIEL
DM
OU
NTE
D R
ELAY
S C
AN
NO
TEX
CEE
D 1
5 VA
2.
SOU
RCE
1-8
WIR
ED IN
TERN
AL
TO M
OTH
ERB
OA
RD
H31
3-1
H31
3-2
H31
5-6
H31
5-8
H31
6-7
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
207
207
207
364
362
207
207
239
SRC
(FA
N_O
PERA
TIO
N)
(EX
T_A
LARM
_SIG
NA
L)B
O4
BO
3
24V
SRC
jprs
24V
SRC
jprs
115V
24V
CLA
SS 2
24V
SRC
jprs
(OPE
N)BO
624
V S
RC
jprs
(EC
ON
/AC
T)
(CLO
SE)BO
5
1-8
102
1819
2021
4NO
4
3NO
3
117
115
116
32
41
86
7
21
6NO
6
3-C
CW
X-C
OM
L2
2-C
W
L1
5NO
5
R26
T1_N
T2_1
15VA
C
TB1C
TB1C
MC
B
MC
B
T3_2
4VT3
_CO
M
TB2
TB2
TB2
T3
PL11
+PP
PL11
+PP
PL11
+PP
PL11
+PP
PL11
+PP
MC
B
AC
T3+
NB
MC
B
307A
305A
303A
303B
318A
315A
315B
168C
203B
(Sch
emat
ic c
on
tin
ues
on
nex
t p
age.
)
42 Daikin IM 696-4
Typical Wiring Diagrams
Figure 18: Control actuator outputs (constant volume RPS with hot water or steam heat with economizer), continued
H3
65
-1
H3
66
-3
H9
69
H9
68
H9
64
H9
65
H3
43
-5H
34
3-6
H3
44
-7
H343-9
H3
44
-8
33
8
33
9
34
0
34
1
34
2
34
3
34
4
34
5
34
6
34
7
34
8
34
9
35
0
35
1
35
2
35
3
35
4
35
5
35
6
35
7
35
8
35
9
36
0
36
1
36
2
36
3
36
4
36
5
36
6
36
7
36
8
36
9
30
6
30
6
20
72
07
24
3
REC
TIFI
ER
DC
12
V
11
5V
REL
IEF
DA
MP
ER(O
PP.
DR
SID
E)
REL
IEF
DA
MP
ER(D
RIV
ESI
DE)
HEA
T
(OP
EN)B1
0
(CLO
SE)B0
9
24
V S
RC
jprs
24
V S
RC
jprs
AC
AC
-+
L1X1
L2X2
1
3B
LK
WH
T
WH
T
BLK
8
9
11
33
36
35
34
5
76
5555555
6666666
5 87
9
6
L2X
-CO
ML1
3-C
CW
2-C
W
10
NO
10
9N
O9
REC
TT4
PL1
7+
PP
AC
T11
+N
B
AC
T10
+N
B
R2
6TB
1F
TB1
F
TB1
F
TB1
F
R2
6
PL1
8+
PP
PL1
8+
PP
PL1
8+
PP
PL18+PP
PL1
8+
PP
VM
1+
NB
MC
BM
CB
36
8A
36
7A
36
3B
36
2A
36
2B
33
9A
33
9C
(Sch
emat
ic c
on
tin
ues
on
pre
vio
us
pag
e.)
Daikin IM 696-4 43
Typical Wiring Diagrams
Figure 19: Condensing section control, RPS 60 (with scroll compressors)/2
.68
/1.6
8/1
.68
H81
4-121.
3K O
HM
, 2W
H81
5-11
(OPE
N O
UTP
UT)
H82
7-10
H82
7-11
H81
7-3
H81
7-4
H81
5-7
MP1
JH
816-
5
MP3
J
H82
2-1
H82
0-3
H82
0-2
H82
1-8
H82
2-12
H81
5-6
J823
A
J823
B
H83
0-4
H83
0-3
H83
1-2
H83
1-4
800
801
802
803
804
805
806
807
808
809
810
811
812
813
814
815
816
817
818
819
820
821
822
823
824
825
826
827
828
829
830
831
832
833
834
835
836
837
817
836
822
207
711
817
727
822
807
705
757
709
711
808
815
727
809
820
115V
24V
CLA
SS 2
BO
4
NO
CO
MB
O5
NO
CO
MB
O6
NO
CO
M
BO
8
NO
CO
M
BO
7
NO
CO
M
BO
9
NO
CO
M
(CO
MPR
#5)
BO
2
NO
CO
M
(CO
MPR
#3) B
O3
NO
CO
M
BO
1
NO
CO
M
(CO
MPR
#1)
DIS
AB
LEEN
AB
LE
DIS
AB
LEEN
AB
LE
B02B01
JUM
PERS
J10
J9
CO
MPR
.C
ON
TRO
LB
OA
RD
INPU
TSB
I=B
INA
RYA
I=A
NA
LOG
(JU
MPE
R LO
CA
TED
JUST
UN
DER
CO
MM
. CA
RD)N2
BU
S
24V
SRC
jprs
BO
7
1413
35
32
41
21
GRD
1815131110
7
20
4
171612981965
213
CO
M2
BI6
BI5
BI4BI3
BI2
CO
M1
BI1
REF
N2-
N2+24
C
BI1
2
BI1
1
BI8
BI1
0
BI9
BI724
V
43
21
1413
111
2
12
8
GRD
30 312928
7NO
7
87A1
A2
A1
A2
A1
A2
1110
21
3A
1A
2
21
2222222
M2
T2
M1
T1
4
76
12(3
2)11
(31)
5
2221
12A
1A
2
21
2222222
1M
2
T2
M1
T1
2
12(3
2)11
(31)
2221
8
3
4 243
12
12
M1
R1
T9
PS1
CC
B1
CS1
N_2
4/8.
38
M3
REF/
2.11
N2+
/2.1
0
N2-
/2.1
0
REF/
8.40
N2+
/8.3
9N2-
/8.3
9
PL25
+PP
LP1
+N
B
PL25
+PP
RESI
STO
R
TB1E
TB1E
TB1E
TB1E
TB1E
MC
B
R1M12
M11
M13
115V
AC
/8.2
0
115V
AC
/8.1
5
PL27
+PP
PL27
+PP
HP3
+N
B
PL25
+PP
M1
HTR
1+
NB
MP1
+N
B
PL25
+PP
PL25
+PP
PL25
+PP
MM
P1
PL25
+PP
115V
AC
/8.1
4
M1
PL27
+PP
M3
HTR
3+
NB
PL27
+PP
MP3
+N
BPL27
+PP
115V
AC
/8.1
9
MM
P3
M3
PL27
+PP
PL27
+PP
PL10
+PP
PL9
+PP
PL9
+PPPL
10+
PPSV
5+
NB
SV1
+N
B
T2_1
15V
AC
T1_1
15V
AC
T1_N
(Sch
emat
ic c
on
tin
ues
on
nex
t p
age.
)
803A
805A
815A81
4A
812A
809A
808A
807A
805B
834A
833A
832A
823A
823B
822A
822B
819A
817A
817B
817C
814B
813A
830A
210D
209C
210C
210D
209C 21
0C
168A
168A
168A
203B
168C
168A
168A
44 Daikin IM 696-4
Typical Wiring Diagrams
Figure 19: Condensing section control, RPS 60 (with scroll compressors), continued
H84
7-3
H84
8-2
(OPE
N O
UTP
UT)
H86
0-10
H86
0-11
H84
8-4
H85
0-7
H85
0-12
MP2
J
H84
8-9
H84
9-8
H85
5-7
H85
3-4
H85
5-6
MP4
J
H85
3-9
H85
4-8
J856
A
J856
B
H86
4-5H
863-
6H
863-
1
H86
4-1
837
838
839
840
841
842
843
844
845
846
847
848
849
850
851
852
853
854
855
856
857
858
859
860
861
862
863
864
865
866
867
868
869
870
855
850
869
719
850
735
855
840
720
762
724
719
841
848
735
842
853
BO
4
NO
CO
MB
O5
NO
CO
MB
O6
NO
CO
M
BO
8
NO
CO
M
BO
7
NO
CO
M
BO
9
NO
CO
M
(CO
MPR
#6)
BO
2
NO
CO
M
(CO
MPR
#4) B
O3
NO
CO
M
BO
1
NO
CO
M
(CO
MPR
#2)
DIS
AB
LEEN
AB
LE
DIS
AB
LEEN
AB
LE
B02B01
JUM
PERS
J10
J9
CO
MPR
.C
ON
TRO
LB
OA
RD
INPU
TSB
I=B
INA
RYA
I=A
NA
LOG
(JU
MPE
R LO
CA
TED
JUST
UN
DER
CO
MM
. CA
RD)N2
BU
S
1413
1413
21
35
43
21
GRD
1815131110
7
20
4
171612981965
213
CO
M2
BI6
BI5
BI4BI3
BI2
CO
M1
BI1
REF
N2-
N2+24
C
BI1
2
BI1
1
BI8
BI1
0
BI9
BI724
V
12
2
3
WH
T
BLK
DRN
87A1
A2
A1
A2
A1
A2
1011
21
A1
A2
7M
2
T2
M1
T1
2222222
12
42
19
8
12(3
2)11
(31)
2221
A1
A2
7M
2
T2
M1
T1
2222222
6
42
19
8
12(3
2)11
(31)
2221
5
1 1
61
2
12
M4
M2
PS2
R2
CS2
CC
B2
N_2
4/8.
