Graph for Gt Sizing
-
Upload
amit-saxena -
Category
Documents
-
view
219 -
download
1
description
Transcript of Graph for Gt Sizing
![Page 1: Graph for Gt Sizing](https://reader030.fdocuments.net/reader030/viewer/2022020208/563dbb6c550346aa9aad0b08/html5/thumbnails/1.jpg)
b) Based on the results it can be concluded that with 16% impedance of GSU transformer, Generator
can operate at its rated 0.85 lagging power factor for a grid voltage variation from 95% to 103%. For a
grid voltage variation of 104% to 105%, MVAR delivered by Generator shall be reduced to maintain
the generator terminal voltage within its specified limits.
c) During leading power factor, for grid voltage variation from 102% to 105%, MVAR absorbed by the
Generator has to be reduced to maintain the generator terminal voltage within its specified limits.
9. REFERENCES
National Grid code.
10. ATTACHMENTS d) Attachment -1: HBD at VWO condition (LMTG 0038-M-41201)
e) Attachment -2: Generator capability curve (LMTG 0038-E-51202)
f) Attachment -4: Typical Diagrammatic ETAP output report