Appin Associates is a 37 year old consulting firm that specializes in:
• Building Automation System (BAS) Design including specification and commissioning with emphasis on BACnet-enabled controls.
• Mechanical Systems Design (HVAC, Boilers, Chillers) paying particular attention to the needs of the FM.
Grant Wichenko is a Professional Engineer. He is a member of :
- ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair of AP-WG - SGPC-13 (BAS Guideline Specification committee – voting member)
Appin Associates was the first Engineering firm to join BACnet International.
![Page 3: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/3.jpg)
Page3
Founded in Switzerland in 1874, the Schindler Group is a leading global provider of elevators, escalators and related services. Schindler mobility solutions move more than one billion people every day all over the world. Behind the company's success are over 60,000 employees in more than 100 countries.
Christopher Mason is Schindler’s Engineering Manager for IoT development in North America and is applying his thirty years of experience in Elevator Controller Development to digitize our Remote Monitoring Platform and associated Customer Portal - SchindlerAhead
ASHRAE Member of EL-WG ASME Member Electrical Code Committee ASME Member Innovation and Technology Code Committee ASME Member Occupant Evacuation Operation Task Group
![Page 4: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/4.jpg)
1. Understand the use case and benefits for monitoring elevators and escalators using BACnet.
2. Understand the need for new BACnet objects and services for monitoring elevators and escalators.
3. Outline the requirements and the options for implementing a BACnet-based elevator monitoring project.
4. Explain BACnet’s proposed plans for implementing Occupant Evacuation Operation (OEO) in a networked manner using BACnet objects and services.
Page4
![Page 5: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/5.jpg)
1. Why do we monitor anything as FMs? 2. We need to know the status, health, alarms and energy consumption of the
various devices in facility. We data in a timely manner and we need to access this data remotely as no-one has time to walk around looking for problems.
3. Elevators and Escalators are special BACnet devices. They are expensive to install and then to maintain. Their design and operation are governed by ASME A17/CSA B44 - 2016. They require regular maintenance and testing that is normally contracted out to an elevator company.
4. BACnet offers device interoperability solutions for HVAC, lighting, fire alarm, security and now elevators and escalators.
5. FMs can use BACnet to monitor – but not control – the status and health of elevators and escalators. They are the most expensive device to install and maintain in a building. The time is NOW!!
Page5
![Page 6: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/6.jpg)
• AstheInternetofThingshasgainedtraction,ConnectivityandCustomerServicehavebecomethedrivingforcebehindadatarevolutionwithintheelevatorindustry.Theexpectationisthatreal-timedataandperformancemetricsarereadilyavailable.
• TheelevatorindustryhasembracedtheInternetofElevatorsandEscalatorsandispioneeringwaystodeliverdatainnewways.
• BACnetasaninternationallyrecognizedcommunicationstandardisseeasthenaturalstageofthisevolution.
Page6
![Page 7: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/7.jpg)
Page7
![Page 8: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/8.jpg)
1. From BACnet’s perspective, there are two types of elevators. 1. MachineRoomLess Elevators (MRLs) where you need a separate
BACnet device for each Elevator. 2. Elevators that require a Machine Room. In this case there is
normally one BACnet device for the elevators in that Machine Room. 2. No elevator at this point is a native BACnet device. The elevators speak a
proprietary protocol whose points are translated to BACnet/IP by a gateway supplied by the elevator supplier.
3. The only other non-manufacturer that makes BACnet gateways for elevators and escalators is Lift-Net™ (https://www.liftnet.com).
4. BACnet offers device interoperability solutions for HVAC, lighting, fire alarm, security and now elevators and escalators.