06
LP2
+N
BPL
26+
PP
PL26
+PP
N2+
/8.0
9
N2-
/8.0
8
REF/
8.09
115V
AC
/8.5
3
R2
115V
AC
/8.4
8
M22
M21
M23
PL28
+PP
PL28
+PP
HP4
+N
B
M2
PL26
+PP
MP2
+N
B
PL26
+PP
PL26
+PP
HTR
2+
NB
PL26
+PP
PL26
+PP
115V
AC
/8.4
8
MM
P2
M2
M4
PL28
+PP
MP4
+N
B
PL28
+PP
PL28
+PP
HTR
4+
NB
PL28
+PP
PL28
+PP
115V
AC
/8.5
3
MM
P4
M4
PL9
+PP
PL10
+PP
PL9
+PP
PL10
+PP
SV6
+N
B
SV2
+N
B
848A84
7A
845A
842A
841A
840A
838A
867A
866A
865A
856A
856B
855A
855B
852B
850A
850B
850C
847B
864A
805A
209C
210C
210D
168A
168A
168A
168A
(Sch
emat
ic c
on
tin
ues
on
pre
vio
us
pag
e.)
Daikin IM 696-4 45
Typical Wiring Diagrams
Figure 20: Condensing section control, RPS 135 (with reciprocating compressors)/2
.68
/1.6
8/1
.68
H83
0-4
H83
0-3
H83
1-2
H83
1-4
H82
7-10
H82
3-10
H82
3-2
H82
7-11
H81
7-3
H81
7-4
H81
5-7
MP1
JH
817D
H80
0BH
816-
5
H81
5-6
MP3
J
H82
2-1
H82
2-12
H82
0-3
(TD
3 C
LOSE
S FO
R5
SEC
ON
DS
AFT
ERB
EIN
G E
NER
GIZ
ED)
H82
0-2
H82
1-8
H80
0B
823A
823A
823A
823A
H81
7BH
817C
H82
2AH
822B
H80
5
H80
5H
822D
H81
4-121.
3K O
HM
, 2W
H81
5-11
800
801
802
803
804
805
806
807
808
809
810
811
812
813
814
815
816
817
818
819
820
821
822
823
824
825
826
827
828
829
830
831
832
833
834
835
836
837
835
819
816
706
817
821
739
822
807
705
757
719
709 83
2
706
808
815
710
817
739
809
820
824
743
822
817
836
822
207
2 M
IN
2 M
IN
115V
24V
CLA
SS 2
BO
4
NO
CO
MB
O5
NO
CO
MB
O6
NO
CO
M
BO
8
NO
CO
M
BO
7
NO
CO
M
BO
9
NO
CO
M
(CO
MPR
#5)
BO
2
NO
CO
M
(CO
MPR
#3) B
O3
NO
CO
M
BO
1
NO
CO
M
(CO
MPR
#1)
DIS
AB
LEEN
AB
LE
DIS
AB
LEEN
AB
LE
B02B01
JUM
PERS
J10
J9
CO
MPR
.C
ON
TRO
LB
OA
RD
INPU
TSB
I=B
INA
RYA
I=A
NA
LOG
(JU
MPE
R LO
CAT
EDJU
ST U
ND
ERC
OM
M. C
ARD
)N2
BU
S
24V
SRC
jprs
BO
7
CO
MPR
#1
4 243
12
12
87A1
A2
A1
A2
A1
A2
A1
A2
87
15
10
35
1110
2
21
21
3A
1A
2
21
2222222
42
31
4
A1
A2
7
3840
120
T2
ML
6
12(3
2)11
(31)
5
2221
21
50
12A
1A
2
21
2222222
142
31
87 A1
A2
3
4547
120
T2
ML
3
12
2
12(3
2)11
(31)
2221
8
21
51
39
46
1413
35
32
41
21
GRD
1815131110
7
20
4
171612981965
213
CO
M2
BI6
BI5
BI4BI3
BI2
CO
M1
BI1
REF
N2-
N2+24
C
BI1
2
BI1
1
BI8
BI1
0
BI9
BI724
V
43
21
1413
111
2
12
8
GRD
30 312928
7NO
7
2222222
21
8
PL10
+PP
PL9
+PP
PL9
+PPPL
10+
PPSV
5+
NB
SV1
+N
B
R1M12
M11
115V
AC
/8.2
0
115V
AC
/8.1
5
M14
M13
R11
R11
PL25
+PP
R3
PL27
+PP
PL27
+PP
PL25
+PP
HP3
+N
B
HP1
+N
B
PL25
+PP
M1
HTR
1+
NB
MP1
+N
B
PL25
+PP
M5
PL25
+PP
TB3
OP1
+N
B
OP1
+N
B
PL25
+PP
MM
P1
PL25
+PP
115V
AC
/8.1
4
M1
TD5
PL27
+PP
M3
HTR
3+
NB
PL27
+PP
MP3
+N
B
R3 M7
PL27
+PP
TB3
OP3
+N
B
OP3
+N
B
TD3
PL27
+PP
115V
AC
/8.1
9
MM
P3
M3
PL27
+PP
TD7
TB3 TB
3O
P3/8
.53
OP1
/8.4
8
M1
R1
T9
PS1
CC
B1
CS1
N_2
4/8.
38
M3
REF/
2.11
N2+
/2.1
0
N2-
/2.1
0
REF/
8.40
N2+
/8.3
9N2-
/8.3
9
PL25
+PP
LP1
+N
B
PL25
+PP
RESI
STO
R
TB1E
TB1E
TB1E
TB1E
TB1E
MC
B
U1_
1+
NB
PL25
+PP
T2_1
15VA
C
T1_1
15VA
CT1
_N
830A
835A
834A
832B
832B
832A
823A
823D
823B
823C
822A
822B
819A
818A
818B
818C
817A
817B
817C
817D
814B
803A
805A
815A81
4A
812A
809A
808A
807A
805B
829A
813A
210D
209C
210C
210D
209C 21
0C
168A
168A
168A
168C
203B
168A
168A
168C
(Sch
emat
ic c
on
tin
ues
on
nex
t p
age.
)
46 Daikin IM 696-4
Typical Wiring Diagrams
Figure 21: Condensing section control, RPS 135 (with reciprocating compressors), continued
(TD
3 C
LOSE
S FO
R5
SEC
ON
DS
AFT
ERB
EIN
G E
NER
GIZ
ED)
MP2
J
MP4
J
H85
0-7
H84
8-4
H85
3-4
H85
5-7
H85
0D
H85
6-10
H86
0-10
H86
0-11
H85
6-11
H85
3-9
H84
8-9
H84
9-8
H85
4-8
JPR
JPR
H85
0-12
H85
5-6
H85
5AH
855B
H85
0BH
850C
856A
856A
H85
5D
H84
7-3
H84
8-2
H86
4-5H
863-
6H
863-
1
H86
4-1
837
838
839
840
841
842
843
844
845
846
847
848
849
850
851
852
853
854
855
856
857
858
859
860
861
862
863
864
865
866
867
868
869
870
852
723
868
850
756
849
854
855
723
841
848
756
842
853
840
729
762
743
73385
7
727
760 86
5
850
855
855
850
869
2 M
IN
2 M
IN
CO
MPR
#2
BO
4
NO
CO
MB
O5
NO
CO
MB
O6
NO
CO
M
BO
8
NO
CO
M
BO
7
NO
CO
M
BO
9
NO
CO
M
(CO
MPR
#6)
BO
2
NO
CO
M
(CO
MPR
#4) B
O3
NO
CO
M
BO
1
NO
CO
M
(CO
MPR
#2)
DIS
AB
LEEN
AB
LE
DIS
AB
LEEN
AB
LE
B02B01
JUM
PERS
J10
J9
CO
MPR
.C
ON
TRO
LB
OA
RD
INPU
TSB
I=B
INA
RYA
I=A
NA
LOG
(JU
MPE
R LO
CAT
EDJU
ST U
ND
ERC
OM
M. C
ARD
)N2
BU
S
12
6
A1
A2
A1
A2 8
7A1
A2
A1
A2
2222222 2222222
7 7
A1
A2
A1
A2
87A1
A2
A1
A2
87
21
21
1011
1011
35
21
21
3
12
42
31
94 12
0T2
120
T2
9
42
8
12(3
2)11
(31)
1522
21
12(3
2)11
(31)
44
21
21
41
ML
ML
48
422
21
8
42
31
43
49
22222222
15
1413
1413
21
35
43
21
GRD
1815131110
7
20
4
171612981965
213
CO
M2
BI6
BI5
BI4BI3
BI2
CO
M1
BI1
REF
N2-
N2+24
C
BI1
2
BI1
1
BI8
BI1
0
BI9
BI724
V
12
2
3
WH
T
BLK
DRN
5
1 1
61
2
12
PL26
+PP
PL28
+PP
M2
M4
R2M22
M21
PL26
+PP
PL28
+PP
M24
M23
R4M6
M8
R12
HTR
2+
NB
HTR
4+
NB
PL26
+PP
PL26
+PP
PL28
+PP
PL28
+PP
R4HP4
+N
B
HP2
+N
B
TD4
MP4
+N
BPL26
+PP
PL26
+PP
OP2
+N
B
OP4
+N
B
PL28
+PP
PL26
+PP
MM
P2
R12
M2
MM
P4
TB3
TD6
TD8
TB3
OP2
+N
B
OP4
+N
B
OP1
/8.1
6
OP3
/8.2
1
PL28
+PP
M4
PL28
+PP
MP2
+N
B
115V
AC
/8.4
7
115V
AC
/8.5
2
115V
AC
/8.4
8
115V
AC
/8.5
2
TB3 TB
3
U1_
2+
NB
PL26
M4
M2
PS2
R2
CS2
CC
B2
N_2
4/8.