5. FMs need to incorporate elevator and escalator monitoring into facility construction projects.
Page8
![Page 9: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/9.jpg)
Page9
Structured View ObjectNode_Type: BUILDINGNode_Subtype: "Headquarter Building"Description: "6670 185th Ave NE, Redmond WA 98052"
Subordinate_Annotations (BACnetARRAY)
· "Lift Machine Room 1"· "Escalator Machine Room 2"· "Lift Machine Room 3"
Structured View ObjectNode_Type: ROOMNode_Subtype: "Lift Machine Room"
Subordinate_Annotations (BACnetARRAY)
· "Machine Room ID”· "Lift Group A"· "Lift Group B"· "Lift Group C"
Structured View ObjectNode_Type: ROOMNode_Subtype: "Escalator Machine Room"
Subordinate_Annotations (BACnetARRAY)
· "Machine Room ID”· "Escalator Group A"· "Escalator Group B"· "Escalator Group C"
Positive Integer Value Object
Object_Identifier: (PIV, n)Description: "Machine Room ID"Present_Value: 2Units: NONE
Positive Integer Value Object
Object_Identifier: (PIV, n)Description: "Machine Room ID"Present_Value: 1Units: NONE
Elevator Group ObjectMachine_Room_ID:Group_ID: 47Group_Mode: DOWN_PEAK
Group_Members (BACnetARRAY)
· ·
Lift Object
Elevator_Group:Installation_ID: 1Car_Position: 12Car_Direction: UPEnergy_Meter: 12768 kWh
Lift Object
Elevator_Group:Installation_ID: 2Car_Position: 37Car_Direction: STOPEnergy_Meter: 38567 kWh
Elevator Group ObjectMachine_Room_ID:Group_ID: 21Group_Mode: DOWN
Group_Members (BACnetARRAY)
·
Escalator Object
Elevator_Group:Installation_ID: 1Operation_Direction:
DOWN_RATED_SPEEDEnergy_Meter: 8832 kWh
-Building -Machine Rooms (2) -Groups of Elevators or Escalators. -Single device as a Lift or an Escalator Object.
TheStructuredViewobjecttypedefinesastandardizedobjectthatprovidesacontainertoholdreferencestosubordinateobjectstocreatemultilevelhierarchies(geographicaldistributionorapplicationorganization).
![Page 10: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/10.jpg)
Page10
PropertyIdentifier PropertyDatatype ConformanceCode
Object_Identifier BACnetObjectIdentifier R
Object_Name CharacterString R
Object_Type BACnetObjectType R
Description CharacterString O
Machine_Room_ID BACnetObjectIdentifier R
Group_ID Unsigned8 R
Group_Members BACnetARRAY[N]ofBACnetObjectIdentifier R
Group_Mode BACnetLiftGroupMode O1
Landing_Calls BACnetLISTofBACnetLandingCallStatus O1
Landing_Call_Control BACnetLandingCallStatus O1
Property_List BACnetARRAY[N]ofBACnetPropertyIdentifier R
Tags BACnetARRAY[N]ofBACnetNameValue O
Profile_Location CharacterString O
Profile_Name CharacterString O 1Thesepropertiesshallbepresentonlyifthisobjectrepresentsagroupoflifts.
Table12-76.PropertiesoftheElevatorGroupObjectType
![Page 11: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/11.jpg)
Group_Mode
UNKNOWN Thecurrentoperatingmodeoftheliftgroupisunknown.
NORMAL Theliftgroupisinnormaloperatingmode,andnospecialoperatingmodeisinplace.
DOWN_PEAK Mostpassengerswanttoleavethebuilding.Thisusuallyhappensbeforelunchbreakoratthecloseofbusiness.
TWO_WAY Manypassengerswanttogetto,orleave,aparticularfloor.Thisusuallyhappenswhenthereisaspecialfunction,ceremony,meetingorconferenceonaparticularfloor.
FOUR_WAY Manypassengerswanttomovebetweentwoparticularfloors.Thiscanhappen,forexample,ataschoolwhenagroupofstudentswantstotravelfromclassroomtoclassroomontwodifferentfloors.
EMERGENCY_POWER Thewholeliftgroupisoperatingunderanemergencypowersupply.Insuchacondition,onlylimitedservicesareprovidedandmostliftsareinahomingmode.Thissituationcanalsooccurduringafirealarm.
UP_PEAK Mostpassengersgatheratthemainterminal,usuallythegroundfloor,togettodifferentfloorsofthebuilding.Thissituationusuallyhappensinthemorningrightbeforeofficehoursorrightafterlunch.