06
LP2
+N
BPL
26+
PP
PL26
+PP
N2+
/8.0
9
N2-
/8.0
8
REF/
8.09
PL9
+PP
PL10
+PP
PL9
+PP
PL10
+PP
SV6
+N
B
SV2
+N
B
868A
867A
865B
865A
856A
656D
856B
856C
855A
855B
852A
851A
851B
851C
850A
850B
850C
850D
847B
826A
848A84
7A
845A
842A
841A
840A
838A
864A
805A
209C
210C
210D
168C 168C
168A
168A
168A
168A
(Sch
emat
ic c
on
tin
ues
on
pre
vio
us
pag
e.)
Daikin IM 696-4 47
Typical Wiring Diagrams
Figure 22: Auxiliary VFD control/1
.68
/2.6
8/3
.11
/3.1
1
H42
5-12
H42
6-4
H42
6-6
H42
6-3
H42
9-10
H42
5-2
H42
6-1
H42
7-9
H43
1-7
H42
9-11
INV
ERTE
R
BY
PASS
INV
ERTE
R
BY
PASS
SOU
RCE
9-16
WIR
ED IN
TERN
AL
TO M
OTH
ERB
OA
RD
H41
3-7
H41
3-6
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
133
145
401
404
309
445
137
133
445
149
145
207
207
604
207
207
207
207
207
207
447
447
427
445
432
445
631
603
S4RE
TURN
AIR
SUPP
LYA
IR
I I I I
SRC
SUPP
LY F
AN
BO
1
24V
SRC
jprs
RETU
RN F
AN
BO
2
24V
SRC
jprs
24V
SRC
jprs
24V
SRC
jprs
SAF
INC
R
BO
14
RAF
INC
R
BO
16
HEA
T EN
AB
LE
BO
11
24V
SRC
jprs
24V
SRC
jprs
SAF
DEC
R
BO
13
RAF
DEC
R
BO
15
24V
SRC
jprs
2ND
2NC
1NO
1NC
2C
1C12
(32)
11(3
1)12
(32)
11(3
1)3
12
9
10
7
46
2 11
87
1
13
13
A2
A1
A2
A1
A2
A1
A2
A1
9-16
1NO
1
H1C
H1U
P
H1D
N
H1C
H1U
P
H1D
N
102
102
35
2NO
2
14N
O14
16N
O16
11N
O11
13N
O13
15N
O15
C3
C1
76
4542
S4
MM
P30
+B
BM
MP4
0+
BB
PL7
+PP
PL7
+PP PL
7+
PP PL8
+PP PL
8+
PP
PL8
+PP
PL7
+PP
PL7
+PP PL
8+
PP
R69
SIG
_1/6
.01
PL8
+PP
R67
R68
M30
I+
BB
M30
B+
BB
M40
I+
BB
M40
B+
BB
T1_N
T2_1
15V
AC
MC
B
MC
B
R46_
47
R48_
49
R67
R68
R25
MC
B
MC
B
MC
B
MC
B
MC
B
MC
B
R20
+G
B
PL18
+PP
PL18
+PP
TB2
TB2
T3_2
4VT3
_CO
M
431A
431B
429A
427A
427B
426A
426B
425A
413A
411A
409A
407A
405A
404A
401A
168C
203B
303A
303B
(Sch
emat
ic c
on
tin
ues
on
nex
t p
age.
)
48 Daikin IM 696-4
Typical Wiring Diagrams
Figure 22:
H443-4
H443-1
H443-7
H44
3-14
H44
3A
H443-5
H443-2
H443-12
H44
3-15
H44
3C
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
401
239
425
405
137
261
404
241
430
409
149
264
DEC
RIN
CR
SAF
AB
B40
1
DEC
RIN
CR
RAF
AB
B40
1
76
4
1
35
1413
7
14
H2D
NH
2VH
2UP
149
1216
108
1113
76
5
2
35
12
1413
15
H2D
NH
2VH
2UP
149
1216
108
1113
R67
PL7+PP
PL7+PP
R61
M30
I+
BB
PL7+PP
PL7
+PP
R46_
47
AFD
10+
NB
R68
PL8+PP
PL8+PP
R66
PL8+PP
M40
I+
BB
PL8
+PP
R48_
49
AFD
20+
NB
443C
443A
443D
445A
445B
443G
443E
443H
445C
445D
(Sch
emat
ic c
on
tin
ues
on
pre
vio
us
pag
e.)
Auxiliary VFD control
Daikin IM 696-4 49
Typical Wiring Diagrams
Figure 23: Modulating gas heat control (standard mod)
/1.6
8
H63
4-8
H63
3-9
H63
2-9
NO
TE:
1.PO
WER
, PIL
OT
& M
AIN
VA
LVE
IND
ICA
TIO
NLI
GH
TS A
RE P
ART
OF
THE
FLA
MES
AFE
GU
ARD
(FSG
) CO
NTR
OLL
ER.
BLA
CK
WH
ITE
BLA
CK
WH
ITE
IGN
ITIO
N T
RAN
SFO
RMER
BLA
CK
BLA
CK
BLA
CK
BLA
CK
H60
4-3
H604-5
H61
0-1
H60
2-2
H60
3-1
H60
3-4
H60
3-2
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616
617
618
619
620
621
622
623
624
625
626
627
628
629
630
631
632
633
634
635
636
207
207
625
632
413
225
402
24V
SRC
jprs
BO
10
24V
SRC
jprs
BO
9
GTYC
OM
CLO
SE
OPE
N
MO
DU
LATI
NG
GA
S &
AIR
VA
LVE
AC
TUA
TOR
(FLO
ATI
NG
)
CC
W(C
L)
CW
(OP)
FSG
-G
FSG
-F
(FLA
ME
ROD
)
FD
MIC
ROC
OM
PUTE
R
5K1
2K1
1K1
(L1)
6K1
3K1
4K1
2K2
FLA
ME
AM
PLI
FIER
T I M E R
FSG
(FLA
ME
SAFE
GU
ARD
)(P
LUG
-IN
TY
PEC
ON
TRO
LLER
)
6000
VX
1X
2
115V
BLK
BLK
9 9 810
NO
10
9NO
9
5
64
11 12
RED
_G63
0-B
WH
T_G
630-
W
YEL
_G63
2-R
YEL
_G63
3-1
YEL
_G63
4-2
21RWH
TB
LK
C2
C1
CO
MN
O
21212121212121
BLK
BLK
BLK
WH
T
BLK
WH
T
107
6
98
L2
345
L2L1
2
6
3
5
4
NB
RED
_G61
7-L
20 202020202020
WH
T_G
617-
R
87
1
L4L3
L2L1
5
31
11482
10
571
38
7
1
2
21
42
8 9
10
NB
RED
_G60
9-L
WH
T_G
609-
R
RED
_G60
3-L3
RED
_G60
2-L2
RED
_G60
2-L1
RED
_G60
2-L1
1
PL19
+PP
PL18
+PP PL
18+
PPM
CB
+M
B
MC
B+
MB
R23
TB11
TB11
VM
I
R23
AS
GV
1
GV
2
GV
3
FSG
IT
TB11
TB11
TB11
TB11
TB11
TB11
R24
+M
BPL
19+
PP
FLC
PL19
+PP
R20
S3
PL19
+PP
R25
+M
B
S1/2
.01 PL
16+
PP
PL19
+PP
SIG
_1/4
.28
HL2
2
BM
T1_N
PL19
+PP
PL16
+PP
TB11
TB11
TB11
TB11
634B
633C
633B
632B
621B
621C
617A
613A
611A
610A
610B
607A
604A
604B
603A
603B
603C
602A
201A
426B
168C
(Sch
emat
ic c
on
tin
ues
on
th
e n
ext
pag
e.)
8
624
609
619
618
50 Daikin IM 696-4
Typical Wiring Diagrams
Figure 23: Modulating gas heat control (standard mod)
PRES
S. R
EG.
PRES
S. R
EG.
AIR
SWIT
CH
AIR
SWIT
CH
CO
NN
.TE
ST
CO
CK
TEST
CO
NN
.TE
ST
CO
CK
TEST
MA
IN G
AS
VA
LVES
GV
3
PILO
T V
ALV
EMA
IN G
AS
VA
LVES
GV
3
PILO
T V
ALV
E
BLO
WER
BU
RNER
BLO
WER
BU
RNER
GV
1
CO
NN
.TE
ST
GV
1
GV
2G
V2
PIPI
NG
DIA
GRA
MPI
PIN
G D
IAG
RAM
PILO
T
REG
.
MA
INPR
ESS.
PILO
T
REG
.
MA
INPR
ESS.
CO
CK
CO
CK
CO
NN
.TE
ST
OV
ER 1
/2 P
.S.I.
HIG
H P
RESS
.(TH
RU 1
/2 P
.S.I.
)
OV
ER 1
/2 P
.S.I.
HIG
H P
RESS
.(TH
RU 1
/2 P
.S.I.
)
REG
.RE
G.
SHU
TOFF
SHU
TOFF
CO
CK
CO
CK
SHU
TOFF
SHU
TOFF
CO
CK
AIR
CO
CK
VA
LVE
GA
SM
OD
.
DA
MPE
RA
IR
VA
LVE
GA
SM
OD
.