Page11
![Page 12: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/12.jpg)
PropertiesoftheLiftObjectTypePropertyIdentifier Object_Identifier Object_Name Object_Type Description Status_Flags Elevator_Group Group_ID Installation_ID Floor_Text Car_Door_Text Assigned_Landing_Calls Making_Car_Call Registered_Car_Call Car_PositionCar_Moving_DirectionCar_Assigned_DirectionCar_Door_StatusCar_Door_Command Car_Door_Zone Car_Mode Car_Load
Car_Load_Units Next_Stopping_Floor Passenger_Alarm Time_Delay Time_Delay_Normal Energy_Meter Energy_Meter_Ref Reliability Out_Of_Service Car_Drive_Status Fault_Signals Landing_Door_Status Higher_Deck Lower_Deck Event_Detection_Enable Notification_Class Event_Enable Event_State Acked_Transitions Notify_Type Event_Time_Stamps Event_Message_Texts
Event_Message_Texts_Config Event_Algorithm_Inhibit_Ref Event_Algorithm_Inhibit Reliability_Evaluation_Inhibit Property_List Tags Profile_Location Profile_Name
Page12
![Page 13: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/13.jpg)
Car_ModeUNKNOWN Thecurrentoperationalmodeoftheliftisunknown. NORMAL Theliftisoperatingnormally.
VIP Theliftisoperatingin“VIP"modebetweenaparticularfloorandthemainterminal.
HOMING Theliftisreturningtothemainterminalandisgoingtostaythere.
PARKING Theliftcarisparkedataparticularfloorandwillnotprovideanyfurtherservice.
ATTENDANT_CONTROL Theliftisbeingmanuallycontrolledbyanattendantinthecar.
FIREFIGHTER_CONTROL Theliftisunderafirefighterliftorfirefightingliftmodeofcontrol.
EMERGENCY_POWER Theliftisoperatingonemergencypower.Theliftmaybelimitedinitsoperation.
INSPECTION Theliftisunderinspectionbyanauthorizedparty.
CABINET_RECALL Controloftheliftisperformedfromacontrolpanelinthecontrolcabinet.
EARTHQUAKE_OPERATION Theliftwillstopoperationatapredefinedfloorforearthquakeevacuation.
FIRE_OPERATION Theliftisreturningtothefireevacuationterminal.
OUT_OF_SERVICE Theliftisnotavailableforservice.
OCCUPANT_EVACUATION Theliftisunderanoccupantevacuationmodeofcontrol.
PROPRIETARY Avendormayhaveotherproprietarymodesofoperation.
Page13
![Page 14: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/14.jpg)
EscalatorOperation_DirectionUNKNOWN Thecurrentoperationdirectionisunknown. STOPPED Theescalatororslantedpassengerconveyorisnotmoving. UP_RATED_SPEED Theescalatororslantedpassengerconveyorismovingupwardatratedspeed. UP_REDUCED_SPEED Theescalatororslantedpassengerconveyorismovingupwardatareduced
speed.Thisisforenergyconservationwhentherearenopassengers. DOWN_RATED_SPEED Theescalatororslantedpassengerconveyorismovingdownwardatratedspeed. DOWN_REDUCED_SPEED Theescalatororslantedpassengerconveyorismovingdownwardunderreduced
speedtosaveenergy. PROPRIETARY Avendormayuseotherproprietaryenumerationvaluestoallowproprietary
escalatoroperation.
EscalatororSlantedPassengerConveyorOperation_DirectionUNKNOWN Thecurrentoperationalmodeisunknown. STOP Theescalatororslantedpassengerconveyorisnotmoving. UP Theescalatororslantedpassengerconveyorismovingupward. DOWN Theescalatororslantedpassengerconveyorismovingdownward. INSPECTION Theescalatororslantedpassengerconveyorisunderinspection.Controlofthe
escalatorisperformedfromacontrolpanelontheescalator.Theescalatorisnotavailablefornormaloperation.
OUT_OF_SERVICE Theescalatororslantedpassengerconveyorisnotavailableforservice. PROPRIETARY Avendormayuseotherproprietaryenumerationvaluestoallowproprietary
escalatormodes. Page14
![Page 15: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/15.jpg)
1. The BACnet Model requires BAS contractors who supply the Front Ends for FMs to support the Elevator and Escalator objects and services.
2. No vendor has implemented these features were recently added to the Standard.
3. The current option is to provide a points list using standard BACnet binary, analog and multistate objects.
4. This model is easily supported by all BAS vendors’ Front Ends.
5. The next slides are from projects done by Appin Associates.
Page15
![Page 16: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/16.jpg)
Page16
1. Appin calls elevator and escalator BACnet integrations PLANTS. 2. This is because there are many different systems that can make up an elevator
or an escalator plant. 3. Here is the list of components of an Elevator Plant. This will vary by job:
1. Elevator – One or more cars in a group 2. Exhaust fan – Normally there is an exhaust fan in the car. 3. Light – Electrical provides lights. 4. Sump/Oil Interceptor pit – There is a pit at the bottom of the hoistway. 5. VFD – Variable speed drives are commonly used now. 6. CRAC – CRACs are needed to cool the Elevator Machine Room 24/7. 7. Camera – There may be one or more cameras inside and in front of the car. 8. Access control – Certain floors may require access control. 9. Circuit Breaker/Trip Unit – Used to monitor power and power quality. 10. Meter – There may be an internal meter on the elevator or we use the Trip Unit. 11. Generator and ATS – The elevator may be backed by a generator c/w an ATS. 12. UPS – The elevator may be backed by a UPS. 13. Other systems to meet Occupant Evacuation Operation (OEO).
![Page 17: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/17.jpg)
Page17
The points list for this job. It is not very complete and it did not meet the specified points list, but this is all that was available from the vendor.
![Page 18: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/18.jpg)
Page18
![Page 19: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/19.jpg)
Page19
Name/PurposeALARMBUTTONACTIVATEDATTENDANTSERVICEATTENDANTUPPUSHBUTTONCARDOORBYPASSMONITORCARCALLLOCKOUT1CARSTOPSWITCHMONITORCARSTOPSWITCHOVERRIDEMONITORDOORDISCONNECTDISTRESSBUZZERDISTRESSINDICATORELECTRICEYESHUTOFFSWITCHEMERGENCYPOWERWARNINGEARTHQUAKE(SEISMIC)DETECTORFIRESERVICE-CAR-ONGATE&LOCKSMONITORHALLCALLPOWERMONITORHOISTWAYDOORBYPASSMONITORHOSPITALEMERGENCYSERVICEHOMING-LOBBYRECALLINSPECTIONINDEPENDENTSERVICE-CARLOADWEIGHER-OVERLOADMOTORCONTACTORFAULTMEDICALEMERGENCY-CAR
NON-EMERGENCYSHUTDOWNOILPRESSURE-OVERLIMITOILTEMPERATURE-OVERLIMITPRESSURESWITCHSAFETYCIRCUITMONITORSECURITYOPERATIONACTIVATIONTAMPERINDICATORRESETCODEBLUEACTIVEINDICATORDISPATCHFAILUREINDICATOREARTHQUAKESEISMICINDICATOREMERGENCYTERMINALSPEEDLIMITFLASHINGHALLSIGNSFIRESERVICE-PHASE1INDICATORHOSPITALEMERGSERVICEACTIVE-INDHOMING-#1-INDICATORINCONSPICUOUSRISEROPERATION-INDINDEPENDENTSERVICE-CAR-INDOFFLINEINDICATOROILLEVELLOWINDICATORSHUNTTRIPBREAKERCONTROLTAMPERINDICATORVALVECONTROL(DOWNSLOW/DOWN)
This is a short form version of the points list that Appin expects on a job. Most points are statuses to help diagnose problems.
![Page 20: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/20.jpg)
Page20
We want to pick up the VFD as this is the most important piece of equipment that needs to be monitored. VFDs will speak BACnet or Modbus so the integration is simple.
![Page 21: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/21.jpg)
Page21
This is a graphic of a BACnet Elevator Monitoring project.
![Page 22: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/22.jpg)
Page22
![Page 23: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/23.jpg)
Page23
![Page 24: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/24.jpg)
Page24
![Page 25: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/25.jpg)
Page25
![Page 26: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/26.jpg)
1. Decide on what points you need to give you an adequate information base.
2. Work with your Construction Department to build elevator and escalator monitoring into the project.
3. Evaluate the options proposed by the elevator vendors and decide what the minimum level is required to meet your needs. Be prepared to negotiate even after contract award as BACnet is new to most vendors.
4. Commission the system and build the graphics as you would any other building system.
5. Decide if you want additional reports on elevator/escalator operation. 1. Note that this may be an additional service that is provided in a proprietary manner.
Page26
![Page 27: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/27.jpg)
Page27
Elevators are not normally used to evacuate the building in a fire event.
![Page 28: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/28.jpg)
2002 2004 2006 2008 2010 2012 2014 2016 2018 2020
IBC NFPA ASMEA17.1 BACnet
IBC
NFPA72/101
ASMEA17.1
BACnetWhitepaper
FirstMandateforadditionalstairwellorOEEsabove420feet
Firstalignmentacrosscodes
Furtheralignmentandrefinement
Largerscalerevisionsbasedonlearningsfromactualjobs.