DA
MPE
R
UPO
N D
ETEC
TIO
N O
F PI
LOT
FLA
ME,
TER
MIN
AL
#10
(IGN
ITIO
N T
RAN
SFO
RMER
--IT
) WIL
L B
E D
E-EN
ERG
IZED
AN
D T
ERM
INA
L #9
(MA
IN G
AS
VA
LVES
--G
V2
& G
V3)
THE
BU
RNER
CO
MB
UST
ION
AIR
BLO
WER
MO
TOR
(BM
). W
HEN
EVER
PO
WER
IS R
ESTO
RED
TO
TH
E FL
AM
E SA
FEG
UA
RD, T
HE
FLA
ME
SAFE
GU
ARD
WIL
L G
O T
HRO
UG
H A
10
SEC
ON
D
CO
NTR
OL
(FLC
) AN
D T
ERM
INA
L #6
ON
TH
E FL
AM
E SA
FEQ
UA
RD (F
SG) I
S PO
WER
ED. T
HE
FLA
ME
SAFE
GU
ARD
TH
EN E
NER
GIZ
ES IT
S TE
RMIN
AL
#4, W
HIC
H P
OW
ERS
(BO
#9) O
R (B
O#1
0) O
N T
HE
MA
IN C
ON
TRO
L B
OA
RD (M
CB
) ARE
CLO
SED
TH
E A
CTU
ATO
R W
ILL
REM
AIN
AT
ITS
PRES
ENT
POSI
TIO
N.
TH
E H
EATI
NG
CA
PAC
ITY
IS M
ON
ITO
RED
BY
TH
E
POSI
TIO
N.
WH
EN T
HE
MA
IN C
ON
TRO
L SY
STEM
CLO
SES
(BO
#9) O
N T
HE
MA
IN C
TRL
BRD
.(MC
B),
THE
AC
TUA
TOR
WIL
L RE
POSI
TIO
N T
OW
ARD
A L
OW
ER F
IRIN
G R
ATE
. IF
NEI
THER
MA
IN C
TRL
BRD
.(MC
B),
THE
GA
S V
ALV
E A
CTU
ATO
R W
ILL
REPO
SITI
ON
TO
WA
RD A
HIG
HER
FIR
ING
RA
TE U
NTI
L EI
THER
(BO
#10)
OPE
NS
OR
THE
AC
TUA
TOR
REA
CH
ES IT
S M
AX
IMU
M
GA
S V
ALV
E A
ND
CO
MB
UST
ION
AIR
DA
MPE
R A
ND
CA
N S
ET T
HE
FIRI
NG
RA
TE B
ETW
EEN
33%
AN
D 1
00%
OF
NO
RMA
L RA
TE.
WH
EN T
HE
MA
IN C
ON
TRO
L SY
STEM
CLO
SES
(BO
#10)
ON
TH
E
WH
ENEV
ER T
HE
BU
RNER
IS IN
OPE
RATI
ON
ITS
FIRI
NG
RA
TE W
ILL
BE
DET
ERM
INED
BY
TH
E "F
LOA
TIN
G"
GA
S V
ALV
E A
CTU
ATO
R (V
M1)
. TH
IS A
CTU
ATO
R PO
SITI
ON
S TH
E B
UTT
ERFL
Y
MA
IN C
ON
TRO
L B
OA
RD (M
CB
) TH
ROU
GH
(AI#
10) V
IA A
PO
SITI
ON
FEE
DB
AC
K P
OTE
NTI
OM
ETER
ON
TH
E A
CTU
ATO
R (V
M1)
.
SAFE
GU
ARD
(FSG
). U
PON
A C
ALL
FO
R H
EAT,
TH
E C
ON
TRO
L SY
STEM
WIL
L C
LOSE
(BO
#11)
ON
TH
E M
AIN
CTR
L B
RD (M
CB
), TH
US
ENER
GIZ
ING
REL
AY
(R20
).
WH
EN T
HE
ROO
FTO
P U
NIT
IS E
NER
GIZ
ED 1
20 V
OLT
PO
WER
IS S
UPP
LIED
TO
TH
E SY
STEM
ON
-OFF
SW
ITC
H (S
1), T
O B
URN
ER O
N-O
FF S
WIT
CH
(S3)
AN
D 2
4 V
OLT
S TO
TH
E (B
O#1
1)
POW
ER IS
FU
RNIS
HED
TH
ROU
GH
TH
E SY
STEM
ON
-OFF
SW
ITC
H (S
1), T
HRO
UG
H T
HE
BU
RNER
ON
-OFF
SW
ITC
H (S
3), T
HRO
UG
H R
ELA
Y (R
20) C
ON
TAC
TS, T
HRO
UG
H T
HE
HIG
H L
IMIT
CO
NTA
CTS
ON
TH
E M
AIN
CTR
L B
RD (M
CB
). B
URN
ER O
N-O
FF S
WIT
CH
(S3)
WIL
L PO
WER
TH
E M
OD
ULA
TIN
G G
AS
VA
LVE
AC
TUA
TOR
(VM
1) A
ND
TER
MIN
AL
#5(L
1) O
N T
HE
FLA
ME
DE-
ENER
GIZ
ED, T
HU
S D
E-EN
ERG
IZIN
G T
HE
BU
RNER
. TH
E FL
AM
E SA
FEG
UA
RD W
OU
LD T
HEN
BE
ON
SA
FETY
LO
CK
OU
T A
ND
WO
ULD
REQ
UIR
E M
AN
UA
L RE
SETT
ING
. TH
E H
EAT
ALA
RM
ALS
O, T
HE
FLA
ME
SAFE
GU
ARD
CO
NTA
INS
"LED
'S"
(LO
WER
LEF
T C
ORN
ER) T
HA
T W
ILL
GLO
W T
O IN
DIC
ATE
OPE
RATI
ON
.
BLO
WER
OPE
RATI
ON
IS S
ENSE
D B
Y T
HE
AIR
SW
ITC
H (A
S), W
HIC
H M
AK
ES T
ERM
INA
L #6
TO
#7.
AFT
ER A
90
SEC
ON
D P
REPU
RGE
PERI
OD
, TER
MIN
AL
#8 (F
IRST
GA
S V
ALV
E
THE
RELA
Y D
RIV
ES T
HE
GA
S V
ALV
E A
CTU
ATO
R (V
M1)
TO
TH
E M
INIM
UM
FIR
ING
RA
TE P
OSI
TIO
N W
HEN
EVER
TH
E FL
AM
E IS
NO
T
RELA
Y (R
24) W
OU
LD T
HEN
BE
ENER
GIZ
ED A
ND
WO
ULD
TH
EN E
NER
GIZ
E TH
E RE
MO
TE "
HEA
T FA
IL"
IND
ICA
TOR
LIG
HT
AN
D S
END
A F
AIL
SIG
NA
L TO
BIN
ARY
INPU
T #5
ON
TH
E
IN T
HE
EVEN
T TH
E PI
LOT
FAIL
S TO
IGN
ITE
OR
THE
FLA
ME
SAFE
GU
ARD
FA
ILS
TO D
ETEC
T IT
S FL
AM
E W
ITH
IN 1
0 SE
CO
ND
S, T
ERM
INA
LS #
4, 8
, 9, A
ND
10
WIL
L B
E
IF T
HE
UN
IT O
VER
HEA
TS, T
HE
HIG
H L
IMIT
CO
NTR
OL
(FLC
) WIL
L C
YC
LE T
HE
BU
RNER
, LIM
ITIN
G F
URN
AC
E TE
MPE
RATU
RE T
O T
HE
LIM
IT C
ON
TRO
L SE
T PO
INT.
INIT
IATI
ON
PER
IOD
BEF
ORE
TH
E PR
EPU
RGE
PERI
OD
WIL
L B
EGIN
.
MIC
ROTE
CH
II M
AIN
CO
NTR
OL
BO
ARD
(MC
B).
WIL
L B
E EN
ERG
IZED
AN
D T
HE
MA
IN F
LAM
E W
ILL
CO
ME
ON
.
THE
FLA
ME
ROD
(FD
).
(PIL
OT)
--G
V1)
AN
D T
ERM
INA
L #1
0 (IG
NIT
ION
TRA
NSF
ORM
ER--
IT) W
ILL
BE
ENER
GIZ
ED.
ON
, AN
D H
OLD
S IT
TH
ERE
UN
TIL
THE
FLA
ME
HA
S LI
T A
ND
BEE
N P
ROV
EN.
LOW
FIR
E ST
ART
IS P
ROV
IDED
BY
REL
AY
(R23
).
SEQ
UEN
CE
OF
OPE
RATI
ON
THE
PILO
T FL
AM
E W
ILL
IGN
ITE
AN
D B
E D
ETEC
TED
BY
TH
E FL
AM
E SA
FEG
UA
RD T
HRO
UG
H
WH
EN 1
20 V
OLT
642
643
644
645
646
647
648
649
650
651
652
653
654
655
656
657
658
659
660
661
662
663
664
665
666
667
668
669
670
(Sch
emat
ic c
on
tin
ues
on
th
e p
revi
ou
s p
age.
)
, continued
Daikin IM 696-4 51
Typical Wiring Diagrams
Figure 24: Multistage electric heat control (4 stage)
500
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522
523
524
525
526
527
528
529
530
531
532
533
(Sch
emat
ic c
ontin
ues
on n
ext p
age.
)
500
546
552
500
548
500
547
500
500
550
556
500
500
553
500
554
(MA
NU
AL)
(MA
NU
AL)
(MA
NU
AL)
(MA
NU
AL)
(MA
NU
AL)
(MA
NU
AL)
(MA
NU
AL)
(MA
NU
AL)
L3B
L3A
L2B
L2A
L1B
L1A
L3-1
L2-1
L1-1
T3T2T1
L3L2L1
L3L2L1
T3T2T1
L3
L2
L1 L3
L2
L1
L3
L2
L1
T3T2T1
L3L2L1
L3L2L1
T3T2T1
L3-7
L2-7
L1-7
43
21
L3
L2
L1
T3T2T1
L3L2L1
L3L2L1
T3T2T1
L3-6
L2-6
L1-6
43
21
L3
L2
L1
T3T2T1
L3L2L1
L3L2L1
T3T2T1
L3-5
L2-5
L1-5
43
21
L3
L2
L1
43
21
43
21
L3
L2
L1
L3-2
L2-2
L1-2
T3T2T1
L3L2L1
L3L2L1
T3T2T1
43
21
T3T2T1
L3L2L1
L3L2L1
T3T2T1
L3-8
L2-8
L1-8
L3-3
L2-3
L1-3
T3T2T1
L3L2L1
L3L2L1
T3T2T1
L3-4
L2-4
L1-4
T3T2T1
L3L2L1
L3L2L1
T3T2T1
43
21
43
21
L3
L2
L1
PB3
PB3
M31
FB31
HTR
1A
HTR
3AH
TR3B
M43
FB43
PB3
HL1
2
HTR
2B
M42
FB42
PB3
HL1
1
HTR
1B
M41
FB41
PB3
HL4
HTR
4A
HL3
HL2
HTR
2A
PB3
M32
FB32
HL1
M44
FB44
PB3
PB3
M33
FB33
PB3
M34
FB34
HL1
4
HL1
3
HTR
4B
508A
508B
508C
507C
507D
506C
506D
516D
516E
516F
515E
515F
514E
514F
511G
510G
512D
512E
512F
511E
511F
511H
510E
510F
510H
507G
506G
508D
508E
508F
507E
507F
507H
506E
506F
506H
512B
512C
511C
511D
510C
510D
507B
506B
510A
511A
512A
510B
511B
506A
507A
520D
520E
520F
519E
519F
518E
518F
516B
516C
515C
515D
514C
514D
514A
515A
516A
514B
515B
520B
520C
519C
519D
518C
518D
518A
519A
520A
518B
519B
519G
518G
515G
514G
52 Daikin IM 696-4
Typical Wiring Diagrams
Figure 24: Multistage electric heat control (4 stage)
(Sch
emat
ic c
ontin
ues
on p
revi
ous
page
.)
HEA
TER
BA
NK
"A
" M31
1 A
M32
2 A
M33
3 A
120
KW
HEA
TER
BA
NK
"B
" M41
1 B
M34
4 A
5 A
6 A
M44
4 B
M43
3 B
M42
2 B
8 B
7 B
120
KW
534
535
536
537
538
539
540
541
542
543
544
545
546
547
548
549
550
551
552
553
554
555
556
557
558
559
560
561
562
563
564
565
566
567
568
569
570
207
506
522
514
506
530
530
514
522
J10
STA
GE
6
STA
GE
5
STA
GE
4
STA
GE
3
STA
GE
2
STA
GE
1
BO
11
SRC
(AU
TO)
(AU
TO)
(AU
TO)
(AU
TO)
(AU
TO)
(AU
TO)
(AU
TO)
(AU
TO)
UN
DER
HEA
TER
DEA
DFR
ON
T
ON
SW
ITC
H B
RAC
KET
IN M
AIN
CO
NTR
OL
PAN
EL
2
NB
2
131211
910
87
6
54
3
21
REF
N2-
N2+24
C
BI1
2
24V
11N
O11
A1
A2
4 5
94
6
9-16
9-16
9-16
9-16
21
A1
A2
21
A1
A2
21
96 97 99
7 8 9
A1
A2
A1
A2
A1
A2
A1
A2
A1
A2
21
21
21
21
21
95 98
933
171
43
21
PL12
+PP
T1_N
/1.6
8
TB11
N2+
B/1
NC
-B/1
REFB
/1
N2+
A/1
N2-
A/1
REFA
/1
T3_C
OM
/3.1
1T3
_24V
/3.1
1
MC
B
T3_2
4V/3
.11
M31
PL12
+PP
PL12
+PP
TB11
PL12
+PP
MC
B
HL3
1
M44
HL4
4
M34
HL3
4
TB11
TB11
TB11
PL12
+PP
PL12
+PP
PL12
+PP
M41
M42
M32
M33
M43
HL4
2
HL4
1
HL3
2
HL4
3
HL3
3
TB11
TB11
TB11
PL12
+PP
TB11
PL12
+PP
T1_1
15V
AC
/1.6
8
HS3
HS1
303B
303A
303A
168C
168A
544C
556A
556B
556C
555A
554A
554B
553A
552A
552B
552C
550A
550B
550C
549A
548A
548B
547A
546A
546B
546C
544B
538A
538B
536A
536B
, continued
Daikin IM 696-4 53
Typical Wiring Diagrams
Figure 25: Energy recovery wheel control
H90
6-1
H90
3-1
H90
4-1
H90
5-1
H90
3-2
H90
4-2
H90
5-2
DRN
4
H92
4-1
H92
5-2
DRN
4
H93
0-1
H93
1-2
H91
2-7
H91
3-6
H91
4-10
H91
2-8
H91
4-10
H91
2-8
H91
2-7
H91
3-6
902
903
904
905
906
907
908
909
910
911
912
913
914
915
916
917
918
919
920
921
922
923
924
925
926
927
928
929
930
931
932
933
109
955
934
207
207
239
959
MTR
EN R
CVY
(EX
HA
UST
AIR
-SEN
SOR
LEA
VIN
G W
HEE
L)
SRC
DIS
AB
LE
DIS
AB
LE
B02B01
J8
J10
ENA
BLE
ENA
BLE
JUM
PERS
ENER
GY
.RE
CO
VER
YB
OA
RD
INPU
TSB
I=B
INA
RYA
I=A
NA
LOG
(JU
MPE
R LO
CA
TED
JUST
UN
DER
CO
MM
. CA
RD)N2
BU
S
(LEA
VIN
G A
IR-S
ENSO
RO
UTD
OO
R A
IR L
EAV
ING
WH
EEL)
(CLO
SE)BO
5
(OPE
N)BO
6
24V
SRC
jprs
24V
SRC
jprs
(OA
DA
MPE
R)1
324
(WIT
H C
CW
SPRI
NG
RET
URN
CLO
SED
)
(RA
DA
MPE
R)1 CO
M
CC
W
CW
24V 42 3
(WIT
H C
WSP
RIN
G R
ETU
RNO
PEN
)
L3-1
2
L2-1
2
L1-1
2
GN
D
W2
V2
U2
W1
V1
U1
L1
T3T2T1
L3L2L1 L3L2
T3T2T1
1 2
4
WH
T
BLK
DRN
1-8
24V
REF
N2-
N2+24
C
BI1
0
BI1
2
BI1
1
BI8
BI9
BI7
AI2
5VD
C
CO
M
AI3
AI6
CO
M
5VD
C
CO
MAI1
1 2
4
5NO
5
6NO
6
WH
T
BLK
DRN
87 6
10
CO
M
CW
24V
CC
W
WH
T
DRN
BLK
PB11
AFD
60+
NB
GN
D1
CB
60
MTR
1+
NB
PL24
+PP
EAT
+N
B
N2+
A/2
.11
N2-
A/2
.12
REFA
/2.1
2
ERB
1
PL23
+PP
LAT
+N
B
T1_1
15V
AC
/1.6
8T2
_24V
AC
/2.6
4T1
_N/1
.68
T2_C
OM
/2.4
7T3
_CO
M
MC
B
MC
B
PL11
PL11
PL11
PL11
AC
T3+
NB
AC
T4+
NB
(Sch
emat
ic c
on
tin
ues
on
nex
t p
age.
)
204B
204A
303B
12L3
12L2
12L1
168C
168A
209C
210C
211C
912B
912A
912A
914A
924C
925C
930C
931C
54 Daikin IM 696-4
Typical Wiring Diagrams
Figure 25: Energy recovery wheel control
H957-12
H957-8
H957-9
H957-7
H93
4-1
H93
4-2
H93
9-4
H93
9-3
H94
1-2
933
934
935
936
937
938
939
940
941
942
943
944
945
946
947
948
949
950
951
952
953
954
955
956
957
958
959
960
961
962
963
964
934
944
903
903
961
959
DEC
RIN
CR
(EN
ERG
Y R
ECO
VER
Y W
HEE
L'S)
BO
7
NO
CO
M
NC
BO
8
NO
CO
M
BO
9
NO
CO
M
BO
1
NO
BO
4
NO
CO
M
NO
BO
6
NO
CO
M
NOB
O2
NO
(CO
MPR
#5)
CO
M
BO
6
BO
5
CO
M
CO
M
(CO
MPR
#1) B
O3
CO
M
CO
M
(CO
MPR
#3)
(BY
PASS
DA
MPE
R)
CW
CC
W
87
8
12
9
7
59
H1U
P
H1C
H1D
N
H2D
NH
2VH
2UP
149
1216
108
1113
1917161298653
2018144 15131110721
JJ
21
3
OPE
N
CO
MC
LOSE
4
2
R60
PL12
PL12
PL12
PL12
R60
R58_
59
R58_
59
AFD
60+
NB
MTR
1+
NB
PL12
PL12
T3_2
4VT3
_CO
M
PL22
AC
T12
+N
B
PL22
PL22
303A
934C
946C
944C
941C
303B
940C
958A
958B
959A
958C
(Sch
emat
ic c
on
tin
ues
on
pre
vio
us
pag
e.)