JointSubmittalofOEMneutral,BACnetprotocolextensionbySchindler/Siemens
Page28
OEE=OccupantEvacuationElevator
![Page 29: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/29.jpg)
IntendedtoevacuatepeoplepriortoarrivaloffirefightersFireAlarmSystemdetectspossiblefireconditionsremotefromtheelevatorlobbiesanddeclaresanevacuationzoneNormalelevatoroperationceases.OnlycallsfromtheevacuationzoneareacceptedAsFireAlarmSystemexpandsevacuationzone,passengerevacuationrequestsfrommorefloorsareaccepted.
EvacuationZone
Fire
Single ActiveFire Alarm
Initiating Device
Two Active Fire Alarm
Initiating Devices
Multiple Active Fire Alarm
Initiating Devices
EvacuationZone Evacuation
Zone
Fire
Fire
Fire
Fire
Fire
Call priority floor
Floor in Evac Zone
Floor 25 Floor 22 Floor 8 on Fire on Fire on Fire
Page29
![Page 30: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/30.jpg)
PORT Group PORT Group PORT Group PORT Group S2SwingCar
Fire Alarm System
Page30
Groupofelevatorcars(Typof3)
RedundantparallelwiringforJBF(keyswitch)andsmokedetectorsatdischargeleveltoindividualgroups
PORT is Schindler’s proprietary destination dispatcher that runs a
group of cars
![Page 31: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/31.jpg)
PORT Group PORT Group PORT Group PORT Group S2SwingCar
RedundantparallelwiringforJBF(keyswitch)andsmokedetectorsatdischargeleveltoindividualgroups
Fire Alarm System
Page31
RemotefiresensorsonallfloorsSerialCommunicationBus
HardwiredOptionnoBACnetintegration
![Page 32: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/32.jpg)
PORT Group PORT Group
Fire Alarm System
Serial Router
S2SwingCar PORT Group
PORT Group
IntegrationofSerialCommunicationProtocolintoElevatorSystem(non-ULonelevatorsideascontrolbyFAS).SerialIProuterasentrypointforOEOsignalstoPORT.
Page32
RemotefiresensorsonallfloorsSerialCommunicationBus
RedundantparallelwiringforJBF(keyswitch)andsmokedetectorsatdischargeleveltoindividualgroups
![Page 33: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/33.jpg)
Page33
![Page 34: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/34.jpg)
Page34
Ateachlobby(byES).
FireCommandCenter
TheESisnotpartofthelifesafetysystembutratheranemergencycontrolfunctionasdefinedinthefirealarmcodes.AssuchtheonlymonitoringrequirementfortheES,whenusingadigitalcommunicationnetworktointerfacewiththeFASisthattheESmustmeetthetimecriteriaforthesupervisionofthecommunication.Sofar,codedoesnotmandatearesponsebytheemergencycontrolfunctionoftheESintheeventthatthecommunicationwiththeFASviathedigitalcommunicationnetworkiscurrentlynotpossible.
HardwiredBackup
![Page 35: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/35.jpg)
Page35
Expanding the BACnet Model FAS Representation for OEO by Life Safety Objects
FAS Representation for OEO by Multi-state Objects FAS Representation for OEO by Binary Objects
![Page 36: Grant Wichenko - cdn.ymaws.com · Grant Wichenko is a Professional Engineer. He is a member of : - ASHRAE SSPC-135 (BACnet committee – voting member), - Member of EL-WG and Chair](https://reader035.fdocuments.net/reader035/viewer/2022081405/5f0c07947e708231d4336737/html5/thumbnails/36.jpg)
Page36
FAS Representation for OEO
QUIET ThisisastandardstateandindicatesthattheOEOfloorhasnofirealarm.OEOwouldbeavailablebutisnotrequiredinthisstate.
OEO_UNAVAILABLE The floor is unavailable forOEO.A reason for thismaybe aPhase1Recallortheelevatorgroupwentout-of-service.
OEO_ALARM Afirealarmisonthefloortheobjectrepresents
OEO_EVAC The floor should be evacuated by theOEO operation of theelevator.
OEO_UNAFFECTED SomefloorsofthegroupmaybeinOEOalarmorevacuationstate,butthisfloorisunaffectedbythefire,doesnotneedtobeevacuated,andisnotservedinOEO.