, continued
Daikin IM 696-4 55
Typical Wiring Diagrams
Figure 25:
(OPEN OUTPUT)
(OPEN OUTPUT)
(OPEN OUTPUT)
(OPEN OUTPUT)
(OPEN OUTPUT)
(OPEN OUTPUT)
TO COOLING STAGE #4
TO COOLING STAGE #3
TO COOLING STAGE #2
TO COOLING STAGE #1
277V, 5A RESISTIVE
120V, 1/10HP, 3FLA, 18LRA, 100VA PILOT DUTY
240V, 1/4HP, 2.9FLA, 17.4LRA, 250VA PILOT DUTY
277V, 1/3HP, 2.98FLA, 17.88LRA, 300VA PILOT DUTY
BINARY OUTPUT ELEC. RATINGS
JUMPERS
ENABLE DISABLEBO1
ENABLE DISABLEBO2
(JUMPER LOCATEDJUST UNDERCOMM CARD)
1.3K OHM, 2W
801
802
803
804
805
806
807
808
809
810
811
812
813
814
815
816
817
818
819
820
821
822
823
824
825
826
827
828
829
830
831
832
833
834
835
836
837
838
839
840
841
842
843
844
845
846
847
848
849
850
851
852
853
854
855
856
207
BO7
NOCOM
NCCOM
BO6
BO8
NOCOM
BO9
NOCOM
BO1
NOCOM
BO4
NOCOMBO5
NOCOMBO6
NOCOM
BO3
NOCOM
BO2
NOCOM
J10
J8
INPUTSBI=BINARYAI=ANALOG
GENERIC.CONDENSER
BOARD
N2BUS
24V SRC
jprs
?
211
221
212
213
210
220
WHT
BLK
DRN
2019
1817
16 15
14
12 13
11
9 10
8 7
6
5 4
3
2
1
5VDC
COM
AI3
AI6
COM
AI2
5VDC
COM
AI1
REF
N2-
N2+
24C
BI12
BI11
BI8
BI10
BI9
BI7
24V
8
7NO7
TB4
TB4
TB4
TB4
REF/2.11
N2+/2.10
N2-/2.10
24VT3
24VNT3
TB4
TB4
GCB1RESISTOR
MCB B07
834A
832A
830B
828B
830A
828A
823A
210D
209C
210C
Generic condenser control (4 stage)
56 Daikin IM 696-4
Typical Wiring Diagrams
Figure 26: Constant volume fan control (SAF and RAF)
401A
404A
426C426B426A
431A
TB2
42
TB2
45
2
R68
10
2
R67
10
R68
3404
1
R67
3401
1
M20
A2A1
M10
A2A1
jprs
24V SRC
MCB
2 2NO
BO2
RETURN FAN207
jprs
24V SRC
MCB
1 1NO
BO1
SUPPLY FAN207
SRC 9-16
MCB207
11(31)
MMP10
12(32) 11(31)
MMP20
12(32)
TO MOTHERBOARDWIRED INTERNAL
SOURCE 9-16
T3_COM
/3.11
T3_24V
/3.11
115VAC_GF/1 T1_N
/1.68
Figure 27:
1003B1003A
1004B
1005B1005A
NTB7
GTB7
HTB7
REC1
CP SL
GRD
SLCP
PL32
1
S11
PL31
1
S10
G1004
2PL32
G1012
NG
REC11
H
31
LT11
BLK WHTw
2PL31
G1009
NG
REC10
H
30
LT10
BLK WHTw
FIELD SUPPLIED 115V/60/1
H1010-2H1010-1
H775 H776
H775
H1006-2H1006-1
H776H775
H775
Light and receptacle power
Daikin IM 696-4 57
Test Procedures
Test Procedures
CAUTION
When troubleshooting the various MicroTech II components, it may be necessary to remove power to the controller by opening system switch S1 in the main control panel. Before doing this, pump down the compressors. To do this, open pumpdown switches PS1 and PS2.
The “Parts List” section at the end of this manual includes a listing of MicroTech II related part numbers.
Troubleshooting Main Control Board (MCB)MCB Battery
Standby power is provided by a 3 VDC lithium battery, which maintains the MCB Static Random Access Memory (SRAM) and the Real Time Clock (RTC) while power is removed from the MCB.
The battery degrades with time depending on load, temperature, and the percentage of time the MCB does not have power. With an operating temperature under 25ºC, battery life expectancy is as follows:
Battery usage Typical life Minimum life
1% 10 years 5 years10% 10 years 5 years
100% 1 year 0.3 years
A battery test is performed each time the MCB power-up diagnostics are executed. The minimum voltage needed to sustain the SRAM and RTC is 2.0 VDC. A warning occurs when the battery voltage drops below approximately 2.5 VDC, which is indicated by the red MCB Error LED blinking after the Main Control Board Power-Up Sequence described below is completed. This warning signals that the battery is reaching the end of its useful life and should be replaced. Once a battery warning alarm occurs, replace the battery within 14 days to avoid complete battery failure and memory loss. Regardless of the battery status, the MCB board continues execution of the on-board program.
Note – After battery replacement, the Error LED does not revert to the normal off condition until one of the following occurs:
• Power is cycled to MCB• The battery is tested at two minutes after midnight each
day. If battery is normal then, the Error LED reverts tonormal
MCB Data Archiving
All the MCB control parameters and the real time clock settings are backed up by the MCB using the SRAM. The
SRAM is maintained by the MCB battery when power is removed from the MCB. To avoid losing the information stored on the board if battery failure occurs, the MCB performs a data archiving function once a day, just after midnight. At this time, all the MCB control parameter settings are archived to a file stored in the MCB FLASH memory.
If the MCB is powered up with a low or defective battery (or no battery), the most recently archived data is restored to the controller.
Note – When this archived data restoration process occurs, it increases the controller startup and initialization period by approximately 75 seconds.
MCB “Cold” Reboot
Whenever troubleshooting of the MCB leads to the conclusion that the MCB is defective, perform a cold reboot before replacing it. A cold reboot consists of removing the MCB battery and cycling power to the controller.
MCB LED Power-Up Sequence
The various LEDs on the MCB are shown in Figure 28. When power is applied to the MCB, the LEDs execute a specific startup sequence, consisting of the following three main components:• The LED Operational Check period• The MCB Error Code Display period• The MCB Initialization period
LED Operational Check Period. When power is applied to the MCB or when the MCB is reset, an operational test of the 16 Binary Input LEDs in the upper left corner and the four miscellaneous status LEDs at the bottom of the MCB is performed. This provides a visual check of the operational status of the LEDs. The following LED sequence should occur: 1 All 16 of the Binary Input LEDs and all the miscellaneous
LEDs (3 green and 1 red) across the bottom of the MCB, turn ON for approximately 1–3 seconds and then turn OFF.
2 The miscellaneous LEDs across the bottom of the MCB sequence ON for one half second and then OFF from left to right (RS-485 Bus Port Activity, RS-232 Port Activity, IP Port Activity, and MCB Error).
3 Binary Input LEDs BI-1 through BI-8 are turned ON for one half second and then turned OFF.
4 Binary Input LEDs BI-9 through BI-16 are turned ON for one half second and then turned OFF.
If any of these LEDs fail to light as described, replace the MCB to correct the problem.
Note – Binary Outputs are not tested and remain off during the LED Operational Check period.
Compressor pumpdown is required before removing power to the controller or unit damage could occur.
Table 23: Battery life expectancy
58 Daikin IM 696-4
Test Procedures
Figure 28: Main control board
!
" # "
" $
!
" $
%
& '
( $
% '
$
" # "
$
$
&
) * ) + * ,
MCB Error Code Display Period. After the LED Operational Check period is complete, if any MCB startup errors are detected, an error code displays. For details regarding the various LED error codes, refer to “MCB LED Startup Error Codes” below.
If no startup errors are detected, all LEDs remain OFF and the MCB Initialization period occurs as described below.
MCB Initialization Period. When the MCB Error Code Display period is complete, MCB Initialization begins. This period consists of the following LED sequence:1 All the LEDs remain OFF for approximately 15–20
seconds (with a normal battery). If the battery is low or defective, this period lasts approximately 90 seconds during which previously archived control parameter data is restored to the controller. Refer to “Main Control Board (MCB) Data Archiving” on page 33.
2 The RS-485 Bus Port Activity Indication LED in the lower left corner of MCB begins blinking indicating activity on the RS-485 bus port, and after an approximate 1–2 second delay, the Binary Input LEDs turn ON according to the Binary Input switch conditions.
3 After a 15–20 second pause, the Binary Output LEDs on the right side of the board turn ON, according to the control program logic, and the startup sequence is complete.
Note – The elapsed time for the entire startup sequence, including the LED Operational Check, the MCB Error Code Display, and the MCB Initialization period is approximately 45 to 120 seconds depending on the network configuration and the MCB battery condition.
Daikin IM 696-4 59
Test Procedures
MCB LED Startup Error Codes
The 16 green Binary Input LEDs in the upper left corner and miscellaneous LEDs on the bottom (3 green and 1 red) of the MCB (Refer to Figure 28 on page 59) can be used to diagnose problems with the MCB.
During the MCB Error Code Display period, MCB failures are indicated by the red MCB Error LED on the bottom right side turning ON or BLINKING along with one other LED turning ON according to Table 24 on page 60. If multiple error conditions exist, each error code appears in succession, lasting approximately 3 seconds each, and then turn OFF. Non-catastrophic errors are indicated during the MCB Error Code Display period with the red MCB Error LED remaining on continuously.
All non-catastrophic errors are logged in RAM to be retrieved by the MCB operating system. Catastrophic errors are indicated during the MCB Error Code Display period with the
red MCB Error LED flashing at a rate of approximately 5.9 Hz. When the MCB Error Code Display period is complete, the startup sequence continues.
The following diagnostic tests are run during the startup sequence:• Battery Test• Flash CRC (Cyclic Redundancy Check) Test• SRAM (Static RAM) Test• Communication Port Tests• IP Register Test
The following sections provide a brief description of each of these startup tests and recommended steps to correct the problem.
LED
Startup errors
BatteryFlashCRC
startup
Flash CRCmain/boot
FlashCRC
config.
RAMlowbyte
RAMhighbyte
RS 485busport
RS 232port
BACnet MS/TP or LONMARK
port (optional)
I/Oexpansion
port
IPport
Table 24: Main control board LED startup error codes
RS-485 bus port ONRS-232 port ON
IP port ONMCB error ON Blinking Blinking Blinking Blinking Blinking ON ON ON ON ON
BI-1 ONBI-2 ONBI-3 ONBI-4 ONBI-5 ONBI-6 ONBI-7 ONBI-8 ON
60 Daikin IM 696-4
Test Procedures
Battery Test
The battery test determines the status of the MCB battery. When the battery fails the test, the error is indicated by the red MCB Error LED and the Binary Input BI-1 LED turning ON during the MCB Error Code Display period. This warning signals the battery is nearing the end of its useful life and should be replaced. Regardless of the battery status, the MCB board continues execution of the on-board program. Once the Main Control Board LED Power-Up Sequence is complete, if the battery is bad, the red Error LED blinks on and off at a rate of one second on and one second off. If the battery is good it remains off.
Note – After battery replacement, the Error LED will not revert to the normal off condition until one of the following occurs:
• Power is cycled to MCB• The battery is tested at two minutes after midnight each
day. If battery is normal then, the Error LED reverts tonormal.
Flash CRC Tests
The startup Flash memory test consists of a sector by sector CRC check of the following Flash code bases:• Startup• Boot• Main• Two Flash data bases: Dictionary and Configuration.
The results of all five tests are saved in SRAM for use by the operating system. A Dictionary failure does not result in a startup error display. The following scenarios describe the possible failure modes of the flash CRC tests.
Bad CRC in Startup Code Base. After displaying the Startup Flash CRC error during the MCB Error Code Display period, the startup process continues, if possible. Since the startup code validity is questionable, correct operation from this point is unpredictable. Daikin recommends downloading the startup code again. If this is not possible or ineffective, replace the MCB.
Bad CRC in Main Code Base and Boot Code Base. After displaying the Main/Boot Flash CRC error during the MCB Error Code Display period, the startup process continues. After the startup sequence is completed, execution is passed to the Boot code. Since the Boot code validity is questionable, correct operation after entering Boot code is unpredictable. A CRC failure in only the Boot or only the Main code base will not result in an error display. Re-downloading the Main and Boot code is recommended.
Bad CRC in Configuration Data Base. This is a fatal error that requires replacing the MCB. The configuration database contains user and factory defined configuration parameters including the device name, communication parameters, and I/O setup and calibration data. After displaying the Configuration Flash CRC error during the MCB Error Code Display period, the startup process continues. If main code is
run, the MCB reboots, resulting in continuously repeating the error code and reboot cycle. If boot code is run, MCB will run with factory default values.
SRAM Test
Simply stated, the SRAM test checks each memory location by writing values to each location, reading the value back and comparing the read back value to the expected value. If a SRAM error is detected in the low byte, the RAM Low Byte failure displays during the MCB Error Code Display period. The MCB then is reset by an external “watchdog” circuit and the Main Control Board LED Power-Up Sequence begins again. If a SRAM failure is detected in the high byte, the RAM High Byte failure displays and the Serial Bus Port LED turns ON during the MCB Error Code Display period. The MCB then is reset by an external “watchdog” circuit and the Main Control Board LED Power-Up Sequence begins again. If either the RAM Low Byte or the RAM High Byte error occurs, replace the MCB.
Communication Port Tests
The various communication ports on the MCB are tested during the Main Control Board LED Power-Up Sequence. This feature allows the processor to verify the internal transmit and receive data paths of MCB data communication channels. Once in the test mode, proper operation of the various communication channels is verified by writing data to the corresponding transmit buffer of the channel under test and then reading the data back from the receive register. If read data does not match write data, the MCB displays the appropriate communication port error during the MCB Error Code Display period and then continues startup and initialization. If any of the possible communication port errors occur, replace the MCB.
IP Register Test
After determining the existence of an optional IP communication module, the MCB performs a series of read/write tests on critical registers of the IP processor. If any of the register tests fail, an IP port failure displays during the MCB Error Code Display period and then the MCB continues running startup and initialization. If the IP port error occurs, replace the IP communication module. If the problem persists after replacing the IP communication module, it is likely the MCB is defective. Refer also to the literature shipped with the IP communication module.
Daikin IM 696-4 61
Test Procedures
Troubleshooting Auxiliary Control Boards (CCB1, CCB2, GCB1, EHB1 and ERB1)This section outlines basic functional checks of the auxiliary control boards that might be connected to the MCB via the RS-485 communication bus interface.
Hardware Check
1 Verify the auxiliary control board has been wired and terminated properly. Refer to the as-built unit wiring schematics or refer to Figure 16 on page 38 (DAC units) or Figure 17 on page 41 (SCC units).
2 Verify the RS-485 Communications module on the auxiliary control board is properly installed. Verify the address switches on the RS-485 Communication module are set to the correct address.
Note – Address switches may “appear” to be set correctly but actually may not be “seated” well. If there is a communication problem between the main control board and an auxiliary control board, try toggling the switches up and down a couple of times, reset them to the correct setting, and cycle power to the auxiliary control board. Refer to Table 4 on page 9.
3 Verify that 24 VAC power is available (CS1 or CS2 switch ON on as applicable) and properly terminated on the J1 terminal block on the auxiliary control board.
RS-485 Communication Card Status LEDs
A set of two status LEDs is located in the lower right area of the RS-485 Communication Card mounted on the auxiliary control boards (refer to Figure 7 on page 11). These LEDs provide useful trouble shooting information. The upper LED verifies that the MCB is transmitting data to the auxiliary control board. The lower LED verifies that the auxiliary control board is transmitting data to the MCB.1 The upper LED should always blink at the same rate as the
RS-485 Activity LED on the MCB (refer to Figure 30). If it is not blinking and the RS-485 Activity LED on the MCB is blinking, verify the wiring between the MCB and auxiliary board is free of defects. If the RS-485 Activity LED on the MCB is not blinking, it is likely the problem is with the MCB.
2 The lower LED should always be blinking. If it is not, perform the hardware checks listed above. If these check out correctly and the problem persists, cycle power to the entire controls system using the system S1 switch. If the problem persists, either the MCB has not been downloaded and configured correctly or the auxiliary control board or it is likely its RS-485 communication card is defective. Use the following procedure to isolate the problem component:a Verify that the MCB download and configuration has
been performed correctly and then cycle power to the entire control system using the S1 system switch. If this has been done and the problem persists, proceed to Step b below.
b Remove power from the control system and replace the RS-485 communication card on the suspect auxiliary control board with a properly functioning card. Do this by exchanging the RS-485 communication card with one of the other auxiliary control boards on the unit. If this is done, make sure to change the addresses switches on the RS-485 communication cards according to Table 4 on page 12. Apply power to the control system and check operation. If the problem follows the suspect communication card, the card is defective. If the problem remains with the suspect auxiliary control board, it is likely the auxiliary control board is defective.
Troubleshooting Keypad/Display Keypad/Display Power Up Initialization
When the keypad/display is connected to the MCB and power is applied, the firmware in the keypad/display runs a diagnostic test of its static RAM (SRAM) and also checks the micro controller ROM for proper checksum. After these tests are completed, the keypad/display responds to a poll of its address by the MCB with an acknowledge message to the MCB. This causes the controller to start downloading display information to the keypad/display. The keypad is locked out until the tests and the download is complete.
Note – The keypad/display address is defined by a four-position dip switch block on the right side of the device. For this application, all four of these switches should be in the UP position, which defines address 32.
When the keypad/display is connected to the MCB and power is applied, the backlight and the red Alarm LED on the display are turned on. The backlight remains on until it times out (15 minutes after a key press or after power up). During the next 5 seconds, the LCD counts down from 9 to 0 in all 80 character locations. After the countdown is complete, the Alarm LED turns off and the display appears as follows:
Version xxx
Addressyy
Statuszz zzzz
Startupaaaa bbbb ccc
Where:
xxx = The version of firmware in the keypad/display
yy = The keypad/display address 32
zzzz = OK normally or NO COMM if the MCB is not communicating with the keypad/display
aaaa = OK normally or IRAM if internal RAM test failed
bbbb = OK normally or XRAM if external RAM test failed
ccc = OK normally or ROM if ROM checksum does not match stored checksum
62 Daikin IM 696-4
Test Procedures
When the MCB finishes downloading to the keypad/display it sends a “download complete” message to the keypad/display. When this message is received, the LCD shows the “main” rooftop application menu screen.
Note – A NO COMM indication on the Status line during the initialization period does not necessarily indicate a problem. A communication problem is indicated if the LCD “hangs,” i.e., it does not proceed to show the “main” rooftop application menu screen.
If aaaa= IRAM, bbbb= XRAM and/or ccc= ROM, replace the keypad/display.
Note – The keypad/display can be connected to the MCB while power is on. The normal elapsed time for the “main” rooftop menu screen to appear in the LCD upon initializing is approximately 60 seconds.
Troubleshooting Temperature SensorsThe MicroTech II temperature sensor consists of a positive temperature coefficient (PTC) silicon sensing element. The resistance of this sensor increases with increasing temperature. The element has a reference resistance of 1035 ohms at 77°F (25°C). Each element is calibrated according to the graphs shown in Figure 29 (°F) and Figure 30 on page 64 (°C). Tabulated resistance vs. temperature data is shown in Table 25.
Use the following procedure to troubleshoot a suspect sensor.1 Disconnect the sensor from the MCB.2 Take a temperature reading at the sensor location. Be sure
to allow the thermometer to stabilize before taking the reading.
3 Use the temperature reading from Step 2 to determine the expected sensor resistance from Table 25.
4 Using an ohmmeter, measure the actual resistance across the two sensor leads.
5 Compare the expected resistance to the actual resistance.6 If the actual resistance value deviates substantially (more
than 10%) from the expected resistance found in Table 25, replace the sensor.
Temperature °F (°C) Resistance in ohms
Table 25: MicroTech II temperature sensor—temperature vs. resistance chart
-40 (-40) 613-31 (-35) 640-22 (-30) 668-13 (-25) 697-4 (-20) 7275 (-15) 75814 (-10) 78923 (-5) 82232 (0) 85541 (5) 88950 (10) 92459 (15) 96068 (20) 99777 (25) 103586 (30) 107495 (35) 1113
104 (40) 1153113 (45) 1195122 (50) 1237131(55) 1279140 (60) 1323149 (65) 1368158 (70) 1413167 (75) 1459176 (80) 1506185 (85) 1554194 (90) 1602203 (95) 1652212 (100) 1702221(105) 1753230(110) 1804239 (115) 1856248 (120) 1908
Daikin IM 696-4 63
Test Procedures
Figure 29. MicroTech II temperature sensor—temperature (°F) vs. resistance graph
500 700 900 1100 1300 1500 1700 1900-40
0
40
80
120
160
200
240
280
Resistance (Ohms)
Tem
pera
ture
(°F)
Figure 30. MicroTech II temperature sensor—temperature (°C) vs. resistance graph
500 700 900 1100 1300 1500 1700 1900
Resistance (Ohms)
-40
-20
0
20
40
60
80
100
120
140
Tem
pera
ture
(°C
)
Troubleshooting Communications ModulesBACnet/IP Module
For a detailed description and troubleshooting information regarding the BACnet/IP communications module, refer to installation and maintenance bulletin IM 703, MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communications Module—BACnet/IP. For details regarding BACnet protocol data, refer to engineering data document, ED 15060, MicroTech II Applied Rooftop Unit Controller Protocol Information.
BACnet MS/TP Module
For a detailed description and troubleshooting information regarding the BACnet MS/TP communications module, refer to installation and maintenance bulletin IM 704, MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller BACnet Communications Module—BACnet/MS/TP. For details regarding BACnet protocol data, refer to engineering data document, ED 15060, MicroTech II Applied Rooftop Unit Controller Protocol Information.
LonMark Modules
For a detailed description and troubleshooting information regarding LonMark communications modules, refer to installation and maintenance bulletin IM 702, MicroTech II Applied Rooftop Unit Controller and Self-Contained Unit Controller LONWORKS Communications Module. For details regarding LONMARK protocol data, refer to engineering data document, ED 15060, MicroTech II Applied Rooftop Unit Controller Protocol Information.
64 Daikin IM 696-4
Troubleshooting Pressure TransducersUse the following procedure to troubleshoot a suspect sensor:1 If the duct static pressure always reads 0" WC on the unit
keypad/display and the discharge inlet vane position or VFD speed is continuously ramping to 100%, check the following:a If the unit has two duct static pressure sensors (SPS1
and SPS2), verify that they both function properly following Steps 2 through 5 below. Also check for faulty wiring connections at analog inputs MCB-AI13 and MCB-AI14. The controller displays and controls to the lower of the two readings. If a sensor is defective and inputs 0 volts to the controller, the static pressure reading on the keypad/display reads 0 and the controller attempts to increase the 0 value to set point by ramping the discharge inlet vanes or VFD up.
b If a second sensor (SPS2) is not installed or the pressure tubing to it is not connected, make sure the 2nd P Sensor= parameter in the Unit Configuration menu of the keypad/display is set to “None” so that the controller ignores the second static pressure analog input MCB-AI14.
c If a second sensor (SPS2) is installed, but it is a building space sensor rather than a duct static pressure sensor, make sure the 2nd P Sensor= parameter in the Unit Configuration menu of the keypad/display is set to “Bldg.”
2 Check the 24 VAC power supply to the sensor.a If the sensor is SPS1 or SPS2 (duct static), verify that
there is 24 VAC between the suspect transducer “+” and “-” terminals.
b If the sensor is SPS2 (building static), verify that there is 24 VAC between the “IN” and “CM2” terminals on the SPS2 terminal block.
c If 24 VAC supply reads low and/or the MCB is malfunctioning, the sensor may be drawing too much current. Disconnect the sensor and recheck the voltage and the MCB operation.
3 Using an accurate manometer or gauge, measure the same pressure that the suspect transducer is sensing. To do this, tap into the transducer high and low pressure tubing or locate the measurement device taps next to the transducer taps.
CAUTION
Note – If the suspect sensor is measuring duct static pressure, verify that the high and low pressure taps are properly installed. An improper pressure tap installation can cause severe fluctuations in the sensed pressure. Refer
to the model-specific installation manual for pressure tap installation guidelines (see Table 2 on page 1).
4 Measure the DC voltage output from the transducer.a If the sensor is SPS1 or SPS2 (duct static), measure the
voltage across the sensor “S” and “-” terminals. b If the sensor is SPS2 (building static), measure the
voltage across the “OT2” and “CM2” terminals on the SPS2 terminal block.
If the measured voltage and pressure do not match, there may be a wiring problem or the transducer may be defective. Check the transducer input circuit wiring and connections for defects.
If the measured voltage and pressure match, the MCB may be missconfigured or defective.
5 Remove power from the controller by opening system switch S1. If available, swap a similar good transducer with the suspect transducer or try installing a new transducer. Restore power by closing S1 and verify whether the suspect transducer is defective.
Figure 31. Duct static pressure transducer voltage vs. pressure
Static Pressure ("W.C.)1 2 3 4
Sen
sor O
utpu
t (V
DC
)
1
2
3
4
5
Figure 32. Building (space) static pressure transducer voltage vs. pressure
Static Pressure ("W.C.)
Sen
sor O
utpu
t (V
DC
)
1
2
3
4
5
-0.25 -0.125 0.000 0.125 0.25The fittings on the pressure transducers are fragile. Splice a tee fitting into each tap tube instead of removing each tap tube from its transducer fitting. Use an airtight cap to cover the test port after the pressure measurement.
65 Daikin IM 696-4
Parts List
Below is a partial list of applied rooftop unit replacement parts. Contact a local sales representative for additional information
Table 26: Component designation Description Daikin part number
MCB Main control board 060006101CCB1 Auxiliary cooling control board (DX Circuit #1 or generic condenser) 112026101
(replaces 106102701)CCB2 Auxiliary cooling control board (DX circuit #2) 112026101
(replaces 106102701)EHB1 Auxiliary electric heat control board 112026101
(replaces 106102701)ERB1 Auxiliary energy recovery control board 112026101
(replaces 106102801)– RS-485 communication module (for auxiliary control boards) 060006202– Standoffs for mounting RS-485 communication module (PN 060006202) onto auxiliary control board (PN
112026101)048166707
– Keypad/display 060006301– Keypad, main control board cable 111044601
ZNT1 Zone temperature sensor with tenant override 111048101Zone temperature sensor with tenant override & remote setpoint adjustment (SCC units only) 111048102
DAT Discharge air temperature sensor (50 ft cable length-field cut to length) 060004705ENT Entering fan air temperature sensor (50 ft cable length-field cut to length) 060004705OAT Outside air temperature sensor (50 ft cable length-field cut to length) 060004705RAT Return air temperature sensor (50 ft cable length-field cut to length) 060004705
SPS1 Static Pressure sensor: duct, No. 1 049545007SPS2 Static pressure sensor: duct, No. 2 049545007
Static pressure sensor: building (space) pressure 049545006T2 Transformer: 115/24 VAC 060004601T3 Transformer: 115/24 VAC 060004601T9 Transformer: 115/24 VAC 060630801
HUM1 Humidity sensor: wall mount 067294901Humidity sensor: duct mount 067295001
PC5 Dirty filter switch: first filter section 065493801PC6 Dirty filter switch: final filter section 065493801PC7 Airflow proving switch 060015801DHL Duct high limit switch 065493801OAE Enthalpy control: electromechanical 030706702
Enthalpy control: electronic (used with RAE) 049262201RAE Return air enthalpy sensor (used with electronic OAE) 049262202SD1 Smoke detector: supply air 049025001SD2 Smoke detector: return air 049025001
– BACnet MS/TP communication module (RS-485) 060006202– BACnet/IP communication module (IP cable 10BASET) 060006201– LONMARK space comfort controller (SCC) communication module 060006203– LONMARK discharge air controller (DAC) communication module 060006204– 5 VDC precision power supply 111049610– Serial port ribbon cable 111047201– MCB battery BR2325– MCB connector repair kit 300036605
Daikin IM 696-4 66
Daikin IM 696-4 67
13600 Industrial Park Boulevard, Minneapolis, MN 55441 USA (612) 553-5330
Daikin Training and Development
Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on training, or call 540-248-9646 and ask for the Training Department.
This document contains the most current product information as of this printing. For the most up-to-date product information please go to www.DaikinApplied.com.